Jump Start: Using Aspen HYSYS

Dynamics with
Columns
A Brief Tutorial (and supplement to training and online documentation)
Nicholas Brownrigg, Product Marketing, Aspen Technology, Inc.
Ajay Lakshmanan, Product Management, Aspen Technology, Inc.
Zachary Peers, Product Management, Aspen Technology, Inc.
Alex Rao, Product Management, Aspen Technology, Inc.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
CVb
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Preparing a Steady-State Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Debutanizer Column Specifics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Development of a Control Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Preparation of Flowsheet for Dynamic Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Implementing and Sizing Control Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Activating Dynamic Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Column Equipment Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Adding and Specifying Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Strip Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Execution of Dynamic Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Implementing Disturbances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


1
Introduction
Columns are an integral part of most processes. They are used to separate components in mixtures where the material
exiting columns often have stringent purity and flow constraints to maintain. It is also important to maintain flow through
columns to ensure safety.
For these reasonsand more, control schemes are usually implemented on columns in order to ensure that variables such
as temperature, pressure, and flow at critical points throughout the column remain constant. Control schemes also help to
maintain product purity and flow, ensuring that acceptable materials exit the column.
In order to obtain working simulation for a column in steady-state operation, Aspen HYSYS can be used. To obtain a
simulation of a column with an implemented control scheme, Aspen HYSYS Dynamics should be utilized. Using both of
these programs in concert provides a comprehensive summary of how a column will perform under varying plant
conditions and perturbations to the columns normal steady-state operation.
This guide will begin with a brief walkthrough of the process for setting up a steady-state column model. The steps
required towards developing and implementing a working control scheme, and studying column dynamic response using
Aspen HYSYS Dynamics, will then be outlined.
Four Aspen HYSYS files come compressed with this guide. The file Debutanizer SS Starter.hsc is the steady-state
simulation for the debutanizer column. Debutanizer Solution RefluxBoilup1 Control Case.hsc is a dynamics-ready file.
This guide will show the steps necessary to add the control equipment to the steady-state debutanizer file that is present
in the LV-1 control case.
In addition, two other alternative control scheme HYSYS files are included. These files are Debutanizer Solution
RefluxBottoms Control Case.hsc and Debutanizer Solution DistillateBoilup Control Case.hsc. The Aspen HYSYS
flowsheet for each of these files and a short description of the control schemes are included in the conclusion section of
this guide.
This document is not meant to be used as a stand-alone reference document. We recommend that a range of other
resources be called upon to give the user a comprehensive view of how to use Aspen HYSYS Dynamics. These may
include:
AspenTech support website (support.aspentech.com) this website has a wealth of information on the use of
AspenTech products and provides answers to frequently asked questions.
AspenTech courseware available in on-line and in-person versions
AspenTech business consultants
This document will show how to prepare a column and analyze its response to varying conditions using Aspen HYSYS
Dynamics. It assumes that the user has Aspen HYSYS V8.0 or higher installed on his or her computer and a functional
process design completed, as well as a very basic knowledge of dynamic simulation using Aspen HYSYS Dynamics.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved.11-4030-0913
2
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Preparing a Steady-State Model
In order to properly use Aspen HYSYS Dynamics, a working steady-state process simulation model must first be obtained
in Aspen HYSYS. For more information about using Aspen HYSYS, please refer to the separate Aspen HYSYS Jump Start
Guide available at www.aspentech.com/JumpStart_HYSYSV8/.
For the purposes of this Jump Start Guide, a complete dynamic simulation of a column will be demonstrated utilizing a
previously completed steady-state Aspen HYSYS process involving a debutanizing column. The process developed is
shown in Figure 1.
Figure 1. Steady-State Process Simulation with Debutanizer Column
Debutanizer Column Specifics
It is important to appropriately design and rate the column that is going to be the focal point of the dynamic simulation by
double-clicking the column model block on the flowsheet. The parameters in Figure 2 were specified for the debutanizer,
including 15 separation stages, a feed on stage 8, a condenser pressure of 13.12 barg, and a reboiler pressure of 13.47 barg.
Feed2
Vent
Cond Duty
Feed1
Debutanizer
SS Specs
C5+
Reb Duty
Butanes
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


