Professional Documents
Culture Documents
mm/year
c(O
2
)
mg/l
l
D
mm
= 1.6 x 10
-2
:
(20)
anodic region: rich in salts, aerated little or not at all,
dense, and wet. Example: Clay; especially aggressive
are sour soils (humus) and soils containing hydrogen
sulfide.
Sand ( = 4 x 10
6
cm) Clay ( = 7 x 10
6
cm)
Figure 5 Surface of steel samples (100 x 150 x 3 mm) after 6
years` corrosion in sand and clay
Humous soil
Clay Sand
Loam
Loam Clay
Peaty soil
C
l
a
y
Sand
S
a
n
d
S
a
n
d
y
m
a
r
l
Sandy
marl
Loess
Clayey
marl
C
la
y
e
y
m
a
r
l
Loamy marl
Lime
Calcareous
marl
C
a
lc
a
r
e
o
u
s
m
a
r
l
C
a
lc
a
r
e
o
u
s
m
a
r
l
H
u
m
o
u
s
s
o
il
H
u
m
o
u
s
s
o
il
L
im
e
L
im
e
Lime 100% Humus 100% Humus 100%
Peaty soil Peaty soil
Sand 100% Clay 100%
Humus 100%
Not aggressive
(cathodic regions
Conditionally
aggressive
Aggressive
(anodic
regions)
3.1.3 Intensity of corrosion in different types of soil
Fig. 6 gives a systematic survey of the different types of
soil. The rates of metal consumption in aggressive soils
may range from 0.05 to 0.10 mm/year. J
K
is quite large;
the reaction of humus acids contributes to this. In soils
conditionally aggressive corrosion velocities are frequently
found to be negligibly small. In both these types of soil,
though, anodic regions develop on traversing pipelines.
Cathodic regions develop only in soils which are not ag-
gressive.
The development of extended corrosion cells on a pipeline
passing through various types of soil does not allow an
estimation of corrosion velocity. As opposed to this the
very positions of the anodic regions may be located quite
well by referring to the groups in fig. 6. Corrosion velocity
will be all the greater, the smaller the anodic and the greater
the cathodic regions are, compare eq. (18). This holds
true provided the electric conductivity of the ground is
sufficient; if it is not, for instance in dry sandy soils, even
large cathodic regions remain inactive with respect to
corrosion cell action. As opposed to this, intensively active
cathodic regions afford fast corrosion of the anodic
regions, then the properties of the soil near the anode
are less influential. So, evi dently, there is no absolute
measure of corrosiveness of a soil. A rating of
aggressiveness in terms of grades may be gained based
on a soil analysis.
Figure 6 Type system of soils and their corrosion aggressiveness
Approximate assumptions of corrosion velocities within
the anodic regions of pipelines may range over a few
0.1 mm per year. Local metal consumption rates above
1 mm/year are definitely due to other reasons to be
detailed in sections 5 and 6. Corrosion danger imposed
by soil containing coal (or coke!) belongs to this group.
The reason is cell formation between the steel surface
and the coke, the latter constituting the cathode, the
former being the anode. In this case there is but one
suitable protective measure: replacement of the soil along
the pipeline.
The presence of coke and foreign electric influences
excluded, unprotected steel pipelines can definitely be
used without the danger of early failure, i.e. for several
years. This is in accordance with experience. At some
later time though, depending on the wall thickness,
damage must be expected. This means corrosion
protection measures are indispensable.
3.2 Methods of corrosion protection
3.2.1 Coatings: passive corrosion protection
The most simple measure of corrosion protection is
coating the steel surface with bitumen or plastics. To be
sure there is a lot of literature and specifications con-
cerning the required properties of the coating materials,
but the purpose of each of these requirements with
relation to corrosion protection is not always obvious.
Essential are these two properties:
The coating material must be stable for a long time
under the relevant service conditions in the ground.
The applied coating must be mechanically as resistant
as possible to minimize frequency and extent of
mechanical damage.
