Orion Documentation page 2 Disclaimer
Disclaimer
CSC (UK) Ltd does not accept any liability whatsoever for loss or damage arising from any errors which
might be contained in the documentation, text or operation of the programs supplied.
It shall be the responsibility of the customer (and not CSC)
to check the documentation, text and operation of the programs supplied,
to ensure that the person operating the programs or supervising their operation is suitably qualified
and experienced,
to ensure that program operation is carried out in accordance with the user manuals,
at all times paying due regard to the specification and scope of the programs and to the CSC Software
Licence Agreement.
Proprietary Rights
CSC (UK) Ltd, hereinafter referred to as the OWNER, retains all proprietary rights with respect to this
program package, consisting of all handbooks, drills, programs recorded on CD and all related materials.
This program package has been provided pursuant to an agreement containing restrictions on its use.
This publication is also protected by copyright law. No part of this publication may be copied or
distributed, transmitted, transcribed, stored in a retrieval system, or translated into any human or
computer language, in any form or by any means, electronic, mechanical, magnetic, manual or
otherwise, or disclosed to third parties without the express written permission of the OWNER.
This confidentiality of the proprietary information and trade secrets of the OWNER shall be construed in
accordance with and enforced under the laws of the United Kingdom.
Orion documentation: Orion software:
CSC (UK) Ltd 2010 CSC (UK) Ltd 2010
All rights reserved. All rights reserved.
Trademarks
Orion is a trademark of CSC (UK) Ltd.
Fastrak is a trademark of CSC (UK) Ltd.
TEDDS is a registered trademark of CSC (UK) Ltd.
The CSC logo is a trademark of CSC (UK) Ltd.
Autodesk and Revit are registered trademarks or trademarks of Autodesk Inc. in the USA and/or other
countries.
Microsoft and Windows are either trademarks or registered trademarks of Microsoft Corporation in the
United States and/or other countries.
Acrobat Reader Copyright 1987-2010 Adobe Systems Incorporated. All rights reserved.
Adobe and Acrobat are trademarks of Adobe Systems Incorporated which may be
registered in certain jurisdictions.
All other trademarks acknowledged.
Table of Contents Orion Documentation page 3
Chapter 1 Overview . . . . . . . . . . . . . . . . 16
Introduction . . . . . . . . . . . . . . . 16
Modelling Analysis and Design Flowchart . . . . . . . . . . 16
Build the Model . . . . . . . . . . . . . . . 17
Derive Beam Loads . . . . . . . . . . . . . . 18
General Building Analysis . . . . . . . . . . . . . 18
Design and Detailing . . . . . . . . . . . . . . 18
Chapter 2 Modelling Techniques . . . . . . . . . . . . . 19
Introduction . . . . . . . . . . . . . . . 19
Modelling Inclined and Lowered Members . . . . . . . . . . 20
Sloping and Lowered Slabs . . . . . . . . . . . . 20
How To Drop Parts of a Slab Panel . . . . . . . . . . . . 21
Sloping and Lowered Beams . . . . . . . . . . . . 24
Sloping and Lowered Columns . . . . . . . . . . . . 25
Sloping and Lowered Walls . . . . . . . . . . . . 26
Working With Planes . . . . . . . . . . . . . 27
Modelling Curved Axes and Beams . . . . . . . . . . . 29
Curved Axes . . . . . . . . . . . . . . . 30
The Curved Axis Generator . . . . . . . . . . . . . 30
Curved Beams . . . . . . . . . . . . . . . 32
The Curved Beam Generator . . . . . . . . . . . . 32
How many segments to use? . . . . . . . . . . . . 33
Linking Angled Beams . . . . . . . . . . . . . 36
Columns and Walls Spanning More Than One Storey . . . . . . . . 40
Example Case Study . . . . . . . . . . . . . . 40
User Defined Supports . . . . . . . . . . . . . 42
What is a default support? . . . . . . . . . . . . . 42
When might a default support be inappropriate? . . . . . . . . . 43
Specifying a User Defined Support . . . . . . . . . . . 43
Applying a User Defined Support . . . . . . . . . . . 44
User Defined Supports - Trouble shooting . . . . . . . . . . 44
Stepped Foundation Levels . . . . . . . . . . . . . 45
Default Supports Method . . . . . . . . . . . . . 45
Single Storey Example of the Default Supports Method . . . . . . . . . 45
Two Storey Example of the Default Supports Method . . . . . . . . . 46
User Defined Supports Method . . . . . . . . . . . . 47
Example of the User Defined Supports Method . . . . . . . . . . 47
Beams with Varying Depth . . . . . . . . . . . . . 48
Example Case Study . . . . . . . . . . . . . . 48
Pinned Member Ends . . . . . . . . . . . . . . 50
To Pin a Single Column . . . . . . . . . . . . . 50
To Pin Multiple Columns . . . . . . . . . . . . . 50
To Remove the Hinges from the Columns . . . . . . . . . . 50
To Pin a Single Beam . . . . . . . . . . . . . 51
To Pin Multiple Beams . . . . . . . . . . . . . 51
To Remove the Hinges from the Beams . . . . . . . . . . 51
Chapter 3 Beam Loads and Load Decomposition Methods . . . . . . . 52
General . . . . . . . . . . . . . . . . 52
Modifying Beam Loads . . . . . . . . . . . . . 52
Beam Loads Dialog . . . . . . . . . . . . . . 53
How to Define a New Point Load . . . . . . . . . . . 54
How to Define a New Uniformly Distributed Load . . . . . . . . . 55
Orion Documentation page 4 Table of Contents
How to Define a New Partial Distributed Load . . . . . . . . . . 55
Using the Load Generator . . . . . . . . . . . . . 55
Using the vertex table . . . . . . . . . . . . . 57
How to Define a New Load on an Inclined Beam . . . . . . . . . 57
Switching between Yield Line and FE load Decomposition. . . . . . . . 59
What is Load Decomposition? . . . . . . . . . . . . 59
Why switch to an FE method? . . . . . . . . . . . . 59
Example of FE Method for Slab Load Decomposition . . . . . . . . 61
Why retain the traditional (yield line) method? . . . . . . . . . 66
Chapter 4 Analysis Methods . . . . . . . . . . . . . . 67
Introduction. . . . . . . . . . . . . . . . 67
Chapter 5 General Building Analysis . . . . . . . . . . . . . 69
Introduction. . . . . . . . . . . . . . . . 69
Structural Model . . . . . . . . . . . . . . . 69
Diaphragm Modelling. . . . . . . . . . . . . . 70
Slabs to define rigid diaphragms (Default Setting) . . . . . . . . . . 71
Single rigid diaphragm at each floor level . . . . . . . . . . . 72
No rigid diaphragm floor levels . . . . . . . . . . . . 73
Excluding Specific Slabs from Diaphragms . . . . . . . . . . . 73
Limitations - diaphragm modelling and inclined planes . . . . . . . . 74
Case Study 1 - single storey pitched frame . . . . . . . . . . . 75
Case Study 2 - storeys linked by inclined planes . . . . . . . . . . 78
Global Constraints . . . . . . . . . . . . . . 81
Pattern Loading. . . . . . . . . . . . . . . 81
Rigid Zones . . . . . . . . . . . . . . . 82
Rigid Zones None . . . . . . . . . . . . . . 84
Rigid Zones Reduced by 25% . . . . . . . . . . . . 85
Rigid Zones Max . . . . . . . . . . . . . . 86
Discussion . . . . . . . . . . . . . . . 87
Rigid Links . . . . . . . . . . . . . . . 88
Shear Walls and Core Wall Systems . . . . . . . . . . . 90
3D Effects . . . . . . . . . . . . . . . . 90
Continuous Beams . . . . . . . . . . . . . . 91
Effects of one Member on Another . . . . . . . . . . . . 93
Sway Effects . . . . . . . . . . . . . . . 95
Transfer Beams. . . . . . . . . . . . . . . 96
Stiffness adjustments . . . . . . . . . . . . . . 96
Flat Slab Construction. . . . . . . . . . . . . . 97
Transfer Levels . . . . . . . . . . . . . . . 97
Supports . . . . . . . . . . . . . . . . 97
Building Analysis Problems Reviewing/Understanding . . . . . . . . 99
What are Errors?. . . . . . . . . . . . . . . 99
What are Warnings? . . . . . . . . . . . . . . 99
Building Model Validity Checking Errors . . . . . . . . . . . 100
Beam Load Analysis Errors . . . . . . . . . . . . . 100
Building Analysis Errors and Warnings . . . . . . . . . . . 101
Overview of Axial Load Comparison Report . . . . . . . . . . 102
Table 1 . . . . . . . . . . . . . . . . 105
Table 2 . . . . . . . . . . . . . . . . 106
Comparisons between tables 1 and 2 . . . . . . . . . . . 110
Table 3 . . . . . . . . . . . . . . . . 110
Table 4 . . . . . . . . . . . . . . . . 111
Table of Contents Orion Documentation page 5
Chapter 6 Eigenvalue Analysis. . . . . . . . . . . . . . 115
Introduction . . . . . . . . . . . . . . . 115
Eigenvalue Analysis Parameters . . . . . . . . . . . . 115
Controlling the Storey Mass . . . . . . . . . . . . 115
Model Stiffness . . . . . . . . . . . . . . 117
Controlling the Number of Mode Shapes Required . . . . . . . . 117
Analysis . . . . . . . . . . . . . . . . 118
Graphical Results . . . . . . . . . . . . . . 118
Numerical Results . . . . . . . . . . . . . . 119
Exporting to S-Frame . . . . . . . . . . . . . . 120
Exporting to S-Frame Example . . . . . . . . . . . . 120
Correction of Self Weight in S-Frame (for Eigenvalue Analysis only) . . . . . . . 120
Chapter 7 Staged Construction Analysis . . . . . . . . . . . 121
Introduction . . . . . . . . . . . . . . . 121
Simple Example . . . . . . . . . . . . . . 121
Staged Construction Modelling and Analysis. . . . . . . . . . 123
Model Creation . . . . . . . . . . . . . . 123
Staged Loading Creation . . . . . . . . . . . . . 123
Stage Control . . . . . . . . . . . . . . . 125
Combining multiple floors into a single stage . . . . . . . . . . 126
Combining the entire structure into a single stage . . . . . . . . . 126
Setting the Duration of Each Stage . . . . . . . . . . . 127
Analysis Properties . . . . . . . . . . . . . . 127
Modulus of Elasticity. . . . . . . . . . . . . . 127
FE Merging . . . . . . . . . . . . . . . 128
Simulaneously designing for FE merged forces and the results of a completely unstaged analysis. . . . 129
Chapter 8 Analysis and Design using FE . . . . . . . . . . . 130
Introduction . . . . . . . . . . . . . . . 130
Model Generation Options . . . . . . . . . . . . . 130
Column / Shear Wall Model Type . . . . . . . . . . . 131
Beam Stiffness Multiplier . . . . . . . . . . . . . 132
Slab Stiffness Multiplier . . . . . . . . . . . . . 132
Column and Wall Stiffness Multipliers . . . . . . . . . . . 132
Cracking and Creep . . . . . . . . . . . . . . 132
Include Column Sections in FE Model . . . . . . . . . . . 132
Include Slab Plates in FE Model . . . . . . . . . . . . 133
Consider Beam Torsional Stiffness . . . . . . . . . . . 133
Include Upper Storey Column Loads . . . . . . . . . . . 135
Upper Storey Column Loads Table . . . . . . . . . . . 135
Floor Mesh and Analysis . . . . . . . . . . . . . 135
Batch FE Chasedown . . . . . . . . . . . . . 136
Meshing and Analysing your Model . . . . . . . . . . . 136
If Slab Plates are NOT included . . . . . . . . . . . . 136
If Slab Plates are included . . . . . . . . . . . . . 137
Validity Checking . . . . . . . . . . . . . . 138
Mesh Density . . . . . . . . . . . . . . . 139
Mesh Uniformity . . . . . . . . . . . . . . 140
Effect of Holes and Boundaries . . . . . . . . . . . . 142
Mesh Sensitivity . . . . . . . . . . . . . . 145
Reviewing Results Contours and Strips . . . . . . . . . . 145
Worked Example Beam and Slab Systems . . . . . . . . . . 146
Introduction . . . . . . . . . . . . . . . 146
Orion Documentation page 6 Table of Contents
FE Mesh Generation . . . . . . . . . . . . . . 147
Review of Contouring Options . . . . . . . . . . . . 149
Deflection Plots. . . . . . . . . . . . . . . 150
Mx and My Plots . . . . . . . . . . . . . . 150
M1 and M2 Plots . . . . . . . . . . . . . . 151
Plots Including Wood and Armer adjustments . . . . . . . . . . 151
Steel Reinforcing Requirement Contours . . . . . . . . . . . 154
Other Contouring Adjustment Options . . . . . . . . . . . 155
Slab Design . . . . . . . . . . . . . . . 156
Effects of Adjusting the Beam and Slab Stiffnesses . . . . . . . . . . 160
Effects of Wood and Armer Moment adjustments on a Regular Slab . . . . . . . 164
Reinforcement Design . . . . . . . . . . . . . . 165
Merging Beam Results . . . . . . . . . . . . . . 167
What does this option do? . . . . . . . . . . . . . 167
When might you use this option? . . . . . . . . . . . . 167
Example . . . . . . . . . . . . . . . . 168
Option 1 A Plateless Model . . . . . . . . . . . . 171
Checking the Beam Designs . . . . . . . . . . . . . 172
Solution 2 A Meshed Model . . . . . . . . . . . . 174
Checking the Beam Designs . . . . . . . . . . . . . 176
Merging Column Results . . . . . . . . . . . . . 177
What does this option do? . . . . . . . . . . . . . 177
When might you use this option? . . . . . . . . . . . . 177
Chapter 9 Building Sway and Differential Axial Deformation Effects . . . . . . 178
Introduction. . . . . . . . . . . . . . . . 178
Chapter 10 Wall Modelling Considerations . . . . . . . . . . . 179
Analytical Idealisations . . . . . . . . . . . . . . 179
Deflection . . . . . . . . . . . . . . . . 179
Cases where one wall option is Preferable . . . . . . . . . . 179
Option to Check Both Ways . . . . . . . . . . . . . 180
Wall Panel Design. . . . . . . . . . . . . . . 180
Forcing Walls to resist all lateral loads . . . . . . . . . . . 181
Adjust Model Stiffnesses . . . . . . . . . . . . . 181
Pin the Columns . . . . . . . . . . . . . . 182
Sway Effects Under Gravity Load . . . . . . . . . . . . 182
Fully Framed Structures . . . . . . . . . . . . . 182
Why does this sway happen? . . . . . . . . . . . . . 183
Structures Incorporating Flat Slab Areas . . . . . . . . . . . 185
Slab Loads Yield Line Decomposition . . . . . . . . . . . 185
Slab Loads FE Decomposition . . . . . . . . . . . . 187
Discussion . . . . . . . . . . . . . . . 188
Load Eccentricity . . . . . . . . . . . . . . 188
Construction and Creep Effects . . . . . . . . . . . . 189
Discrete Cores . . . . . . . . . . . . . . . 190
Results based on an FE Chase Down . . . . . . . . . . . 191
Closing Summary . . . . . . . . . . . . . . . 192
Chapter 11 Sway Deflection Verification . . . . . . . . . . . . 193
Introduction. . . . . . . . . . . . . . . . 193
Comparison of Orion's alternative wall modelling options. . . . . . . . 193
Compare analysis results using other software. . . . . . . . . . 194
Table of Contents Orion Documentation page 7
Chapter 12 Overview of Bracing and Sway Sensitivity . . . . . . . . . 196
Introduction . . . . . . . . . . . . . . . 196
Automatic Assessment of Sway Sensitivity . . . . . . . . . . 196
User Defined Bracing . . . . . . . . . . . . . 197
Classification Requirements of each code . . . . . . . . . . 198
BS8110 (similarly CP65 and HK-2004) . . . . . . . . . . . 198
. . . . . . . . . . . . . . . . . ACI 318-02199
EC2 . . . . . . . . . . . . . . . . 200
Implementation of EC2 Classification in Orion . . . . . . . . . 202
Setting the Braced/Bracing Members . . . . . . . . . . . 202
Assessment of Sway Sensitivity . . . . . . . . . . . . 202
Worked Example for a Sway Sensitive EC2 Structure . . . . . . . . 203
Model Analysis Properties . . . . . . . . . . . . . 204
ACI Classification (for comparison). . . . . . . . . . . . 204
EC2 Classification to Annex H . . . . . . . . . . . . 206
Application of Load Amplification Factors . . . . . . . . . . 208
Chapter 13 Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings . 209
Introduction . . . . . . . . . . . . . . . 209
Opening Discussion . . . . . . . . . . . . . . 210
Example 20 Storey Building . . . . . . . . . . . . . 212
Traditional Analysis Results . . . . . . . . . . . . . 213
Emulating the Traditional Approach in Orion . . . . . . . . . 215
Sub-Floor Analysis (FE Chasedown) . . . . . . . . . . . 216
Building Analysis, area factor adjustment methods . . . . . . . . 217
Why do the two models give such different answers? . . . . . . . . . 219
How do we eliminate this effect if we want to? . . . . . . . . . . 220
Increasing the column area factor . . . . . . . . . . . 221
What is a reasonable upper limit for the column area factor adjustment? . . . . . . 224
Detailed comparisons of the analysis results . . . . . . . . . . 224
Recommendation . . . . . . . . . . . . . . 226
Is it acceptable to simply emulate the traditional design result? . . . . . . 227
Ignoring differential axial displacements . . . . . . . . . . 227
Making allowances for differential axial displacements . . . . . . . . 227
What is a reasonable lower limit for the area factor adjustment? . . . . . . 228
What is the impact on the design when both upper and lower-bounds are taken into consideration? 228
Consider Case where AF = 2.7 is upper bound and AF = 1.5 is the lower bound: . . . . . 229
Consider Case where AF = 4.0 is upper bound and AF = 1.0 is the lower bound: . . . . . 229
Consider Case where FE Chasedown is upper bound and AF = 1.5 is the lower bound: . . . . 229
What is the impact on the design when Pattern Loading is Introduced? . . . . . 229
Conclusion on Design Impact . . . . . . . . . . . . 230
Overall Summary of Suggested Procedure . . . . . . . . . . 231
Closing Discussion . . . . . . . . . . . . . . 232
Typical Concerns . . . . . . . . . . . . . . 232
What answers are we trying to get? . . . . . . . . . . . 232
Fixed Values for Area Adjustment Factor . . . . . . . . . . 232
Side Effects on Lateral Load Analysis . . . . . . . . . . . 233
Will FE Chasedown also eliminate differential axial deformation? . . . . . . 233
Is this going to result in uncompetitive over design? . . . . . . . . 234
Could I avoid all this complication if Staged Construction Analysis were used? . . . . 234
DADE Analysis & Design Flowchart . . . . . . . . . . . 235
Chapter 14 Using Staged Construction Analysis to Emulate Traditional Design . . . 237
Introduction . . . . . . . . . . . . . . . 237
Orion Documentation page 8 Table of Contents
Worked Example: . . . . . . . . . . . . . . . 237
Previous Results (from FE Analysis and Unstaged Building Analysis) . . . . . . 238
Sub-Floor Analysis (FE Chasedown) . . . . . . . . . . . . 238
Building Analysis without Area Factor adjustment . . . . . . . . . . 238
Building Analysis with Area Factor adjustment . . . . . . . . . . 238
Staged Construction Analysis Result . . . . . . . . . . . 239
Does Staged Analysis eliminate DADE? . . . . . . . . . . . 240
Use of Staged Construction as the upper bound solution . . . . . . . . 242
Chapter 15 Design and Detailing. . . . . . . . . . . . . . 243
Introduction. . . . . . . . . . . . . . . . 243
Chapter 16 Slab Design . . . . . . . . . . . . . . . . 244
Overview . . . . . . . . . . . . . . . . 244
Slab Strip Errors Reviewing/Understanding . . . . . . . . . . 244
No. of Slabs and Beams along strip is not consistent! . . . . . . . . . 244
Creating Member (but nothing seems to happen) . . . . . . . . . 244
Chapter 17 Beam Design to BS8110 . . . . . . . . . . . . . 246
Introduction. . . . . . . . . . . . . . . . 246
Beam Design Settings . . . . . . . . . . . . . . 247
The BS8110 Beam Design Process . . . . . . . . . . . . 247
1. Check slenderness limits for lateral stability- Cl 3.4.1.6 . . . . . . . . 247
2. Rectangular or flanged - Cl 3.4.1.5 . . . . . . . . . . . 248
3. Analysis of Sections - Cl 3.4.4.1 . . . . . . . . . . . . 248
4. Design for Bending- Cl 3.4.4.4 and Cl 3.4.4.5 . . . . . . . . . . 248
5. Design for Shear- Cl 3.4.5 . . . . . . . . . . . . . 251
6. Deflection Checks- Cl 3.4.6 . . . . . . . . . . . . 253
Worked Example . . . . . . . . . . . . . . . 253
The Design Model . . . . . . . . . . . . . . 253
Beam Design Settings . . . . . . . . . . . . . . 254
Analysis Results . . . . . . . . . . . . . . . 255
Performing the Design . . . . . . . . . . . . . 256
Design for Bending - Cl 3.4.4.4 . . . . . . . . . . . . 256
Design for Shear - Cl 3.4.5 . . . . . . . . . . . . . 258
Deflection Checks- Cl 3.4.6 . . . . . . . . . . . . . 260
Output Calculations . . . . . . . . . . . . . . 261
Chapter 18 Beam Detailing . . . . . . . . . . . . . . . 262
Introduction. . . . . . . . . . . . . . . . 262
The Design and Detailing Process . . . . . . . . . . . . 262
Overview . . . . . . . . . . . . . . . . 262
The Design Tab . . . . . . . . . . . . . . . 263
The Parameters Tab . . . . . . . . . . . . . . 264
The Bar Selection Tab . . . . . . . . . . . . . . 264
The Curtailment Tab . . . . . . . . . . . . . . 265
The Detailing Tab . . . . . . . . . . . . . . 266
The Layers Tab . . . . . . . . . . . . . . . 266
Overview of Patterns . . . . . . . . . . . . . . 267
Pattern 1 The Splice Bar Method. . . . . . . . . . . . 267
Pattern 2 The Alternative Method . . . . . . . . . . . 269
Pattern 3 The Hanger Bar Method . . . . . . . . . . . 270
The Bent-Up Pattern Method . . . . . . . . . . . . 271
Overview of Beam Bar Spacing . . . . . . . . . . . . 272
Table of Contents Orion Documentation page 9
Minimum Top and Bottom Steel Spacing . . . . . . . . . . . 272
Maximum Tension Steel Spacing . . . . . . . . . . . . 272
Maximum Compression Steel Spacing . . . . . . . . . . . 272
Maximum Compression Steel Spacing - Cantilever beams . . . . . . . . 273
Maximum Bar Spacing for Crack Control (EC2 only) . . . . . . . . . 274
Detailed Example and Comparisons . . . . . . . . . . . 274
Overview . . . . . . . . . . . . . . . 274
Basic Setup . . . . . . . . . . . . . . . 275
Design Tab . . . . . . . . . . . . . . . 276
Parameters Tab . . . . . . . . . . . . . . 276
Bar Selection Tab . . . . . . . . . . . . . . 277
Curtailment Tab . . . . . . . . . . . . . . 278
Detailing Tab. . . . . . . . . . . . . . . 281
Initial Design and Drawing Creation . . . . . . . . . . . 286
Effects of Applying Preferences . . . . . . . . . . . . 288
Bar Spacing Maximisation . . . . . . . . . . . . . 289
Limiting the Bar Range . . . . . . . . . . . . . 290
Merging Bars . . . . . . . . . . . . . . . 292
Minimum Tension Lap . . . . . . . . . . . . . 293
Stop Using 2
nd
Support and Span Bars . . . . . . . . . . . 294
Extend and Merge End Bars . . . . . . . . . . . . 296
Extend Support Bars Symmetrically . . . . . . . . . . . 298
Standardise Link Size . . . . . . . . . . . . . 299
Uniform Links . . . . . . . . . . . . . . 302
Summary . . . . . . . . . . . . . . . . 303
Chapter 19 Column Design to BS8110 . . . . . . . . . . . . 305
Introduction . . . . . . . . . . . . . . . 305
The BS8110 Column Design Process . . . . . . . . . . . 306
1. Braced or unbraced - Cl 3.8.1.5 . . . . . . . . . . . 306
2. Calculate effective height- Cl 3.8.1.6 . . . . . . . . . . . 307
3. Check slenderness limits- Cl 3.8.1.7 & 3.8.1.8 . . . . . . . . . 307
4. Classify as short or slender- Cl 3.8.1.3 . . . . . . . . . . 307
5. If slender - calculate M_add- Cl 3.8.3.1 . . . . . . . . . . 307
6. Calculate minimum moments - Cl 3.8.2.4 . . . . . . . . . . 308
7a. If braced, calculate design moments about each axis - Cl 3.8.3.2 . . . . . . 308
7b. If unbraced, calculate design moments about each axis - Cl 3.8.3.7 . . . . . 308
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5 . . . . . . . 308
9. Member Design - Cl 3.8.4 . . . . . . . . . . . . 309
Worked Examples . . . . . . . . . . . . . . 310
The Design Model . . . . . . . . . . . . . . 310
Column Design Settings . . . . . . . . . . . . . 311
Braced Rectangular Column Example . . . . . . . . . . . 313
Performing the Design . . . . . . . . . . . . . 314
1. Braced or unbraced - Cl 3.8.1.5 . . . . . . . . . . . 314
2. Calculate effective height- Cl 3.8.1.6 . . . . . . . . . . . 315
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8 . . . . . . . . . 316
4. Classify as short or slender - Cl 3.8.1.3 . . . . . . . . . . 316
5. If slender - calculate Madd- Cl 3.8.3.1 . . . . . . . . . . 316
6. Calculate minimum moments - Cl 3.8.2.4 . . . . . . . . . . 318
7. Calculate design moments about each axis - Cl 3.8.3.2 . . . . . . . . 318
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5 . . . . . . . 319
9. Member Design - Cl 3.8.4 . . . . . . . . . . . . 320
Cross check of the above solution . . . . . . . . . . . 321
Bi-Axial Design Method Example . . . . . . . . . . . . 323
Braced Circular Column Example . . . . . . . . . . . . 325
Orion Documentation page 10 Table of Contents
1. Braced or unbraced - Cl 3.8.1.5 . . . . . . . . . . . . 326
2. Calculate effective height- Cl 3.8.1.6 . . . . . . . . . . . 326
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8 . . . . . . . . . 326
4. Classify as short or slender - Cl 3.8.1.3 . . . . . . . . . . . 327
5. If slender - calculate Madd- Cl 3.8.3.1 . . . . . . . . . . . 327
6. Calculate minimum moments - Cl 3.8.2.4 . . . . . . . . . . 327
7. Calculate design moments about each axis - Cl 3.8.3.2 . . . . . . . . 328
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5 . . . . . . . 328
9. Member Design - Cl 3.8.4 . . . . . . . . . . . . . 329
Unbraced Circular Column Example . . . . . . . . . . . 329
1. Braced or unbraced - Cl 3.8.1.5 . . . . . . . . . . . . 329
2. Calculate effective height- Cl 3.8.1.6 . . . . . . . . . . . 330
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8 . . . . . . . . . 330
4. Classify as short or slender - Cl 3.8.1.3 . . . . . . . . . . . 330
5. If slender - calculate Madd - Cl 3.8.3.1 . . . . . . . . . . . 330
6. Calculate minimum moments - Cl 3.8.2.4 . . . . . . . . . . 331
7. Calculate unbraced design moments about each axis - Cl 3.8.3.2 . . . . . . 332
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5 . . . . . . . 332
9. Member Design - Cl 3.8.4 . . . . . . . . . . . . . 332
Chapter 20 Wall Design and Detailing . . . . . . . . . . . . 337
Introduction. . . . . . . . . . . . . . . . 337
Conservatism in the design method . . . . . . . . . . . 337
Wall Design and Detailing Options . . . . . . . . . . . . 337
Design With End Zones . . . . . . . . . . . . . 337
Design Without End Zones . . . . . . . . . . . . . 339
Should I use End Zones? . . . . . . . . . . . . . 339
Plain Wall Design . . . . . . . . . . . . . . 340
Option to use Single Layer of Reinforcement . . . . . . . . . . 342
Design with Mesh Reinforcement . . . . . . . . . . . . 343
The "Revert to Loose Bar" Option . . . . . . . . . . . . 344
How the "Revert to Loose Bar" Option Works . . . . . . . . . . 344
Limitation of "Revert to Loose Bar" Option . . . . . . . . . . . 344
Column Steel Details View . . . . . . . . . . . . . 345
Mesh and Minimum Reinforcement Requirements . . . . . . . . . 345
Points to Consider . . . . . . . . . . . . . . 346
Which Mesh Type is Better? . . . . . . . . . . . . . 347
Overview of Possible Reinforcement Arrangements . . . . . . . . . 348
Design using Type A Mesh (not considering plain wall design option) . . . . . . 349
Design using Type A Mesh (considering plain wall design option) . . . . . . 350
Design using Type B Mesh (considering plain wall design option) . . . . . . 351
Limitation Copy/Paste Bars will not work . . . . . . . . . . 351
Chapter 21 Foundation Design . . . . . . . . . . . . . . 352
Introduction. . . . . . . . . . . . . . . . 352
Foundation Design Settings. . . . . . . . . . . . . 352
Foundation Depth . . . . . . . . . . . . . . 353
The Foundation Forces Table . . . . . . . . . . . . 354
Combining Columns and Walls for Shared Foundation Design . . . . . . . 355
To combine multiple columns and walls . . . . . . . . . . . 355
To ungroup columns and walls . . . . . . . . . . . . 355
Calculation of the Combined Footing Design Forces . . . . . . . . . 355
Creating a Typical Pad/Pile Footing for Multiple Foundations . . . . . . . 356
To create a typical footing . . . . . . . . . . . . . 356
Pad Footings . . . . . . . . . . . . . . . 357
Defining a Pad Footing . . . . . . . . . . . . . 357
Table of Contents Orion Documentation page 11
Pad Footing Details . . . . . . . . . . . . . . 358
Combined Pad Footings . . . . . . . . . . . . . 358
Pile Caps . . . . . . . . . . . . . . . . 359
Defining a Pile Cap . . . . . . . . . . . . . . 359
Basic Design Procedure . . . . . . . . . . . . . 361
Limitations . . . . . . . . . . . . . . . 361
Larger Pile Groups . . . . . . . . . . . . . . 362
Pile Cap Details . . . . . . . . . . . . . . 363
Combined Pile Caps . . . . . . . . . . . . . . 363
Strip Footings . . . . . . . . . . . . . . . 364
Defining a Strip Footing . . . . . . . . . . . . . 364
Strip Analysis Options . . . . . . . . . . . . . 368
Adjusting the Subgrade Coefficient . . . . . . . . . . . 368
Enveloping all Load Combinations. . . . . . . . . . . . 373
Strip Footing Design. . . . . . . . . . . . . . 374
Beam Design . . . . . . . . . . . . . . . 376
Creating Wide Strip Footings . . . . . . . . . . . . 378
Combined Strip Footings . . . . . . . . . . . . . 379
Defining a Combined Strip Footing . . . . . . . . . . . 379
Analysis and Design . . . . . . . . . . . . . . 379
Raft (or Mat) foundations . . . . . . . . . . . . . 379
Piled Rafts . . . . . . . . . . . . . . . . 380
Defining a Piled Raft . . . . . . . . . . . . . . 380
Piled Raft Design . . . . . . . . . . . . . . 381
Chapter 22 Solution Options for Inclined/Lowered Members . . . . . . . 383
Introduction . . . . . . . . . . . . . . . 383
Overview of Solution Options and Limitations . . . . . . . . . 384
Inclined Beam and Slab Loads . . . . . . . . . . . . 384
Building Analysis Worked Example . . . . . . . . . . . 385
Diaphragm Modelling . . . . . . . . . . . . . 385
Simplified Load Decomposition . . . . . . . . . . . . 387
Analysis . . . . . . . . . . . . . . . . 387
Load Comparison Check . . . . . . . . . . . . . 388
Switching to FE Beam Load Decomposition . . . . . . . . . . 389
Design and Detailing . . . . . . . . . . . . . 391
Inclined Beam Design . . . . . . . . . . . . . 391
Inclined Beam Detail Drawings and Quantities . . . . . . . . . . 391
Inclined Column Design . . . . . . . . . . . . . 392
Inclined Column Detail Drawings and Quantities. . . . . . . . . . 392
Tapered Wall Design. . . . . . . . . . . . . . 392
Tapered Wall Detail Drawings and Quantities . . . . . . . . . . 393
Design and Detailing of the Inclined Slabs . . . . . . . . . . 393
Tapered Wall Modelling . . . . . . . . . . . . . 393
General Limitations - Inclined/Lowered Members . . . . . . . . . 396
Load decomposition for lowered slabs. . . . . . . . . . . 396
FE Analysis Worked Example . . . . . . . . . . . . 401
Introduction . . . . . . . . . . . . . . . 401
Example Model . . . . . . . . . . . . . . 401
FE Chasedown Analysis . . . . . . . . . . . . . 401
FE Model Generation . . . . . . . . . . . . . 401
Load Comparison Check . . . . . . . . . . . . . 403
Member Design based on FE Analysis . . . . . . . . . . . 404
Limitations - FE Analysis of Inclined/Lowered Members . . . . . . . . 405
Limitations - Finite Element Analysis and Building Sway . . . . . . . . 405
S-Frame Comparison . . . . . . . . . . . . . 406
Orion Documentation page 12 Table of Contents
Typical Test Model Results . . . . . . . . . . . . . 407
. . . . . . . . . . . . . . . . . 408
. . . . . . . . . . . . . . . . . 408
Discussion . . . . . . . . . . . . . . . 409
Conclusions . . . . . . . . . . . . . . . 409
Chapter 23 Overview of Solution Options for Transfer Levels . . . . . . . 410
Introduction. . . . . . . . . . . . . . . . 410
Understanding the Problem and the Limitations . . . . . . . . . 410
Where Beams support Columns and Walls . . . . . . . . . . 411
Where Slabs support Columns and Walls . . . . . . . . . . 411
Key Limitation . . . . . . . . . . . . . . . 411
Chapter 24 Transfer Beams General Method . . . . . . . . . . . 413
Modelling and Analysis . . . . . . . . . . . . . . 413
Analysis Model Options . . . . . . . . . . . . . 413
Model Tab . . . . . . . . . . . . . . . 413
Stiffnesses Tab . . . . . . . . . . . . . . . 414
Settings Tab . . . . . . . . . . . . . . . 414
Analysis . . . . . . . . . . . . . . . . 415
Load Comparison Check . . . . . . . . . . . . . 416
Design and Detailing of the Transfer Beams . . . . . . . . . . 417
Discussion of Frame Analysis Results . . . . . . . . . . . 418
Gravity Loads (Mid-Pier Wall Modelling) . . . . . . . . . . . 418
Building Analysis Results . . . . . . . . . . . . . 419
Front Transfer Beam . . . . . . . . . . . . . . 420
Rear Transfer Beam . . . . . . . . . . . . . . 421
Frame Action . . . . . . . . . . . . . . . 422
Gravity Loads (FE Meshed Wall Modelling) . . . . . . . . . . 424
Building Analysis Results . . . . . . . . . . . . . 425
Front Transfer Beam . . . . . . . . . . . . . . 426
Rear Transfer Beam . . . . . . . . . . . . . . 427
Frame Action . . . . . . . . . . . . . . . 428
Limitations Transfer Walls . . . . . . . . . . . . . 429
Supporting Beam to carry all Wall Load . . . . . . . . . . . 430
No supporting Beam Wall to act as a Deep Beam . . . . . . . . . 431
Beam and Wall to Work Together . . . . . . . . . . . . 432
Limitations Walls Supported by more than 1 Beam . . . . . . . . 436
Analysis . . . . . . . . . . . . . . . . 437
Results based on Mid-Pier Wall Idealisation . . . . . . . . . . 438
Results based on Meshed Wall Idealisation . . . . . . . . . . 439
Alternative Modelling Option Split the wall . . . . . . . . . . 440
Mid-Pier Model . . . . . . . . . . . . . . . 441
Meshed Model . . . . . . . . . . . . . . . 442
Summary/Recommendations . . . . . . . . . . . . 443
Option 1 Do not split the wall . . . . . . . . . . . . 443
Option 2 Split the wall . . . . . . . . . . . . . 443
Chapter 25 Transfer Beams FE Method, Option 1 (Simplest) . . . . . . . 444
Modelling and Initial Analysis . . . . . . . . . . . . 444
The FE Analysis and Load Chase Down . . . . . . . . . . . 444
Axial Load Comparison . . . . . . . . . . . . . . 447
Merging Column Analysis Results . . . . . . . . . . . . 448
Table of Contents Orion Documentation page 13
Column Design . . . . . . . . . . . . . . 449
Merging Beam Analysis Results . . . . . . . . . . . . 451
Merging Options . . . . . . . . . . . . . . 451
Discussion of Merged Results . . . . . . . . . . . . 452
Front Transfer Beam. . . . . . . . . . . . . . 452
Beam Design . . . . . . . . . . . . . . . 454
FE Chase Down with Duplicate Floors . . . . . . . . . . . 456
Chapter 26 Transfer Beams FE Method, Option 2 . . . . . . . . . 458
Modelling and Initial Analysis . . . . . . . . . . . . 458
The FE Analysis and Load Chase Down . . . . . . . . . . . 459
Axial Load Comparison . . . . . . . . . . . . . 463
Merging Column Analysis Results . . . . . . . . . . . . 464
Merging Beam Analysis Results . . . . . . . . . . . . 465
Discussion of Merged Results . . . . . . . . . . . . 465
Front Transfer Beam. . . . . . . . . . . . . . 465
Beam Design . . . . . . . . . . . . . . . 466
Effect of adjusting Slab Stiffness Factor . . . . . . . . . . . 466
Chapter 27 Solution Option for Transfer Slabs . . . . . . . . . . 468
Modelling and Initial Analysis . . . . . . . . . . . . 468
Column and Wall Positioning . . . . . . . . . . . . 469
Slab Insertion . . . . . . . . . . . . . . . 470
Building Analysis . . . . . . . . . . . . . . 470
Alternative Modelling Option . . . . . . . . . . . . 473
Concluding Note on Modelling . . . . . . . . . . . . 474
The FE Analysis and Load Chase Down . . . . . . . . . . . 474
Axial Load Comparison . . . . . . . . . . . . . 480
Merging Column Analysis Results . . . . . . . . . . . . 481
Merging Beam Analysis Results . . . . . . . . . . . . 481
Chapter 28 Flat Slab Models . . . . . . . . . . . . . . 482
Introduction . . . . . . . . . . . . . . . 482
Scope of Flat Slab Design in Orion . . . . . . . . . . . 482
Braced Buildings . . . . . . . . . . . . . . 482
Un-Braced Buildings. . . . . . . . . . . . . . 482
Example of a more Irregular Model . . . . . . . . . . . 483
Overview . . . . . . . . . . . . . . . 483
Slab Analysis, Design and Detailing . . . . . . . . . . . 484
Meshing . . . . . . . . . . . . . . . 484
Deflection . . . . . . . . . . . . . . . 486
Bottom Steel Reinforcement Provision . . . . . . . . . . . 486
Top Steel Reinforcement Provision . . . . . . . . . . . . 490
Additional Notes on Bottom Steel Provision . . . . . . . . . . 496
Column Design . . . . . . . . . . . . . . 502
Chapter 29 Punching Shear Checks . . . . . . . . . . . . . 503
Introduction . . . . . . . . . . . . . . . 503
BS8110 Design Code Requirements . . . . . . . . . . . 503
The Design Procedure . . . . . . . . . . . . . 503
Check Maximum Shear Capacity. . . . . . . . . . . . 503
Check Shear on Series of Perimeters . . . . . . . . . . . 503
Simple Examples . . . . . . . . . . . . . . 504
Orion Documentation page 14 Table of Contents
Checking a Typical Internal Column . . . . . . . . . . . 505
Performing the Check . . . . . . . . . . . . . . 506
Checking Maximum Shear Capacity . . . . . . . . . . . . 506
Check Shear on a Series of Perimeters . . . . . . . . . . . 507
Providing Shear Reinforcement . . . . . . . . . . . . 509
Checking a Typical Edge Column . . . . . . . . . . . . 511
Checking a Typical Corner Column . . . . . . . . . . . 514
Column Drop Panels . . . . . . . . . . . . . . 515
Dealing with Openings . . . . . . . . . . . . . 518
Openings which have been modelled . . . . . . . . . . . 518
Calculation of the Effective Shear Force . . . . . . . . . . . 520
Allowing for Openings which have not been modelled . . . . . . . . . 521
Final Batch Check and Output . . . . . . . . . . . . 523
Concluding Notes . . . . . . . . . . . . . . . 524
Limitations . . . . . . . . . . . . . . . 524
Holes . . . . . . . . . . . . . . . . 525
Dimension x used at the face of the loaded area . . . . . . . . . . 526
Slab Merging . . . . . . . . . . . . . . . 527
Specification of Effective Slab Reinforcement . . . . . . . . . . 531
Providing the Shear Reinforcement . . . . . . . . . . . . 531
Punching Perimeters . . . . . . . . . . . . . . 531
Walls . . . . . . . . . . . . . . . . 532
Overlapping Perimeters . . . . . . . . . . . . . 532
Discontinuous Columns . . . . . . . . . . . . . 533
Advantages . . . . . . . . . . . . . . . 533
EC2 Design Code Requirements . . . . . . . . . . . . 533
The Design Procedure. . . . . . . . . . . . . . 533
Check Maximum Shear Capacity . . . . . . . . . . . . 533
Check Shear Capacity at the Basic Control Perimeter. . . . . . . . . 533
Calculate Shear Reinforcement Required and Length of Outer Control Perimeter . . . . 534
Calculation of Magnification Factor . . . . . . . . . . . 534
Internal column . . . . . . . . . . . . . . 534
Edge column . . . . . . . . . . . . . . . 535
Corner column . . . . . . . . . . . . . . . 535
Calculation of W
1
. . . . . . . . . . . . . . 536
Chapter 30 Slab Deflection Checks . . . . . . . . . . . . . 539
Introduction. . . . . . . . . . . . . . . . 539
Overview of Concrete Slab Deflection . . . . . . . . . . . 539
Instantaneous Deflection . . . . . . . . . . . . . 539
Creep Deflection . . . . . . . . . . . . . . 540
Shrinkage Deflection . . . . . . . . . . . . . . 540
Creep/Cracking Allowance Summary . . . . . . . . . . . 541
Slab Depth and Deflection Comparisons . . . . . . . . . . . 541
Standard Slab Details . . . . . . . . . . . . . . 541
Comparison of Span / Eff depth checks for grade C20/25 concrete. . . . . . . 542
Rigorous Deflection Calculations for grade C20/25 concrete. . . . . . . . 542
Comparison of Span / Eff depth checks for grade C35/45 concrete. . . . . . . 545
Rigorous Deflection Calculations for grade C35/45 concrete. . . . . . . . 546
Deflection Estimates using Linear FE Analysis . . . . . . . . . . 548
FE Analysis Results for C20/25. . . . . . . . . . . . . 549
FE Analysis Results for C35/45. . . . . . . . . . . . . 549
Overall Summary of Minimum Slab Depths . . . . . . . . . . 550
Summary . . . . . . . . . . . . . . . . 550
Table of Contents Orion Documentation page 15
Chapter 31 Linking and Merging Projects . . . . . . . . . . . 552
Introduction . . . . . . . . . . . . . . . 552
Creating a Foundation Project . . . . . . . . . . . . 554
Requirements for Models to be Linked for Foundation Design . . . . . . . . 554
Procedure for Linking Existing Models into a Foundation Project . . . . . . . 554
Linked Project Manager . . . . . . . . . . . . . 556
Chapter 32 Reports and Drawing Output . . . . . . . . . . . 557
Introduction . . . . . . . . . . . . . . . 557
Orion Reports . . . . . . . . . . . . . . . 557
Report Manager . . . . . . . . . . . . . . 559
Quantity Reports . . . . . . . . . . . . . . 559
Drawings . . . . . . . . . . . . . . . . 560
Examples . . . . . . . . . . . . . . . 561
Orion Documentation page 16 Chapter 1 : Overview
Chapter 1 Overview
Introduction
The aim of this handbook is to provide added background information together with hints,
tips, and examples all of which should help you to make the most of Orion. This manual is not
written at a Getting Started level, and it is recommended that you have worked through basic
training examples in order to become familiar with the system and terminologies used, before
addressing the more complex detail provided here.
Copies of the getting started and basic training manuals in pdf format are installed with Orion
and can be accessed by clicking on the links below.
Orion Quick Start guide.pdf
Orion Standard Training Manual.pdf
(If the links do not work please browse to find the file name indicated above in the HELP
sub-folder of the Orion Program Folder).
It is particularly noted that the Standard Training Manual covers many topics in sufficient
detail that no further mention is required in this document.
Modelling Analysis and Design Flowchart
If you write down the main headings for what you expect a Concrete Building Modeller to do
it will probably look pretty simple:
1. Provide a way to input/describe the model.
2. Analyse it.
3. Design it.
4. Produce Calculations.
5. Produce Drawings.
If you have worked through the training course notes you will know that Orion lets you do all
this. The following flow chart illustrates this basic sequence, but it also indicates options. The
existence of such options can sometimes lead to confusion which option should you choose?
In this chapter we will try to deal with each heading in a little more detail, indicate when you
might use the optional routes, and provide cross reference to other chapters with more detailed
information and/or worked examples.
Chapter 1 : Overview Orion Documentation page 17
Build the Model
As noted earlier, the primary source of help in this aspect of Orion usage is the Training
Manual. Ordinary regular models can be constructed with speed and ease.
Many chapters in this manual provide modelling information, hints and tips for more unusual
circumstances.
1.
Build the model
Orion modelling, analysis and design flowchart
Slab design based on tabulated code coefficients
2.
Derive beam loads using the Yield
Line (tributary area) approach
3.
Run the general building analysis to
generate column, wall and beam
design forces
2a - optional
Derive beam loads based on a special
FE model. Choose whether to use
these loads selectively or on all
beams
3b - optional
Use same FE models to generate and
merge alternative slab design forces
4.1
Beam design and
detailing
4.2
Column/Wall design
and detailing
4.3
Slab design and
detailing
3a - optional
Use sequential FE floor analyses to
chase gravity loads down through the
structure. Selectively merge/override
column wall and beam design forces
with those of the general building
analysis
Orion Documentation page 18 Chapter 1 : Overview
Derive Beam Loads
This might incorrectly be regarded as part of the building analysis, it is not, slab loads are
decomposed onto the supporting beams prior to building analysis. Examining the flowchart
indicates that you have options here and it is important to understand what these are and
when you might use them. The default load decomposition method is based on tributary
areas, and is commonly known as the Yield Line Method. This method has limitations in
circumstances such as:
1. When the slab boundaries are highly irregular
2. When there are significant holes defined in the slab
3. When there are eccentric concentrated point, patch, or line loads
The alternative FE Method will deal with these more extreme conditions. A more detailed
discussion and example is provided in the chapter Beam Loads and Load Decomposition
Methods.
General Building Analysis
A full 3D analysis model is derived from the physical information that you describe when
constructing the model. This may sound simple but in fact there are numerous potential
subtleties to consider here, items such as:
1. Does a full 3D analysis actually give the answers you expect?
2. How are diaphragms modelled?
3. How is pattern loading catered for?
4. How are walls modelled?
5. etc.
These and other related topics are considered in the chapters General Building Analysis ,
Wall Modelling Considerations and Overview of Differential Axial Deformation Effects in
3D Analysis of Buildings
It is worth noting here that the 3D analysis model of a complete building is primarily a frame
element model with an option to use FE meshing of shear/core walls. It does not include FE
meshed floor elements. Since flat slab (or flat plate) structures do not include beams the basic
3D building analysis will not deal with these structures. The chapter Flat Slab Models
describes the alternative solution provided for these circumstances.
Design and Detailing
Much of the element design theory is covered in the following chapters: Beam Design to
BS8110 , Column Design to BS8110 and Wall Design and Detailing .
As beam and slab systems become more irregular, you may wish to turn to the optional FE
analysis for the slab design, the chapter Analysis and Design using FE provides additional
information in this regard.
Chapter 2 : Modelling Techniques Orion Documentation page 19
Chapter 2 Modelling Techniques
Introduction
The Standard Training Manual covers many of the modelling techniques required for a
typical structure in sufficient detail that no further mention is required here. It can be accessed
by clicking on the following link: Orion Standard Training Manual.pdf
Note If the link does not work please browse to find the file name indicated above in
the HELP sub-folder of the Orion Program Folder.
More advanced modelling techniques may also on occasion be required. The following cases
are discussed in this chapter:
1. Modelling Inclined and Lowered Members By default columns and walls are vertical,
beams and slabs are horizontal, however it is possible to specify otherwise to cater for
inclined and lowered members.
2. Modelling Curved Axes and Beams - It is possible to generate axes on a curve to facilitate
the definition of curved slab edges and beams.
3. Linking Angled Beams - If beams connect at an angle the program will attempt to
automatically determine if they should be linked on the detail sheet. However if the
default arrangement is unsatisfactory you can choose to revise it.
4. Columns and Walls Spanning More Than One Storey Each column and wall only spans
one storey in the building unless explicitly specified otherwise. If the column/wall spans
more than one storey, the number of storeys should be defined using Len (Storey) field in
the member properties dialog. This ensures the correct length is used in the slenderness
calculations when the column/wall is designed.
5. User Defined Supports These can be employed to model supports which occur above
the common foundation level. They can also be used to model (linear elastic) ground
springs.
Note Currently user defined supports are only active in the Building Analysis model
and not in the FE Analysis model.
6. Stepped Foundation Levels Often buildings will be built on sloping sites, or they may
have to accommodate split basement levels. These situations are catered for within Orion
using either of two methods depending on the complexity of the modelling situation.
7. Beams with Varying Depth Generally, beams will have constant section properties
(width and depth) from the beginning of the member to the end, however there may be
occasions when you need to change the beam depth part way along the member.
8. Pinned Member Ends Columns and beams are by default fixed ended members,
however to alter the way forces are distributed the user can introduce pins at specific
locations within the model.
Orion Documentation page 20 Chapter 2 : Modelling Techniques
Modelling Inclined and Lowered Members
Although beams and slabs are by default analysed with their centre-lines assumed to be at a
common elevation, it is possible to raise or lower them out of the floor plane so that this is not
the case. Similarly, although by default each column and wall is created vertically and each
beam and slab is created horizontally, they can also be defined at other inclinations.
This section describes how to define inclined and lowered members - it is important that you
familiarise yourself with the associated limitations before you use them. For further details see
the chapter Solution Options for Inclined/Lowered Members
Note The features described in this section are for the purpose of defining occasional
sloping/lowered elements within a model which still contains distinct horizontal
floor planes. These features are NOT intended to facilitate the modelling of
structures with complex geometries in which the floor planes are not readily
apparent.
Note In some cases, using engineering judgement to make an allowance to the loading
(to cater for the expected effects of the sloped/lowered elements) may actually be
simpler than introducing the sloped/lowered elements themselves.
Sloping and Lowered Slabs
To create a sloping slab panel you must first define a Plane to align it to. (see Working With
Planes on page 27). Once the plane has been defined the slab can simply be moved into the
new plane.
A slab panel may be dropped using the Rel Level box in the Slab Properties dialog. Entering a
negative value in the Rel Level box will drop the current slab beneath the general slab level by
the amount specified.
Note that the slab design moments obtained (using either the moment coefficient strip
method or Finite Elements strip method) would not be any different for a dropped slab panel
in comparison to an identical panel which had not been dropped. This is because the level
difference would not be recognized in the analysis.
Chapter 2 : Modelling Techniques Orion Documentation page 21
However, because the slab strips would be cut differently in a dropped slab panel the
reinforcement curtailment would be improved, as described later in this section.
How To Drop Parts of a Slab Panel
The example case below illustrates a partial drop.
In order to drop a part of a slab panel, you need to insert dummy axes and dummy beams
surrounding the drop panel.
The original slab layout is shown in the figure below:.
In this case study we will define a partial drop with 2000 x 2000 dimensions at the upper right
corner of slab panel 1S1.
Step 1: Inserting Dummy Axes to Define the Borders of the Drop Panel
Select axis 2 and press the Axis Offset button to offset it by 2000 mm to left direction. Set the
new axis label as 1a. Then, select axis B and offset it by 2000 mm to below direction. Set the
new axis label as A1.
Orion Documentation page 22 Chapter 2 : Modelling Techniques
Set the new axes as Not To Plot, since we don't want to include these axes in the output
drawings.
It is always good practice to shorten the dummy axes wherever they are not used to decrease
the number of axis intersections.
Step 2: Inserting Dummy Beams Around the Drop Panel
Now we will insert dummy beams that surrounds the drop panel. Since we will drop the panel
by 200 mm and the thickness of the panel will be 150 mm, the dummy beams will have a depth
of 350 mm.
Before inserting the dummy beams, you have to delete the existing slab 1S1, otherwise Orion
will not let you insert overlapping members.
Chapter 2 : Modelling Techniques Orion Documentation page 23
Insert the beams 1B1A and 1B1B as shown in the figure below.
Step 3: Inserting Slab Panels
Now you are ready to insert the slab panels. You have previously erased the slab 1S1 so you will
need to re-insert it so that it excludes the area surrounded by the dummy beams.
Then, you can insert the drop panel 1S1a, with the Rel Level defined as -200 mm as shown
below. Additionally, if you are going to analyse the slabs using moment coefficients method,
you have to set the Slab Type to be 9 Four Edges Discontinuous
Orion Documentation page 24 Chapter 2 : Modelling Techniques
Step 4: Inserting Slab Strips
Definition of the slab strips passing through the dropped panel needs additional care.
The reinforcement of the dropped panel must be bent at the edges. Therefore, a strip must be
inserted spanning only the dropped panel 1S1a, with end-conditions defined as Bob both at
start and at end.
Similarly, the slab strip that is inserted along slab 1S1 between the axes A1 and B must also
have end-conditions defined as Bob both at start and at end.
Sloping and Lowered Beams
Beams can be set above or below the storey level, or they can be inclined by using the del z
boxes for each end of the beam in the Beam Properties dialog. Entering a negative value in the
del z box will drop the beam end beneath the general slab level by the amount specified.
If multiple members are to be edited it can be more efficient to first define a Plane to align
them to (see Working With Planes on page 27).
Chapter 2 : Modelling Techniques Orion Documentation page 25
Sloping and Lowered Columns
Column levels can be set above or below the storey level using the del z boxes in the Column
Properties dialog (3D tab). Entering a negative value in the del z box will drop the column end
beneath the general slab level by the amount specified.
Columns can be inclined by specifying, (from the Column Properties, (General tab), different
axis intersections for each end of the column.
Columns can be associated with Planes (see Working With Planes on page 27) in order to
raise or lower the column end relative to the storey level. Planes are not used to create inclined
columns.
Orion Documentation page 26 Chapter 2 : Modelling Techniques
Sloping and Lowered Walls
Wall levels can be set above or below the storey level for each end of the wall by using the del z
box in the Shear Wall Properties (3D tab). Entering a negative value in the del z box will drop
the wall end beneath the general slab level by the amount specified.
Walls can be inclined by specifying, (from the Properties - General tab) different axis
intersections for the top and bottom of the Wall as shown below.
Walls can be associated with Planes in order to raise or lower the wall ends relative to the
storey level. Planes are not used to create inclined walls.
Chapter 2 : Modelling Techniques Orion Documentation page 27
Working With Planes
Planes can be defined which may be offset from the storey level and which may also be
inclined. They are inserted in a similar way to slabs. Initially, as shown below, they are placed
horizontally at the storey level - the level and inclination being controlled by three node points
at the corners of the plane.
If the default node points identified are not suitable, one, or all can be reselected using the
appropriate Pick Point icon on the Plane Properties dialog. Once the required node points are
displayed, the Z elevation of each can be updated in order to change the level, or inclination of
the plane.
Having defined the plane and the members which are to be part of the plane, the next step is to
Move Members to the Plane Definition. This command can be accessed from the right click
Orion Documentation page 28 Chapter 2 : Modelling Techniques
menu, (or from the Planes branch of the Structure Tree).
As shown below, all members contained within, or at the edge of the plane are adjusted to the
plane.
Chapter 2 : Modelling Techniques Orion Documentation page 29
Modelling Curved Axes and Beams
It is possible to define beams and slabs that are curved in the floor plane. Curved beams by
definition have to be placed on a curved axis. This axis can either be created via a 'Curved Axis
Generator' or it can be generated automatically if the beam is formed using the 'Curved Beam
Generator'.
If you look closely at a curved beam you will see that it is actually formed from a series of
straight segments. You can specify how many segments to use when defining the beam.
Curved Beam formed from 6 segments
Curved Beam formed from 12 segments
Orion Documentation page 30 Chapter 2 : Modelling Techniques
Curved Axes
Curved axes are required for the definition of curved beams and curved slab edges. They are
formed from a number of linked straight axis segments which approximate to the curve
required. Provided the curve has a constant radius it should be created using the 'Curved Axis
Generator'. If you require a curve which doesn't have a constant radius you are restricted to
placing and then linking each axis segment manually.
The Curved Axis Generator
Straight axes are created by simply clicking and dragging between two points. To create a
curved axis, (or to generate multiple, or offset axes) you follow the same procedure, apart from
you must press and hold down the Shift key while dragging between the points. When you let
go of the mouse a dialog appears as shown below allowing you to define the degree of
curvature and apply offsets, or repeat spacings.
Offset Options
These options can be applied to both straight and curved axes. Instead of the axis passing
through the points clicked, it is drawn offset by the amount specified.
Curved axis insertion methods
Three methods exist for specifying the curve: Chord Offset; Centre Offset and Radius. The
number of straight segments forming the curve can also be controlled as can the decision to
draw the tangent segments external or internal to the curve. As you type in curve properties a
preview is displayed on screen.
Chapter 2 : Modelling Techniques Orion Documentation page 31
Insertion/Generation Options
These options can be applied to both straight and curved axes. Multiple axes can be created at
equal or varying spacings as required.
Preview with Axis Segments Drawn External
Preview with Axis Segments Drawn Internal
Orion Documentation page 32 Chapter 2 : Modelling Techniques
Curved Beams
Curved beams are composed of a number of linked straight beam segments approximating to
the curve required. They are defined using the 'Curved Beam Generator'.
The Curved Beam Generator
A straight beam is created by simply clicking and dragging between two points. A curved
beam can be created in the same way, apart from you must press and hold down the Shift key
while dragging between the points. When you let go of the mouse a dialog appears as shown
below allowing you to define the degree of curvature.
Offset Options
These options can be applied to both straight and curved beams. Instead of the beam passing
through the points clicked, it is drawn offset by the amount specified.
Curved beam insertion methods
Four methods exist for specifying the curve: Chord Offset; Centre Offset; Radius and 'Use
Existing Curved Axis'. The first three methods are the same as those used for defining curved
axes, the forth method only becomes active if both the start and end point clicked are linked
by an existing curved axis
Having specified the beam, a preview of how it will look is displayed on the plan view. Once
you are happy that it is positioned correctly, click OK to generate it.
Chapter 2 : Modelling Techniques Orion Documentation page 33
Insertion/Generation Options
These options can be applied to both straight and curved beams. Multiple beams can be
created at equal or varying spacings as required.
How many segments to use?
There is no definitive answer to this question for all cases - it will depend on the length of the
beam and the amount of curvature introduced. The default of six segments will often prove
sufficient, (we certainly wouldn't suggest using any less than six), but if you are in doubt you
can check for yourself by examining the effect on the analysis result of introducing more
segments.
Note By Increasing this number of segments a smoother curve is formed, however it also
increases the size of the analysis model (potentially taking longer to solve). This
more refined model may not significantly improve the accuracy of the result.
Example Case Study:
The model shown below is analysed with the curved beam initially modelled with 6, then 12
and finally 24 segments. The resulting moments and deflections are then compared.
Orion Documentation page 34 Chapter 2 : Modelling Techniques
Analysis Results for different numbers of Segments

Although from the above it can be seen that the deflections haven't converged on a stable
answer, the hogging and sagging moments remain fairly constant. If the six segment model
were adopted the beam would be designed for slightly higher moments than if a more refined
model were adopted.
Beam End Conditions
Hinges can be applied at either end of a curved beam by using the 'Update Beam End
Conditions' command accessed from the right click menu.
Six Segments
Twelve Segments
Twenty Four Segments
Model
Deflection
(mm)
Hogging
Moment (kN)
Sagging
Moment (kN)
6 Segments 68 47.3 -14.6
12 Segments 45 47.0 -13.6
24 Segments 40 46.9 -13.4
Chapter 2 : Modelling Techniques Orion Documentation page 35
Marking Cantilever Curved Beams
Free ends can be specified at either end of a curved beam by using the 'Mark Free End of
Cantilever Beam' command accessed from the right click menu.
Editing the Position of a Curved Beam
Currently this is not possible. If the beam is not in the correct location you will have to first
delete and then recreate it.
Editing Curved Beam Section Properties
Currently this is not possible. If the sectional properties of the beam are not correct you will
have to first delete and then recreate it.
Editing Curved Beam Member Loads
Beam Member Loads can be applied by using the 'Edit Member Loads' command accessed
from the right click menu. The dialog that is displayed only shows the loads applied on one
beam segment at a time. The forward and backward arrows can be used to move from one
segment to the next.

