Protocol

Type
Setting of the 4-bit DIP Switch of the
SW_ADDR
GSM/CDM
A
0001
WCDMA 0010
0 ON
1 OFF
EMUA HUAWEI
ON
1 2 3 4
INSTALLATION OF EMUA
DC-PDU
Kabel monitor alarm di konek pada UPEU port MON1
Kabel monitor alarm di konek pada UPEU port MON1
Power utk EMUA dikonek pada port Spare pada DC-PDU
Sensor Alarm Box EMU
Number Position
7 Rectifier Failure S1 SW12A_1 disesuaikan 0
4 Heat Detector Active S2 SW12A_2 disesuaikan 1
6 Door Open S3 SW12A_3 disesuaikan 2
1 PLN Power Failure S4 SW12A_4 disesuaikan 3
5 Smoke Alarm S5 SW12A_5 disesuaikan 4
8 DC power too low S7 SW12A_7 disesuaikan 6
2 DC Fan active S8 SW12A_8 disesuaikan 7
Temperature & Humadity DEFAULT SWTHE 1 & 2 ON
Infrared DEFAULT SWBKE_3 OFF
Waterlog DEFAULT SWBKE_1 OFF
3 AC #1
9 AC #2
Smoke Alarm DEFAULT SWBKE_2 ON
Access Equipment DEFAULT SWBKE_4 ON
SW12A_6 disesuaikan
LSA Box
Port No.
EAC
S6
Type : EMUA
Extended Boolean
Port No. (BTS
Scripts)
Alarm Description Physical port
DIP Switch
script:
set cbtsenvswtextport:btsid=xxx,portid=0,opmode=def,alminfo="Rectifier Failure",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=1,opmode=def,alminfo="Heat Detector Active",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=2,opmode=def,alminfo="Door Open",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=3,opmode=def,alminfo="PLN Power Failure",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=4,opmode=def,alminfo="Smoke alarm",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=6,opmode=def,alminfo="DC Power Too Low",confirm=y;
set cbtsenvswtextport:btsid=xxx,portid=7,opmode=def,alminfo="DC FAN Active",confirm=y;



S4
S7
S8
S2
S5
S3
S1
S6
Water Log Sensor NC SW_BKE_1 OFF enable ON disable
Smoke Detect Alarm NC SW_BKE_2 ON enable
Infrared NC SW_BKE_3 OFF enable ON disable
Door Open NC SW_BKE_4 ON enable OFF disable
status DIP switch status Sensor Relay SW_BKE DIP switch
Water Log
dari kiri kekanan:
putih, hijau, merah, konek ke water sensor
Temperature & Humadity
T+ T- RH+ RH-
Infra Red
_
+ R
NC
TAMP
For Implementation Only used 4 Relays. There are :
Relay 1 : Power Failure / AC Mains
Relay 2 : High / Under Voltage
Relay 3 : Rectifier Failure / Rectifier module broken
Relay 4 : BLVD
Number Position
7 Rectifier Failure NC S 1 SW12 A1 up
8 DC Power Too Low NC S 7 SW12 A7 up
PS48180-1800-X6
LSA Box Port No 8
EAC Box
Port
DIP Switch
LSA Box
Port No.
Censors
Alarm Description
Relay
Position
2
3
3
2
2
3
Jumper
LSA Box Port 7