R
F
= A r
-1
(22)
The size of this uncovered steel surface is proporti-
onal to the square of the same mean radius:
S
F
= B r
2
(23)
With a voltage U acting upon the pipeline around the
damages, Ohm`s law gives:
I
a
=
U
R
F
Ur
A
= (24)
J
a
=
I
a
S
F
U
A B
= r
-1
(25)
So the current density J
a
will increase, if the radius r
decreases!
5.3 Protection measures
Protection against danger caused by foreign cathodes
may be accomplished in two ways:
Galvanic separation
Local cathodic protection
5.3.1 Galvanic separation
Galvanic separation is the most effective means because
by it the very source of corrosion cell danger is
eliminated.
The reliability of this depends on easy control of all the
sites of possible connections, and on the certainty with
which accidental contacts may be excluded in practice.
Standards and regulations specify galvanic separation
to be effected for house connections in public gas delivery
systems, because for inside the building, intentional
connecti ons for personal protecti on are made
compulsory by DIN/VDE-regulations. With reinforced
concrete construction and interconnection of all domes-
tic installations being common today, personal protection
observing DIN/VDE results in the formation of spacious
foreign cathodes with respect to gas pipelines, that have
to be disconnected from these by inserting insulating
flanges.
5.3.2 Local cathodic protection, hot spot protection
In ranges of industrial plant, galvanic separation is
inapplicable because of the presence of too many
interconnections, in many instances also for construc-
tional reasons. Applicable then is local cathodic protec-
tion. The techniques of normal CP cannot be followed
for these reasons:
The foreign cathodes will consume much more current
than the pipeline to be protected. Large ohmic drops in
the ground will result. So IR will become a substantial
part of the on-potential.
The pipeline and the foreign cathodes vastly differ
with respect to their electrochemical properties. Free
corrosion endangers the pipeline anodically. Given
cathodic polarization, the two areas are polarized
differently. After switching off the protective current for
the off-potential to be measured, comparatively large
relaxation currents between the pipeline and the foreign
cathode will flow. The corresponding ohmic drop will
falsify the off-potential too. The measured value is more
positive than the IR-free (true) value.
The basis of local cathodic protection may be derived
from eq. (19). The protection current is rated and fed in
so that the foreign cathodes do not deliver cell current
but consume protection current. Then eq. (19) gives:
In other words; Aimed at is the polarization of the foreign
cathodes so as to render them harmless instead of
breaking their corrosion cell with the pipeline. Within
industrial plant many 10
4
m
2
of reinforced concrete surface
I
>
=
J
k
S
k
and J
a
<
=
0 (26)
contact the ground and consume a mean current of about
5 mA m
-2
, so the order of magnitude of the current
consumed for local cathodic protection of a special plant
is 10
2
A. The interference problems raised by such
currents can only be solved by all underground in-
stallations being incorporated into the protection system.
Fig. 16 shows the application of local cathodic protection
to a power station with large cooling water ducts (nomi-
nal diameters 2000 and 2500 mm) and water conduits
for fire extinguishing. For 19 000 m
2
of reinforced concrete
foundations and 2000 m
2
of copper groundings a current
of 120 A is fed in via eight deep-groundbeds
With a resistivity of 150 to 350 m this soil is a compara-
tively poor conductor; so, for a local potential lowering
of specific objects to be protected, a directed current
may be fed in via horizontal groundbeds.
The values given under Aare pipe-to-soil potentials
measured with free corrosion going on before local cath-
odic protection was installed. These potentials range from
U
Cu/CUSO4
= -0.5 to -0.1 V. The values given under B,
and Care on-potentials (off-potentials) measured after
4 months and one year, respectively, of the protection
system being in operation. As expected, it was not
possible to produce off-potentials more negative than
the critical protection potential (-0.85 V), this is in spite
of (some) vastly negative on-potentials. However, due
to the IR-bound error still present in the off-potential
measurements, this impossibility does not imply that
the object is not fully cathodically protected. There are
ways of measuring that work with polarization probes
and/or test coupons, and enable off-potentials at critical
points of the structure to be measured sufficiently
depleted of I R-errors. Thi s affords a rel i abl e
ascertainment of protection.