Note If you change data for one segment then this change is saved when you move to
another segment. If you press cancel you are only cancelling edits made to the
current segment, edits applied to previous segments are not cancelled.
Orion Documentation page 36 Chapter 2 : Modelling Techniques
Linking Angled Beams
When beam detail sheets are created, any beams which connect in a straight line are linked
automatically. In the special case of beams meeting at angled intersections, it may not be
immediately clear if they should be linked or not, particularly if multiple beams meet at the
same point.
The program will attempt to automatically determine the linking, however if the default
arrangement is unsatisfactory you can choose to revise it. This is achieved by manually linking
those axes on which you require the beams to appear as linked.
Consider the example shown below, none of the highlighted beams are co-linear but it would
make sense to link some of them on the detail sheet.
The the program chooses to automatically link the beams as follows:
Beams 1B3 and 1B4 are linked Beams 1B1 and 1B5 are linked Beam 1B2 is not linked
Chapter 2 : Modelling Techniques Orion Documentation page 37
Note The analysis is completely unaffected by the way the beams are linked together -
only the beam details are affected.
The resulting detail drawing is shown below:
Manually Linking the Intersecting Axes
It would make more sense to link beams 1B1 and 1B2 on the detail sheet and have 1B5 detailed
as a single span. This can be achieved by linking the intersecting axes A1 and A2 in the plan
view.
The axes are linked as follows:
Select the first axis to be linked (A1)
From the Right Click menu choose Link Intersecting Axes
Pick the axis to be linked to this axis (A2)
The two axes are immediately linked together
If you require, you can then continue to pick further intersecting axes to link to the end of
this one
Orion Documentation page 38 Chapter 2 : Modelling Techniques
Once the axes have been linked only the first axis label is displayed. The linked axes can now
be selected/unselected as a single entity.
If at any time you require to return the linked axes to their original unlinked state, this can be
achieved by choosing Separate Linked Axes from the Right Click menu.
After either linking or unlinking, although the analysis results are unaffected, a re-analysis is
still required. This is because the data has to be stored in a different way in preparation for
beam design and detailings. After re-analysis the affected beams should be re-designed.
Having linked axis A1 to A2 the beams are now linked as follows:
Beams 1B3 and 1B4 are linked Beams 1B1 and 1B2 are linked Beam 1B5 is not linked
Chapter 2 : Modelling Techniques Orion Documentation page 39
The revised detail drawing is shown below:
Note It is not always possible to link intersecting axes - for example a Dir 1 axis can
not be linked with a Dir 2 axis and vice-versa. In such cases it may be necessary to
detail the beams individually.
Orion Documentation page 40 Chapter 2 : Modelling Techniques
Columns and Walls Spanning More Than One Storey
Each column and wall only spans one storey in the building unless explicitly specified
otherwise. If the column/wall spans more than one storey, the number of storeys should be
defined using Len (Storey) field in the member properties dialog. This ensures the correct
length is used in the slenderness calculations when the column/wall is designed.
Example Case Study
In this example, some columns in the 5
th
storey span to the 3
rd
storey top level as shown below.
The clear height of these columns is twice that of other columns at the 5
th
and 4
th
storeys and
they will not be affected or restrained by any rigid diaphragm action that may exist at the 4
th

storey.
To define a column that spans two storeys
1. From the storey list go to the topmost storey that the column spans to, (in this example it is
St05).
2. In the Graphic Editor, select the column spanning more than 1 storey.
Chapter 2 : Modelling Techniques Orion Documentation page 41
3. Enter the number of storeys that the column spans in the Len (Storey) box. In this example
enter 2 as shown below.
4. Press the Update button to apply the modification to the selected column.
5. Select the floor below, and delete the column that is already covered by the column in the
upper storey. In this example select the 4P
th
P storey and delete the corner column as shown
below. Note that, if the column spans more than two storeys, this step must be repeated for
all the lower floors covered by that column.
Orion Documentation page 42 Chapter 2 : Modelling Techniques
User Defined Supports
These can be applied to the lower end of any column or wall at any level to introduce an
external support or spring. The translational (in global X, Y and Z) and rotational (about
global X, Y and Z) degrees of freedom can be set to fixed, or free, or a spring stiffness can be
assigned.
Unless you specify and apply user defined supports, every column and wall in your model
adopts a default support.
Note Currently user defined supports are only active in the Building Analysis model
and not in the FE Analysis model.
What is a default support?
The support provided by default is dependant upon the storey level at which the column or
wall stops.
For columns and walls that stop at ST00 (i.e. the foundation) Default = Fully Fixed
Support
For columns and walls that stop at ST01 and above Default = No External Support
In the simple model shown below, the grey shaded columns and walls are stopping at ST00,
hence they each have fully fixed supports.
Whereas, the columns and walls that stop at ST01, (again shaded in grey below) have by
default no external support. The loads within these columns will therefore be transferred
directly into the members in the lower storey.
Chapter 2 : Modelling Techniques Orion Documentation page 43
When might a default support be inappropriate?
In typical models you will often find that default supports are all that is needed. However,
certain situations might require you to specify and apply user defined supports.
Cases where user defined supports could be necessary include:
Buildings with sprung, or pinned
1
supports
Buildings with stepped foundations
Specifying a User Defined Support
If a fixed support is inappropriate, a pinned or spring support can be defined as follows:
1. Choose Support Type Definitions from the Members menu.
2. Click the Add New button and enter a label to describe the new support type.
3. To define a translational release in a particular direction uncheck the x, y or z support box
as appropriate.
4. To define a rotational release in about a particular axis uncheck the X-Rotation, Y-Rotation
or Z-Rotation support box as appropriate.
5. To define a translational spring in a particular direction enter the spring stiffness in the
appropriate x, y or z box, (having first unchecked the corresponding support box).
6. To define a rotational spring in a particular direction enter the spring stiffness in the
appropriate X-Rotation, Y-Rotation or Z-Rotation box, (having first unchecked the
corresponding support box).
7. Click OK to save the new support definition.
Footnotes
1. releasing the end of the member is a simpler technique for achieving a pinned connection to the support.
Orion Documentation page 44 Chapter 2 : Modelling Techniques
Applying a User Defined Support
Having defined a new support type as above, it can then be assigned to a specific column or
wall using the member properties dialog:
1. Select and load the properties for the column or wall.
2. Click on the 3D tab and choose the appropriate Support Type from the list.
3. Click on Update to save the change.
User Defined Supports - Trouble shooting
In models where you have applied user defined supports we would recommend that you
carefully review the analysis results to ensure they are working as you intended. Careless
application of supports could have unexpected effects.
Mechanisms
A mechanism may be introduced if, for example, you have applied a pinned support to a pin
ended member.
Diaphragm restraint
Typically, a rigid diaphragm exists within the floor slab. Hence, if a slab connects to the base of
a column which has a user defined support applied, the support will be directly restraining the
rigid diaphragm itself. This could inadvertently prevent lateral displacements from developing
at that level even if this was not the original intention.
Load Paths
User defined supports are assumed to transfer any reaction directly to the foundation. You
should not apply a user defined support at an upper storey level unless there is means for this
transfer to occur.
A stepped foundation is an example of where a user defined support would be appropriate,
whereas, a transfer column situation (i.e. where the column is supported by another member)
is an example of where it is not.
Chapter 2 : Modelling Techniques Orion Documentation page 45
Stepped Foundation Levels
The model shown below illustrates a stepped foundation level. In such models care is required
to ensure that the columns and walls are correctly supported. A fixed support is only
automatically placed underneath each column and wall that is physically connected to the
common foundation level (indicated by the grey plane ).
Depending on the model complexity, and the type of analysis carried out, one of two
modelling methods may be appropriate for achieving this, we shall referto these as:
Default Supports Method
User Defined Supports Method
Default Supports Method
All columns and walls that are supported on a foundation (irrespective of the foundation level)
are initially created so that their lower end connects to the general foundation level (St00). The
foundation level is then adjusted by raising or dropping the lower end of the columns and
walls relative to the St00 level as required.
Because the columns and walls connect to St00 they are all automatically provided with a
default support.
Note This approach can be used for models solved either by Building Analysis or FE
Chasedown Analysis.
Single Storey Example of the Default Supports Method
In the model below the step occurs below the lowest floor level (St01). All the columns and
walls are defined with Len (Storey) = 1. The only requirement is to vary the foundation level to
form the step. This is achieved by raising, or dropping, the base level of the appropriate
columns and walls .
Orion Documentation page 46 Chapter 2 : Modelling Techniques
Two Storey Example of the Default Supports Method
In the model below the step occurs above the lowest floor level (St01).
The columns to the right of the model must initally be defined with Len (Storey) = 2 so as to
enable them to connect to the foundation. (If this was not done they would be treated as
unsupported.) Their base levels are then raised to the appropriate level by applying a dZ-Bot
figure as described below.
To change the base level of selected columns and walls
1. In the plan view select the columns and walls to be changed.
2. Display the columns member table and change the dZ-Bot figure for all the selected
columns. A negative figure will lower the base level below the common foundation level
and a positive figure will raise it.
3. Repeat the above process for the walls changing both dZ-Bot, I and dZ-Bot,
Chapter 2 : Modelling Techniques Orion Documentation page 47
User Defined Supports Method
In this method it is not necessary for all the columns and walls to connect to the general
foundation level (St00). User defined supports are applied at the floor level at which the
foundation exists. The foundation level is then adjusted by raising or dropping the lower end
of the columns and walls relative to the current storey.
Note This approach can only be used for models solved by Building Analysis. FE
Chasedown Analysis does not currently recognise user defined supports.
Example of the User Defined Supports Method
In the example below, the columns to the right, which are defined spanning from ST02 down
to ST01 are to be supported on a raised foundation.
The exact level of the raised foundation is specified by applying a dZ-Bot figure to the columns
which is measured from the current storey level (in the same way as described in the Default
Supports Method).
Because these columns do not connect to St00, they are initially unsupported. Therefore user
defined supports will need to be manually defined and applied. For details of how to specify
these supports refer to the section- User Defined Supports
Note If the raised foundation level coincides exactly with an existing storey level, it
may be necessary to offset one from the other to avoid a user defined support
being applied within a floor diaphragm. This can result in an illegal constraint at
the joint in question.
Note User defined supports can be either pinned, fixed, or spring bases as required.
Orion Documentation page 48 Chapter 2 : Modelling Techniques
Beams with Varying Depth
Generally, beams will have the constant section properties (width and depth) from the
beginning of the member to the end, however there may be occasions when you need to
change the beam depth part way along the member.
You can define a second beam along the axis in order to change the section properties.
Naturally, you need to define a Non-frame dummy axis in order to create an axis intersection
at the particular location that the beam change section properties, to insert the second beam.
Note that this procedure is known as Splitting Beams and while it is possible, it will have
implications affecting the resulting beam detail. You will need to review and possibly edit the
automatically produced detail to ensure it is acceptable.
Example Case Study
In this example, there is a first floor beam shown below which has a varying depth. The beam
changes depth from 500 mm to 750 mm after 1500 mm from its left insertion point.
This is modelled using the following steps:
1. Before creating the beam, insert a grid line to cross the beam at the point where its depth
will change. You can do this by offsetting the axis (say Axis 1) at the I end of the beam a
distance 1500 mm. The name of the axis can be any dummy label (say 1x).
Changing the Depth of the Beam

2 beam with
section 250x750
nd
Non-frame axis to
create an intermediate
intersection
1 beam with
section 250x500
st
1B25 1B25A
250x750 250x750
Chapter 2 : Modelling Techniques Orion Documentation page 49
2. Stretch the end-points of the new axis 1x, so that it crosses only the grid line that the beam
will be defined (say A).
3. Remove the check in the View Codes option of this dummy grid line, so that it is defined to
be a ghost axis and check the Not to Plot option so that this axis will not be visible in any
printed output.
4. Instead of creating a single beam, insert two beams, 1B25 from axis 1 to axis 1x and 1B25A
from axis 1x to axis 2.

Non-frame axis to
create an intermediate
intersection
1500 mm
1 1x
1x
2
A

2 beam with
section 250x750
nd
Non-frame axis to
create an intermediate
intersection
1 beam with
section 250x500
st
1B25 1B25A
250x750 250x750
1x
1x
Orion Documentation page 50 Chapter 2 : Modelling Techniques
Pinned Member Ends
Columns and beams are by default fixed ended members, however to alter the way forces are
distributed the user can introduce pins at specific locations within the model
To Pin a Single Column
A column can be pinned at one or both ends, using the appropriate End-Condition button in
the Column Properties dialog.
The different conditions available are tabulated below:
To Pin Multiple Columns
Multiple columns can be pinned using the Update Column End Conditions option in the
shortcut menu accessed using the right mouse button after selecting one or more columns.
After choosing the desired end condition a button menu appears for filtering options.
Using this button menu, you can either apply the selected end condition to selected columns,
or all columns in the current storey, or all columns in the building.
To Remove the Hinges from the Columns
In order to remove the pin conditions of selected columns or all columns in the current storey
or all columns in the building you can use the No Hinges (Fix-Fix) option of the Update Column
End Conditions menu.
Fix-Fix (no hinges)
Pin-Pin (both ends pinned)
Fix top-Pin bottom (hinge at bottom end)
Pin top-Fix bottom (hinge at top end)
End Conditions Application Filter Options
Chapter 2 : Modelling Techniques Orion Documentation page 51
To Pin a Single Beam
A beam can be pinned at one or both ends, using the appropriate End-Condition button in the
Beam Properties dialog.
The different conditions available are shown below:
To Pin Multiple Beams
Multiple beams can be pinned using the Update Beam End Conditions option in the shortcut
menu accessed using the right mouse button after selecting one or more beams.
After choosing the desired end condition a button menu appears for filtering options.
Using this button menu, you can either apply the selected end condition to selected beams, or
all beams in the current storey, or all beams in the building.
To Remove the Hinges from the Beams
In order to remove the pin conditions of selected beams or all beams in the current storey or
all beams in the building you can use the No Hinges (Fix-Fix) option in the Update Beam End
Conditions menu.
Fix-Fix (no hinges)
Pin-Pin (both ends pinned)
Pin-Fix
Fix-Pin
End Conditions Application Filter Options
Orion Documentation page 52 Chapter 3 : Beam Loads and Load Decomposition Methods
Chapter 3 Beam Loads and Load Decomposition Methods
General
Orion calculates the beam loads automatically using the slab area loads, beam wall load
information and unit weight of the members. Calculated loads can be viewed and modified (if
necessary) using the Edit Member Loads function on the right mouse click menu. The
following distributed loads are calculated automatically:
Beam self weight as a uniformly distributed load (using the unit weight of concrete defined
in the Project Parameters menu and the geometry of the beam),
Dead and imposed (live) loads transferred from the adjacent slabs (as distributed function
loads calculated based on the self weight and area loads of the slabs),
User defined additional dead and imposed (live) loads (any additional loads that cannot be
determined automatically can be defined by the user),
User defined additional beam wall (dead) loads
Dead and imposed point loads transferred by supported secondary beams do not show up
when using Edit Member Loads and neither do point loads from supported columns and walls.
This is because these members are themselves part of the 3D analysis model. The loads they
transfer can only be seen in terms of steps in the shear force diagram. For more information
on supported columns and walls refer to the chapter Overview of Solution Options for
Transfer Levels.
Modifying Beam Loads
When you select a beam and use a right mouse click to access the shortcut menu, you can
select the Edit Member Loads option to view the beam vertical loads.
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 53
Beam Loads Dialog
The following buttons and fields are displayed on the Load Profile dialog.
Load Table
Each load in the Load Editor is represented as a row in the Load Table. A hand icon will appear
in the right-most column to mark any manually defined user loads (none shown above).
Typically, Uniformly Distributed Loads and Partial Distributed Loads may exist in this table.
The selected load will be highlighted in the accompanying drawing to the right of the Load
Table. You can only edit or delete manually defined user loads.
Edit Button
You can edit an existing manually defined user load in the Load Editor by clicking on this
button. Note that automatic loads will be loaded as Read-Only to this editor. You cannot make
any modifications to automatic loads.
Delete Button
You can delete an existing manually defined user load in the Load Editor by clicking on this
button. Note that automatic loads cannot be deleted.
New Load Button
You can define new manually defined user loads with the Load Editor by clicking on this
button. For example, if you want to define a new point load, click this button to display the
Load Editor, enter the Reference X, Dead Load and Imposed Load fields. Define the Load
Transfer Side and close the dialog by pressing the OK button.
Slab Load Calculation Method
This option allows you to swap between alternative methods for decomposing slab loads to
establish beam loads. A detailed discussion of this is provided in the section Switching
between Yield Line and FE load Decomposition later in this chapter.
Beam Load Editor
Orion Documentation page 54 Chapter 3 : Beam Loads and Load Decomposition Methods
OK Button
If you close the Beam Loads dialog by clicking the OK button after making any modifications,
all the changes will be saved.
Cancel Button
If you close the Beam Loads dialog by clicking the Cancel button after making any
modifications, the changes made on the beam will be discarded.
How to Define a New Point Load
You can do the following steps to define a new manual point load:
1. Press the New Load button to open the Load Editor.
2. Press the Point Load button at the top of the dialog to define a point load.
3. Press the From Above button in the Load Transfer Side group (default) at the bottom of the
dialog.
4. Optionally, enter a label for the load.
5. Enter the Reference X. This is the distance of the point load from the reference point of the
beam (which is the I-end).
6. Enter the load magnitudes into the Dead Load G and Imposed Load Q fields.
7. Press the OK button to insert the point load. Alternatively you can abort the process using
the Cancel button.
Load Profile Editor Dialog (Point Load)
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 55
How to Define a New Uniformly Distributed Load
You can do the following steps to define a new manual uniformly distributed load (UDL):
1. Press the New Load button to open the Load Editor.
2. Press the Uniformly Distributed Load button at the top of the dialog to define a uniformly
distributed load.
3. Press the From Above button in the Load Transfer Side group (default) at the bottom of the
dialog.
4. Optionally, enter a label for the load.
5. Enter the Dead Load G and Imposed Load Q details.
6. Press the OK button to insert the uniformly distributed load. Alternatively you can abort
the process using the Cancel button.
How to Define a New Partial Distributed Load
You can define a partial load either by using the Load Generator or by directly defining the
load points using the vertex table.
Using the Load Generator
1. Press the New Load button to open the Load Editor.
2. Press the Partial Distributed Load button at the top of the dialog to define a partial
distributed load.
3. Press the From Above button in the Load Transfer Side group (default) at the bottom of the
dialog.
Load Profile Editor Dialog (UDL)
Orion Documentation page 56 Chapter 3 : Beam Loads and Load Decomposition Methods
4. Optionally, enter a label for the load.
5. Press the Load Generator button to open the Loading Options dialog.
6. Select a load shape by pressing the appropriate button in the top portion of the dialog.
7. Enter the values for the parameters defining the geometry and magnitude of the load.
Here, x is the start distance to the load, and a, b, c are the widths of the load segments.
8. Enter the P values for load cases Dead Load G and Imposed Load Q.
9. Press the OK button to insert the partial distributed load. Alternatively you can abort the
process using the Cancel button.
Note The vertex table is filled with the details of the partial load you have defined.
Loading Options Dialog
Load Profile Editor Dialog (Partial Distributed Load)
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 57
Using the vertex table
Alternatively you can modify or directly define a new partial load by using the vertex table.
For example, to add a partial 2.5 m width UDL with magnitude G=6 kN and Q=3.5 kN,
starting from x=5 m you can use the following steps:
1. Select the 4P
th
P vertex in the table.
2. Press the Add Below button to append a new vertex to the end of the table.
3. Modify the x value to 5. 0.
4. Press the Add Below button again to append another vertex to the end of the table.
5. Modify the x value to 7. 5, the G value to 6. 0 and the Q value to 3. 5.
6. Press the Add Below button again to append another vertex to the end of the table.
7. Modify the x value to 5. 0, the G value to 6. 0 and the Q value to 3. 5.
8. Press the Add Below button again to append a closing vertex to the end of the table.
9. Modify the x value to 7. 5, the G value to 0 and the Q value to 0.
10. Close the dialog by pressing the OK button to insert the partial distributed load.
How to Define a New Load on an Inclined Beam
The following points should be noted:
Loads applied via the Load Editor are always applied vertically, even if the beam is inclined.
For UDL and VDL loads the magnitude of the load, P (in kN/m) should be entered as a
sloped load value.
Load Profile Editor with a 2.5 m partial UDL entered to the end
Orion Documentation page 58 Chapter 3 : Beam Loads and Load Decomposition Methods
The Load Editor requires all loads (including point loads) to be input using a horizontal
projected distance rather than a distance measured on the slope.
For example, a 5m long beam at a slope of 30 degrees would have a horizontal projected length
of 4m. A point load at mid span would therefore be defined with a Reference X, of 2m as shown
below.
The load is analysed correctly at the mid point of the sloped length - this can be confirmed by
displaying the loading diagram in the beam analysis results.
Sloped load input using horizontal projected distance along the member
Sloped load output using inclined distance along the member)
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 59
Switching between Yield Line and FE load Decomposition
What is Load Decomposition?
Slabs are not modelled as part of the general building analysis. To do this would require a fully
meshed up FE model at every floor level in a multi-storey 3D model. For realistic structures,
such models remain beyond the reasonable capacity of current computer hardware/
processors.
Therefore, when you define slabs and loads on slabs, Orion has to work out what loading
should be applied to the supporting beams. By default this is done in a traditional method
based on tributary areas.
The boundaries of the tributary areas loading each beam can be viewed graphically as shown
above. These look similar to potential Yield Lines, hence the name given to this default
method.
In this, as in many other areas, Orion effectively applies the sort of engineering methodology
that has been used in hand calculations for many years.
Why switch to an FE method?
This method has limitations in circumstances such as:
1. When the slab boundaries are highly irregular and particularly where some edges of a
complex boundary are unsupported.
2. When there are significant holes defined in the slab.
3. When there are eccentric concentrated point, patch, or line loads.
Orion Documentation page 60 Chapter 3 : Beam Loads and Load Decomposition Methods
In such circumstances beam loads are more accurately calculated by using a Finite Elements
Model.
Consider the simple 6 m by 4 m slab shown above. Eccentric concentrated point loads are
applied and a large void also has been defined.
The Traditional (Yield Line) method of load transfer would ignore the hole, and it would
average out the point load by calculating an equivalent UDL to apply over the whole area of
the slab. Although the load is not lost, its effect is independent of its proximity to any of the
surrounding beams. This is all reasonably apparent when you examine the beam loads.
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 61
The loading on beam 1B1 is a simple trapezoidal profile where the peak UDL is adjusted to
account for the point loads. Based on this method, beam 1B2 sees an identical loading profile.
When you run a building analysis, a completely symmetrical set of column loads is
determined as shown below.
Example of FE Method for Slab Load Decomposition
By using the optional Finite Elements Model, the point loads will be much more accurately
distributed. The slab load will also be more accurately distributed, including the deductions
and effects associated with the void.
The procedure for generating optional beam loads based on an FE model is as follows:
1. Select the Load Decomposition by FE command from the Run menu as shown below.
Orion Documentation page 62 Chapter 3 : Beam Loads and Load Decomposition Methods
2. Click on the button Determine Loads Transferred from Slabs, this will open up an FE
modelling window.
It is important to note the advice on mesh density that is given in the above dialog.
3. A plate size is suggested by default. Click the Generate Mesh icon and the slab is meshed
automatically.
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 63
In this case the suggested plate size results in 234 plates being generated, and although not
well meshed around the opening this is probably sufficient in this simple example for the
intended purpose.
4. Close this FE window and then also the Finite Element Analysis Form. This will result in the
following dialog being displayed.
5. The FE results can be applied to selected beams, all beams in the current storey, or to the
whole model. Choose Apply to All Beams in the Model.
You are then returned to the Graphic Editor.
Having completed the above process, FE information exists and has been applied to all beams
in the model. You can review this on a beam-by-beam basis. Select any beam and open the
beam loads dialog, it will have swapped to the Finite Elements Slab Load Decomposition
Method. The new loading for beam 1B1 is shown below.
As expected the load intensity is peaking towards the ends where the point loads are applied.
Orion Documentation page 64 Chapter 3 : Beam Loads and Load Decomposition Methods
To utilise these new loadings it is necessary to reperform the building analysis. On completion
we can see a very different distribution of column loads.
The total IL using the Yield Line method was approximately 267.6 kN. Using the FE method it
has dropped to 265.5 kN, this is slightly lower because no load is applied to the hole.
Note If you change any slab loads or beam layouts, you must remember to reperform
the Load Decomposition by FE command before reperforming the building
analysis.
Chapter 3 : Beam Loads and Load Decomposition Methods Orion Documentation page 65
Note Axial load comparisons are performed at the end of each analysis. This is a
comparison of applied loads vs. analysis reactions. Since you can choose
decomposition methods on a beam-by-beam basis you can cause this comparison
to show discrepancies. In the example above, if you choose finite element
decomposition for beam 1B1 only, the comparison will be displayed as shown
below.
The first applied loads table shows the totals for the loads applied to each slab, beam, etc. The
second applied loads table shows the loading totals after decomposition. Since the
decomposition methods have been mixed so that a worst case is used for every beam, the total
loading after decomposition is higher. You can then see that this higher loading is maintained
in the building analysis.
Orion Documentation page 66 Chapter 3 : Beam Loads and Load Decomposition Methods
Why retain the traditional (yield line) method?
Having reviewed the example above this is a question you might ask. The main point to bear
in mind is that the example is unusual/extreme. Concentrated loads and dominant openings
are not the norm.
The main disadvantage of the FE method is speed. When there are a large number of slabs,
there are a correspondingly large number of plates required and the analytical models (even
though it is one floor at a time) get big and hence slow.
Comparisons of uniformly loaded slabs have shown excellent correlation between the
traditional (yield line) and FE methods, so you may find it easier to continue using the
traditional method for much of your work.
If you think about the differences the FE method makes, you will be able to decide when it
might be more appropriate - clearly the FE method is better if you have to deal with significant
holes and/or isolated loading.
Ultimately, neither method is going to suit everybody all of the time. For this reason you can
pick and choose on a beam by beam basis if you wish, or you can design all the beams using
one method and then check them using the other. When checking you can use the option to
select new steel when previous bars are insufficient so that you end up with all beams designed
for the worst case from either load decomposition method.
Note In the FE method beams are replaced by a line of fully fixed supports. As a
consequence, in ordinary regular slabs both the yield line and FE method will
share loads equally to internal and edge beams. In other words continuity is not
being considered. This is a simplification that has long been accepted in hand
calculations.
A more extreme example of the above would be a cantilever slab. The beam
adjacent to the cantilever takes the entire cantilever slab load, plus half of the
internal slab load, for long cantilevers that can be a significant under estimate.
The only way to account for continuity in such a case would be to run an FE
chasedown analysis and then merge the resulting beam loads. This method deals
with the continuity, a higher load is put on the beam adjacent to the cantilever
and correspondingly less load is put on the next internal beam - some engineers
may prefer this. For details of how to perform an FE chasedown analysis refer to
the chapter "Overview of Analysis and Design Using FE".
Chapter 4 : Analysis Methods Orion Documentation page 67
Chapter 4 Analysis Methods
Introduction
Having constructed and loaded your model, an analysis will be required before member
design
1
can commence. The analysis method(s) used will depend on a number of factors; for
certain structures (eg flat slabs) two or more analyses may be required.
A brief summary of the analysis methods available within Orion is given below, these are then
discussed in more detail in the next four chapters:
General Building Analysis
A full 3D analysis is performed for all load cases and combinations, (vertical and lateral). The
analysis model consists primarily of frame elements with an option to use FE meshing of
shear/core walls. It does not include FE meshed floor elements.
General Building Analysis can be used to determine:
Frame deflections/sway sensitivity
Beam design forces (from both vertical and lateral combinations)
Column and wall design forces (from both vertical and lateral combinations)
Foundation forces (from both vertical and lateral combinations)
In flat slab structures - the beam, column and wall design forces from lateral
combinations.
A full description of this method is provided in the chapter General Building Analysis.
Eigenvalue Analysis
An Eigenvalue Analysis can (optionally) be performed as part of General Building Analysis to
determine natural frequencies and mode shapes.
A full description of this method is provided in the chapter Eigenvalue Analysis.
Staged Construction Analysis
This is a sophisticated method of solution which takes account of time dependant effects. It is
used in place of general building analysis where it is felt necessary to model the time
dependant properties of concrete.
Staged Construction Analysis can be used to determine:
Frame deflections/sway sensitivity
Beam design forces (from both vertical and lateral combinations)
Column and Wall design forces (from both vertical and lateral combinations)
Foundation Forces (from both vertical and lateral combinations)
In flat slab structures - the beam, column and wall design forces from lateral
combinations.
A full description of this method is provided in the chapter Staged Construction Analysis.
Footnotes
1. the exception being slabs, which can be designed directly using tabulated code coefficients, where applicable.
Orion Documentation page 68 Chapter 4 : Analysis Methods
Finite Element Floor Analysis
Analysis is performed for vertical load cases and combinations on a single floor at a time
extracted from the 3D building. In the analysis model, slabs are represented by horizontal FE
meshed floor elements and beams by horizontal frame elements. Supporting columns and
walls are also modelled (optionally) as frame elements as are the columns and walls
connecting with the slab from floors above.
Sequential FE floor analyses can be performed to chase gravity loads down through the
structure. The resulting column, wall and beam forces can be merged with those of the
General Building Analysis.
FE floor analysis is required for the solution of flat slab (or flat plate) structures.
Finite Element Floor Analysis can be used to determine:
Floor deflections
Slab design forces
Beam design forces (for vertical combinations)
Column and wall design forces (for vertical combinations)
Foundation forces (for vertical combinations)
A full description of this method is provided in the chapter Analysis and Design using FE.
Chapter 5 : General Building Analysis Orion Documentation page 69
Chapter 5 General Building Analysis
Introduction
This chapter is split into two sections:
The Structural Model section below describes various modelling considerations and
analysis options that have a significant impact on the building analysis result.
The Building Analysis Problems Reviewing/Understanding section discusses the error
and warning messages you might encounter when running a building analysis. It also
describes how you can perform a model validity check and how you can further cross
check the analysis result using the Axial Load Comparison Report.
Structural Model
A full 3D analysis model is derived from the physical information that you describe when
constructing the model. This may sound like a relatively simple and comprehensive solution
to the analytical modelling of any structure but in fact there are numerous difficulties, options,
and even personal preferences to consider here. The following list introduces most of these
items which are then discussed in more detail in the remainder of this section:
1. Diaphragm Modelling The analysis model is a 3D frame (stick) model, slabs are only
modelled in the sense that their diaphragm action is accounted for. What are the options
relating to how/when diaphragms are included? How are inclined planes handled?
2. Global Constraints What are they and when might you use them?
3. Pattern Loading How is pattern loading catered for?
4. Rigid Zones What are they and why would you use them?
5. Rigid Links What are they?
6. Shear Walls and Core Wall Systems How are walls modelled?
7. 3D Effects A full 3D analysis will sometime give answers that you do not expect, is it
wrong?
8. Stiffness adjustments What options are available and when might you use them?
9. Flat Slab Construction Dealing with structures that incorporate some degree of flat slab
(flat plate) construction.
10. Transfer Levels Dealing with beams and slabs that support discontinuous columns or
walls.
11. Supports Default supports and how to create new support types.
Orion Documentation page 70 Chapter 5 : General Building Analysis
Diaphragm Modelling
In a typical building lateral resistance is provide at a few discrete points and it is assumed that
applied lateral loads will be distributed to the lateral load resisting systems via floor diaphragm
action. Within Orion diaphragm modelling is achieved using diaphragm constraints.
A diaphragm constraint will maintain exact relative positioning of all nodes that it constrains,
i.e. the distance between any two nodes constrained by a diaphragm will never change,
therefore no axial load will develop in any member that lies in the plane of a diaphragm
between any two constrained nodes.
When running the building analysis the model options tab gives options as shown below.
For the diaphragm modelling there are 3 options:
Slabs to define rigid diaphragms (Default Setting),
Single rigid diaphragm at each floor level,
No rigid diaphragm floor levels.
Chapter 5 : General Building Analysis Orion Documentation page 71
The differences between these options can be demonstrated with the simple model below.
A single floor level has 2 separated slab areas that are linked by 2 beams.
Within the main graphics window Orion will always indicate a single overall centre of mass for
the entire floor level as shown below.
It is important to note that in the case of discrete diaphragms, or when there is no diaphragm
at all, this overall central location is provided for information only.
Slabs to define rigid diaphragms (Default Setting)
If the building is analysed with this setting then Orion will find any discrete areas of
interconnecting slabs and set up discrete diaphragms as appropriate. Separate notional loads
are calculated and applied to each diaphragm area. These applied notional loads and the
Orion Documentation page 72 Chapter 5 : General Building Analysis
resulting sways can all be examined in the model and analysis results display. Perhaps the
easiest way to see that 2 discrete diaphragms have been created is to look at an exaggerated
view of deflections.
For each of the two diaphragm areas a separate centre of mass location is determined and the
notional load is applied at that position. The view above shows the values for the Fy case in
this example. Note that the mass of the walls increases the applied notional load in the left
hand diaphragm area. Clearly the right hand area is moving independently to the left hand
area which is better restrained by the walls as opposed to frame action.
Single rigid diaphragm at each floor level
If the building is analysed with this setting then Orion will find apply a single diaphragm
constraint to every node at any given level. The existence of slabs is completely ignored/
irrelevant. A single notional load is calculated and applied at the overall centre of mass as
shown below. Once again the easiest way to see the effect of this setting is to look at an
exaggerated view of deflections.
This time we can see the entire level translating and rotating as a unit, since the centre of mass
and hence the applied notional load is very eccentric to the core walls, the dominant effect in
this example is one of rotation.
Chapter 5 : General Building Analysis Orion Documentation page 73
No rigid diaphragm floor levels
If you have defined slabs but for some reason you do not wish a diaphragm effect to be
considered you can completely eliminate diaphragm constraints using this option. In this case
notional loads are applied separately at every node in the floor level, these applied notional
loads and the resulting sways can all be examined in the model and analysis results display.
Once again the easiest way to see the effect of this setting is to look at an exaggerated view of
deflections.
The frame that is restrained by the wall hardly moves at all, other frames move to differing
degrees. Note that the frames which do not include walls have the same stiffness and so the
differing deflections relate to differing notional loads.
Excluding Specific Slabs from Diaphragms
In the example above there was no slab defined in the area linking region between grids 4 and
5. What if there was a slab in this area as shown below?
If the linking slab was substantial you might consider that it maintains the diaphragm action
between the two areas. However, as the link becomes more slender then at some point you
will decide it cannot maintain diaphragm action between the two areas. In this case you can
edit the properties of the slab and exclude it from diaphragm as shown above. In this case you
Orion Documentation page 74 Chapter 5 : General Building Analysis
can still use the default option Slabs to Define Rigid Diaphragms and the resulting deflections
will be the same (ignoring small change due to additional notional load from the added slab)
as were shown above for that option.
Limitations - diaphragm modelling and inclined planes
Inclined diaphragms can be created and are catered for correctly. It is also possible to have
multiple differently inclined diaphragms as long as they do not interconnect. However, it is not
possible to cater for differently inclined and interconnected diaphragms. In such a situation a
single diaphragm constraint is formed that constrains all nodes within it equally. This
situation will trigger warnings during analysis as the results can be adversely affected.
Note If a warning appears during analysis, indicating that nodes constrained by a
diaphragm do not lie in the same plane, it should not be ignored. You should
review the diaphragm model and consider excluding any inclined slabs from it,
this will often rectify the problem.
Chapter 5 : General Building Analysis Orion Documentation page 75
Case Study 1 - single storey pitched frame
If either the Slabs to Define Rigid Diaphragm or Single Rigid Diaphragm at Each Floor Level
option is used a warning message is displayed during the analysis indicating that the nodes
constrained by the diaphragm do not all lie in the same plane.
A single diaphragm is created within the pitched roof as shown below.
Orion Documentation page 76 Chapter 5 : General Building Analysis
On first viewing the above may not appear unreasonable, however, because the rigid arms that
constrain all the nodes to move together are not co-planar there are incorrect side effects as
demonstrated by the bending moment diagram below.
The diaphragm is holding up the mid-span node on the raking beams causing an unexpected
hogging moment at that point. In addition, axial loads develop in the inclined beams (below)
which would not happen if they existed in a properly inclined diaphragm.
Chapter 5 : General Building Analysis Orion Documentation page 77
Considering a sway case (below), it seems that the diaphragm is constraining displacements in
the horizontal plane only.
The degree to which the results are affected is related to the pitch of the inclined beams. As the
pitch reduces the effect drops, however it should be noted that it is still significant even at
relatively low pitches.
A workaround in this example would be to re-run the analysis using the option No Rigid
Diaphragm Floor Levels. The resulting bending moment diagram is then as shown below.
Orion Documentation page 78 Chapter 5 : General Building Analysis
Alternatively, exclude one of the slabs meeting at the apex (as described in the second case
study below) so that there are two differently inclined but separate diaphragms. (You should
find results are very similar to those obtained using the first workaround.)
Case Study 2 - storeys linked by inclined planes
In this example inclined planes have been used to define ramps between the storey levels.
If either the Slabs to Define Rigid Diaphragm or Single Rigid Diaphragm at Each Floor Level
option is used a warning message is displayed during the analysis indicating that the nodes
constrained by a diaphragm do not all lie in the same plane.
Because the storeys are linked, a single diaphragm has been created constraining all the floor
nodes as shown below.
Chapter 5 : General Building Analysis Orion Documentation page 79
When a lateral load is applied, each floor moves by the same amount - obviously the model is
not behaving as intended.
Diaphragm action is required to help resist the lateral loads, so specifying No Rigid Diaphragm
Floor Levels is not an acceptable solution. The answer is to restrict diaphragm action to the
horizontal floor planes only. This is achieved by excluding the inclined slabs from the
diaphragm as shown below.
Orion Documentation page 80 Chapter 5 : General Building Analysis
Because the storeys are no longer linked, separate diaphragms are formed at each floor level as
shown below.
By viewing the deflections under lateral load it can be seen that each floor is now moving
independently of the other floors as intended.
Chapter 5 : General Building Analysis Orion Documentation page 81
Global Constraints
You can use the options in the building analysis dialog shown above to apply general
constraints to the floor translation/rotation:
X/Y and Torsion Permitted,
X/Y Permitted, Torsion Prevented,
Only X Permitted,
Only Y Permitted,
The default setting is X/Y (translation) and Torsion Permitted and it allows full/free
movement of the floor. This means that the lateral load resisting systems you define will be
required to stabilise the building. For the vast majority of buildings this is an appropriate
choice.
It is also possible to model a 2D frame in Orion, in such a case the permitted movement might
be restricted to the in-plane direction, Only X, or Only Y as appropriate.
Pattern Loading
Designs codes generally require that pattern loading is considered in the analysis/design of
continuous beams. Orion has a method of automatically patterning both dead and imposed
loads along continuous beam lines. This subject is discussed in some detail in the Standard
Training Manual.
Orion Documentation page 82 Chapter 5 : General Building Analysis
Rigid Zones
Rigid zones deal with two aspects of the analysis and design of concrete frames:
1. Design codes generally allow you to design for forces at the face of a support.
2. From an analytical modelling point of view it is commonly accepted that a simple
centre-line model does not properly idealise the physical size of members. By modelling
rigid zones we account for the extra stiffness that exist within the 3D block where the
members physically interact with one another.
The chapter dealing with Wall Modelling Considerations shows examples that take this
second point to a more extreme level. Beams attach to the ends of walls (not the centre lines)
and we are happy to models walls and beams in this way. Why would the same not be true
where beams attach to columns?
To demonstrate the effect of rigid zone modelling the following simple example will be used.
Chapter 5 : General Building Analysis Orion Documentation page 83
A simple symmetrical structure is shown in the rendered view above. When running the
building analysis you have a choice of 3 model options relating to rigid zones, none, reduced
by 25%, and maximum as shown below.
The sections below describe what each of these options will do.
Orion Documentation page 84 Chapter 5 : General Building Analysis
Rigid Zones None
The analysis results are as shown above. The beam bending moment diagrams extend right to
the centre of the column, the beams will be designed for a support moment of 77.91 kNm and
a span moment of 86.56 kNm.
This is the most simplistic analysis model and is likely to be the most similar to any models
you may have created in general analysis packages.
Chapter 5 : General Building Analysis Orion Documentation page 85
Rigid Zones Reduced by 25%
The analysis results are as shown above. Note that the beam bending moment diagrams do
not extend right to the centre of the column, they stop at the face of the column. The column
moment diagram also stop at the underside of the beams. No diagrams are shown on the rigid
zone lengths.
Importantly, for this model type, although the bending moment diagram starts at the face of
the column the actual rigid length within the rigid zone only extends to 75% of this length (i.e.
it is reduced by 25%).
Comparing the moment diagrams to the case where no rigid zones are used we see that:
1. The span moment is reduced from 86.56 kNm to 76.44 kNm. Adding rigid zones at the
ends of beams generally lifts the bending moment diagrams and hence will slightly reduce
span moments.
2. Although the diagram has been lifted the support moment of 77.91 kNm has reduced
slightly to 75.12 kNm because the moment is now being taken at the face rather than the
centre-line of the column.
3. The column design moments are also reduced from 77.91 to 69.59 kNm.
Orion Documentation page 86 Chapter 5 : General Building Analysis
Rigid Zones Max
The analysis results are as shown above. Once again the beam bending moment diagrams do
not extend right to the centre of the column, they stop at the face of the column. The column
moment diagram also stop at the underside of the beams. No diagrams are shown on the rigid
zone lengths.
Importantly, for this model type, the bending moment diagram starts at the face of the column
AND the actual rigid length within the rigid zone extends to 100% of this length (i.e. it is
max).
Comparing the moment diagrams to the cases where no rigid zones and reduced rigid zones
are used we see that:
1. The span moment is further reduced from 86.56 kNm to 76.44 to 73.2 kNm. Adding full
rigid zones at the ends of beams increases the lifting of the bending moment diagrams.
2. In this case the diagram has been lifted so much that the support moment of 77.91 kNm
which reduced slightly to 75.12 kNm using reduced rigid zones has now increased to 78.36
kNm.
3. The column design moments which reduced from 77.91 to 69.59 kNm have also increased
again slightly to 72.28 kNm.
Chapter 5 : General Building Analysis Orion Documentation page 87
Discussion
It should be noted that the simplistic model used above to demonstrate rigid zones does not
deal with the complexities of continuous beams and pattern loading and may to some degree
exaggerate the effects of rigid zone modelling. A more typical four span continuous beam
example is considered below.
Above results when no rigid zones are used.
Below results when rigid zones are reduced by 25%, span moments reduced by 12% in end
span, support moments reduced by around 10%.
Orion Documentation page 88 Chapter 5 : General Building Analysis
Below results when maximum rigid zones are used, span moments reduced another 23%
and support moments increase again by 23% but are still less than the moments when no
rigid zones are used.
In general the use of rigid zones reduced by 25% will result in the maximum reduction in
support moments combined with a less extreme reduction in the span moment. It is
considered that this option will give maximum efficiency and will be the preferred option for
most designers using Orion.
NOTE: Although this option can often result in reduced support and span design moments, it
should not be confused with moment redistribution. In theory there is nothing to these
design forces being further reduced by the use of moment redistribution.
Rigid Links
3D analysis models are still centre-line models, members need to line up to connect to each
other. When you construct a 3D model in a general analysis package you will naturally see
where things do not line up and make adjustments so that connections are made. When
working in Orion you tend to feel that you are working with the physical model rather than the
analytical model that is derived from it. Sometimes members will not line up and in such
cases Orion will attempt to make the required connections by adding rigid links.
Chapter 5 : General Building Analysis Orion Documentation page 89
The simple example shown below should help clarify this.
The beams on grids 1 and 1a do not line up but are both supported by the same column. In
this example this column is actually inserted at the intersection of 1a and A1. If we look at a
3D stick view we can see the frame that has been defined as shown below.
Orion Documentation page 90 Chapter 5 : General Building Analysis
The column appears to support one of the beams but not the other. However, when the
analysis is carried out Orion will automatically connect the end of any beam that lies within the
physical plan perimeter of any column or wall to that column or wall. So when this model is
analysed a rigid link is added as shown below.
In this example the column was defined in an offset manner directly in line with one of the
beams. To be more precise it could have been defined on a new grid on its own centre line and
then rigid links would have been created from both supporting beams to the column.
Note that rigid links should not be confused with rigid zones, rigid zones are not used in the
above model but could have been.
Note that rigid links will also be created where smaller offset columns sit on larger columns or
walls in the floor below.
Shear Walls and Core Wall Systems
There are optional methods for idealising walls within Orion. This subject is discussed at
length in the chapter on Wall Modelling Considerations.
3D Effects
In general our traditional engineering expectations are developed from considering simplified
sub-models for analysis and design. When a full 3D model is created unanticipated effects
sometimes creep in, is this wrong?
Some simple examples will help demonstrate these effects.
Chapter 5 : General Building Analysis Orion Documentation page 91
Continuous Beams
Traditionally continuous beam lines are analysed and designed in isolation. The modelling of
the support conditions in such cases is often unsophisticated. In the example below a series of
3 span secondary beams are supported at different points on primary beams and also directly
by columns.
When analysed in 3D using unadjusted gross member properties the bending moments for a
general UDL case are as shown below.
Orion Documentation page 92 Chapter 5 : General Building Analysis
Note how the end span moments for the internal beams (which all carry the same load) vary
from 38.94 to 49.54 kNm. The smallest value occurs on the central column line and largest
occurs where the beam is supported at the centre of the primary beam. The variation is not
too significant but does start to indicate the importance of all the relative stiffnesses in a 3D
model.
However, note that hogging moments develop at the extreme ends of the secondary beams
where they are supported by a primary beam. Investigation would show that these develop
because torsional forces are developing in the primary beams. A traditional 2D continuous
beam line analysis will generally model this support as a pin and no hogging moment will
develop. In fact torsion is only usually considered in traditional hand calculations where its
development is essential to the local stability of the structure.
In generating the above results the default unadjusted properties of the rectangular beam
sections were used in the analysis. These results are exactly what you would get from any
general 3D analysis package. In Orion you have options to apply adjustment factors to the
default properties of groups of elements as shown below.
These adjustments are discussed further in the next section, but it is worth noting here that by
default Orion suggests adjusting the torsional stiffness factor of beams by a factor of 0.01 (i.e.
reducing to 1%). This is suggested because in most cases this means that the results of a 3D
analysis will be more compatible with the tried and tested analysis/design achieved using older
2D idealisations.
Chapter 5 : General Building Analysis Orion Documentation page 93
When the model above is reanalysed using this setting the results are as shown below.
The hogging moments have disappeared and the end span moments have increased and
become more consistent at around 67 kNm.
Effects of one Member on Another
The most likely 3D effect is one where the design forces generated are not what you expect.
This sort of effect could happen in many different ways and becomes more likely as the
structural arrangement becomes more complicated and irregular. However, it can be
demonstrated with the very simple model shown below.
Orion Documentation page 94 Chapter 5 : General Building Analysis
A beam is selected along grid A at the front of the model. The loading, shear and moment
diagrams for this beam are shown below.
The loads are slightly offset due to the triangular area of slab being supported, but the bending
moment diagram shows an (unexpected?) sagging moment at the left end support and an
(expected?) hogging moment at the right end support. Can this be correct?
Chapter 5 : General Building Analysis Orion Documentation page 95
The explanation relates to the diagonal beam across the floor. It has been loaded with an extra
UDL. When the structure is examined in the building analysis post processor we can see how
it deflects and bends.
The heavily loaded diagonal beam is putting a big moment into the supporting columns and
the joint is clearly rotating. This rotation cannot happen without some effect on the other
connected beams. When viewed in this way the design moments in the beam do not seem
unreasonable.
Innumerable examples of this nature could be developed. The point is that if the design forces
in a member seem wrong you cannot assume that the analysis is wrong. You need to review
the results carefully and in particular look at the nature of deflections.
Sway Effects
Many structures will undergo a natural sway under purely vertical (gravity) loads. These
sways can sometimes introduce significant changes to the expected moment diagrams in
beams in much the same way as is shown in the example above.
In such cases it is important to ensure that checks are made for combinations where notional
load cases are applied in sympathy with the natural sway of the structure.
In such situations where you might like to check for differences exposed by a 3D analysis of a
floor in isolation, the chapter Analysis and Design using FE introduces this option.
In more extreme cases buildings stabilised by shear and core walls will sway significantly
under purely vertical load, this topic is discussed in more detail in the chapter Wall Modelling
Considerations.
Orion Documentation page 96 Chapter 5 : General Building Analysis
Transfer Beams
The way in which load accumulates in columns that are in turn supported on transfer beams
in a full 3D analysis is often at odds with initial/traditional expectations. This subject is
specifically dealt with in the series of chapters dealing with transfer levels and in particular the
section Discussion of Frame Analysis Results in the chapter Transfer Beams General
Method.
Stiffness adjustments
When you construct a model you set/control the analysis model properties by:
Using the Building Parameters options to globally set/change material properties.
Applying releases (pins) to any member end.
Selecting any individual member and override the calculated section properties.
When you run building analysis you then have options to apply global adjustment factors to
the properties of members on a group by group basis as shown in the dialog below.
Some reasons why you might use these options could include:
Minimising Torsion in Beams
In the 3D Effects section earlier in this chapter, the Continuous Beams example shows how
torsions will often develop in 3D analysis. These torsions would not have been identified or
designed for using more traditional subframe analysis. When the torsions are reduced or
eliminated the major axis design moments usually go up. For this reason Orion defaults to the
setting shown above which reduces torsional stiffness by a factor of 100.
Chapter 5 : General Building Analysis Orion Documentation page 97
However, if you have a model that (unusually) actually relies on torsion for stability then using
the above setting will often mean that extremely large deflections accrue.
Investigating Deflections
You could use different values of Youngs Modulus to investigate different loading conditions
for example use the default short-term value when considering wind load conditions, then
reanalyse with multipliers to reduce Youngs Modulus to allow for long-term effects in other
cases and general design.
Flat Slab Construction
It is worth noting here that the 3D analysis model of a complete building is primarily a frame
element model with an option to use FE meshing of shear/core walls. It does not include FE
meshed floor elements. Since flat slab (or flat plate) structures do not include beams the basic
3D building analysis will not deal with these structures on its own.
Orion supports the analysis and design of Braced Flat Slab Structures by integrating the results
of sequential finite element floor analyses (a top down procedure referred to as FE Chase
down) with the results of the 3D building analysis. The chapter Flat Slab Models describes the
solution provided for these circumstances.
Transfer Levels
A transfer level is an upper level within the structure at which one or more columns or walls
stop. The discontinuous column or wall is supported by beams or slabs such that its load is
transferred to other columns/walls.
This topic is discussed at length in a series of chapters and worked examples beginning with
the chapter Overview of Solution Options for Transfer Levels.
Supports
In a simple model such as the one shown below, all columns and walls finish at a common
foundation level.
In such models, by default a fixed support is automatically placed underneath each column
and each wall at the top of the common foundation level, (indicated by the grey plane).
Orion Documentation page 98 Chapter 5 : General Building Analysis
If a fixed support is inappropriate, a pinned or spring support can be defined using Support
Type Definitions from the Members menu.
Having defined a new support type, it can then be assigned to a specific column or wall using
the member properties as shown:
Note the special meaning of Support Type: Default
For columns and walls that stop at ST00 - Default = Fixed Support
For columns and walls that stop at ST01 and above- Default = No Support
User defined supports are further discussed in the chapter Modelling Techniques. This
chapter also discusses their application to stepped foundation levels.
Chapter 5 : General Building Analysis Orion Documentation page 99
Building Analysis Problems Reviewing/Understanding
The majority of regular models constructed in Orion will run through building analysis
without any messages. However for some models the building analysis process can display
error or warning messages at various stages during execution.
Tip There is an option to run validation checks at any stage, if your building analysis
is giving errors or warnings and you have not run the validation checks, it is
recommended that you do so. This may expose the cause of problems.
Tip Many building validation errors can be avoided by ensuring that the option to
check the validity automatically each time a member is inserted is active. This is
done by clicking on the Graphic Editor View Settings and on the Plan settings
tab, and ensuring that you leave the option Dont check Model During Member
Insertion unchecked.
Note On completion of analysis a series of comparisons are made between the loads
that you applied and the results of load decomposition and subsequent analysis.
If the differences exceed a small percentage variation warnings will be given. All
such warnings should be investigated.
Note Beyond the above, it is not anticipated that you need to read this section until
such time as you are trying to understand or resolve errors or warnings.
What are Errors?
Errors may indicate solution problems (errors) or modelling errors on physical/engineering
grounds.
Errors cannot be ignored, you should investigate until you understand the error message and
if possible take action to remedy the situation or contact Technical Support.
What are Warnings?
Once understood, warnings can often be ignored the important point is that you take the
time to review the messages and decide whether an action is warranted.
Different Errors and Warnings will appear at the different stages of the Building Analysis
Process.
Orion Documentation page 100 Chapter 5 : General Building Analysis
Building Model Validity Checking Errors
Building Validation checks the eight conditions indicated in the dialog:
If any of these conditions occur an error message will be displayed which will clearly indicate
the members that are invalid. You should return to the graphic editor to correct the error and
then re-perform the building model validity check to confirm the problem has been resolved.
On rare occasions a particular error message is displayed:
Er r or : beam1B157 i s over l appi ng wi t h beam1B157
At first this does not appear to make sense since it suggests that a beam is overlapping with
itself. On investigation you will find that there are two beams with identical labels at exactly
the same location. If you encounter this problem you should simply delete one of the beams
while checking that you have not lost any manually applied loads. Note that you will not
immediately see the other beam after deleting the first one, but executing the redraw or regen
function will make it reappear.
Note: If there are no errors as a result of Building Model Validity Checking, it does not follow
that your model is 100% error free. There are many other conditions that are not checked at
this stage, which could result in your model being incorrect. These conditions are checked
during later stages of the building analysis process.
Beam Load Analysis Errors
There should be no errors encountered during Beam Load Analysis.
In some complex arrangements where irregular slabs are supported by numerous beams and
walls on a complex perimeter problems may be encountered. Please report any such problem
to your support department. Note that these problems may be overcome by redefining the
slab, or perhaps by passed by using the option for FE load decomposition.
Chapter 5 : General Building Analysis Orion Documentation page 101
Building Analysis Errors and Warnings
Just as in any general 3D analysis package, you can define releases as you create the structure
and hence you have the flexibility to create mechanisms within the structure. Most
unexpected analysis messages will relate to the existence of such mechanisms.
If you see messages about singularities as shown above than it usually means that too many pin
ended members have been defined. It is recommended that you review the structural model
in the Building Analysis postprocessor and eliminate the unnecessary releases.
If there are so many releases that the structure is unstable then this will usually result in the
message shown below.
This message should never be ignored unless you are dealing with a transfer slab structure
see below.
Orion Documentation page 102 Chapter 5 : General Building Analysis
The following warning messages are commonly displayed during Graphical Data Preparation:
The above message informs you that columns (and walls) exist at an upper storey but do not
continue to foundation level and that the means of support at the transfer level are uncertain.
(i.e. a column sitting on a beam does not generate such a warning.)
Action Required
If it is intended that the columns are transfer columns and you are clear as to the means of
support (e.g. a transfer slab) then you can ignore the warning provided that you have taken
account of the related requirements outlined in the chapter Overview of Solution Options
for Transfer Levels later in this handbook.
If it is not intended to be a transfer column return to the graphic editor and remodel so that
you have a support member in the desired location.
Overview of Axial Load Comparison Report
Chapter 5 : General Building Analysis Orion Documentation page 103
A simple model can be created for a simple illustration of the Axial Load Comparison Report.
The 3D view of the model is as above. The plan view of the model is as below.
General information regarding the model.
The following report is produced by Orion for this model. Note that there are 4 main sections
(tables) of information the headings of which have been emboldened.
Beam size: 250 mm (width) x 500 mm (depth)
Column size: 500 mm x 250 mm
Column Height: 2800 mm
Slab Thickness: 175 mm therefore self-weight = 4.2 kN/m
2
Loadings on slab: self-weight (calculated automatically based on thickness of slab)
SIDL = 1 kN/m
2
Total Dead Load = 5.2 kN/m
2
Imposed Load = 0 kN/m
2
Orion Documentation page 104 Chapter 5 : General Building Analysis
AXIAL LOAD COMPARISON REPORT
SUM OF APPLIED LOADS (Using Un-Decomposed Slab Loads):
------------------------------------------------------
G - Dead Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 33.6 0.0 65.0 117.3 0.0 215.9
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 215.9
Q - Live Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 0.000 0.000 0.000 0.000 0.000 0.000
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 0.000
SUM OF APPLIED LOADS (After Decomposing Slab Loads):
----------------------------------------------------
G - Dead Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 33.6 0.0 182.3 0.0 0.0 215.9
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 215.9
Q - Live Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 0.000 0.000 0.000 0.000 0.000 0.000
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 0.000
Chapter 5 : General Building Analysis Orion Documentation page 105
BUILDING ANALYSIS COLUMN/SHEARWALL AXIAL LOADS:
-----------------------------------------------
Storey G Delta G Q Delta Q
(kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ----------
St01 215.9 215.9 0.0 0.0
------- ---------- ---------- ---------- ----------
Total 215.9 0.0
FINITE ELEMENTS ANALYSIS COLUMN/SHEARWALL AXIAL LOADS:
------------------------------------------------------
Storey G Delta G Q Delta Q
(kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ----------
St01 223.6 223.6 0.0 0.0
------- ---------- ---------- ---------- ----------
Total 223.6 0.0
The purposes and validity of the comparisons that can be made between the sections of this
table are discussed in the following sections.
Table 1
SUM OF APPLIED LOADS (Using Un-Decomposed Slab Loads):
------------------------------------------------------
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 33.6 0.0 65.0 117.3 0.0 215.9
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 215.9
Q - Live Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 0.000 0.000 0.000 0.000 0.000 0.000
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 0.000
This table shows the sum of:
Member self-weights
Applied loads on beams
Applied loads on slabs
The slab loads are calculated based on the area as seen on plan i.e they are not yet
decomposed onto beams.
Orion Documentation page 106 Chapter 5 : General Building Analysis
The detailed calculations are therefore as follows:
Table 2
Differences between this table and table 1 are specifically intended to expose problems in slab
load decomposition. Since there are two methods of slab load decomposition supported we
will look at each of these separately.
Using Yield Line Decomposition
SUM OF APPLIED LOADS (After Decomposing Slab Loads):
----------------------------------------------------
G - Dead Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 33.6 0.0 182.3 0.0 0.0 215.9
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 215.9
Q - Live Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 0.000 0.000 0.000 0.000 0.000 0.000
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 0.000
Once again this table shows the sum of:
Member Self-weights
Applied loads on beams
Applied loads on slabs
Columns Self Weight = 0.25 m x 0.5 m x 2.8 m(height) x 24 kN/mP
3
P x 4(nos)
= 33.6 kN
Beams Loads = [(0.25 m(width of beam) x 5 m(length) x 4(nos)) x 0.5 m(depth of beam)
x 24 kN/mP
3
P] + [(0.25 m(width of beam) x 5 m(length)) x 1 kN/mP
2
P]
<additional beam loads from SIDL >
= 65 kN
Slab Loads = [(5 m - 0.25 m(half width of beam x 2)) x (5 m - 0.25 m(half width of
beam x 2))] x 5.2 kN/mP
2
P
= 117.3 kN
Chapter 5 : General Building Analysis Orion Documentation page 107
The key difference in this table is that the slab loads are now decomposed and thus counted as
UDLs, VDLs etc. on the supporting beams. Therefore, you will find that the slab loads become
zero but the beam loads increase accordingly.
Decomposed Slab Loads Consider again the model and the decomposed slab loads shown
below.
Orion Documentation page 108 Chapter 5 : General Building Analysis
The plan view shows the yield lines, strictly speaking these are really just load decomposition
lines which are used to show the area of slab loading that will be attributed to each beam. This
method of area load decomposition is commonly known as the Yield Line Method. Looking at
the triangular load distribution generated on the above beam, the beam load calculation
effectively becomes:
The beam loading profile and the above calculation clearly get much more complex when
more irregular slab arrangements are used.
The calculations reported in table 2 are therefore as follows:
Decomposed Slab Load = (A1 + A2 + A3 + A4) kN/m2 <Please refer to diagram>
= 4 x 29.33 kN
= 117.3 kN
Columns Self Weight = UNCHANGED
= 33.6 kN
Beams Loads = 65 kN + 117.3 kN
= 182.3 kN
Chapter 5 : General Building Analysis Orion Documentation page 109
Using Finite Element Decomposition
If slab loads are decomposed using the alternative FE method, the loadings from the slab are
applied to the beam as a complex beam load as shown below.
SUM OF APPLIED LOADS (After Decomposing Slab Loads):
----------------------------------------------------
G - Dead Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 33.6 0.0 182.0 0.0 0.0 215.6
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 215.6
Q - Live Loads:
Storey Column ShearWall Beam Slab Rib Total
(kN) (kN) (kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ---------- ---------- ----------
St01 0.0 0.0 0.0 0.0 0.0 0.0
------- ---------- ---------- ---------- ---------- ---------- ----------
Total 0.0
Orion Documentation page 110 Chapter 5 : General Building Analysis
Comparisons between tables 1 and 2
Comparison between these 2 tables provides an indication of the success of the slab load
decomposition. If the totals in table 2 are less than those in table 1 this would give an
indication that loads have gone missing during the decomposition process in which case you
should:
1. Check that slab loads are applied within slab boundaries
2. Visually Check Yield Lines if they do not look right on the plan the decomposition is
probably not right.
3. If Yield Lines are wrong, consider swapping to the FE Load Decomposition method.
Note Both FE and Yield Line decomposition decompose slab loads to beams. If there
are areas without beams (where slabs are supported directly by columns i.e.
Flat Slabs) the decomposition process is guaranteed to lose load. In such cases
full FE analysis must be used and the discrepancy between the totals in tables 1
and 2 should be seen as an indicator of this requirement.
Note In all but the simplest of models, there will always be a small discrepancy between
table 1 and 2. However, this can be ignored especially if the decomposed load in
table 2 is slightly higher than the un-decomposed load in table 1.
Table 3
BUILDING ANALYSIS COLUMN/SHEARWALL AXIAL LOADS:
-----------------------------------------------
Storey G Delta G Q Delta Q
(kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ----------
St01 215.9 215.9 0.0 0.0
------- ---------- ---------- ---------- ----------
Total 215.9 0.0
The figures in this table reflect the results of the building frame analysis. The building analysis
is a frame analysis where the beams are loaded with all the decomposed slab loads. Therefore
the input is based on either the yield line or FE Load Decomposition method; whichever has
been selected.
When the analysis is complete the accumulated column loads on each storey are shown in the
table.
It is therefore appropriate to compare table 2 with table 3 which is in effect a comparison of
analysis input with analysis results. If the totals are different the building analysis is incorrect
in some way in which case you should check:
If there were warnings during the building analysis, have you ignored them and is it OK to
ignore them?
If transfer levels exist, check whether the discontinuous columns are properly supported.
Chapter 5 : General Building Analysis Orion Documentation page 111
Note Flat slab models are a good example of the case where there will be discrepancies
and loads are lost, but this can all be ignored since Finite Element Analysis load
Chase Down is required see next section.
Table 4
Note This table is only available if an FE Chase Down (finite element analysis load
chase-down) has been performed:
When performing the FE Floor Analysis, there are 2 options available.
Option 1: Include Slab Plates in FE Model
When this option is active as shown above, a meshed up FE model is created as shown below.
Orion Documentation page 112 Chapter 5 : General Building Analysis
Slab loads are applied to all the individual shells and so the slab load decomposition is
effectively inherent in the FE analysis of the floor.
After analysis the total axial loads in columns and walls are derived at each level and reported
in table 4 as shown below.
FINITE ELEMENTS ANALYSIS COLUMN/SHEARWALL AXIAL LOADS:
------------------------------------------------------
Storey G Delta G Q Delta Q
(kN) (kN) (kN) (kN)
------- ---------- ---------- ---------- ----------
St01 223.6 223.6 0.0 0.0
------- ---------- ---------- ---------- ----------
Total 223.6 0.0
The total loads and self-weights reported will always be slightly different in FE analysis
because this is a true centre-line model. In this simple example the loads effectively total up as
follows:
Note The area of the slab used in the FE model is different (greater) than the area used
in tables 1 and 2 because the slab extends to the centre-line (not the edge) of the
beam. This has two effects:
The self weight if the slab in the zone that overlaps with the beam is
double counted small extra load.
Column Self Weight = 0.25 m x 0.5 m x 2.8 m(height) x 24 kN/m
3
x 4(nos)
= 33.6 kN
(this part is unchanged)
Beams Loads = [(0.25 m(width of beam) x 5 m(length) x 4(nos)) x 0.5 m(depth) x 24
kN/m
3
]
= 60 kN
(i.e. self weight only finishes loads are not applied to the beam)
Slab Self Weight = (5 m x 5 m) <area of meshing plan> x 5.2 kN/m
2
= 130.0 kN
(see note below)
Total = 60 kN + 33.6 kN + 130.0 kN
= 223.6 kN
Chapter 5 : General Building Analysis Orion Documentation page 113
The finishes and imposed loads that apply on the outer edge of edge
beams will not be counted small loss of load.
When this option is used it is appropriate to compare the totals in table 1 with table 4 (Load
before decomposition and FE analysis results which embody both decomposition and
analysis). Some degree of difference must be accepted for the following reasons:
In all models, there will be a slight difference for the reasons noted above.
The FE method makes much better allowance for holes in slabs.
If totals returned from FE Analysis (table 4) are significantly less than totals from table 1, the
FE Analysis model may be incorrect. In such cases the following possibilities should be
checked:
Are slab line loads applied outside the building perimeter or over voids.
If the option to include column and wall sections in the model has been used, are slab line
loads applied through columns or walls (the load inside the column or wall boundary is
included in table 1 but is not taken into account in the FE analysis because the load could
not physically exist.)
As above, but checking for point loads applied inside column boundary.
Incorrectly modelled cantilever slabs.
Note The totalling of loads in table 4 will be incorrect if some columns are len(storey)
2 or more, but the results themselves are actually correct.
Option 2: Exclude Slab Plates in FE Model
Orion Documentation page 114 Chapter 5 : General Building Analysis
In this case the FE analysis is simply a 3D frame analysis where the decomposed slab loads are
applied to the beams.
In this case it is valid to compare table 2 with table 4 since this is checking that the
decomposed loads which were intended to be applied to the FE models have been successfully
applied.
Chapter 6 : Eigenvalue Analysis Orion Documentation page 115
Chapter 6 Eigenvalue Analysis
Introduction
An Eigenvalue Analysis can be performed as part of the Building Analysis in order to calculate
natural frequencies and mode shapes; these will be dependent on storey mass and model
stiffness. The Eigenvalue Analysis results can then be used for seismic design purposes and
can also be of value if wind tunnel tests are required.
Eigenvalue Analysis Parameters
Controlling the Storey Mass
The storey mass for Eigenvalue analysis is always based on the dead load G plus a fraction of
the live load Q.The degree to which the live load is assumed to participate is controlled by the
participation factor (n), which can be specified on the Lateral Loading tab of the Building
Parameters dialog.
Note For Lateral Load calculations, the storey weight can be based on G or Q or
G+nQ. The Live Load Participation Factor, (n) does not affect the Notional
Load Calculation unless the G+nQ option is selected.
Orion Documentation page 116 Chapter 6 : Eigenvalue Analysis
The G and Q components of the Storey Mass/Weight can be derived from either the
decomposed beam loads, or the undecomposed slab loads. The method used is controlled via
the Settings tab of the Building Analysis Model Options dialog as shown below.
The mass/weight determined for the chosen option can be reviewed by hovering the cursor
over the Center of Gravity of the form plan after running a Building Analysis.
C of G based on Un-decomposed Slab Loads, m = 553t
Chapter 6 : Eigenvalue Analysis Orion Documentation page 117
If all slabs transfer their loads to beams or walls, either option should produce a similar mass/
weight. This can clearly be seen not to be the case in the above (flat slab) example - the mass
determined using the Decomposed Beam Loads option is significantly smaller than that from
the Use Undecomposed Slab Loads option. In such models it is important that the latter option
is always selected.
Model Stiffness
The engineer should use section properties that are appropriate for the Eigenvalue Analysis.
For columns and walls this could involve making global stiffness adjustments to model
cracked section properties. The ACI code may be referred to for some guidance in this regard.
These adjustments can be made via the Model Options/Stiffnesses tab of the Building Analysis
dialog.
Controlling the Number of Mode Shapes Required
These are set on the Lateral Loading tab of the Building Parameters dialog.
C. of G. based on Decomposed Beam Loads, m = 106t
Orion Documentation page 118 Chapter 6 : Eigenvalue Analysis
Analysis
The analysis produces results for both the Static and Eigenvalue Analysis that can be accessed
simultaneously in the graphical post processor.
Graphical Results
To view a mode shape, activate the Displacements button and select the mode shape required
from the Loading menu as shown below. Animation can be activated if required from the
Displacements menu.
Chapter 6 : Eigenvalue Analysis Orion Documentation page 119
Numerical Results
Numerical output from the analysis is accessed from the Report tab Eigenvalue Results
Report Button.
This button shows information relating to the frequencies and mass participations as shown
below.
Orion Documentation page 120 Chapter 6 : Eigenvalue Analysis
Exporting to S-Frame
If you export the model to S-Frame to cross check the Eigenvalue analysis, you will need to
make a minor adjustment before running the analysis. This is necessary because the way
S-Frame stores the mass information is slightly different to the way it is held in Orion.
Exporting to S-Frame Example
In Orion For a simple table model the frequency of the first mode is given as 7.124Hz. The
mass at the single floor level is 31.847 tonne (312.4kN). This mass includes for the weight of all
columns and walls below the floor.
When the model is opened and analysed in S-Frame the frequency is 6.97Hz The difference is
accounted for by the way the mass due to self weight is being modelled in S-Frame.
Correction of Self Weight in S-Frame (for Eigenvalue Analysis only)
Two materials are exported to S-Frame - The first material (MAT1) is assigned to the
columns/walls and has a mass Orion ignores this mass in the vibration calc because it has
included it in the floor mass, S-Frame does not ignore this mass, therefore the mass is double
counted in S-Frame.
The second material (MAT2) used for beams has zero mass.
In order to get compatible Eigenvalue analysis results between Orion & S-Frame you are
required to switch off the mass of MAT1 in S-Frame. This is done by setting the force density
to zero.
If the density of the materials is set to zero in S-Frame the frequency for the first mode
increases to 7.125Hz.
Note In S-Frame, for the G loadcase, selfweight of the structure is introduced by a
gravitational factor - hence the above adjustment will invalidate the gravity case
results if a static analysis is performed.
Chapter 7 : Staged Construction Analysis Orion Documentation page 121
Chapter 7 Staged Construction Analysis
Introduction
Staged construction analysis is a sophisticated method of solution which, if used with a
reasonable degree of care can more closely reflect the real behaviour of the structure.
A standard 3D analysis takes no account of time dependant effects - it assumes the structure
has been constructed instantaneously. In the real world a concrete building has to be
constructed in stages - typically one floor at a time. Depending on the number of storeys
within the building a significant period of time can elapse from the commencement of first
floor to completion of the top floor. Because concrete matures with time, this means that at the
top floor the concrete has properties which lag behind those of the first floor (and to a
reducing degree each intermediate floor).
Another aspect of the staged nature of concrete construction is that any settlement of existing
lower floors which takes place prior to the pouring of the current floor is allowed for on site
when establishing the current floor level. This effect can not be allowed for in a standard 3D
analysis, however it is catered for automatically in a staged construction analysis.
Simple Example
A model consisting of two blocks is constructed as shown below. The first floor plan and
loading is identical in both blocks. A second floor framework is added to the right hand block
but with no imposed load applied to that level.
A standard 3D analysis can be performed for the above, in which all members are analysed
simultaneously with all the loads applied.
A staged construction analysis can also be performed. If the option were selected to stage the
imposed load only, the analysis would proceed as follows:
In the first stage, only the first floors are analysed for their imposed load.
In the second stage, the second floor is added and the analysis repeated (for the
undeformed model) but this time only for the imposed load at second floor level.
Note In this way, each stage can only affect the result in its own and previous stages.
Orion Documentation page 122 Chapter 7 : Staged Construction Analysis
Results for Q - Unstaged
In the unstaged result you can see that Q load applied at first floor is causing moments to
develop in the structure above. If that frame existed when the load was applied then this is
completely logical.
Results for Q - Staged
In the staged result no moments develop in the frame above the first floor members and in fact
the forces in the first floor structure are identical in the single storey frame and the two storey
frame. This is logical if all the load is applied before the frame above exists AND assuming
that all deflection is instantaneous.
Note The effect of creep is not considered in the above - in reality the first floor beams
would continue to deflect and the joints continue to rotate after the frame has
been built and loaded. Therefore, although there are no moments in the second
floor frame at the point at which it is constructed, the creep of the first floor
structure should cause some moments to develop over time in the second floor.
Chapter 7 : Staged Construction Analysis Orion Documentation page 123
Staged Construction Modelling and Analysis
Model Creation
No additional steps are required when creating a model for staged construction. Stages are
created automatically, (each storey being treated as a separate stage). Stages can be adjusted
once the model has been created as described in the section Stage Control.
Staged Loading Creation
Staged loading is specified within the Load Combination Editor by clicking the Loading
Generator button.
Using the controls you are able to stage any gravity load case and then create combinations of
staged and unstaged cases.
Stage Construction Cases Check this box to activate staged construction.
Stage Duration Specify the default duration of each stage, this can subsequently be
amended for individual stages - see Stage Control.
Stage Construction Cases: G Check this box to create an sG staged loadcase.
Stage Construction Cases: Q Check this box to create an sQ staged loadcase.
Create New Combinations for Staged G and Q When not checked one set of
combinations is created which uses the staged cases, when checked two sets of
combinations are created, one with the unstaged cases and the second with the staged
cases.
Orion Documentation page 124 Chapter 7 : Staged Construction Analysis
The result of checking the Create New Combinations for Staged G and Q box is shown below:
Combinations 1 to 7 are not staged at all, combinations 8 to 14 use fully staged G + Q.
Alternatively you may choose to have combinations of staged G and unstaged Q.
As shown above, the Loading Generator populates the Load Combinations Editor with a
column header for each staged and unstaged loadcase. The generated combinations are
displayed in rows.
Note You are not restricted to the automatically generated combinations and factors,
you have complete control to add, delete, or modify the combinations as you see
fit.
In this way you can design for an envelope of staging assumptions. Note that you can even
include staged pattern load cases! While in reality this may not seem entirely logical, it might
actually be the best way of getting closest to the results generated by traditional sub-frame
analysis. However, staged G plus unstaged Q might be preferred because they create the worst
effects in different places and might actually produce a lower peak.
Chapter 7 : Staged Construction Analysis Orion Documentation page 125
Stage Control
Stages are defined within the Load Combination Editor by firstly clicking the Load Cases
button. Next, highlight a staged loadcase, (for example SG as shown below) and click Edit.
Initially each floor level is considered to be a stage - so by default a 5 storey building is
analysed in 5 stages as shown below:
You can if required specify different time durations for the individual stages. See Setting the
Duration of Each Stage
Orion Documentation page 126 Chapter 7 : Staged Construction Analysis
Combining multiple floors into a single stage
You are not restricted to having each floor analysed as a separate stage, several storeys can be
combined into a single stage.
For example you may choose to analyse the previous 5 storey building in just 2 stages:
Stage 1 as displayed above comprises storeys 1 and 2,
Stage 2 comprises storeys 3, 4 and 5.
To reduce the original five stages to two stages you would proceed as follows:
1. Stage 1 must always start at storey 1 so this is left as is,
2. Stage 2 starts at storey 3, when this is entered the screen is shown thus:
3. Stages 3 and 4 are not required and need to be deleted - this is achieved by clicking in the
topmost stage (4) and putting "0" in the storey column.
4. Repeat once more so that you are left with stages 1 and 2.
Combining the entire structure into a single stage
The same technique for deleting stages can be used to place the entire structure in a single
stage. The reason for doing this is to allow the model to be simultaneously designed for
patterned load combinations derived from the building analysis AND combinations derived
from the FE merged load cases. See FE Merging for details.
Chapter 7 : Staged Construction Analysis Orion Documentation page 127
Setting the Duration of Each Stage
The duration of each stage controls the modulus of elasticity used at that stage - it is assumed
that a normal cement is used so that E
c
at age t is estimated by:
E
c
(t) =
E
(t)E
c
(28)
1
with

