Low Voltage Products

Switches
Change-over and transfer switches
Rotary change-over and bypass cam switches

162 500 A

lth /A
le /AC-22A, < 415V
le /AC-23A, < 415V

lth /A
le /AC-22A, < 415V
le /AC-23A, < 415V
le /AC-21B, < 415V

lth /A
le /AC-22A, < 415V
le /AC-23A, < 415V

Change-over switches

OT16F
OT25F
OT40F

OT63F
OT80F

OT100F
OT125F

OT160E
OT200E
OT250E

OT160E_W
OT200E_W
OT250E_W

25 32 40
16 25 40
16 20 23

63
63
45

100
100
80

160 200 250


160 200 250
160 200 250

160
160
160

80
80
75

125
125
90

200
200
200

OT315E
OT400E
250
250
250

OT1000E
OT1250E

OT1600E

OT2000E
OT2500E

1000
1000
1000

1600
1600
1250

2000

2500

2000

2500

1250
1250
1250

315 400
315 400
315 400

OTM160E
OTM200E
OTM250E

OTM160E_W
OTM200E_W
OTM250E_W

OTM315E
OTM400E

OTM630E
OTM800E

160
160
160

160
160
160

315
315
315

630
630
630

200 250
200 250
200 250

200 250
200 250
200 250

400
400
400

800
800
800

S01575A

II

S01473A

NO I
O OFF

Accessories

O OFF

NO I

Optional handles
Extended shafts
Auxiliary contacts

Terminal shrouds
Connecting accessories
Locking accessories

Secured power supply


Growing importance of a secure
power supply
As industrial processes and IT applications diversify, a secure power
supply is becoming an increasingly important asset in the drive to
cut production and maintenance costs. In emergency situations,
the system logic of power distribution can become complex with
mechanical devices looking after making, breaking, conducting and
isolating power. Loads may sometimes need to be transferred from
one supply to another this will be the case when energy use is
restricted or when the supply source is overloaded.

II

M
Man.

Tested against IEC 60947-6-1


In change-over applications where the loaded switch may need
to be operated remotely, adequate durability has been ensured by
Closed
transitionofswitch
testing against the IEC 60947-6-1 standard u
in the
specification
endurance requirements.
Utilization categories:
AC-31 for non-inductive or slightly inductive load
AC-33 for motor loads or mixed loads including motors

Comparison of endurance test between


IEC 60947-3 and -6-1 (Ie = 315 Amperes).
Number of operating cycles
Category
Category I Test Operating
A
B
cycle
[A]

IEC 60947-3 AC-23


1000

200

315

O-I-O

315

O-I-O-II-O

IEC 60947-6 AC-33


4000

1000

to diverse applications
Ensuring service continuity
ABB OTc change-over switches ensure service continuity with a number of built-in, integrated safety features. The
change-over mechanism, for example, offers three stable positions which ensure isolation of the two asynchronous
power supplies. This eliminates any risk of short-circuit between them, even in the presence of transient voltages.
In the motorized versions, the control circuit offers extra security: if two commands are received simultaneously, the
OFF command is always given priority.

Easy installation for local or remote control


The design of ABB OTc changeover switches is advanced and
compact, allowing installation in
confined spaces at considerable
savings. They are very easy to
install: the manually operated
switch is operated via a handle
fixed directly on the switch or on
the panel door.
The 16 to 125 Ampere sizes can
be snapped-on to a DIN rail and
the front fits in the 45 mm consumer unit cut-out.

II

FF
OO

The motorized change-over


switches have snap-on control
wire connections. Auxiliary
contacts can be snapped-on
to the sides of the switches
and the power terminals can
be connected in parallel with
bridging bars.

NO

Applications
II

ABB Change-over switches are suitable


for any emergency power supply system
application requiring an uninterrupted
supply of power from generator sets, UPS
equipment or power utilities.
In Automatic Transfer Switching Equipment (ATSE), emergency power is transferred automatically from one supply to
another via one or more load circuits by

the system logic that controls the motor


operated transfer switch.
The Closed Transition Transfer switches

ensure uninterrupted manual bypass to


the power line. They have two overlapping positions (I and II) which ensure that
the equipment is powered even when
maintenance work is being done.
The door-mounted rotary cam switches
come in many types: with two and three
positions, with spring return, with overlapping contacts and so on.
5

Manual change-over switches


Technical data
Data according to IEC 60947-3
Switch size

OT16_

......................................................................................................
Rated insulation voltage and rated
operational voltage AC20/DC20
Dielectric strength
Rated impulse withstand voltage
Rated thermal current and rated operational
current AC20/DC20

Pollution
degree 3
50 Hz 1min.

