James Golinveaux

Kevin Maughan
Jeff Barkley
Applications of the Tyco Model EC-25
Storage Sprinkler
Copyright 2012 Tyco Fire Protection Products. All rights reserved.
Te products and specications published herein are for general evaluation and reference purposes only and are subject to change
by Tyco Fire Protection Products without notice. For the most up-to-date information, please visit www.tyco-re.com. Te infor-
mation provided in this application paper should not be relied on as a substitute for professional advice concerning specic appli-
cations. ALTHOUGH TYCO FIRE PROTECTION PRODUCTS HAS ENDEAVORED TO ENSURE ITS ACCURACY,
ALL INFORMATION HEREIN IS PROVIDED ON AN AS IS BASIS, WITHOUT WARRANTY OF ANY KIND,
EITHER EXPRESS OR IMPLIED. Without limiting the foregoing, Tyco Fire Protection Products does not warrant the accu-
racy, adequacy or completeness of any such information. All users of the information provided herein assume the risk of use or
reliance on such information and Tyco Fire Protection Products shall not be liable for any damages for such use including, but not
limited to, indirect, special, incidental or consequential damages.
Applications of the
TYCO Model EC-25 Storage Sprinkler
Applications of the
TYCO Model EC-25 Storage Sprinkler
1
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Benets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Simple Bay Example with Full Coverage Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Simple Bay Example at Reduced Coverage Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Short Grid Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
FM Global - Lowest Hydraulic Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
About the Authors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Applications of the
TYCO Model EC-25 Storage Sprinkler
2
Introduction
As with any new technology, understanding appropriate applications is the key to successful implementation.
Te TYCO Model EC-25 Sprinkler is the most powerful control-mode sprinkler ever developed. In addition
to better re protection, it provides unsurpassed economic advantages Simply stated, the increased perfor-
mance of this technology sets historical precedence; it performs above the magic 100 ft
2
(9,3 m
2
) maximum
spacing limitations imposed for Extra Hazard and Storage occupancies since the development of the spray
sprinkler in the early 1950s.
Trough tested performance, the Model EC-25 Sprinklers 100 ft
2
(9,3 m
2
) minimum and the 196 ft
2

(18,2 m
2
) maximum sprinkler spacing provide a superior level of re protection by eliminating sprinkler skip-
ping and controlling the number of operating sprinklers. Additionally, the safety factor of the discharge from
the initial sprinkler in a re event is considerable. With a K-factor of 25.2 GPM/psi
1/2
(362,9 LPM/bar
1/2
),
the rst sprinkler with an average static water supply of 70 psi (4,83 bar) will discharge approximately 210
GPM (795 LPM) or slightly over a 1.0 GPM/ft
2
(40,7 mm/min) for a coverage area of 196 ft
2
(18,2 m
2
) per
sprinkler. In contrast, a sprinkler with a K-factor of 8.0 GPM/psi
1/2
(115,2 LPM/bar
1/2
) will only discharge
67 GPM (253,6 LPM) or only a 0.67 GPM/ft
2
(27,2 mm/min) over a coverage area of 100 ft
2
(9,3 m
2
) per
sprinkler.
Benets
Key benets of the Model EC-25 Sprinkler include lower installed cost and better re protection when com-
pared to standard coverage sprinkler systems. Tese benets are provided by:
Fewer opened sprinklers and fewer consumed pallets than K-8.0 (115), K-11.2 (160), and K-16.8 (240)
standard coverage sprinklers as shown in full-scale re tests performed at UL
Fewer branch lines and fewer sprinklers as a result of the extended coverage area
Lower operating pressures in accordance with the S x L Spacing Rules dened by NFPA 13, Section 8.5.2
Lowest hydraulic system demand provided in NFPA 13 2013 Edition, Chapter 21 Alternative Sprinkler
System Designs for Chapters 12 through 20 and FM Global Property Loss Prevention Data Sheet 8-9,
July 2011 Revision, and Engineering Bulletin 06-11
Applications of the
TYCO Model EC-25 Storage Sprinkler
3
Simple Bay Example with Full Coverage Area
For a 40,000 ft
2
(3716,1 m
2
) building with 200 ft (61,0 m) long bays where the bays are greater than
25 ft (7,6 m) and up to 28 ft (8,5 m) wide, the number of branch lines can be reduced from three, when using
a standard spray sprinkler, to two using Model EC-25 Sprinklers as shown in Figure 1.
With this bay spacing, the full coverage area of 196 ft
2
(18,2 m
2
) can be achieved. With greater than
25 ft (7,6 m) to 28 ft (8,5 m) bays, the Model EC-25 Sprinkler is spaced at 14 ft (4,3 m) intervals along
each branch line. A total of 15 sprinklers per branch line and 30 sprinklers per bay are needed. Assuming a
required density of 0.60 GPM/ft
2
(24,4 mm/min), the pressure at the sprinkler is 21.7 psi (1,50 bar) with a
coverage area of 196 ft
2
(18,2m
2
) per Model EC-25 Sprinkler. In comparison, if utilizing standard coverage
sprinklers, 3 branch lines are required with 19 sprinklers per branch line for a total of 57 sprinklers per bay.
Refer to Table 1 for further comparisons.
Versus
>25-0 to 28-0
(7,62 to 8,53 m)
7-0
(2,13 m)
14-0
(4,27 m)
1
4