3
Figure 2. Column Design Parameters
Additional required column specifications of the reflux ratio, butane recovery from the condenser, and C5 exiting the
reboiler can be made in the Specs window. For the particular debutanizer column in this guide, the butane recovery is
96.25% and the C5+ in the condenser is set at 2.5%, which makes the percentage of C5+ in the bottoms 97.5%. From
these parameters, Aspen HYSYS calculates a reflux ratio of 3.697 and a molar reflux flow of 777.0 lbmole/hr. Figure 3
shows the Specs window and the setting up of the butane recovery in the condenser.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
4
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Figure 3. Setting Column Specifications
Once a steady-state column has been solved in Aspen HYSYS, the user can then continue to develop a control scheme
and add dynamic equipment to the flowsheet in order to begin a dynamic simulation using Aspen HYSYS Dynamics.
Development of a Control Scheme
To develop a control scheme for the column, the columns response to feed changes should be studied. Initially, for the
simulation set up in Figure 1, Feed 1 has a flowrate of 18,000 lb/hr, while Feed 2 has a flowrate of 9,000 lb/hr. Using the
Column Profiles window under the Performance tab for the column, it can be seen that the current feed flow scheme
results in the stage parameters shown in Figure 4.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


5
Figure 4. Column Profile for Debutanizer
In order to develop an appropriate control scheme, the feed flow rates should be changed to discover which variables
within the column vary most. The following table shows feed flow changes made to the column and the corresponding
changes to column parameters that displayed the most variance with the feed change.
Table 1. Changes in Column Performance with Feed Changes
The temperature on tray 6 in the debutanizer increased and decreased according to a respective increase or decrease of
the flowrate of the Feed1 stream. Also, with an increase in the flowrate of Feed1, an increase in the i-C5 mass fraction and
decrease of condenser and reboiler duty was observed. For these reasons, the control scheme described in the following
section should be implemented.
Feed1 Flow
(lb/hr)
Feed2 Flow
(lb/hr)
Tray 6 Temperature
(F)
Mass Fraction i-C5 in
Butanes Stream
Condenser Duty
(Btu/hr)
Reboiler Duty
(Btu/hr)
18,000 9,000 218.1 .0210 6.563e6 5.631e6
9,000 18,000 213.1 .0193 6.860e6 7.113e6
0 27,000 210.9 .0206 7.171e6 8.653e6
27,000 0 231.5 .0402 6.331e6 4.252e6
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
6
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Preparation of Flowsheet for Dynamic Simulation
(Note that the Dynamic Assistant can be used to guide the user in preparing a flowsheet for dynamic simulation. The
Dynamic Assistant will suggest all the steps covered in this section.)
Implementing and Sizing Control Valves
Dynamic simulation requires the proper equipment to be modeled on the flowsheet in order to work properly. The first
pieces of equipment that should be added are valves. For the case being used in this guide, four valves will be necessary
based on the control scheme identified. The valves should be connected to inlet streams Feed 1 and Feed 2 and outlet
streams Butanes and C5+, as depicted below in Figure 5. All valves should have a pressure drop of 7 psig.
Figure 5. Flowsheet with Valves Added
Valves 100 and 101 need to be sized. This is done by clicking on the Rating tab in the valve window and then clicking the
Size Valve button in the bottom left of the window.
Feed2 To Feed2
VLV-101
Vent
Cond Duty
VLV-102
VLV-103
Feed1
Butane Product
Liquid Product Debutanizer
To Feed1
VLV-100
C5+
Reb Duty
Butanes
SS Specs
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


7
Figure 6. Sizing a Valve
Activating Dynamic Specifications
The next step in moving towards dynamic simulation is to activate the pressure specifications under the Dynamics tab
for streams To Feed1, To Feed2, Butane Product, and Liquid Product, by checking the box shown in Figure 7.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
8
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Figure 7. Activating Dynamic Parameters
In a similar fashion, check the flow specification box for the streams Vent and Reflux. Reflux is located within the
column subflowsheet environment. Also ensure that no dynamic specifications are checked for streams Feed1 and
Feed2.
Column Equipment Sizing
Next, the reboiler, condenser, and tray section must be given sizes. In order to define the reboiler and condenser volumes,
open the column window and move to the Rating tab and click Vessels in the navigation pane, shown in Figure 8. Enter
530 ft3 for both the reboiler and condenser for the purposes of this guide.
Figure 8. Sizing Reboiler and Condenser
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