/ ambient 40C
/ ambient 40C
/ ambient 60C

Ip (r.m.s.) 50 kA, 415 V


Max. OFA_ fuse size

In open air
In enclosure
In enclosure
Cu
up to 500 V
690 V
up to 500 V
690 V
up to 415 V
440 V
500 V
690 V
230 V
400 V
415 V
500 V
690 V
up to 415 V
500 V
690 V
c (peak)
gG/aM

Ip (r.m.s.) 100 kA, 500 V


Max. OFA_ fuse size
Icw (r.m.s.)
Icm (peak)

c (peak)
gG/aM
690 V 1s
690 V

..with minimum conductor cross section


Rated operational current, AC-21A
Rated operational current, AC-22A
Rated operational current, AC-23A

Rated operational power, AC-23A 1)


The kW-ratings are accurate for 3-phase 1500
R.P.M. standard asychronous motors

Rated breaking capacity in


category AC-23
Rated conditional short-circuit
current Ip (r.m.s.) and corresponding max.
allowed cut-off current c (peak) value.
The cut-off current c refers to values
listed by fuse manufacturers
(single phase test acc. to IEC60269).
Rated short-time withstand current
Rated short-time making capacity 2)

V
kV
kV
A
A
A
mm2
A
A
A
A
A
A
A
A
kW
kW
kW
kW
kW
A
A
A
kA
A/A

750
6
8
25
25
20
4
16
16
16
16
16
16
16
10
3
7.5
7.5
7.5
7.5
128
128
80
6.5
40/32

kA
A
kA
kA
W

0.5
0.7
0.3

Power loss / pole

With rated current

Mechanical endurance

Number of oper. cycles3)

Cycles

10 000

Mechanical endurance / switch

Number of operations

Oper.

20 000

Cable size

Cu-wire size suitable for


terminal clamps
Counter torque required
Typical for 3-pole switches
3-pole switch
4-pole switch

mm2
AWG
Nm
Nm
kg
kg

0.75-10
18-8
0.8
1
0.25
0.31

Terminal tightening torque


Operating torque
Weight without accessories

Data
. . . . . . according
. . . . . . . . . . . .to
. . .UL508
. . . . . . . .(Listed)
.........................................................................
Current
Horsepower, 3-phase

1)
2)
3)

These values are given for guidance and may vary acc. to the motor manufacturer.
Short circuit duration >50ms, without fuse protection
Operating cycle: O - I - O - II - O

6
1SCC303003C0201

200 V
208 V
240 V
480 V
600 V

A
HP
HP
HP
HP
HP

16
3
3
5
10
10

Manual change-over switches


Technical data

OT25_

OT40_

OT63_

OT80_

OT100_

OT125_

......................................................................................................
750
6
8
32
32
25
6
25
25
25
25
20
20
20
11
4
9
9
9
9
160
160
88
6.5
40/32

0.5
0.7
0.6

750
6
8
40
40
32
10
40
40
40
40
23
23
23
12
5,5
11
11
11
11
184
184
96
6.5
40/32

750
6
8
63
63
50
16
63
63
63
63
45
45
45
20
11
22
22
22
15
360
360
160
13
100/80

750
6
8
80
80
63
25
80
80
80
80
75
65
58
20
22
37
37
37
18.5
640
464
160
13
100/80

750
6
8
115
115
80
35
100
100
100
100
80
65
60
40
22
37
37
37
37
640
480
320
16.5
125/125

750
6
8
125
125
100
50
125
125
125
125
90
78
70
50
22
45
45
45
45
720
560
400
16.5
125/125

0.5
0.7
1.6

17
100/80
1
1.4
2.8

17
100/80
1.5
2.1
4.5

2.5
3.6
4.0

2.5
3.6
6.3

10 000

10 000

10 000

10 000

10 000

10 000

20 000

20 000

20 000

20 000

20 000

20 000

0.75-10
18-8
0.8
1
0.25
0.31

0.75-10
18-8
0.8
1
0.25
0.31

1.5-35
14-4
2
1.2
0.64
0.70

1.5-35
14-4
2
1.2
0.64
0.70

10-70
8-00
6
2
0.90
1.18

10-70
8-00
6
2
0.90
1.18

......................................................................................................
25
7.5
7.5
7.5
15
20