-
0

(
4
,
2
7

m
)
1
4

-
0

(
4
,
2
7

m
)
1
0

-
8

1
/
2

(
3
,
2
6

m
)
1
0

-
8

1
/
2

(
3
,
2
6

m
)
1
0

-
8

1
/
2

(
3
,
2
6

m
)
4-8
(1,42 m)
4-8
(1,42 m)
9-4
(2,84 m)
9-4
(2,84 m)
7-0
(2,13 m)
>25-0 to 28-0
(7,62 to 8,53 m)
Extended Coverage
196 ft
2
(18,2 m
2
)
2 Branch Lines
Standard Coverage
100 ft
2
(9,3 m
2
)
3 Branch Lines
Bay Bay
Figure 1: Simple Bay Example of Branch Line Spacing in Bays more than 25 ft to 28 ft (7,62 to 8,52 m)
at full coverage area of 196 ft
2
(18,2m
2
)
Applications of the
TYCO Model EC-25 Storage Sprinkler
4
Simple Bay Example at Reduced Coverage Area
Now consider for the same 40,000 ft
2
(3716,1 m
2
) building with 190 ft (57,9 m) long bays are spaced with a
width greater than 28 ft (8,5 m) up to 30 ft (9,1 m), the exibility of the Model EC-25 Sprinklers allows the
use of a smaller protection area of 144 ft
2
(13,4 m
2
) at 15 ft (4,6 m) spacing between branch lines.
When using a coverage area up to 144 ft
2
(13,4 m
2
), the Model EC-25 Sprinklers may be spaced up to
15 ft (4,6 m) in one direction. Figure 2 uses this 15 ft (4,6 m) allowance between branch lines. With this
smaller protection area, the extended coverage sprinklers are spaced at 9 ft 7 in (2,9 m) along each branch line
for a total of 20 sprinklers per branch line and 40 sprinklers per bay.
Again, in comparison, if utilizing standard coverage sprinklers, 3 branch lines are required with 19 sprin-
klers per branch line for a total of 57 sprinklers per bay. Tis spacing results in a total of 399 standard cover-
age sprinklers per 40,000 ft
2
(3716,1 m
2
) system as compared to 280 Model EC-25 Sprinklers with less than
maximum Model EC-25 Sprinkler spacing. Te required pressure of the Model EC-25 Sprinkler has been
reduced to 11.7 psi (0,81 bar) as compared to the standard coverage sprinkler pressure requirement of 28.7 psi
(1,98 bar) when utilizing an K-11.2 (160) sprinkler. Refer Table 2 for side by side comparison.
Table 1: Summary of Simple Bay Example with Optimum Bay Width
Model EC-25
Extended Coverage
Sprinkler
Standard Coverage
Sprinkler
Comments
Number of Branch
Lines per Bay
2 3
Possible branch-line savings per bay
can be a major factor in reducing
material and labor cost of installation.
Greater than 25 ft (7,6 m) to
28 ft (8,5 m) bays are optimal
Number of Sprinklers
per Bay
30 57
47% less sprinklers
Total Sprinklers 210 399
Minimum Pressure
at Sprinkler
21.7 psi at 196 ft
2
(1,50 bar at 18,2 m
2
)
28.7 psi at 100 ft
2