E
(t) = squareroot (
cc
(t)
where
(
cc
(t) = exp [0.25(1 - squareroot (28/t)]
The significance of the stage duration on E
c
is illustrated below:
From the above it can be seen that changes due to duration do not have a large impact on the
results after the first few days.
Analysis Properties
As per unstaged construction, factors are applied via the Model Options/Stiffnesses tab
(shown above). These are applied across all construction stages.
Modulus of Elasticity
The Modulus of Elasticity Factor in particular requires careful consideration as it should be
employed in order to make any allowances for creep and cracking. The value entered here is
applied to the short term modulus of elasticity E
c
(28) defined in Material dialog.
As described in the previous section Setting the Duration of Each Stage further factors are
then applied to the E value to account for the duration of each construction stage.
Note Any allowance for creep is only dealt with effectively in the context of an
unstaged analysis..
Note The E value adopted is very important in relation to sway sensitivity assessment
for EC2 (and for other codes also if the ACI sway option is used).
Footnotes
1. Taken fron Concrete Structures Amin Ghali, Renaud Favre, M. Elbadry
Duration 1 day 0.59 E
c
(28)
Duration 15 days 0.96 E
c
(28)
Duration 28 days 1.00 E
c
(28)
Duration 99 days 1.06 E
c
(28)
Orion Documentation page 128 Chapter 7 : Staged Construction Analysis
FE Merging
When G and Q loads are merged from the FE analysis they replace all the G and Q loadcases -
so G-fe replaces G, GP11, GP12, and Q-fe replaces Q, QP11, QP12, etc.
Staged loadcases are never replaced by FE merged results - the consequence of this on the
combinations is as follows:
For combinations of entirely staged cases no merging takes place.
For combinations of entirely unstaged cases - G, GP11, GP12, Q, QP11, QP12, etc. are
replaced.
For combinations that contain both staged and unstaged cases, only the unstaged cases are
replaced.
The latter situation is investigated in more depth below:
Terminology:
G and Q = results from 3D analysis
G-s and Q-s = results from 3D analysis where staged construction has been considered
G-fe and Q-fe = results merged from FE floor analysis where limitations noted above
continue to apply.
1. Initially both G and Q are staged and the option to Create New Combinations for Staged
G and Staged Q is checked:
the result is that before merging there are two sets of combinations:
G + Q
G-s + Q-s
In this case the merged FE forces would affect the unstaged combinations. Therefore:
G-fe + Q-fe
G-s + Q-s
This may be considered to be an attractive mix of combinations by some engineers.
2. You may have chosen to edit the original combinations so that the first combination is
based on staged rather than unstaged G, hence before merging the two sets of
combinations are:
G-s + Q
G-s + Q-s
FE merging only affects the unstaged results so in this case you would end up designing
for an envelope that simultaneously considers
G-s + Q-fe
G-s + Q-s
Chapter 7 : Staged Construction Analysis Orion Documentation page 129
3. You may have chosen not to stage Q at all in which case before merging there is a single
combination:
G-s + Q
FE merging only affects the unstaged results so in this case you would end up designing
for:
G-s + Q-fe
The above might or might not be considered adequate, that is for you to decide.
Simulaneously designing for FE merged forces and the results of a completely unstaged analysis.
Clearly the above introduces the possibility that FE merged forces can be designed for
simultaneously with a combination where staged conditions are considered. What it does not
allow is the possibility of simultaneously designing for FE merged forces and for the results of
a completely unstaged analysis.
However, a workaround can be employed to achieve this if you run a single staged
construction analysis for both G and Q as follows:
In the Load Generator, check the options to stage both G and Q and also to Create New
Combinations for Staged G and Staged Q:
Edit the two staged loadcases so that the entire model is put in the first stage and set the
duration to 28 days.
Before merging there are now two sets of combinations, (although the staged combination
produces exactly the same result as the unstaged):
G + Q
G-s + Q-s
FE merging only affects the unstaged results so you end up designing for an envelope that
simultaneously considers
G-fe + Q-fe
G-s + Q-s (which in this case is identical to G + Q)
Orion Documentation page 130 Chapter 8 : Analysis and Design using FE
Chapter 8 Analysis and Design using FE
Introduction
When you run FE Floor analysis you are presented with many options. In this chapter we aim
to help make sense of these options by providing an overview of their meaning/effect and also
indicate when each option would tend to be of most importance. Throughout this chapter we
will also cross reference to more detailed examples that illustrate the use of each option in
practice.
Model Generation Options
When you run the FE Floor Analysis module the following dialog will immediately be
displayed.
If you have previously run an analysis for the floor the settings will have been saved and will
now be redisplayed. A brief introduction to each item/option is given below.
-
Chapter 8 : Analysis and Design using FE Orion Documentation page 131
Column / Shear Wall Model Type
You have a choice of 3 model types:
1. The short frame model.
2. Z Restrained (Pinned Support) Model.
3. Elastic Spring Element.
As shown below, the short frame model option creates a 3D subframe for the floor including
the columns/walls. The other two models do not include the columns/walls and so any fixity
moments that develop between the floor system and the columns are excluded.
We strongly recommend that the default Short Frame Model is used unless/until you have
some specific reason to try another option.
Orion Documentation page 132 Chapter 8 : Analysis and Design using FE
Beam Stiffness Multiplier
When the FE model is generated it uses the gross section properties of the un-flanged beam
when calculating the inertia (I). Youngs Modulus (E) is taken as defined in the main building
parameters.
It is possible that you may want to increase I to account for flanged section properties. It is
also possible that you may want to decrease I to account for cracking, creep and shrinkage if
deflection is a concern.
However, in framed systems deflection is generally not a concern and the advice given in
Codes/Standards is that a consistent set of properties be used. Since the column properties are
based on the gross section, it is felt that the default use of the gross section properties of the
un-flanged beam is generally appropriate.
Slab Stiffness Multiplier
As for beams, the FE model is generated using the gross section properties of the slab when
calculating the inertia (I). Once again Youngs Modulus (E) is taken as defined in the main
building parameters.
When you are looking at a beam and slab system, it is considered highly likely that you will
want to reduce the slab stiffness relative to the beam stiffness. Even with a flat slab system, you
may also decide to adjust the slab stiffness.
The reasons for this are best understood by reference to the following examples:
For Beam and Slab Systems, refer to the Worked Example Beam and Slab Systems
section later in this chapter.
For Flat Slab Systems refer to the chapter Flat Slab Models and in particular the discussion
of slab deflection estimation.
Column and Wall Stiffness Multipliers
The FE model is generated using the gross section properties when calculating the inertia (I).
and the Youngs Modulus (E) is taken as defined in the main building parameters.
Typically you would only need to adjust the column stiffness for the purpose of making a
cracking and creep allowance.
Cracking and Creep
As previously stated the advice given in Codes/Standards is that a consistent set of properties
be used. Hence if the Cracking and Creep function is used the calculated stiffness factor is
applied by default to all member types.
Include Column Sections in FE Model
This option allows you to create a more sophisticated model that idealises a rigid zone
extending to the perimeter of the column sections. This modelling sophistication is really
only of interest in flat plate models where it helps tackle the problem of extreme local hogging
Chapter 8 : Analysis and Design using FE Orion Documentation page 133
moments that are generated over column heads in traditional analysis model idealisations.
Refer to the chapter on Flat Slab Models for an example of the effect of this option. Note that
activating this option may introduce more meshing difficulties during model generation.
For beam and slab models this option has little positive effect and may only introduce
difficulties, hence we recommend it is better not to activate this option for such models.
Include Slab Plates in FE Model
This option allows you to create floor grillage models where the slabs are not modelled or
meshed. In these models the beams are loaded using the same decomposed loads as are
applied in the general building analysis. This modelling option has a various potential uses:
1. A fast solution option for Transfer Beams Refer to the chapter Transfer Beams FE
Method, Option 1 (Simplest) for a worked example.
2. It allows you to investigate grillage effects that are not normally considered in any
subframe analysis. For example the forces in a line of secondary beams can be influenced
by the varying rigidity of primary support beams. As in the transfer beam example noted
above, you have the option to merge results and check beams for the results of alternative
analytical idealisations.
Consider Beam Torsional Stiffness
The option to consider or exclude beam torsional stiffness for FE analysis has been included to
allow you to model in line with traditionally accepted idealisations. For example, in hand
calculations, or in any continuous beam design package, and in fact in Orions 2D
sub-structuring approach to building analysis, a continuous secondary beam supported by
other primary beams is assumed to receive vertical support, but rotational compatibility is
ignored. i.e. a secondary beam will not introduce torsions in a supporting primary beam.
In practice these torsions are known to exist, but are assumed not to be significant. When this
option is not checked Orions 3D floor analysis will operate more in line with this commonly
accepted idealisation.
Orion Documentation page 134 Chapter 8 : Analysis and Design using FE
Note however that in some models excluding the beam torsional stiffness will allow a
mechanism to develop.
In the example shown here a curved elevation is modelled with a series of straight beams. If
the FE model is created without including beam torsional stiffness the deflections are extreme,
indicating the presence of a mechanism.
Around the curve, moments in one element translate to a combination of moments and
torsions in the adjacent elements due to the angular change.
Chapter 8 : Analysis and Design using FE Orion Documentation page 135
When remodelled including beam torsional stiffness the deflections diagrams start to look
much more reasonable as shown below.
Note Orion does not consider torsion within beam design, so if significant torsions are
developing these would need separate design checks. You can check torsion levels
by reviewing the FE Analysis Output Report, or if you have S-Frame, you can
export to that and review the results graphically.
Include Upper Storey Column Loads
This option allows you to automatically include the column self weight and also reactions
from the FE analysis of the floor above as loading input for the current floor. This enables an
FE load chase down procedure that allows Orion to provide solutions for transfer beams/slabs.
Refer to the chapters on these options starting with Overview of Solution Options for
Transfer Levels for a full discussion and worked examples.
Upper Storey Column Loads Table
This option displays a table allowing you to review the column loads being applied when the
above Include Upper Storey Column Loads option is used.
Floor Mesh and Analysis
This option opens the modelling window in which you can mesh and then refine the mesh for
your floor model. This is discussed in a little more detail in the following section Meshing and
Analysing your Model.
If you have chosen to model without plates then meshing is unnecessary, you can simply enter
and immediately exit this window in order to generate the beam element model.
When you exit from this window the model will be automatically analysed.
Orion Documentation page 136 Chapter 8 : Analysis and Design using FE
Batch FE Chasedown
This option displays a table allowing you to specify all of the model generation options and
mesh parameters required for every floor in the building. By clicking on OK you are then able
to perform the chasedown procedure for all floors in a single batch. An option is provided for
you to check and if necessary adjust the meshing at each floor. It is recommended that the
meshing is reviewed and approved during the first run and also after any significant edits.
If you need to abort the chasedown at any stage simply click on the cross at the top right of the
analysis progress window shown below.
Meshing and Analysing your Model
If Slab Plates are NOT included
When you click the mesh generation option, you initially see an isometric view of the model.
If you have chosen this model type you do not need to do anything in this window, the
complete model is already created, you simply need to exit at which point the model will be
automatically analysed.
Chapter 8 : Analysis and Design using FE Orion Documentation page 137
If you wish, you can review the model by activating more of the view options from the menu
on the left of the screen. The options you are most likely to switch on/off are also available as
drop down iconised menus along the top of the screen - you should find these more
convenient to use. However all of this (and more) can also be reviewed in the results window.
For detailed examples using this modelling option, refer to the chapter Transfer Beams FE
Method, Option 1 (Simplest) or to the following section on Merging Beam Results.
If Slab Plates are included
When slab plates are included, you need to mesh up the model before exiting the mesh
generation option.
Prior to generating the mesh it is imperative that all columns have been positioned on slab
boundaries - otherwise no connection can be formed between the slab and the column.
It is also strongly recommended that each slab panel has been defined so that none of its
internal angles are greater than 180 degrees. L shaped panels fall into this category - these can
be avoided if you split the L shape into two or more rectangular panels.
Overall it is important not to enter into FE meshing of floor slabs with an expectation that
everything will always work first time. Meshing is often an inexact and iterative procedure
that takes a little time to get right.
The mesh generator will try to create a mesh for you within the parameters that you set, but it
is not always possible. When a mesh is generated it is up to you to be confident that it is a
reasonable mesh for the problem you are trying to assess. The sections below list the more
common issues that seem to arise in relation to mesh generation. Meshing is also discussed in
more detail in the following examples in this chapter, and also in the examples in the chapter
Flat Slab Models.
Orion Documentation page 138 Chapter 8 : Analysis and Design using FE
Validity Checking
Note that the validity checks accessed from the main Building Analysis dialog will issue
warnings about slabs that may cause problems during FE meshing and analysis.
These types of messages can be very helpful when trying to isolate meshing problems or mesh
regularity issues as discussed in the following sections. Note that messages such as shown
above are only warnings, they can be ignored provided you are happy with the meshing you
generate.
If you get errors referring to overlapping slabs and columns (such as shown below) these will
significantly affect the FE models and cannot be ignored.
Chapter 8 : Analysis and Design using FE Orion Documentation page 139
Mesh Density
Mesh density is strongly influenced by the target Plate Element Size that is provided as input
before you press the Generate Model button. Orion suggests an initial default of 800mm, and
for a simple regular layout such as shown above where the slabs are placed in squares with the
supporting columns at the corners this default will be very reasonable.
The mesh that gets generated will also be strongly influenced by the the Mesh Uniformity
Factor which is accessed from the Model menu. In the above mesh (which was generated with
a mesh unifomity of 100%) 6 plate segments are produced between the column heads. We
recommend that you generally aim for around 6 to 8 plate segments between column heads.
Orion Documentation page 140 Chapter 8 : Analysis and Design using FE
Mesh Uniformity
If we alter the example above so that there are still 9 panels but they are not all the same size,
then meshing with the default plate element size and keeping the mesh unifomity at 100%
results in the mesh shown below.
This is not an ideal mesh. In several places there are only 4 segments between columns.
At this point we can start to adjust the Plate Element Size and/or the Mesh Uniformity Factor to
achieve a more satisfactory solution.
By retaining a uniform mesh and reducing the plate size to achieve the objective of having a
minimum of 6 plates between the closely spaced columns at top right, we must reduce the
plate size to 500mm as shown below. This produces a total of about 1800 plates; the top right is
now OK but we are generating more plates than we really need elsewhere.
Chapter 8 : Analysis and Design using FE Orion Documentation page 141
If we swap to the other extreme, i.e. the least uniform mesh setting, and then adjust the plate
element size; a reasonable mesh is achieved when the plate size is set at 2000mm as shown
below. (Although in this example the uniformity factor is over-riding the plate element size
setting, so that the maximum size is not being achieved anywhere within the slab.) The total
number of plates required in this case is 1678.
The objective is to find a uniformity setting that allows you to reduce the number of plates
because you do not have areas with significantly more plates than are really necessary.
The mesh above is achieved with a plate size of 800mm and a uniformity of 50%. It has 866
plates rather than 1678 and is equally as good for the important bottom left corner panel.
Orion Documentation page 142 Chapter 8 : Analysis and Design using FE
Effect of Holes and Boundaries
Holes can not be placed on a slab boundary, but in the view above some holes have been added
close to a boundary. In the panel containing one hole, the hole is positioned 25 mm from the
edge of the panel. In the panel containing two holes, one is 25 mm from the edge of the panel,
and the two holes are only 25 mm apart.
Chapter 8 : Analysis and Design using FE Orion Documentation page 143
If we mesh this model with a plate element size of 800mm and the default mesh uniformity
factor of 25% the result is as shown above. The meshing always generates nodes (edges) along
panel boundaries and is therefore trying to create very small plates to work through the small
gaps (as shown below).
The meshing shown here is actually useless for all practical purposes. In such circumstances
Orion will sometimes generate coarse but unusable meshes, other times it may generate a
message such as shown below.
Orion Documentation page 144 Chapter 8 : Analysis and Design using FE
Either way you need to recognise that either the meshing density/refinement needs to be
changed or the model needs to change. In the view below some small but important changes
have been made.
The slabs have been redefined so that there are no edges near to grid 10, this means there
are no small gaps to deal with between the holes and fictitious edges along that grid line.
The two closely spaced holes have been idealised as one larger hole thus avoiding the
problem of the small gap between them. In practice, where there are a cluster of services
openings this idealisation is not only helpful from an analytical point of view, it often
proves to be more economic and flexible from a construction point of view.
This revised model will mesh easily and well as shown above.
Chapter 8 : Analysis and Design using FE Orion Documentation page 145
Mesh Sensitivity
In general the more elements you use the more precise the answers will be. Considering this
in conjunction with the notes in the previous sections you may conclude that if/when in doubt
the best thing to do is just ask for more plates and create a finer mesh. If you really are in
doubt this is not a bad rule to follow, but this is sometimes also referred to as over meshing
and it has a few drawbacks to consider:
As you add more and more elements you will find that the increased meshing is having
less and less effect on the results checking sensitivity to meshing changes is standard
practice in FE modelling. In essence this is only a speed problem meshing, analysis and
presentation/interpretation of results all get slower as the number of plates in a model
increases.
Stress Point Intensification with highly refined meshes you will begin to expose local
effects (very high forces theoretically applying over very short distances) that are of no
practical interest in RC design work. The most common example of this is the extreme
hogging moments that traditional FE analysis tends to expose over column heads in flat
slab models. The principle is however equally applicable to corners adjacent to holes etc.
Reviewing Results Contours and Strips
The various contouring and strip result options are best explained in the context of worked
examples. The following example covers most of the options, additional notes are included in
the examples in the chapter Flat Slab Models.
Orion Documentation page 146 Chapter 8 : Analysis and Design using FE
Worked Example Beam and Slab Systems
Introduction
In this example we will work with the reasonably simple floor layout shown above. If you want
to work through the example for yourself, you can load model DOC_Exampl e_04. In order
not to destroy the example for someone else you should then save the model with a new name
before proceeding.
One point to notice is that slab angles that have been defined in the angled wing of this model.
The wing is angled at 40 degrees and by defining this angle in the slab information we are
essentially designing the angle of the orthogonal reinforcing system that will be used in this
wing. As we will see later this allows us to see much more relevant contouring details.
Chapter 8 : Analysis and Design using FE Orion Documentation page 147
FE Mesh Generation
Start with the model settings as shown above. Later in this example we will look again at the
effects of adjusting the slab stiffness multiplier, in this section we will focus on meshing
ensure the Plate Element Size is set to 1000mm and the Mesh Uniformity Factor is set to 100
then click on the Floor Mesh and Analysis button.
Orion Documentation page 148 Chapter 8 : Analysis and Design using FE
Click on the mesh button and you should see a meshed model formed of 614 plates as shown
above this is NOT a good mesh. (See previous section).
The mesh generator tries to refine the mesh adjacent to holes with the result that remote
panels end up quite coarsely meshed as shown above. In beam and slab systems a reasonable
rule of thumb is that there should be at least 6 and preferably 8 segments generated along the
lengths of the beams. (In flat slab systems a similar principle can be applied to the stretches
between columns.)
There are two ways in which you can change the meshing. If you want to increase the
refinement locally around the holes and corners you can reduce the mesh unifomity factor, or
if you want to increase the refinement generally across the whole slab you can reduce the plate
element size.
The the mesh unifomity factor was set to 100, if we reduce this to 25 and re-mesh the result is
as shown below.
This is a big improvement, however there are still a few beams with only 5 and 6 nodes along
their length. Although the total number of plates used has increased to 2488, we might decide
yet more plates are required, and ideally we need a bit more mesh refinement around the
openings.
Chapter 8 : Analysis and Design using FE Orion Documentation page 149
If we keep the mesh uniformity factor at 25 but reduce the plate element size to 600mm we get
the mesh shown below.
This has had the desired effect. It has to be noted again that meshing is not an exact science, if
in doubt you should reduce the plate element size and accept the slightly slower performance
associated with the larger model.
Having created an acceptable looking model, you can now exit from the FE preprocessor and
the model will be automatically analysed.
Review of Contouring Options
After analysis you can select the Analysis Post Processing option and begin to review the
results. You can select from a number of contour displays and we will look at each of them
now.
Orion Documentation page 150 Chapter 8 : Analysis and Design using FE
Deflection Plots
In any analysis package it is always good practice to look at the deflections if the deflections
do not make sense the results will not either. In this case the contours look very reasonable.
The model has an obvious angled line of symmetry, and the deflection contours are also
symmetrical. The only point that might draw some attention is the deflections of the primary
edge beams. They are not big deflections, but they are more significant than the slab
deflections.
Mx and My Plots
Chapter 8 : Analysis and Design using FE Orion Documentation page 151
An Mx plot is shown above. Mx and My contours are displayed relative to a single global
coordinate system. Since this model has an angled line of symmetry the contour pattern is not
symmetrical.
If you imagine X direction bars running from left to right (horizontally) in the above view
then Mx moments are the moments that these bars will need to be designed to resist (but see
also the later notes on design moments including Wood and Armer adjustments).
Since it is unlikely that reinforcing bars will be positioned horizontally in the angled wing,
these contours are of little value for that region.
M1 and M2 Plots
In the introduction to this example it was noted that a slab angle (the reinforcing angle) has
been defined for each slab panel.
An M1 plot is essentially an Mx plot where the contours are displayed relative to a local
coordinate system for each slab panel. The local system is defined by the angle of rotation
applied to each slab panel. For this model this means that we can now see a symmetrical
contour plot where the contours in each wing are relevant to the orthogonal reinforcing
system that will be used in each wing.
Notice that in any contour plot you can use the mouse pointer to highlight any node (as shown
above) and the precise information about that node is displayed at the foot of the window.
Plots Including Wood and Armer adjustments
Wood and Armer adjustments take plate torsional moments into account to generate adjusted
design moments. It is beyond the scope of this manual to present the derivation of the
equations for these adjustments. If detailed background on this is required you should refer to
slab/bridge design texts, or to the original papers:
Wood, R.H. The reinforcement of slabs in accordance with a pre-determined field of
moments as published in Concrete, 2. February 1968, pp69-76,
Orion Documentation page 152 Chapter 8 : Analysis and Design using FE
Armer, G.S.T. Correspondence as published in Concrete, 2. August 1968, pp319-320.
It is noted that the implementation of the adjustments within Orion is limited to orthogonal
reinforcing systems.
The adjustments apply differently to hogging and sagging moments, so there are 4 possible
contour diagrams that can be displayed.
An Md1-bot plot is shown above. This is essentially the M1 sagging (bottom) moments
adjusted to account for plate torsion. The blue zones on the plot are hogging areas, the
maximum sagging moment is 5.4, which is almost identical to the M1 sagging moment (5.3)
shown previously.
Chapter 8 : Analysis and Design using FE Orion Documentation page 153
An Md1-top plot is shown below. This is the adjusted M1 hogging (top) moments. The red
zones on the plot are sagging areas, the maximum hogging moment is 8.2, which is a little
higher than the M1 hogging moment shown above.
Since they are based on the M1 and M2 moments these design moment plots are also
symmetrical for this floor system.
The degree to which Wood and Armer adjustments affect the design moments is entirely
dependent on the levels of Mxy (or M12) moments these can be regarded as twisting
moments.
Regular beam and slab systems do not tend to have high twisting moments coincident with
peak hogging/sagging moments and Wood and Armer effects are often of little significance.
In this model you can find places where the effect I more significant.
Orion Documentation page 154 Chapter 8 : Analysis and Design using FE
You can review the Mxy or M12 moment contours as shown below.
Corners are always areas where twisting is high. In this model there is also quite a high twist
developing over the beams along the angled line of symmetry. We will see how this affects the
strip design moments later in this example.
Steel Reinforcing Requirement Contours
2 sets of steel area requirement contours are provided:
As contours 4 options
As1-bot, As2-bot, As1-top, As2-top
These steel areas are based on the M1 and M2 moments (i.e. moments that do not include
the Wood and Armer adjustments).
Chapter 8 : Analysis and Design using FE Orion Documentation page 155
As(d) contours 4 options
As(d)1-bot, As(d)2-bot, As(d)1-top, As(d)2-top
These steel areas are based on the Md1 and Md2 moments (i.e. moments that include the
Wood and Armer adjustments).
It is recommended that unless you have some specific reason for ignoring the Wood and
Armer adjustments you should always work with the As(d) contour results.
Other Contouring Adjustment Options
Before accessing the postprocessor you will have noted the option to apply global adjustment
factors to all Positive (Sagging) or Negative (Hogging) moments. This is not the same as
moment redistribution, but it would potentially allow for redistribution style effects to be
introduced.
It should be noted that FE floor models do not include any pattern loading, it is not feasible/
logical to automate pattern loading to generate every possible worst case scenario for every
conceivable irregular arrangement and any size of model. A more realistic use of these
adjustments may be to amplify the sagging moments (perhaps 10 to 20%) if you are concerned
about allowing for load patterning. This will be discussed further later in this example.
Once you are in the post processor viewing moment contours you will also have noticed a
drop down option relating to Col/Wall Node Interpretation. This has little effect on beam and
slab systems and is a little more relevant to flat slab design. This option is discussed in more
detail in the chapter on Flat Slab Models.
Orion Documentation page 156 Chapter 8 : Analysis and Design using FE
Slab Design
The design approach, which involves creating slab strips and then designing based on
tabulated code coefficients, is covered in the training manual. Discussion there also extends to
the option of using an FE strip. In this section we will look at some comparisons between the
two approaches and also look a little closer at the FE modelling options and how these might
affect design based on an FE analysis.
For this sort of regular slab it would be considered quite reasonable to use the traditional strip
method outlined in the codes. The importance of setting the slab type correctly is noted again,
refer back to the training manual if you have any doubts on this.
When you design the strip X1 on this basis the design moments are given in the output shown
below.
Chapter 8 : Analysis and Design using FE Orion Documentation page 157
Now we can change the strip to an FE Span Strip by updating the slab strip properties first
check the FE Strip option under the General tab then choose the appropriate type of FE strip on
the FE tab as shown below.
Orion Documentation page 158 Chapter 8 : Analysis and Design using FE
Now remesh the model and then go into the FE Postprocessor to review the analysis results.
In the view above the moment diagram is determined along the actual cut line, in the table
below you can see the peak moments captured from the wider area of slab as indicated on the
plan view in the background.
We can compare the hogging and sagging moments in the table above with those reported
using the coefficient method earlier. Where we now have a hogging moment of 7.5 kNm, it
was 4.6 kNm. Where we now have a sagging moment of 4.8 kNm, it was 4.5. Before
continuing it is worth emphasising that these peak moments indicated above are very close to
or exceed the moments determined by the empirical code approach.
Chapter 8 : Analysis and Design using FE Orion Documentation page 159
More interestingly, the peak hogging does not occur at the first internal support, at that
support the FE analysis gives a moment of 4.4 kNm,whereas a traditional empirical approach
gives 5.6 kNm. Traditional idealisations will assume that beams are rigid lines of support, but
this support is deflecting. The deflection diagram for the strip cut line can also be viewed as
shown below.
The relative beam deflections are obvious and in a stiffness analysis this will clearly have an
impact on the design shears and moments. In effect we have built-in modelling of support
flexibility in an FE analysis.
Orion Documentation page 160 Chapter 8 : Analysis and Design using FE
Effects of Adjusting the Beam and Slab Stiffnesses
The empirical code method takes no specific account of support flexibility, we can attempt to
emulate this by adjusting the relative stiffnesses of the beams and the slabs.
Increase the beam stiffness multiplier to 1.5 (arguably to account for the flanges), and decrease
the slab stiffness to 0.01. We would not suggest that such a large adjustment be used in
practice.
Chapter 8 : Analysis and Design using FE Orion Documentation page 161
In the view below we can see deflection contours and the moments determined on the strip.
These moments are actually more in line with the moments determined by the empirical
approach. The hogging moments are more regular but the peak is still a good bit higher than
determined by the empirical approach, 7.0 kNm as opposed to 5.6 kNm.
The sagging moments are similar but a little lower than determined by the empirical approach,
3.2 kNm as opposed to 3.4 kNm being the most extreme variation. (Ignoring the angled slab).
The empirical approach is deemed to include for load patterning and moment redistribution.
BS8110 also advises that where the loads are not patterned, there should be a 20%
redistribution of support moments with a resulting increase in sagging moments. In the
current model that would mean reducing the 7.0 kNm hogging to 5.7 kNm and increasing the
4.4 kNm sagging (end span) to about 5.0 kNm, and the 3.2 kNm sagging (internal span) to
about 4.4 kNm. This gives very good agreement on the hogging moments, but the sagging
moments are higher than determined by the empirical approach.
Note that for reasons made much clearer in the chapter on Flat Slab Models, the simple
principles of redistribution as traditionally applied to 2D frames do not make sense within the
more complex analytical geometry of a 3D FE model.
Orion Documentation page 162 Chapter 8 : Analysis and Design using FE
Returning to the previous model where the beam and slab stiffnesses might be regarded as
more reasonable, we did not have the extremely high hogging moments to start with. To some
degree by actually accounting for the beam stiffness we have shifted the BMD reducing the
hogging moments and increasing the sagging moments. Would it be safe to reduce the
hogging moments further? Should the sagging moments be amplified?
It is important that we do not regard the empirical approach as the correct answer, it is one
possible method that comes with documented limitations. When we analyse a complete 3D
subframe model we are dealing with a good analytical model, and it probably does not make
sense to start making lots of adjustments to try and make its results fit with those derived from
a table of coefficients.
Before accessing the postprocessor you do have the option to apply moment adjustment
factors as shown below.
We are unaware of any authoritative texts providing analysis and design guidance relating to
FE modelling and analysis. In considering the requirements to adjust the moments we are
probably considering serviceability rather than safety issues. This is all discussed in greater
depth in the chapter on Flat Slab Models. In that chapter we suggest that you should be very
cautious about applying negative adjustment factors of less that 1, it is suggested that you
might apply an adjustment to the positive (sagging) moments of up to around 1.2. Once again,
we emphasise that this is not the same thing as 20% moment redistribution.
If we return to the original beam and slab stiffness settings you can then review the results
after introducing a positive (sagging) moment multiplier as shown above.
Chapter 8 : Analysis and Design using FE Orion Documentation page 163
In the view below the hogging moments are unchanged, but the sagging moments are factored
up by 1.2.
Orion provides the tools to make such adjustments, but in the absence of any authoritative
guidance on the subject we cannot make any definitive suggestions. In this particular example
the unaltered moments seem to provide a reasonable set of design forces, when the option of
amplifying the sagging moment is used an even safer set is generated. If in doubt we can only
suggest that you consider making this sort of adjustment.
Orion Documentation page 164 Chapter 8 : Analysis and Design using FE
Effects of Wood and Armer Moment adjustments on a Regular Slab
Refer back to the section Plots Including Wood and Armer adjustments in this chapter for an
introduction to this. Consider the same strip (X1) swap to view the Design Moments, this
diagram shows the hogging and sagging moments after applying Wood and Armer
Adjustments. Note that in some places both a hogging and a sagging moment is generated.
In this case the 1.2 factor is still being applied to positive (sagging) moments. Comparing with
the previous diagram all the forces increase slightly, but the moment at the right hand end
where the support beam is angled to the line of the strip (and to the line of the reinforcement)
is more significantly increased.
The adjusted design moments are never (by definition) less than the unadjusted moments.
Designing based on adjusted moments is optional. Comparing the above with the moments
calculated based on tabulate code coefficients, you might feel even more justified in not
applying an amplification factor of as much as 1.2 to the sagging moments.
Chapter 8 : Analysis and Design using FE Orion Documentation page 165
Reinforcement Design
As you exit from the FE postprocessor a dialog is displayed.
The transfer option needs to be checked in order to pass FE results back to Orion for strip
design. The interpolation option is of little significance in beam and slab work. It is more
important in Flat Slab Models and it is therefore discussed in the chapter Flat Slab Models.
You can choose whether or not to use the design moments including Wood and Armer
adjustments.
Back in the main Orion graphical editor, you can select one or several strips. You can then
right click and select options to run a check design on any existing bars, or delete the bars and
then update the strip to design new bars.
You could for example design strips based on the empirical code method, and then update the
slabs to FE Strips and check the steel provided on the basis of FE results.
Orion Documentation page 166 Chapter 8 : Analysis and Design using FE
This may in fact be a very attractive option in many cases. In this example (since minimum
steel requirements dominate) the original steel works for the revised moments from FE.
Chapter 8 : Analysis and Design using FE Orion Documentation page 167
Merging Beam Results
What does this option do?
This option allows you to choose which results are to be used to design beams, on a beam by
beam basis you can use either:
The beam results obtained from the building analysis.
OR, the beam analysis results based on the FE analysis.
In fact, you do not have to choose, you can design all the beams using the results from the
building analysis and then check them all using results from the FE analysis.
When might you use this option?
Examples of when merging might be appropriate include:
1. Floor layouts containing transfer beams. A full discussion of this plus worked examples is
presented in a series of chapters beginning with the Overview of Solution Options for
Transfer Levels.
2. Complicated floor layouts where the traditional Yield Line approach to load
decomposition is inappropriate, and/or layouts that include significant cantilever beams
or slabs. Note that for this condition you also have the option of using the FE Load
decomposition and then continuing to work with the general building analysis.
3. In Flat Slab models where there are occasional beams, for example a perimeter edge beam.
Orion Documentation page 168 Chapter 8 : Analysis and Design using FE
Example
To illustrate grillage effects we can continue with DOC_Exampl e_04. In order not to destroy
the example for someone else you should then save the model with a new name before
proceeding.
In this example we will focus on the selected beam, 1B17. At the lower end of this beam, its
reaction is transferred to the long horizontal beam (1B2). At the top end the beam frames into
a wall.
After running the building analysis you can review the results. Beam 1B17 is supported at one
end on beam 1B2. This beam can be seen to deflect vertically, and rotationally it will act like a
pin, because the torsional stiffness factor used in the analysis was left at the default of 0.01.
Chapter 8 : Analysis and Design using FE Orion Documentation page 169
At the other end Beam 1B17 does not deflect as it is supported by a wall.
The shears and moments in this beam resulting from this analysis are shown below.
Orion Documentation page 170 Chapter 8 : Analysis and Design using FE
In addition to the above it is also worth noting the moments in the supporting beam 1B2 as
shown below.
Alternative Beam Results can be generated in FE and merged with Building Analysis Results
in either of two ways:
1. Using a Plateless model.
2. Using a fully meshed model.
We will look at each of these in turn in the following two examples.
Chapter 8 : Analysis and Design using FE Orion Documentation page 171
Option 1 A Plateless Model
Run the FE Floor analysis, use the settings shown below, then click on the mesh generation
option to create the model, then exit and analyse.
1. After analysis click on the option to merge beam results and merge results for all beams.
2. Now review the merged results for beam 1B17.
Orion Documentation page 172 Chapter 8 : Analysis and Design using FE
There is very good agreement between this result and that obtained by the building
analysis. This is to be expected because in the plateless model the slab does not participate
in the analysis. The slab loads are transferred directly to the supporting members based on
the yield line distribution method.
3. You can make similar comparisons on other beams in this model to see how the design
forces hardly change. On Beam 1B2 for instance, the moments are almost identical as
shown below.
Checking the Beam Designs
If you had designed all the beams based on the building analysis results you should be able to
see a summary table along the lines shown below.
Chapter 8 : Analysis and Design using FE Orion Documentation page 173
Having merged all the FE results, you can now carry out a batch check design using the option
not to revise the reinforcing and the utilisation ratios hardly change. The moment in beam
1B18 increases marginally so that its utilisation ratio is just greater than 1.0, sufficient to
register as a fail.
For this reasons illustrated in the Merging Beam Analysis Results section in the chapter
Transfer Beams General Method, we recommend that having analysed and designed all the
beams using one method (e.g. Building Analysis) you should then run a check design for
merged results to find any members that fail. At this point you should adjust (increase only)
the steel in those members interactively until they pass. Then you should find that you can
run a check design for either set of analysis results and everything should pass.
Again, it is worth noting that one of the most compelling reasons for not simply using FE
analysis, merging results and then designing for the merged results is that FE analysis does not
deal with patterned load, everything is fully loaded. It is very worthwhile trying to use the
general building analysis and then merge and check for FE results selectively.
Orion Documentation page 174 Chapter 8 : Analysis and Design using FE
Solution 2 A Meshed Model
Run the FE Floor analysis, use the settings shown previously, then click on the mesh
generation option to access the FE Analysis preprocessor. Mesh up the model and you should
see a mesh as shown below.
Exit from the preprocessor to analyse the model. After analysis click on the option to merge
beam results and merge results for all beams.
Chapter 8 : Analysis and Design using FE Orion Documentation page 175
Now review the merged results for beam 1B17.
In this model all the loads are applied to the shells, (no applied load will be displayed on the
beam loading diagram). However, the effects of the loading from both the shells and the
supported beam are clear to see on the shear force diagram.
Orion Documentation page 176 Chapter 8 : Analysis and Design using FE
In this case the design moments are in reasonably close agreement with those determined by
both the Plateless model and the building analysis model. It is important to note that this
result is related to the use of the slab stiffness multiplier that was set to 0.15. If we reset it to 1.0
and run the analysis again, the merged results for the same beam change as shown below.
The diagrams are similar, but the maximum shear and moments are all lower. This occurs
because the slab is sufficiently stiff that it starts to carry a significant proportion of the load
direct to the columns. Other aspects of this effect relating to slab design were discussed earlier
this chapter. In general, if you are designing beams using FE analysis results with meshed up
models, then you need to be very careful that the beam design forces are what you expect them
to be. This can often be achieved by setting the slab stiffnesses to be low or extremely low and
then perhaps ignore slab deflection results.
Checking the Beam Designs
Having merged the FE results for the meshed model the beam design can be checked in the
same way as described for the plateless model.
Chapter 8 : Analysis and Design using FE Orion Documentation page 177
Merging Column Results
What does this option do?
This option allows you to choose which results are to be used to design columns:
The column results obtained from the building analysis.
OR, the column analysis results based on the FE analysis.
When might you use this option?
Examples of when merging might be appropriate include:
1. Floor layouts containing transfer beams. A full discussion of this plus worked examples is
presented in a series of chapters beginning with the Overview of Solution Options for
Transfer Levels.
2. In any model where you have determined a need to merge beam results the possibility of
merging column results is also worth considering.
3. In Flat Slab models. Refer to the chapter Flat Slab Models for more information on this.
Orion Documentation page 178 Chapter 9 : Building Sway and Differential Axial Deformation Effects
Chapter 9 Building Sway and Differential Axial Deformation Effects
Introduction
The following section of the Engineers Handbook contains five chapters primarily relating to
the topics of Building Sway and Differential Axial Deformation Effects:
The Wall Modelling Considerations chapter discusses: alternative analytical
idealisations of walls, how model stiffness can be adjusted in order to force walls to resist
all lateral loads, and also how differential axial deformations can produce sway effects
under gravity load.
In the Sway Deflection Verification chapter a sway deflection comparison is made
between Orion and other analysis sofware.
The Overview of Bracing and Sway Sensitivity chapter clarifies the bracing and
slenderness classification procedures for columns and walls for each of the design codes.
The subsequent design implications are also examined.
The Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
chapter seeks to explain this 3D analysis effect, discusses whether it can be ignored for
design purposes and also looks at how it can be catered for if necessary by designing for
a wider envelope of forces.
The Using Staged Construction Analysis to Emulate Traditional Design chapter
investigates if it is possible to use staged construction analysis to deal with differential
axial deformation effects.
Chapter 10 : Wall Modelling Considerations Orion Documentation page 179
Chapter 10 Wall Modelling Considerations
Analytical Idealisations
Orion supports alternative analytical idealisations of walls.
This topic is discussed in detail within a training presentation that is available in PDF format
alongside this document and accessed via the link below.
Shear Wall Modelling Presentation.pdf
(If the link does not work please browse to find the file name indicated above in the HELP
sub-folder of the Orion Program Folder)
This presentation is given and discussed in detail during Orion Advanced Training Days.
Deflection
For deflection estimation the above presentation demonstrates that the alternative analytical
idealisations yield very similar results for any given input data.
However, if deflection estimates are to be regarded as meaningful they have to be based on
correct input and in this regard allowances must be considered in two areas:
Material Properties Deflections are directly proportional to the Youngs modulus value
you define as input, what is the correct value to use? A short term value may be
appropriate for wind loads, but perhaps a long term value should apply to notional loads?
Allowance for cracking gross section properties are used by default, should some
adjustment be made to allow for cracking? (It is understood that many engineers will
adjust (reduce) stiffnesses by up to around 50% to allow for cracking, the ACI code may be
referred to for some guidance in this regard.)
Cases where one wall option is Preferable
As is shown in the training presentation, the alternative wall modelling options will generally
produce very compatible results. In more unusual circumstances one option might be
considered preferable to another, such circumstances would include:
Very Short Walls
When walls are short the meshing may need to be very refined in order to generate more than
one shell along the length of the wall.
In such cases the mid-pier idealisation may be preferable.
Orion Documentation page 180 Chapter 10 : Wall Modelling Considerations
Very Long Walls
For very long walls the rigid arms extending from the mid-pier element are very long and
might not be sufficiently rigid to develop full out of plane effects. A good example of this
would be the case where out of plane beams attach to the extreme ends of a long wall (on one
side only). The torsional rigidity of the beam may not allow full beam end hogging moments
to develop.
In such cases the meshed wall idealisation may be preferable.
More importantly however is the fact that a long wall is designed as a single entity. A meshed
wall will allow varying deformations and concentrations of stresses along it's length, but the
results are all re-integrated to create a single set of design forces on the entire wall length. In
cases such as a basement wall that support a series of differently loaded columns and walls
along it's length this averaging may not be desirable. Consideration should be given to
breaking such a wall into a series of co-linear design panels that are then designed seperately
(exactly as an engineer would have traditionally considered strips within such walls)
Extreme Layout Variation between Floors
A good example of layout variation would be the case where a wall is broken into panels
around door openings at each floor level. However, the door positions are moving from one
floor to the next. The mid-pier element of wall panels in the upper floor are not therefore
directly above the mid-pier elements in the floor below.
From an overall building analysis point of view this is not a problem.
Provided that the mid-pier element of the wall above sits somewhere on the rigid arms of
the wall below this is not a problem.
In the special case where the mid-pier element of the wall above sits on a coupling beam
over an opening in the wall below the mid-pier model will generate some very
conservative design forces in the coupling beam. (As is discussed in relation to transfer
beams in the chapter Overview of Solution Options for Transfer Levels and onwards).
Hence in some specific circumstances the meshed wall idealisation may be considered
preferable.
Option to Check Both Ways
In considering the above it is worth re-emphasising that you always have the option to analyse
and design using one modelling option for walls and then at some stage reanalyse using the
other option and run a check design on all members. Any failures can then be isolated and
examined.
Wall Panel Design
The analysis phase described above determines Wall Panel Design Forces. Each wall panel is
then independently designed for these forces. Therefore, when Orion designs a wall panel it is
designing a discrete rectangular section. The design phase is discussed in detail in the chapters
Column Design to BS8110 and Wall Design and Detailing
Chapter 10 : Wall Modelling Considerations Orion Documentation page 181
Forcing Walls to resist all lateral loads
Orion uses the flexural stiffness of columns and core walls to resist lateral loading. This means
that sway effects introduce bending in both walls and columns/frames according to relative
stiffnesses. Typically walls are much stiffer and will naturally attract the vast majority of lateral
load. However, design codes tend to describe a more simplistic approach to lateral loading
advising that columns may be designed as braced (and hence designed for gravity loads only)
if walls or other bracing systems provide full restraint. In order to satisfy this some engineers
feel it is important to ensure that the walls are designed to resist 100% of the lateral loading. If
desired, this may be achieved in several ways in Orion.
Adjust Model Stiffnesses
In the analysis model options you can adjust the relative stiffnesses of walls/columns/beams.
You can make the walls stiffer and/or you can weaken the columns and beams.
Several Points should be borne in mind if such adjustments are made:
If changing the wall stiffnesses it is better to apply a factor to the E value since this will
apply to both the meshed and mid-pier modelling options.
If you only change the column stiffnesses then you will change the way in which moments
develop at beam/column interfaces. It makes more sense to make relatively equal
adjustments to both the beams and the columns.
If the above adjustment is made at not too extreme a degree (e.g. reduce beams and
column stiffnesses by factor of 0.5), then the analysis results are probably valid for design
of all members.
If extreme adjustments are made than it is probably safest to use these analysis results only
for a cross check on wall design. Therefore the approach to design might be:
Make no adjustments, analyse and design all members.
Make required adjustments, analyse, and check wall designs only.
Alternatively the check design might be carried out on a copy of the model as
described in the section below for very much the same reasons as stated below.
Orion Documentation page 182 Chapter 10 : Wall Modelling Considerations
Pin the Columns
This approach seems to be used in practice but needs to be used with more caution than the
stiffness methods described above. Fictitious pins are assumed and applied at the top and
bottom of every column. It is recommended that a copy of the model is made and that the
pins are created in the copy. After analysis design should be restricted to the wall members
only, designing beams and columns for analysis results based on the existence of assumed pins
could result in serious design flaws.
Sway Effects Under Gravity Load
Most models will sway to a small degree when subjected to purely vertical loads. For most
models/structures this effect is likely to be quite insignificant. For some models it could be
more significant.
In this section of this chapter we will show that:
1. This effect relates to differential axial compression within the lateral load resisting
elements of the structure, primarily shear and core walls.
2. This effect is always exposed by any analysis of a fully framed structure.
3. This effect can be exposed in Flat Slab models which are stabilised by core walls.
4. There are many reasons why this effect will generally be insignificant in terms of design.
Fully Framed Structures
Chapter 10 : Wall Modelling Considerations Orion Documentation page 183
The structure above is a very simple 10 storey model with a single C-Shape core which is
completely offset to one side of the building. For the purposes of this example only, all the
beams have been pinned at both ends thus eliminating any frame action which would provide
sway stiffness. The structure is therefore completely reliant on the core walls for stability.
The first point to note is that this is an extreme example. The view below shows how the
building sways and twists under the action of notional loads.
The twisting effect is considerable and the maximum deflections at the top floor actually
exceed 1 m. A real structure cannot be acceptably stabilised by such an eccentric C-Shape
core.
When we consider the dead load case (where only vertical loads are applied) lateral sway is
also evident as shown below.
Why does this sway happen?
In the view above the vertical stress contours are also shown in the core walls the variation of
stress along the length of the flanges of the C-shape core is evident.
Orion Documentation page 184 Chapter 10 : Wall Modelling Considerations
The design forces in the wall panels at first floor level are shown below. Note that the loads in
the flanges 1W1 and 1W3 are higher than in the web 1W2. The average load per meter in
these shorter flanges is therefore a lot higher.
Looking at this view it is possible to imagine how the effective centre of loading applied to the
C-shape core is offset to the right and above its centroid (which will be quite close to the
centre of rigidity shown in the view above). The eccentric load causes an unresisted curvature
in the core and hence sway develops at the upper floors.
The same effects are evident regardless of whether meshed or mid-pier idealisations are used.
Before moving on to look at a very similar model but using flat slabs it is worth noting that the
total Imposed Load in the three panels of the above core wall is 626 + 229 + 403 = 1258 kN.
Chapter 10 : Wall Modelling Considerations Orion Documentation page 185
Structures Incorporating Flat Slab Areas
As is noted above the sway effect arises because of the eccentric application of load to a core
wall. The magnitude of the sway is related to the magnitude and point of application of the
axial load.
Slab Loads Yield Line Decomposition
If this building is analysed using yield line decomposition of slab loads then a message is
displayed to indicate that the building analysis has not captured all the applied loads.
Orion Documentation page 186 Chapter 10 : Wall Modelling Considerations
At this stage the analysis results displayed on plan will show no loads in columns and some
loads in walls.
The amount of load in the walls will be incorrect, it could be too high or too low, in this case
the total Imposed Load in the three panels of the above core wall is 275 +139 + 276 = 690 kN
a lot less than was derived in the model where pinned beams were included.
Basically, as is well documented elsewhere, this building analysis is of no value as regards the
dead and imposed load cases. For a flat slab model the design cases for the dead and imposed
loads would usually come from the merged results of an FE chase down.
Chapter 10 : Wall Modelling Considerations Orion Documentation page 187
Slab Loads FE Decomposition
However, the loading applied to the walls (not the columns) can be corrected by using the FE
load decomposition option (refer to the section Switching between Yield Line and FE load
Decomposition in the chapter Beam Loads and Load Decomposition Methods for more
information on this option). After making this change the loads in the walls change as shown
below.
The total Imposed Load in the three panels of the above core wall is now 768 11+ 695 = 1452
kN. As a total this is not too dissimilar to the 1258 kN total given for the model that included
the pinned beams, slab continuity effects in the FE analysis mean that more load is attracted to
the core in this case. This load is also more eccentric with the result that tension develops in
the web (for this extreme example.
Orion Documentation page 188 Chapter 10 : Wall Modelling Considerations
Once again the sway of the structure for the gravity load case is evident in the analysis
postprocessor view and the variation of stress along the length of the flanges of the C-shape
core is also evident.
In this example the maximum sway that is developing is 65 mm, the discussion below should
put this in some context.
Discussion
Load Eccentricity
As noted at the outset, the model used above is an extreme example. In order to generate the
most extreme offset loading within the C-shape core it is positioned along on edge of the
model. In this position this single core cannot stabilise the structure effectively. The sway
under notional load cases exceeds 1000 mm. This structure is not something that would be
built.
Chapter 10 : Wall Modelling Considerations Orion Documentation page 189
Where structures are stabilised by a single core, the core is normally positioned more centrally
and will tend to attract more uniform loading.
If the example is adjusted as shown above so that the core attracts load from all sides then the
sway under gravity load only drops from 65 to 13 mm (everything else being equal). Even so
this structure still undergoes very significant sway due to notional loads and would again
probably not be something that would actually be constructed. (The open C-Shape of the core
is very susceptible to twist.)
Construction and Creep Effects
In the event that sway induced by gravity loads seems significant and some estimation of the
actual displacement is required then some thought should be given to the sequence of
construction and to subsequent creep effects.
The sway is occurring as a result of differential axial deformation within the walls. This axial
deformation is a combination of immediate deformations each time a new floor is supported
and ongoing creep deformations. Both of these effects are time dependent. When a floor load
is added the concrete in the walls that support the floor will be younger in the floor
immediately below and progressively older at lower floors. The younger concrete will see a
greater immediate deformation and a greater long term creep deformation as a result of any
applied load. A detailed discussion of this is beyond the current scope of this handbook, but it
is worth noting that there would be a good deal of common background with the discussion of
flat slab deflections accessed via the chapter on Flat Slab Models.
Orion Documentation page 190 Chapter 10 : Wall Modelling Considerations
A very sophisticated assessment of this effect would take account of construction sequencing
and time dependent effects. In such circumstances the result needs to be assessed for
sensitivity to variations in the assumptions on which they are based. To be fully accurate this
analysis would need to take account of the fact that some of the deflection would be
constructed out as the walls are constructed as vertical as is practical during construction.
In fact the result achieved by any such complex analysis will lie somewhere between two
extremes that might be predicted more readily be a simple linear static analysis using different
E (Youngs Modulus) values for the concrete.
A short term E value might be used to estimate a minimum value for the total deflection.
In the case of walls cracking effects can probably be discounted so only additional creep effects
need to be considered. It is likely that the net effect of creep will be something less than a
doubling of instantaneous deflection. Hence the value determined above could be doubled, or
another analysis could be made with E set to half of the short term value.
Note Where flat slab models are being considered it is common practice to use long
term values of E set at around of the short term value. When this has been
done deflection estimates of sway arising from the building analysis are likely to
be too high, perhaps by a factor of 2 based on the suggestions above.
Discrete Cores
Where structures have discrete cores or numerous discrete walls providing stability the effects
will often counteract each other.
In the above view the model is mirrored so that there are two C-shape cores. This model does
not sway at all in the X direction under gravity load and the vertical load contours indicate
relatively uniform stresses within the cores.
Chapter 10 : Wall Modelling Considerations Orion Documentation page 191
In this case the two cores lean against each other, the diaphragms at each floor stop any
curvature from developing. The axial loads in the wall panels at first floor level are much
more uniform as shown below.
The total Imposed Load in the three panels of the above core wall is now 435 + 663+ 324 =
1422 kN. On a panel by panel basis these are very different forces than were given by the
un-mirrored model, but the total for the 3 panels is very similar to the 1452 kN given
previously. Note that the major axis moments in the wall panels are also much reduced.
Results based on an FE Chase Down
For most models engineers will be happy to use the panel design forces merged from an FE
analysis chase down. In this case the results for this core wall would then be as shown below:
Orion Documentation page 192 Chapter 10 : Wall Modelling Considerations
Once again the distribution of forces in the 3 wall panels is different, but the total Imposed
Load is very similar at 561 + 391+ 473 = 1425 kN. The FE Chase down method does not deal
with sway introduced by differential axial compression in the core walls over the full height of
the building. It does however introduce more minor axis bending effects where the walls
interact with the slabs.
For many walls supporting flat slab floors the minor axis bending can be more significant in
the panel design than variations in axial load and major axis moment that may be introduced
by sway effects.
For this simple 10 storey example building, despite the fact that the sway effects have been
forced to be unrealistically extreme, the walls only require nominal reinforcement regardless
of which set of design forces their design is based on.
It is suggested that for flat slab models it is important to have always designed the walls for the
loads generated based on an FE chase down. You then have the option of cross checking these
designs for the results generated by a building analysis where wall loading has been
determined using FE decomposition at each floor.
Closing Summary
In this section we have been discussing Sway Effects Under Gravity Loads, it is important to
emphasise that this relates entirely to sway that is generated in the presence of purely vertical
applied loads.
The possibility of sway developing due to differential axial shortening is something that would
have been routinely ignored in hand calculations by most engineers looking at most
structures.
This has nothing to do with notional loads which are applied separately and will always be
designed for provided you have included them in your design combinations.
For framed models in Orion the effect is always included / exposed by the 3D analysis.
For flat slab models the effect will not be exposed by an FE chase down but can be exposed if
desired. It is emphasised however that we recommend walls are designed for the loads from
an FE chase down and then a subsequent check design can be made for building sway effects if
desired. For many reasons noted within the text of this section it is anticipated that this check
will only produce more critical design in tall buildings and/or quite extreme examples.
Chapter 11 : Sway Deflection Verification Orion Documentation page 193
Chapter 11 Sway Deflection Verification
Introduction
In order to produce a sway deflection comparison against other analysis software, a 20 storey
building is analysed in Orion using both mid-pier and meshed idealisations of walls. (The
Example 20 Storey Building described in the later chapter on Differential Axial Deformation
Effects is used for this purpose.)
The results for lateral load cases are then compared against other analysis packages.
Example Model:
Comparison of Orion's alternative wall modelling options
The model is initially analysed in Orion using a mid-pier idealisation of the wall panels. The
analysis is then repeated using the alternative meshed FE shell model idealisation.
Orion Documentation page 194 Chapter 11 : Sway Deflection Verification
Shown below is a comparison of the two sets of results.
It can be seen from the above that both midpier and meshed FE shell wall modelling options
work equally well.
Compare analysis results using other software
Orion models can be exported to other analysis software such as S-Frame or SAP. The models
created for this example were exported and the results for both the mid-pier and meshed
idealisations of walls are compared in the tables below.
Mid-Pier Wall Model
Mid-Pier Wall
Model
Meshed Wall
Model
Difference
Applied dead load 39187 39187
Decomposed dead load 39187 39187
Dead load reaction 39187 39187
Applied live load 11985 11985
Decomposed live load 11985 11985
Live load reaction 11985 11985
Wind X max (mm) 101.6 100.1 -1.5%
Wind X min (mm) 101.3 99.6 -1.5%
Wind X max resultant (mm) 101.8 100.3 -1.5%
Wind Y max (mm) 79.9 76.0 -4.9%
Wind Y min (mm) 35.9 35.8 0
Wind Y max resultant (mm) 81.7 77.7 -4.9%
Orion S-Frame SAP
Dead load reaction 39187 39187
Live load reaction 11985 11985
Wind X max (mm) 101.6 101.6 101.6
Wind X min (mm) 101.3 101.4 101.3
Wind X max resultant (mm) 101.8 101.7
Wind Y max (mm) 79.9 79.9 79.9
Wind Y min (mm) 35.9 35.9 35.9
Wind Y max resultant (mm) 81.7 82.5
Chapter 11 : Sway Deflection Verification Orion Documentation page 195
Meshed Wall Model
* For the Etabs comparison the model was constructed by a 3rd party. In this model the
default wall idealisation was not used, the walls were meshed more finely. CSC do not
assume responsibility for the accuracy of this model.
Orion S-Frame SAP ETABS*
Dead load reaction 39187 39187
Live load reaction 11985 11985
Wind X max (mm) 100.1 100.2 100.1 104.3
Wind X min (mm) 99.6 100.0 99.9
Wind X max resultant (mm) 100.3 100.3
Wind Y max (mm) 76.0 76.2 75.9 79.9
Wind Y min (mm) 35.8 35.8 35.8 35.7
Wind Y max resultant (mm) 77.7 78.4
Orion Documentation page 196 Chapter 12 : Overview of Bracing and Sway Sensitivity
Chapter 12 Overview of Bracing and Sway Sensitivity
Introduction
The purpose of this chapter is to clarify the bracing and slenderness classification procedures
for columns and walls for each of the design codes. The subsequent design implications are
also examined.
Automatic Assessment of Sway Sensitivity
Sway sensitivity is automatically determined in Orion when the design code is set to EC2.
For other codes as discussed below, an assessment of sway sensitivity can also be made,
however it should be noted that this is based on analytical results and the recommendations of
the ACI code.
Whenever sway sensitivity is assessed automatically you are advised to be aware of the
limitations that apply, these can be viewed by clicking the Limitations button on the Building
Analysis/ Reports tab.
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 197
User Defined Bracing
In both the BS8110 code and also CP65 there are no provisions for assessing sway sensitivity
by analytical methods.
Therefore, when using BS8110 or CP65 you need to check the option for User Defined Bracing
for Columns and Walls and then apply the condition (braced or unbraced) that you deem
appropriate for the building.
If you do not check this option then Orion will make an assessment of sway sensitivity based
on analytical results and the recommendations of the ACI code.
Note however that this assessment is deflection dependent and that the ACI code gives
guidance on appropriate adjustments to section/material properties to be used in the building
analysis for the purposes of this assessment. Such adjustments will increase the deflection
value used in the checks.
Note that the check can result in different classifications for different storeys which is not a
condition that is recognised by BS8110. We continue to advise that this assessment is used
cautiously and that when the appropriate overall condition is determined that this should be
applied as a user-defined classification (in accordance with BS8110).
Orion Documentation page 198 Chapter 12 : Overview of Bracing and Sway Sensitivity
Classification Requirements of each code
The classification procedures in each of the codes are as follows:
BS8110 (similarly CP65 and HK-2004)
Bracing Classification In BS8110 columns (and walls in minor axis direction) are
considered as braced if lateral stability is provided (predominantly) by walls or other stiffer
elements. This classification remains a matter of engineering judgement.
Global P-Delta Effects it is an inherent assumption in the above that walls provide
sufficient lateral stiffness that global sway of the building is small and hence "Big" P-delta
effects can be ignored in braced structures. For un-braced structures there is no clear
statement on whether or not global P-Delta is also considered ignorable or is simply
considered to be adequately catered for in the amplification of design moments noted below.
Slenderness Classification this is based on the effective length. In braced structures
effective lengths are < 1 and in un-braced structures effective lengths are > 1. It is considerably
more likely that a member gets classified as slender when it has been classified as un-braced.
Short (Non-Slender) Members will see no amplification of moment at all, even if they are
un-braced.
Slender Members (Members susceptible to P-Delta effects)
Braced-Slender Elements - additional moments are calculated based on effective length
and are considered to be a maximum at around mid height. These moments are not added
to the highest end moment so this may or may not end up being a critical design
condition. This additional moment is clearly intended to cater for "little" P-delta effects
(strut buckling)
UnBraced-Slender Elements - additional moments are calculated based on effective length
(which is longer and hence additional moments will be greater), and are considered to be a
maximum at the member ends. The additional moment is added to the highest end
moment so this will always end up being a critical design condition.
It is assumed that this amplification of the critical design condition is intended to cater for
both big and little P-delta effects.
The advantage of the above procedure is that moment amplification in each column is related
only to the classification and slenderness of that column. Where columns are unbraced this is
not entirely logical and cl3.8.3.8 does provide an option where the average slenderness effect
for an entire unbraced storey level can be used for all members at that level. Typically this
would mean that members which are un-braced but not slender add to an average stiffening
effect and so the design should be less conservative. This option is not applied in Orion
because the design procedure would become highly iterative (the design of every column
would affect the design of every other column at an un-braced level and moment
amplification would need to be introduced to non-slender members).
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 199
ACI 318-02
When the design code is set to BS8110, CP65 or HK-2004; if you uncheck User Defined
Bracing for Columns and Walls, a facility is made available for assessing the susceptibility of
individual storeys to P-Delta effects. This uses the ACI method of classification during the
building analysis.
Bracing Classification using the ACI approach each storey level within a building is
classified as sway or non-sway. The code also provides a method allowing analytical
assessment of this classification based on deflections arising from a linear analysis of the
structure.
Global P-Delta Effects when a storey is classified as "non-sway" then it can be assumed that
global P-Delta effects are small enough to be ignored at that level. When a storey is classified
as "sway" then the frame analysis results need to be amplified in some way, options given are:
A second order analysis (which would inevitably affect all members in the structure)
Approximate moment magnification methods (cl.10.13.2 appears to indicate that this
moment amplification only needs to be applied to the slender members at each floor level
(similar to BS8110) is this logical? - or should this amplify the sway moments in all
columns and walls on a level by level basis?)
Slenderness Classification this is based on the effective length. At "Non-sway" levels
effective lengths are < 1 and at "sway" levels effective lengths are > 1. It is considerably more
likely that a member gets classified as slender when it exists at a "sway" level.
Short (Non-Slender) Members will see no amplification of moment at all even if they are at
"Sway" levels.
Slender Members (Members susceptible to P-Delta effects)
Slender Elements at Non-Sway Levels - additional moments are calculated based on
effective length and are considered to be a maximum at around mid height. These
moments are not added to the highest end moment so this may or may not end up being a
critical design condition.
In essence the approach here is identical to that used for braced slender members in
BS8110.
Elements at Sway Levels - as noted above the end moments of all members may be
amplified to account for Global P-Delta effects. If a member at such a level is classified as
slender, the calculation of the magnified moment is not based on the effective length of
each individual member, moment magnifiers are based either on the stability index for the
floor (cl.10.13.4.2) or an assessment of the average buckling capacity of all members at the
floor (cl.10.13.4.3 - similar to the optional method in BS8110).
The additional moment is added to the highest end moment so this will always end up
being a critical design condition.
Additional check (cl.10.13.5) - having amplified the end moments there is a requirement
to check that intermediate slenderness effects (using effective length = 1.0L) are not more
critical.
Orion Documentation page 200 Chapter 12 : Overview of Bracing and Sway Sensitivity
While the method of moment amplification is different for slender members at sway levels, the
general principles of moment amplification are the same in BS8110 and ACI and the terms
used for classification are interchangeable:
BS8110 Braced = ACI Non-Sway
BS8110 Un-Braced = ACI Sway
The ACI has the advantage that the classification is not a matter of engineering judgement and
also that it introduces the flexibility to mix both braced and un-braced classifications within
one structure.
The ACI amplifications are applied only to lateral load cases - this does not address the fact
that sway will occur as a result of vertical loads applied to any unsymmetrical structure and
hence ignores the possibility that significant P-delta effects could accrue due to this aspect of
sway. However, for the majority of "building" type structures this simplification/assumption is
likely to be acceptable.
There does seem to be a question mark relating to the ACI approach for slender columns. If
the sway moment amplification is made using the stability index then should the column be
taken into design as a braced column using an effective length = 1.0 (because the unbraced
(global P-Delta) aspect of slenderness has already been allowed for?). This seems much less
conservative than the suggested implementation procedure for EC2 discussed below.
EC2
In EC2 similar terminologies are used but the meanings are different:
Cl 5.8.1 - Introduces concept of braced and bracing members.
Cl 5.8.2 - Second Order Effects - this clause distinguishes between global effects (applying
to the whole structure) and isolated member effects (slenderness).
Bracing Classification Bracing members are the members which are assumed to provide
the lateral stability of the structure. Columns and walls that are not bracing members are
classified as braced. Unfortunately there is an element of engineering discretion involved in
this classification which will be discussed later.
Global P-Delta Effects there is some guidance on determining if these effects can be
ignored (For the purposes of this discussion we will classify structures in which global P-Delta