40
10
10
10
20
25

60
15
15
15
30
30

80
20
20
20
40
40

7
1SCC303003C0201

Manual and motorized change-over switches


Technical data
Data according to IEC 60947-3
Switch size

OT_160_

OOT_200_

OT_250_

......................................................................................................
Rated insulation voltage and rated
operational voltage AC20/DC20
Dielectric strength
Rated impulse withstand voltage
Rated thermal current and rated operational
current AC20/DC20
..with minimum conductor cross section
Rated operational current, AC-21A

Pollution
degree 3
50 Hz 1min.

/ ambient 40C
/ ambient 40C

Rated operational current, AC-22A


Rated operational current, AC-23A

Rated operational power, AC-23A 1)


The kW-ratings are accurate for 3-phase 1500
R.P.M. standard asychronous motors

Rated breaking capacity in


category AC-23

In open air
In enclosure
Cu
up to 500 V
690 V
up to 500 V
690 V
up to 415 V
440 V
500 V
690 V
230 V
400 V
415 V
500 V
690 V
up to 415 V
500 V
690 V
c (peak)
gG/aM
c (peak)
gG/aM
c (peak)
gG/aM
690 V 0.15s
690 V 0.25s
690 V 1s
690 V

V
kV
kV
A
A
mm2
A
A
A
A
A
A
A
A
kW
kW
kW
kW
kW
A
A
A
kA
A/A
kA
A
kA
A
kA
kA
kA
kA

Rated conditional short-circuit


current Ip (r.m.s.) and
cut-off current c (peak) value.
The cut-off current c refers to values
listed by fuse manufacturers
(single phase test acc. to IEC60269).
Rated short-time withstand current

Ip (r.m.s.) 80 kA, 415 V


Max. OFA_ fuse size
Ip (r.m.s.) 100 kA, 500 V
Max. OFA_ fuse size
Ip (r.m.s.) 80 kA, 690 V
Max. OFA_ fuse size
Icw (r.m.s.)

Rated short-time making capacity 2)

Icm (peak) 3)

Power loss / pole

With rated current

Mechanical endurance

Number of oper. cycles4)

Cycles

Mechanical endurance / switch

Number of operations
Metric thread
diameter x length
Counter torque required
Typical for 3-pole
switches
3-pole switch
4-pole switch

Oper.

Terminal bolt size


Terminal tightening torque
Operating torque
Weight without accessories

1000
10
12
160
160
70
160
160
160
160
160
160
160
160
45
90
90
110
160
1 280
1 280
1 280
40.5
355/315
40.5
315/315
40.5
355/315
15
15
8
30

1000
10
12
200
200
95
200
200
200
200
200
200
200
200
60
110
110
132
200
1 600
1 600
1 600
40.5
355/315
40.5
315/315
40.5
355/315
15
15
8
30

1000
10
12
250
250
120
250
250
250
250
250
250
250
250
75
140
145
170
250
2 000
2 000
2 000
40.5
355/315
40.5
315/315
40.5
355/315
15
15
8
30

2.4

6.5

8 000

8 000

8 000

16 000

16 000

16 000

mm

M8x25

M8x25

M8x25

Nm

15-22

15-22

15-22

Nm

kg
kg

2.5
3.2

2.5
3.2

2.5
3.2

.Data
. . . . . .according
. . . . . . . . . . . .to
. . IEC
. . . . . 60947-6-1
............................................................................
Class of equipment
Rated short-time withstand current
Rated operational current, AC-31B
Rated operational current, AC-33B

Icw (r.m.s.)