Complicated adjustment steps during the design and
construction phases, and later on, controlling measure-
ments and the handling of very large protection currents
in view of possible interference with foreign objects,
necessitate this type of protection to be managed by
expert enterprises having advanced experience. During
the last decade progress was manifested in numerous
successful applications.
Figure 16 Local cathodic protection in a power station
Deep groundbrds
Horizontal anodes
Cooling water lines
Fire extinguishing lines
A
B
C
Pipe-to-soil potential under free corrosion conditions
Pipe-to-soil potential after 4 months` polarization
Without brackets: On-potential, in brackets: Off-potential
Same as B, but after one years` polarization
6.1 Origins of stray currents
A stray current is an underground current originating
from current-carrying parts of electrical installations. In
most cases these are the rails of electric railways. But
CP facilities installed for foreign objects to be protected
may also be responsible. Related interference problems
were discussed already with regard to fig. 14. Depending
on the geometric situation of the pipeline in relation to
the direction of the current, i.e. the electric field generated
by the unit in question, stray current will enter the pipeline
over large areas. Within the most positive region the
stray current leaves the pipeline for the ground, and here
it causes anodic corrosion.
6.2 Characteristics of stray current action
Corrosion caused by stray currents is in many respects
similar to that caused by foreign cathodes. However,
there are typical differences, too.
Corrosion danger essentially depends on current
density only. Properties of the ground are of no concern,
actually, provided a stray current does flow. So only in
sandy soils of very high resistivity is the corrosion
danger diminished.
The influence of the pipe coating is varied.
If there is no direct connection leading in stray current
from foreign objects to the pipeline, a high coating
resistivity could be useful, because stray current entry
would be cut down. On the other hand in the region of
current exit the same conditions are given, as were
discussed in section 5.2.4 with respect to foreign
cathodes, in view of eqs. (22) through (25), page 24.
Hence in this area a high coating resistivity is un-
favourable. Useful would be only a coating 100% free of
holidays, and that after the laying of the line and during
service.
As opposed to the situation with foreign cathodes, the
origin of danger cannot be eliminated. Stray currents
are present in the ground, and they do not need connec-
tions to enter the pipeline. A suitable protection measure
is not impediment of stray current entry but that of stray
current exit.
As in the case of danger caused by foreign cathodes,
the corrosion rate is hardly assessable. Values ex-
ceeding 1 mm/year may be expected. The endangered
regions are characterized by very positive pipe-to-soil
potentials. Contrary to the action of foreign cathodes
and foreign protection facilities the potential accom-
panying railway currents is intensely variable with time.
Depending on construction and usage of the railway track
the regions of entry and exit of stray current are subject
to considerable alterations. For these reasons simple
measurements of potentials are not sufficient; necessary
is recording the potentials for several hours duration.
The same way as with foreign cathodes creating danger,
the user of the pipeline may, by potential measurements,
recognize stray currents to be present. These measure-
ments must by all means be continued for several hours
while the neighbouring railway tracks are being used.
Assessment of the danger can be achieved by an ex-
pert only. The intense danger of early damage necessi-
tates protection measures as soon as possible.
6 Corrosion caused by stray currents;
protection methods
Figure 17a Stray currents originating from railways
6.3 Protection measures against stray
currents
Protection may be achieved by leading the stray current
through electrical connections back directly to the
installation that produces it. Fig. 17 shows schematically
stray currents being created by a D.C. railway and flowing
through a neighbouring pipeline. Near the rectifier railway
feeding station of the railway the stray current leaves
the pipeline and causes severe anodic corrosion in this
area. This is the very location for protection measures to
be taken.