effects cannot be ignored as "sway sensitive"). Cl 5.8.3.3 (1) gives a simple equation that is only
applicable in limited circumstances and is actually also difficult to apply. Initial calculations
using this equation have suggested that it would be too conservative resulting in too many
structures being classified as sway sensitive.
Annex H provides slightly more general guidance. In order to automate the Annex H
classification in Orion, the approach has been modified to become similar in principal to the
ACI classification method. It is noted that a single classification gets applied to the entire sway
resisting structure (the bracing members). If it is determined that global P-Delta effects
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 201
cannot be ignored (the structure is sway sensitive) then the approach becomes a user driven
procedure, in which the sway loads are amplified in accordance with Annex H. This is a
relatively simple procedure applied as follows:
1. View the sway sensitivity report to obtain the suggested load amplification factors.
2. Apply this amplification to the existing load combination factors.
3. Re-analyse using the option to over-ride further sway sensitivity assessment and design
the structure as if it is not sway sensitive (because the global P-Delta effects are now
catered for).
Tests have indicated that the sway sensitivity assessment procedure described above results in
a non-sway classification for the vast majority of structures .
Note Although the classification applies to the bracing members, it is impossible to
isolate these when analysing the structure, so P-delta forces (introduced by load
amplification or P-delta analysis) will accrue in all members (braced or bracing,
short or slender).
Slenderness Classification this is based on the effective length. For braced members
effective lengths are < 1 and for bracing members effective lengths are > 1. It is considerably
more likely that a member gets classified as slender when it has been classified as a bracing
member.
Short (Non-Slender) Members:
As noted above, if these members exist in a sway sensitive frame then there may have been
some amplification of the design forces introduced during the general analysis procedure.
no other amplification of moments is then applied.
Slender Members (Members susceptible to P-Delta effects)
Slender Braced Members - additional moments are calculated based on effective length
and are considered to be a maximum at around mid height. These moments are not added
to the highest end moment so this may or may not end up being a critical design
condition.
In essence the approach here is identical to that used for braced slender members in
BS8110 and ACI.
Slender Bracing Members - as in BS8110 - additional moments are calculated based on
effective length (which is longer and hence additional moments will be greater). Un-like
BS8110 the additional moment does not have to be added to the highest end moment
(because the end moment is already amplified if the structure is sway sensitive). In EC2
additional moments in slender members are introduced in the same way regardless of
whether or not the member exists in a sway sensitive frame.
In summary - it seems EC2 maintains a distinction between global P-delta effects and local
slenderness effects which potentially results in a 2 stage amplification of moments. Once the
sway sensitivity is assessed the global P-Delta effects are introduced in the analysis results as
necessary. For the local slenderness effects the general principles of moment amplification in
EC2 are very similar to those applied in BS8110:
EC2 Braced = BS8110 Braced
EC2 Bracing = BS8110 Un-Braced (but we would expect that the EC2 amplification might
be lower since the BS8110 amplification at this point mixes both global and local effects
whilst in EC2 any global effects would already have been introduced).
Orion Documentation page 202 Chapter 12 : Overview of Bracing and Sway Sensitivity
Implementation of EC2 Classification in Orion
Setting the Braced/Bracing Members
EC2 requires the user to distinguish between the braced and the bracing members of a
structure. This can be specified on the Lateral Drift tab of Building Parameters. Note this
setting has nothing to do with assessing sway sensitivity which is dealt with separately.
The purpose is to identify Bracing Members in each Global Direction (The member types that
contribute to lateral stability of the building). The default setting is as shown above, (columns
considered to be braced; walls considered to be braced about their minor axis, but to provide
bracing to the structure about their major axis).
Assessment of Sway Sensitivity
Most of the guidance surrounding EC2 suggests/assumes that most buildings will be classified
as non-sway. Essentially the expectation is that the assumption made in BS8110 design, that
any building stabilised by shear/core walls is non-sway, will prove to be correct.
Whether this proves to be true is somewhat irrelevant, the fact is that sway sensitivity
classification has to be made and the Eurocode provides three options for doing this:
1. Use cl 5.8.3.3 (eq5.18)
2. Use guidance from Annex H
3. Do a P-Delta analysis and check that the change in results is less than 10% (cl 5.8.2), if true
than you can revert to linear elastic analysis.
Note The Annex H guidance has been adopted for the first Eurocode release of Orion.
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 203
If the structure is classified as sway sensitive then there are two options for dealing with this:
1. Annex H - Application of increased horizontal forces.
2. Do a P-Delta Analysis
In fact there is a third option which might be applied when an engineer discovers a building is
sway-sensitive - they may find a way to add more shear walls and change the classification!
Initially the P-delta option may seem attractive but it must be recognised that EC2 is very clear
on the fact that realistic member properties accounting for creep and cracking must be used
and the calculation of these properties becomes a unique procedure for every member.
Note For sway sensitive structures, the Annex H guidance has been adopted for the
first Eurocode version of Orion.
Worked Example for a Sway Sensitive EC2 Structure
A model is constructed as shown above with two 3m wall panels providing stability in each
direction.
Floor to floor ht= 3.0 m
Wall Length / Width= 3m / 0.2m
Concrete Grade= C30/37
G= 7 kN/m2 (total including walls)
Q= 2.5 kN/m2
Beams are provided for load collection only - they are pinned at both ends in order that lateral
loads are focussed in the shear walls.
Orion Documentation page 204 Chapter 12 : Overview of Bracing and Sway Sensitivity
Model Analysis Properties
The notes with eq H.8 indicate that cl 5.8.7.2 should be referred to - the stiffness of the
members used in the analysis leading to the classification must be adjusted and Cl 5.8.7.2 is
referred to for the adjustment.
Cl 5.8.7.2 gives a procedure for calculation of Nominal Stiffness of compression members.
Rigorous use of this clause would require iteration since the adjusted properties are member
specific (load and reinforcement and even direction dependent).
Simplified alternatives are given, the simplest of which still involves the use of theta-ef (the
"Effective Creep Ratio") which remains a member specific calculation.
Note For the first Orion Eurocode version these adjustments are left entirely to the
user.
Referring to eq 5.26, if we assume theta-ef is around 1.5 then the suggested approximate
stiffness adjustment can be calculated:
Kc = 0.3 / (1 + 0.5*theta-ef) = approx 0.175
For the beams adjustments must be made to allow for creep and cracking - assume:
I-cracked = 0.5 I-conc
(eqn5.25) Ecd-eff = Ecd / (1 + theta-ef) = Ecd / 2.5
Therefore total adjustment to EI = 0.5/2.5 = 0.2.
Overall it seems that initial adjustments might be as low as 0.15 to 0.2 EI for all members. To
put this in perspective consider the slightly more concise advice given in the ACI. ACI
suggests reducing stiffness (EI) by a factor of 0.35 (or 0.7 if the members can be shown to be
uncracked). It is also noted that the 0.35 factor should be further reduced if sustained lateral
loads are applied, it seems logical that notional loads should be regarded as sustained lateral
loads. Therefore, a 0.2 adjustment factor may prove to be a little over conservative, but it is not
wildly different to the ACI advice.
Consider also that ACI classifies a building as sway sensitive when Q > 5% while EC2 allows
this to increase to 10% - therefore, if the EC2 adjustment factor is around 0.175 compared to
ACI factor of 0.35, then the classifications of the buildings would be almost identical.
ACI Classification (for comparison)
Member Properties are adjusted before analysis as shown above. Note that the recommended
column and beam adjustment is 0.7 and for cracked walls it is 0.35.
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 205
The report shows the structure is classified as sway-sensitive at all but the lowest floor level.
In the ACI only 5% second order effects are assumed to be ignorable. Q is the measure of this
and at this point it is interesting to note that although Q is only marginally smaller than 0.05 at
the lowest level, it becomes quite significantly greater at the top level.
In fact, if we reduce this to a 4 storey building then the report below shows that the structure is
still classified as sway-sensitive at the upper levels.
Note As shown above, P-Delta effects can be proportionally higher at upper levels .
Orion Documentation page 206 Chapter 12 : Overview of Bracing and Sway Sensitivity
EC2 Classification to Annex H
Based on the discussion in Model Analysis Properties, member properties are adjusted before
analysis as shown above. Note that although we are using 0.17, you may decide on a higher or
lower value based on your engineering judgement.
The report shows that the 5 storey structure is classified as sway-sensitive at all floor levels.
In EC2 10% second order effects are assumed to be ignorable. Q is the measure of this and so
the actual check is that if Q > 0.1 then the classification is sway-sensitive. For the figures above
we can see this is true at all levels.
It is noted that although Q is only marginally greater than 0.1 at the lowest level, it becomes
quite significantly greater at the top level.
Chapter 12 : Overview of Bracing and Sway Sensitivity Orion Documentation page 207
In fact, if we reduce this to a 4 storey building then the report below shows that although Q
becomes less that 0.1 at the lowest level, the structure is still classified as sway-sensitive at the
upper levels.
Although the reduced section properties together with the increased ignorable P-Delta
amplification limit means that the threshold for sway-sensitive/non-sway classification is very
similar for the two codes, the amplification factors that apply to buildings that are classed sway
sensitive are bigger (double) for EC2.
EC2 does not seem to recognise the concept that a building can have different sway sensitivity
at different levels, a single classification and amplification factor is applied to the whole
building. This requirement is catered for in the report by including an extra line for All
storeys. In the above 4 storey example the Q value calculated for All storeys is 0.1497
(therefore sway sensitive).
Total deflection = 5.99mm
Total Axial Load (F-V.Ed)= 30349
Total Shear Load (F-H.Ed)= 101.2
Total height = 12m
Q = 1.5 (30349 * 0.00599) / (101.2 *12) = 0.1497 > 0.1 (therefore sway sensitive).
Orion Documentation page 208 Chapter 12 : Overview of Bracing and Sway Sensitivity
Application of Load Amplification Factors
Provided the model is classified as non-sway no further adjustments are required - the
member design is performed using the existing load combinations and factors.
If (as in this case) the model is classified as sway-sensitive, the second-order effects must be
accounted for in the design. As previously stated, the code provides two options for achieving
this:
Annex H - Application of increased horizontal forces.
Do a P-Delta Analysis
In the current version of Orion the former approach is adopted - when the model is classified
as sway-sensitive a load amplification factor is automatically applied to the existing design
load combinations.
The amplification factor, Delta-s, is calculated from the Q value for All storeys as follows:
Delta-s = F
H,Ed
/ F
H,0Ed
= 1 / (1-Q)
In the original 5 storey example Q = 0.271. Hence the amplification factor displayed on the
Horizontal Drift Classification Report is
1/(1-0.271) = 1.372.
It is possible to over-ride this value if required and enter an amplification factor based on your
own engineering judgement. To do this, re-display the Building Parameters, then from the
Lateral Drift tab check the box to apply the User-defined Sway Amplification Coefficient. You
can then over-ride the automatically calculated value in one or both directions.
If you have applied user-defined sway amplification co-efficients, it is not necessary to
re-analyse the building before the members are designed.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 209
Chapter 13 Overview of Differential Axial Deformation Effects in 3D Analysis of
Buildings
Introduction
Differential axial deformation will occur in the 3D analysis of any typical building frame. This
deformation can significantly affect beam bending moments. For the purposes of discussion
the effect is referred to as a "Differential Axial Deformation Effect" (DADE).
During any analysis members subject to compression will shorten. In a concrete frame
columns and walls under compression will both shorten. Highly stressed members will
shorten by greater amounts than lower stressed members. Where two adjacent members
shorten by a different amount there will be an effect (DADE) introduced in any members that
attach to both the shortening members.
Example:
Central column shortening by more than external columns introducing bending
effects in connecting beams.
CSC have previously sought to raise engineers awareness of this and other 3D analysis effects
by illustrating them in seminars held around the world. This particular effect is known and
studied by academia, one reference that provides a good overview is:
Effects of Axial Shortening of Columns on Design and Construction of Tall Reinforced Concrete Buildings
By M.T.R. Jayasinghe and W.M.V.P.K. Jayasena
Available to download from the ASCE Research Library (http://www.ascelibrary.org)
Focusing on DADE, the key points of the discussion in these notes are:
Traditional methods of idealising sub-sections of structures for design purposes inherently
completely ignore this effect. However, the existing building stock which is largely
designed in this way appears serviceable, it seems that ignoring DADE has not caused any
significant problems.
An analysis of a complete 3D model of a structure will inherently introduce this effect.
Designers with experience in the traditional method look at the analysis results of a full 3D
analysis and will quite rightly question the design forces that are displayed.
There is a demand to use 3D analysis but at the same time find a way to achieve member
design forces that are reasonably close to the forces that would always have been used.
These notes demonstrate methods of achieving this.
Checks are required to establish whether the method used has had an impact on sway
deflections. If it does not then potentially designers can stop at this point on the basis that
the traditional design approach has been reasonably emulated.
Orion Documentation page 210 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Potentially engineers will also want to consider that DADE should not be completely
ignored. These notes show how a second analysis run could be made so that the initial
design can be checked and strengthened as necessary. In essence this means that the
structure ends up being designed for a wider envelope of design conditions (forces),
clearly this must be a conservative approach.
Concerns have been expressed that designing for this envelope could be uneconomic. For
an example model it is shown that the additional reinforcement associated with this
conservative approach is quite nominal.
It is important to re-emphasise that although this discussion is in relation to Orion, the effect
under discussion will occur in any analysis software. Equally, most of the suggested strategies
for dealing with this effect could be applied in other software.
Finally, the possibility that staged construction analysis will somehow easily deal with this
issue is often raised. This point is covered in the closing discussion the key points being that:
Staged Construction is not a simple analysis technique.
It does not generate results that emulate traditional design (i.e. DADE is not completely
eliminated)
If it is not used with a reasonable degree of care and understanding then a staged
construction analysis can be a sophisticated and time consuming way of getting dubious
answers.
Opening Discussion
In these notes we will establish some traditional sub-frame results for beams at the 20th floor
of a building and then look at how closely these results can be emulated using full 3D analysis.
Several general discussion topics should be borne in mind as the results are compared.
Traditional practice for the analysis and design of multi-storey concrete frames has involved a
significant degree of idealisation of the structure:
Lateral load is often assumed to be exclusively resisted by a selected subset of members:
Special models are constructed to determine the member forces which develop when
lateral loads are applied.
It is quite normal to ignore the sway that can be introduced when pure gravity load is
applied to a non-symmetrical structure.
For the remaining structure only gravity forces are considered:
Column and beam design is based on "sub-frame" analysis.
Typically sub-frame support points are assumed to provide rigid vertical support, the
possibility of elastic deformation of the support is ignored.
The result is that designs would be the same for the beams on the 20th floor as on the 1st
floor.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 211
We present the results from the traditional analysis as a target "baseline" result. This should
not be confused with being a "correct" result. A few thoughts on this:
A Quote:
"Engineering (and some may think FE practice also) is the art of modelling materials
we do not wholly understand, into shapes we cannot precisely analyse, so as to
withstand forces we cannot properly assess, this in such a way the public and
(hopefully) the customer has no reason to suspect the extent of our ignorance."
Structural Engineering Modelling and Analysis,
by Arthur T. Murphy
The Structural Engineer - 3rd Feb. 2004
If a structure were loaded to full design load at all levels and the actual forces that
developed in the members were measured what degree of variation with the forces
assumed at design stage would be found to exist?
If two engineers were independently given the same building frame and design brief
would they both end up designing every element for exactly the same forces?
Basically Engineers have traditionally idealised a very complex problem, applied safety factors,
and established design forces which have been used successfully for many years. This is a
good result, but should not be regarded as some sort of scientifically accurate result.
Now there is a trend towards full 3 dimensional modelling and analysis of buildings. Creating
a single analysis model for an entire building will inevitably have the following effects:
Lateral load is shared throughout the structure according to relative stiffness:
Where robust core walls and shear walls exist these provide the vast majority of the
resistance to these loads.
The sway that occurs when pure gravity load is applied to any non-symmetrical
structure will naturally be introduced.
For the structure which predominantly resists gravity forces:
Elastic shortening of compression members (columns and walls) will occur.
As a result the analysis results for beams on the 20th floor will not be the same as those
on the 1st floor.
It is worth taking note of all of the above differences before we focus more specifically on
sub-frame modelling and the inclusion/exclusion of DADE. The approach used is aimed at
largely eliminating DADE, it does not eliminate natural sway effects. It must be acknowledged
that sway effects will cause some unavoidable differences in the comparisons.
There is no intention to suggest that the new 3D analysis model now creates scientifically
accurate results, a great many simplifications, assumptions, etc. remain. The overall objective
of the above discussion is to encourage consideration of the comparisons in these notes from
an engineering standpoint.
Orion Documentation page 212 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Example 20 Storey Building
Example Model:
Storey Height
Fdn to G/F 0.5m
G/F to 1/F 4.0m
1/F to Roof 3.05m per storey
Wall Thickness (mm)
Fdn to 10/F 10/F to Roof
Shear Wall 300 225
Core Wall 350 250
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 213
Column Size (mm)
Beam Size (mm)
Slab Thickness
125mm
Height of Openings
All openings to be 2300mm from floor level including the opening at G/F between columns
C1 and C2.
In a separate exercise it has been demonstrated that sway results for this model are in excellent
agreement with results achieved using other software. Refer to the next chapter, Sway
Deflection Verification for details.
Traditional Analysis Results
As already discussed a 'traditional' design will historically have been based on the results of a
series of discrete 2D subframe analyses:
Sub-frame analyses are carried out at each floor from top down (assuming fixed supports)
Deflection compatibility between sub-models is ignored.
Fdn to 10/F 10/F to Roof
C1 750 x 1250 (at Fdn to 1/F only)
C2 750 x 1250 (at Fdn to 1/F only)
C3 500 x 1500 400 x 1500
C4 500 x 1500 400 x 1500
C5 500 x 1500 400 x 1500
C6 500 x 1500 400 x 1500
Fdn to 10/F 10/F to Roof
B1 & B2 400 x750 300 x500
B3 & B4 400 x750 400 x500
B5 & B6 450 x700 300 x 450
B7, B8 & B9 350 x650 250 x 500
Orion Documentation page 214 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Column and wall forces are established by summing up the axial loads determined in each
of the separate analyses. Or, in many cases the axial loads are determined by simply
calculating an assumed supported floor area at each floor.
Both 2D and 3D subframe models can be created and analysed in Orion if required. To
emulate the result that would be achieved by subframe analyses in both directions the top
storey is extracted and analysed as a single floor model.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 215
The analysis results for this 3D subframe are shown below (mid-pier wall idealisation has been
used).
To enable comparisons to be made with other approaches, the bending moment diagram can
be plotted for the highlighted beams.
We shall consider this our "baseline" answer against which other approaches can be
benchmarked.
Once again it is important to note the comments made in the opening discussion about the
assumptions inherent in the above result. It is a target baseline, it should not be regarded as
some sort of perfectly correct result.
Emulating the Traditional Approach in Orion
Orion has two basic analysis methods:
Sub-Floor Analysis
Referred to in Orion as FE Chasedown analysis.
Building Analysis
Analysis of a full 3D model
Since Orion's "FE Chasedown" analysis uses a sub-frame approach, we should expect to find it
agrees closely with the "baseline" answer.
Orion Documentation page 216 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Orion's 'building analysis' does not utilise sub-frames, instead it treats the entire structure as a
single 3D frame in which the columns and walls are only fixed at the foundation level.
We will now consider each of the above analysis methods in turn by comparing them against
our "baseline" answer.
Sub-Floor Analysis (FE Chasedown)
By choosing the option in Orion to perform an 'FE chasedown analysis', a batch process is
initiated in which a separate analysis of all floors is performed one after the other, starting at
the top of the building, and continuing to the ground level. For each analysis the calculated
reactions from the floor above are treated as load input for the current floor.
When this is run, the bending moment diagram for the comparison frame at the top storey is
as follows:
This appears to be in very reasonable agreement with the baseline analysis result shown below.
Although the results are not exactly identical, the differences are generally small and are likely
to be down to internal differences in the way FE beam and wall elements are assumed to
connect.
There is however a limitation to this approach - whilst in building analysis pattern load cases
can be automatically derived and included, they are not considered in the FE chasedown
analysis. Consideration of pattern loads would increase the peak design forces but two other
factors could be taken into account:
Support Moments are taken at the centreline of supporting columns. Introducing rigid
zones to the analysis and taking design moments at the face of supports would result in
changes to design moments which are predominantly reductions where beams frame into
columns.
Moment redistribution is not considered.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 217
Some engineers may wish to consider using the FE Chasedown results on the basis that the
factors above have some counterbalancing effect. However, other engineers will prefer to
know that pattern load has been considered and for this reason we tend to suggest that the area
factor adjustment method which is illustrated in the next section may be considered
preferable.
Building Analysis, area factor adjustment methods
By choosing the option in Orion to perform a 'building analysis', a single frame model of the
entire structure is created and analysed for all load cases and combinations.
Prior to analysis, global adjustments can be made to member groups used in the analysis
model, the default settings for these are as shown below:
If the analysis is run using the above default settings, the bending moment diagram for the
comparison frame at the top storey is as follows:
There appears to be an anomaly, an unexpected sagging moment is occurring at the beam
support.
Orion Documentation page 218 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
To gain a better understanding of why this is happening we need to think about the 3D nature
of the analysis model. To begin with let's display the above diagram in 3D along with the other
beams at the top floor:
This result appears to disagree with our "baseline" answer obtained from the analysis of the top
floor as a discrete model, which is shown below:
Bending moments at the top floor of the building analysis model:
Bending moments in the 'control' model:
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 219
This raises two immediate questions:
Why do the two models give such different answers?
If we were to accept the results for the baseline model as being our target result, is there
any way to adjust the building analysis model to bring it back in to line with this target?
Why do the two models give such different answers?
To resolve this we need to compare the two deflection diagrams.
In the baseline model the vertical deflections at the beam support points have been eliminated.
This is not the case in the building analysis model - vertical deflections occur at the beam
support points. Since stresses are greater in the columns, these deflections are greater at
column support locations than at the wall support locations. The differential in these
deflections is most obvious along the line of the frame on which the 'anomaly' in the bending
moments was detected. (shown in dashed lines above.)
Deflections under dead load for the baseline model:
Deflections under dead load for the top floor of the building analysis model:
Orion Documentation page 220 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
The differential tends to increase as you get higher in the building. Evidence for this can be
seen in the change of shape of the bending moment diagram along the line of the highlighted
frame when plotted for the entire building.
There is an obvious change in the bending moment between the ground and the 9th floor.
There is another change at the 10th floor but this is due to a change in beam sizes. It is perhaps
interesting to see that the effect is so noticeable over the first 9 floors. This is partly because
the case of a beam spanning from a wall to a column and back to a wall is typically the most
critical sort of location for exposing this effect.
Differential axial deformations account for the different answers obtained from the two
models. Traditional sub-frame analysis ignores this effect. Sub-frame analyses assume there
is no vertical deflection at supports, whether it is appropriate to ignore this will be discussed
later in these notes. For the time being we will assume that you want to ignore it, in which case
we now need to determine if it is possible to eliminate it.
How do we eliminate this effect if we want to?
We have already seen that this effect is eliminated in Orion's FE chasedown analysis (because
it is a sub-frame analysis).
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 221
In order to eliminate it from Orion's building analysis, we need to reconsider the default
stiffness settings applied to member groups in the analysis model.
There are probably several strategies of adjusting member properties that could be employed
to try and reduce / eliminate DADE.
1. Make column vertical deflections consistent with the wall deflections by increasing the
area factor applied to columns.
2. Eliminate column and wall vertical deflections completely by substantially increasing the
area factor applied to columns and walls.
3. Adjust beam stiffnesses so that the differential vertical deflections induce much lower
bending moments.
4. etc?
After various trials it has been found that the first method (column area factor adjustment)
seems effective without readily introducing unwanted side effects. Therefore, these notes now
focus on this method.
Increasing the column area factor
The objective is to increase the column area factor so that the differential axial deformation
between columns and walls is reduced towards the point of being eliminated.
By examining the deflected shape of the frame with the original area factor (AF) of 1.0, it is
possible to estimate an average area factor which may achieve this.
Vertical Deflections under dead load at the top floor for AF = 1.0
Orion Documentation page 222 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
If the model is re-analysed with the column AF 2.2 as calculated above, the revised deflected
shape indicates a marked reduction in the differential axial shortening.
The above deflection diagram for AF 2.2 shows that some differential deformation still
remains. This is explained by the fact the stiffer columns also attract more load (increasing it
towards the value that the sub-frame analyses would determine). A second iteration of the AF
calculation should reduce it.
LH AF = 4.4/4.9 = 0.9,
RH AF = 4.4/2.9 = 1.5
Average AF = (0.9+ 1.5)/2 = 1.2
Applying a further factor of 1.2 to the existing 2.2 the new AF becomes 1.2x2.2 = 2.65 - use 2.7.
If the model is analysed with the column AF 2.7 the differential axial shortening is almost
eliminated.
Results for these analyses can again be compared with the result from the baseline model.
Vertical Deflections under dead load at the top floor for AF = 2.2
Vertical Deflections under dead load at the top floor for AF = 2.7
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 223
With the AF of 2.2 the BM's developed in beams B1 and B2 at the top floor are as follows:
When the AF is increased to 2.7 these become:
These can be compared with our baseline sub-frame result:
Applying a column AF of 2.2 reduces the effects of differential axial shortening and eliminates
the sagging at the central column support. When the AF is increased to 2.7 the result is even
closer to that of our baseline subframe.
Using this slightly higher AF value of 2.7 ensures a conservative design at the column support.
The same value would not be applicable. Arriving at this value is a matter of some judgement
but the above demonstrates that a logical process can be applied.
Whether the AF should be increased still higher would be a matter of engineering judgement.
For example if the AF is increased to 4.0, the resulting bending moments are as follows:
With this higher area factor the hogging moment at the column increases further, however it is
reduced at the wall supports.
Orion Documentation page 224 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
NOTE: An area factor of 4.0 is likely to be extreme for most buildings. In this example it
has reversed the differential deformations - the walls are now shortening by more than the
columns, as shown below:
What is a reasonable upper limit for the column area factor adjustment?
The objective in setting an upper limit is to reduce or largely eliminate the differential axial
deformation so that the design forces at each floor more closely resemble those obtained from
a traditional approach.
Although differential axial shortening is not taken into account in traditional subframe
analysis methods, it will still exist to a greater or lesser extent in real buildings. Even taking
into account the staged nature of construction there will always be some amount of differential
shortening that actually does occur.
The objective of setting the upper limit is therefore to obtain a realistic set of design forces,
without necessarily being concerned about completely eliminating the effects of differential
axial shortening.
Detailed comparisons of the analysis results
The above approaches demonstrate that DADE can be at largely eliminated from the analysis
results in attempts to emulate the results achieved by a traditional sub-frame approach.
To establish a better understanding of the effects of adjusting the area factor we will now
compare other aspects of the analysis results in more detail.
Gravity Loads
When the area factor is used to counteract axial shortening, it affects the axial force
distribution as well as the bending moments. This is illustrated in the table below, showing
how the dead load results change at the base of the frame containing beams B1 and B2 as the
area factor is increased:
The axial and bending moment results which accrue at the bottom level of the walls and
column along the frame under consideration can be tabulated as follows:
Vertical Deflections under dead load at the top floor for AF = 4.0
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 225
In this case the FE Chasedown results represent the result for the baseline model.
As the area factor is increased there is a shift of axial load from the walls into the columns.
This is to be expected. It is moving the results back towards those obtained for the baseline
model. For the bending moments however it seems that this method results in much higher
bending moments in the wall panels than the baseline model. This moment occurs for all AF
levels, it is not introduced by the use of an increased AF. It is likely that this moment is
developing as a result of sway effects that will occur in the full 3D analysis but are excluded
from traditional sub-frame analysis.
Lateral Loads
The deflections at the top of the building under lateral load can also be compared:
It can be seen from the above that an increase in the area factor from 1.0 to the value of 2.7 or
even the extreme value of 4.0 has very little impact on the deflections at the top of the building
due to lateral load. This is because the columns are not significant in resisting sway deflection.
If the deflections were changing then some increased caution in the use of the AF would be
appropriate, this is noted again later.
AF 1.0 AF 2.2 AF 2.7 AF 4.0
FE chasedown
(i.e. subframe)
Left Hand Wall Axial (kN) -3219 -3091 -3065 -3025 -3042
Column Axial (kN) -3233 -3954 -4103 -4342 -4112
Right Hand Wall Axial (kN) -3044 -2862 -2828 -2776 -2889
Left Hand Wall Moment top
(kNm)
-453 -439 -436 -432 -198
Column Moment btm (kNm) -0.6 -1.6 -1.8 -2.2 7
Right Hand Wall Moment
btm (kNm)
-711 -555 -525 -479 7
AF 1.0 AF 2.2 AF 2.7 AF 4.0
FE chasedown
(i.e. subframe)
Wind X max (mm) 101.6 99.0 98.4 97.5 N/A
Wind X min (mm) 101.3 98.3 97.7 96.7 N/A
Wind X max resultant (mm) 101.8 99.2 98.4 97.7 N/A
Wind Y max (mm) 79.9 78.4 78.3 78.0 N/A
Wind Y min (mm) 35.9 35.0 34.8 34.5 N/A
Wind Y max resultant (mm) 81.7 80.4 80.3 80.1 N/A
Orion Documentation page 226 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
The axial and bending forces in the columns and walls at the bottom of the model can also be
compared for the wind load cases. The effect that increasing the area factor has on these forces
due to wind in X is illustrated below:
Since the introduction of the AF had only a small effect on the deflection (comparing with
AF=1.0), it has a similarly small impact on the distribution of forces.
Recommendation
Based on the above it is recommended that where DADE is of concern and there is a desire to
largely eliminate it, the strategy adopted for applying an AF adjustment should be:
1. After an initial analysis using AF = 1, examine the beam bending moments and the
vertical deflections of columns and walls at the top floor of the structure. Also record
sway deflections in both directions.
2. Using the approach demonstrated in this chapter, determine an appropriate AF
adjustment to apply.
3. Re run the analysis and review the revised results at the top floor. If the DADE seems to
have been largely eliminated continue with design of all column and wall members.
4. If the deflections are largely unchanged then you might choose to stop at this point,
however, the discussion below should be considered.
5. If the deflections have changed significantly then it is strongly recommended that a
second analysis run is made with a lower AF and that the columns and walls (at least) are
checked for the results of this revised analysis. Within Orion this is a simple procedure
and the implications of this are illustrated in the next section.
AF 1.0 AF 2.2 AF 2.7 AF 4.0
FE chasedown
(i.e. subframe)
Left Hand Wall Axial (kN) 1113 965 937 895 N/A
Column Axial (kN) 1824 2160 2223 2321 N/A
Right Hand Wall Axial (kN) -153 -225 -239 -261 N/A
Left Hand Wall Moment top
(kNm)
681 652 651 648 N/A
Column Moment btm (kNm) 124 121 121 120 N/A
Right Hand Wall Moment
btm (kNm)
9572 9390 9356 9305 N/A
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 227
Is it acceptable to simply emulate the traditional design result?
Ignoring differential axial displacements
If you are happy to work on this basis then all you need to do is adopt one of the methods
described previously for emulating the traditional design, taking note of the associated pros
and cons.
FE Chasedown Analysis
Within Orion there is an automatic batch procedure for achieving this. Despite the name "FE
chasedown", the use of Finite Elements to model the slab is optional and unless there is a
specific reason for doing so it is recommended that these are not used. This method will then
very closely emulate the traditional analysis assumptions of sub-frame analysis for gravity
loads.
A building analysis is still required to determine results for the lateral load cases.
Orion allows you to automatically merge the results of these two analyses to generate the
design combinations for all members.
Cons - No pattern loading and no rigid zones.
Building Analysis - Area Factor (AF) method
Pros - Pattern loading is considered and rigid zones can also be introduced for economy.
Cons - Applying a single area factor globally may not fully remove differential axial
deformation at all locations.
Making allowances for differential axial displacements
The inherent assumption within the traditional sub-frame approach is that differential axial
displacement does not take place to a degree that would affect the design results. What a 3D
analysis demonstrates is that this might not be the case.
Therefore, having analysed the structure on the basis that differential axial displacements are
ignored (using one of the methods described above), you have results that can be considered
as an upper-bound solution. The next step is therefore to establish a lower-bound for which
each member can then be checked.
In effect this procedure will ensure that all the members are designed for a slightly wider
envelope of forces between these two limits. Two questions tend to be raised when this
approach is discussed. First there is the question of what values should be used for the upper
and lower limits. Second there is a concern that this could end up being considered as
uneconomic by comparison with traditional designs. Each of these questions is considered
below.
Orion Documentation page 228 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
What is a reasonable lower limit for the area factor adjustment?
Using a low AF allows the effects of differential axial deformation to be exposed. However, as
is demonstrated earlier in these notes, an AF=1.0 will sometimes give results that seem
completely incorrect when compared with expected values based on traditional sub-frame
analysis.
Clearly AF=1.0 can be used as a conservative lower limit. However, bearing in mind that
traditional design methods have completely eliminated this effect, it is worth considering
whether or not some slightly increased value could be easily justified.
This topic is discussed in reasonable depth in CSC's 3D effects presentation which notes that:
More detailed consideration of the way in which creep and loading develop over time and
through the construction phase dictates that some proportion of differential axial
deformation being predicted is unrealistic. AF=1.0 will over estimate the effect of
differential axial deformation.
Consideration of ACI advice on analysis model properties which allow for the more likely
case that beams are cracked while columns/walls are not would have the same effect as
introducing an AF = 1.5. (ACI 318-08 cl 10.10.4.1 the precise clause number varies in
older versions of the ACI, but the guidance appears consistent.)
It was suggested in that presentation that a lower bound of somewhere between 1.5 and 2.0 is
reasonable. 1.5 would be the more conservative value to use (since it widens the envelope
between the lower and upper values).
What is the impact on the design when both upper and lower-bounds are taken into consideration?
To establish this a comparative study can be undertaken using the test model.
The total weight of beam, column and wall steel can be determined using one of the methods
for emulating the traditional approach. (i.e. the upper-bound solution). The model can then
be reanalysed, having made an allowance for differential axial displacements, (i.e. the
lower-bound solution). The reinforcement provision already established is then checked for
the new design forces and if necessary the provision is increased at any failing locations. The
overall impact can be assessed in terms of the changes to the total steel reinforcement weight.
The results of this exercise are as follows:
Upper Bound
Emulation
Method
Design for
Upper-bound
Only
Add check for
Lower-bound
AF 1.5
Add check for
Lower-bound
AF 1.0
AF 2.2 Total Beam Steel (kg) 44980 45334 (+0.8%)
Total Column & Wall Steel (kg) 80185 80211
(+0.03%)
80712
(+0.7%)
AF 2.7 Total Beam Steel (kg) 44907 45273
(+0.8%)
46438
(+3.3%)
Total Column & Wall Steel (kg) 80192 80261
(+0.09%)
80762
(+0.7%)
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 229
Note: the total beam reinforcement weight quoted doesn't include the weight of 2B10, 3B14
and 3B15 as these proved to be inadequate for the forces involved.
Consider Case where AF = 2.7 is upper bound and AF = 1.5 is the lower bound:
In this case the implications of considering the envelope are quite minimal. A 0.8% increase in
beam reinforcement and a 0.01% increase in column and wall reinforcement is introduced.
Consider Case where AF = 4.0 is upper bound and AF = 1.0 is the lower bound:
In this case the envelope being considered includes extremes that have been suggested to be
the most conservative at both ends. The result is that a 4.4% increase in beam reinforcement
and a 0.8% increase in column and wall reinforcement is introduced.
Consider Case where FE Chasedown is upper bound and AF = 1.5 is the lower bound:
FE chasedown only provides results for the gravity loadcase, lateral load results must come
from the full 3D building analysis. In this case the least overall reinforcement weight is
determined. This is likely to be because sway effects introduced by gravity load get eliminated
(as they are in a traditional sub-frame analysis).
What is the impact on the design when Pattern Loading is Introduced?
In order to compare all the methods on a like for like basis, the reinforcement weight
comparisons above did not include analysis or design for pattern load conditions. It was noted
earlier that the FE Chasedown method in Orion does not currently cater for pattern loads.
Pattern loads can only be considered by the AF method where the full 3D building analysis is
used. The full 3D analysis also allows rigid zones to be introduced in which case design
moments are taken at the face rather than the centreline of supports. Therefore, we can look at
the overall impact of considering pattern loads but at the same time introducing the efficiency
of rigid zones.
AF 4.0 Total Beam Steel (kg) 45774 46528
(+1.6%)
47781
(+4.4%)
Total Column & Wall Steel (kg) 80187 80344
(+0.2%)
80845
(+0.8%)
FE Chasedown Total Beam Steel (kg) N/A 43847 45658
(+4.1%)
Total Column & Wall Steel (kg) N/A 80545 82180
(+2.0%)
Upper Bound
Emulation
Method
Design for
Upper-bound
Only
Add check for
Lower-bound
AF 1.5
Add check for
Lower-bound
AF 1.0
Orion Documentation page 230 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
The reinforcement weights when both pattern load and rigid zones are considered are as
follows:
..
Compare the total weight requirement after designing for upper bound of 2.7 and lower
bound of 1.5. For the beams the weight is now 40964kg, it was 45273kg before rigid zones
were introduced. For the columns the weight is now 78891kg, it was 80261kg before rigid
zones were introduced. The new reinforcement weights are also slightly lower than the weight
previously shown when the FE chasedown method was used (43847 and 80545 respectively).
For this example model, the AF method can be used with double benefit when compared to
FE chasedown:
1. It eliminates any concerns about not having considered pattern loads
2. By introducing the efficiency of rigid zones it also results in the least overall reinforcement
requirement.
Conclusion on Design Impact
For the example model it seems that the impact of considering upper and lower bound
solutions would have quite minimal effect on overall construction cost. For the columns and
walls in particular it seems that the vast majority of members are unaffected.
The FE chasedown method does not allow pattern loads to be considered at the upper bound.
If this is a concern then the AF method must be used. In practice the AF method will be a
little more time consuming to apply, but this example also demonstrates that allowing the use
of rigid zones along with full pattern loading could have a net overall benefit when compared
to the FE chasedown method.
Upper Bound
Emulation
Method
Design for
Upper-bound
Only
Add check for
Lower-bound
AF 1.5
Add check for
Lower-bound
AF 1.0
AF 2.7 Total Beam Steel (kg) 40437 40964
(+0.8%)
42295
(+3.3%)
Total Column & Wall Steel (kg) 78778 78891
(+0.1%)
79517
(+0.9%)
AF 4.0 Total Beam Steel (kg) 40951 41568
(+1.6%)
42839
(+4.6%)
Total Column & Wall Steel (kg) 78851 78980
(+0.2%)
79606
(+1.0%)
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 231
Overall Summary of Suggested Procedure
Assuming the Area Factor method is to be adopted the following steps summarise the entire
procedure that should be undertaken.
Determine if DADE is important for the structure under consideration.
After an initial analysis using AF = 1, examine the beam bending moments and the
vertical deflections of columns and walls at the top floor of the structure.
If effects are not a concern then no further action is required.
If steps need to be taken to eliminate DADE record sway deflections in both directions
before proceeding.
Initial Design - Emulate traditional hand calculation methods
Use the approach demonstrated in these notes to determine an appropriate AF
adjustment to apply. (If it is your intention to perform the check design stage below
then there is little harm in erring on the high side at this point)
Re run the analysis and review the revised results at the top floor. If the DADE seems
to have been largely eliminated continue with design of all column and wall members.
Design all columns/walls/beams
If the sway deflections are largely unchanged then you might choose to stop at this
point, however, if you prefer to cross check taking some account of DADE then
proceed to next stage.
If the deflections have changed significantly then it is strongly recommended that a
second analysis run is made with a lower AF and that the columns and walls (at least)
are checked for the results of this revised analysis.
Check Design - Allow for differential axial deformations
Use a column area multiplier of between 1.5 and 2.0 (1.0 if you want to be more
conservative)
Run check design on all columns/walls/beams. (Check design on beams might be
considered optional)
Increase reinforcement on any failed members
(needs to be done interactively on beam lines)
Final Design and Submission Calculations
Return to the AF determined at the initial design stage above.
Run check design on all columns/walls/beams (all should pass if the above exercise
was completed properly).
Generate submission calculations:
Moment diagrams etc based on this analysis will be more familiar to the checking
engineer.
You will however have designed for larger moments in some places, so the steel
may appear to be overprovided at those points.
The above is illustrated in a DADE Analysis & Design Flowchart at the end of this chapter
together with the possible option of using the FE chasedown procedure.
Orion Documentation page 232 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Closing Discussion
Typical Concerns
The sorts of concerns expressed by engineers as they begin to consider this topic for the first
time and then in greater detail are:
1. The suggested area factor is not a defined value, it is just a suggested range of values. I
really want a fixed value or values that can always be used.
2. Making these adjustments to cater for gravity load may be logical but are there side
effects? For example, will it cause completely different force distribution and building
deflection under wind loading cases?
3. Does the FE chasedown option provide another (better?) way to eliminate differential
axial deformation?
4. If I am designing for a wider envelope of forces am I not over-designing the structure?
5. Can this all be solved more accurately by using Staged Construction analysis?
What answers are we trying to get?
Discussion of any of the above has to be prefaced by an acceptance and understanding of the
fact that "correct" answers do not exist. This point is introduced in the opening discussion.
The uncertainties associated with concrete as a material and with construction generally
dictate this. These sorts of uncertainties (cracking, creep, etc) are noted in the seminar
presentation.
Traditionally answers have been achieved by methods involving very significant idealisation -
continuous beam/sub-frame analysis. Generally such designs would totally ignore the
potential impact of differential axial deformation. Are these design forces to be considered as
the "correct" answers, or should the potential impact of differential axial deformation be
considered?
Assuming it is agreed that differential axial deformation should not be completely ignored
then we have a decision to make - do we always allow for axial deformation and abandon the
previous methods where it was ignored? This is a really a matter for the general engineering
community, but if we assume that there is concern about abandoning the results that have
always been used with no particularly detrimental effect, then we inevitably end up having to
consider designing for an envelope of forces derived from differing assumptions.
Fixed Values for Area Adjustment Factor
A single fixed value could only be possible if a decision were made to either always ignore or
always allow for differential axial deformation. For reasons noted above this does not seem to
be a viable option and so we must really focus on whether a range with fixed upper and lower
limits is possible.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 233
For the upper limit we are considering the case where differential axial deformation is being
largely eliminated. Values of 3-5 are discussed in the presentation but this is actually
something that can be quite structure dependent. However, it is also something where logic
can be applied. If the deflections from an un-modified analysis are examined and a wall is
deflecting down by 2mm while the columns adjacent to it are deflecting 5.5mm then the area
factor required to eliminate this will be a little in excess of 5.5/2 = 2.75. (Bear in mind that the
stiffer columns will attract increased axial load).
In the example the relatively large size of the columns compared to the walls results in quite a
low figure of around 2.7 being a reasonable upper limit, but use of values slightly higher than
this would really only add a little to overall design conservatism.
For the lower limit we are considering the case where differential axial deformation is allowed
for. As is noted above a logical but very conservative lower limit is 1.0. For reasons detailed in
the presentation we suggest that a 1.5 value is actually a very reasonable lower limit.
Side Effects on Lateral Load Analysis
There will be some effect, but the following must be noted:
The area factor is only affecting the axial load deformation characteristics of the columns,
the bending stiffness is not affected.
Generally walls are providing the majority of lateral load resistance and so adjusting
column properties has quite limited impact on deflections.
Once again the impact of this is illustrated in the example. The percentage change in
deflections is relatively small.
A bigger question (not considered here) is the extent to which any analysis accurately predicts
lateral deflection. The result is again entirely dependent on allowances made for creep and
cracking. ACI guidance on this is more thorough and suggests varying member stiffness
adjustments.
Will FE Chasedown also eliminate differential axial deformation?
Yes - this is demonstrated in these notes. Instead of running the building analysis with the
increased area factor, results from an FE chasedown could be used. There is however a
limitation in this approach, pattern load cases are not considered during FE chasedown. For
this reason we would suggest that the area factor adjustment method is not dismissed.
In Orion pattern load cases are automatically derived and included in the full building
analysis. We understand that in some other software this is not so easy to achieve and so
perhaps it is not considered imperative that patterning is considered as well as eliminating
differential axial deformation. In this case some engineers may prefer the option in Orion to
use FE chasedown.
Orion Documentation page 234 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Is this going to result in uncompetitive over design?
Traditional design tended to ignore the impact of differential axial deformation. If we now
consider this effect, but continue to consider the traditional results as well, then the envelope
of design forces will inevitably widen for some members which will result in more onerous
design. However, for the example model considered the net effect of this proved to be quite
minimal.
Is this over design, or a more thorough and professional approach taking account of modern
analytical capabilities? This is really another question for the engineering community.
Could I avoid all this complication if Staged Construction Analysis were used?
This would not avoid complication - it would just mean that different complications need to
be addressed. A single staged construction analysis can not deliver "correct" answers. The
unknowns associated with the input for such an analysis dictate this. This is illustrated within
our presentation, but the key point to consider is that this type of analysis means you have to
define properties that would not normally be defined for a basic elastic-static analysis, and you
would have to allow for uncertainties associated with these:
Time varying properties of concrete - you have to be able to define what properties should
be used at every time step (stage). This includes consideration of early age creep effects.
You have to define the way in which loading becomes active through the stages.
You must then layer on top of this the need to consider patterning of load. In this context
there is load patterning along beam lines but also the need to consider loaded and unloaded
floors through the height of the building. Can this be realistically achieved as part of a staged
construction analysis of a large structure?
As with any analysis, if it is not used with a reasonable degree of care and understanding then
a staged construction analysis can be a sophisticated and time consuming way of getting bad
answers.
We would suggest that a staged construction analysis is another way of establishing an
envelope of possibilities. The parameters applied during this process are not specified in any
design code so this approach ought to be subject to a similar degree of judgment and scrutiny
as is required for the area factor adjustment approach.
Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings Orion Documentation page 235
DADE Analysis & Design Flowchart
01.
Build/Edit the Model
02
Derive Beam Loads
Yield Lines or
FE decomposition for BeamLoads
05.
Run Building Analysis
This step is mandatory in order to produce
analysis results for the lateral loads
This step also produces a lowerbound
analysis solution for gravity loads (in which
DADE may exist)
04.
Decide if Rigid Zones are to be used
When utilised in Building Analysis, rigid
zones can producea more economicsolution
09.
Which
method to resolve
DADE?
06.
Initial Design
Check
AF1.
Determine upperbound AF
AF2.
Re-run Building Analysis using
upperbound AF
compare sway deflections with
those obtained fromlowerbound
solution (step 05)
AF3.
Design all members
This is a design for the
upperbound analysis solution
in which DADE has been
minimised
08.
Design All members
AF4.
Re-run Building Analysis using
lowerbound AF
This re-instates thelowerbound
analysis solution obtained in
step 05
AF6.
Re-run Building Analysis using
upperbound AF and check all
members
If step AF5 above was done
properly all should pass at this
point and design calculations
should be saved
FE3.
Run FE Chasedown Analysis
DON'T use meshed floors
DO include upper storey loads
FE4.
Merge FE beam and
column results
Because FE Chasedown considers
gravity loads only, the lateral results
fromstep 05. are still retained
FE5.
Design all members
This is adesign for the upperbound
analysis solution in which DADE are
virtually eliminated
FE6.
Un-merge FE beam and
column results
This re-instates the lowerbound
analysis solution obtained in
step 05
FE7.
Check all columns and walls
Increase reinforcement in failed
members
AF5.
Check all members
Increasereinforcement in failed
members
FE8.
Optionally - check all beams
Because thelowerbound solution
caters for pattern load theuser may
want to consider its effect
Increase reinforcement in failed beams
FINISH
START
yes
sizes OK
AF
FE
07.
Is DADE a
concern?
no
sizes
not OK
FE1.
Are Rigid
Zones set to
None?
FE2.
Set Rigid Zones to None and re-run
Building Analysis
FE results can not be merged if rigid
zones havebeen used
yes
no
03.
Decide on a lowerbound AF
Conservatively use thedefault AF =1.0
To reduce DADE, use 1.5 2.0
FE9.
Re-merge FE beam and column
results and check all members
If steps FE7 and FE8 above were done
properly all should pass at this point &
design calculations should be saved
Orion Documentation page 236 Chapter 13 : Overview of Differential Axial Deformation Effects in 3D Analysis of Buildings
Flowchart Notes.
Box
No.
Comment
03. Justification for increasing the AF may be derived from ACI advice on analysis
model properties which allows for the more likely case that beams are cracked
while columns/walls are not. Refer to What is a reasonable lower limit for the
area factor adjustment? for an introduction to further discussion on this.
04. See Rigid Zones for further details on the use of these.
06. Inadequate initial member sizing can have significant impact on force
distribution around the structure. It is important to review the member sizing
at an early stage in order to prevent having to increase undersized members
later on.
07. Determine if DADE is important by examining
how the beam bending moments change over the height of the structure,
the vertical deflections of vertical elements at the top floor
see Why do the two models give such different answers? for details of how to
do this.
08. If DADE is not a concern, the design is now complete.
09. It is down to user preference which method is adopted for minimising/
eliminating DADE, noting that:
AF method - Applying a single area factor globally may not fully remove
differential axial deformation at all locations.
FE Chasedown method - No rigid zones, and for the upperbound solution
no pattern loading.
AF1. See Increasing the column area factor for details of how to do this.
AF2. The deflections at the top of the building under lateral load should be
compared. Provided the differences are small the impact on the distribution of
lateral forces will be small. See Overall Summary of Suggested Procedure for
additional notes on this. If the high AF is affecting the deflections it is more
important that the lower bound solution is checked for all members.
Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design Orion Documentation page 237
Chapter 14 Using Staged Construction Analysis to Emulate Traditional Design
Introduction
As described in the previous chapter a 'traditional' design will historically have been based on
the results of a series of discrete 2D subframe analyses, in which:
Sub-frame analyses are carried out at each floor from top down (assuming fixed supports)
Deflection compatibility between sub-models is ignored.
Column and wall forces are established by summing up the axial loads determined from
each of the separate analyses.
Alternative methods of emulating the above in Orion were investigated and the following
methods were described:
Sub-Floor Analysis
Referred to in Orion as FE Chasedown analysis.
Building Analysis with Area Factor Adjustment
Analysis of a full 3D model
In this chapter a third alternative is explored via a worked example:
Staged Construction Analysis
Analysis of a full 3D model in stages
Worked Example:
In the previous chapter we established some traditional sub-frame results
for beams at the 20th floor of a building and then looked at how closely
these results were emulated using full 3D analysis., the purpose of the
exercise being to quantify the effects of differential axial deformations.
From the results it was possible to then formulate recommendations for
emulating a traditional design.
In this worked example the same model is used to examine 3D staged
construction analysis and compare the results with those obtained
previously. Once again the objective is to derive a means of emulating a
traditional design.
Orion Documentation page 238 Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design
Previous Results (from FE Analysis and Unstaged Building Analysis)
A single beam line at the top floor was chosen for the purposes of comparison.
Sub-Floor Analysis (FE Chasedown)
The bending moment diagram below was obtained by performing an FE chasedown analysis.
This type of analysis eliminates differential axial deformation effects (DADE) and is
considered a reasonable base-line answer against which the other approaches can be compared
Building Analysis without Area Factor adjustment
When a BuildingAnalysis was run using default settings, the bending moment diagram for the
comparison frame was as follows, the effect of DADE is clearly apparent:
Building Analysis with Area Factor adjustment
As discussed in Chapter 13 Area Factors can be applied to reduce DADE. With the AF set at
2.7 the following result was obtained
Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design Orion Documentation page 239
Staged Construction Analysis Result
Currently this is only available for unfactored cases utilising 25% rigid arms:
The unstaged G+Q*F result (with 25% rigid arms and AF = 2.2) is:
Super-posing these answers we get a staged combination result as follows:
The staged result initially appears to offer an as good or better means of eliminating DADE
than is achieved through the Area Factor approach, (although comparison is difficult as the
staged and AF results in the above table allow for rigid arms whereas the FE result does not).
However, when the staged results are examined in more detail the conclusion is less clear cut.
Solution Method
LH Support
Moment
Span Moment
RH Support
Moment
FE Chasedown -100.4 67.4 -103.8
BA unstaged -189 70 -16
BA AF 2.2 -126.2 62.9 -84.4
BA staged -115.8 62.4 -95
Orion Documentation page 240 Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design
Does Staged Analysis eliminate DADE?
To answer this question, firstly we need to make a comparison between the unstaged and the
staged bending moments that develop over the full height of the example building:
Each bending moment diagram shows a significant step change at the 10th floor - this can be
accounted for by the step change in beam sizes that takes place at this level.
Unstaged Q - BMD Floors Staged Q - BMD Floors
Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design Orion Documentation page 241
DADE is clearly affecting the unstaged analysis results from the second floor all the way
through to the top floor of the building.
The staged analysis seems to be largely unaffected by DADE at the upper floor levels, but this
does not hold true from around the 10th floor level and below. (In this particular worked
example it should be noted that the effect is being amplified due to the central column size
being larger over the first 10 storeys.)
The shape of the above bending moment diagrams can be understood more clearly by
considering the extent by which the central column shortens in each analysis.
In the unstaged analysis the column axial shortening must accumulate as you get higher in the
building. The vertical deflection of the column at the top floor is directly affected by the axial
shortening of the lower columns, which is occuring due to the load they each carry.
In the staged analysis, the top floor forces and deflections are determined from the analysis of
the final stage alone, in this stage only the top floor loads are applied and the loads carried by
other floors have no influence - hence column shortening is not being accumulated from one
floor to the next.
So in the staged analysis, why are we seeing DADE occurring, particularly at the 10th floor
and below? - To answer this you need to consider how the forces and deflections at the 10th
floor are determined from the combined effect of the analyses of 10th stage to the final stage,
(consisting of all the loads from the 10th floor to the top floor). This significant amount of
load is being carried by a column which is 10 storeys high - there is undoubtably going to be
considerable axial shortening taking place.
Unstaged Analysis Deflections
\
1st Floor 10th Floor Top Floor
Staged Analysis Deflections
1st Floor 10th Floor Top Floor
Orion Documentation page 242 Chapter 14 : Using Staged Construction Analysis to Emulate Traditional Design
Lower in the building, at the 1st floor level the column is carrying a much greater load -
however, because it is so short the amount of axial dispacement would be minimal.
Conclusions
Staged Construction does not eliminate DADE. (this particular example exacerbates the effect
because of the change in sections - the effect may not be so evident in other models??).
It moves the position where they are most significant (to building mid height ) and reduces
them to some degree.
This result is not technically wrong , but is it what engineers want?
If you are happy to completely ignore differential axial displacements then all you need to
do is adopt one of the methods described previously for emulating the traditional design,
taking note of the associated pros and cons.
If you are happy to take some account of DADE then staged construction may offer the
best solution.
Use of Staged Construction as the upper bound solution
The previous chapter discussed use of AF method to establish lower and upper bound
solutions and designing for the resulting envelope. (You could also use ACI method of
reducing inertias)
In this chapter an alternative has been provided to the above using staged construction, in
which the lower bound solution is an unstaged analysis and the upper bound solution is staged
G+Q. (You might however consider closing the gap between these by taking the upperbound
as staged G and unstaged Q).
Chapter 15 : Design and Detailing Orion Documentation page 243
Chapter 15 Design and Detailing
Introduction
The following section of the Engineers Handbook contains six chapters relating to the design
and detailing of the various member types:
Slab Design looks at slab strip errors and the actions required should you encounter
them.
Beam Design to BS8110 looks at Orions beam design process, relating it to the relevant
code clauses. A worked example is included.
Beam Detailing provides an overview of the beam detailing process, describing the
available patterns and beam detailing settings. A worked example is used to illustrate
how careful application of preferences can produce either: a minimum weight solution
(where the details may be more complex), or a more standardised detail (with a slightly
higher weight of reinforcement).
Column Design to BS8110 looks at Orions column/wall design process, relating it to the
relevant code clauses. Worked examples are included.
Wall Design and Detailing looks at additional aspects of Orions design process that are
unique to walls.
Foundation Design describes the procedures required for defining and designing the
various foundation elements available in Orion.
Orion Documentation page 244 Chapter 16 : Slab Design
Chapter 16 Slab Design
Overview
Referring back to the Modelling Analysis and Design Flowchart in the initial Overview
chapter, you can see that slab design may be based either on tabulated code coefficients, or on
finite element analysis (FE) results.
Design based on the tabulated code coefficients is covered in the training manual. Discussion
there also extends to the option of using an FE strip, but design based on FE is covered in
greater depth in this manual in the chapters Analysis and Design using FE and Flat Slab
Models.
In both cases, the design approach involves creating slab strips. Checks are applied as you
create these strips to ensure they are valid. The following brief notes may be of some additional
assistance (assuming that you have already completed the training examples successfully).
Slab Strip Errors Reviewing/Understanding
The Slab Strip creation process will fail and display an error message if you are attempting to
define an invalid strip. The message is displayed on the status line at the bottom of the screen,
No. of Slabs and Beams along strip is not consistent!
This occurs if you have defined a strip that does not pass through alternating beams and slabs
in the correct sequence.
A typical occurrence of this is when attempting to create a strip that either begins or ends with
a cantilever slab but you have set the end condition to either Bob or Slab.
It could also occur if you have drawn a strip that spans across an open area such as a lift core
where there is no slab.
Finally, it could also occur if at some point along the strip it encounters two consecutive slabs
without a beam separating them.
Action Required:
For case 1 above, change the end condition to Cantilever and update the strip.
For case 2, split the strip into two half strips. Draw one strip ending in the open area and then
a second strip coming out of the open area.
For case 3, redefine the slab panels so that the strip passes from beam to slab panel to beam
etc.
Creating Member (but nothing seems to happen)
This occurs if your strip doesnt entirely traverse one entire slab.
Chapter 16 : Slab Design Orion Documentation page 245
Action Required:
Interrupt the process by clicking on to another command on the Members toolbar, then
redraw the strip but increase its length so that it entirely traverses at least one entire slab.
Orion Documentation page 246 Chapter 17 : Beam Design to BS8110
Chapter 17 Beam Design to BS8110
Introduction
Orion designs beams bent about the major axis using the code clauses given in BS 8110-1:1997:
Part 1 Section 3.4.
The following table summarises the various stages of the beam design process:
Step Calculation Clause
1. Slenderness limits for lateral stability 3.4.1.6
2.
If flanged - calculate effective width of flanged
beam
3.4.1.5
3. Analysis of Sections 3.4.4.1
4. Design for Bending
3.4.4.4,
3.4.4.5
Calculate K/K 3.4.4.4
Calculate z 3.4.4.4
Calculate x 3.4.4.4
Calculate A
s
required 3.4.4.4
If K > K calculate A
s
required 3.4.4.4
5. Design for Shear 3.4.5
Calculate shear stress in beam, v 3.4.5.2
Calculate design concrete shear stress, v
c
3.4.5.4
Determine shear reinforcement 3.4.5.3
Spacing of links 3.4.5.5
6 Deflection of Beams 3.4.6
Span/effective depth ratios 3.4.6.3
Modification of span/effective depth ratios for
tension/compression reinforcement
3.4.6.5
3.4.6.6
Chapter 17 : Beam Design to BS8110 Orion Documentation page 247
Beam Design Settings
You take control of the above design process by configuring the Beam Design Settings dialog
to your preference.
For further details of the implications of adjusting the various settings see the chapter Beam
Detailing
The BS8110 Beam Design Process
1. Check slenderness limits for lateral stability- Cl 3.4.1.6
A warning message is displayed during the member definition if the slenderness limit has
been exceeded.
Orion Documentation page 248 Chapter 17 : Beam Design to BS8110
2. Rectangular or flanged - Cl 3.4.1.5
The choice of this setting is set via the Design tab of Beam Design Settings as shown below:
The option to use the rectangular section (rather than the flanged section) when the flange is
in compression will generally result in slightly more conservative steel area requirements,
however if minimum steel requirements apply then design using the flanged section will
introduce greater steel requirements.
If a flanged section is used the effective width is determined from Cl 3.4.1.5.
3. Analysis of Sections - Cl 3.4.4.1
All considerations stated in the Cl 3.4.4.1 are fulfilled. The simplified stress block for concrete
as illustrated in Figure 3.3 is utilized.
4. Design for Bending- Cl 3.4.4.4 and Cl 3.4.4.5
Bending is checked for the top edge in three regions:
1. left (worst case forces in end region - 25% clear span)
2. middle (worst case forces in mid region - 50% clear span)
3. right (worst case forces in end region - 25% clear span)
Similarly, bending is checked for the bottom edge in three regions:
1. left (worst case forces in end region - 15% clear span)
2. middle (worst case forces in mid region - 70% clear span)
3. right (worst case forces in end region - 15% clear span))
Chapter 17 : Beam Design to BS8110 Orion Documentation page 249
The design moments for each of the six regions can be displayed by clicking the Design button
shown below.:
The effective depth h to the centre of the bars is worked out separately at each location. This is
automatically reduced if the steel doesnt fit in a single layer.
Orion Documentation page 250 Chapter 17 : Beam Design to BS8110
You can control this calculation via the Design tab of Beam Design Settings as shown below:
Centre of Gravity of Steel Bars the section effective depth will be determined based on
the centre of gravity of the tension bars. In this method, the contribution of each tension
bar in the section will be considered separately.
Centre of Gravity of Layers in this more conservative method the calculation of section
effective depth is based on the average of the distances of the steel bar layers.
Values for K, K, x, As, and As are then all calculated for each region and are also shown in the
same table.
Where the ratio of K/K is less than 1.0 no compression steel is required.
Chapter 17 : Beam Design to BS8110 Orion Documentation page 251
5. Design for Shear- Cl 3.4.5
The design shear force at the column face, Vd is displayed in the same table as the design
moments:
From the Design tab of Beam Design Settings you can specify if you want to design for this
value, or (if the conditions of Cl. 3.4.5.10 are met) you may choose to design for the shear at d
from the column face.
Orion Documentation page 252 Chapter 17 : Beam Design to BS8110
If the latter option is adopted the design shear force at d is then displayed and used in the
design calculations as shown below:
In the above table, the maximum shear stress v is determined from Cl 3.4.5.2 and is always
based on Vd (not Vd@d). This is cross checked against the maximum permissible shear stress
v-max, which is defined in the beam design settings.
vc is calculated using the equation in table 3.8. In BS8110 the concrete grade considered for
shear is capped at 40N/mm2.
Link requirements are established from Table 3.7 as follows - v is determined from either Vd or
Vd@d depending on your choice in the beam design settings and Vnom Nominal shear
capacity (based on minimum link provision) is established.
The maximum shear requirement is then checked at each end of the beam and if the nominal
capacity is not sufficient additional links are provided over a distance (x) extending to the
point where the nominal capacity is adequate (or beyond if user preferences dictate minimum
lengths).
Chapter 17 : Beam Design to BS8110 Orion Documentation page 253
6. Deflection Checks- Cl 3.4.6
Basic span/effective depth ratios are calculated from Table 3.9 and modification factors
applied according to Table 3.10 and 3.11.
Note The beam size is not automatically increased to satisfy the deflection criteria - it
is highly unusual for beams to be sized so that deflection is a controlling factor.
Also, it should be noted that increasing the steel is usually a highly uneconomic
way of controlling deflection. It is more normal to conclude that the beam is not
deep enough if beam deflection checks fail.
Worked Example
The Design Model
The example model Doc_Example_4 is opened and saved to a new name (so as not to destroy
the original example). In the calculations that follow, the steel grade has been set to 500 with a
steel material factor of 1.15. Bar diameters permitted for the longitudinal steel in the beams
have been limited to 10, 12, 16, 20 and 25mm. The minimum link diameter is set to 10mm.
The concrete grade is C40. Note that to obtain similar results you will need to apply the same
settings. However, the actual design process would be identical irrespective of which material
grades, material factors and bar diameters are used.
The continuous beam on grid line 2 will be designed and the following calculations will focus
on the design of beam 1B14.
Orion Documentation page 254 Chapter 17 : Beam Design to BS8110
Beam 1B14
span = 4m
beam depth, h = 400mm
beam width, b = 250mm
cover = 20mm
Beam Design Settings
The beam design settings initially adopted are as shown:
Settings on the Design tab
Note Where the cover shown above has been set to 0 - as noted on the dialog, the cover
is then based on code requirements - (i.e. a default cover of 20mm is applied). You
may prefer to enter a value directly into each field to set the cover required.
Settings on the Parameters tab
Chapter 17 : Beam Design to BS8110 Orion Documentation page 255
Settings on the Bar Selection/Steel Pattern tab
Settings on the Bar Selection/Links tab
Analysis Results
Having run a building analysis using default analysis settings, the design envelope for all
combinations is as follows:
Orion Documentation page 256 Chapter 17 : Beam Design to BS8110
Performing the Design
To perform the design calculations select beam 1B14, right click and choose Beam
Reinforcement Design from the menu. This will display the data for the three beams on Axis 2,
with beam 1B14 highlighted:
Each stage of the design process will now be examined in detail.
Design for Bending - Cl 3.4.4.4
Click the Design button to see the six design moments for 1B14 determined from the analysis
moments shown previously:
The area of steel calculations are listed below the design moments. These can be confirmed
with simple hand calculations using Cl 3.4.4.4. However, before this can be done we need to
know the bar sizes used to accurately calculate the effective depth.
Click the Steel Bars button to see the steel bars provided:
Chapter 17 : Beam Design to BS8110 Orion Documentation page 257
Effective depth to bar centre
h (RHS top edge) = 400 - 20 - 10 - 12/2= 364mm
h (other locations) = 400 - 20 - 10 - 10/2 = 365mm
Area of Steel Required: Top Edge - Left Hand Side
K = M/bd
2
f
cu
= 0.011
K = 0.156
K/K = 0.07 < 1.0 compression steel not required
z = d(0.5 + (0.25 K/0.9)
0.5
) = 0.99d
z = min (0.99d, 0.95d) = 347mm
x = (d-z) / 0.45 = 40.6mm OK
As required = M / 0.87f
y
z = 98.0mm
2