PC

PC

690 V 0.1s

kA

15

15

15

up to 415 V
up to 415 V

A
A

160
160

200
200

250
250

These values are given for guidance and may vary acc. to the motor manufacturer.
Short circuit duration >50ms, without fuse protection
Max. distance from switch frame to nearest busbar / cable support 150 mm
4)
Operating cycle: O - I - O - II - O
5)
Category AC-21B, up to 415V
6)
For manual change-over switches.
7)
For motorized change-over switches.
1)
2)
3)

8
1SCC303003C0201

PC

Manual and motorized change-over switches


Technical data

OT_315_

OT_400_

OT_630_

OT_800_

OT1000_

OT1250_

OT1600_

OT2000_

OT2500_

......................................................................................................
1000
10
12
315
315
185
315
315
315
315
315
315
315
315
100
160
180
220
315
2 520
2 520
2 520
59
500/500
61.5
500/450
59
500/500
31
24
15
65

1000
10
12
400
400
240
400
400
400
400
400
400
400
400
132
220
230
280
400
3 200
3 200
3 200
59
500/500
61.5
500/450
59
500/500
31
24
15
65

1000
10
12
630
630
2 x 185
630
630
630
630
630
630
630
630
200
355
355
400
630
5 040
5 040
5 040
83.5
800/1 000
90
800/800
83.5
800/1 000
38
36
20
80

1000
10
12
800
800
2x240
800
800
800
800
800
800
800
800
250
450
450
560
800
6 400
6 400
6 400
83.5
800/1 000
90
800/800
83.5
800/1 000
38
36
20
80

1 000
10
12
1 000

1 000
10
12
1 250

1 000
10
12
1 600

1 000
10
12
2000

1 000
10
12
2500

2 x 300
1 000
1 000
1 000
1 000
1 000
1 000
1 000
1 000
315
560
560
710
1 000
10 000
10 000
10 000
100
1 250/1 250
106
1 250/1 250

2 x 400
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
400
710
710
900
1 200
10 000
10 000
10 000
100
1 250/1 250
106
1 250/1 250

2 x 500
1 600
1 600
1 600
1 600
1 250
1 250
1 250
1 250
400
710
710
900
1 200
10 000
10 000
10 000
100
1 250/1 250
106
1 250/1 250

3 x 500
2000 5)

4 x 500
2500 5)

50
50
50
92

50
50
50
92

50
50
50
92

50
50
50
110

50
50
50
110

6.5

10

25

40

19

29

48

55

85

8 000

8 000

5 000

5 000

3 000

3 000

3 000

2000

2000

16 000

16 000

10 000

10 000

6 000

6 000

6 000

4000

4000

M10x30

M10x30

M12x40

M12x40

M12x60

M12x60

M12x60

M12x60

M12x60

30-44

30-44

50-75

50-75

50-75

50-75

50-75

50-75

50-75

16

16

27

27

78

78

78

78

78

4.7
5.8

4.7
5.8

12.8
15.6

12.8
15.6

32.3
40.2

32.3
40.2

34.8
43.3

48
60

48
60

......................................................................................................
PC

PC

PC

PC

PC

PC

PC

PC

25

25

38

38

50

50

50

50

PC
50

315
315

400
400

6306)/6507)
6306)/6507)

8006)/7207)
8006)/6507)

1 000
1 000

1 250
1 000

1 600
1 000

2000

2000

9
1SCC303003C0201

Motorized change-over switches


Technical data
Data for motorized change-over switches OEM according to IEC 60947-3
Switch size

OEM
1000

OEM
1250

OEM
1600

......................................................................................................
Rated insulation voltage and rated
operational voltage AC20/DC20
Dielectric strength
Rated impulse withstand voltage
Rated thermal current and rated
operational current AC20/DC20

Pollution degree 3
50 Hz 1min.

/ ambient 40C
/ ambient 40C
/ ambient 60C

..with minimum conductor cross section


Rated operational current, AC-21A
Rated operational current, AC-22A
Rated operational current, AC-23A

Rated operational power,


AC-23A

Rated conditional short-circuit


current Ip (r.m.s.) and
corresponding max. allowed
cut-off current c (peak) 1)
Rated short-time withstand current
Rated short-circuit making capacity
Mechanical endurance
Mechanical endurance / switch
Terminal bolt size
Terminal tightening torque
Operating torque

The kW-ratings are


accurate for 3-phase
1500 R.P.M. standard
asynchronous motors.
Ip (r.m.s.) : 50 kA, 690 V

Icw (r.m.s.)
Icm (peak)
Number of operating cycles 3)
Number of operations

V
kV
kV

1000
8
8

1000
8
8

1000
8
8

In open air
In enclosure
In enclosure
Cu

A
A
A
mm2

up to 690 V
1000 V
up to 500 V
up to 415 V
440 V
500 V
220-240 V
400-415 V
440 V
500 V
c (peak)