(1,98 bar at 9,3 m
2
)
Less required pressure at
almost double the spacing of an
11.2 (160) K-factor Standard
Coverage Sprinkler
Applications of the
TYCO Model EC-25 Storage Sprinkler
5
Table 2: Summary of Simple Bay Example with Non-Optimum Bay Width
Model EC-25
Extended Coverage
Sprinkler
Standard Coverage
Sprinkler
Number of Branch Lines Per Bay 2 3
Number of Sprinklers Per Bay 40 57
Total Sprinklers 280 399
Minimum Pressure at Sprinkler 11.7 psi (0,81 bar) 28.7 psi (1,98 bar)
Versus
>28-0 to 30-0
(8,53 to 9,14 m)
7-6
(2,29 m)
15-0
(4,57 m)
9

-
7

(
2
,
9
3

m
)
9

-
7

(
2
,
9
3

m
)
1
0

-
0

(
3
,
0
5

m
)
1
0

-
0

(
3
,
0
5

m
)
1
0

-
0

(
3
,
0
5

m
)
5-0
(1,52 m)
5-0
(1,52 m)
10-0
(3,05 m)
10-0
(3,05 m)
7-6
(2,29 m)
>28-0 to 30-0
(8,53 to 9,14 m)
Extended Coverage
144 ft
2
(13,38 m
2
)
2 Branch Lines
Standard Coverage
100 ft
2
(9,3 m
2
)
3 Branch Lines
Bay Bay
Figure 2: Simple Example of Branch Line Spacing in Bays > 28 to 30 ft (8,5 to 9,1 m) at reduced
144 ft
2
(13,4 m
2
) coverage area
Applications of the
TYCO Model EC-25 Storage Sprinkler
6
Short Grid Example
Figures 3 and 4 can be used to demonstrate branch line savings without major modications to pipe size due
to the low operating pressures of the Model EC-25 Sprinkler.
Figure 3 shows a representative grid system designed for standard spray sprinklers. Tis system consists of a 6
in (150 mm) primary main and riser as well as a 4 in (100 mm) secondary main. Tere are 24, 2 in (50 mm)
branch lines.
150'
(45,7 m)
230'
(70,1 m)
6" (150 mm)
PRIMARY
MAIN
6" (150 mm)
RISER AND
SUPPLY
MAIN
4" (100 mm)
SECONDARY
MAIN
2" (50 mm)
BRANCH
LINES
Figure 3: Layout K-11.2 (160) and K-16.8 (240) Standard Spray Sprinklers
Applications of the
TYCO Model EC-25 Storage Sprinkler
7
Figure 4 shows a grid system designed with the extended coverage Model EC-25 Sprinkler for the same sys-
tem size as shown in Figure 3. Tis system consists of a 6 in (150 mm) primary main and riser as well as a 6 in
(150 mm) secondary main. Tere are 17, 2 in (50 mm) branch lines.
Table 3 compares the material required for the sprinkler systems shown in Figures 3 and 4 in a building with
27 ft (8,2 m) high ceilings with up to 20 ft (6,1 m) of Group A Plastic Commodities storage.
150'
(45,7 m)
224'
(68,3 m)
6" (150 mm)
PRIMARY
MAIN
6" (150 mm)
RISER AND
SUPPLY
MAIN
6" (150 mm)
SECONDARY
MAIN
2" (50 mm)
BRANCH
LINES
Figure 4: Actual Layout TYCO K-25.2 (360) Model EC-25 Sprinkler Showing fewer required branch
lines
Table 3: Comparison of K=11.2 (160), K=16.8 (240), and Model EC-25 Sprinklers
Material
Model EC-25
Extended Coverage
Sprinkler
K-11.2 (160)
Standard Sprinkler
K-16.8 (240)
Standard Sprinkler
Total Branch Line
2550 ft at 2 in NPS
(777,2 m at 50 mm)
3600 ft at 2 in NPS
(1097,3 m at 50 mm)
3600 ft at 2 in NPS
(1097,3 m at 50 mm)
Total Primary Main
224 ft at 6 in NPS
(68,3 m at 150 mm)
230 ft at 6 in NPS
(70,1 m at 150 mm)
230 ft at 6 in NPS
(70,1 m at 150 mm)
Total Secondary Main
224 ft at 6 in NPS
(68,3 m at 150 mm)
230 ft at 4 in NPS
(70,1 m at 100 mm)
230 ft at 4 in NPS
(70,1 m at 100 mm)
Total Feed Main
20 ft at 6 in
(6,1 m at 150 mm)
20 ft at 6 in
(6,1 m at 150 mm)
20 ft at 6 in
(6,1 m at 150 mm)
Riser
27 ft at 6 in
(8,2 m at 150 mm)
27 ft at 6 in
(8,2 m at 150 mm)
27 ft at 6 in
(8,2 m at 150 mm)
Applications of the