Minimum As from Table 3.25
0.13x250x400 =130mm
2
Area of Steel Required: Top Edge - Right Hand Side
K = M/bd
2
f
cu
= 0.022
K = 0.156
K/K = 0.14 < 1.0 compression steel not required
z = d(0.5 + (0.25 K/0.9)
0.5
) = 0.97d
z = min (0.97d, 0.95d) = 346mm
x = (d-z) / 0.45 = 40.4mm OK
As required = M / 0.87f
y
z = 196.7mm
2

Note Similar calculations to those shown above are performed for the other four
regions.
Area of Steel Provided:
The steel provision is dictated by the current Beam Design Settings. The bar selection and
curtailment options chosen will greatly influence the weight of steel and the complexity of
the resulting detail. For more information see the Beam Detailing chapter of this
Handbook.
Orion Documentation page 258 Chapter 17 : Beam Design to BS8110
Design for Shear - Cl 3.4.5
On the Reinforcement Data dialog, click on any of the link fields for 1B14 to see the shear
design calculations:
Left Hand Support
Max shear stress from Cl 3.4.5.2
v =Vd / b
v
d = 0.41 N/mm
2
< v-max - OK
v
c
is calculated using the equation in table 3.8
d = 365mm, As = 157.1mm
2
100A
s
/b.d = 0.172
Note As provided is used in the above calculation
v
c
= (40/25)
0.33
0.79.(0.172)
0.33
(400/365)
0.25
/1.25 = 0.42
Right Hand Support
Max shear stress from Cl 3.4.5.2
v =Vd / b
v
d = 0.49 N/mm
2
< v-max - OK
v
c
is calculated using the equation in table 3.8
d = 366mm, As = 226.2mm
2
100A
s
/b.d = 0.247
v
c
= (40/25)
0.33
0.79.(0.247)
0.33
(400/366)
0.25
/1.25 = 0.48
Chapter 17 : Beam Design to BS8110 Orion Documentation page 259
Span
v
c
is calculated using the equation in table 3.8
d = 365mm, As = 235.6mm
2
100A
s
/b.d = 0.258
v
c
= (40/25)
0.33
0.79.(0.258)
0.33
(400/365)
0.25
/1.25 = 0.48
Link requirements
Determine if minimum bars at maximum spacing provide minimum links
A
sv_req
/ s
v
= (0.4.b
v
.)/0.87f
yv
= 0.23
For minimum bars at maximum spacing, provide H10 links at 250mm centres
A
sv_prov
/ s
v
= 2 x 78.5 / 250 = 0.63
In this case OK - (if not OK decrease the spacing until requirement is met).
Calculate v
nom
using the minimum links
capacity from v
c
v
c
b.d = 43.8kN
capacity from links
(0.87 f
yv
A
sv_prov
/ (b
v
.s
v
)). (b
v
.d) = 99.8N
v
nom
= 43.8 + 99.7 = 143.6 kN
Determine if shear at the ends exceeds v
nom

40.7kN < 143.6kN
In this case OK - hence minimum links apply for whole length of beam.
Orion Documentation page 260 Chapter 17 : Beam Design to BS8110
If the shear at either end had exceeded v
nom
- the distance, x to the point where v
nom
is
adequate would be determined as shown below, and a calculation performed to
determine the increased links to apply over that length.
Deflection Checks- Cl 3.4.6
Checks are based on the span values for sagging moment design.
L/d = 4000/365 = 10.96 OK
Table 3.9. For a rectangular beam - basic permissible ratio = 26
Table 3.10 modification for tension reinforcement
M/bd
2
= 0.91
A
s req
= 201.2
A
s prov
= 235.7
fs = 2f
y
.A
s req
/ (3A
s prov
) = 284.5N/mm
2
Modification Factor = 1.44
Table 3.11 modification for compression reinforcement
100As
prov
/bd = 0.172
Modification Factor = 1.05
Therefore adjusted Permissible L/d = 26*1.44*1.05 = 39.4 OK
Chapter 17 : Beam Design to BS8110 Orion Documentation page 261
Output Calculations
The following report shows the output for the beams along axis 2:
Orion Documentation page 262 Chapter 18 : Beam Detailing
Chapter 18 Beam Detailing
Introduction
Orion has always included numerous beam design and detailing options that are all controlled
from the main beam Settings and Parameters dialog that is shown below.
Given that there are tabs with sub-tabs and numerous options under each, the control of these
settings can be very daunting. With each Orion release even more options tend to be added in
order to respond to user demand to be able to apply more and more specific preferences.
The objective of this chapter is to provide a brief overview of the options in general and then
more specifically the reinforcement pattern options, the first of which is highlighted above.
The Design and Detailing Process
Overview
It is worth considering why so many options have developed and to do so requires some
reflection on the design and detailing process. We can break this process into stages:
1. A model is created and analysed.
2. Analysis results are reviewed and design forces are established at critical cross sections.
3. Cross section design determines the areas of reinforcement required.
4. Bars are selected that provide at least sufficient reinforcement.
Chapter 18 : Beam Detailing Orion Documentation page 263
5. The bars are arranged and curtailed so that the reinforcement provided is sufficient at all
cross sections.
6. The information is conveyed on a detail drawing.
This may initially seem simple enough but it soon becomes apparent that any two engineers or
draughtsmen are quite likely to apply different preferences (personal preferences or company
standards) and get different results at every stage of the process.
The analysis stage is not the focus for this document but it is worth noting that Orion provides
many analysis options, which will mean the analysis results differ, for example:
Option to use rigid zones (not only generates a more complex analysis model but also
means that design moments at the face rather than the centre-line of the column may be
used).
Option to use flanged or rectangular section for the beams.
Options to adjust stiffnesses of beams, columns, etc.
Having got the analysis results we head into design and that is where all the settings in the
Beam Settings and Parameters dialog start to apply. The dialog is organised so that the main
tabs introduce settings in the order in which you would apply them in the design process. The
following subsections of this chapter provide an overview of the settings under each of the
main tabs in turn.
The Design Tab
These settings are generally self evident, they will tend to have a slight influence on the values
of A
s
required that emerge from the design. For example the options to design for the shear at
the column face and to use the rectangular section (rather than the flanged section) when the
flange is in compression will result in slightly more conservative steel area requirements.
Orion Documentation page 264 Chapter 18 : Beam Detailing
The Parameters Tab
Again, these settings are generally self evident, they set limits on the ranges and spacing of bars
which are considered when bars are being selected to provide reinforcement which at least
meets the minimum requirements determined during design.
The Bar Selection Tab
In this tab we start to apply more specific preferences which will affect the way in which bars
are selected to meet the A
s
requirements determined in design.
Chapter 18 : Beam Detailing Orion Documentation page 265
Standard Pattern 2 shown above is currently the most commonly used option. Many of the
other options under this tab and also under the curtailments tab are more tuned to standard
pattern 2. Later in this chapter we will look at each of the patterns in turn and at some of the
other options (particularly relating to this tab and the following curtailment tab) in more
detail.
The Curtailment Tab
In this tab we apply preferences as to how the reinforcement is curtailed. Although this is not
under the Detailing tab, these sorts of preferences are more traditionally applied by the detailer
than the designer.
Orion Documentation page 266 Chapter 18 : Beam Detailing
The Detailing Tab
In this tab all the preferences relate to detailing presentation options, i.e. changes here only
relate to presentation and not to the reinforcement selection.
The Layers Tab
Settings in this tab control the layering, line types etc. to be used in the DXF file, which can be
loaded into most general drafting packages.
Chapter 18 : Beam Detailing Orion Documentation page 267
Overview of Patterns
The concept of different basic patterns, which can then be optimised according to personal
preference, is actually derived from the publication Standard Method of Detailing Concrete
published by the Institution of Structural Engineers (UK) August 1999. In the section on
beam detailing (cl 5.4.20), two basic methods of detailing are introduced:
The Splice Bar Method A pattern aimed at prefabrication of cages and minimisation of
in situ steel fixing.
The Alternative Method A pattern more suited to in situ steel fixing.
Orions Patterns 1 and 2 are based on these suggestions.
Pattern 1 The Splice Bar Method
Orion Documentation page 268 Chapter 18 : Beam Detailing
The pattern is shown diagrammatically in the dialog above and in the typical detail below. The
main attribute of this pattern is that top and bottom bars all stop at each side of columns/
supports and then splice bars are used to maintain the required continuity through the
support.
All sorts of preferences can be applied to the pattern, generally this becomes a balance between
complexity and material efficiency, this concept is explored in detail later in this chapter.
Some general points worth noting at this stage are:
There are various options to merge bars through supports and between spans. If the
objective of using this pattern is to create beam details such that discrete reinforcing cages
for each beam can be constructed then lifted into position the merging options should all
be switched off.
Currently the pattern does not support top span bars that extend to the face of the support
(link hanger bars), the top span bars will always stop short of the support. This may mean
that the links towards each end of the cage are not fixed as securely as might be desired
during lifting. Some extra (un-detailed) top bars may be required.
In general it appears that this pattern has not yet been widely employed by Orion users, or if
used it has generated very little feedback. However since the pattern does encourage off-site
or low-level prefabrication it offers the possibility of reducing site risks by reducing work at
height. There may even be financial benefits to be secured from factory production of cages.
It is considered possible that the use of this pattern may become more dominant in the future.
Chapter 18 : Beam Detailing Orion Documentation page 269
Pattern 2 The Alternative Method
The pattern is shown diagrammatically in the dialog above and in the typical detail below.
Currently the top bars are the same for this pattern and pattern 1. The bottom bars are
different, the main difference being that they are allowed to run through the support and lap
directly with the bars in the adjacent span.
All sorts of preferences can be applied to the pattern, generally this becomes a balance between
complexity and material efficiency, this concept is explored in detail later in this chapter.
Some general points worth noting at this stage are:
This pattern is the mostly commonly used and so many of the options/preferences
introduced by user request tend to be more applicable to this case. The Detailed Example
and Comparisons are therefore most applicable to this pattern.
There are various options to merge bars through supports and between spans. Since this
pattern is not intended to lend itself to prefabrication these options are more applicable.
Orion Documentation page 270 Chapter 18 : Beam Detailing
Pattern 3 The Hanger Bar Method
The pattern is shown diagrammatically in the dialog above and in the typical detail below.
Currently the bottom bars are the same for this pattern and pattern 2. The top bars are
different, the main difference being that (link) hanger bars are used which can run through
several spans. These bars provide any required span moment resistance. Additional top
reinforcement is then added in as necessary through the supports.
Note that the detailing option to Re-Plot the Bars below the Beam has been used here to show
how top hanger bars extend through span 1 and into the middle of span 2.
All sorts of preferences can be applied to the pattern, generally this becomes a balance between
complexity and material efficiency, this concept is explored in detail later in this chapter.
Chapter 18 : Beam Detailing Orion Documentation page 271
Some general points worth noting at this stage are:
Since small bars extend right through the support where additional bars are also added,
this pattern may tend to produce cluttered details at the support or even prove to be
impractical from a spacing point of view.
As with pattern 1, it appears that this pattern has not yet been widely employed by Orion users,
or if used it has generated very little feedback.
The Bent-Up Pattern Method
This pattern is used in high seismic regions and is only shown here for completeness. The
current version of Orion only supports the Turkish earthquake code (in the Turkish language
version of Orion). In non-seismic regions use of this pattern is probably acceptable and is likely
to produce a very robust structure, probably at the expense of both reinforcement weight and
on-site construction complexity.
For now it is recommended that Orion users in non-seismic regions do not use this pattern. In
future releases when other international seismic design codes begin to be supported this
pattern will be more important.
Orion Documentation page 272 Chapter 18 : Beam Detailing
Overview of Beam Bar Spacing
This section explains the implementation of spacing checks in Orion. The application of such
checks in an automated design is potentially a highly complex procedure, (as every steel
selection affects every other steel selection). The approach adopted in Orion is relatively
simple, with the intention of enabling the smallest bars to work at the maximum allowable
spacing.
For each beam the spacing checks are applied at the six locations where the design checks are
performed - top left, span and right and bottom left, span and right:
The Bar spacing controls on the Parameters tab then operate as follows:
Minimum Top and Bottom Steel Spacing
These two fields are used to set the minimum desirable steel bar spacing.
The values entered must be equal to or greater than the minimum allowable spacing values
specified in the active reinforcement code. If you use a bigger value than the minimum
requirements of the code, the code values are still used by the program whenever necessary.
Maximum Tension Steel Spacing
The value entered must be equal to or less than the calculated maximum spacing for bars in
tension from the active reinforcement code. Note that the calculated value depends upon the
steel yield stress.
In an automated design Orion selects bottom span bars so as not to exceed this limit. The limit
is not applied to the bottom left and right support bars, although they are unlikely to exceed it
in most cases. The one exception that can occur is if, on the Steel Bar Selection > Steel Pattern
tab you check the option Use 2nd Bottom Bars for 70% As. This option is used to curtail this
steel so only 30% of it runs to the support; as a result you end up with larger spacings at the
ends. The spacing at the supports will potentially exceed the maximum limit (if this is the case
it is brought to your attention by being highlighted in red). The assumption is that by checking
the Use 2nd Bottom Bars for 70% As option you are intending the spacings at supports to be
increased in this way, hence the design is not rejected.
Maximum Compression Steel Spacing
In an automated design Orion selects top span bars so as not to exceed this limit (and by
extension the top left and right support bars are also spaced so as not to exceed the same
limit).
Chapter 18 : Beam Detailing Orion Documentation page 273
Maximum Compression Steel Spacing - Cantilever beams
If you examine a cantilever beam in interactive design you will find that the max spacing at the
top span and the cantilever end are shown in red as shown below:
This is because the compression steel spacing check is being applied to the designed top span
and cantilever end bars. However, as there is no design requirement for bars at this location
the check will always appear to fail. In this situation, providing the spacing check for the top
bars at the supported end is OK then the red text at these two locations can be ignored; the top
support bars are pulled through in the beam detail
Orion Documentation page 274 Chapter 18 : Beam Detailing
Maximum Bar Spacing for Crack Control (EC2 only)
In addition to the above user specified checks, an extra spacing check is applied if the design
code is set to EC2. Both top and bottom bars are checked at span and support locations in
accordance with Table 7.3N. This check is much more dependent on steel stress and the
loading conditions.
It is important to note that when the maximum spacing for crack control is exceeded the
actual spacing is highlighted in red but (providing the above user specified checks are
satisfactory) the design is not rejected - however, if the default tension and compression
spacings from the EC2 template have been adopted it is highly unlikely that this situation can
arise.
Detailed Example and Comparisons
Overview
As noted in the above sections, Orion offers lots of options to first choose a basic
reinforcement pattern and to then apply preferences as to how bars are selected, curtailed and
detailed. In general the application of any preference means that you are making a choice
between:
A minimum reinforcement weight option where the details may be more complex and
slightly more time consuming (more costly) to construct.
A more standardised/simplified detail where the weight of reinforcement is slightly higher,
but construction may be simplified.
Ultimately a judgement on the balance between standardisation and minimum weight is
applied in the hope of minimising the overall cost of construction. Traditionally engineers
and detailers will apply their preferences in this regard with very little quantitative knowledge
on either side of the equation. Orion offers much more scope to allow you to investigate the
impact of different standardisation options so that you have the potential to make more
considered judgements.
In this section we will start by setting up a basic reinforcing pattern and find the weight of
reinforcement that this generates for an entire floor. We will then start to apply preferences
one at a time, and in each case look at how the details get simplified but also determine how
much reinforcement weight gets added.
Note The procedure shown in this section can be applied to any Orion model (or more
usually one floor of a larger model) in a matter of minutes or perhaps hours
(depending on model size).
Chapter 18 : Beam Detailing Orion Documentation page 275
Basic Setup
First we will get the design and detailing set up so that we have the base data on which further
comparisons can be made. The floor we will look at is shown on the next page.
It is a reasonably simple layout of nearly 50 beams with typical spans in the region of 5 to 7 m.
The applied factored load is approximately 22 kN/m
2
.
The following subsections show the basic settings used for the initial design.
Orion Documentation page 276 Chapter 18 : Beam Detailing
Design Tab
The above settings are reasonably standard and will not be changed during any of the
subsequent comparisons.
Parameters Tab
In general the above settings are reasonably standard, but as will be shown in the subsequent
comparisons, adjusting or restricting the range of bars sizes to be used can influence the
efficiency of the design.
Chapter 18 : Beam Detailing Orion Documentation page 277
Bar Selection Tab
On the Method sub-tab shown above the bar size minimisation option is selected. This is
generally not the preferred option, but as will be shown it will actually lead to the minimum
weight of steel being determined.
Note that the steel bar area tolerance can be used to introduce an additional safety factor
during preliminary design.
Pattern 2 is selected and the options to use extra bars locally to enhance the support and span
moment capacities are both activated.
Orion Documentation page 278 Chapter 18 : Beam Detailing
The options that are not checked add constraints that will add reinforcement weight.
The options in the Bent-up Bars tab are only relevant to the Bent-up Pattern.
The links options are set as shown above.
Once again the options that are not checked add constraints that will add reinforcement
weight.
Curtailment Tab
Chapter 18 : Beam Detailing Orion Documentation page 279
On the Steel Bars sub-tab shown above the option to lap the bottom bars outside the support is
used. This seems to be the preferred option of most Orion users as it tends to reduce clutter
within the column. Although merging will reduce reinforcement weight slightly these options
are not activated yet, we will look at their effect later. The other options that are not checked
add constraints that will add reinforcement weight.
On the Steel Bars 2 sub-tab shown above the options are not checked once again because
adding these constraints will add reinforcement weight.
Note that the minimum Tension Lap Factor. This factor works as follows:
If you set the factor to 1.0, but for the lap in question the code minimum is 1.4, then we
still use 1.4.
If you set the factor to 1.4, but for the lap in question the code minimum is 1.0, then your
user over-ride applies - 1.4 gets used.
Orion Documentation page 280 Chapter 18 : Beam Detailing
Options under the Bob Control sub tab shown above are self-explanatory.
Note the setting for Min. Steel Bob Length shown above is 25 Dia. The actual minimum
specified in BS 8666:2005 Table 2 varies depending on the bar diameter. For 10mm bars it is 12
Dia, for larger bar sizes it reduces further to around 10 Dia. (Potentially then you might
consider reducing this for greater ecomony.)
The Min Steel Bob Length is compared with the bob length that would be required to achieve
the anchorage length, (which for design to BS8110 is taken from Table 3.27). Note that the
anchorage length is measured from the inside face of the supporting member.
The settings shown above are not changed within the comparisons in the next section.
Chapter 18 : Beam Detailing Orion Documentation page 281
Detailing Tab
As noted earlier, the options under this tab only affect the style of the display and not the
content. These options will not be changed at all during the comparisons in the next section.
The settings used for the comparisons are shown here with some brief discussion. In general
these might be considered a good set of suggested settings, but it is best to experiment a little
with all of these until you have optimised the detailing style to suit your own preferences.
On the General sub-tab shown above note the option to include bar marks. If you want to see
the bar mark appear in the bar label in the usual style you must also ensure that the settings in
the Graphical Editor Settings dialog are set as shown below.
Orion Documentation page 282 Chapter 18 : Beam Detailing
In the Beams sub-tab shown below we are using the option to refer to beams by the axes
(grids) that they lie on and between.
Note It is probably more usual to activate the option to put the beam label below the
detail, but this option is automatically deactivated when one of the other options
we will use is activated see later.
Chapter 18 : Beam Detailing Orion Documentation page 283
In the Sections sub-tab shown above we are choosing to see 3 sections on every beam, this can
be cut down. We have also chosen to use the axis (grid) label as a prefix to every section and
so we can restart the section numbers on every axis and still have a unique label on every
section. Since the axis labels are also used to reference the beams everything can be easily
cross-referenced.
Note If you choose to reference the beams using the beam labels (the numbers generated
as each beam is added to the model), it would be better to add the beam label as a
prefix to the section.
Orion Documentation page 284 Chapter 18 : Beam Detailing
In the Steel Bars and Links sub-tab shown above we have chosen to Re-plot the bars below the
beam. This is an extra option that goes beyond normal detailing practice, it is not suggested
in detailing guides perhaps because the extra drawing work it would generate would not be
justified when the drawings are prepared by hand. In Orion you get this extra/alternative
presentation of the reinforcement detail for no extra effort see below.
At first glance the above does not look standard and perhaps this puts some people off.
However the exploded reinforcement details provide extra (and clearer) information. We
would suggest that many Orion users might seriously consider using this option as a new way
of providing better information to the site. Alternatively, as we will see in the following
section, Orion provides a schedule that gives the overall weight of reinforcement, but it is not a
Chapter 18 : Beam Detailing Orion Documentation page 285
traditional bar bending schedule. If a traditional schedule is to be prepared the details need to
be taken off the drawings that Orion prepares, the detailer who prepares the schedule might be
able to do this more easily using the exploded view of the reinforcement.
The options under the Side Bars and Dimensioning (shown above) sub-tabs are all self-evident
and will not be changed during the following comparisons.
Orion Documentation page 286 Chapter 18 : Beam Detailing
Initial Design and Drawing Creation
Using the filter options to filter to the floor of interest, a design is then run of all the beams in
the floor. During this exercise care is taken to always reselect all bars during redesign.
Chapter 18 : Beam Detailing Orion Documentation page 287
Next a beam detail sheet is created for all the beams (i.e. all the beams on this floor) and the
option to include a quantity table is checked.
Clearly this sheet is not intended for printing, it is a quick way to get a lot of details into one
DXF file which a detailer can then organise onto several drawings for final editing and then
issue.
Orion Documentation page 288 Chapter 18 : Beam Detailing
Notice that at the top corner of the sheet there is a schedule that can be seen in partial close up
below.
At the top there is a summary of reinforcement used, below that the data is broken down for
each bar position (each bar mark) in two columns. For this initial design of all the beams on
this floor the key points to be noted are:
Total Reinforcement Weight 3246 kg
Total bar marks used 134
Effects of Applying Preferences
We will now go on to examine how the details are simplified as we apply a range of
preferences. As we do so we will also take note of how this adds reinforcement weight when
compared with the above data for the initial design.
Chapter 18 : Beam Detailing Orion Documentation page 289
Bar Spacing Maximisation
As noted earlier, the option to minimise bar sizes is not often used since this results in lots of
small bars being used at close centres rather than a few larger bars at wider spacing. If we
change to the more usual bar spacing maximisation method as shown above the weight of steel
changes as shown below.
The weight of reinforcement increases to 3467 kg but the number of bar marks reduces to 121.
Also note how the weight of H25 has gone up from 505 to 1130 kg while the H12 have
dropped from 930 to 285 kg.
In this case the weight goes up because the As provided (and hence weight used) changes in
bigger steps. For example if As required is 510 mmP
2
P then the size minimisation method will
pick 5 H12 (As = 566 mmP
2
P), while the spacing maximisation method might pick 2 H20 (As =
628 mmP
2
P).
We would emphasise again that the size minimisation method is not generally used and so in
the closing summary we have not used it as the base line figure for percentage comparisons.
Orion Documentation page 290 Chapter 18 : Beam Detailing
Limiting the Bar Range
This option is probably under utilised. In this example we will squeeze the maximum main
bar diameter which can be used down to H20 from H25. Basically this means that in
situations where 2 H25s were chosen we will now get 3 H20, etc. In addition there will be
some saving due to shorter laps.
The weight of reinforcement decreases to 3324 kg and the number of bar marks decreases by 1
to 120.
Chapter 18 : Beam Detailing Orion Documentation page 291
Note If you try to restrict the maximum bar size too much lots of beams will start to
appear as failed on the beam design summary see below.
The beams have a utilisation ratio of less that 1 but are being shown as failing because the
smaller bars (maximum size H16) at closer spacing are failing checks on minimum spacing. If
the failing beams are filtered out and redesigned with the maximum bar size increased to H20
then in this model the weight of reinforcement can actually be optimised to 3234 kg but at the
expense of going back up to 136 bar marks.
Ideally you probably want to use a range where the vast majority of beams pass with one
setting and then the remainder can be filtered out and will pass in a second run with a
different setting. The degree to which this would be necessary would be quite structure
dependent.
Orion Documentation page 292 Chapter 18 : Beam Detailing
Merging Bars
This option is widely used. Where bar groups of the same size meet they will be merged into
one bar group in preference to lapping (provided the total bar length is less that the specified
maximum bar length in the parameters tab). Therefore this option will reduce weight due to
savings in laps but will result in the handling and fixing of longer bars on site.
In this example the weight of reinforcement decreases to 3272 kg and the number of bar marks
decreases to 109. As we continue to simplify the detailing, later in the exercise this option will
start to have a greater effect.
Chapter 18 : Beam Detailing Orion Documentation page 293
Minimum Tension Lap
It is common practise to standardise laps. This can be done by changing the the minimum
Tension Lap Factor from 1.0 to 1.4. The result of this change is that where the code minimum
of 1.0 could be used then your user over-ride applies - 1.4 gets used throughout.
The weight of reinforcement increases to 3348 kg - the number of bar marks remains the same
at 109.
Orion Documentation page 294 Chapter 18 : Beam Detailing
Stop Using 2
nd
Support and Span Bars
In the bar selection tab settings shown earlier, all the options relating to 2
nd
support and span
bars were activated. The view below shows the sort of detail that this produces.
Note the shorter top support bars and the extra bottom span bars laid in to the central section
of the span. If the options are now deactivated as shown below, the detailing becomes simpler.
Chapter 18 : Beam Detailing Orion Documentation page 295
Notice how only one group of top support bars is used and that in the span all the bars extend
full length of the span.
The weight of reinforcement increases to 3614 kg and the number of bar marks drops to 86.
Orion Documentation page 296 Chapter 18 : Beam Detailing
Extend and Merge End Bars
In the bar curtailment tab above all the options to extend the top and bottom span bars right
in to the support have been activated. The options not to use any extra (shorter) bars locally at
the end support are also activated. The view below shows the simplified detail that results in
an end span.
Chapter 18 : Beam Detailing Orion Documentation page 297
Comparing the view above with the view below (that was obtained when the end support
curtailment options were all unchecked):
In the top view the H20 L bars in the top of the beam are extended and the short H16 span
bars disappear.
the bars in the bottom of the beam are unchanged - this option will not really have any
effect on the bottom bars unless there are significant wind/sway moments that cause more
steel to be required at the support than in the span.
The weight of reinforcement drops slightly to 3608 kg and the number of bar marks drops to
82.
Orion Documentation page 298 Chapter 18 : Beam Detailing
Extend Support Bars Symmetrically
In the bar curtailment tab above the option to extend the support bars symmetrically is
activated. In the view below you can see how support bars are extended to a proportion of the
span length (default 0.3 L may be adjusted to 0.25 L in line with BS8110 simplified detailing
rules the top span bars will by default be designed for the maximum hogging moment in the
central section of the beam see the design tab settings.)
When the bars are extended symmetrically the detail is arguably simpler (as shown below)
with less potential for misplacement when fixing on site. However it is worth noting that this
option will become impractical when the adjacent span lengths vary dramatically it can
mean that the top support bars start running right through the short span.
Chapter 18 : Beam Detailing Orion Documentation page 299
The weight of reinforcement increases to 3640 kg and the number of bar marks remains
unchanged at 82.
Standardise Link Size
Orion Documentation page 300 Chapter 18 : Beam Detailing
General Note When Orion is asked to Design Link Spacing at Supports it will check the span
region and each support region. If it finds that the reinforcement required in either support
region is the same as in the span region those two regions will be merged. The example below
shows this case.
In the links tab above two additional options have been activated:
Select Symmetrical Links for Support Regions This option means that when support
regions are required at both ends the bar size (but not the same spacing) used at each end
will be the same.
Same Bar Size at Support and Span This option means that the same bar size (but not the
same spacing) will be used throughout the span of each beam.
Chapter 18 : Beam Detailing Orion Documentation page 301
In the view above you can see how the second of these settings has forced the use of H10 links
throughout this beam, but since the maximum link spacing is 300 mm this just means extra
reinforcement weight.
In the particular model being used here H8 bars were used almost everywhere, so the above
two settings make almost no difference to the total steel quantity.
The weight of reinforcement increases to 3644 kg and the number of bar marks is unchanged
at 82. On a different project it is quite likely that applying these settings will have a bigger
effect on reinforcement weight.
Orion Documentation page 302 Chapter 18 : Beam Detailing
Uniform Links
The option to Design Link Spacing at Supports is not checked.
In the view above you can see how one link size and spacing is now used throughout this span.
Applying this preference to this model causes a reasonably significant increase in
reinforcement weight.
The weight of reinforcement increases to 3737 kg and the number of bar marks is still
unchanged at 82.
Chapter 18 : Beam Detailing Orion Documentation page 303
Summary
In the detailed example in the previous section we have successively applied more and more
bar selection and curtailment settings preferences and recorded how these changes affect the
total weight of reinforcement in an entire floor. The following table summarises the findings.
We would suggest the main points to be drawn from this example are:
1. Most Orion users will use the Bar Spacing Maximisation Method hence the use of the 3467
kg weight as the base line in the above table.
2. Most users will probably not have examined the possibilities of limiting the preferred
range of bars used in which case potential efficiencies may have been missed (in this case a
saving of 4% in reinforcement weight).
3. If the weight after Limiting the Bar Range (3324 kg) were used as the base line figure then
the net effect of introducing all the standardisation/simplification up to and including the
option to Standardise Link Size is:
The number of bar marks reduces from 120 to 82 (more than 30% reduction)
The weight increases to 3737 kg (a 12.5% increase)
4. We would suggest that the option to use Uniform Links throughout is used cautiously; it
can add a lot of weight.
5. If the bar range is not so limited, but all the other preferences up to the option to
Standardise Link Size are still applied, the total weight goes up from 3644 kg to:
If T25s are allowed 3841 kg (an extra 5.5%)
If T32s are allowed 3927 kg (an extra 8%)
Cumulative Adjustments
No of Bar
Marks
Used
Total
Weight
kg
Percentage Weight
Added
Starting Model using Bar Size
Minimisation
134 3246 -6%
Bar Spacing Maximisation 121 3467 Base Line
Limiting the Bar Range 120 3324 -4%
Merging Bars 109 3272 -6%
Standardise Laps 109 3348 -3%
Stop Using 2
nd
Support and Span Bars 86 3614 +4%
Extend and Merge End Bars 82 3608 +4%
Extend Support Bars Symmetrically 82 3640 +5%
Standardise Link Size 82 3644 +5%
Use Uniform Links 82 3737 +8%
Orion Documentation page 304 Chapter 18 : Beam Detailing
Based on this example, the most important message is therefore the need to examine the
effects of reducing the maximum size of bar to be used in the design.
Finally, it is worth re-emphasising that all of these sorts of judgements have traditionally been
made on something of a gut feel basis during the course of design and detailing. The
automated procedures that Orion provides allow you to investigate options, quantify effects,
and optimise the design for any project in a matter of minutes or perhaps an hour.
Chapter 19 : Column Design to BS8110 Orion Documentation page 305
Chapter 19 Column Design to BS8110
Introduction
By default, Orion designs columns bent about a single axis, or bent about both axes using the
code clauses given in BS 8110-1:1997: Part 1 Section 3.8.
The following table summarises the various stages of the BS8110 column design process:
As indicated in the table, the program provides two design methods.
The default method applies Cl 3.8.4.5 to convert bi-axial moments into an equivalent uni-axial
design moment.
Alternatively if the bi-axial design method is selected, the bi-axial moments calculated in step
7 are fed directly into the member design stage and a more rigorous solution technique
developed from first principles is adopted. This can produce some economy, however because
the neutral axis will lie on an incline the results of the design process will be more difficult to
cross check.
Step Calculation Clause
1. Braced or unbraced? 3.8.1.5
2.
Calculate effective height using Part 2 of
the code
3.8.1.6
3. Check slenderness 3.8.1.3
4. Classify as short or slender 3.8.1.3
5. If slender - calculate Madd 3.8.3.1
6. Calculate minimum moments 3.8.2.4
7a. If braced - calculate design moments 3.8.3.2
7b. If unbraced - calculate design moments 3.8.3.7
8.
If using the BS8110 design method -
Calculate equivalent uni-axial design
moments
(If using the Bi-Axial design method -
skip this stage)
3.8.4.5
9. Member design 3.8.4
Orion Documentation page 306 Chapter 19 : Column Design to BS8110
For poly-line columns, as shown below, the bi-axial design method will always be adopted. .
The choice of design method is set via the column design settings dialog shown below..
The BS8110 Column Design Process
1. Braced or unbraced - Cl 3.8.1.5
Globally, columns will be considered as braced if this option has been selected in the Building
Parameters. Individual columns can have their braced/unbraced status modified within the
Chapter 19 : Column Design to BS8110 Orion Documentation page 307
Column Interactive Design, via the Slenderness tab as shown below:
For walls, the braced/unbraced status is applied in the same way as it is for columns. However,
it should be noted that walls can always be considered as braced along their major axis (i.e dir
1).
2. Calculate effective height- Cl 3.8.1.6
The effective height is determined from the equation:
l
e
=l
o
A rigorous assessment of the effective length is undertaken using the formulae given in 2.5 of
BS 8110-2:1985. Perhaps surprisingly, this can often result in a greater effective length than is
determined from the Tables 3.19 and 3.20 of BS 8110-1:1997.
Note: The beta value determined by part 2 can be edited and replaced by the value from the
tables if required.
3. Check slenderness limits- Cl 3.8.1.7 & 3.8.1.8
An error message is displayed during the interactive design if the slenderness limit has been
exceeded
4. Classify as short or slender- Cl 3.8.1.3
Columns and walls are considered as short when both the ratios lex/h and ley / b are less than
15 (braced) and 10 (unbraced), otherwise they are slender.
5. If slender - calculate M_add- Cl 3.8.3.1
In order to calculate the additional moment induced in the column it is required that factor K
be determined. Although the code allows for K to be conservatively taken as 1.0, Orion
calculates K using the equation 33 in the code:
K = (Nuz - N) / (Nuz - Nbal) <= 1
Orion Documentation page 308 Chapter 19 : Column Design to BS8110
The calculation of As
required
is itself an iterative process and K is re-calculated at every
iteration.
The following assumptions are applied to ensure the calculation of K remains slightly
conservative.
Calc of Nuz -
equation has two parts:
Steel - 0.87*fy*Asc - in this equation Orion uses Asc required (since it is illogical that we
should be able to fail a section by providing more steel than is required).
Concrete - 0.45*fcu*Ac - in this equation the net concrete area is used.
(Ac = gross area - Asc)
Calc of Nbal
The code indicates that this is based on 0.25*fcu*b*d. (d = eff depth). However, with the
aim of keeping Nbal large (hence making the calculation of K more conservative),
actually uses the gross concrete area here.
6. Calculate minimum moments - Cl 3.8.2.4
The minimum design moment is calculated in both directions taking the design ultimate axial
load acting at a minimum eccentricity as per Cl 3.8.2.4.
7a. If braced, calculate design moments about each axis - Cl 3.8.3.2
The design moment is calculated in both directions as the greatest of: M2, M
i
+M
add
,
M1+M
add
/2 or, e
min
*N
Where:
M
1
M
2
and M
add
are as defined in figure 3.20
M
i
= 0.4 M
1
+ 0.6 M
2
>= 0.4 M
2

7b. If unbraced, calculate design moments about each axis - Cl 3.8.3.7
The design moment is calculated in both directions as per figure 3.21
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5
Because there will always be at least a minimum moment acting in both directions, for
rectangular columns the design moment will always be determined from equations 40 and 41
in the code.
For Mx/h' >= My/b'
Mx' = Mx + (beta * h'/ b' * My)
For Mx/h' < My/b'
Chapter 19 : Column Design to BS8110 Orion Documentation page 309
My' = My + (beta * b'/ h' * Mx)
For circular columns the moments in the two directions are resolved.
9. Member Design - Cl 3.8.4
With the design axial load and design moment established, the program determines the
required steel area using the BS8110 stress block. The neutral axis of the cross section is
determined and a bar size and spacing obtained to provide sufficient moment capacity.
Each design combination is considered and the one that results in the largest steel area
requirement is selected as being critical.
Note If the minimum area of steel is satisfactory for every combination, the program
will record combination 1 as being critical, ( irrespective of the relative
magnitude of loads in each combiation) .
Three methods of bar selection are available:
Fixed bar layout The bar locations are defined by the user and the program
determines the bar size required
Bar Spacing Maximisation The program determines the bar size and spacing with the
aim to maximise the spacing. This is normally the preferred option.
Bar Size Minimisation The program determines the bar size and spacing with the aim
to minimise the bar size.
M Mx
2
My
2
+ =
Orion Documentation page 310 Chapter 19 : Column Design to BS8110
The maximum axial load is checked against Cl 3.8.4.3 or Cl 3.8.4.4. The program defaults to
the more conservative capacity determined by Cl 3.8.4.4. The clause used can be changed via
the BS8110 tab of the column design settings as shown:
Worked Examples
The Design Model
The example model Doc_Example_4 is opened and saved to a new name (so as not to destroy
the original example). The copied model is then adjusted so that its storey height is increased
to 5.5m and it is then re-analysed. In this model the steel grade is 460 and the steel material
factor is 1.15. Bar diameters of 13mm are used and 12mm bar diameters are excluded. The
minimum link diameter is set to 10mm. Note however, the actual design process would be
identical irrespective of which steel grade and material factor and bar diameters are used.
Chapter 19 : Column Design to BS8110 Orion Documentation page 311
Column Design Settings
The column design settings initially adopted are as shown:
Design Parameters
Steel Bars - Layout/Selection
Orion Documentation page 312 Chapter 19 : Column Design to BS8110
Steel Bars - Longitudinal Steel
Steel Bars - Links
Chapter 19 : Column Design to BS8110 Orion Documentation page 313
Braced Rectangular Column Example
Column 1C8 will be used to demonstrate the design process for a rectangular column.
column dimension in direction 1b
1
= 500 mm
column dimension in direction 2b
2
= 250 mm
The clear height of column in the two directions takes account of the beams framing in to the
top of the column.
L
o1
= 5500mm - 500mm = 5000 mm
L
o2
= 5500mm - 400mm = 5100 mm
Note As shown on the design screen above, if only 3 bars are placed in the x direction
the default clear bar spacing limit of 200mm (as specified in the Column Design
Settings) would be slightly exceeded. In the worked examples the Max. Column
Steel Bar Spacing has been relaxed to 205mm in order that the above bar layout
can be used.
Orion Documentation page 314 Chapter 19 : Column Design to BS8110
Performing the Design
To perform the calculations click the Design button. This will design the column for all the
highlighted design combinations. Design combination 1 is found to be critical and is
highlighted in red in the table as shown below.
Each stage of this design process will now examined in detail.
1. Braced or unbraced - Cl 3.8.1.5
In this example the column has been defined as braced in both directions. This can be
confirmed by clicking on the Slenderness tab.
Chapter 19 : Column Design to BS8110 Orion Documentation page 315
2. Calculate effective height- Cl 3.8.1.6
The effective length factors
1
and
2
that have been calculated are also displayed on the
Slenderness tab as shown.
These effective length factors are calculated as follows:
In direction 1
Beam stiffness at top of column
L = 5500mm b= 250mm d = 500mm
k
b1
=b*d
3
/(12* L) = 473484.8 mm
3

Column stiffness
k
c1
= b
2
*b
1
3
/(12 * L
o1
) = 520833.3 mm
3
calculation using the formulae given in 2.5 of BS 8110-2:1985

c2
= k
c1
/ k
b1
= 1.100

c1
= 1 (fixed base is defined in this example)

cmin
= min (
c1
,
c2
) =1.000
eq3 = 0.7 +0.05 *(
c1
+
c2
) = 0.805
eq4 = 0.85 +0.05 *(
cmin
) = 0.900

1
= min (eq3,eq4) = 0.805
In direction 2
Beam stiffness at top of column
L =4250mm b= 250mm d = 400mm
k
b1
=b*d
3
/(12* L) = 313725.5 mm3
Column stiffness
k
c1
= b
1
*b
2
3
/(12* L
o1
) = 130208.3 mm3
Orion Documentation page 316 Chapter 19 : Column Design to BS8110
Calculation using the formulae given in 2.5 of BS 8110-2:1985

c2
= k
c1
/ k
b1
= 0.415

c1
= 1 (fixed base is defined in this example)

cmin
= min (
c1
,
c2
) =0.415
eq3 = 0.7 +0.05 *(
c1
+
c2
) = 0.771
eq4 = 0.85 +0.05 *(
cmin
) = 0.871

2
= min (eq3,eq4) = 0.771
Effective member lengths
Le1 =
1
* L
o1
= 4025 mm
Le2 =
2
* L
o2
= 3931 mm
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8
60 * 250mm = 15000mn OK
4. Classify as short or slender - Cl 3.8.1.3
The classification is shown on the Column Reinforcement Design dialog.
5. If slender - calculate Madd- Cl 3.8.3.1
Depending on the classification the
a
and M
add
values have been calculated accordingly and
are displayed on the Slenderness tab.
In direction 1

a1
= 1/2000 * (
1
* L
o1
/b
1
)
2
= 0.032
Chapter 19 : Column Design to BS8110 Orion Documentation page 317
column is not slender, hence
M
add1
= 0 kNm
In direction 2

a2
= 1/2000 * (
2
* L
o2
/b
2
)
2
= 0.123
Column is slender, hence:
Calculate M
add
K = (Nuz - N) / (Nuz - Nbal) <= 1
Applied Axial Load, N = 151.8 kN
col dimension (in direction under consideration), h = 500 mm
column width, b
2
= 250 mm
concrete grade, f
cu
= 40 N/mm2
steel grade, f
y
= 460 N/mm2
material factor for steel ,
s
= 1.150
area of steel requiredA
s_req
= 654.1 mm2
Nuz = 0.45 * f
cu
* (b
1
*b
2
- A
s_req
)+ 0.87 * f
y
* A
s_req
= 2500.0 kN
Nbal = 0.25 * f
cu
* (b
1
*b
2
)= 1250.0 kN
(Nuz - N) / (Nuz - Nbal) = 1.879
Hence
K = 1
A
u
= (
a2
* K * b
2
) = 30.8 mm
Additional MomentM
add2
= N * A
u
= 4.68 kNm
Orion Documentation page 318 Chapter 19 : Column Design to BS8110
6. Calculate minimum moments - Cl 3.8.2.4
These are shown on the Column Reinforcement Design dialog.
Minimum eccentricity1 = min (0.05* h, 20mm) = 20mm
Minimum eccentricity2 = min (0.05* b, 20mm) = 12.5mm
M
1min
= N * 20mm = 3.04 kNm
M
2min
= N * 12.5mm = 1.90 kNm
7. Calculate design moments about each axis - Cl 3.8.3.2
These are also shown on the Column Reinforcement Design dialog.
In direction 1
Smaller end momentM
11
= -28.20 kNm
Larger end momentM
21
= 57.41 kNm
M
i1
= 0.4 M
11
+ 0.6 M
21
>= 0.4 M
21
M
i1
= 0.4*M
11
+ 0.6*M
21
= 23.17 kNm
0.4 * M
21
= 22.96 kNm
Hence
M
i1
= 23.17 kNm
M
d1eff
= Max (abs(M
21
),abs(M
i1
+M
add1
),abs(M
11
+Ma
dd1
/2), M
1min
) = 57.41 kNm
In direction 2
Smaller end momentM
12
= 7.85 kNm
Larger end momentM
22
= -15.77 kNm
M
i2
= 0.4 * M
12
+ 0.6* M
22
>= 0.4 M
21
Chapter 19 : Column Design to BS8110 Orion Documentation page 319
M
i2
= 0.4*M
12
+ 0.6*M
22
= -6.32 kNm
0.4 * M
22
= -6.31 kNm
Hence
M
i2
= -6.32 kNm
M
d2eff
= Max (abs(M
22
),abs(M
i2
+Ma
dd2
),abs(M
12
+M
add2
/2), M
2min
) = 15.77 kNm
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5
The effective design moment is calculated from equations 40 and 41
longitudinal bar dia = 13mm
cover = 20mm
links = 10mm
Mx = M
d2eff
= 15.77 kNm
My = M
d1eff
= 57.41 kNm
h' = b
2
- cover - links - dia/2 = 213.5 mm
b' = b
1
- cover - links - dia/2 = 463.5 mm
Mx/h' = 73.9 kN
My/b' =123.9 kN
Mx/h' < My/b' hence
My' = My + ( * b'/ h' * Mx)
N/(b
1
*b
2
*f
cu
) = 0.030
= 0.961
My' = My + ( * b'/ h' * Mx) = 90.3 kNm
Orion Documentation page 320 Chapter 19 : Column Design to BS8110
9. Member Design - Cl 3.8.4
Design forces
N = 151.75kN
My' = 90.39kNm
Mx' = 0.00kNm
Solution determined by Orion:
Distance to neutral axisYbar = 64.84 mm
Area of steel requiredA
sreq
= 650.8 mm2
Area of steel providedAs
prov
= 796.4 mm2
Reinforcement in Section
X1 = cover +links + dia/2 = 36.5 mm
X2= 500mm /2 = 250.0 mm
X3= 500mm - cover - links - dia/2 = 463.5 mm
Ybar > X1, hence bars at X1 are in compression
Chapter 19 : Column Design to BS8110 Orion Documentation page 321
Calculate maximum axial load - Cl 3.8.4.3 or Cl 3.8.4.4.
In this example the design ultimate axial load is determined using Cl. 3.8.4.3.
N
max
= 0.4*f
cu
* b
1
* b
2
+ 0.75 * As
prov
* f
y
= 2274.8 kN > N OK
Cross check of the above solution
The solution can be cross checked using two basic equations given in standard texts. For
example: W.H. Mosley and J.H. Bungey, Reinforced Concrete Design, (MacMillan)
1. Resolving forces vertically:
N = F
CC
+ F
ST
+ F
SC
Where:
Fcc is Concrete compressive force
F
ST
is Steel tensile force
F
SC
is Steel compressive force
2. Taking moments about mid-depth of section (should equate to zero):
The applied moment My' must be balanced by the moment of resistance of the forces
developed within the cross section.
Resolving forces vertically:
N = F
CC
+ F
ST
+ F
SC
Bars in tension are fully stressed, hence
Total Tensile force in bars at X2 and X3
Orion Documentation page 322 Chapter 19 : Column Design to BS8110
F
ST
= -4*As
req
/6 * 460N/mm2 /1.15 = -173.56kN
Compressive force in concrete, using the BS8110 rectangular stress block
F
CC
= 0.67/1.5 * f
cu
* (0.9*Ybar*h) = 260.67 kN
Total compressive force in bars at X1
F
SC
= N - F
ST
- F
CC
= 64.69 kN
Taking moments about mid-depth of section (should equate to zero):
Distance to centre of concrete compression force X
CC
= 500mm/2 - 0.9*Ybar/2 = 220.8 mm
Distance to centre of steel compression force X
SC
=500mm/2 - X1= 213.5 mm
Distance to centre of steel tension force X
ST
=(X3+X2)/2 -500mm/2 = 106.8 mm
My' - X
CC
*F
CC
+ X
ST
*F
ST
- X
SC
*F
SC
= 0.5 kNm
The right hand side of the above equation should equate to zero to within an acceptable
tolerance. To determine if this result is OK, recalculate the actual value of My' required for this
to be the case and then compare the two.
My'actual = X
CC
*F
CC
- X
ST
*F
ST
+ X
SC
*F
SC
= 89.90 kNm
My' / My'actual = 1.005 OK
Note that the above cross check shows that if the As
required
was actually the amount provided
then the required capacity is just sufficient.
In all cases As
prov
will exceed As
req
to some degree. Orion reports the ratio: As
req
/As
prov
as the
utilisation ratio.
Utilisation Ratio As
req
/As
prov
= 0.82
Chapter 19 : Column Design to BS8110 Orion Documentation page 323
It is important to appreciate that 82% utilisation does not mean that 18% more load can be
added. As is shown on the interaction diagram for this column, a great deal more axial load
could be added.
Bi-Axial Design Method Example
From the Column Design Settings dialog, change the design method to bi-axial.
Orion Documentation page 324 Chapter 19 : Column Design to BS8110
Then re-design column 1C8 once more.
It is important to note that design stages 1 to 7 are identical to the previous example, hence the
effective design moments about each axis are unchanged:
M
d1eff
= Max (abs(M
21
),abs(M
i1
+M
add1
),abs(M
11
+M
add1
/2), M
1min
) = 57.41 kNm
M
d2eff
= Max (abs(M
22
),abs(M
i2
+M
add2
),abs(M
12
+M
add2
/2), M
2min
) = 15.77 kNm
Instead of converting these to a uni-axial design moment (as per stage 8), an exact solution is
determined using the bi-axial moments.
The result is that the area of steel required drops from 650.8mm2 to 328.8mm2.
Thus, this design method can obviously be seen to provide a more economical solution. The
drawback is that because the neutral axis is no longer parallel to either face of the column
verification is more difficult. The cross checks required do not lend themselves to hand
calculation.
Chapter 19 : Column Design to BS8110 Orion Documentation page 325
Braced Circular Column Example
From the Column Design Settings dialog, change the design method to BS8110-Cl.3.8.4.5..
Column 1C12 will be used to demonstrate the design process for a circular column.
Click on the Parameters button and change to fixed bar layout.
This will force the design to adopt the number of bars shown in the 'Qty' cell of the above
table. In this example we will use 8 bars in the design, (Qty = 8). When the design is
performed, the bar sizes will be adjusted to obtain an economic solution based on this layout.
column diameterD = 500 mm
The clear height of column in the two directions takes account of the beams framing in to the
top of the column.
L
o1
= 5500mm - 500mm = 5000mm
L
o2
= 5500mm - 400mm = 5100mm
Orion Documentation page 326 Chapter 19 : Column Design to BS8110
1. Braced or unbraced - Cl 3.8.1.5
All the columns in this building should be considered as braced. If the column is designed as
such, the effective length factors in the two directions are calculated as:

1
= 0.846

2
= 0.900
2. Calculate effective height- Cl 3.8.1.6
The values of
1
and
2
are calculated in the same way as in the previous rectangular column
example. The full calculations will therefore not be repeated here.
The column slenderness is calculated as:
L
e1
=
1
* L
o1
= 4230 mm
L
e2
=
2
* L
o2
= 4590 mm
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8
60 * D = 30000 mm OK
Chapter 19 : Column Design to BS8110 Orion Documentation page 327
4. Classify as short or slender - Cl 3.8.1.3
5. If slender - calculate Madd- Cl 3.8.3.1
Short hence:
Additional MomentM
add1
= 0 kNm
Additional MomentM
add2
= 0 kNm
6. Calculate minimum moments - Cl 3.8.2.4
Applied Axial Load, N = 243.4 kN
Minimum eccentricity, e
min
= min (0.05* D, 20mm) = 20 mm
M
min
= N * e
min
= 4.87 kNm
Note that when braced, combination 2 is identified as the critical combination.
Orion Documentation page 328 Chapter 19 : Column Design to BS8110
7. Calculate design moments about each axis - Cl 3.8.3.2
In direction 1
Smaller end momentM
11
= -19.97 kNm
Larger end momentM
21
= 40.56 kNm
As the column is short the effective moment is simply:
M
d1eff
= Max (abs(M
21
), M
min
) = 40.56 kNm
In direction 2
Smaller end momentM
12
= -39.85 kNm
Larger end momentM
22
= 80.60 kNm
M
d2eff
= Max (abs(M
22
), M
min
) = 80.60 kNm
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5
Mx = M
d2eff
= 80.60 kNm
My = M
d1eff
= 40.56 kNm
Mx' = squareroot (Mx
2
+ My
2
) = 90.23 kNm
Chapter 19 : Column Design to BS8110 Orion Documentation page 329
9. Member Design - Cl 3.8.4
Solution determined by
Distance to neutral axisYbar = 88.30 mm
Area of steel requiredAs = 520.3 mm2
Area of steel providedAs_prov = 1061.9 mm2
No. of bars providednbar = 8
Before cross checking this solution for equilibrium, we will first make the column unbraced.
Unbraced Circular Column Example
The previous calculations are now repeated with the column specified as unbraced.
1. Braced or unbraced - Cl 3.8.1.5
To change the column to unbraced, uncheck the 'Dir 1 and Dir 2 braced' boxes on the
slenderness tab as shown below and the click the Design button:
Orion Documentation page 330 Chapter 19 : Column Design to BS8110
When unbraced, the effective length factors in the two directions for this column change to:

1
= 1.439

2
= 1.684
2. Calculate effective height- Cl 3.8.1.6
When considered unbraced, the column slenderness is calculated as:
L
e1
=
1
* L
o1
= 7195 mm
L
e2
=
2
* L
o2
= 8588 mm
3. Check slenderness limits - Cl 3.8.1.7 & 3.8.1.8
60 * D = 30000 mm OK
4. Classify as short or slender - Cl 3.8.1.3
5. If slender - calculate Madd - Cl 3.8.3.1
In direction 1

a1
= 1/2000 * (
1
* L
o1
/D)
2
= 0.104
In direction 2

a2
= 1/2000 * (
2
* L
o2
/D)
2
= 0.148
Chapter 19 : Column Design to BS8110 Orion Documentation page 331
Calculate M
add
K = (Nuz - N) / (Nuz - Nbal) <= 1
Note that now the column is unbraced, combination 1 has become the most critical
combination and hence the value of N has changed in the calculation of K below.
Applied Axial LoadN = 285.1 kN
Area of sectionA = pi * (D/2)2 =196349.5 mm2
concrete gradef
cu
= 40 N/mm2
steel gradef
y
= 460 N/mm2
material factor for steel
s
= 1.150
area of steel requiredAs
req
= 845.1 mm2
Nuz = 0.45 * f
cu
* (A - As
req
)+ 0.87 * f
y
* As
req
= 3857.3 kN
Nbal = 0.25 * f
cu
* A = 1963.5 kN
(Nuz - N) / (Nuz - Nbal) = 1.886
Hence K = 1
A
u1
= (
a1
* K * D) = 51.8 mm
Additional MomentM
add1
= N * A
u1
= 14.76 kNm
A
u2
= (
a2
* K * D) = 73.8 mm
Additional MomentM
add2
= N * A
u2
= 21.03 kNm
6. Calculate minimum moments - Cl 3.8.2.4
Minimum eccentricity e
min
= min (0.05* D, 20mm) = 20 mm
M
min
= N * e
min
= 5.70 kNm
Orion Documentation page 332 Chapter 19 : Column Design to BS8110
7. Calculate unbraced design moments about each axis - Cl 3.8.3.2
In direction 1
Smaller end momentM
11
= 0.00 kNm
Larger end momentM
21
= 0.00 kNm
M
d1eff
= Max (abs(M
21
+M
add1
),abs(M
11
+M
add1
), M
min
) = 14.76 kNm
In direction 2
Smaller end momentM
12
= -47.50 kNm
Larger end momentM
22
= 96.21 kNm
M
d2eff
= Max (abs(M
22
+M
add2
),abs(M
12
+M
add2
), M
2min
) = 117.24 kNm
8. Calculate equivalent uni-axial design moments - Cl 3.8.4.5
Mx = M
d2eff
= 117.24 kNm
My = M
d1eff
= 14.76 kNm
Mx' = squareroot (Mx
2
+ My
2
) = 118.17 kNm
9. Member Design - Cl 3.8.4
Design forces
N = 285.056kN
My' = 118.17kNm
Chapter 19 : Column Design to BS8110 Orion Documentation page 333
Solution determined by Orion:
Distance to neutral axisYbar = 103.90 mm
Area of steel requiredAs
req
= 845.1 mm2
Area of steel providedAs
prov
= 1061.9 mm2
No. of bars providednbar = 8
Area of steel required per barAs/nbar = 81.8 mm2
Cross check of the above solution
Reinforcement in Section
column diameter D = 500 mm
bar diameter dia = 13 mm
cover = 20 mm
links = 10mm
Bar distances from mid depth
X1 = D/2 - cover - dia/2 = 213.5 mm
Orion Documentation page 334 Chapter 19 : Column Design to BS8110
X2= squareroot (X1
2
/2) = 151.0 mm
X3= 0mm
X4 = X2= 250mm
X5 = X1 = 214 mm
Ybar > (250mm -X2), hence bars at X1 and X2 are in compression
Resolving forces vertically:
N = F
CC
+ F
ST
+ F
SC
Where:
F
CC
is Concrete compressive force
F
ST
is Steel tensile force
F
SC
is Steel compressive force
Bars in tension are fully stressed, hence
Total Tensile force in bars at X3, X4 and X5
F
ST
= -5* As
req
/nbar * 460N/mm2 /1.15 = -211.3kN
Tensile force per bar at X3, X4 and X5
F
STbar
= F
ST
/5 = -42.3kN
The area of concrete in compression (the shaded area above) is determined from the equation:
A = R
2
tan-1 (squareroot (R/r)
2
-1) - r (squareroot (R
2
- r
2
)
R = D/2 = 250 mm
r = R - Ybar = 146 mm
A = 29568 mm2
Chapter 19 : Column Design to BS8110 Orion Documentation page 335
Compressive force in concrete, using the BS8110 rectangular stress block
F
CC
= 0.67/1.5 * f
cu
* (0.9*A) = 475.5 kN
Total compressive force in bars at X1and X2
F
SC
= N - F
ST
- F
CC
= 20.9 kN
Compressive force per bar at X1 and X2
F
SCbar
= F
SC
/3 = 7.0 kN
Taking moments about mid-depth of section (should equate to zero):
For this hand calculation it has been assumed that the centre of concrete compression force is
at 2Ybar/3 from the top of the section. The software would of course perform a rigourous
calculation to determine the exact position of the centre of concrete compression force.
Distance to centre of compression force X
CC
= R - 2*Ybar/3 = 180.7 mm
My'actual = X
CC
*F
CC
+ X1*F
SCbar
+ 2*X2*F
SCbar
- 2*X4*F
STbar
- X5*F
STbar
= 121.0 kNm
Orion Documentation page 336 Chapter 19 : Column Design to BS8110
My' / My'actual = 0.98 OK
Utilisation Ratio As
req
/As
prov
= 0.80 OK
Chapter 20 : Wall Design and Detailing Orion Documentation page 337
Chapter 20 Wall Design and Detailing
Introduction
Orion designs walls in the same way as columns, therefore for general details of the design
process refer to the previous chapter - Column Design to BS8110.
In this chapter additional aspects of the process that are unique to walls are examined.
Conservatism in the design method
The analysis phase described inthe chapter Wall Modelling Considerations determines Wall
Panel Design Forces. Each wall panel is then independently designed for these forces.
Therefore, when Orion designs a wall panel it is designing a discrete rectangular section.
In the cases of Core Walls (where there are several interconnected panels), this design
approach will be conservative for two reasons:
1. Core walls introduce flanges, and just as for beams these flanges will enhance the bending
capacity when they are considered (and when they act in compression). The concrete
stress block develops over a reduced depth and so a bigger lever arm develops between the
concrete and steel forces, hence greater moment capacity.
2. As is shown below, the detailing where panels overlap must be manually edited so that the
sum of the requirements for each panel are provided in the overlapping zone. Where the
critical design case determining the requirements in each panel is different it will be
conservative to provide the sum of the two.
Wall Design and Detailing Options
As with columns, preferences can be applied to the design and there are a number of aspects of
this that are worth highlighting.
Design With End Zones
Choosing to use End Zones makes a significant difference to the way reinforcement is
provided within the section - heavier bars will be concentrated in a zone at each end of the
wall and smaller bars will be used in the mid section.
Orion Documentation page 338 Chapter 20 : Wall Design and Detailing
In the column/wall design settings you can choose between shear wall reinforcing styles
shear walls with or without End Zones.
The column application plan view below shows the reinforcing for wall panels when end zones
are requested. Note that there is significant overlapping of the bars where the panels overlap.
Chapter 20 : Wall Design and Detailing Orion Documentation page 339
As noted earlier, this is one of the areas where manual adjustment of the detailing is required.
The detailer needs to look at the total reinforcement required in the overlapping zone and
provide the same total in a revised corner detail. For example, at the corner of walls 1 and 2,
wall 1 has 7 T20 bars and wall 2 has 13 T16, the detailer might change this to 10 T25. As noted
previously this summing of the individual panel requirements is a safe engineering approach.
Design Without End Zones
The view above shows the column application plan view after redesigning all the walls having
changed to the design setting where End Zones are not considered.
When end zones are not used the same bar size will be used throughout the length of the wall
with the exception of the end corner bars which may be larger.
Once again there is a certain amount of overlapping reinforcing between wall panels that
needs to be rationalised, but this tends to be a simpler process where end zones are not used.
Should I use End Zones?
The subject of zoned reinforcement (or boundary elements) tends to be dealt with under the
heading of Earthquake Resistance in building codes and texts. However it is clearly logical
that zoning of reinforcement in the ends of wall panels is a valid and potentially more efficient
approach to wall design wherever lateral loading is generating significant in-plane moments.
The main reason why the option not to consider end zones becomes more efficient at lower
loading levels is that minimum steel requirements start to dominate. Within Orion, when
zoned reinforcement is used then minimum reinforcing requirements within the zones are
applied. These minimum levels mean that the overall minimum reinforcing requirement for
the wall is around 0.52%. When end zones are not used the standard BS8110 code limit of
0.4% is applied.
Orion Documentation page 340 Chapter 20 : Wall Design and Detailing
Note Even when end zones are not used Orion will still tend to suggest a larger bar size
at the extreme ends of the wall. Sometimes this might be needed because it
increases the supplied steel just enough to exceed the minimum steel requirement.
Sometimes it may also help to satisfy detailing (maximum spacing) requirements
across the end of the wall. However Orion will often provide larger bars here for
no other reason than it is considered Good Practice. In the case of intersecting
walls it is particularly felt that this is good practice. However, it is acknowledged
that some engineers would prefer to use a single main bar size throughout and the
option to set this preference will be added in a future release of Orion. For now it
is possible to interactively adjust the sizes of the end bars to achieve this objective.
The British Standard does not really acknowledge or provide guidance on End Zones. It is
written from the point of view that walls will be quite uniformly reinforced, hence many Orion
users will prefer to use the option NOT to consider end zones. As is demonstrated in the
above example, for many structures this will actually give a lesser reinforcing requirement.
The only argument that can be set against this approach is in the case where the walls are
actually resisting significant in-plane moments. In such cases not only does the end zone
approach become more efficient, it also puts the steel where the strain is and so potentially
limits cracking more efficiently.
Plain Wall Design
In the column/wall design settings you can choose to Use Plain Wall Design where it is
applicable.
BS8110 cl 1.3.4.7 defines a plain wall as one that contains either no reinforcement, or
insufficient to satisfy the criteria in cl 3.12.5. Any reinforcement supplied is ignored when
considering the strength of the wall. Where no reinforcement is required in the design of the
wall cl 3.9.4.19 indicates that if reinforcement is provided at all, it should be at least 0.25% (for
Gr460/500 steel) and 0.3% (for Gr250 steel)
Therefore, if design can be based on no reinforcement and this indicates a capacity in excess of
that required for the design combinations, a lower minimum reinforcement level can be used.
Note Where reinforcement is less than 2% design will automatically exclude ties.
Chapter 20 : Wall Design and Detailing Orion Documentation page 341
Orion will determine if a wall section is in compression throughout for each applied load
combination. When compression throughout is proven then design will utilise this lower
minimum steel provision.
The "detailed design report" option includes a statement that wall is in compression
throughout and that plain wall design applies as shown below:
Although plain wall design applies, the capacity of the section (and hence the utilisation
ratios) are still based on the provided area of steel.
The final calculations, interaction curves, etc relate to design of the section using the actual
supplied reinforcement. These calculations also show the NA position calculated for the
critical combination.
This NA position effectively reflects the theoretical capacity moment for the given axial load
and the required reinforcement. Therefore this may often indicate that the NA lies in the
section hence implying that the section is not in compression throughout - when designed as a
plain wall this is a false implication and can be ignored.
Orion Documentation page 342 Chapter 20 : Wall Design and Detailing
Option to use Single Layer of Reinforcement
This option may be appropriate in thinner walls. In the column/wall design settings you can
use the Max. Width for Single Layer Walls box to specify the maximum thickness of wall in
which single layer of reinforcement is to be used.
The single layer may be either mesh or loose bars and it may be used in conjunction with end
zone reinforcement if required.
Chapter 20 : Wall Design and Detailing Orion Documentation page 343
Design with Mesh Reinforcement
The option to consider use of mesh reinforcement in walls is available and initially controlled
via Material Property Settings.
In the column/wall design settings you can then set preferences relating to mesh
reinforcement. The settings shown below would be quite reasonable in this regard.
Orion Documentation page 344 Chapter 20 : Wall Design and Detailing
Note the Min. Wall Length for Mesh Steel - a wall of this length or greater will attempt to adopt
mesh reinforcement - provided you have chosen to use a fabric for wall web steel in the
material properties dialog.
You should set the mesh width to that of the standard panel width you intend to use.
The "Revert to Loose Bar" Option
The option to use loose bars (shown checked above) applies during the main steel design
routines when mesh has been specified. If no mesh can be found with sufficient main steel
reinforcement to meet the design requirements then the wall is set to use loose bar and
re-designed on that basis.
How the "Revert to Loose Bar" Option Works
In the properties for any wall, the Web Steel (Longitudinal) property will initially be set as
"default". The default setting results in loose bars being used if the wall in question is shorter
than the minimum length for mesh steel with mesh steel being used for longer walls. However,
in the latter case, if it is determined that no available mesh is adequate and the "Revert to
Loose Bar" option has been checked then the Web Steel property for the wall be re-set to a
relevant non-default value as shown below.
Once this is done then loose bar will always be selected for that wall until the property is re-set
back to default. Re-setting these properties would be tedious if done interactively so when
running batch design we have added the option to "Try Using Mesh in all Walls". When this is
checked the properties are re-set to default before the batch design and so if the design forces
have changed mesh could be selected in a wall where loose bar has previously been selected.
Limitation of "Revert to Loose Bar" Option
The design will not revert to loose bars in the following cases:
1. If the main bars of a mesh provide sufficient main reinforcement but subsequently it is
found that lateral bars do not provide sufficient transverse reinforcement, then the design
will show the wall as failed and will not automatically revert to using loose bar.
Generally this possibility only applies to B series meshes in thicker walls (as indicated by
the * in the Minimum Reinforcement Requirement tables below).
Chapter 20 : Wall Design and Detailing Orion Documentation page 345
2. If the main bars of a mesh provide sufficient main reinforcement to meet combined Axial
load and bending, but subsequently it is found that the limiting axial load is not sufficient,
then the design will show the wall as failed and will not automatically revert to using loose
bar. This requires walls to be subject to unusually high axial loads and should occur very
rarely.
Column Steel Details View
The view below shows the column steel details view for a wall with mesh reinforcement. This
view is obtained from right mouse click menu within the column application plan view.
Mesh and Minimum Reinforcement Requirements
It is important to appreciate that standard meshes will not be suitable in all walls, in many
cases meshes will not even provide the required minimum levels of reinforcement required by
the code. The tables below should help clarify this.
Plain walls - min horizontal and vertical reinforcement is 0.25% (basically an anti-crack
provision)
Reinforced Walls - min vertical reinforcement increases to 0.4%.
These minimums dictate the extent to which meshes can ever be used in wall design.
Orion Documentation page 346 Chapter 20 : Wall Design and Detailing
Minimum Meshes in Walls with a Single Layer of Reinforcement
Minimum Meshes in Walls with a Double Layer of Reinforcement
* In these cases no mesh is adequate because no mesh provides sufficient horizontal
reinforcement to meet the required minimum percentage.
Points to Consider
Based on the above it is clear that:
1. If using the option to consider a single layer of reinforcement in thinner walls then only an
A393 mesh is ever suitable in this situation and this only applies when the plain wall
design option is selected and applicable. Therefore:
If B-Series mesh is specified mesh will never be selected.
If the plain wall design option is not activated then mesh will never be selected.
If the setting for maximum thickness of single layer walls is set to anything much
greater than 150mm, then meshes will never be selected in the thicker walls. (It is
considered that this setting should generally be set to 150mm or less)
Wall
Thickness
Plain Walls Reinforced Walls
A series mesh B series mesh A series mesh B series mesh
125mm A393 * - *
150mm A393 * - *
175mm - * - *
200mm - * - *
Wall
Thickness
Plain Walls Reinforced Walls
A series mesh B series mesh A series mesh B series mesh
125mm A193 B196 B283
150mm A193 B196 A393 B385
175mm A252 B503 A393 B503
200mm A252 B503 - B503
250mm A393 * - *
300mm A393 * - *
Chapter 20 : Wall Design and Detailing Orion Documentation page 347
2. For walls thicker than 150mm where double layer reinforcement is being used:
If the plain wall design option is activated then potentially A-series meshes can be
selected in quite thick walls.
However, where plain wall design is not selected or not applicable, then A series
meshes will not be picked in any of the thicker walls.
If B-series meshes are selected then mesh will never be picked in walls thicker than
200mm. (This is because no B mesh satisfies the min horizontal reinforcement
requirement for thicker walls).
3. Where no mesh is suitable the design will either fail (which could be many/most walls in a
building) or design may revert to using loose bar if that option has been activated.
Which Mesh Type is Better?
Currently you are required to choose either A-Series or B-Series meshes, they cannot be mixed
within one project. In the specific case where wall loads dictate that significantly more that
min reinforcement is required then the B-series is better. However, this is not necessarily the
most common condition for walls. If B-series is selected then there is the possibility that many
wall designs will fail (because of limitation noted above). Additionally there is no point in
attempting to consider single layer reinforcement while also selecting B-Series mesh as the
default reinforcement because all walls thin enough for single layer reinforcement to apply will
simply fail (again because of limitation noted above).
Since A-Series meshes are not greatly affected by the limitation (and hence a design can be
achieved for most walls regardless of thickness) it is considered that in general it will be
preferable to use the A-Series meshes. Where plain wall design applies these meshes are also
more cost effective since they do not over-provide reinforcement in the vertical direction
simply in order to achieve min reinforcement in the horizontal direction.
Orion Documentation page 348 Chapter 20 : Wall Design and Detailing
Overview of Possible Reinforcement Arrangements
The options shown above allow for a large range of reinforcement configurations to be
considered automatically. If a single layer option is selected (as highlighted above) it will only
be used in walls thinner than a specified max thickness (shown as 150mm above), for thicker
walls a double layer of mesh will be used.
The example below demonstrates the range of design outcomes that are possible..
Chapter 20 : Wall Design and Detailing Orion Documentation page 349
A simple model is created with 8 walls (as above) set with lengths and widths such that
different design results are expected:
Walls 1 - 4 are 150 mm thick - with max thickness of single layer walls set to 150 mm we
expect to see single layer reinforcement in all these walls. Walls 4 - 8 are 175 thick so
double layer reinforcement is used.
Min length of wall in which mesh can be used is set to 1300mm - so we only ever expect to
see mesh in walls 3,4,7 and 8.
W1 (900x150) and W5 (1050x175) - are both short walls - setting allows use of end zones
in short walls.
W4 is identical size to W3 - the loads in this wall have been increased in order to
demonstrate that when mesh is specified as the default preference, the design will revert to
using loose bars if the largest available mesh is not adequate. (Same applies to W8 and
W7)
View above shows design result when plain wall design is not active and when loose bar is set
as the general preference - a successful design is achieved for all walls. (Note that the
reinforcement requirement in wall 8 exceeds 2% resulting in the automatic introduction of tie
bars in the wall.) View below shows how design changes if the plain walls design option is
activated.
NOTE: Review of the designs at this point confirms that plain wall design is applicable to
walls 1,2,3,5,6,7 and hence the steel supplied in these walls drops as shown above.
Design using Type A Mesh (not considering plain wall design option)
Refer to the Mesh and Minimum Reinforcement Requirements table earlier in this chapter-
this indicates that the heaviest mesh (A393) will not be sufficient in single layer walls, but that
A393 may be OK as double layer mesh in the 175 thick walls.
Orion Documentation page 350 Chapter 20 : Wall Design and Detailing
Change default material to A-mesh and run design.
Unexpectedly in 1W3 A393 is selected, this is achieved because heavy end bars are selected to
increase the area of steel provided to beyond 0.4%, this would not be possible on longer walls.
In walls W4 and W8 the heaviest available meshes are not adequate and so the design has
successfully reverted to the use of loose bar.
Design using Type A Mesh (considering plain wall design option)
Refer to the Mesh and Minimum Reinforcement Requirements table earlier in this chapter-
this indicates that (A393) would be OK as single layer mesh in the 150 thick walls if plain wall
design applies.
Check the option to consider plain wall design and re-design.
In W3, A393 mesh is still used, but the end bar sizes reduce.
In W7, A252 is now used instead of A393.
Chapter 20 : Wall Design and Detailing Orion Documentation page 351
Design using Type B Mesh (considering plain wall design option)
Refer to the Mesh and Minimum Reinforcement Requirements table earlier in this chapter -
this indicates that B-mesh will never be suitable in any single layer wall. B503 may be OK as
double layer mesh in the 175 thick walls.
Check the option to consider plain wall design and re-design..
As expected design fails in walls W3 and W4. For reasons stated earlier (Limitations of Revert
to Loose Bar Option), since these failures relate to the failure of any mesh to provide minimum
horizontal steel, we do not expect the design to revert to use of loose bar in this case.
Limitation Copy/Paste Bars will not work
Note that if you copy bars from a wall with mesh reinforcement to a wall that has loose bar
reinforcement (or vice versa) the procedure will result in a confused status where check
designs fail and the walls need to be re-designed.
Orion Documentation page 352 Chapter 21 : Foundation Design
Chapter 21 Foundation Design
Introduction
In addition to building superstructure analysis and design, Orion includes foundation design
calculations for the following:
Pad Footings /Combined Pad Footings,
Pile Caps / Combined Pile Caps,
Strip Footings / Combined Strip Footings,
Raft (or Mat) foundations / Piled Rafts
Foundation Design Settings
The allowable soil stress and the coefficient of subgrade reaction are set in the Building
Parameters General tab.
Some further detailed preferences are set in the Graphical Editor Settings Foundations tab.
Note in particular the Allowable Soil Stress Ultimate Strength Factor - in Orion the foundation
design procedures assume that the permissible bearing pressure is used in conjunction with
ultimate loads.
Hence if the allowable soil stress is given as 200 kN/m
2
the program then checks factored
combinations against a factored permissible bearing pressure of 1.4 x*200 = 280 kN/m
2
. This
is usually conservative.
Chapter 21 : Foundation Design Orion Documentation page 353
Foundation Depth
The foundation depth is set up globally for the whole structure a via the Edit Storey dialog.
In order to create detail drawings including starter bars, a reasonable (non zero) foundation
depth is required.
Although the foundation depth is added onto the column length displayed in the 3D window,
it does not effect the column design length.
A column kicker depth cn be set in in Column Design Settings Settings Detail Drawings -
General tab.
If different footing heights have been specified in the same model, the undersides are all set
out at the foundation depth - the topsides will thus vary in elevation.
Orion Documentation page 354 Chapter 21 : Foundation Design
The Foundation Forces Table
This table displays the foundation design forces for each column and wall. To display the table,
right click on either the Pad & Pile Bases, or Strip Footings branch of the Structure Tree - these
branches are only available when the current storey is St00.
The forces and moments displayed are initially those determined from the analysis. If required
they can be revised in one of two ways:
Applying a Force Override To apply a Force Override simply overtype the displayed
value with the override value. Columns which have had a force override applied are
indicated by a tick in the Edited checkbox. If you remove the tick the value determined
from the analysis is restored.
Added Axial Load If you require, an extra axial load can be added to the value
displayed. The extra load is entered in the Added Axial Load column. If you want to add
the same amount of axial load to all columns this can be achieved by clicking the 'Apply
added axial load to all columns' button. This feature can be particularly useful for piled
foundations.
Note If the loads are edited via either of the above methods, the revised values are the
ones displayed on the plan view at foundation level.
Chapter 21 : Foundation Design Orion Documentation page 355
Combining Columns and Walls for Shared Foundation Design
It is possible to group columns/walls together so that their combined action is supported by a
single foundation. Grouping of columns/walls in this way enables the design of:
Combined Pad Footings
Combined Strip Footings
Pilecaps supporting multiple columns/walls
To combine multiple columns and walls
1. Display the foundation level, (ST00) in the Plan View.
2. Select the columns and/or walls that are to be part of the group.
3. From the right click menu select Combine Selected Columns and Walls for Shared
Foundation Design.
4. The members are now grouped together for the purposes of foundation design.
To ungroup columns and walls
1. Select any member in the group (this selects all members of the group).
2. From the right click menu select Remove Foundation Column Grouping.
3. The members are now ungrouped.
Calculation of the Combined Footing Design Forces
The axial forces in the individual group members are summed together to provide the design
axial force for the footing.
The design moment is calculated as the sum of the moments in the individual columns, plus
an additional moment due to eccentricity of the axial force in each member from the
geometric centroid of the group.
Orion Documentation page 356 Chapter 21 : Foundation Design
In the example above two pinned columns are supported on a single pad base. The combined
design forces for load combination 1 are thus:
N = 19.4kN + 345.1kN = 364.5kN
Mx = 345.1kN x 0.9m - 19.4kN x 0.9m = 293.1 kNm
My = 0 kNm
Creating a Typical Pad/Pile Footing for Multiple Foundations
If you insert multiple pad footings or pile caps simultaneously, you are given the option to
create a standard footing at all locations which will then be designed for the worst case
loading.
To create a typical footing
1. Display the foundation level, (ST00) in the Plan View.
2. Select the columns and/or walls required
3. Display the right click menu and select Insert Pad Footing or Insert Pile Cap.
4. Check the option Create Typical Footing for the Selected Columns then click OK
Chapter 21 : Foundation Design Orion Documentation page 357
Pad Footings
The footing is sized to ensure the soil is not overstressed. If the applied moment is greater in
one direction, it will usually be rectangular, although you can restrict the design to a square
footing if you prefer.
Reinforcement to resist bending is determined in each direction and punching and shear
checks are performed.
If required, more than one column can be supported by a single footing. For details refer to the
section on Combined Pad Footings
Defining a Pad Footing
The requirements/procedure for defining a pad base are in the help system. The steps
involved are summarised below:
1. A valid building analysis (or FE chase down procedure) must have been completed so that
the relevant foundation design loads exist. Column reactions are simply fed into the pad
base design module, there is no more complex interaction of superstructure and the
foundation analysis models.
2. Display the foundation level, (ST00) in the Plan View.
3. Select the column under which the pad base will be inserted. More than one column may
be selected. In that case, the calculated pad base (based on the effects transferred from all
the selected columns) can optionally be inserted to all selected columns.
4. Display the right click menu and select the Insert Pad Footing option.
5. The Pad Base Properties menu will be displayed. Check the parameters in this menu and
then press the Analysis button to design the footing.
6. Use the up arrow buttons located to the right of the "Lx" and "Ly fields to decide on the
desired footing size.
7. Press OK to close the Pad Base Design dialog, then press OK once more to complete the
insertion of the footing. The base is then displayed on the Plan View as shown above.
Orion Documentation page 358 Chapter 21 : Foundation Design
Pad Footing Details
Footing elevations and sections can be created as Foundation Detail Sheets. as shown below.
Combined Pad Footings
A combined pad footingcan be used when two (or more) columns are close enough to each
other to be supported on a single foundation.
Before a combined pad footing can be defined you must first group the columns together so
that their combined action is applied to the footing. For details of how to group the members
together see the earlier section Combining Columns and Walls for Shared Foundation
Design.
Once the columns have been grouped together you simply proceed to define the footing in an
usual way. see the earlier section Defining a Pad Footing.
Chapter 21 : Foundation Design Orion Documentation page 359
Pile Caps
Defining a Pile Cap
The requirements/procedure for defining a pile cap are summarised below:
1. A valid building analysis (or FE chase down procedure) must have been completed so that
the relevant foundation design loads exist. Column reactions are simply fed into the pad
base design module, there is no more complex interaction of superstructure and the
foundation analysis models.
2. Display the foundation level, (ST00) in the Plan View.
3. Select the column under which the pile cap will be inserted. More than one column may
be selected. In that case, the calculated pile cap (based on the effects transferred from all
the selected columns) will optionally be inserted to all selected columns.
4. Display the right click menu and select the Insert Pile Cap option.
5. The Pile Cap Design dialog will be displayed as shown below.
Orion Documentation page 360 Chapter 21 : Foundation Design
Define the pile and pile cap data as required. The pile cap dimensions can be calculated
automatically - if entered manually the initial values may be rounded up or down during
the analysis process, (if this happens try modifying the inital value and analysing again).
Note The reinforcement defined here is neither designed or checked in any way
6. On the Loads tab you can use the existing combination data or input manually defined
loads. Surcharge is also applied on this tab.
7. On the Parameters tab you can specify the minimum number of piles, spacing
requirements and other design parameters.
Note that the max pile spacing multiplier only applies to walls , so as to achieve efficient
transfer of load through the pile cap.
Chapter 21 : Foundation Design Orion Documentation page 361
If you check the box to allow a tapered footing, then the corners will be chamfered (as
illustrated by the footing shown on the right at the start of this section).
8. Press the Analysis button to design the pile cap.
9. A report is displayed as shown below. If required, a column forces table and the pile axial
forces can be added to this report - options for this exist on the Parameters tab.
10. The number of piles used can be adjusted on the fly by clicking the (+)Increase or
(-)Decrease buttons. It is not possible to decrease to less than the original number of piles
calculated. In other words, (+)Decrease can only be used to reduce an (+)Increase.
11. Click OK to insert of the Pile Cap. The footing is then displayed on the Plan View.
Basic Design Procedure
The basic design process involves a simple procedure:
1. Set number of piles (Start with 1 pile)
2. Find a valid pile arrangement (setting out) for current number of piles
3. Check the pile arrangement - if piles fail then go back to step 1 and increase number of
piles by 1, keep iterating until a number of piles is determined that passes.
Limitations
Within the above apparently simple process there are a number of limitations to be considered:
1. Piles are positioned on a fixed spacing basis, spacing is not adjusted (increased) to resist
bending, the number of piles is always increased.
2. Pile groups are centred on the supported member - No offset grouping to resist applied
moments.
Orion Documentation page 362 Chapter 21 : Foundation Design
3. No ability to model ground beam systems in such a way that analysis is performed and
additional loads are introduced to the pile caps.
4. Design relates to pile selection only, no design is carried out for the pile cap:
No shear checks or cap depth checks
No reinforcement design of any type.
5. Design is not based on Working Load Combinations. The Pile Capacities are factored
during the design so they can be used in conjunction with ultimate loads as follows:
The pile SWL is defined during input.
Design is carried out using factored combinations with a factor applied to SWL
(default 1.4).
The Factor applied to SWL is specified on the Foundations tab in Graphic Editor Settings .
Note There is potential for a significant error if you incorrectly provide the ultimate
design capacity of the pile (which may be 3 times SWL)
6. No general summaries (pile schedules).
Larger Pile Groups
Larger pile groups are achieved automatically as shown below.
Currently there is no way to apply preferences to prevent non-preferred layouts from being
proposed and no way to interactively define an alternative preferred layout.
Chapter 21 : Foundation Design Orion Documentation page 363
Pile Cap Details
Pile cap elevations and sections can be created as Foundation Detail Sheets. as shown below.
Combined Pile Caps
A combined pile cap can be used when two (or more) columns are close enough to each other
to be supported on a single foundation.
Before a combined pile cap can be defined you must first group the columns together so that
their combined action is applied to the footing. For details of how to group the members
together see the earlier section Combining Columns and Walls for Shared Foundation
Design.
Once the columns have been grouped together you simply proceed to define the pile cap in the
usual way. see the earlier section Defining a Pile Cap.
Orion Documentation page 364 Chapter 21 : Foundation Design
Strip Footings
For the most part strip foundation design is relatively straightforward. However, Orion offers
some options in relation to strip analysis and the existence of such options can introduce
uncertainty in some cases. This section therefore focuses primarily on the strip analysis
options that are offered during the course of strip analysis and design.
Defining a Strip Footing
The requirements/procedure for defining a strip are in the help system. In this example we
will consider a strip running between columns C2, C5, C7 and C9 as shown above. The steps
involved are as follows:
1. A valid building analysis (or FE chase down procedure) must have been completed so that
the relevant foundation design loads exist. Column reactions are simply fed into the
foundation design modules, there is no more complex interaction of superstructure and
foundation analysis models.
2. Beams are defined between the columns along this line (as shown in the previous screen
shot) Note that these beams will be required to resist the longitudinal moments developed
along the strip. Hence the sizing of these beams needs to be realistic and getting the size
right may prove to be an iterative and interactive procedure we are starting here with a
beam strip 800 wide and 800 deep.
Chapter 21 : Foundation Design Orion Documentation page 365
3. The 3 beams need to be selected and then a right click exposes the option to Insert Strip
Footing and the strip footing design dialog appears as shown below.
Orion Documentation page 366 Chapter 21 : Foundation Design
4. The strip design is performed, as discussed in more detail in the following sections. When
the design is saved the strip appears on the Plan view at foundation level as shown below
5. The foundation beam design is then carried out in a similar manner to the design of
superstructure beams, but it is a 2 stage process:
a. First use the Create/Update Footing Beam Records option as shown above. (This
transfers the strip analysis results data into the beam design module.)
b. Then run the Foundation Beams design option. In this case only one strip has been
defined and so the beam design dialog appears as shown below.
Chapter 21 : Foundation Design Orion Documentation page 367
6. You can design the foundation beams interactively or in a batch mode in exactly the same
way as you would for beams in the supported building and drawings can be created/
exported in the usual way.
7. Elevations and sections are created as shown above, it is probably best to activate the
option to label bars within the section since this means that the cantilever footing steel is
also noted up as shown below. It is also suggested that it is better to use the detailing
option to Re-plot the bars below the beam resulting in a display as shown above. The
foundation beam detailing is not yet as automated as the mains structure beam detailing
and this ensures that the maximum amount of information is readily available when final
edits are made.
We will now examine some of the options and the design philosophy in a little more detail.
Orion Documentation page 368 Chapter 21 : Foundation Design
Strip Analysis Options
There are various options at this point the left and right extension length and the footing
depth are not determined or optimised automatically during design these could be set now or
reset after an initial design is examined.
The assumed design philosophy is that a footing cantilevers out to each side of the 800 by 800
longitudinal beam, in the example above the assumed initial depth for this footing is 400 mm.
If the footing width is set to zero a minimum width will then be calculated automatically.
Note that the axial loads listed in the table of design information relate to one currently
selected load combination. A design carried out at this point is for the one selected
combination only. To design for all combinations the design envelope option must be
checked. We will look at this later, for now we will make analysis comparisons based on the
G+Q*F combination only.
Adjusting the Subgrade Coefficient
The analysis method accounts for the assumed elastic deformation of the soil and the model
used is that of a beam supported by springs. The springs model the stiffness of the soil which
you define by setting the subgrade coefficient. The subgrade coefficient defined in the
building parameters is displayed here and can be edited.
Chapter 21 : Foundation Design Orion Documentation page 369
When you click on design a tabbed dialog is displayed, on the first tab calculations are shown
for review/printing, on the second tab diagrams are displayed for review/printing. The
diagrams for this strip are initially as shown below.
Note that the bearing pressures are varying, with peak pressures occurring under the load
positions.
The permissible bearing pressure was given as 200 kN/m
2
. Since the applied column loads are
factored the design is aiming to keep the peak bearing pressure below a factored allowable
pressure which is conservatively assumed to be 1.4*200 = 280 kN/m
2
. (The 1.4 factor can be
adjusted in the foundation settings.)
Orion Documentation page 370 Chapter 21 : Foundation Design
In this initial run this has been slightly exceeded, but as is shown below, some degree of
manual optimisation is always required.
When the initial design is reviewed you can see that the footing width is not a practical sort of
number you might change this to something like 3000 mm. You might also think that the 1
m extensions are a bit long, lets reduce those to 800 mm. The revised diagrams are then as
shown below.
Chapter 21 : Foundation Design Orion Documentation page 371
You may not be confident of what value to define for the sub-grade coefficient, the table below
indicates the potential range of values that might be considered.
We can easily examine the effect of changing this coefficient, the diagram below shows the
result when this strip is rechecked with the coefficient reduced from 80000 to 8000 .
This results in a more uniform bearing pressure with lower peak values. By assuming weaker
soil springs we are in effect considering the footing as being relatively more rigid and so the
pressures get spread more evenly. If the design were carried out on this basis a narrower strip
footing could be used. But notice that the span bending moments in the strip have increased
significantly while the moments under the columns have reduced. In fact this result is
probably more akin to the results achieved in traditional hand calculations.
Orion Documentation page 372 Chapter 21 : Foundation Design
In practice you may want to design for a range of possibilities, this can be achieved
automatically in Orion by using the step option as shown below.
We have asked the design to consider a range of subgrade coefficients from 8000 to 80000 and
the resulting diagrams for this one load combination are then as shown below.
The bearing pressure diagram shows a single case and indicates the maximum bearing
pressure from all the cases considered. The diagrams indicate show the envelope of design
conditions that have been developed.
Chapter 21 : Foundation Design Orion Documentation page 373
Enveloping all Load Combinations
As noted earlier it would be normal to do this from the outset, the Design Envelope option is
now checked as shown below.
For this example this results in the following revised diagrams:
Orion Documentation page 374 Chapter 21 : Foundation Design
As noted previously the pressure diagram displayed at this point is not necessarily the most
critical one, but the maximum pressure is shown. The envelope diagrams for design forces
have now widened to include the worst cases for all load combinations and the required range
of sub-grade coefficients.
In practice you may not want to consider such an extreme range of sub-grade coefficients as
have been used here, but the points to note are:
Higher sub-grade coefficients result in higher local bearing pressures and hence
potentially wider footings.
Lower sub-grade coefficients result in some higher strip design forces which may be closer
to those that you would expect on the basis of traditional hand calculations.
Note General Limitation The analysis never attempts to take any account of column
base moments transverse to the strip direction. It is anticipated that such forces
will not be allowed to develop where the intention is to use a strip footing i.e. it
is assumed that the column bases will have been defined as pinned or that the
moments are nominal. If you wish to consider wide strips where biaxial moments
get applied from the columns the FE foundation design option should be used.
Strip Footing Design
We will continue with the same example used to demonstrate the analysis options in the
previous section.
The above cross section illustrates the two aspects of the strip design:
1. The longitudinal beam that spreads the column point loads along the length of the strip
in this case an 800 x 800 beam.
2. The cantilever edges that in effect spread the line load developed by the beam out to the
edges of the strip. Within Orion this part is referred to as the footing design.
Chapter 21 : Foundation Design Orion Documentation page 375
When the design is run from Strip Footing dialog shown above, the results dialog appears as
shown below.
In the previous section we looked at the results shown on the diagrams tab, here we are
looking at the numerical results. In the previous section we saw that the maximum bearing
pressure was established as 278 kN/m
2
. This peak figure is repeated in the numerical results
above.
Orion Documentation page 376 Chapter 21 : Foundation Design
The design of the steel required in the cantilever footing is carried out at this point. Note that
the cantilever is considered as the distance from the face of the beam and not the centre-line of
the strip and that the peak bearing pressure is used. For the bar size defined in the input
dialog, the minimum spacing requirement is determined. You can change the bar size and the
footing depth until you have an arrangement that you are comfortable with. These sorts of
changes do not affect the bearing pressures.
Beam Design
Scrolling further down the strip design results you will see the design forces for the beam
being reported at the end, but the beam design is not carried out at this point. These are the
forces that are transferred to the beam design module when you Create/Update Footing Beam
Records. You may notice that the design moments noted above for transfer are not identical to
the moments indicated on the envelope diagram in the previous section. This is because
alternative Minimum Moments are also calculated and shown in the results at the top of the
data shown above.
Chapter 21 : Foundation Design Orion Documentation page 377
If the minimum moments exceed the analytical results then they are used in design. The
minimum moments are based on average bearing pressures (W) and are calculated as follows:
Minimum Span Moment = WL
2
/16 (where L is the span length)
Minimum Support Moment = WL
2
/12 (where L is the longer of the 2 spans to each side of
the support in question)
In cases with multiple equal spans these minimums are unlikely to dominate significantly if at
all. In cases with unequal spans they may be more significant. In this example the minimum
moments are greater in several cases. Application of such minimums may be regarded as good
practice since they ensure that the foundation strip is more capable of dealing with loading
variations (pattern loads) and variable ground conditions (soft spots). If you feel that these
minimums are introducing too much conservatism you can adjust them in the Foundation
Design Settings dialog shown at the start of this chapter.
Having transferred the design forces the beam is designed in the same way as superstructure
beams. Design reports are available (as shown below) as are options to print/export
reinforcement details.
Orion Documentation page 378 Chapter 21 : Foundation Design
Creating Wide Strip Footings
Strip footings with deep stiffening beams are more structurally efficient but may be considered
more costly to construct in some circumstances. Many engineers prefer wide rectangular strip
footings as indicated above, particularly for lower rise construction.
Wide strip footings can be generated in Orion, but the following should be noted:
1. You need to start by defining wide beams between the supported columns, and then select
and insert the strip footing in the usual way.
2. These strips tend to be shallow and therefore flexible so you may find a wide variation of
bearing pressures on stiffer ground (when the sub-grade coefficient is higher).
3. When you do the design you do not want a cantilever footing to be introduced, you will
probably need to keep changing the beam width until an acceptable solution is achieved.
4. Links are introduced to satisfy longitudinal shear only. As with superstructure beams
there is a maximum of 3 links (6 legs) across the section. For wide footings this may not
be sufficient.
5. No design across the width of the strip is carried out i.e. the links are not designed to
resist any transverse bending.
6. Punching Shear under the columns may be a more critical design condition than shear
across the full section of the beam. This it is NOT checked at all.
Chapter 21 : Foundation Design Orion Documentation page 379
Combined Strip Footings
A combined strip footing is commonly used when two lines of closely spaced columns are
themselves close enough to each other to be supported on a single foundation. An example
might be underneath movement joints exist in the superstructure.
Defining a Combined Strip Footing
Before a combined strip footing can be defined you are required to first of all group the
adjacent columns together so that their combined action is applied to the footing. For details
of how to group the members together see the section Combining Columns and Walls for
Shared Foundation Design earlier in this chapter.
Once each group of columns along the strip has been defined you simply proceed to define the
footing in an identical way to an ordinary strip footing. see the previous section Defining a
Strip Footing.
In summary the steps involved are as follows:
1. A valid building analysis (or FE chase down procedure) must have been completed so that
the relevant foundation design loads exist. Grouped column reactions are simply passed
into the foundation design module, there is no more complex interaction of
superstructure and foundation analysis models.
2. Beams are defined between the columns along the line joining the grouped columns.
Note that these beams will be required to resist the longitudinal moments developed along
the strip. Hence the sizing of these beams needs to be realistic and getting the size right
may prove to be an iterative and interactive procedure.
3. The beams need to all be selected and then a right click exposes the option to Insert Strip
Footing and the strip footing design dialog appears.
Analysis and Design
For details of the analysis and design procedure, refer to the notes in the earlier section Strip
Footings.
Raft (or Mat) foundations
This topic is discussed within the standard training course notes, available in PDF format
alongside this document and accessed via the link below.
Orion Standard Training Manual.pdf
Orion Documentation page 380 Chapter 21 : Foundation Design
Piled Rafts
Defining a Piled Raft
The requirements/procedure for defining a piled raft are summarised below:
1. A valid building analysis (or FE chase down procedure) must have been completed so that
the relevant foundation design loads exist. Column reactions are simply fed into the FE
raft foundation analysis module, there is no more complex interaction of superstructure
and the foundation analysis models.
2. Display the foundation level, (ST00) in the Plan View.
3. Select the slabs under which the piles will be inserted. More than one slab may be selected.
4. Display the right click menu and select the Insert Pile option.
5. Click on the desired setting out point in the Plan View.
Chapter 21 : Foundation Design Orion Documentation page 381
6. The Pile Properties dialog will be displayed as shown below.
Define the pile and pile spacing data as required. A preview of the resulting pile layout is
displayed in the Plan View.
7. Click OK to create the raft.
Piled Raft Design
After completing the placement of piles in the raft, in order to determine the individual pile
loads the next stage is to perform an FE analysis of the foundation.
Note that when preparing the FE model of the foundation you are given the option to ignore
the bearing capacity of soil.
On completion of the FE analysis the calculated pile loads are checked against the pile safe
working loads (factored in the vertical case) and each pile is given a pass or fail status.
The calculated pile loads and pass/fail statuses are displayed in the FE post-processor by
clicking the 'Display Pile Forces' button on the Nodes pull down menu.
Orion Documentation page 382 Chapter 21 : Foundation Design
Where load exceeds capacity the pile node is shown red, where it is greater than 90% the pile
node is orange, for < 90 % the pile node is green.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 383
Chapter 22 Solution Options for Inclined/Lowered Members
Introduction
The objective of this chapter is to demonstrate the solution options available for structures
containing inclined/lowered members, of which any of the following are possible:
sloping and/or lowered slabs
sloping and/or lowered beams
sloping and/or lowered columns
sloping and/or lowered and/or tapered walls
Specific attention is drawn to the additional limitations that apply when any of the above have
been employed and to those areas where extra care during modelling is necessary.
Consider the model shown above, which features a number of inclined members:
inclined beams, slabs and columns have been defined at storey 2,
these columns and also the end wall have been lowered beneath the general floor level,
a tapered wall has been defined at storey 1.
Note The features described in this chapter are for the purpose of defining occasional
sloping/lowered members within a model containing distinct horizontal floor
planes. These features are NOT intended to facilitate the modelling of structures
with complex geometries in which the floor planes are not readily apparent.
The method used for creating inclined/lowered members is described elsewhere - see
Modelling Inclined and Lowered Members
Orion Documentation page 384 Chapter 22 : Solution Options for Inclined/Lowered Members
Overview of Solution Options and Limitations
The presence of inclined/lowered members in a structure does not in itself preclude the use of
either the Building Analysis or FE Chasedown Analysis method of solution. However you
must be aware of the limitations that apply to each - particularly if the latter method is
adopted.
This chapter uses a Building Analysis Worked Example to illustrate the first solution method.
This is then followed by a list of the general limitations - see General Limitations - Inclined/
Lowered Members.
For those structures for which an FE Chasedown Analysis solution is required, a second
worked example is included - see FE Analysis Worked Example following this is a list of those
limitations applicable specifically to FE- see Limitations - FE Analysis of Inclined/Lowered
Members.
If an FE chasedown analysis is performed a further item to be considered is the suitability of
the analysis model for accurately determining building sway - this is discussed in the section:
Limitations - Finite Element Analysis and Building Sway
Inclined Beam and Slab Loads
The following points should be taken into consideration when applying loads to inclined
beams and slabs:
Gravity loads applied to inclined beams and slabs are always applied vertically, (not
perpendicular to the slab).
Area and line loads applied via the Slab Load tool are always applied to the projected slab
area and therefore take no account of the incline.
For slab loads defined via the slab properties dialog (including slab self weight) - whether
or not the incline is taken into account when determining the loaded area will depend on
the method of solution:
building analysis takes the incline into account (irrespective of whether yield line, or FE
beam load decomposition is used).
FE analysis ignores the incline.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 385
Building Analysis Worked Example
The model described at the start of this chapter is used in this example.
Diaphragm Modelling
One of the key issues to consider for any model which incorporates inclined planes is the
diaphragm modelling. There is a potential for errors to result if those nodes being constrained
by a diaphragm do not all lie in the same plane. A warning is displayed during the building
analysis if such a situation exists:
In this example there is a potential problem at storey 2. The deviation from a common plane is
small and the error introduced will not be too great, however, for the purpose of the example it
is convenient to remove the problem. Corrective action requires the physical exclusion of the
two inclined slabs from the floor diaphragm as shown below.
Orion Documentation page 386 Chapter 22 : Solution Options for Inclined/Lowered Members
Note that the removal of slabs from a diaphragm in this manner is only effective if the Storey
Diaphragm Model is set to Slabs to Define Rigid Diaphragm in the Building Analysis Model
Options.
The diaphragm model that results as a consequence of the above settings is shown below, note
that all nodes constrained by each diaphragm are constrained within a single plane:
For further guidance on the topic of working with diaphragms and inclined planes see
Diaphragm Modelling
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 387
Simplified Load Decomposition
For any storey containing inclined beams and slabs irrespective of the load decomposition
method the following simplification is always applied:
All inclined (or lowered) beams and slabs are considered to be in the same plane for the
purposes of load decomposition.
In this example, although the slabs at storey 2 contain two slopes, the entire floor remains
continuous, hence irrespective of the load decomposition method adopted the simplification
described above has no adverse effects.
Where models contain inclined (or lowered) beams or slabs, it remains the user's
responsibility to ensure that whichever decomposition method is applied, the above
simplification does not adversely affect the results of the building analysis.
Refer to Load decomposition for lowered slabs in the General Limitations section for an
example of when corrective action is necessary.
Analysis
A building analysis is to be performed using yield line load decomposition.The diaphragm
model is set as Slabs to Define Rigid Diaphragm and the other Analysis Model settings are as
shown below.
When the building analysis is run it completes with no errors or warnings.
Orion Documentation page 388 Chapter 22 : Solution Options for Inclined/Lowered Members
Load Comparison Check
For all structures it is worth checking the axial load comparison report available after analysis.
This report shows up to 4 tables, the first indicates the sum of loads as they are applied to the
structure (the "un-decomposed" loads). The second indicates the sum of loads as they are
applied to beams at each level (after "decomposing" slab loads). The third indicates the total
column/wall loads derived at each level after the building analysis. The fourth (not shown
above) indicates the total column/wall loads derived at each level if an "FE Chase Down" has
been performed.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 389
In the example above you can see that no significant loading discrepancies have occurred in
either the load decomposition phase or the building analysis phase, the analysis is complete.
The following points should be noted:
The reduction in self weight due to the wall and two columns being lowered below the
general floor level at storey 2 is accounted for.
The slight increase in self weight where beams, slabs and columns have been inclined is
accounted for.
For the two inclined slabs, the sloped area rather than the projected area has been used
when calculating the full area dead and live loads.
The total column/wall loads reported in the third table are adjusted to take into
consideration any non-vertical columns or walls. Only the axial force component is
adjusted, no allowance is made for the inclusion of a vertical shear component. This may
result in a slight discrepancy between the second and third tables.
Switching to FE Beam Load Decomposition
For the purposes of load decomposition irrespective of the method used, inclined/lowered
beams and slabs are considered to be in the same plane, this is clearly apparent when viewing
the FE load decomposition model for storey 2 as shown below:
If the analysis is re-run having been loaded on this basis, the same adjustments for inclined
members are made as were described previously and hence the building analysis result should
be similar to that obtained on the basis of yield line decomposition.
Orion Documentation page 390 Chapter 22 : Solution Options for Inclined/Lowered Members
The axial load comparison report based on FE beam load decomposition is as follows:
Although there is a slight increase in the load applied when the FE decomposition method is
used, this is due to a slight conservatism in the FE decomposition method generally (and is
unrelated to the presence, or otherwise, of inclined members).
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 391
Design and Detailing
All beams, columns and walls can be designed automatically as part of a single batch building
analysis and design if requested, as shown below.
Inclined Beam Design
The sloped beam length is used for design. The design procedure is identical to that for
horizontal beams as covered in the chapter Beam Design to BS8110.
Inclined Beam Detail Drawings and Quantities
The sloped beam lengths are also taken into account in the detail drawings and steel
quantities. Details along the lines of those shown below are produced automatically.
Note The concrete and formwork quantities do not take account of the sloped length
of the beams.
Orion Documentation page 392 Chapter 22 : Solution Options for Inclined/Lowered Members
Inclined Column Design
Inclined columns are designed and detailed in a similar manner to vertical columns. The
inclined column length is used in the design calculations.
In this example, the two inclined columns have been dropped below the general slab level,
which shortens their designed length (by 500mm), however, because they are inclined their
length increases slightly, hence the actual design length is only shorter by 423mm.
The design procedure is described in the chapter Column Design to BS8110
Inclined Column Detail Drawings and Quantities
The Column Application Plan for storey 2 is shown below:
Each section is drawn perpendicular to the face of the member - for the inclined columns the
sections are therefore inclined as opposed to horizontal.
By examining the longitudinal steel details, it is clear that the drop has been accounted for, (the
bar lengths differ by exactly 500mm). However, it is also clear that these lengths do not take
into account column inclines (if they did the H16-2 bars would be slightly longer). This
limitation also applies in the column steel quantity reports.
Note Similarly, the concrete and formwork quantities take into account the column
drops but do not take account of the column inclines.
Tapered Wall Design
The tapered wall is designed as a rectangular section of constant cross-section. Tapered wall
properties are always derived from the cross-section at the top of the wall.
Note If a tapered wall is specified where the cross section at the top is larger than at the
base, the resulting design would be unconservative.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 393
Tapered Wall Detail Drawings and Quantities
The detailing and quantities produced for the tapered wall require attention as the
reinforcement is provided to suit the top cross-section only as shown below.
Note The tapered parts of the wall are not included in the concrete quantities. The
formwork also follows the same sizing ignoring the taper.
Design and Detailing of the Inclined Slabs
Inclined slabs are designed and detailed as if they were horizontal.
The effective spans used for calculating the moment co-efficients, the deflection checks and
the bar lengths are the horizontal projections of the inclined span lengths.
The concrete and formwork quantities also assume a horizontal slab and consequently give
lower quantities for each.
Tapered Wall Modelling
A mid-pier idealisation has been used for the all the walls in the analysis model. In this section
we shall investigate the consequences of switching to an FE idealisation for the tapered wall.
Orion Documentation page 394 Chapter 22 : Solution Options for Inclined/Lowered Members
Gravity Loads (Mid-Pier Wall Modelling)
The axial loads developed in the tapered wall at foundation level are shown below (by
activating the appropriate display setting).
Gravity Loads (FE Meshed Wall Modelling)
If the building analysis is repeated using FE meshed walls the axial loads developed in the
columns and walls at foundation level are shown below.
Although the overall results are only affected very slightly, there is a local increase in the axial
force due to dead load in the tapered wall.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 395
This increase is attributable to the chosen method of modelling. The mid-pier modelling of
the tapered wall uses an average width defined by top width which means a reduction in the
wall self weight used in the analysis.
The section of the wall used in the analysis based on mid-pier modelling is shown hatched,
above.
The FE shell model gives a closer approximation to the actual self weight of the tapered wall.
We would not suggest that this is sufficient reason to use FE Meshed Wall modelling generally.
Tapered walls are unlikely to feature in a typical model and even if they do, the amount of
error introduced by the mid-pier idealisation is quite small - the benefits of simplicity and
speed of solution that are offered by the mid-pier wall solution should not be ignored.
Note It is possible to specify mid-pier modelling in the Building Analysis options menu,
but then to locally over-ride this setting for an individual wall, via the 3D tab of
the Shear Wall Properties dialog.
Orion Documentation page 396 Chapter 22 : Solution Options for Inclined/Lowered Members
General Limitations - Inclined/Lowered Members
Note If an FE chasedown analysis is performed, a further set of limitations are also
applicable, these are described in the section: Limitations - FE Analysis of
Inclined/Lowered Members
The following limitations always apply when using inclined members:
1. If the end of a beam, or the edge of a slab has been lowered so that a vertical gap exists
between it and other members at the same storey, it is still assumed to be physically
connected to the other members for the purpose of beam load decomposition.
2. Slab partial area loads are always applied to the projected slab area and therefore take no
account of the slab incline.
3. Slab line loads are always applied to the projected slab length and therefore take no
account of the slab incline.
4. Diaphragm modelling - There is a potential for errors to result if those nodes being
constrained by a diaphragm do not all lie in the same plane. (A warning is displayed
during the building analysis if such a situation exists.)
5. Axial load comparison report - Although the column/shear wall axial loads totals shown
in the report are adjusted to take into consideration any non-vertical columns or walls,
only the axial force component is adjusted, no allowance is made for the inclusion of a
vertical shear component. This may result in a slight discrepancy between the total of the
axial loads when compared to the sum of applied loads. The discrepancy only exists in the
axial load comparison report and doesn't affect the column design.
6. Column Detailing - bar lengths are not increased to take into account sloped member
lengths.
7. Concrete and formwork quantities are not increased to take into account sloped member
lengths.
8. Tapered Wall Design - The tapered wall is designed as a rectangular section of constant
cross-section. Tapered wall properties are always derived from the cross-section at the top
of the wall.
9. Tapered Wall Detailing - Reinforcement is provided to suit the top cross-section only.
Load decomposition for lowered slabs
The consequences that can result from the first of the limitations mentioned above can best be
understood by way of a further example. Consider the model below, which although it only
consists of a single storey has a number of lowered beams and a lowered slab, (created by
defining a lowered plane):
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 397
Note that there are two transverse beams in the middle bay, one directly underneath the other.
The structure may appear valid but a problem can be seen in the load decomposition views.
Yield line decomposition
Both transverse beams in the middle bay are considered to be in the same plane for the
purposes of load decomposition - hence they are both conservatively loaded by the slabs from
both sides.
Orion Documentation page 398 Chapter 22 : Solution Options for Inclined/Lowered Members
FE load decomposition
When FE decomposition is used, once again both transverse beams in the middle bay are
considered to be in the same plane - however using this method one of the two beams attracts
all of the slab load while the other is unloaded (apart from it's own self weight) - using this
method there is potential for some beams to be under designed.
Suggested Workaround
The recommended method of modelling in this scenario is to use floors defined by separate
storey levels and limit the use of planes to sloping and minor offsetting of slabs.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 399
Alternative Workaround - Returning to the single storey method with a lowered plane, but
with 2 grid lines defined at close proximity so each beam is on a different grid line (and hence
receives load from one slab only). The program automatically detects that both beams are
connected to the same columns.
Plan layout showing the additional grid lines.
The 3D view showing the beams correctly modelled at different levels
Orion Documentation page 400 Chapter 22 : Solution Options for Inclined/Lowered Members
The yield line decomposition
The FE load decomposition
From both the above load decomposition diagrams, it can be seen that the correct loads are
applied to each beam in the centre of the model.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 401
FE Analysis Worked Example
Introduction
FE chasedown analysis is permitted for structures containing inclined members, however it is
strongly recommended that you familiarise yourself with the associated limitations as
described at the end of this section before doing so.
If an FE chase down analysis is performed for a structure containing inclined members it
remains the user's responsibility to ensure that the analysis method is appropriate.
Example Model
The model from the building analysis example is re-used:
FE Chasedown Analysis
The analysis uses an idealised model in which sloped floor planes are adjusted to the
horizontal.
The following simplifications are applied:
Inclined beams and slabs are modelled horizontally at the general floor level.
Lowered (or raised) beams and slabs are modelled horizontally at the general floor level.
Any columns or walls which have had their top ends lowered (or raised) are modelled as if
they still connect at the general floor level.
tapered walls are modelled as rectangular walls, based on the top cross section of the wall.
FE Model Generation
The analysis models are created with a reduced slab stiffness multiplier (0.15) the aim of the
reduction being to transfer most of the slab load directly into the beams - (see Worked
Example Beam and Slab Systems in the Analysis and Design using FE chapter). When
creating the analysis models the following warning message is displayed:
Orion Documentation page 402 Chapter 22 : Solution Options for Inclined/Lowered Members
The message is self explanatory relating to the horizontal idealisations used.
The FE Analysis model for storey 2 is shown below, note that the floor plane is horizontal.
The FE Analysis model for storey 1 is shown below. Note that the inclined columns are
positioned vertically at the point where they connect to the floor. The loads being applied
from the storey above via these columns are displayed.
p
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 403
Load Comparison Check
The axial load comparison report based on FE chasedown analysis is as follows:
Partly because of the previously mentioned simplifications, the sum of axial loads for the FE
Analysis do not exactly match the previous Building Analysis results.
Orion Documentation page 404 Chapter 22 : Solution Options for Inclined/Lowered Members
Member Design based on FE Analysis
Beam design
Extreme care is required when merging the FE results for inclined beams with their respective
building analysis results. The building analysis model uses the sloped member length, whereas
the FE model uses the shorter horizontal length. This can significantly affect the reliability of
the results - the steeper a beam is sloped the more unreliable the results become. During the
merging process you are warned which beams are potentially affected.
When any beam is designed, the diagram moments are automatically cross checked against
the analysis moments. If merged FE results are used for steeply inclined beams, there is a high
likelihood that a mis-match will occur. In such circumstances, because the design forces are
invalid the beam fails. If you attempt to examine the results an error will be displayed similar
to the one shown below.
When the beams in the example model are re-checked after merging the FE results no
analysis/diagram moment mis-matches occur (because the beam slopes are small). Although
the beam utilisation ratios change, the reinforcement previously determined adequate for the
building analysis results remains adequate for all but one of the beams.
Column Design
For columns (and walls) a similar disparity exists - the building analysis model uses the sloped
member length, whereas the FE model uses the shorter vertical length. However, in this
situation an analysis/diagram moment mis-match will not arise - this is because the design
only requires the forces at the ends of the column - the forces at other points along the
member length are not considered.
In the example model, when the columns and walls are re-checked after merging, again the
utilisation ratios change. This result is not unexpected as different axial loads and moments
are bound to be generated by the different analytical approaches.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 405
Limitations - FE Analysis of Inclined/Lowered Members
Note See also the general limitations for inclined members General Limitations -
Inclined/Lowered Members
The following limitations apply when performing an FE Analysis of a model containing
inclined/lowered members:
1. Sway effects are not catered for in the FE Analysis model - these may be significant in
models containing inclined elements. This limitation is examined in detail in the next
section: see Limitations - Finite Element Analysis and Building Sway
2. Inclined beams and slabs are modelled horizontally at the general floor level.
3. As a result of the above, loads applied to inclined beams and slabs are calculated on the
projected rather than sloped lengths.
4. Lowered (or raised) beams and slabs are modelled horizontally at the general floor level.
5. Any columns or walls which have had their top ends lowered (or raised) are modelled as if
they still connect at the general floor level.
6. The self weight of a sloped beam is calculated based on the sloped length and used in the
idealised model, where it will be shown shorter.
7. Inclined raft foundations are modelled horizontally.
Limitations - Finite Element Analysis and Building Sway
All FE Floor models in Orion (irrespective of whether they contain inclined members or not)
are translationally restrained in the floor plane. This idealisation is common to any traditional
subframe model. Building sway is assumed only to affect the sway resisting part of the
structure, typically the shear walls and core walls. In addition, if any inclined columns exist
they are modelled as vertical.
As an example, consider the structure shown below, consisting of four 8m bays in both
directions, inclined columns are defined in the last bay:
Orion Documentation page 406 Chapter 22 : Solution Options for Inclined/Lowered Members
The FE analysis model for this is as shown below, note the inclined columns in the last bay.
Given the above, a potential concern is worthy of discussion:
Gravity loads in the inclined columns will induce a lateral force that has to be resisted by
the stabilising structure (typically shear walls). Could this sway effect appreciably change
the moments in the inclined columns?
S-Frame Comparison
To investigate how significant this concern may be it is necessary to perform a comparative
study. The results from the Orion model for varying degrees of column slope are compared to
those obtained after exporting the model to S-Frame (a general analysis program). In the
S-Frame model multiple analysis runs are performed having removed the translational
restraint at the floor level.
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 407
The affect of varying the lateral stiffness is also investigated by changing the length of the walls
and also by remodelling them using shells as shown below:
The moment at the top of one of the inclined corner columns is recorded for 3 different
column inclines (45, 30 and 15 deg) and for a wall length of 1.5m and then 3m. These results
can be compared to the Orion model results (in which the floor is translationally restrained).
Typical Test Model Results
Orion model: Column Top Moments
Floor translationally restrained
Column slope Wall model sway direction
(kNm)
perpendicular
to sway (kNm
0 degrees Short wall (1.5m) 126.6 -126.5
Long wall (3.0m) 126.3 -126.7
15 degrees Short wall (1.5m) 126.0 -128.2
Long wall (3.0m) 125.7 -128.1
35 degrees Short wall (1.5m) 117.4 -121.4
Long wall (3.0m) 117.0 -121.3
45 degrees Short wall (1.5m) 101.6 -102.9
Long wall (3.0m) 101.3 -102.8
Orion Documentation page 408 Chapter 22 : Solution Options for Inclined/Lowered Members
S-Frame model: Column Top Moments
Column slope 15 degrees
Column slope 30 degrees
Column slope 45 degrees
translationally restrained translationally unrestrained
sway direction
(kNm)
perpendicular
to sway (kNm
sway direction
(kNm)
perpendicular
to sway (kNm
Short wall 126.7 -128.9 113.3 -127.3
Short wall
(meshed)
- - 115.2 -127.4
Long wall 126.4 -128.8 117.1 -127.5
Long wall
(meshed)
- - 118.8 -127.6
translationally restrained translationally unrestrained
sway direction
(kNm)
perpendicular
to sway (kNm
sway direction
(kNm)
perpendicular
to sway (kNm
Short wall 118.1 -122.3 89.7 -119.3
Short wall
(meshed)
- - 95.6 -119.4
Long wall 117.8 -122.2 98.4 -120.0
Long wall
(meshed)
- - 103.2 -120.2
translationally restrained translationally unrestrained
sway direction
(kNm)
perpendicular
to sway (kNm
sway direction
(kNm)
perpendicular
to sway (kNm
Short wall 102.3 -103.8 55.0 -100.3
Short wall
(meshed)
- - 65.6 -9100.9
Long wall 102.1 -103.8 69.7 -101.4
Long wall
(meshed)
- - 78.0 -101.8
Chapter 22 : Solution Options for Inclined/Lowered Members Orion Documentation page 409
Discussion
By modelling the floor as translationally restrained, the Orion FE model does not cater for
building sway. The significance of this can initially be examined by comparing for the "short
wall" model the Orion results with the translationally unrestrained S-Frame results. These
show that the elimination of building sway in the Orion model in this example produces a
conservative answer for the column under investigation. In this example the degree of
conservatism increases as the amount of sway increases (i.e. as the column slope increases -
12% for a 15 degree slope rising to nearly double the moment for a 45 degree slope.)
By making the comparison using the stiffer "long wall (meshed)" model instead, the
conservatism is 7% for a 15 degree slope rising to 25% for a 45 degree slope.
Several Points should be noted:
1. Even 2 discrete 3m long panels is probably providing an unrealistically low resistance to
sway and hence this example is probably exagerating this effect - in a practical structure it
is likely to be much smaller.
2. However, the sway effect would not necessarily always reduce column moments. In cases
where ignored sway might increase the moments this could be offset against the
conservatism.
3. In an un-braced structure (where sway stability relies on the interaction of columns and
slabs) this effect could not be ignored. As is noted elsewhere, unbraced flat slab
construction is beyond the intended scope of Orion.
4. Finally, inclined columns will clearly cause tensions and compressions to develop in the
slab. This effect will not develop in the idealised Orion model. Some consideration
should be given to this to ensure that tying details are adequate.
A final more general point is that the comparisons made also highlighted the increased
modelling sensitivities that arise when inclined members meet FE meshes. This issue is very
similar to the issues that arise when beams intersect with walls. There is extensive discussion
of this in the wall modelling presentation accessed from the wall modelling chapter.
Conclusions
Sway effects are catered for in Orion's Building Analysis, however they are not catered for in its
Finite Element Analysis of a sub-floor structure. (In exactly the same way as a traditional
sub-frame analysis would ignore sway effects arising from vertical loading).
Although in this example the effect was conservative, this may not always be the case for other
structural geometries.
Orion Documentation page 410 Chapter 23 : Overview of Solution Options for Transfer Levels
Chapter 23 Overview of Solution Options for Transfer Levels
Introduction
A transfer level occurs wherever a column or wall is supported by a beam or slab. Consider
the simplified model shown here.
In this model there are walls along the rear and side elevations that stop at first floor level.
There are also two columns on the front elevation that sit on a first floor level transfer beam.
During a general building analysis of this structure, a completely coherent 3D analysis model
can be constructed and solved. Orion will not any issue warning or error messages for a
structure as simple as this one. However, in any model containing transfer levels there are
potential problems and limitations to bear in mind. Orion provides more than one way of
dealing with such models. This chapter is intended to introduce the options available to you
and the potential limitations.
Understanding the Problem and the Limitations
Broadly speaking there are two cases to consider here, we will now briefly introduce each in
turn and cross refer to examples in subsequent chapters that illustrate the issues and suggested
solutions in greater detail.
Chapter 23 : Overview of Solution Options for Transfer Levels Orion Documentation page 411
Where Beams support Columns and Walls
As noted above, many models containing transfer beams can be analysed and designed
without any apparent difficulty. The first part of the example in the chapter, Transfer Beams
General Method illustrates this point.
The chapter goes on to illustrate the issues of which you need to beware:
3D Analysis Effects Any traditional 3D linear elastic analysis of a structure may not give
results that are in line with your engineering expectations.
Walls supported by more than one beam (An example to show an arrangement that needs
to be handled with caution).
Subsequent chapters go on to illustrate the optional FE Chase Down methods for assessing
transfer beams:
A simpler/faster way that you would use for more regular buildings and in particular
where you do not intend to make use of FE analysis results for slab design. A worked
example for this is provided in the chapter Transfer Beams FE Method, Option 1
(Simplest).
A more complex variation of the method above which uses the meshed up FE Floor
models. If it is your intention to use FE results for slab design, then you will find it easier
to use this method since it reutilises the same floor models. A worked example for this is
provided in the chapter Transfer Beams FE Method, Option 2.
In these examples we show how beams can initially be designed using one method and then
cross checked and amended using another.
Where Slabs support Columns and Walls
In such circumstances the only method for designing the slabs to resist the axial loads from
the discontinuous columns is an FE Chase Down. A worked example for this is provided in the
chapter Solution Option for Transfer Slabs.
Key Limitation
Before delving into the detail of the specific examples in the following chapters, it is worth
noting the key limitation that continues to apply to structures containing transfer levels.
The FE Chase Down method does not deal with sway (lateral) loads in any way. Sway
resistance is always assessed using the building analysis and is therefore subject to the
limitations of that analysis. If the columns/walls that are discontinuous are an important
element of the sway resistance system for your building then you will need to consider your
design with some care. For example:
1. If continuous walls brace your building then columns would be regarded as braced for the
purposes of design. Such columns are almost unaffected by sway loads and designed
exclusively for gravity loads. Where such columns stop at transfer levels, Orions iterative