9
To size the trays for the column, open the Tray Section window and then double click the named Tray/Packed Section,
shown in Figure 9. This will open the sizing form for that tray section.
Figure 9. Sizing Tray Section
Enter a tray diameter of 4.5 ft, a tray spacing of 1.8 ft, a Weir height of 0.15 ft, and a Weir length of 4.0 ft to complete tray
sizing.
Adding and Specifying Controllers
Six controllers should be added to the flowsheet for process control. The process variables, output targets, and acceptable
tuning parameters for each valve are listed in Table 2.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
10
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Table 2. Controller Connections and Variables Controlled
After implementing the control scheme from the above table, the flowsheet should then appear as Figure 10 displays
below.
Figure 10. Flowsheet with Controllers Implemented
To Feed2
Vent
Cond
Duty
VLV-102
VLV-103
Feed1 Butane
Product
Liquid
Product
Debutanizer
To Feed1
VLV-100
C5+
Reb Duty
Butanes
VLV-101
Feed2
FIC
Feed1
FIC
Cond PC
Column TC
Reboiler LC
Cond LC
Feed2
SS Specs
Controller Process Variable Source Output Target Object
Tuning
Parameters
Action Range
Feed1 FIC Feed1 Mass Flow
VLV-100
Actuator Desired Position
K
c
= 0.5
T
i
= 1.0
Reverse
0 lb/hr
30,000lb/hr
Feed2 FIC Feed2 Mass Flow
VLV-101
Actuator Desired Position
K
c
= 0.5
T
i
= 1.0
Reverse
0 lb/hr
30,000lb/hr
Cond PC
Condenser Vessel
Pressure
Condenser Duty Control Valve
K
c
= 1.0
T
i
= 2.0
Direct 180 psia - 220 psia
Cond LC
Condenser Liquid
Volume Percent
VLV-102 Actuator Desired
Position
K
c
= 2.0
T
i
= 5.0
Direct
210F
260F
Column TC
Column Stage 6
Temperature
Reboiler Duty Control Valve
K
c
= 2.0
T
i
= 5.0
Reverse 0% - 100%
Reboiler LC
Reboiler Liquid Volume
Percent
VLV-103 Actuator Desired
Position
K
c
= 2.0
T
i
= 5.0
Direct 0% - 100%
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


11
Strip Charts
Strip charts help users to view the results of dynamic simulation to disturbances. Four strip charts are automatically
available under the Dynamics tab once the control scheme is implemented. These strip charts show the liquid percent
level in the condenser and reboiler versus time, the two feed mass flows versus time, condenser pressure and column
stage 6 temperature versus time, and the composition in the Butanes product stream versus time. These strip charts can
be found by clicking the Strip Charts button under the Dynamics header in the ribbon, then selecting the desired
graph, shown in Figure 11.
Figure 11. Opening Strip Charts
Execution of Dynamic Simulation
After following the steps towards setting up a steady-state flowsheet for dynamic simulation, the dynamic simulation can
be run. To accomplish this, click the Dynamics tab on the main ribbon in Aspen HYSYS, shown below. Alternatively,
hitting F7 with Aspen HYSYS open will automatically enter dynamics mode. Once the Dynamics tab has been opened,
activate Dynamics Mode by clicking the appropriate button, shown in Figure 12. Then, to run a dynamic simulation, either
click the Run button, or press F9.
Figure 12. Navigating to the Dynamics Tab from the Main Ribbon and Running a Dynamic Simulation
If the steps in this guide are followed, the Dynamics Assistant will indicate that there are changes suggested before
running the dynamic simulation. The suggested changes would revert some of the set up steps listed in this guide. Simply
press No when prompted to run the dynamic simulation.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
12
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Implementing Disturbances
Some process modification suggestions to view dynamic response for the control scheme implemented include:
Change the feed flowrate
Change the feed composition
Change the temperature setpoints
Change the pressure setpoints
Change both temperature and pressure setpoints
To change the composition or feed flowrates, once the dynamic simulation has been initialized, the feed streams
definition worksheet can be opened by double clicking the appropriate stream. Then, the streams flow or composition can
be modified. Additionally, flow controller setpoints can be modified to initiate disturbance in the simulation.
To change the setpoints for either temperature or pressure, the controllers Parameters tab can be used or the face plate
for a controller can be opened by double clicking the appropriate controller and selecting the Face Plate option, shown
in Figure 13.
Figure 13. Changing the Setpoint and Opening a Face Plate for a Controller
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