TYCO Model EC-25 Storage Sprinkler
8
In the example described in Figures 3 and 4, even though the Model EC-25 Sprinkler installation requires
up-sizing the secondary main from 224 ft (68,3 m) of 4 in (100 mm) pipe to 6 in (150 mm) pipe, there is an
elimination of 1,050 ft (320 m) of 2 in (50mm) pipe required for the branch lines and the labor required to
install 7 additional branch lines required for standard coverage sprinklers.
A density of 0.60 GPM/ft
2
(24,4 mm/min) was used to calculate the system demand and pressure. For the
building, the supply at the base of the riser is the following:
Static 82 psi (5,65 bar)
Residual 71 psi (4,90 bar)
Flow 2123 GPM (8036,4 LPM)
If operating pressure is a constraint, under NFPA 13 the Model EC-25 Sprinkler oers the exibility of reduc-
ing the coverage area using the S x L Spacing Rules and reducing the pressure necessary to deliver the required
water demand using the density/area method. For example, Model EC-25 Sprinklers provide the advantage of
extremely low operating pressures at 100 ft
2
(9,3 m
2
) while acting as standard coverage sprinklers delivering
0.67 GPM/ft
2
(27,29 mm/min) density at only 7 psi (0,48 bar).
Table 4: Comparison of Pressure and Flow for K-11.2 (160), K-16.8 (240), and Model EC-25 Sprinklers
Model EC-25
Extended Coverage
Sprinkler
K-11.2 (160)
Standard Sprinkler
K-16.8 (240)
Standard Sprinkler
System Demand
76.42 psi at 1361.2 GPM
(5,27 bar at 5152,7 LPM)
69.26 psi at 1239.4 GPM
(4,78 bar at 4691,6 LPM)
54.36 psi at 1278.6 GPM
(3,75 bar at 4840,0 LPM)
Available Pressure at
System Demand
77.2 psi
(5,32 bar)
77.9 psi
(5,37 bar)
77.7 psi
(5,36 bar)
Applications of the
TYCO Model EC-25 Storage Sprinkler
9
Lowest Hydraulic Demand
While ESFR Sprinklers have become the standard in ceiling-only storage protection over the last several years,
the Model EC-25 Sprinkler now has the lowest system demand when used in accordance with NFPA 13 2013
Edition, Chapter 21 Alternative Sprinkler System Designs for Chapters 12 through 20 and specied in FM
Global Property Loss Prevention Data Sheet 8-9, July 2011 Revision, and Engineering Notice 06-11.
Te Model EC-25 Sprinkler only requires a 6 sprinkler design for ceilings of 30 ft (9,0 m) or less as compared
to ESFR sprinklers that require a 12 sprinkler design. Reducing the sprinklers in the design by half translates
into a signicant saving in hydraulic demand for the system while almost doubling the sprinklers coverage
area resulting in fewer branch lines and sprinklers.
Table 8: Design Hydraulic Requirement Including Hose for Class 1 to 4 and Cartoned Unexpanded
Plastic Commodities for Ceiling Height of 30 feet (9,0 meters) in Open Frame Rack Storage
Arrangements
Model EC-25
ESFR
K-14 (200)
ESFR
K-17 (240)
ESFR
K-22 (320)
ESFR
K-25 (360)
Number of
Sprinklers
6 12
Pressure
FM & NFPA 13 FM & NFPA 13 FM & NFPA 13 FM & NFPA 13 FM NFPA 13
30 psi
(2,07 bar)
50 psi
(3,45 bar)
35 psi
(2,41 bar)
25 psi
(1,72 bar)
20 psi
(1,38 bar)
15 psi
(1,0 bar)
Hose
Allowance
250 GPM at
spacing 14 ft
(950 LPM at
spacing 4,3 m)
250 GPM at spacing 12 ft
(950 LPM at spacing 3,7 m)
Hydraulic
Requirement
Including
Hose
1078 GPM at
spacing 14 ft
(4080 LPM at
spacing 4,3 m)
1438 GPM at
spacing 12 ft
(5440 LPM at
spacing 3,7 m)
1443 GPM at
spacing 12 ft
(5412 LPM at
spacing 3,7 m)
1594 GPM at
spacing 12 ft