building analysis and/or FE Chase Down methods will collect all the gravity loads and
apply them to the beams or slabs as appropriate. This sort of condition is not a concern.
Orion Documentation page 412 Chapter 23 : Overview of Solution Options for Transfer Levels
2. It is much less common to see un-braced columns i.e. buildings where sway resistance is
provided by frame action between columns and beams/slabs. In such cases concerns
relating to discontinuous columns would be greater the same issues as described for
walls below would apply.
3. Discontinuous walls are more of a concern. Walls generally attract more significant sway
loads thus generating moments (or couples) at the transfer level. In the chapter Transfer
Beams General Method examples show how this condition is catered for analytically
while the design may prove to be conservative. However, in such circumstances it is
recommended that an increased level of attention is paid to the parallel checks that are
required when using any analysis/design software.
Chapter 24 : Transfer Beams General Method Orion Documentation page 413
Chapter 24 Transfer Beams General Method
Modelling and Analysis
If you want to work through this example for yourself, you can load model
DOC_Exampl e_01. In order not to destroy the example for someone else you should then
save the model with a new name before proceeding.
Analysis Model Options
Having loaded this model you should confirm that analysis model option settings are made as
shown below.
Model Tab
Orion Documentation page 414 Chapter 24 : Transfer Beams General Method
The default settings are used as shown above.
Stiffnesses Tab
The default settings are used as shown above.
Settings Tab
The default settings are used as shown above.
Note that the option to Issue Warnings for Unsupported Columns . is also checked at the
moment.
Chapter 24 : Transfer Beams General Method Orion Documentation page 415
Analysis
Check the options as shown above and start the building analysis which should then run with
no error or warning messages and be completed as shown below.
Orion Documentation page 416 Chapter 24 : Transfer Beams General Method
Load Comparison Check
For all structures it is worth looking at the axial load comparison report available after
analysis.
This report shows up to 4 tables, the first indicates the sum of loads as they are applied to the
structure (the un-decomposed loads). The second indicates the sum of loads as they are
applied to beams at each level (after decomposing slab loads). The third indicates the total
column/wall loads derived at each level after the building analysis. The fourth (not shown
above) indicates the total column/wall loads derived at each level if an FE Chase Down has
been performed.
In the example above you can clearly see that no loading discrepancies have occurred in either
the load decomposition phase or the building analysis phase, the analysis is complete.
Chapter 24 : Transfer Beams General Method Orion Documentation page 417
Note In the analysis settings you have the option to define an Axial Load Comparison
Tolerance, in this example it was set to the default 5%. If the overall totals in the
above tables vary by more than this amount Orion will issue warnings at the end
of the analysis.
Design and Detailing of the Transfer Beams
All beams and columns, including the transfer beams and columns can be designed
automatically as part of a single batch building analysis and design if requested as shown
below.
Transfer beams are designed and detailed like any other beam; this procedure is controlled by
the beam design settings and preferences as covered in the Orion Training Manual. Details
along the lines of those shown below are produced automatically.
The columns above the beam are shown automatically and slab and beam lines behind the
beam are optionally dotted in.
Orion Documentation page 418 Chapter 24 : Transfer Beams General Method
Discussion of Frame Analysis Results
Gravity Loads (Mid-Pier Wall Modelling)
The axial loads developed in the columns and walls at second floor level are shown below (by
activating the appropriate display setting).
Does it seem strange that the internal columns along grid A do not develop higher axial loads
than the corner column?
Chapter 24 : Transfer Beams General Method Orion Documentation page 419
Building Analysis Results
The results can be reviewed graphically to see shear force diagrams as shown above and
bending moment diagrams as shown below. Note how the side and rear walls are idealised
with a single mid-pier element.
Orion Documentation page 420 Chapter 24 : Transfer Beams General Method
Front Transfer Beam
The member force diagrams for the front transfer beam are shown above. It all looks very
reasonable a peak sagging moment of 579 kNm, and end shears of up to 336 kN.
Notice that the loading diagram does not show applied loads at the transfer column positions.
The transfer columns are a part of the analysis model and so the loads they transfer can only
be seen in terms of the steps in the shear force diagram, which are clearly visible.
Notice the small steps in the bending moment diagram under the supported column
positions, these are a small indication of the frame action being developed with the columns
themselves, this step could be eliminated by pinning the bottom of the transfer columns.
It is noted that there is currently no (easy) way to account for IL reductions within the
columns that load the transfer beam, in beams supporting columns with many levels above
this means that the transfer beam design will be conservative by default.
Chapter 24 : Transfer Beams General Method Orion Documentation page 421
Rear Transfer Beam
The member force diagrams for the rear transfer beam are shown above. Again, it all looks
very reasonable a peak sagging moment of 1155 kNm, and end shears of up to 416 kN.
Note that the wall is idealised as single mid-pier element therefore its load is concentrated at
the centre of the beam as can be seen from the shear force diagram. Clearly this idealisation
will tend to result in conservative design of the transfer beams.
Orion Documentation page 422 Chapter 24 : Transfer Beams General Method
Frame Action
Now consider the moment diagrams for the continuous beam line at second floor level above
the front transfer beam.
Perhaps not what some might initially expect there is no hogging across the transfer column
positions. This is a logical result of any full 2D or 3D analysis, the transverse beam is
deflecting, hence the supported columns are deflecting and this has an effect on the beams
above. In essence the loads are being shared according to the stiffnesses of the beams at all
levels. This effect makes more sense when the deflections for the frame are viewed as shown
below.
Chapter 24 : Transfer Beams General Method Orion Documentation page 423
This also explains the apparently low axial loads noted in the transfer columns at the start of
this section.
It is an entirely logical result the same as would be given by any general 3D frame analysis
package. It is probably not the same result as would be derived by traditional hand calculation
methods. An engineer carrying out hand calculations would probably consider each floor
independently designing the continuous beam lines on the assumption that the columns
provide a rigid support producing a moment diagram along the lines shown below.
This may be more in line with traditional expectation but it has not considered the vertical
deflection of columns supported by beams or slabs at a lower level. A 3D analysis inherently
considers this effect.
Is there a correct answer what is it? Since the answer is related to deflection it relates to
stiffness assumptions. This can become an extremely complex subject which is discussed in
some detail in the context of Flat Slab Analysis and Design in the chapter Analysis and Design
using FE of this handbook. A very sophisticated assessment would take account of
construction sequencing and time dependent effects. In such circumstances the result needs
to be assessed for sensitivity to variations in the assumptions on which it is based. In fact the
result achieved by any such complex analysis will lie somewhere between the two extremes
shown above. A simpler approach to satisfying these extremes is to ensure that your design
covers for both possibilities. This can be achieved in Orion in one of two ways.
1. Carry out a building analysis on the basis described above and design all members.
2. EITHER:
Edit the properties of the transfer beam and artificially increase its stiffness (by increasing
both the inertia and the shear area) and hence largely eliminate transfer beam deflection.
Reanalyse and examine results to see that this has had the desired effect then run a design
check on all members in the structure if any member fails investigate and increase
reinforcement accordingly.
Orion Documentation page 424 Chapter 24 : Transfer Beams General Method
3. OR, as an alternative to 2. above:
In Orion it is possible to force the entire vertical load to be carried by the transfer beam by
using either of the FE methods, further discussion of this analysis result is picked up in the
Discussion of Merged Results section in the chapter Transfer Beams FE Method,
Option 1 (Simplest). In essence this emulates the traditional hand calculation approach.
Gravity Loads (FE Meshed Wall Modelling)
If the building analysis is repeated using FE meshed walls the overall results will be affected
slightly and there will be some significant local differences which are discussed in this section.
The axial loads developed in the columns and walls at second floor level are shown below (by
activating the appropriate display setting).
There are very small changes in the distribution of axial loads in the columns and walls. The
effect where the internal columns along grid A do not develop higher axial loads than the
corner column still applies.
Chapter 24 : Transfer Beams General Method Orion Documentation page 425
Building Analysis Results
Once again, the results can be reviewed graphically to see shear force diagrams as shown above
and bending moment diagrams as shown below. Note how the side and rear walls are now
idealised with a mesh of shell elements.
Orion Documentation page 426 Chapter 24 : Transfer Beams General Method
Front Transfer Beam
The member force diagrams for the front transfer beam are very similar to those given by the
mid-pier idealisation. The peak sagging moment has increased from 579 kNm to 584 kNm,
and the maximum end shears has decreased from 336 kN to 326 kN.
Overall the change from mid-pier to meshed wall modelling has had no significant impact on
the design forces developing in this beam despite the fact that one end of the beam interacts
with a wall.
Chapter 24 : Transfer Beams General Method Orion Documentation page 427
Rear Transfer Beam
In this case the shear forces at the ends of the beam are almost unaffected by the change for
mid-pier to meshed wall idealisation. The maximum end shear decreases from 416 to 410 kN.
However, over the length of the wall we can see a series of step changes in the shear force
diagram as the wall interacts with the beam. This interaction also appears to have the effect of
smoothing the BMD and the peak sagging moment drops from 1155 kNm to 947 kNm.
Within the length of the wall the wall itself will provide a much deeper compression zone thus
reducing steel tension reinforcement requirements. Within Orion the beam is designed in
isolation ignoring this interaction of beam and wall elements. Orions design for a moment of
947 kNm could therefore still be argued to be conservative.
This situation needs a little more consideration as the wall becomes proportionately longer in
relation to the transfer beam. This is discussed further in the Limitations Transfer Walls
section later in this chapter.
Orion Documentation page 428 Chapter 24 : Transfer Beams General Method
Frame Action
Consider again the moment diagrams for the continuous beam line at second floor level above
the front transfer beam.
The numbers change slightly but the same effect occurs, there is no hogging across the transfer
column positions. As before this effect makes more sense when the deflections for the frame
are viewed as shown below.
Chapter 24 : Transfer Beams General Method Orion Documentation page 429
Limitations Transfer Walls
Consider the wall at the left hand side of the above model. It stops at first floor level and a
beam is placed under this wall despite the fact that there is a column under each end of the
wall. On the whole there seems to be 3 engineering approaches adopted in such situations:
1. A beam is defined, so the engineer expects the beam to carry all of the wall load.
2. No beam is defined the wall must be designed to act as a deep beam spanning between
the supporting columns.
3. A beam is defined but only for detailing reasons, or perhaps to provide an inbuilt
construction stage support for the wall above. In essence the engineer expects the beam to
be ignored or to carry a very small proportion of the load and that the wall should then be
designed as a deep beam for the greater part of the load.
Orion provides different levels of support for each of these approaches, we will consider each
in turn in more detail.
Orion Documentation page 430 Chapter 24 : Transfer Beams General Method
Supporting Beam to carry all Wall Load
As was shown earlier in this chapter, if the model is analysed using the mid-pier idealisation of
walls then the load is concentrated at the centre of the wall and the beam is designed for a
moment that would normally be regarded as conservative.
In this case the moment is 905 kNm and the sum of the end shears is 715 kN.
If you want to ensure that a supporting beam is conservatively designed to support all the
loads from a wall above we recommend that you use the mid-pier idealisation. If this is going
to be too conservative an approach then the meshed wall modelling option can be used
provided the points made in the Beam and Wall to Work Together section below are taken
into account.
Chapter 24 : Transfer Beams General Method Orion Documentation page 431
No supporting Beam Wall to act as a Deep Beam
Analytically Orion supports this option with no difficulty. Make a copy of DOC_Exampl e_01
and delete the beam under the wall. Analyse using the mid-pier idealisation and the analysis
will proceed with no errors or warnings. When the analysis model is viewed as shown below
you can see this is because Orion creates rigid arms at every floor level of a wall and the arms at
first floor level connect to the supporting columns at each end of the wall. The axial loads that
develop in the supporting columns can be seen in the view below.
Orion Documentation page 432 Chapter 24 : Transfer Beams General Method
Swapping to a meshed wall and reanalysing similar results can be seen.
Once again it is worth noting that even in meshed walls Orion inserts beam elements at each
floor level for numerous reasons discussed elsewhere. In the absence of such elements (and in
particular in more complex models which include transfer walls) the comparison of results
between the meshed and mid-pier idealisation would not be so good.
LIMITATION The model has been solved analytically, but Orion does not automatically
recognise walls which require deep beam design. In the current version it remains
essential that a manual design is carried out for all Transfer Wall Panels.
Beam and Wall to Work Together
If the original model is reanalysed using meshed walls the results for the same beam change as
shown below.
Chapter 24 : Transfer Beams General Method Orion Documentation page 433
The moment has dropped from 905 kNm to 263 kNm and the sum of the end shears has
dropped from 715 kN to 562 kN. Given that the mid-pier model generates a single central
point load where a UDL might be a more realistic we should expect the reduction in moment
to be at least in the ratio of WL/4 reduced to WL/8 i.e. something less than 50% for this
single span example. In fact the moment has dropped by nearly 70%. The reduction may not
be as significant for more complex situations with continuous transfer beams.
The stepped shape of the shear force diagram is indicative of the interaction between the shells
and the beam. The drop in moments and shears is an indication that the meshed wall has a
stiffness in its own right and is carrying loads direct to the supporting columns.
In fact, these are probably still conservative design forces for the supporting beam. When
Orion constructs the analytical model of meshed walls it creates relatively rigid beams at each
floor level and where these beams overlap with real beams it replaces the properties of the real
beam with those of a more rigid beam. Therefore the more rigid beam is going to attract a
greater share of the design forces and the design will tend to be conservative.
Orion Documentation page 434 Chapter 24 : Transfer Beams General Method
You have the option to apply adjustments to the rigid beams used in these walls using the
analysis option to adjust the moment of inertia as shown below.
Note that a Modulus of Elasticity adjustment will not affect the merged beam because it retains
the material properties of the transfer beam.
If a 0.2 factor is applied as shown above then the results in the transfer beam change as shown
below.
Chapter 24 : Transfer Beams General Method Orion Documentation page 435
The moment has dropped from 263 kNm to 152 kNm and the sum of the end shears has
dropped from 562 kN to 478 kN.
Caution A great deal of effort has gone into establishing the rigid member properties that
are generated by Orion. As is shown elsewhere Orion will generate very
compatible results using either the mid-pier or meshed models when the default
properties are accepted. Applying significant adjustments to these multipliers
could seriously affect the overall validity of the analysis.
In conclusion, by using the meshed wall option the transfer beam and wall will both carry
load. As is shown in this example the design forces developed in the transfer beam are still
likely to be conservative. However, the wall is required to carry some of the load and in this
respect the same limitation as is noted for the case where there is no supporting beam is
applied.
LIMITATION Where meshed walls are supported by transfer beams, the model is solved
analytically, but Orion does not automatically recognise that such walls require some
degree of deep beam design checking. In the current version it remains essential that a
manual design is carried out for all such Transfer Wall Panels.
However, assuming the transfer beam reinforcement can be considered as tension
reinforcement in the deep beam design, it is considered likely that manual design checks in
such situations will tend to show that little or no additional reinforcement is required.
Orion Documentation page 436 Chapter 24 : Transfer Beams General Method
Limitations Walls Supported by more than 1 Beam
In the above view you can see a wall supported at first floor level but it sits on two different
transfer beams.
If you want to work through this example for yourself, you can load model
DOC_Exampl e_07. In order not to destroy the example for someone else you should then
save the model with a new name before proceeding. The first floor plan view is shown below.
Chapter 24 : Transfer Beams General Method Orion Documentation page 437
Analysis
You can immediately launch an analysis of this building with the settings as shown below and
using the mid-pier idealisation for walls.
At the start of the analysis there is a message as shown below.
The message is not completely clear as to the problem. Orion is checking to ensure that where
a wall is not supported by at least 2 columns that it is supported by the same beam at both
ends. However, there are many permutations of this sort of support condition and not all will
generate warnings. In fact the analysis will continue to run quite happily. It is better to
understand the issue which can be explained by examining the results.
Orion Documentation page 438 Chapter 24 : Transfer Beams General Method
Results based on Mid-Pier Wall Idealisation
In this case the wall is symmetrically positioned over a supporting column below. Hence the
mid-pier element of the wall sits directly on this column. This is likely to mean that lower
moments and shear forces develop in the transfer beams to each side of the column. These
forces are shown below for the Factored G + Q combination.
Chapter 24 : Transfer Beams General Method Orion Documentation page 439
Results based on Meshed Wall Idealisation
In this case the meshed wall elements will obviously be interacting with the supporting beams.
The forces that develop in the transfer beams are shown below for the Factored G + Q
combination.
The span moment only increases slightly from 145 to 158 kNm. However the hogging
moment increases greatly from 649 to 1374 kNm and the end shears increase from 237 to
789kN.
Orion Documentation page 440 Chapter 24 : Transfer Beams General Method
As was noted earlier in the chapter, these are likely to be conservative transfer beam design
forces due to the rigid link modelling that is used at the bottom of the meshed wall.
However, the wall itself needs to be considered as an inverted deep beam hogging over the
support. Once again this requires some manual check design calculations.
Alternative Modelling Option Split the wall
In this workaround the model is adjusted, the wall is split into two panels directly above the
supporting column.
The split walls are defined face to face no wall extension is defined at the interface.
With the edits made, the building analysis can be rerun for each of the wall modelling options.
Using this alternative modelling the analysis will run with no error/warning messages. We can
now examine the effects that this has on the results.
Chapter 24 : Transfer Beams General Method Orion Documentation page 441
Mid-Pier Model
Now the mid-pier elements of the two separate walls are sitting part way along each of the
transfer beams. The forces that develop in the transfer beams are shown below for the
Factored G + Q combination.
The span moment only increases slightly from 145 to 168 kNm. However the hogging
moment increases greatly from 649 to 1584 which is now higher than the 1374 kNm given by
the meshed wall. The end shears increase from 237 to 865 which is again greater than the
789kN given by the meshed wall.
Orion Documentation page 442 Chapter 24 : Transfer Beams General Method
Meshed Model
The model looks identical to that generated for the un-split wall. In other examples it may
differ slightly because the meshing would not break down to the same sizes. In fact the
properties of the rigid elements created within the walls are related to the dimensions of the
wall so we may see slight differences in the results shown below.
However, in this example the results for the split wall when meshed are identical to those given
when the wall was not split.
Chapter 24 : Transfer Beams General Method Orion Documentation page 443
Summary/Recommendations
Where a transfer wall has numerous points/lines of support there are two basic options:
Option 1 Do not split the wall
The analysis may give warnings.
In this case the Mid-Pier idealisation may not be appropriate (regardless of whether or not
warnings are given).
The meshed idealisation may be preferable but might not be an upper bound.
An advantage of this method is that the wall is then designed as a single long element.
Consideration should be given to manual design checks regarding the design of the transfer
wall panel as a deep beam.
Option 2 Split the wall
In this case the analysis will start to run without error messages.
The mid-pier idealisation will tend to provide a most conservative upper bound for design of
the transfer beam.
The meshed idealisation will generate the same or very similar results as it did when the wall
was not split.
A potential disadvantage of this method is that the wall is then designed as a series of discrete
elements and some manual adjustment of the design details will be required to reintegrate.
However, for very long walls (particularly those with varying load intensity) this may be
deemed appropriate and in fact something of an advantage.
Consideration should again be given to manual design checks regarding the design of the
transfer wall panel as a deep beam.
Orion Documentation page 444 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
Chapter 25 Transfer Beams FE Method, Option 1 (Simplest)
This chapter and the chapter Transfer Beams FE Method, Option 2 describe the alternative
methods that have been introduced in Orion to help deal with transfer levels. Both these
methods utilise 3D analysis on a floor-by-floor basis. This method is the simplest and has least
potential for errors arising from modelling anomalies. It is fast because it avoids the need for
large meshed up models incorporating 1000s of plate elements. However, if it is your
intention to use FE meshing and analysis for slab design work you should probably use option
2, which is described in the chapter Transfer Beams FE Method, Option 2.
Modelling and Initial Analysis
If you want to work through this example for yourself, you can load model
DOC_Exampl e_01. In order not to destroy the example for someone else you should save the
model with a new name before proceeding. This is the same model as was used for illustration
of the General Method in the chapter Transfer Beams General Method.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 445
The FE Analysis and Load Chase Down
Choose the option to run Finite Element Floor Analysis. The FE analysis dialog includes
various features/options which influence the analysis model that is generated for the selected
floor. These options are discussed in some detail in the chapters Analysis and Design using
FE and Flat Slab Models later in this handbook.
In order to chase the loads down through the building using the simpler modelling option you
must start at the top floor level and work downwards. At each level you must set/consider the
options as shown above, noting that:
This model has no duplicate floors, duplicates can be accommodated but there are rules to
note, see the section FE Chase Down with Duplicate Floors section later in this chapter
for more information.
Removing the check against the option to Include Slab Plates in FE model means that you
work with a simple stick model as shown later.
Including or excluding beam torsional stiffness will make little difference to the overall
validity of the load chase down. (However, engineers have traditionally calculated forces
in floor grillage systems without allowing for torsion and Orion does not consider torsion
within beam design, so lets exclude it for the purposes of this example.)
Checking the option to Include Upper Storey Column Loads means that the reactions
established by FE analysis of the level above will be reapplied as loads within the model
you create for the current level. It also adds in the self-weight of the columns for the
current level. You can review these loads by clicking on the Column Loads Table button.
Since there will be no slab elements, adjusting the slab stiffness multiplier will have no
effect, you could however adjust the relative stiffness of the beams. Orion uses the gross
sectional area of the beams (ignoring flanges) and columns by default, so you might make
this adjustment to allow for the flanges.
Orion Documentation page 446 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
You can run the FE Chase Down manually starting at the top level by making the appropriate
model generation settings and clicking the mesh generation button. This creates the model for
the top level and opens a window so that you can review it. Simply exit from this window to
analyse. Repeat this process for each non duplicate level in the building.
Alternatively you can run the process automatically by clicking on the Batch FE Chasedown
button. The batch method also allows you to review and adjust the mesh at each floor level if
required.
After analysis, options have been added to allow graphical review of the applied loads. The
picture below shows the accumulated dead loads applied at the first floor level in this example
model.
Note that the dead loads shown in the discontinuous columns above are similar, but slightly
higher than the 63 to 68 kN loads determined in the chapter Transfer Beams General
Method.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 447
Axial Load Comparison
Having completed an FE Chase Down (sequential FE analysis of all floors starting at the top
and working down) you can review the resulting column loads in the Axial Load Comparison
Report accessed from the main building analysis dialog.
For this model there are no discrepancies, as you will see in the chapters Overview of Solution
Options for Transfer Levels and Transfer Beams General Method this is not always the case.
The most important comparison when reviewing the results of the FE Chase Down (shown in
the last table in the report above) is with the first table (the un-decomposed slab loads).
Orion Documentation page 448 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
Merging Column Analysis Results
Having completed the sequential floor analysis column design forces can be updated by
merging the results from FE with those from the main building analysis. Column results are
merged using the appropriate button on the postprocessor tab of the FE analysis dialog. Lets
look at how the results change before and after merging.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 449
The view above shows column loads before merging. These are the loads from the general
building analysis carried out using the mid-pier idealisation for walls and with rigid zones set
to none.
The view above shows column loads after merging. Obviously the loads on the transfer beams
have increased, but as the axial load comparison shows, the total load is the same at all levels.
Column Design
Having merged the column results, the columns can be designed in the usual way. Note that
you have the option to design them based on building analysis results and then check them
based on the merged FE results. The view below shows the column design summary based on
the building analysis results. Note that the reinforcement and utilisation ratios may be
different on your machine because of different design settings/preferences that you may have
set.
Orion Documentation page 450 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
After merging the analysis results from the FE Chase Down and using the batch mode check
design option, the reinforcement is unchanged, but the utilisation ratios change as shown
below.
Some utilisation ratios are higher, some are lower, it is simply a function of the different axial
loads and moments that are generated by the different analytical approaches. Clearly one wall
is now failing. This is occurring since the FE chase down is generating higher moments in the
wall because of the increased bending in the transfer beam that is connected to it. Any failed
members can be filtered out and selectively redesigned.
Note that you could also have used the options to create and save reports so that you have a
complete set of column design calculations, one set based on the building analysis, a second
set based on the FE Chase Down.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 451
Merging Beam Analysis Results
Merging Options
As with the column results above, the beam results are merged using the appropriate button on
the postprocessor tab of the FE analysis dialog.
When you merge beam results a message box will appear confirming whether or not the
merge has been successful at each level.
It should be noted that when results are merged there will no longer be any pattern load cases
results for the beams.
Orion Documentation page 452 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
Discussion of Merged Results
Front Transfer Beam
The chapter Transfer Beams General Method included a section Discussion of Frame
Analysis Results in which frame analysis effects were introduced. In this section we can make
some comparisons with those results. The member force diagrams for the front transfer beam
are shown below.
Note that the beam label is annotated (FE) indicating that the diagrams are based on the results
of FE analysis. Once again, the shear force diagram clearly indicates the presence of high point
loads at the expected positions.
The diagrams are quite similar to those shown in the chapter Transfer Beams General
Method, in this case the shear forces and moments are a little higher (maximum sagging
moment increasing from around 579 kNm to 712 kNm). The left hand end hogging moment
has increased from around 258 to 360 kNm. The transfer of this force into the wall is the
explanation for the wall failure noted above. The maximum shear force has increased from
around 336 kN to 377 kN.
All this is to be expected since the FE chase down accumulates all the loading in the columns
and applies it to the transfer beam. There is no frame action that generates sharing of load
back up to the floor above. In fact, this approach probably more closely emulates traditional
hand calculations.
It is noted that there is currently no (easy) way to account for IL reductions within the
columns that load the transfer beam, in beams supporting columns with many levels above
this means that the transfer beam design will be conservative by default. If it is essential to try
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 453
assess the effect of IL reduction this can be achieved by creating a copy model with a new set of
load combinations where the IL factor is reduced from 1.6 to say 0.96 if a 40% reduction is
required. This model can then be only be used for the design of the transfer beams.
Now we can compare the diagrams for the continuous beam line at second floor level above
the transfer beam.
These results may look more in line with initial expectations than those shown in the chapter
Transfer Beams General Method, but what is the correct answer? Some might say that the
sequential nature of construction means that the above style of diagrams is more appropriate
for the self-weight, this would mean that the correct answer lies somewhere in the middle of
the two extremes. This particular model may be an extreme example of this effect, but we
would recommend that the possible effects of load redistribution be quite carefully considered
in any transfer situation.
Once again, the check design mode for beams can be used, so if you wanted to design for one
extreme and then check for the other you can do it as shown below.
Orion Documentation page 454 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
Beam Design
The design summary for the beams in this model based on the building analysis results in the
chapter Transfer Beams General Method is shown below.
Having merged the beam results the design and detailing can again proceed as for any other
beam, the summary below shows the changes after running a batch mode check design
without allowing any of the reinforcing to change.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 455
Now lots of the beams fail, so we can rerun the batch design and use the option to increase
steel only when required, if you do that the summary may change as shown below to show that
everything passes.
However, in the batch mode when a beam fails all the steel in the beam is reselected, so if you
un-check the merge option and then check the beams again you might find that beams which
previously passed now fail, as shown below.
For this reason we recommend that having analysed and designed all the beams using one
method (e.g. Building Analysis) you should then run a check design for merged results to find
any members that fail. At this point you should adjust (increase only) the steel in those
members interactively until they pass. Then you should find that you can run a check design
for either set of analysis results and everything should pass.
Finally, it is worth noting that one of the most compelling reasons for not simply using FE
analysis, merging results and then designing for the merged results is that FE analysis does not
deal with patterned load, everything is fully loaded. It is very worthwhile trying to use the
general building analysis and then merge and check for FE results selectively.
Orion Documentation page 456 Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest)
FE Chase Down with Duplicate Floors
In the simple example in this chapter information has been defined at all three levels of the
building. It is possible to have duplicate floor and have these dealt with automatically as part
of the FE Chase Down procedure without the need to mesh and analyse them. However, there
are more restrictions on what can be regarded as valid duplicate when the FE subframe models
are involved.
The FE model for each floor includes the columns and walls above and below that floor, so for
the models to be identical the wall and column arrangements above and below identical floors
must also be identical.
Consider the 10-storey model above. The folders indicate that information is defined at upper
levels 10, 9, 6, and 1.
From a beam layout point of view level 9 might be identical to level 10. However there are no
columns above level 10 so the FE models at these two levels will never be identical. Hence it is
always necessary to create information and generate the FE models at the top 2 levels in any
model if an FE Chase Down is to be used.
In the model above 7 and 8 are valid duplicates of level 9.
Chapter 25 : Transfer Beams FE Method, Option 1 (Simplest) Orion Documentation page 457
Level 6 has information, the model takes up an increased plan area and new columns start
from this level.
For the same reasons as at the top two floors, level 5 is not a valid duplicate of level 6. If you
try to work through an FE Chase Down for this model then you will get a message as shown
below when you try to create the model at level 1.
By copying storey information from level 6 to level 5 this model will have information at
enough floors for an FE Chase Down to be completed.
Note that information is always required at level 1 and therefore as an absolute minimum in
any model information is required at 3 levels, Top, 2
nd
Top, and First.
Orion Documentation page 458 Chapter 26 : Transfer Beams FE Method, Option 2
Chapter 26 Transfer Beams FE Method, Option 2
This chapter and the chapter Transfer Beams FE Method, Option 1 (Simplest) describe
alternative methods that have been introduced in Orion to help deal with transfer beams. Both
these methods utilise 3D FE analysis on a floor-by-floor basis. This 2
nd
option is simply a
variation of the method described in the chapter Transfer Beams FE Method, Option 1
(Simplest), but this time using the meshed up floor models. This option is therefore a little
more complex, slower, and has a bit more potential for errors arising from modelling
anomalies. However, if it is your intention to use FE meshing and analysis for slab design
work you will probably find it easier to stick to this option rather than trying to swap back and
forth between the two.
Modelling and Initial Analysis
If you want to work through this example for yourself, you can load model
DOC_Exampl e_01. In order not to destroy the example for someone else you should save the
model with a new name before proceeding.
This is the same model as was used for illustration of the other methods in the previous
chapters. There is no need to make special changes in support of this new method. Refer to
the opening notes in the chapter Transfer Beams FE Method, Option 1 (Simplest) for an
overview of the problem.
Chapter 26 : Transfer Beams FE Method, Option 2 Orion Documentation page 459
The FE Analysis and Load Chase Down
Choose the option to run Finite Element Floor Analysis. The FE analysis dialog includes
various features/options which influence the analysis model that is generated for the selected
floor. These options are discussed in some detail in the chapters Analysis and Design using
FE and Flat Slab Models later in this handbook.
In order to chase the loads down through the building you must once again start at the top
floor level and work downwards. At each level you must set/consider the options as shown
above, noting that:
This model has no duplicate floors, duplicates can be accommodated but there are rules to
note, see the section FE Chase Down with Duplicate Floors at the end of the chapter
Transfer Beams FE Method, Option 1 (Simplest).
Checking the option to Include Column and Wall Sections in the Model means that a more
sophisticated model which idealises a rigid zone extending to perimeter of the column or
wall is used. This modelling sophistication is really only of interest in flat plate models and
may introduce more meshing difficulties. For beam and slab models it is better not to
activate this option.
Checking the option to Include Slab Plates in FE model means that you will need to mesh
up the floor slab as shown later.
Including or excluding beam torsional stiffness will make little difference to the overall
validity of the load chase down. (However, engineers have traditionally calculated forces
in floor grillage systems without allowing for torsion and Orion does not consider torsion
within beam design, so lets exclude it for the purposes of this example.)
Checking the option to Include Upper Storey Column Loads means that the reactions
established by FE analysis of the level above will be reapplied as loads within the model
you create for the current level. It also adds in the self-weight of the columns for the
current level. You can review these loads by clicking on the Column Loads Table button.
Orion Documentation page 460 Chapter 26 : Transfer Beams FE Method, Option 2
The theoretical stiffness of the slab relative to the beams can make a big difference to the
load paths and influence the design moments determined in the beams. Refer to the
chapter Analysis and Design using FE for more detailed discussion of this effect. For this
example set the slab stiffness multiplier to 0.2. At the end of this chapter we will also look
at the effect of changing this setting for this model. You could also adjust the relative
stiffness of the beams. Orion uses the gross sectional area of the beams (ignoring flanges)
and columns by default, so you might make this adjustment to allow for the flanges. In
this example leave the beam stiffness multiplier set to 1.0.
At each level in turn you click on the mesh generation button. This takes you into the FE
Preprocessor where you can mesh up your model. You can use the mouse controls to zoom/
pan/rotate the model until you see a view as shown below for the third floor level.
When you first access any model Orion will suggest a default number of plates. Mesh-
ing is not an exact science, to a large degree the more plates the better, but as a rule of
thumb you should aim to see at least 6 to 8 nodes generated along the length of each
beam. In this model changing from the initial default to 600 plates, the resulting mesh
Chapter 26 : Transfer Beams FE Method, Option 2 Orion Documentation page 461
is as shown below.
Note Click buttons in the menu bar to toggle on and off the display content.
You can keep changing the suggested number of shells and re-mesh to review the result until
you are happy. Since we have 6 nodes along the length of the middle beam at the front we will
use this mesh density.
Refer to the chapter Analysis and Design using FE for more discussion on mesh density in FE.
When you exit from the preprocessor the model of this floor will be automatically analysed.
Repeat the modelling options and meshing at the second and then the first floor levels.
Alternatively you can run the above process for all floors automatically by clicking on the
Batch FE Chasedown button. The batch method also allows you to review and adjust the mesh
at each floor level if required.
Orion Documentation page 462 Chapter 26 : Transfer Beams FE Method, Option 2
After analysis, the postprocessing option allows graphical review of the applied loads and
other results. The picture below shows deflection contours together with the applied nodal
loads for the Dead Load case.
Note that the dead loads shown in the discontinuous columns above are quite similar to those
determined in the chapter Transfer Beams FE Method, Option 1 (Simplest).
Within the FE Post Processor you can of course also review contour diagrams for all sorts of
shell results. Once again you should refer to the chapters Analysis and Design using FE and
Flat Slab Models later in this handbook for more detailed discussion.
Chapter 26 : Transfer Beams FE Method, Option 2 Orion Documentation page 463
Axial Load Comparison
Once again, having completed an FE Chase Down (sequential FE analysis of all floors starting
at the top and working down) you can review the resulting column loads in the Axial Load
Comparison Report accessed from the main building analysis dialog.
For this model there are small discrepancies between the loads developed in the FE Chase
Down (shown in the last table in the report above) when compared with the sum of applied
loads in the first table (the undecomposed slab loads).
These differences are explicable and unavoidable. The FE model is a traditional centre-line
analysis model. For the meshed up model the loads are applied to the plates, the plates are
then supported by the beams and columns. The model is constructed on outer grids spaced at
5 m by 8 m, so the total plan area for the centre-line model is 40 mP
2
P .
Orion Documentation page 464 Chapter 26 : Transfer Beams FE Method, Option 2
Consider the imposed loads: the imposed load at each level is 2.5 kN/mP
2
P , so the load at each
floor is 200 kN. However, when Orion calculates beam loads using the yield line
decomposition method in preparation for the general building analysis it takes account of the
size of the beams and adds in imposed loads on the outer half of the perimeter beams. So in
this example the FE Chase Down finds a little less imposed load than the building analysis.
Consider the dead loads: in the FE analysis the slabs exist right up to the centre line of the
beams. However, when Orion calculates beam loads using the yield line decomposition
method in preparation for the general building analysis it takes account of the size of the
beams and only considers the self weight of the slab up to the face of the beam. So in this
example the FE Chase Down effectively double counts a small amount of slab weight where
the slab and beam overlap and hence finds a little more dead load than the building analysis.
Using either of these methods it is quite likely that Orion has been more rigorous in
decomposing and maintaining loads than most Engineers would have deemed necessary in
hand calculations or more traditional approaches.
A more detailed discussion of the Axial Load Comparison can be found in the chapter
General Building Analysis.
Merging Column Analysis Results
Having completed the sequential floor analysis column design forces can be updated by
merging the results from FE with those from the main building analysis. You can then design
columns or check previously designed columns for these new slightly different loads. This
procedure is identical regardless of whether the floors have been meshed and can therefore be
followed for this meshed up version of the model by referring back to the section Merging
Column Analysis Results in the chapter Transfer Beams FE Method, Option 1 (Simplest).
Chapter 26 : Transfer Beams FE Method, Option 2 Orion Documentation page 465
Merging Beam Analysis Results
As with the column results above, the beam results are merged by checking the appropriate
button on the postprocessor tab of the FE analysis dialog shown above.
Discussion of Merged Results
Front Transfer Beam
The chapter Transfer Beams FE Method, Option 1 (Simplest) included a section Discussion
of Merged Results in which comparisons were made with the results obtained using the
simpler FE based option and the general method.
In this section we can make some further comparisons with those results. The member force
diagrams for the front transfer beam are shown below.
Note that the beam label is annotated (FE) indicating that the diagrams are based on the results
of FE analysis. Once again, the shear force diagram clearly indicates the presence of high point
loads at the expected positions.
The diagrams are quite similar to those shown in the previous chapter, in this case the shear
forces and moments are a little higher (maximum sagging moment increasing from around
712 kNm to 741 kNm). The left hand end hogging moment has decreased from around 360
kNm to 306 kNm. The maximum shear forces have also decreased slightly.
The notes in the chapter Transfer Beams FE Method, Option 1 (Simplest) regarding the way
these FE chase down methods concentrate the loading in the lowest beam are equally
applicable here.
Orion Documentation page 466 Chapter 26 : Transfer Beams FE Method, Option 2
We can again compare the diagrams for the continuous beam line at second floor level above
the transfer beam.
These results may look to be in line with initial expectations but you should refer again to the
discussion in the chapter Transfer Beams FE Method, Option 1 (Simplest) for an alternative
view on this.
Beam Design
Having merged the beam results you can then design the beams or check previously designed
beams for these new slightly different loads. This procedure is identical regardless of whether
the floors have been meshed and can therefore be followed for this meshed up version of the
model by referring back to the Beam Design section in the chapter Transfer Beams FE
Method, Option 1 (Simplest).
Effect of adjusting Slab Stiffness Factor
To illustrate this effect, repeat the sequential FE modelling and analysis this time using a slab
stiffness factor of 1.0.
On completion you can merge and compare the column forces, and as you might expect, you
should find that the column force distribution is not greatly affected.
Chapter 26 : Transfer Beams FE Method, Option 2 Orion Documentation page 467
However, lets now look at the beam design forces that will get merged. The member force
diagrams for the front transfer beam are shown below.
The hogging and sagging moments on the transfer beam have both reduced slightly. The
shears at each end of the beam have also dropped. In this example the differences are not very
dramatic, but in other examples you may well find that they can be.
The effect that is occurring is that the slabs are carrying a proportion of the load straight to the
supporting columns and by stiffening the slab the effect gets bigger. Once again you should
refer to the chapter Analysis and Design using FE for a more detailed discussion of this and
other aspects of FE analysis.
Orion Documentation page 468 Chapter 27 : Solution Option for Transfer Slabs
Chapter 27 Solution Option for Transfer Slabs
The chapter Transfer Beams FE Method, Option 2 showed the option to load a meshed up
floor model with column loads accrued from upper levels. Since there is no necessity for a
column node to sit on a beam, this solution simply reutilises the same sort of meshed floor
model option at the transfer slab level.
Modelling and Initial Analysis
For Transfer slabs the solution method is essentially the same as for transfer beams. Consider
a revised version of the simplified model used in the previous transfer beam examples.
If you want to work through this example for yourself, you can load model
DOC_Exampl e_02. In order not to destroy the example for someone else you should save the
model with a new name before proceeding.
All the beams have been removed at first floor level and a deep flat (transfer) slab has been
created.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 469
There are a few points to note about the modelling of this simple layout that can often have
greater implications in larger and more complex models:
Column and Wall Positioning
Note that every column and wall sits at the edge but not necessarily at a corner of the slab
panel. It is important that you do not define slabs that simply span over or under internal
columns and walls. You can check whether you have defined such slabs accidentally by
running a building validity check, which will generate warnings for any such clashes.
Orion Documentation page 470 Chapter 27 : Solution Option for Transfer Slabs
Slab Insertion
The default slab insertion method is Beam Region in which case Orion will look for a closed
perimeter of beams around the area in which you click and insert a slab extending to that
perimeter. This option does not work where there are no beams.
For Flat Slab models you need to change the insertion method to either Axis Region or Pick
Axes.
Using Axis Region Orion will look for a closed perimeter of axes (grids) around the area in
which you click and insert a slab extending to that perimeter. If you did that for the model
shown above you would end up with 3 slabs. That would not necessarily be a problem, but one
slab will do. Using the axis region method you can merge these slabs as you insert them if you
press and hold the control key while you click in each of the 3 areas.
For more complex boundaries you might use the Pick Axes option in which case you pick the
axes that define the boundary of a slab by clicking on them one at a time.
Overall it is better to have larger and hence fewer slabs and to avoid small or thin infill strips.
This will generally result in better meshing in the FE module, refer to the next chapter
Analysis and Design using FE for more guidance on this.
Building Analysis
Run the building analysis as described in the Modelling and Analysis section in the chapter
Transfer Beams General Method. During the analysis errors will be displayed as shown
below, but you will have the option to continue.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 471
The first message shown below lists columns and walls that the system regards as
unsupported. This basically means columns and walls that stop at an upper floor level and
which do not sit on a beam.
Press OK and then the message below appears.
Note that the error suggests that the analysis results will not be reliable this cannot be
ignored if you expect to use the building analysis results for design. In the case of any flat slab
structure and in particular transfer slabs you will use FE Chase Down analysis so you will not
going to be relying on these results for gravity load design, press Yes to continue.
At the end of the analysis you should see an axial load comparison warning.
The first warning is telling us that only 35% of the applied load is being applied successfully
decomposed onto beams and hence included in the building analysis. Essentially this is also
telling us that the building analysis results are of little value.
Orion Documentation page 472 Chapter 27 : Solution Option for Transfer Slabs
At this point it is worth examining the structural model that has been created and analysed.
The problem is very obvious, the two front columns and the wall at the rear do not sit on
anything, so the loads in these frames actually reach the end wall and columns by virtue of
beam and vierendeel action at the upper level.
This is not a mechanism, it is potentially a valid structure, but it is ignoring the transfer slab
and so it is not the structure we want to consider here.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 473
Alternative Modelling Option
Clearly this is quite a regular model and in such cases you can make use of the option to define
Support Band beams as shown below.
Band beams are defined along grids A and B. Support band beams are in a sense fictitious
beams that allow you to generate a coherent building analysis model but these beams are not
passed to the FE model, so they do not affect the FE results.
For this particular model the edits shown above mean that the Building Analysis will run with
no errors or warnings and the axial load comparison will be perfect no missing loads.
This may initially seem to be the best option for dealing with transfer slabs, and for simple/
regular models it probably is. However, most of the real models we see, and especially those
involving flat slabs and transfer slabs, are not regular. It can often be very difficult to insert a
logical system of band beams.
Orion Documentation page 474 Chapter 27 : Solution Option for Transfer Slabs
Concluding Note on Modelling
Regardless, of how a structure like this is modelled, the building analysis results should all be
treated with a good degree of caution. In this simple example the discontinuous columns and
walls clearly participate in the lateral load resistance of the structure and none of the
modelling options above really deal fully with that issue.
The FE Analysis and Load Chase Down
In order to chase the loads down through the building using this model, you could stick to
exactly the same sequence and settings as were used in the chapter Transfer Beams FE
Method, Option 2. However, lets take this opportunity to illustrate that you can swap
between the simpler and more complex modelling options at different levels:
Start at the top level and work downwards.
At the 3
rd
and then the 2
nd
floor levels use the grillage (unmeshed) model option as described
in the chapter Transfer Beams FE Method, Option 1 (Simplest).
When you get to the first floor check the option to Include Slab Plates in FE model and use the
settings and mesh density as described in the chapter Transfer Beams FE Method, Option 2.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 475
After analysis use the options for graphical review of the applied loads. The picture below
shows the accumulated dead loads applied at the first floor level in this example model
together with the deflected contours for that case.
Although a little difficult to see in the above view, the column loads are the same as
determined in the chapter Transfer Beams FE Method, Option 1 (Simplest).U This is as
expected, since the 3
rd
and 2
nd
floor FE models are identical in this chase down, and the
analysis at those levels is unaffected by what goes on at the first floor.
More importantly, after analysis, you can see moment and deflection contours for the transfer
slab that take account of the supported column and wall loads. At this point we enter into the
general topics associated with FE analysis and Flat slab design which are described in much
more detail in the following two chapters, Analysis and Design using FE, and Flat Slab
Models.
Orion Documentation page 476 Chapter 27 : Solution Option for Transfer Slabs
For this example we will look quickly at some of the results, which can quickly be exposed.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 477
In the view above we can see a contour diagram in the background showing design sagging
(tension in bottom) moments generated in the longer span direction of the slab. On top of
that is a section view showing design moments on a line (red dots along the centre of the strip)
cut in the same direction. Note the high local moment at the column head at the right had end
of the line.
Orion Documentation page 478 Chapter 27 : Solution Option for Transfer Slabs
By changing to an Integral strip, we can see the results captured and averaged over a specified
the width of strip, in this case a 1 m wide strip at the edge of the slab. This shows how the high
moment at the RH end is a local effect and in fact higher average hogging moments are
generated at the slab to wall boundary at the other end.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 479
This next view shows the top and bottom reinforcing requirements averaged over this 1 m
wide strip. The view below shows A
s
required contours for bottom steel in direction 1.
Note While in some respects a deep slab such as illustrated in this example can be
treated as any other flat slab it is noted that such slabs may well also require
some different/extra design and detailing considerations in areas such as
deflection, punching, and perhaps reinforcement bundling. It is recommended
that the details of such important structural elements be thoroughly cross
checked.
Orion Documentation page 480 Chapter 27 : Solution Option for Transfer Slabs
Axial Load Comparison
Once again, having completed an FE Chase Down (sequential FE analysis of all floors starting
at the top and working down) you can review the resulting column loads in the Axial Load
Comparison Report accessed from the main building analysis dialog.
For this model (before introduction of any band beams at first floor level) we still have the
discrepancies occurring during load decomposition and building analysis that are discussed
earlier in this chapter. However, the results for the FE Chase Down (shown in the last table in
the report above) compare perfectly with the sum of applied loads in the first table (the
undecomposed slab loads).
This means that the FE Chase Down procedure appear to have been successful and we can
now continue to merge column and beam design forces.
Chapter 27 : Solution Option for Transfer Slabs Orion Documentation page 481
Merging Column Analysis Results
Having completed the sequential floor analysis column design forces can be updated by
merging the results from FE with those from the main building analysis. You can then design
columns or check previously designed columns for these new slightly different loads. This
procedure is identical regardless of whether the floors have been meshed and can therefore be
followed for this meshed up version of the model by referring back to the section Merging
Column Analysis Results in the chapter Transfer Beams FE Method, Option 2.
Merging Beam Analysis Results
As with the column results above, the beam results are merged by checking the appropriate
button on the postprocessor tab of the FE analysis dialog shown above.
The notes in the previous chapters regarding the way these FE Chase Down methods
concentrate the loading in the lowest beam are equally applicable here, but in this case it
applies to the slab.
For the beams at the upper floors the design moments from the building analysis may or may
not be meaningful, it will depend on which of the modelling options discussed earlier in this
chapter you have used. If they are not useful you will be restricted to designing the beams for
the merged FE results. It is likely that the use of the alternative modelling option (earlier in
this chapter) is most likely to generate meaningful design information in the building analysis
phase.
Orion Documentation page 482 Chapter 28 : Flat Slab Models
Chapter 28 Flat Slab Models
Introduction
When tackling the subject of flat slabs some fundamental issues routinely arise:
The building codes provide simplified methods of dealing with regular flat slab models. 0In
practice a large proportion of models do not seem to fit within these limitations and so
engineers turn to more advanced FE methods.
Having turned to more advanced FE methods in order to look at models with more irregular
geometry, engineers are often faced with FE results that seem unreasonable to them.
Then there is the need to consider compliance with deflection limits and how allowances
should be made for creep, cracking and shrinkage - for a detailed discussion of these see the
Slab Deflection Checks chapter.
These topics and more are also discussed in detail within a training presentation that is
available in PDF format alongside this document and accessed via the link below.
Orion Flat Slab Training.pdf
(If the link does not work please browse to find the file name indicated above in the HELP
sub-folder of the Orion Program Folder).
The above presentation extract is given and discussed in detail during Orion Advanced
Training Days. The extract assumes that the content of the Analysis and Design using FE
chapter of this handbook has already been covered.
The remainder of this chapter focuses on a practical example in which the techniques
described in the presentation are put to use to design an irregular model.
Orion is also able to undertake the Punching Shear Checks associated with flat slab design.
The implementation of these checks and associated limitations are discussed in the succeeding
chapter.
Scope of Flat Slab Design in Orion
Braced Buildings
Orions FE module for flat slab analysis and design is aimed primarily at Braced Buildings as
defined in the relevant design code. Typically this means that the lateral stability of the
building should be provided by shear walls and that the slabs are then only designed for
Gravity Load effects.
Un-Braced Buildings
In this more unusual case lateral stability is provided by interaction between the slabs and the
columns. This sort of construction appears to be less common and is usually restricted to
relatively low rise buildings.
Chapter 28 : Flat Slab Models Orion Documentation page 483
In such cases the sway design is beyond the current scope of Orion. However, some engineers
have still used Orion for a gravity load design and then made separate checks/assessments of
the sway effects. Where the structural grid is sufficiently regular these checks have sometimes
made use of Orions Band Beam option which models fictitious beams within the slab.
However, it must be accepted at the outset that this form of design will require more
thoughtful, interactive, and time consuming design involvement by the engineer.
Example of a more Irregular Model
Overview
The training presentation concentrates on regular models so that comparisons can be made
between traditional code methods and results achieved using FE.
In this example a more irregular problem will be considered.
Orion Documentation page 484 Chapter 28 : Flat Slab Models
Consider the model shown above. A core wall system is assumed to brace the structure and
therefore the flat slabs and peripheral columns are to be designed for gravity loads only.
Although it looks like a simple layout, it would actually be very difficult to apply the
idealisation of column and middle strips and hence it becomes almost impossible to apply the
codes simplified design methods.
Slab Analysis, Design and Detailing
The methods illustrated in the training presentation for a simple/regular model are in
principle equally applicable to this more irregular model. However, we will work through the
steps again to emphasise some points of note.
If you want to work through the example for yourself, you can load model DOC_Exampl e_06.
In order not to destroy the example for someone else you should then save the model with a
new name before proceeding.
Meshing
Ensure that the concrete material properties are adjusted so that a long term E value is used, in
this case C40 concrete is used with E set to 7000 N/mm
2
. At the 4
th
floor level use settings as
shown above.
Chapter 28 : Flat Slab Models Orion Documentation page 485
You could adjust the mesh density from the default down to a lower setting that you think
might be acceptable. However, using the default 1500 shells and setting the regularity factor to
1.0 produces a mesh as shown below which is clearly more than adequate.
Analyse the model and then access the postprocessor setting the Positive (sagging) Moment
Factor to 1.2.
Orion Documentation page 486 Chapter 28 : Flat Slab Models
Deflection
Estimated total deflection is peaking at around 70mm along the perimeter lengths between
columns. The distance between these columns is about 11.3m therefore we should be looking
to see total deflection restricted to around 11300/250 = 45mm. A 300 thick slab is probably not
adequate for these long edges. However we will continue with the example unaltered.
For a detailed discussion of how allowances might be applied for creep, cracking and
shrinkage see the Slab Deflection Checks chapter.
Chapter 28 : Flat Slab Models Orion Documentation page 487
Bottom Steel Reinforcement Provision
Before starting to review reinforcement requirements right click in the graphics area and set
the effective depth information to some reasonable values.
We will start by assuming that the whole slab is to be reinforced orthogonally in the Global X
and Y directions.
At this point the slabs reinforcement angles have not been adjusted, so direction 1 steel is
aligned with global X, which runs from left to right in the view below.
Orion Documentation page 488 Chapter 28 : Flat Slab Models
This view shows bottom steel requirements in direction 1 and as might be anticipated the peak
requirements are occurring along the longest free edges. In direction 2 (below) we see a very
similar situation and a very similar peak requirement of just over 1300 mm
2
/m.
In practice you may want to consider the reinforcing requirements if the main steel along the
angled edges is aligned to the edge. This can be done and will be shown in the Additional
Notes on Bottom Steel Provision section at the end of this example.
Chapter 28 : Flat Slab Models Orion Documentation page 489
We can now use the custom contours option to show where different steel reinforcement
provisions would be adequate. In general the strategy would be to decide on some general
lower level of reinforcement to be provided continuously throughout the slab and identify the
regions where an increased provision is required.
In the view above we have set the lower general provision to T12 at 200 and we can see that
this is sufficient over a large proportion of the slab.
We have then considered the possibility of laying in extra T16 at 200 (providing T12 and T16
alternate bars) and the view shows that this is adequate everywhere else.
These requirements can be simply communicated to the detailer by exporting the above
contours to the main graphical editor and then to DXF.
The same procedure would be repeated for the bottom steel in both directions.
Orion Documentation page 490 Chapter 28 : Flat Slab Models
Top Steel Reinforcement Provision
Chapter 28 : Flat Slab Models Orion Documentation page 491
As expected, a review of the top reinforcing requirements shows that in theory no steel is
required over large areas of the slab and that the hogging moments intensify rapidly over the
column heads and the core wall. However, many (most?) engineers would tend to provide
minimum reinforcement throughout the top of an irregular flat slab and so the user-defined
contours shown below show this as the minimum level.
In this case we can see T10 at 200 will be provided everywhere.
Then we see large areas where T16 at 200 would need to be added leaving relatively small areas
where a higher provision is necessary.
As is covered in the training presentation, the only practical way to deal with these peak
requirements is to integrate results in strips cut across the column and wall heads.
Orion Documentation page 492 Chapter 28 : Flat Slab Models
In the view below a 2 m wide strip is cut across the head of the most critical internal column.
Based on the proportions and span of the slabs involved this might be considered as a
reasonable strip width and the average steel requirement in this width is 1772 mm
2
/m.
However, if this steel were provided, it must be provided over at least the 2 m width of the
strip. Clearly this strip strays beyond the contour boundaries where a much lower steel
requirement has been shown to be adequate.
Chapter 28 : Flat Slab Models Orion Documentation page 493
As an alternative it is more conservative to cut a narrower strip as shown below.
This strip is cut just within the boundaries where the lower provision of T10@200 + T16@200
is shown to be adequate. The average requirement in this narrower strip has increased to 2187
mm
2
/m. (This is also more in line with the rule of thumb expectation that the peak hogging
steel provision will be in the order of double the peak sagging steel provision).
Orion Documentation page 494 Chapter 28 : Flat Slab Models
The same principle is applied at the walls.
Peak requirements tend to occur around the ends/corners of walls, and a little unusually in
this example the peak requirement at the wall corner is actually higher than at the column.
Once again there would be arguments for cutting a wider strip and determining a lower
Chapter 28 : Flat Slab Models Orion Documentation page 495
average steel requirement in the vicinity of the wall, but given that we are working with a
standard 200 spacing elsewhere, the choice here lies between T20@200 and T25@200 clearly
T25@ 200 are required.
In order to achieve standardisation throughout you may then choose to provide T25 at 200 as
a standard patch of reinforcement across all column heads. Once again this information can
be communicated to the detailed by adjusting the user defined contours as shown above. The
yellow patches indicate the minimum zones in which the peak reinforcement is required.
However, it would probably be good practice to apply a standard minimum patch throughout,
in this case something like a minimum of 8 T25@200 across all column heads. To be effective
these bars must also extend a full anchorage length beyond the point where they are required.
Orion Documentation page 496 Chapter 28 : Flat Slab Models
Additional Notes on Bottom Steel Provision
It was noted that for this slab some of the highest sagging moments and hence the greatest
bottom steel requirements occur along the angled slab edges. This requirement was being
established on the assumption that direction 1 and 2 steel will be provided in the global X and
Y directions throughout. The steel requirement at this point is high in both directions.
Chapter 28 : Flat Slab Models Orion Documentation page 497
If you check you will find high design moments in both directions at these points, and if you
look at the unadjusted moments you will find that Mxy is very high and that the Wood and
Armer adjustment is having a big impact on the design moments for reinforcement if it is not
going to be provided parallel to the free edge.
Logically you would expect that steel provided parallel to the free edge would be the most
efficient solution in an area like this.
Orion Documentation page 498 Chapter 28 : Flat Slab Models
There are 2 ways in which this requirement can be investigated in Orion.
When you cut a strip at an angle as shown above you will automatically be looking at moments
and hence reinforcing requirements along the cut line.
Chapter 28 : Flat Slab Models Orion Documentation page 499
Alternatively you can define the intended reinforcing angles in any/every slab independently
and view contours on that basis. In the view below, you can see how the reinforcing angle has
been reset in the four panels adjacent to these edges.
Orion Documentation page 500 Chapter 28 : Flat Slab Models
After re-meshing and reanalysis, you will see contours as shown below.
Chapter 28 : Flat Slab Models Orion Documentation page 501
The direction 1 steel area requirements are shown above appear very similar to the
requirements shown earlier before this adjustment was made. The direction 2 requirements
shown below are quite different. Direction 2 is perpendicular to the free edges, and as
expected the reinforcement requirement becomes nominal at the edges where a peak was
previously exposed.
In other examples the feature that allows contours to be simultaneously displayed relative to
different axis systems can seem a little strange until you get used to them, refer back to the
XReview of Contouring OptionsUX in the chapter Analysis and Design using FE for more detail
if necessary.
In terms of the weight of reinforcing provided, it would be more efficient to design a perimeter
ring and then place orthogonal infill steel, but this may not be the fastest/simplest or even the
cheapest construction solution. Using Orion as shown above you can quite easily investigate
such options and you could even create extra slabs to define a ring beam zone.
As was noted in this example and in the training presentation, it is relatively easy to generate
the design information (the information that can be passed to a detailer) in Orion. This
example should reinforce the view that for flat slabs it may be better to restrict your use of
Orion to this level of detail and then revert to traditional detailing.
Orion Documentation page 502 Chapter 28 : Flat Slab Models
Column Design
By following the procedure for sequential FE floor analysis and then export of column design
forces described in the chapter Transfer Beams FE Method, Option 2 column loads can be
made available for design.
The view above shows that axial loads and moments are transferred from the FE analysis
(short frame model) and that the braced columns can now be designed in Orion including for
IL reduction factors if desired.
Since there are no beams attached to these columns Orion assumes a small strip of slab is
effective as the beam and calculates effective length factors on this basis.
Chapter 29 : Punching Shear Checks Orion Documentation page 503
Chapter 29 Punching Shear Checks
Introduction
In Orion R13.0 a basic interactive punching shear check was introduced. Since then some
enhancements have been made which we believe have made it a more attractive design aid.
However, the nature of the design code requirements tend to dictate that punching shear
checks can not be safely automated in batch runs. For this reason Orions punching shear
check is an interactive design tool, you need to use it carefully on one column at a time to
review/establish the correct design settings for each column. Having done so rechecking can
be carried out in a more automatic fashion.
In this chapter we will show what this check can do for you and illustrate the limitations of
which you need to be aware.
BS8110 Design Code Requirements
The Design Procedure
In BS8110 section 3.7.6 covers the requirements for checking punching shear. Orions
punching shear check cannot be used without a reasonable understanding of the codes
requirements. The following notes provide a brief overview of these then in the next section of
this chapter we will use specific examples to go into more detail and illustrate limitations.
BS8110 cl 3.7.7.6 describes a design procedure; the notes below expand on this.
Check Maximum Shear Capacity
This is a check at the face of the loaded area, refer to BS8110 cl 3.7.6.4.
By default Orion will perform this check, but limitations do apply.
Check Shear on Series of Perimeters
The first perimeter is at 1.5 d from the face of the column (the loaded area) subsequent
perimeters are at 0.75 d increments i.e. 2.25 d, 3.00 d, 3.75 d, etc.
To make an accurate check on each perimeter the following needs to be known/controlled:
Is it an internal/edge/corner condition?
How much main reinforcement is effective?
Are there holes, for which you need to account?
For each perimeter three results are possible:
The check fails with v > 2 v
c
in which case a required area of shear reinforcement cannot
be calculated so the whole checking procedure terminates.
Orion Documentation page 504 Chapter 29 : Punching Shear Checks
The check fails but the required area of shear reinforcement can be calculated and the
checking procedure moves on to the next check perimeter.
The check passes in which case no shear reinforcement is required and no further checks
on subsequent perimeters are required.
Note Where shear reinforcement is found to be required on a Check Perimeter it is
important to note that it is then provided on (and shared between) two
reinforcing perimeters as discussed later in this chapter.
Simple Examples
In this section we will look at a series of relatively simple examples using the model shown
below.
However, although it looks simple, this model is sufficient to illustrate most aspects of the
checking procedure including:
A typical internal column.
Chapter 29 : Punching Shear Checks Orion Documentation page 505
Typical edge columns with varying slab cantilevers.
Typical corner columns with varying slab cantilevers.
The effects of openings.
The model is set out on a regular 7.5 m grid, the slab is 300 thick with 0.5 kN/m
2
finishes and
5.0 kN/m
2
imposed load. The columns are 400 mm square.
Checking a Typical Internal Column
Orion Documentation page 506 Chapter 29 : Punching Shear Checks
Performing the Check
In the view above column 2C9 is selected, right click and select the Column Punching Check
option to expose the punching check dialog as shown. The options this exposes will generally
be discussed in more detail as we go through the examples, but in summary they are:
Floor Slab Merging Options
These options would be used in cases where the punching perimeters are not found
(generally in cases of complex slab geometry), refer to the section Slab Merging for more
details. In the first instance these options can be ignored.
Column Punching Perimeter Options
Rectangular/Polyline Column allows you to choose the shapes of punching perimeters
that will be considered. BS8110 only considers idealised rectangular perimeters as
highlighted, so all checks will be made using this setting.
Note For circular columns, the same principle applies - BS8110 only considers idealised
rectangular perimeters so checks should be made using the rectangular as opposed
to the circular setting.
Check Column Perimeter and Check Column Drop Panel Perimeter (only active if a drop
has been defined) These options allow the check on maximum shear capacity at the face
of the loaded area to be toggled on and off.
Periphery Reduction Amount An allowance for holes that have not been modelled or
may be cut in the future see the section on Dealing with Openings.
Include Load Within Punching Perimeter When this option is checked the shear load
considered on each successive punching perimeters will reduce (due to the increasing area
of loading that falls within the punching perimeter. When un-checked the shear load will
be the same on all perimeters i.e. the check becomes more conservative.
Column Location
As will be illustrated in the following examples, it is the users responsibility to indicate the
location (internal/edge/corner) and hence the more applicable shear checks as detailed in
BS8110 cl 3.7.6.2 and 3.7.6.3.
Slab Reinforcement X (and Y)
The effective area of tension reinforcement in each direction must be input manually.
Checking Maximum Shear Capacity
This is a check at the face of the loaded area, refer to BS8110 cl 3.7.6.4.
Chapter 29 : Punching Shear Checks Orion Documentation page 507
If no changes are made and the column is checked with the settings as shown the result is as
shown below.
The output indicates the design forces and then makes the first punching check (at the face of
the loaded area). For this and most reasonable examples this check passes.
The red perimeter is indicating that the checks then fail at the next perimeter see below.
Check Shear on a Series of Perimeters
Continuing with the same example, the code requires the first perimeter check to be made at
1.5 d from the face of the column (the loaded area). Note that Vt is slightly reduced for this
perimeter, from 1139.5 kN at the face of the column to 1112.8 kN (because the option to
include the load within the punching perimeter is active i.e. we have included its exclusion.)
Orion Documentation page 508 Chapter 29 : Punching Shear Checks
The output above indicates that v > 2v
c
reference should be made to BS8110 cl 3.7.7.5, once
v exceeds this level justification of shear resistance moves beyond the limits of the code.
Hence in this situation Orion simply indicates the perimeter in red on the plan view and the
output suggests that something must be done to increase v
c
(or reduce v).
The shear capacity v
c
is influenced by concrete grade and provided steel. For this check we
accepted the default bars T8@250. Clearly a much higher steel provision would be normal
across a column head so we can now rerun the check with more realistic steel say T20@200
(probably still a little low).
The result for this revised check is shown above.
The 1
st
perimeter at 1.5 d is checked and it fails, and Asv required is determined as 1088 mm
2
.
The 2
nd
perimeter at 2.25 d is checked and it fails, and Asv required is determined as 1445
mm
2
.
Chapter 29 : Punching Shear Checks Orion Documentation page 509
The 3
rd
perimeter at 3.0 d is checked and it passes so no further perimeters need to be
checked.
The plan view reflects these key results the first two perimeters are shown red and the Asv
requirement is written on each perimeter. The 3
rd
perimeter is shown green. This sort of red,
red, green series of perimeters is ultimately what you will see against all of the columns.
Note Since the punching shear perimeter length increases and the shear load decreases
on each successive perimeter you may expect to see a reducing Asv requirement on
the successive perimeters. For higher shear loads this will be true, however, where
nominal shear reinforcement is required
(Asv min = 0.4ud/0.95f
yv
) the requirement will increase as a function of
perimeter length (u).
Note The input of main reinforcement has 2 effects. The bar size influences the value
of effective depth (d) used in the checks, and the spacing sets the total effective
tension steel (Ast). In practice you might actually have alternate bars of different
sizes providing a total Ast (say 1850 mm
2
/m for the purposes of an example). In
this case you would simply use the larger bar size and adjust the spacing so as to
achieve the correct Ast value as shown below. It is the Ast value that is
important, the spacing is irrelevant in the context of this check.
Providing Shear Reinforcement
Orion will create a plan view showing all the failed perimeters and the associated Asv
requirements.
Note that on 2C10 the very slightly higher punching load is sufficient to mean that the Asv
requirement on the first perimeter is greater than the minimum requirement which applies on
2C9. On the second perimeter however the minimum requirement applies to both columns.
Orion Documentation page 510 Chapter 29 : Punching Shear Checks
In practice punching shear resistance may be provided in different ways using various
proprietary systems. If it is to be provided using links, the detailing requirements of BS8110 cl
3.7.7.6 and fig 3.17 must be adhered to. This remains a detailing exercise but the following
notes indicate the points to watch continue to consider column 2C9:
Check Perimeter at 1.5 d
The 1088 mm
2
required at the first check perimeter should be provided on at least 2
reinforcement perimeters:
At 0.5 d at least 40% i.e. approx. 435 mm
2