13
In the Parameters tab, the setpoint can be manually typed to the desired value. If the face plate is used, the setpoint can
be modified by dragging the red arrow highlighted in Figure 14.
Figure 14. Face Plate with Highlighted Setpoint Control
To test the implemented control scheme, a dynamic simulation was run. After letting the process come to steady-state
operation, the flowrate of the stream To Feed1 was increased from 18,000 lb/hr to 28,000 lb/hr. The control response
was evident in the Feed Flows strip chart, shown below in Figure 15.
Figure 15. Feed Flows Strip Chart from Dynamic Simulation of Debutanizer
The increased flow to 28,000 lb/hr to the column can be seen, as well as a small perturbation to the Feed 2 stream from
the steady-state value of 9000 lb/hr.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
14
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Additional strip charts showing the dynamic response for the simulation can be generated for the temperature on tray 6 of
the column and condenser vessel pressure. This strip chart is shown in Figure 16.
Figure 16. Strip Chart Showing Tray 6 Temperature and Condenser Pressure
It can be observed that both the temperature and condenser pressure show fluctuations when the column feed
experienced disturbancebefore each parameter returned to its original value due to the control response.
Figure 17 shows another strip chart for the liquid level percent present in the reboiler and condenser.
Figure 17. Strip Chart Showing Liquid Percent Level in Condenser and Reboiler
For this strip chart, neither the liquid level percent in the reboiler nor the condenser fully reaches its steady-state value of
50% before the feed flow disturbance is activated. However, upon control response, the liquid levels both move towards
their steady-state values.
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


15
Conclusion
Dynamic simulation is a very powerful tool that allows users to view how processes will behave when deviations from
steady-state operation occur. Aspen HYSYS Dynamics is the premier dynamic simulator, combining the simulation power
of Aspen HYSYS with the ability to view rigorous dynamic process response.
Aspen HYSYS Dynamics is especially effective for its use in viewing column dynamic response and exploring various
control schemes to limit steady-state operation deviations in columns. The control scheme shown in this guide is a reflux-
boilup control. Reflux-boilup control responds well to feed disturbances. The reflux flow rate controls the distillate
composition while the heat input to the reboiler controls the bottoms composition.
Other suggestions for control schemes to be implemented on the debutanizer column, as well as the scheme shown in
this guide, are included in Table 3.
Table 3. Alternate Control Scheme Configurations
Figure 18 shows the flowsheet of Aspen HYSYS file Debutanizer Solution DistillateBoilup Control Case.hsc, which is an
example of Distillate-Boilup control. This Aspen HYSYS file was downloaded along with this guide and is available for
examination and modification inside of Aspen HYSYS and Aspen HYSYS Dynamics.
Control
Configuration
Name
Manipulated
Variable for
Condenser LC
Manipulated
Variable for
Reboiler LC
Manipulated Variable
for Primary Composition
Control
(Stage 6 Temperature)
Manipulated Variable
for Secondary Composition
Control
(Fixed in Base Case)
Manipulated
Variable for
Pressure Control
Reflux-
Boilup 1
Distillate Flow
Rate
Bottoms Flow
Rate
Reboiler Duty Reflux Flow Rate Condenser Duty
Reflux-
Boilup 2
Distillate Flow
Rate
Bottoms Flow
Rate
Reflux Flow Rate Reboiler Duty Condenser Duty
Distillate-
Boilup 1
Reflux Flow Rate
Bottoms Flow
Rate
Reboiler Duty Distillate Flow Rate Condenser Duty
Distillate-
Boilup 2
Reflux Flow Rate
Bottoms Flow
Rate
Distillate Flow Rate Reboiler Duty Condenser Duty
Reflux-
Bottoms 1
Distillate Flow
Rate
Reboiler Duty Bottoms Flow Rate Reflux Flow Rate Condenser Duty
Reflux-
Bottoms 2
Distillate Flow
Rate
Reboiler Duty Reflux Flow Rate Bottoms Flow Rate Condenser Duty
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
16
Jump Start: Using Aspen HYSYS