(5957 LPM at
spacing 3,7 m)
1602 GPM at
spacing 12 ft
(6061 LPM at
spacing 3,7 m)
1421 GPM at
spacing 12 ft
(5270 LPM at
spacing 3,7 m)
Applications of the
TYCO Model EC-25 Storage Sprinkler
10
Te Model EC-25 Sprinkler requires an 8 sprinkler design for ceilings of 35 ft (10,5 m) compared to ESFR
sprinklers, which require 12 sprinklers. Tis one-third reduction of sprinklers required in the design translates
into a signicant saving in hydraulic demand for the system while requiring fewer branch lines and sprinklers.
Table 9- Design Hydraulic Requirement Including Hose for Class 1 to 4 and Cartoned Unexpanded
Plastic Commodities for Ceiling Height of 35 feet (10,5 meters) in Open Frame Rack Storage
Arrangements
Model
EC-25
ESFR
K-14 (200)
ESFR
K-17 (240)
ESFR
K-22 (320)
ESFR
K-25 (360)
Number of
Sprinklers
8 12
Pressure
FM & NFPA 13 FM & NFPA 13 FM NFPA 13 FM & NFPA 13 FM NFPA 13
40 psi
(2,76 bar)
75 psi
(5,17 bar)
50 psi
(3,45 bar)
52 psi
(3,6 bar)
35 psi
(2,41 bar)
30 psi
(2,07 bar)
20 psi
(1,4 bar)
Hose
Allowance
250 GPM at
spacing 12 ft
(950 LPM at
spacing
3,7 m)
250 GPM at spacing 10 ft
(950 LPM at spacing 3,0 m)
500 GPM at
spacing >
12 to 14 ft
(1.900 LPM at
spacing
> 3,7 to 4,3 m)
N/A
Hydraulic
Requirement
Including
Hose
1525 GPM
spacing 12 ft
(5769 LPM
spacing
3,7 m)
1705 GPM at
spacing 10 ft
(6423 LPM at
spacing
3,0 m)
1676 GPM at
spacing 10 ft
(6338 LPM at
spacing
3,0 m)
1704 GPM at
spacing 10 ft
(6460 LPM at
spacing
3,0 m)
1840 GPM at
spacing 10 ft
(6899 LPM at
spacing
3,0 m)
1906 GPM at
spacing 10 ft
(7210 LPM at
spacing
3,0 m)
1602 GPM at
spacing 10 ft
(6061 LPM at
spacing
3,0 m)
1775 GPM at
spacing >
12 to 14 ft
(6719 LPM at
spacing
> 3,7 to 4,3 m)
N/A
Te Model EC-25 Sprinkler provides similar savings for Class 1 to 4 and Cartoned Unexpanded Plastic
Commodities in Solid-Piled, Palletized, Shelf, or Bin-Box storage arrangements.
For storage buildings, the average ceiling height is the range of 27 to 34 ft (8.2 to 10.4 m). Terefore, for most
buildings, the Model EC-25 Sprinkler provides a new level of performance that requires less water over a
larger coverage area with fewer branch lines, fewer sprinklers, and often lower pressures than ESFR sprinklers
in common use today.
Applications of the
TYCO Model EC-25 Storage Sprinkler
11
Summary
In summary, the TYCO Model EC-25 Storage Sprinkler provides lower installed cost and better re protec-
tion when compared to standard coverage sprinkler systems because of these key benets:
Better Fire Protection
In re tests that compared the Model EC-25 Extended Coverage Sprinkler with K-8.0 (115), K-11.2 (160),
and K-16.8 (240) standard coverage sprinklers, the Model EC-25 Sprinkler opened fewer sprinklers and
consumed fewer pallets.
Fewer Branch Lines
Te Model EC-25 Sprinkler provides signicant exibility in optimizing the number of branch lines in a
bay supporting distances from 8 ft (2,4 m) to 14 ft (4,3 m) with a coverage area up to 196 ft
2
(18,2 m
2
).
Spacing to the 15 ft (4,6 m) maximum is only allowed with a coverage area of 144 ft
2
(13,4 m
2
).
Fewer Sprinklers
Te same extended coverage that reduces the number of branch lines also reduces the number of sprin-
klers on the branch lines.
Lower Operating Pressures
Using the NPFA 13 S x L Spacing Rules, the Model EC-25 Sprinkler can cover smaller areas while oper-