6.3.1 Immediate drainage
Via a heavy duty low ohmic resistor the pipeline is
directly connected to the stray current source, i.e. the
railway track.Even this measure alone is very effective,
provided the connection is made in the immediate
neighbourhood of the rectifier railway feeding station of
the railway, and the overhead conductor is the positive
pole. Thus the negative potential of the rails is transfer-
red to the pipeline, so that even a moderate cathodic
protection may be the result.
Figure 17 Protection against stray currents originating fro railway
stray currents in the soil, pipeline and current drain
Anodic region
Cathodic region
of influenced unprotected pipeline
6.3.2 Rectified drainage
This is a special case of immediate stray current drai-
nage. It is characterized by heavy duty diodes incor-
porated in the draining connections to the rails. The
diodes are meant to ensure that current can only flow
from the pipeline to the rails and not in the opposite
direction. This type of draining connection must be
applied, if a direct drainage cannot be installed in the
immediate neighbourhood of the rectifier railway feeding
station. Increasing with the distance from the railway
rectifier is the chance of pole changings taking place
between pipeline and rails according to varying situations
in railway traffic, so that there is the danger of stray
current entering through the very drainage. This is to be
prevented by diodes. Rectified drainage must be installed
in several locations along the pipeline, where stray current
may often leave.
6.3.3 Forced drainage
With this type of drainage a protective rectifier unit is
incorporated into the connection. By means of its voltage
the rectifier extracts the stray current from the pipeline
and directs it to the rails. Actually this is a normal
arrangement for cathodic protection, the rails repre-
senting the anode. Since due to varying situations in
railway traffic the voltage pipeline/rail may be subject to
substantial alterations, the protective rectifier unit should
be adjustable to voltage variations with time. There are
several possibilities to lower the resulting current
variations, e.g. installation of inductivities.
6.3.4 Use of controlling rectifiers for forced drainage
In the case of very large current variations it is ad-
vantageous to use rectifiers controlling the potential. By
means of the fixed reference electrode RE the rectified
current is controlled so as to keep the pipe-to-soil po-
tential in the place of drainage at a fixed value U
nom
. At
larger distances from the reference electrode the stray
current influence is different, so there are increases in
the temporal variations of the pipe-to-soil potential again,
but this is of no concern to the protection effectiveness.
If in some region the pipe-to-soil potential is often found
to be too far positive, another protection unit must be
installed there.
A
B
7.1 Types and causes of high voltage
influence
In densely populated areas there is not always a way
around constructing pipelines running in close proximity
to open high voltage lines, crossing them or even
parallelling them for some distance. Due to alternating
voltages induced in these pipelines high contact voltages
may develop, which necessitates protective measures.
During construction and operation of pipelines special
measures must be taken according to relevant standards
and regulations, also with regard to the cathodic pro-
tection system. There are two main types of interference
which must be assessed in different ways:
Short time interference caused by short circuit
currents of the high voltage power line
Permanent interference caused by operating currents
of the high voltage power line
In both cases by a suitable grounding of the pipeline the
induced contact voltages must be safeguarded against
exceeding the admissible extremes. In section 4,
however, it was pointed out that disconnection from
groundings is a prerequisite for cathodic protection.
Groundings consume protection current, and, because
of possible relaxation currents flowing after the protection
current switch-off, they may cause measuring problems
in the determination of true potentials by application of
the off-potential technique.
7.2 Protective measures against too high
voltages in personal contact
According to to relevant standards and regulations the
voltages permissible for bodily contact depend on the
duration of their action, this enables different protection
measures to be taken against the two above mentioned
types of interference.
7.2.1 Short time interference caused by short circuit
currents of the high voltage power line
In the case of a short circuit of this kind, power is cut
off after about 0.2 s. Permissible for bodily contact are
voltages exceeding 1000 V. This means the required
groundings may be connected to the pipeline across
excess voltage drains, working by way of gas discharge
with starting voltages (threshold voltages) about 250 V.
So during normal operation the groundings are electri-
cally separated from the pipeline, and neither do they
interfere with cathodic protection nor with its control by
potential measurement. With a short circuit given, secure
grounding is provided for the short duration required.