A
A
A
A
A
A
kW
kW
kW
kW
kA

1000
1000
900
2x
(60x5)
1000
1000
1000
800
800
800
250
400
400
450
105

1250
1250
1000
2x
(80x5)
1250
1000
1250
800
800
800
250
400
400
450
105

1600
1600
1250
2x
(100x5)
1600
1000
1600
800
800
800
250
400
400
450
105

690V, 1s
690V/500V

kA
kA
Cycles
Oper.
mm
Nm
Nm

50 2)
105
3000
6000
12x60
50...75
25

50 2)
105
3000
6000
12x60
50...75
25

50 2)
105
3000
6000
12x60
50...75
25

Metric thread diameter x length


Counter torque required
3-pole switches

Data according to IEC 60947-6-1

......................................................................................................
Rated operational current, AC-31B
Rated operational current, AC-33B
Rated operational current, AC-31A
Rated operational current, AC-33A

up to 415 V
up to 415 V
up to 415 V
up to 415 V

The cut-off current c refers to values listed by fuse manufacturers (single phase test acc. to IEC60269).
Maximum distance between busbar support and switch terminal 70 mm.
3)
Operating cycle: O - I - O - II - O
1)
2)

10
1SCC303003C0201

A
A
A
A

1000
800
1000
450

1250
800
1250
450

1600
800
1600
450

UL/CSA manual transfer switches


Technical data
Data according to UL and CSA
OETLNFC800

OETLNFC1200

UL1008

UL1008

V
A

600
800

600
1200

V
A

240
630

Switch size

OT200U_

OT400U_

OT600U_

......................................................................................................
Standards

UL98
UL98
CSA 22.2#4 CSA 22.2#4

General use ratings - 1- or 3-phase ratings


Horsepower, 3-phase ratings

240V
480V
600V

Resistive load
Voltage
Current
Total load
Voltage
Current
Short-circuit ratings

Required protection

Circuit
breaker
Class J/L
fuse
fuse size
Class RK5
fuse
fuse size

UL98
CSA 22.2#4

600

600

600

A
HP
HP
HP

200
75
150
200

400
125
250
350

600
200
450
500

kA

14

25

35

kA

65/100

100

100

400/200

600

800

kA

100

600

Data according to IEC 60947-3

......................................................................................................
Rated insulation voltage and rated
operational voltage AC20/DC20
Dielectric strength
Rated impulse withstand voltage
Rated thermal current and rated operational
current AC20/DC20
..with minimum conductor cross section

Pollution degree 3
50 Hz 1min.

/ ambient 40C

Rated operational current, AC-23A

current Ip (r.m.s.) and


corresponding max. allowed
cut-off current c peak value 1)
Rated short-time withstand current
Rated short-circuit making capacity
Mechanical endurance
Mechanical endurance / switch
Terminal bolt size
Terminal tightening torque
Operating torque

In open air

Ip (r.m.s.) : 100 kA,


500 V
Max. OFA_ fuse size
Ip (r.m.s.) : 80 kA,
690 V
Max. OFA_ fuse size
Icw (r.m.s.)
Icm (peak)
Number of operating
cycles 3)
Number of operations
Metric thread diameter x length
Counter torque
required
3-pole switches

1000
10
12

1000
10
12

1000
10
12

1000
8
8

1000
8
8

250

400

800

1250

1600

mm2

120

240

up to 690 V
up to 500 V
690 V
up to 500 V
690 V

A
A
A
A
A

250
250
250
250
250

400
400
400
400
400

2x
240
800
800
800
800
800

2x
(80x5)
1250
1250

2x
(100x5)
1600
1600

800

800

c (peak)

kA

40.5

61.5

90

gG/aM

315/315

500/450

800/800

c (peak)

kA

40.5

59

83,5

gG/aM
690V, 1s
690V

A
kA
kA

355/315
8
30

500/500
15
65

800/1000
20
80

50 2)
105

50 2)
105

Cycles

8000

8000

5000

3000

3000

Oper.

16000

16000

10000

6000

6000

mm

M8x25

M10x30

M12x40

M12x60

M12x60

Nm

15...22

30...44

50...75

50...75

50...75

Nm

16

27

25

25

Cu

Rated operational current, AC-21A


Rated operational current, AC-22A

Rated conditional short-circuit

V
kV
kV

Data according to IEC 60947-6-1

......................................................................................................
Rated operational current

1)
2)
3)

AC-31B
AC-33B
AC-31A
AC-33A

up to 415 V
up to 415 V
up to 415 V
up to 415 V

A
A
A
A

250
250

400
400

800
800

1250
800
1250
450

1600
800
1600
450

The fuse in single-phase test according to IEC 60269.