Dynamics with Columns


Figure 18. Distillate-Boilup Control Case Flowsheet
Distillate-Boilup control is effective for columns operating at high reflux. The distillate flow rate controls the distillate
composition while the heat input to the reboiler controls the bottoms composition.
Figure 19 shows the flowsheet of the Aspen HYSYS file Debutanizer Solution RefluxBottoms Control Case.hsc, which is
an example of Reflux-Bottoms control. This file was also downloaded in conjunction with this guide.
Reflux-Bottoms control is effective when the boilup ratio of a column is high. The reflux controls distillate composition
while the bottoms flow controls the bottoms composition.
To Feed1
Vent
Cond Duty
VLV-102
VLV-103
Feed2
Butane
Product
Liquid Product
Debutanizer
To Feed2
VLV-100
C5+
Reb Duty
Butanes
VLV-101
Feed1 FC
Feed 2 FC
Cond PC
Cond LC
Column TC
Reboiler LC Key Compositions
Feed1
To Feed 2
P/F Specs Pressure
Pressure 198.5 psig
To Feed 1
P/F Specs Pressure
Pressure 199.2 psig
Vent
P/F Specs Flow
Molar Flow 0.0
Butane Product
P/F Specs Pressure
Pressure 182.6 psig
Liquid Product
P/F Specs Pressure
Pressure 186.9 psig
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen Technology, Inc. All rights reserved. 11-4407-1013
Jump Start: Using Aspen HYSYS

Dynamics with Columns


17
Figure 19. LB Control Case Flowsheet
In-depth exploration of these control schemes, as well as others that would be appropriate for a users specific process,
ultimately leads to safer and more profitable column operation.
Additional Resources
Public Website:
http://www.aspentech.com/products/aspen-hysys-dynamics.aspx
Online Training:
http://www.aspentech.com/products/aspen-online-training
AspenTech YouTube Channel:
http://www.youtube.com/user/aspentechnologyinc
To Feed1
Vent
Cond Duty
VLV-102
VLV-103
Feed2
Butane
Product
Liquid Product
Debutanizer
To Feed2
VLV-100
C5+
Reb Duty
Butanes
VLV-101
Feed 1 FC
Feed2 FC
Cond PC
Cond LC
Column TC
Reboiler LC
Key Compositions
Feed1
To Feed 2
P/F Specs Pressure
Pressure 198.5 psig
To Feed 1
P/F Specs Pressure
Pressure 199.2 psig
Vent
P/F Specs Flow
Molar Flow 0.0
Butane Product
P/F Specs Pressure
Pressure 182.6 psig
Liquid Product
P/F Specs Pressure
Pressure 186.9 psig
Worldwide Headquarters
Aspen Technology, Inc.
200 Wheeler Road
Burlington, MA 01803
United States
phone: +17812216400
fax: +17812216410
info@aspentech.com
Regional Headquarters
Houston, TX | USA
phone: +12815841000
So Paulo | Brazil
phone: +551134436261
Reading | United Kingdom
phone: +44(0)1189226400
Singapore | Republic of Singapore
phone: +6563953900
Manama | Bahrain
phone: +97317503000
For a complete list of offices, please visit
www.aspentech.com/locations
2013 Aspen Technology, Inc. AspenTech

, aspenONE

, the Aspen leaf logo, the aspenONE logo, and OPTIMIZE are trademarks of Aspen
Technology, Inc. All rights reserved. 11-4407-1013
About AspenTech
AspenTech is a leading supplier of software that optimizes process manufacturingfor energy, chemicals,
engineering and construction, and other industries that manufacture and produce products from a
chemical process. With integrated aspenONE

solutions, process manufacturers can implement best


practices for optimizing their engineering, manufacturing, and supply chain operations. As a result,
AspenTech customers are better able to increase capacity, improve margins, reduce costs, and become
more energy efficient. To see how the worlds leading process manufacturers rely on AspenTech to
achieve their operational excellence goals, visit www.aspentech.com.