ating at lower pressures, delivering 0.67 GPM/ft (27,2 mm/min) at 100 ft
2
(9,3 m
2
) spacing with an oper-
ating pressure of only 7 psi (0.48 bar).
Lowest Hydraulic System Demand
Te Model EC-25 Sprinkler provides a minimal water requirement, combined with extended coverage
spacing, for ceiling heights of 35 ft (10,5 m) or less as provided in NFPA 13 2013 Edition, Chapter
21 Alternative Sprinkler System Designs for Chapters 12 through 20 and FM Global Property Loss
Prevention Data Sheet 8-9, July 2011 Revision, and Engineering Notice 06-11.
To learn more about how you can use the TYCO Model EC-25 Sprinkler to reduce your installed system
costs and provide better re protection, contact your local Tyco Representative.
Applications of the
TYCO Model EC-25 Storage Sprinkler
12
About the Authors
James E. Golinveaux
Senior Fellow, Water Fire Suppression, Tyco Fire Protection Products
With 30 years of experience in the re protection industry including both contracting and manufacturing,
Mr. Golinveaux is currently Sr. Fellow of Water Suppression Products for Tyco Fire Protection Products. His
present role applies his experience globally in the re protection industry to develop advancements in water-
based re protection devices and systems. He sits on the Board of Trustees for the Fire Protection Research
Foundation, as well as multiple other Boards and Councils including the Factory Mutual Advisory, AFSA,
NFSA, International Fire Sprinkler Association, and the Fire Sprinkler Association of Brazil. He is also a
member of the NFPA 13, 88A, 101, and 5000 Technical Committees. He has consistently served as a subject
matter expert for the past two editions of the NFPA Fire Protection Handbook and the NFPA 13 Handbook.
Kevin Maughan
Manager of Technical Services, Water Fire Suppression, Tyco Fire Protection Products
Mr. Maughan has been deeply involved in the re protection industry for 29 years, with 13 years in the con-
tracting side of the business and the remainder of his career in the manufacturing and R & D side of the busi-
ness. Since 2004, he has served as Manager of Technical Services for Tyco Fire Protection Products. Currently,
Mr. Maughan serves as a Principle NFPA Committee Member for NFPA 14, NFPA 24, and NFPA 80A.
Je Barkley
Product Manager, Water Fire Suppression, Tyco Fire Protection Products
With over 20 years of product management and marketing experience in a variety of industries, Mr. Barkley is
Product Manager for the Water Storage product line at Tyco Fire Protection Products, located at the Cranston
Technology Center in Rhode Island. In this role, Mr. Barkley is involved with research, development, and
support of existing and new products to protect high piled storage facilities such as warehouses and distribu-
tion centers. Mr. Barkley has authored a number of technical papers in automatic test equipment, electronic
design automation, and re protection.
Applications of the
TYCO Model EC-25 Storage Sprinkler
13
WORLDWIDE HEADQUARTERS
Tyco Fire Protection Products
1400 Pennbrook Parkway
Lansdale, PA 19446
800-523-6512 / 215-362-0700
CRANSTON TECHNOLOGY CENTER
Tyco Fire Protection Products
1467 Elmwood Avenue
Cranston, RI 02910
Technical Services
800-381-9312 / 1-401-781-8220
www.tyco-re.com October 2011 www.tyco-re.com November 2012

You might also like