Maximum distance between busbar support and switch terminal 70 mm.
Operating cycle: O - I - O - II - O.

11
1SCC303003C0201

Motor operators
Technical data
Data for motor operator OTM according to IEC 60947
160...250

315...400

600...800

220 - 240
110 - 125
48
24

220 - 240
110 - 125
48
24

220 - 240
110 - 125
48
24

0.85 - 1.1 x Ue

0.85 - 1.1 x Ue

0.85 - 1.1 x Ue

s
s
s
s

0.4 - 1.0
0.5 - 1.5
0.5 - 1.5
0.4 - 1.0

0.4 - 1.0
0.5 - 1.5
0.4 - 1.0
0.4 - 1.0

0.4 - 1.0
0.6 - 1.2
0.6 - 1.6
0.5 - 1.5

s
s
s
s

1.0 - 2.0
1.1 - 2.5
1.4 - 2.5
1.0 - 2.0

0.9 - 2.0
1.2 - 2.6
1.0 - 2.0
1.0 - 2.0

0.9 - 2.0
1.2 - 3.0
1.3 - 3.0
1.1 - 2.5

s
s
s
s
A
A
A
A
A
A
A
A
mA
mA
A
A
mm

0.4 - 1.0
0.4 - 1.1
0.5 - 1.1
0.4 - 1.0
0.2
0.5
1.1
3.3
1.3
2.1
4.4
16.8
T / 315 / H
T / 500 / H
T / 1.25 / H
T / 4.0 / H
5x20

0.4 - 1.0
0.5 - 1.5
0.4 - 1.0
0.4 - 1.0
0.5
0.6
2.1
4.2
2.1
2.5
8.3
17.5
T / 500 / H
T / 630 / H
T / 2.5 / H
T / 5.0 / H
5x20

0.4 - 1.0
0.6 - 1.5
0.7 - 1.6
0.5 - 1.5
0.7
0.8
2.6
4
2.8
4.6
8.4
22.4
T / 1000 / H
T / 1000 / H
T / 2.5 / H
T / 5.0 / H
5x20

cycles/min
cycles/min
cycles/min
cycles/min
cycles/min
cycles/min
cycles/min
cycles/min

1
1
1
1
10
10
10
10

1
1
1
1
10
10
10
10

kV
kV

1
1
1
1
10
10
10
10
III
4
1.5

ms

100

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Switch
. . . . . .size
....................................
Rated operational voltage Ue

Operating voltage range


Operating time 1)

Operating transfer time 1)

Pollution degree 3
50/60 Hz

90 I-0, 0-I, 0-II, II-0

180 I-0-II, II-0-I

OFF -time when operating I - II or II - I 1) 180

I - II, II - I

Nominal current In 1)

Current Inrush 1)

Overload fuse

Type / In / Capacity

Operating rate

Size
Cycle 0-I-0-II-0
Max. continuous

Max. short-time 10 cycles

Overvoltage category
Rated impulse withstand voltage Uimp
Dielectric strength
Impulse command
Terminals
Voltage supply wiring for Ue
Cross section
Short-circuit protection device
Push-button control
Cross section
Maximum cable length
State information of locking
Handle attached or motor operator locked
Locking motor operator
Short-circuit protection device
Protection degree
Operating temperature
Transportation and storage temperature
Max. altitude
1)

Under nominal conditions

12
1SCC303003C0201

V AC
V AC/DC
V DC
V DC
0.85 - 1.1 x Ue
220-240V AC
110-125V AC/DC
48V DC
24V DC
0.85 - 1.1 x Ue
220-240V AC
110-125V AC/DC
48V DC
24V DC
0.85 - 1.1 x Ue
220-240V AC
110-125V AC/DC
48V DC
24V DC
220-240V AC
110-125V AC/DC
48V DC
24V DC
220-240V AC
110-125V AC/DC
48V DC
24V DC
220-240V AC
110-125V AC/DC
48V DC
24V DC
220-240V AC
110-125V AC/DC
48V DC
24V DC
220-240V AC
110-125V AC/DC
48V DC
24V DC
50 Hz 1min.
Min. impulse
duration

solid/stranded
max. fuse size
C - II - I - O
solid/stranded

mm2
A
mm2
m

11-12-14 (C/O)
23-24 (NO)
MCB type and size
C
C
m

PE- N - L
1.5 - 2.5
16
no SELV
1.5 - 2.5
100
no SELV
5A/250V/cosj=1
5A/250V/cosj=1
C/2A
IP20
-25...+55C
-40...+70C
2 000