At 1.25 d the balance of approx. 653 mm
2

Check Perimeter at 2.25 d
The 1445 mm
2
at this second check perimeter must again be provided on 2 reinforcement
perimeters the first of which is at 1.25 d and is therefore common to the previous check
perimeter.
At 1.25 d at least 40% i.e. approx. 578 mm
2
but 653 mm
2
already provided above.
At 2.0 d the balance of approx. 1445 653 = 792 mm
2
is required.
Now consider the detailing requirements on each perimeter. The main restriction to note is
that the maximum spacing of link legs along any perimeter is 1.5 d which in this example is a
spacing of 380 mm. The spacing of main bars is likely to further dictate the maximum spacing
that can be used say main bars are at 100 crs then maximum reasonable spacing is 300 mm.
The table below indicates the minimum area of shear reinforcement that will be provided on
each perimeter if a 300 mm link leg spacing is used.
It seems that T8 legs at 300 will be required on each of 3 reinforcing perimeters.
Note There are some further points to consider in relation to the provision of shear
reinforcement around holes. See further comments in the section Dealing with
Openings.
Perimeter at
(distance
from face of
column)
Minimum
Asv reqd
mm
2
Perimeter
Length
(mm)
Min No of
Link Legs
(at 300 mm
crs)
Min Area of shear reinforcement
provided assuming min bar size of:
T6 T8 T10
0.5 d 435 2620 9 254 mm
2
452 mm
2
707 mm
2
1.25 d 653 4150 14 396 mm
2
704 mm
2
1100 mm
2
2 d 792 5680 19 537 mm
2
955 mm
2
1491 mm
2
Chapter 29 : Punching Shear Checks Orion Documentation page 511
Checking a Typical Edge Column
In the above view a column close to an edge has been selected and a check has been made
using the same settings as were used for the internal columns above.
The view shows how Orion has correctly detected the shortest punching perimeter in
accordance with BS8110 figure 3.19, however, clauses 3.7.6.2 and 3.7.6.3 require that a
distinction is made between internal and edge columns. This affects the calculation of Veff in
both directions. Orion cannot make this distinction automatically for all potential geometries,
and so it never attempts to make it at all. THE USER MUST ALWAYS CONTROL THIS
SELECTION.
Orion Documentation page 512 Chapter 29 : Punching Shear Checks
In this simple case the red and green perimeters clearly indicate that the free edge is close
enough that this check should be made as an edge condition on all perimeters. If we rerun the
check having changed to the appropriate column location setting the result changes as shown
below.
The result looks similar, but the Asv requirements have actually changed. In actual fact in this
example the requirement on the first perimeter has reduced, and on the second perimeter min
requirements continue to apply. In fact, because of the way Orion calculates the dimension x
used in the calculation of Veff (see later discussion) this is likely to be the case, but this result
cannot be guaranteed for all edge conditions.
Chapter 29 : Punching Shear Checks Orion Documentation page 513
As an example of where some care needs to be taken with the selection of edge conditions,
consider the column shown below.
The first perimeter is that of an internal column, the second is an edge condition. When
checked as an internal column the Asv requirement shown above is 1088 mm
2
(min
reinforcement). When checked as an edge column the calculation of v changes, but the
minimum Asv requirement continues to apply i.e. the result is unchanged in this example.
Beyond the requirement to consider and apply the appropriate check there is no difference
between the checks for internal and edge columns.
Orion Documentation page 514 Chapter 29 : Punching Shear Checks
Checking a Typical Corner Column
The example shown above illustrates a simple corner column case. The points made for the
edge column in the previous section are equally applicable here, the obvious difference being
that the corner column location must be selected. In this example, the corner column with
significant overhangs passes the punching shear check with no reinforcement being required.
Chapter 29 : Punching Shear Checks Orion Documentation page 515
Column Drop Panels
In the view above column 2C10 has been selected and a 2m square by 500mm deep drop panel
has been defined at the top of the column.
The purpose of a drop panel is typically to remove the need for additional punching shear
reinforcement. This can be achieved by adjusting the geometry of the column drop panel.
When the checks are performed the objective is therefore to obtain two green perimeters as
shown above. The inner perimeter (at 1.5d from the column) confirms that the drop is
sufficiently deep and the outer (at 1.5d from the drop) confirms that it is sufficiently wide.
Orion Documentation page 516 Chapter 29 : Punching Shear Checks
Check Punching around the Column Perimeter
For the inner perimeter shown above to be determined (and an output report created for it),
the option Check Column Perimeter has to be ticked on punching check dialog.
When the calculation is performed punching checks are carried out at the face of the loaded
area and at the first perimeter, (both checks taking account of the increased slab depth). A red
perimeter indicates that the depth of the drop panel should be increased.
Note Depending on the size of panel, it is possible for the first perimeter at 1.5d to
occur outside the drop panel. The calculations are then performed at this
perimeter based on the increased slab depth. however, in such a case the
calculation becomes irrelevant and can be ignored.
Chapter 29 : Punching Shear Checks Orion Documentation page 517
Check Punching around the Drop Panel Perimeter
The Check Column Drop Panel Perimeter option must be ticked in order to check the outer
perimeter beyond the drop panel.
This time when the calculation is performed, a check is carried out at the face of the drop
panel (taking account of the increased slab depth) and subsequent perimeters are then
checked beyond this for the unthickened slab. A red perimeter indicates that the width of the
drop panel should be increased.
Note For an output report to be created for the results around the drop panel
perimeter (as shown above), the option Check Column Perimeter should be left
unticked.
If both options Check Column Perimeter and Check Column Drop Panel
Perimeter are ticked, all the required checks are performed and the graphical
display of the perimeters is created accordingly, however, the accompanying
report will only display the results around the column perimeter.
Orion Documentation page 518 Chapter 29 : Punching Shear Checks
Dealing with Openings
Openings which have been modelled
In the view above a small hole has been positioned close to a column. On the punching
perimeters that are drawn you can then see sections in black (rather than red or green)
indicating the lengths on the check perimeters that are excluded. The excluded length is
established as the length between lines radiating from the centre of the column past each of
the extreme edges of the hole.
Chapter 29 : Punching Shear Checks Orion Documentation page 519
In actual fact this is quite a small hole (150 mm square) and is actually something we would
not recommend complicating the FE modelling with. We would tend to recommend that you
allow for something like this by using the Periphery Reduction Amount option. Before moving
on to that, it is worth noting just how significant the reductions due to this (any) small hole
can be.
Examining the calculations above, note that:
1. At the face of the column the perimeter length for the maximum shear capacity check is
never reduced, although this is rarely critical by the time other checks are passing, you
may want to consider the possible effect of some reduction here.
2. At 1.5 d from face The perimeter length is reduced by 393 mm (from 4660 mm to 4267
mm).
3. At 2.25 d from face The perimeter length is reduced by 522 mm (from 6190 mm to 5668
mm).
Orion Documentation page 520 Chapter 29 : Punching Shear Checks
4. At 3.00 d from face The perimeter length is reduced by 651 mm (from 7720 mm to 7069
mm).
As expected the reduction length is increasing. The main point to note is that a small hole of
150 mm side quite close to the face of the column reduces the punching perimeter by much
longer lengths.
Note Providing Shear Reinforcement The reported Asv requirements relate to the
effective perimeter length even though there is an unbroken full perimeter. The
detailing guidance in BS8110 does not indicate whether the required
reinforcement should be provided on a similarly shortened perimeter. An option
to allow for this would be to factor up the Asv requirement by the ratio of the full
perimeter to the reduced perimeter and then provide reinforcement on the full
perimeter.
Note Due to the almost infinite variations of intersecting slab shapes and hole shapes
and positioning, it is quite possible that Orion will have difficulties accurately
predicting punching perimeter reductions, this point is illustrated in the
concluding notes.
Calculation of the Effective Shear Force
During punching shear checks the identified transfer force (V
t
) is adjusted to allow for
variations induced by transfer moments (M
t
). Referring to BS8110 clauses 3.7.6.3 and 3.7.6.4,
the applicable cases and equations are:
Internal Columns:
For bending in both directions:
V
eff
= V
t
(1 + 1.5 M
t
/(V
t
*x)) (eq25)
Edge Columns
Where bending is about an axis parallel to the free edge:
V
eff
= 1.25 V
t
Where bending is about an axis perpendicular to the free edge:
V
eff
= V
t
(1.25 + 1.5 M
t
/(V
t
*x)) (eq26)
Corner Columns
For bending in both directions:
V
eff
= 1.25 V
t
BS8110 defines x as the length of the side of the perimeter considered parallel to the axis of
bending. There is no guidance as to whether or not this dimension should be shortened if
openings affect the perimeter. There is no guidance on what to do when the length is
shortened on one face but not on the other. Where opinions have been sought on this there is
a view that x should not be shortened to account for openings, however no authoritative
guidance has been found to this effect.
Looking to the above example, for direction 1 bending on the first perimeter one side is
shortened by 393 mm. The most conservative view would be that x should be taken as 1165 -
393 = 772 mm. In Orion x is taken as the average of the two relevant sides, in this case (1165 +
772) / 2 = 968 mm. This is believed to be a reasonably conservative interpretation of the code
requirements.
Chapter 29 : Punching Shear Checks Orion Documentation page 521
Allowing for Openings which have not been modelled
As noted above the modelling of small holes creates unnecessary complication and is often
best avoided. In many projects there may also be a need to allow for holes without actually
knowing for sure where they are. This can be achieved using the option to specify a periphery
reduction.
Using the same example as above and initially applying a reduction length of 393 mm (the
same as Orion calculated for the first perimeter) the result is as shown below.
Points to note are:
1. Looking at the detail of the calculations you may note that x is not reduced to account for
the existence of un-modelled holes. This avoids what some may regard as the over
conservative adjustments to x which Orion applies when the holes are modelled.
Orion Documentation page 522 Chapter 29 : Punching Shear Checks
2. Despite the above, for the first perimeter the calculated Asv requirement is identical. This
is because the design in direction 2 is dominating and in that direction x was not reduced
when the hole was modelled.
3. For the second perimeter the Asv requirement is a little higher because using this option
the length reduction is constant on all perimeters (hence it is 393 mm rather than 522
mm). On this perimeter min Asv requirements are being used and so the requirement
increases as the perimeter length increases. Given that we are only allowing for the
possibility of a hole, we should check the requirements when no hole is allowed for as
shown below.
In essence the above is exemplifying the note made earlier regarding the practicalities of
providing the shear reinforcement. If the Asv requirements obtained by excluding a perimeter
length are factored up by the ratio of the full perimeter to the reduced perimeter so that
reinforcement can then be provided on the full perimeter a very reasonable result will be
achieved, perhaps erring on the side of conservatism.
In conclusion, for this model if an allowance had to be made for the possibility of holes (up to
say 150 mm) adjacent to any column, it would be quite reasonable to specify a periphery
reduction of around 400 mm to all columns rather than take the time to attempt to model
every possible hole in detail. The reported Asv requirement might then be factored up slightly
to allow for the point made above.
Chapter 29 : Punching Shear Checks Orion Documentation page 523
Final Batch Check and Output
Having set up the punching design information at each column location it is possible to rerun
a batch check on punching shear for all columns as shown below.
Orion Documentation page 524 Chapter 29 : Punching Shear Checks
When accessed this option will show a table where the key design information can be reviewed
and adjusted if necessary.
So for the final run on this model a perimeter reduction of 400 mm is applied to all columns.
Concluding Notes
Limitations
Three points emphasised throughout this chapter are:
1. The punching shear checks required by design codes are quite empirical by nature and
engineering judgement is often required as to which part of the checks are most
applicable.
2. Potentially there are an almost infinite number of variations of intersecting slab shapes,
hole shapes, discontinuous edges, etc. It is quite possible that Orion will have difficulties
accurately predicting punching perimeters in many circumstances.
3. As a result, the checks must initially be carried out on one column at a time so that the
engineer can take proper control over the input and review the results.
The areas in which we would particularly highlight the limitations of the current checking are:
Chapter 29 : Punching Shear Checks Orion Documentation page 525
Holes
It is possible that Orion will have difficulty identifying correct punching perimeters as the
geometry of slabs and openings become more complex. The example below shows the sort of
issue that could occur.
Two holes are positioned near to a column. Orion has identified the circular hole outside the
check perimeters and has reduced the perimeters accordingly, the black sections of the
perimeter lines can be seen on close examination.
For the rectangular opening however, reduced lengths are also shown that extend above and
below the edges of the opening. The above view was created using an older release of Orion.
However, there is some debate as to whether these extended exclusions are actually required,
and in fact introducing these extensions was found to cause other difficulties.
Orion Documentation page 526 Chapter 29 : Punching Shear Checks
The view below shows the punching perimeters that are now generated in the current release.
There are no extensions to the excluded lengths where a check perimeter is actually broken by
a hole, the splayed reduction of length is only applied to unbroken perimeters. Note that an
additional periphery reduction is still applied this value could be further increased if you
wished to make more allowance for extended exclusions at the sides of the hole.
If you identify or are concerned about problems of this nature we would appreciate being sent
the example so that we can look into the matter. In the meantime we would suggest using the
options to either simplify the holes or to remove them and specify a periphery reduction
length.
Dimension x used at the face of the loaded area
At the face of the loaded area you will find that value of x used is the same as at the first
check perimeter. It is not taken as just the column dimension. The justification for this
assumption is discussed below:
We found that when you do the check using the actual column dimensions then columns in
fairly ordinary situations start to fail. When we talked to people in the industry about this we
found that in practice they tended to ignore this check completely (assuming it to be ok by
inspection) or if they did it they just used the actual shear force and did not bother to amplify
it at all, or sometimes that they just assumed the 1.15 amplification noted in Clause 3.6.7.2
would cover it. Everyone felt that the check seemed incorrect (over conservative) when
applied more rigorously using the column dimensions as "x" at the face of a column.
Chapter 29 : Punching Shear Checks Orion Documentation page 527
Basically as you approach the column "x" decreases rapidly and so the amplification calculated
in Veff becomes extreme. Internal columns with ordinary transfer moments are treated as
worse cases than edge columns with very high transfer moments where the amplification of
Veff is a fixed value of 1.25Vt. It also seems to work back to front in terms of the way it
amplifies V - for example using a 600x300 column, if the same transfer moment is applied in
both directions the amplification of Veff will be greater when bending is in the strong
direction (because x=300) than when bending in the weak direction - seems counter intuitive?
Furthermore there is the complication that x is unquantifiable for irregular and even circular
column perimeters.
After investigations at CSC and external consultations, the conclusion arrived at was that
making the same amplification as at the first check perimeter seemed reasonable and probably
more conservative than what had previously been done/assumed in practice for many years.
Slab Merging
For Orion to be able to resolve the punching perimeter around any column all of the slabs
inserted around that area need to be merged into one. For simple geometries this is not a
challenge. For more complex cases it is a significant challenge where improvements have been
made on an ongoing basis.
Where difficulties are encountered the floor slab merge options may help to either resolve the
issue completely, or isolate the problem so that the modelling can be adjusted.
The examples below are exaggerated in some respects but they do show how the features work.
Orion Documentation page 528 Chapter 29 : Punching Shear Checks
Notice that some of the punching perimeters in the slab area shown above are clearly
incorrect. The option to Hatch Floor Area can be used as shown below and this shades all the
slab areas that Orion has managed to merge.
Clearly one of the slabs has not been included, the reasons why this might happen vary, but
usually become apparent if the boundary of the slab is examined in close up. In this example
the slab and some of the adjacent small strips do not meet properly, the slabs can be redefined
and the merged floor area and punching perimeters are all then resolved as shown below.
Chapter 29 : Punching Shear Checks Orion Documentation page 529
Note In general it is good practice to avoid thin strips of slab and have fewer slabs
wherever possible. Not only does it avoid the sort of problem shown above, it is
also less likely to cause meshing difficulties during the FE analysis.
Tip The Slab Merging option can be used at any stage during model creation,
therefore you can check your model for potential problems as you create it rather
than finding problems later on when much more editing (and reanalysis) may be
required to eliminate them.
A second typical problem occurs where lots of grids meet at or near a single point. The view
below shows a column where 6 grids are meeting in close proximity and the punching shear
check is showing a long section of black (missed) perimeter.
Orion Documentation page 530 Chapter 29 : Punching Shear Checks
When the hatching option is used you can begin to see more clearly how the slabs have not
been defined so that a triangle has been missed within the column. (This sort of problem
usually occurs in smaller triangles than shown here.)
If we now check the option to include the column wall and beam edges and then re-hatch, the
area inside the column is considered as another slab area and so the merged boundary works
round the perimeter of the column. This will potentially avoid all problems relating to local
inaccuracies where grids meet.
Chapter 29 : Punching Shear Checks Orion Documentation page 531
If the punching shear check is them made with this option active the perimeters seem much
more reasonable. Note that in this example the missed triangle actually extends outside the
column and so is considered as a hole with the resultant shortening of the punching perimeter.
Specification of Effective Slab Reinforcement
When defining the effective slab reinforcement you can only provide one value which will
apply at all the check perimeters. In practice it is possible that lesser values of effective tension
reinforcement may be applicable at perimeters further from the column perimeter. In such
cases results from multiple checks may need to be used, or the more conservative (lower) value
could be used for a single check across all perimeters.
Providing the Shear Reinforcement
Orion provides the design checks and information to allow the detailing to commence. As
noted within the examples, the detailing is not necessarily a trivial matter, especially when
allowances for holes need to be made.
Punching Perimeters
The displayed punching perimeters should look correct and complete. No examples of
incorrect perimeters are shown in this document (other than the debatable perimeters shown
above).
The presence of holes and/or complex irregular slab geometry may trigger problems in the
perimeter identification. Where holes appear to be the source of the problem it is again worth
considering removing the holes and using the option to specify a periphery reduction. Where
slab geometry appears to be the source of the problem it is possible that the slabs can be
redefined locally to avoid the problem.
Orion Documentation page 532 Chapter 29 : Punching Shear Checks
Walls
Checks on walls are made but should be viewed with particular caution.
The example above shows 3 discrete walls being checked. In this example the perimeter of the
wall on grid D looks suspicious (line being drawn outside the slab). On closer checking you
would find that the effective length of the punching perimeter is actually correct.
It is particularly advisable to check the lengths used for the punching perimeters in the case of
walls, and it is also noted that overlapping perimeters (see Overlapping Perimeters below) will
almost always apply where core walls are used.
In addition there could well be some debate as to the applicability of a concentrated punching
load check in the case of long walls, BS8110 provides no additional guidance on this. Could
there be a stress concentration at the ends that is not being checked?
Overlapping Perimeters
Where supports are closely spaced and perimeters overlap the code requires that a single
combined perimeter be checked. Orion does not identify such conditions and will simply
draw overlapping perimeters on the screen. If this condition occurs additional hand
calculations are required to substantiate the design.
Chapter 29 : Punching Shear Checks Orion Documentation page 533
Discontinuous Columns
In the special case where a slab supports a column or wall Orion will not make any checks at
all. The case remains beyond the current scope and additional hand calculations are required
to substantiate the design.
Advantages
Checking punching perimeters by hand can be a very tedious and time-consuming task. It is
not yet something that we can completely automate in Orion, and so it must still be treated as
an interactive activity. This interactive checking procedure will also be subject to limitations
in many projects.
However, we hope that this chapter still illustrates the potential for significant time saving if
punching shear checks are made using Orion. It is especially noted that once the initial checks
have been made (thus setting up the correct check data), subsequent rechecking can be carried
out very quickly indeed.
It is also noted that by following the training guidance notes and making checks as models are
constructed limitations can be determined earlier and hence time can be saved overall.
We look forward to receiving comments on this feature so we can continue to refine it to meet
the demands of designers.
EC2 Design Code Requirements
The Design Procedure
In EC2 section 6.4 covers the requirements for checking punching shear. Orions punching
shear check cannot be used without a reasonable understanding of the codes requirements.
The following notes provide a brief overview of these.
Cl 6.4.3 describes the basic design procedure; shear capacity is checked at the face of the
column and then at the basic control perimeter. If shear reinforcement is required a further
perimeter is established at which shear reinforcement is no longer required.
Check Maximum Shear Capacity
This is a check at the face of the loaded area, refer to clause 6.4.5(3) of EC2.
The length of the shear perimeter at the column face may be calculated in accordance with
clause 6.4.5(3). Note that this only provides specific design guidance for rectangular columns
with this guidance being further limited, for the case of edge and corner columns, to those
cases where the edge(s) of the slab coincide with the edge(s) of the column. Therefore for
other column shapes and scenarios Orion has to modify the equations presented in EC2. It is
considered that the equations used by Orion will result in either the correct perimeter length
being obtained or a conservative value (i.e. an underestimate of the perimeter length).
Check Shear Capacity at the Basic Control Perimeter
The basic control perimeter is at 2d from the face of the column (the loaded area), where d is
the average effective depth of the tension reinforcement.
Orion Documentation page 534 Chapter 29 : Punching Shear Checks
To make an accurate check on this perimeter the following needs to be known/controlled:
Is it an internal/edge/corner condition?
How much main reinforcement is effective?
Are there holes, for which you need to account?
The shear stress at the modified basic control perimeter, v
Ed,1
is calculated from Eqn 6.38 as
follows:
v
Ed,1
= V
t
/ (u
1
d)
The punching shear resistance of slab without punching shear reinforcement, v
Rd,c
is then
calculated at the basic control perimeter. Three results are possible:
If v
Ed,1
> 2v
Rd,c
the slab thickness is inadequate, the check has failed and no further
calculations possible for the particular column.
else
If v
Ed,1
<= v
Rd,c
the punching shear resistance of the slab is aedquate without the provision
of shear reinforcement. No further calculations are necessary.
else
the punching shear resistance of the slab is inadequate without the provision of shear
reinforcement. Shear reinforcement is required, and the checking procedure moves on to
determine a further perimeter where shear reinforcement is no longer required.
Calculate Shear Reinforcement Required and Length of Outer Control Perimeter
The quantity of shear reinforcement required when the shear stress at the basic control
perimeter, v
Ed,1
, exceeds the shear strength of the slab without shear reinforcement, v
Rd,c
is
calculated using clause 6.4.5(1) and Eqn 6.52.
The length of perimeter where shear reinforcement is not required, u
out
is calculated from Eqn
6.54.
Calculation of Magnification Factor
As with BS8110, EC2 increases the basic punching shear force to obtain the design punching
shear force when an unbalanced bending moment is transferred between the slab and column.
In EC2 this design punching shear force is obtained by multiplying the basic punching shear
force by the magnification factor which has a value greater than 1.0. The purpose of this
section is to detail the way in which Orion determines the value of for various column
situations.
Internal column
is calculated using the equation:
Magnification factor = 1 + k1.(M
t1
/V
t
).(u
1
/W
11
) + k
2
.(M
t2
/V
t
).(u
1
/W
12
)
Where k
y
& k
z
are factors from Table 6.1 depending on the column aspect ratio for the
particular direction
M
t1
& M
t2
are the transferred moments in the two orthogonal directions
Chapter 29 : Punching Shear Checks Orion Documentation page 535
V
t
is the transferred shear force
u
1
is the length of the basic control perimeter located at 2.0d from the face of the
column
W
11
and W
12
are the first moments of the basic control perimeter about the two axes
(see the section on calculation of W
1
below)
The length of the basic control perimeter is modified to take account of the presence of actual
physical holes in accordance with 6.4.2(3) and the first moment of area of the perimeter is
calculated based on this reduced length.
For the case where the presence of holes is represented by a value of the Perimeter Reduction
(General) greater than zero then, since the actual location of the loss of perimeter is unknown,
the value of is calculated as follows:
Magnification factor = 1 + (u
1
/u
1,red
).[k1.(M
t1
/V
t
).(u
1
/W
11
) + k
2
.(M
t2
/V
t
).(u
1
/W
12
)]
Where u
1
is the full perimeter length ie not reduced by Perimeter Reduction
u
1,red
is the reduced perimeter length ie reduced by Perimeter Reduction
W
11
& W
12
are both calculated based on the full perimeter length
Edge column
If the user chooses not to select that the column be treated as an edge column the value of
will be calculated as for an internal column as detailed above taking account of the presence of
the edge of the slab.
If the user selects that the column be treated as an edge column then the component of
resulting from the transferred moment about the axis parallel to the edge of the slab is taken as
1.4 ie as in Figure 6.21 of EC2. The component of to take account of any transferred bending
moment about the axis perpendicular to the slab edge is calculated using the right hand term
of equation 6.44 ie k.(u
1
/W
1
).e
par
which is effectively the generic equation 6.39. The effects of
the moments about the two orthogonal axes are then combined using simple addition as
follows:
Magnification factor = 1.4 + k.(M
t
/V
t
).(u
1
/W
1
)
where k, M
t
and W
1
all relate to bending about the axis perpendicular to the edge of the slab.
Where actual physical holes are present or the Perimeter Reduction is greater than zero, W
1
is
calculated as described for an internal column but taking account of the location of the edge of
the slab.
Corner column
If the user chooses not to select that the column be treated as a corner column the value of
will be calculated as for an internal column as detailed above taking account of the presence of
the edge of the slab.
If the user selects that the column be treated as a corner column the value of will be taken as
1.5 from Figure 6.21 of EC2 with no additional calculation. The value of 1.5 is not adjusted if
actual physical holes are present or if the Perimeter Reduction is greater than zero.
Orion Documentation page 536 Chapter 29 : Punching Shear Checks
Calculation of W
1
EC2 describes W
1
as a factor which 'corresponds to a distribution of shear as illustrated in
Figure 6.19 and is a function of the basic control perimeter u
1
'.
Figure 6.19: Shear distribution due to an unbalanced moment at a slab-internal
column connection
W
1
may be calculated from equation 6.40 as follows:
W
1
= int
0
u
|e|l
Note nt
0
u
means integral between limits 0 & u ie over the full length of the perimeter
where l is a length increment of the perimeter
and |e| is the modulus of the distance of the increment from the axis about which the
moment acts
or in other words W
1
= the first moment of the perimeter about the axis about which
the moment acts.
EC2 does not state specifically which axis is meant by 'the axis about which the moment acts'.
Is it the column centreline, the centroidal axis (elastic neutral axis) of the perimeter or the
equal 'area' axis (plastic neutral axis) of the perimeter? For a doubly symmetric perimeter ie
one surrounding an internal column and which isn't affected by the presence of holes, all three
of these perimeters are coincidental. Figure 6.19 of EC2 shows such a perimeter and so doesn't
help in defining about which axis W
1
should be calculated.
However, Figure 6.19 does appear to indicate a plastic distribution of stresses with both
positive and negative stresses occurring. In order to maintain a vertical equilibrium of forces
this would dictate that W
1
be calculated about the plastic neutral axis of the perimeter.
An extensive amount of investigation has gone into the effect on of calculating W
1
about
both the column centreline and the perimeter plastic neutral axis. This has shown that where
the two differ in location then, almost without exception, the value of is greater when W
1
is
calculated about the perimeter plastic neutral axis compared to the column centreline.
However, for internal columns, even with fairly substantial holes modelled, the difference in
the value of is relatively small being of the order of 5%. With a small hole modelled, say
250mm square, the difference in the two values becomes negligible. For edge and corner
columns, however, the difference becomes quite significant. For a particular column and slab
Chapter 29 : Punching Shear Checks Orion Documentation page 537
arrangement examined, the values of for an edge and corner column with W
1
calculated
about the column centreline were 1.782 and 2.049 respectively but with W
1
calculated about
the perimeter plastic neutral axis these increased to 2.727 and 3.644 respectively. These values
were calculated assuming no holes present to affect the perimeter. Some comparison ought,
therefore, to be able to be made between the values of for edge and corner columns
presented in Figure 6.21 (for a regular structural layout) shown below and the calculated
values.
Figure 6.21: Recommended values of
As can be seen from Figure 6.21 the recommended values of for edge and corner columns in
a structure with a regular layout are 1.4 and 1.5 respectively which are both approximately
three quarters of the corresponding value of obtained with W
1
calculated about the column
centreline and a significantly smaller proportion of the value of obtained with W
1
calculated
about the perimeter plastic neutral axis.
For these reasons therefore, ie for internal columns, a small difference between the value
obtained with W
1
calculated about the column centreline and the perimeter plastic neutral
axis and for edge and corner columns, an apparently over conservative value of obtained
when W
1
is calculated about the perimeter plastic neutral axis, Orion calculates W
1
with
respect to the column centreline.
It should be noted that for internal columns the value of will only be affected by the axis
about which W
1
is calculated when actual physical holes which affect the perimeter are
modelled since, in all other cases (including when the Perimeter Reduction is greater than
zero), the column centreline and the perimeter plastic neutral axis are coincidental. For edge
and corner columns which are selected to be treated as edge and corner columns the axis
about which W
1
is calculated will only affect that portion of applied to an edge column due
to the transferred moment, if any, about the axis perpendicular to the edge of the slab when
actual physical modelled holes affect the perimeter. This is because for edge columns with the
perimeter unaffected by actual physical holes the column centreline and perimeter plastic
neutral axis perpendicular to the slab edge are coincidental and for all other elements of for
edge and corner columns which are selected to be treated as edge or corner columns the
method adopted by Orion for obtaining doesn't require the calculation of W
1
.
Orion Documentation page 538 Chapter 29 : Punching Shear Checks
Chapter 30 : Slab Deflection Checks Orion Documentation page 539
Chapter 30 Slab Deflection Checks
Introduction
The "Creep/Cracking" button located on the "Finite Element Floor Analysis" form is used to
make an allowance for creep, cracking and shrinkage when determining concrete slab
deflection.
A comprehensive discussion of creep, cracking and shrinkage is provided in the following
topics, along with a detailed comparison of the BS8110 and EC2 slab deflection checks.
Overview of Concrete Slab Deflection
Total Concrete slab deflection can be broken down into 3 main parts each of which is often
estimated as accounting for around 1/3 of the total deflection:
Instantaneous Deflection (Cracked section effects are part of this part)
expected to be up to or around 1/3.
Creep
expected to be > 1/3.
Shrinkage
expected to be < 1/3.
Various texts may be consulted for opinion on the variation in these proportions and other
aspects of deflection estimation:
Ref 1: Concrete Society Publication TR58 - Deflection of Concrete Slabs and Beams.
Ref 2: Concrete Society Publication TR64 - Guide to the Design and Construction of
Reinforced Flat slabs.
The key point is that they are all of significant importance. Now consider each of these
headings in a little more detail.
Instantaneous Deflection
A common rough estimate is that the overall effect of cracking along the length of a beam will
on average double the uncracked deflection. Bear in mind that the theoretical degree of
cracking varies along the beam length of the beam. Therefore if you calculate deflection
ignoring cracking and creep and shrinkage then the value you have is around 1/6 of the total.
In essence this is the basis of the accepted practice/guidance that a multiplier of between 4 and
6 should be applied to deflection calculations based on a short term E value. The 4 to 6 range
recognises the different loading types and uncertainties involved, offices are typically assumed
to be closer to the 4 and storage situations are assumed to be closer to 6.
A cracked section analysis only improves your estimation of this sub-section of the total
deflection estimate. The accuracy of cracked section analysis is also variable - different
analysis products do different things in this regard and will get different answers. Ideally the
analysis should consider all of the following:
Orion Documentation page 540 Chapter 30 : Slab Deflection Checks
The cracked/uncracked status of every shell in the mesh should be determined separately -
some products may make more generalised adjustments?
Each individual shell can possibly be cracked in one direction and not cracked in the other
- to cater for this requires non isotropic properties. Some products may not have the
capability to do this?
Allowing for supplied steel. In theory, by over-providing steel you can delay or prevent
cracking. Ideally the provided steel needs to be defined in such a way that every shell
knows how much reinforcement will actually pass through it (top and bottom in each
direction). Alternatively some simplification of this may be used where As-supplied =
Factor * As-required, is this flexible enough?
Early Age Cracking
As part of the construction process concrete slabs tend to see some of their most onerous
design conditions when they are only days or weeks old. Cracking is more likely to happen
in young concrete, once it is cracked it is cracked! An accurate cracked section deflection
calculation should consider this. It seems that most or all FE slab products offer little if
any control over this.
Most or all FE slab design packages will make some degree of simplification in the procedures
used to introduce cracked section deflection effects.
Creep Deflection
The deflection of a concrete slab subjected to a constant loading will increase over time. The
rate of this increase is dependent on a number of factors, but to accurately assess creep you
definitely need to know something about the proposed sequence and timing of loading.
Once again many software packages are not dealing with this in any great degree of detail -
overall adjustment factors are assumed.
Shrinkage Deflection
If you reinforce a concrete section asymmetrically then as the concrete shrinks the shrinkage
will be resisted more on the side that has more reinforcement and so the shortening of that
side will be less. A curvature is induced in the member with the more heavily reinforced side
being on the outside of the curve. This curvature will naturally add to the overall deflection.
Theoretical solutions for this exist but so far as we know no one has found/applied a way of
doing this in the context of a 3 dimensional FE floor analysis. Shrinkage deflection is always
added as an adjustment factor, or is it being ignored?
At this point it is also worth considering the practice of adding tension reinforcement in order
to control deflection by virtue of the theory that cracking is being controlled. When shrinkage
is considered the addition of this reinforcement causes increased deflection. Is it clear and
proven that this practice definitely has the intended effect?
Chapter 30 : Slab Deflection Checks Orion Documentation page 541
Creep/Cracking Allowance Summary
Deflection estimation for concrete beams and slabs is not an exact science, whatever method
you use you should bear in mind the significant uncertainties involved - it remains an
estimate.
With regard to FE analysis of flat slabs the requirement to consider cracked section analysis is
often raised as being important. In fact this only introduces a greater degree of certainty to
around 1/6 of the total deflection estimate. Rather than focussing specifically on the effect of
cracking engineers should focus on the estimates of overall deflection and consider the
possible accuracy/error in this total.
There is a belief among some proportion of practicing engineers that traditional methods of
sizing slabs based on span/effective depth methods are conservative and therefore that a more
detailed deflection estimate involving assessment of creep/cracking/shrinkage will allow
thinner slabs to be proved as adequate. On the following pages comparisons are made for a
very simple example. It demonstrates that this expectation is not fulfilled and that the rigorous
methods could be quite wasteful if applied un-necessarily. It demonstrates that the use of
linear FE analysis along with appropriate stiffness multipliers is a very effective method for
demonstrating serviceability compliance in normal circumstances.
Slab Depth and Deflection Comparisons
In this section comparisons of slab depth and deflection are made for BS8110 and EC2.
Standard Slab Details
The following is applied consistently throughout:
A 6m span simply supported slab is considered
Dead Load is taken as - Self weight + 1.5kN/m2 finishes
Imposed Load is taken 5kN/m2 IL (including 1.0 for partitions). This is applied regardless
of the classification of the load type as "office" or "storage".
Orion Documentation page 542 Chapter 30 : Slab Deflection Checks
Comparison of Span / Eff depth checks for grade C20/25 concrete.
Notes:
EC2 offers a small advantage compared to BS8110 when the "office" loading category is
considered.
The benefit of adding 50% reinforcement is limited to around a 10% reduction in slab
depth.
Rigorous Deflection Calculations for grade C20/25 concrete.
Rigorous deflection calculations are performed for both the storage and office loads.
General Notes on the Calculation Method
The Concrete Centre Spreadsheet TCC31R is used throughout. The calculations implemented
in this spreadsheet include allowance for cracking, creep, and shrinkage as specified in EC2 .
An FE analysis cannot bring any more rigour to these calculations. In practice the calculations
applied in most if not all FE packages will involve simplifications and/or the use of simple
adjustment factors in place of aspects of the more rigorous calculation.
When using TCC31R the user is required to provide input on the timing and nature of loading
during construction. The following assumptions are applied consistently:
Construction Loading includes propping load = 50% of slab load plus 0.75kN/m2
construction load allowance.
Construction Load is applied at the date stated in the tables and finishes at day 60.
Partitions load is assumed to exist from day 60.
Full dead + permanent imposed load is assumed to exist from day 90.
Design
Code
Slab
Thickness
mm
As req'd
for
strength
mm2/m
Increase
req'd for
deflection
control
As
provided
mm2/m
Concrete
Saving %
Increased
Reinforce
ment Cost
%
BS8110 290 835 4 % 894 - -
260 909 30 % 1340 10 % 50 %
250 939 46 % 1608 14 % 80 %
240 973 71% 2011 17 % 125 %
EC2
storage
290 848 2 % 894
260 928 42 % 1340 10 % 50 %
EC2 office 270 855 1 % 894
255 898 18 % 1149 9% 29 %
Chapter 30 : Slab Deflection Checks Orion Documentation page 543
Storage Condition
Notes:
A 310mm slab is borderline when EC2 span/effective depth showed 290 to be adequate.
A 50% reinforcement increase is required to get the depth down to 290mm
Cannot get anywhere near the 260 thick slab justified in BS8110 and EC2 span/eff depth
when 50% reinforcement is introduced.
Adding 50% reinforcement is allowing something less than a 10% reduction in slab depth.
Adding 50% reinforcement reduces deflections by 10 to 15% and seems to have less effect
on the deflection affecting the partitions.
In all cases the deflection affecting partitions is very close to 50% of the permanent
deflection.
Decreasing slab depth by 6.5% results in deflection increase of 12%
Office Condition
Slab
Thickness
(mm)
Strike at
(days)
Constructi
on Load at
(days)
Reinf 't
increase
applied for
deflection
control
Permanent
Deflection
(target
limit
24mm)
Imposed
Deflection
(target
limit
12mm)
Deflection
affecting
Partitions
310 14 28 0 % 24.12 0.92 12.59
7 14 0 % 26.50 1.35 13.34
290 7 14 0 % 29.68 1.53 15.37
7 14 50 % 25.20
(-15%)
1.14 13.93
(-10%)
Slab
Thickness
(mm)
Strike at
(days)
Constructi
on Load at
(days)
Reinf 't
increase
applied for
deflection
control
Permanent
Deflection
(target
limit
24mm)
Imposed
Deflection
(target
limit
12mm)
Deflection
affecting
Partitions
290 14 28 0 % 24.80 5.24 10.56
7 14 0 % 26.45 5.56 11.13
275 7 14 0 % 28.59 6.00 12.45
7 14 50 % 24.67
(-14%)
4.42 11.90
(-5%)
Orion Documentation page 544 Chapter 30 : Slab Deflection Checks
Notes:
In offices 30% of the IL is assumed to be permanent
The permanent deflection does not include instantaneous deflection from the balance of
the IL.
Permanent Deflection (not total deflection) is checked against the span/250 limit. This
may seem unconservative, however the end result is still conservative by comparison with
EC2 span/effective depth.
A 290mm slab is borderline when EC2 span/effective depth showed 270 to be adequate.
A 50% reinforcement increase only reduces the depth down to 275mm.
Cannot get anywhere near the 255 thick slab justified in EC2 span/eff depth when 50%
reinforcement is introduced.
Adding 50% reinforcement is allowing something less than a 10% reduction in slab depth.
Adding 50% reinforcement reduces deflections by 5 to 15% and seems to have less effect
on the deflection affecting the partitions.
In all cases the deflection affecting partitions is 40 to 50% of the permanent deflection.
Decreasing slab depth by 5% results in deflection increase of 8%
Chapter 30 : Slab Deflection Checks Orion Documentation page 545
Comparison of Span / Eff depth checks for grade C35/45 concrete.
Notes:
EC2 offers very significant reductions by virtue of considering an increased concrete
grade. This is generally accepted in principle, there is however some debate as to the
degree of this apparent advantage. (Ref Paper by Alasdair Beal - The Structural Engineer
20th October 2009)
In this example the reduction of slab depth allowable using EC2 is as much as 20%
(290mm down to 230mm). If stiffness is assumed to be proportional to h3 then this
corresponds to a 50% reduction in stiffness. If stiffness is only assumed to be proportional
to h2 then this still corresponds to a 35% reduction in stiffness. Was there a 35 to 50%
margin of overdesign in BS8110? It seems a reasonable question.
The benefit of adding 50% reinforcement is limited to around a 10% reduction in slab
depth.
Rigorous Deflection Calculations for grade C35/45 concrete.
Rigorous deflection calculations are performed for both the storage and office loads.
General Notes on the Calculation Method
The notes made in relation to C20/25 concrete apply.
Design
Code
Slab
Thickness
mm
As req'd
for
strength
mm2/m
Increase
req'd for
deflection
control
As
provided
mm2/m
Concrete
Saving %
Increased
Reinforce
ment Cost
%
BS8110 290 825 4 % 894 - -
260 885 30 % 1340 10 % 50 %
250 908 46 % 1340 14 % 50 %
240 933 71% 1608 17 % 80 %
EC2
storage
250 923 2 % 1005
225 1007 49 % 1608 10 % 60 %
EC2 office 230 943 6 % 1005
225 962 14 % 1149 2 % 14 %
Orion Documentation page 546 Chapter 30 : Slab Deflection Checks
Storage Condition
Notes:
A 260mm slab is required when EC2 span/effective depth showed 250 to be adequate.
A 50% reinforcement increase is required to get the depth down to 250mm
Cannot get anywhere near the 225 thick slab justified in EC2 span/eff depth when 50%
reinforcement is introduced.
Adding 50% reinforcement is allowing something less than a 10% reduction in slab depth.
Adding 50% reinforcement reduces deflections by 20%.
In all cases the deflection affecting partitions is 50 to 60% of the permanent deflection.
Decreasing slab depth by 8% results in deflection increase of 10%
Office Condition
Slab
Thickness
(mm)
Strike at
(days)
Constructi
on Load at
(days)
Reinf 't
increase
applied for
deflection
control
Permanent
Deflection
(target
limit
24mm)
Imposed
Deflection
(target
limit
12mm)
Deflection
affecting
Partitions
260 14 28 0 % 24.02 0.24 14.77
7 14 0 % 24.35 1.15 12.77
250 7 14 0 % 27.89 0 15.85
7 14 50 % 22.41
(-20%)
0.89 12.71
(-20%)
240 7 14 50 % 26.84 0 15.67
Slab
Thickness
(mm)
Strike at
(days)
Constructi
on Load at
(days)
Reinf 't
increase
applied for
deflection
control
Permanent
Deflection
(target
limit
24mm)
Imposed
Deflection
(target
limit
12mm)
Deflection
affecting
Partitions
240 14 28 0 % 24.57 5.96 11.56
7 14 0 % 26.58 6.45 11.08
230 7 14 0 % 28.38 6.81 12.19
7 14 50 % 24.50
(-14%)
4.90 11.65
(-4%)
Chapter 30 : Slab Deflection Checks Orion Documentation page 547
Notes:
In offices 30% of the IL is assumed to be permanent
The permanent deflection does not include instantaneous deflection from the balance of
the IL.
Permanent Deflection (not total deflection) is checked against the span/250 limit. This
may seem unconservative, however the end result is still conservative by comparison with
EC2 span/effective depth.
A 240mm slab is borderline when EC2 span/effective depth showed 230 to be adequate.
A 50% reinforcement increase reduces the depth down to 230mm.
Cannot quite get down to the 225 thick slab justified in EC2 span/eff depth.
Adding 50% reinforcement is allowing something less than a 10% reduction in slab depth.
Adding 50% reinforcement reduces deflections by 5 to 15% and seems to have less effect
on the deflection affecting the partitions.
In all cases the deflection affecting partitions is 40 to 50% of the permanent deflection.
Decreasing slab depth by 4% results in deflection increase of 7%
Orion Documentation page 548 Chapter 30 : Slab Deflection Checks
Deflection Estimates using Linear FE Analysis
Guidance on Short Term E values are given in the codes. It is made clear that there is
potentially significant variation in these values. Typical values for the concrete grades being
considered in this document are:
To give an estimate of total deflection that can be compared to the span/250 limit it is
recommended that the short term values indicated above are significantly reduced to allow for
effects of creep, cracking and shrinkage. General guidance on this has been:
Storage Condition - Reduce by a factor of 6
Office Condition - Reduce by a factor of 4
Therefore, an FE analysis can be carried out using the adjusted E values and deflection
contours can be reviewed. For this example the total deflection limit = 6000/250 = 24mm
Example results using the above guidance are given below.
BS8110 EC2
C20/25 25N/mm2
(Range 19 - 31)
30
(Range - 30% to + 20%)
C35/45 29N/mm2
(Range 23 - 35)
34
(Range - 30% to + 20%)
Chapter 30 : Slab Deflection Checks Orion Documentation page 549
FE Analysis Results for C20/25
Storage Condition (EC2 material properties)
Office Condition (EC2 material properties)
FE Analysis Results for C35/45
Storage Condition (EC2 material properties)
Office Condition (EC2 material properties)
Slab Deflection
290 23.0
280 25.1
Slab Deflection
270 18.3
260 20.1
250 22.2
240 24.6
Slab Deflection
280 22.1
270 24.2
260 26.6
250 29.3
Slab Deflection
230 24.1
240 21.7
Orion Documentation page 550 Chapter 30 : Slab Deflection Checks
Overall Summary of Minimum Slab Depths
The table below shows the minimum depths that could be considered adequate for each of the
examples under consideration. In all cases reinforcement is not being added in order to
control deflection.
Notes:
In every case rigorous deflection estimation cannot justify the slab depths that are
considered adequate based on EC2 span / effective depth.
For the storage condition the E/6 adjustment to stiffness results in very reasonable slab
depths being deemed adequate.
For the office condition the E/4 adjustment leads to a slab that is definitely too thin in one
case (*). In general this advice seems quite reasonable / borderline when the adjustment is
applied to the BS8110 properties. It may not be completely adequate as Engineers move to
the use of EC2 properties in analysis models. E/5 may be better advice for the office
situation.
Summary
Key observations from this exercise and all other work done on this topic are:
1. BS8110 span /effective depths appear to assume a low grade of concrete and do not
differentiate between different loading conditions. It seems logical that the depths given
by BS8110 will be conservative when higher grades of concrete are used and when the
loading is transient rather than sustained.
2. EC2 span /effective depths deal with this and seem to allow significantly reduced slab
depths when both of these factors are introduced. The magnitude of the benefit
introduced by EC2 is open to some debate.
3. Rigorous deflection estimation:
Does introduce benefits compared to BS8110 when higher concrete grades are considered.
Is never able to justify the slab depths that are considered adequate based on EC2 span /
effective depth.
In general it seems that at least 50% extra reinforcement needs to be added in order to
match the thicknesses deemed adequate by span / effective depth
4. Deflection Checks based on Linear FE estimation:
Concrete Usage BS8110spa
n/depth
EC2 span/
depth
EC2
Rigorous
Linear FE E
as EC2
Linear FE E
as BS8110
C20/25 Storage 290 290 310 290 310
C20/25 Office 290 270 290 240 * 260
C35/45 Storage 290 250 260 270 290
C35/45 Office 290 230 240 230 250
Chapter 30 : Slab Deflection Checks Orion Documentation page 551
Does introduce benefits compared to BS8110 when higher concrete grades are considered.
Is generally not able to justify the slab depths that are considered adequate based on EC2
span / effective depth.
For office loading situations the suggested E/4 adjustment should be used cautiously, E/5
may be a more prudent minimum adjustment, especially if the higher short term E values
introduced in EC2 are assumed as the starting point.
5. If reinforcement is added in order to reduce slab depth:
Adding reinforcement has an impact but it is not significant and may not be economic.
Adding 50% to the tension reinforcement will allow slab depth to be reduced by less than
10%. (Typically only 20mm for slabs up to around 300mm thick)
6. If reinforcement is added in order to reduce deflection:
Calculations suggest that adding 50% to the tension reinforcement will reduce total
deflection by 10 to 20%.
Where concern relates more to the deflection occurring after the introduction of walls and
other sensitive/brittle finishes then adding 50% to the tension reinforcement has less
impact - perhaps only 5 to 10%.
7. Adjusting the slab depth has the greatest direct impact of deflection.
Rigorous calcs suggest a 5 to 10% reduction in depth leads to a 10 to 20% increase in
deflection.
8. Where concern relates to the estimation of deflection affecting brittle finishes:
In theory this is significantly affected by construction stage events and the time at which
the brittle finish is applied.
The concrete centre spreadsheet may be used to determine the reasonable ratio between
this deflection and total deflection. For the examples considered this ratio varied from 40
to 60%. For each specific example the variation of this ratio was less than 10%.
Based on this the maximum deflections affecting brittle finishes can be estimated to some
reasonable degree of accuracy.
9. Overall Accuracy:
It has to be remembered that regardless of the apparent sophistication of deflection
estimate techniques, estimates are still estimates and a significant margin of uncertainty
exists.
Orion Documentation page 552 Chapter 31 : Linking and Merging Projects
Chapter 31 Linking and Merging Projects
Introduction
This chapter provides an overview of the reasons why, and the way in which, model linking
and merging is used in Orion. Although the two features are related they are used for quite
different purposes:
Linking Models for Common Foundation Design
Merging (Complete) Models
Note The Merging (Complete) Models feature has yet to be enabled in the market
version of the program.
Why Merge Models?
Model merging allows an engineer working on one project to import an entire model that has
been created separately. The two models can be combined to create a single large project and
once created there will be no cross reference or linking back to the source project(s). This
feature allows:
More than one engineer to work on the creation of model data for a large project.
Where there is repetition of the floor plan within a project, a standard sub-section can be
defined and then merged several times to create the full model (in effect a "copy/paste"
function).
Model relocation - If for whatever reason a model has been created a great distance from
the origin, it can be relocated to a more convenient position. The original model is simply
merged into a new empty model using the offsets, once again emulating a "copy/paste"
function.
Why Link Models for Common Foundation Design?
Separate blocks of buildings (they are separated because of shrinkage issues or seismic
reasons) are modelled in different projects in practice. They are modelled separately
because, they require separate post-analysis controls (Soft Storey, Weak Storey, torsion
control, hammering checks, additional eccentricities etc.)
Statically, free chunks of uncoupled 3D systems in space will yield the same analysis results
regardless of separate modelling. However, modelling those together will make the model
unnecessarily crowded.
There will be separate blocks of buildings in a large construction complex. Some of these
blocks are identical. Engineers tend to analyse and design only one of those blocks. The
typical project is then used for other similar blocks.
Linking models allows a common foundation to be modelled for these kinds of buildings.
Separate models are maintained for each block, one of the models contains a common
foundation which links to the other models.
Chapter 31 : Linking and Merging Projects Orion Documentation page 553
How is Linked Foundation Design Data Introduced?
In any project, links to one or more other models can be made so that a common
foundation system analysis and design is possible. The project in which the links are
created (the 'foundation project'), becomes the one in which the foundation design for all
the linked models is undertaken.
Not all members or storeys are transferred from the linked models - only the supported
columns and walls at foundation level, with their loadings.
The project in which the links are created is not restricted in any way - you are free to
construct, analyse and design the model in the usual way. The foundation columns and
walls from the linked models do not get considered in the Building Analysis or Post
Analysis processes, they are only considered in the foundation design.
It is not essential to define any superstructure model for the foundation project, you are
able to link from a blank (master) project to other projects if you prefer to do so.
Models that are linked in to the foundation project can be re-located by translation but not
rotation. You are responsible for setting up the source models at the appropriate relative
angles.
During linking the foundation design forces created in the linked model populate a
foundation forces data table thus creating a complete composite set of data which can be
used in foundation design.
At foundation level, new slabs, beams and foundation systems are able to be defined as
required.
What is a Linked Column?
Columns that have been imported by linking read their analysis results directly from the
linked model. Analysis results of linked columns cannot be changed unless a force
override is applied.
If the position of the column in the linked model is altered then the link will be broken in
foundation project.
Columns can be deleted.
What is a Force Override?
Whether linked or not, you are able to apply force overrides to columns for the purposes of
foundation design.
Force overrides are applied via the The Foundation Forces Table.
For a linked column the link to it's original project is retained, however, the analysis results
are overridden.
You can select to cancel the override operation at a later stage. In which case, the analysis
results will be restored from the linked model.
What is Link Deletion?
You can if required completely break the relation of the column with the linked model.
The column becomes part of the foundation project and you are then able to change the
section and analysis results.
Orion Documentation page 554 Chapter 31 : Linking and Merging Projects
Creating a Foundation Project
Requirements for Models to be Linked for Foundation Design
The models should have same load cases and combinations.
Procedure for Linking Existing Models into a Foundation Project
1. Open the project in which you want to create the foundation.
2. From the File menu choose Model/File Import, Load Building Model.
The following dialog is displayed;
3. Select the model to import. Note that models can reside in different drives and directories
of the computer.
4. Enter a Block Character for the imported model.
5. Choose whether the imported columns and walls are to have the block character added to
their reference, or if they are to retain their existing labels (where this is possible).
6. Click the Load Model button.
7. Initially the axes for the linked model will be loaded as a ghost picture.
8. Before import, the linked model must be located in its correct position on the foundation
project.
9. Rough positioning can be done by clicking the Drag Two Points button. Click Move Model
to see the effect.
Chapter 31 : Linking and Merging Projects Orion Documentation page 555
10. Fine tuning can be done by entering X and Y entries directly. Again click Move Model to
see the effect.
11. Click Finish to import the model.
Imported Grids
When a new model is linked into the foundation project, the grid system is merged first. That
is, colinear and overlapping grids are combined, the existing parent grid is taken as the
reference.
In this way, since the existing grid system is not changed, the references of columns inserted
before will stay unchanged.
Imported Columns (and Walls)
Determination of Insertion Points
1. The new co-ordinates for the insertion point of each imported column are
determined.
2. The imported columns are then placed on to the merged grid system at these
co-ordinates.
3. The axes used to define the insertion point of each imported column are automatically
reselected. The first two axes which pass through the insertion point are found by the
program and assigned to the column.
Note If three or more axes pass through the insertion point, the axes adopted by the
column in the imported model may differ from the original model.
Orion Documentation page 556 Chapter 31 : Linking and Merging Projects
Linked Project Manager
The Linked Project Manager is used to monitor the status of all linked/unlinked models
within the project:
If one of the linked projects is highlighted, the Link Management button becomes active.
When clicked the following dialog is displayed:
Remove the Reference of the Selected Project
Two options are available:
Delete All Columns and Walls of the Selected Project. This option removes the link to
the highlighted project and deletes the associated columns and walls.
Un-link All Columns and Walls of the Selected Project This option removes the link to
the highlighted project but the columns and walls are not deleted. You have the option to
retain the existing analysis forces, or to delete them, in which case they can be respecified
via the Foundation Column Loads Table.
Update the Link Information of All Columns and Walls of the Selected Project
This option deletes any user defined loads in the highlighted project.
Chapter 32 : Reports and Drawing Output Orion Documentation page 557
Chapter 32 Reports and Drawing Output
Introduction
Various forms of output can be generated from the program:
Orion Reports
These can printed individually, or combined together using the Report Manager.
Quantity Reports
These can either be printed directly, or exported to Microsoft Access or Excel.
Drawings
These can either be plotted directly, or exported to DXF
Orion Reports
Orion Reports can be created from each of the modules. The main reports are formatted and
consist of a header & footer and a main body containing text, graphics and/or tables.
From the Report Print Preview the report can be configured and printed, or it can saved for
later printing via the Report Manager, (allowing it to be merged together with other Orion
Reports).
Options also exist for exporting the report to different formats as follows:
PDF Saves the report in pdf format.
TXT opens the report in a text editor, but strips out any formatting. Reports containing
graphics can not be opened in a text editor.
TDF Exports as a TAB delimited file.
Note Certain data output (e.g. the FE Analysis Output Report) is unlikely to form
part of your calculation submission and is only created as plain text - it cannot
therefore be incorporated into a formatted report.
The following table summarises the main reports available:
Module Report Type
Load Decomposition Output Report Plain text
Building Analysis Storey Loads Plain text
Building Analysis Validity Check Plain text
Orion Documentation page 558 Chapter 32 : Reports and Drawing Output
Building Analysis Analysis Output Report
4 configurations available as follows:
Nodal Results
Frame Element Results
Shell Element Results
Structural Member Results
Formatted
Building Analysis
and FE Analysis
Axial Load Comparison Report Formatted
Building Analysis Pre-Analysis Checks Report Formatted
Building Analysis Post-Analysis Checks Report Formatted
Building Analysis Analysis Model Echo Report Formatted
Building Analysis Storey Lateral Displacements Report Formatted
Building Analysis Column Bracing (Sway) Classification Formatted
Building Analysis Eigenvalue Results Report Formatted
Building Analysis Beam Load Analysis Report Formatted
FE Analysis Output Report Plain text
Column Design Column Capacity Analyses Formatted
Column Design Column (utilisation) Table Plain text
Column Design Column Reinforcement Design Report Formatted
Column Design Column Forces Listing Plain text
Column Design Interactive Design Report Plain text
Beam Design Beam Capacity Analysis Formatted
Beam Design Beam (utilisation) Table Plain text
Beam Design Beam Reinforcement Design Report Formatted
Slab Strip Slab Strip Check Design Plain text
Slab Analysis and
Design
Slab Analysis and Design Report Formatted
Column Punching
Check
Column Punching Check Plain text
Pad/Pile Footing Pad/Pile Footing Results Formatted
Strip Footing Strip Footing Results Formatted
Stair Design Stair Design Results Plain Text
Module Report Type
Chapter 32 : Reports and Drawing Output Orion Documentation page 559
Report Manager
Formatted reports (once generated by the different modules), will be listed in the Report
Manager. Three options exist for creating a combined report.
All Reports
With this option selected, individual reports can be selected and added to a combined report.
Txt Files
With this option selected, only those formatted reports that can be displayed as text files will
be listed. Individual reports can be selected and added to a combined report, however all
formatting and graphics will be stripped from this report.
Merged Report
If the All Reports option has been previously used to create one or more combined reports and
these reports have themselves been saved, then with this option selected, these combined
reports can be merged with each other.
Quantity Reports
Quantity Reports can be created for concrete, formwork and steel bars.
By clicking on the Quantity Extraction Tables icon (or from the menu File/Quantity Extraction
Tables), formatted reports can be created and printed or the data can be exported to either
Microsoft Access or Excel.
Note Steel bar schedules are only available for those members/slab strips that have
been successfully designed.
Quantity Extraction
Tables
7 extraction tables are available as
follows:
Concrete Quantity Extractions
Formwork Quantity Table
Slab Steel Bars Table
Column/Wall Steel Bar Table
Beam Steel Bars Table
Rib Beam Steel Bars Table
Foundation Beam Steel Bars Table
Formatted
Module Report Type
Orion Documentation page 560 Chapter 32 : Reports and Drawing Output
Drawings
The following table summarises the kinds of drawing available:
Module Drawings
Form Plan 1. General arrangements and sections including slab
reinforcement and dimensions. Slab steel quantity tables
can optionally be included.
2. Flat slab general arrangements including area of steel
contours.
3. Flat slab punching shear perimeters.
Column Application
Plan
4. Reinforcement in column and wall sections, optionally
including:
Steel quantity tables
Longitudinal steel details
Lateral steel displayed near columns
Lateral steel grouped
Foundation Details 5. Pad and pile footing reinforcement and dimensions.
Optionally including a steel quantity table.
Column Design 6. Column Schedule. Includes reinforcement in column and
wall sections arranged by member label for each storey.
Column Design 7. Column Detail Drawings (in elevation).
Beam Design 8. Beam Detail Drawings. Beam reinforcement in elevation
and section. Optionally including a steel quantity table.
Chapter 32 : Reports and Drawing Output Orion Documentation page 561
Examples