Motor operators and auxiliary contacts


Technical data
Technical data for motor operator OEM
Rated insulation voltage (control circuit), Ui
Operating temperature
Rated control voltage
Rated control frequency (230 VAC)

250V
-5... +40C
0.85...1.1 x Us
45...66 Hz

Operation time [s]


when operating
0-I, 0-II, I-0 or II-0
Min
Max

Operation time [s]


when operating
I-II or II-I
Min
Max

OFF-time [s]
when operating
I-II or II-I
Min
Max

Nominal
voltage
Us [V]

Type

24

OEM10001600

0.3

1.1

0.7

0.4

48

OEM10001600

0.3

0.6

1.9

0.3

230

OEM10001600

0.4

1.4

2.7

0.5

Nominal
voltage
[V]

Operational
current [A]

Max. current
[A]

230 VAC

48 VAC/VDC

18

24 VAC/VDC

10

36

Max. continuous
operating rate
[cycles / h]

Max. short-time
( 10 cycles)
operating rate
[cycles / h]

120

240

120

240

1.4

120

240

Connection diagram
for supply and control
wires
(max. 2.5 mm2)

F3

L1

14

13

14

13

14

13

PE

II

1
3
4
5
6

Technical data for auxiliary contacts according to IEC 60947-5-1


For OA1G_, OA2G_, OA3G_, OA7G_, OA8G_

For OZXK_

......................................................................................................
Ue/[V]
230
400
415
690

AC15
Ie/[A]
6
4
4
2

Ue/[V]
24
72
125
250
440

Ie/[A]
10
4
2
0.55
0.1

DC12

P/[W]
240
290
250
140
44

Ie/[A]
2
0.8
0.55
0.27

DC13

P/[W]
50
60
70
70

AC12
Ue/[V]
Ie/[A]
120
8
240
6
400
4
415
4
480
3
500
3
690
2

DC12
Ue/[V]
Ie/[A]
125
1.1
250
0.55
440
0.31
500
0.27
600
0.2

13
1SCC303003C0201

Manual transfer switches, closed transition


Technical data
Data according to UL508 (Recognized)

Switch size
General use
Voltage
Current
Short circuit current r.m.s

OESC

250K_

500K_

250K04N2

400K04N2

V
A
kA

480
250
50

480
500
50

480
250 1)
50

480
400 2)
50

V
kV
kV
A
mm2
V
A
A
kA

1000
8
12
250
120
1000
250
250
42

1000
8
12
500
2x 120
1000
500
500
42

1000
8
12
250
120
1000
250 1)
250 1)
42

1000
8
12
400
240
1000
400 2)
400 2)
42

Cycles
Oper.
mm
Nm
Nm

8000
16 000
M10x40
30...44
30

8000
16 000
M10x40
30...44
30

8000
16 000
M10x40
30...44

8000
16 000
M10x40
30...44

Data according to IEC 60947-3


Rated insulation voltage
Pollution degr. 3
Dielectric strength
50 Hz 1min.
Rated impulse withstand voltage
Rated thermal current in ambient 40 C
In open air
...with minimum cable cross section
Cu
Rated operational voltage AC-20 and DC-20
Rated operational current, AC-21A
500 V
Rated operational current, AC-22A
500 V
Rated conditional short-circuit current Ip (r.m.s.)
Ip : 50 kA/ 500 V
and corresponding max. allowed cut-off
current c, peak value.
Mechanical endurance
Number of operating cycles 3)
Mechanical endurance / switch
Number of operations
Terminal bolt size
Diameter x length
Terminal tightening torque
Counter torque required
Operating torque
3-pole switches

1)
2)

Powerpoles 250 A; Neutral 400 A, with minimum cable cross section 240 mm2.
Powerpoles 400 A; Neutral 630 A, with minimum cable cross section 2 x 185 mm2.

14
1SCC303003C0201

3)

Operating cycle: O - I - O - II - O