AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT
SUMMARY OF RESULTS
Summary of Results Title Test Specimen #1 New Construction Test Specimen #2 Replacement Primary Product Designator HS-LC25 1803 x 1422 (71 x 56) HS-LC30 1803 x 1422 (71 x 56) Design Pressure 1200 Pa (25.06 psf) 1440 Pa (30.09 psf) Operating Force (in motion) 36 N (8 lbf) N/A Air Infiltration 0.61 L/s/m 2 (0.12 cfm/ft 2 ) N/A Water Penetration Resistance Test Pressure 290 Pa (6.06 psf) N/A Uniform Load Structural Test Pressure 1800 Pa (37.62 psf) 2160Pa (45.14 psf) Forced Entry Resistance Grade 10 N/A
Summary of Results Title Test Specimen #3 New Construction Test Specimen #4 Replacement Primary Product Designator HS-LC40 1600 x 1118* (63 x 44*) HS-LC40 1600 x 1118* (63 x 44*) Design Pressure +1920 Pa (+40.13 psf) +1920 Pa (+40.13 psf) Negative Design Pressure -2160 Pa (-45.14 psf) -2400 Pa (-50.16 psf) Operating Force (in motion) N/A N/A Air Infiltration N/A N/A Water Penetration Resistance Test Pressure N/A N/A Uniform Load Structural Test Pressure 3240Pa (67.71 psf) 3600Pa (75.24 psf) Forced Entry Resistance N/A N/A
Test Completion Date: 10/07/08
Reference must be made to Report No. 86433.04-501-44, dated 07/27/10 for complete test specimen description and data.
Archi tectural Testi ng
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT
Rendered to:
IDEAL WINDOW MANUFACTURING 100 West 7th Street, P.O. Box 48 Bayonne, New J ersey 07002-0048
Project Summary: Architectural Testing, Inc. was contracted by Chelsea Building Products to perform testing on four Series/Model 700/730, PVC horizontal sliding windows at the ATI test facility in located Springdale, Pennsylvania. The samples tested successfully met the performance requirements for the following ratings: Test Specimen #1: HS-LC25 1803 x 1422 (71 x 56); Test Specimen #2: HS-LC30 1803 x 1422 (71 x 56); Test Specimen #3: HS-LC40 1600 x 1118* (63 x 44*); and Test Specimen #4: HS-LC40 1600 x 1118* (63 x 44*). This report is a reissue of the original Report No. 86433.04-501-44. This report is reissued in the name of through written authorization of Chelsea Building Products. Test specimen description and results are reported herein. The samples were provided by the client.
General Note: An asterisk (*) next to the size designation indicates that the size tested for optional performance was smaller than the Gateway test size for the product type and class.
Test Specification: The test specimens were evaluated in accordance with AAMA/WDMA/CSA 101/I.S.2/A440-05, Standard/Specification for Windows, Doors, and Unit Skylights.
Test Specimen Description:
Series/Model: Rep/NC Professional PerfectFit 1 & 2 Lifescapes Majestic XX Slider
Product Type: Poly Vinyl Chloride (PVC) Horizontal Sliding Window, Type XX
Archi tectural Testi ng
86433.01-501-44 Page 2 of 10
Test Specimen Description: (Continued)
Test Specimen #1: HS-LC25 1803 x 1422 (71 x 56)
Overall Size: 1803 mm (71") wide by 1422 mm (56") high
Sash Size (2): 883 mm (34-3/4") wide by 1327 mm (52-1/4") high
Screen Size: 854 mm (33-5/8") wide by 1314 mm (51-3/8") high
Overall Area: 2.6 m 2 (27.6 ft 2 )
Glazing Type: The unit was exterior glazed with nominal 7/8" thick sealed insulating glass fabricated from two sheets of 1/8" thick clear annealed glass separated by a rectangular-shaped aluminum spacer system, single sealed.
Test Specimen #2: HS-LC30 1803 x 1422 (71 x 56)
Overall Size: 1803 mm (71") wide by 1422 mm (56") high
Sash Size (2): 883 mm (34-3/4") wide by 1327 mm (52-1/4") high
Overall Area: 2.6 m 2 (27.6 ft 2 )
Glazing Type: The unit was exterior glazed with nominal 7/8" thick sealed insulating glass fabricated from two sheets of 1/8" thick clear annealed glass separated by a rectangular-shaped aluminum spacer system, single sealed.
Test Specimen #3: HS-LC40 1600 x 1118* (63 x 44*)
Overall Size: 1600 mm (63") wide by 1118 mm (44") high
Sash Size (2): 781 mm (30-3/4") wide by 1022 mm (40-1/4") high
Overall Area: 1.8 m 2 (19.3 ft 2 )
Glazing Type: The unit was exterior glazed with nominal 7/8" thick sealed insulating glass fabricated from two sheets of 3/32" thick clear annealed glass separated by a "U" shaped steel spacer system, single sealed.
Archi tectural Testi ng
86433.01-501-44 Page 3 of 10
Test Specimen Description: (Continued)
Test Specimen #4: HS-LC40 1600 x 1118* (63 x 44*)
Overall Size: 1600 mm (63") wide by 1118 mm (44") high
Sash Size (2): 781 mm (30-3/4") wide by 1022 mm (40-1/4") high
Overall Area: 1.8 m 2 (19.3 ft 2 )
Glazing Type: The unit was exterior glazed with nominal 7/8" thick sealed insulating glass fabricated from two sheets of 3/32" thick clear annealed glass separated by a "U" shaped steel spacer system, single sealed.
The following descriptions apply to all specimens.
Finish: All finish was white.
Frame Construction: The extruded PVC frame was of mitered and welded corner construction. Snap-in rigid PVC roller tracks were located at the sill.
Sash Construction: The extruded PVC sashes were of mitered and welded corner construction.
Weatherstripping:
Description Quantity Location
0.187" backed by 0.220" 2 Rows All rails, jamb stiles high center fin pile
0.187" backed by 0.350" 1 Row Lock stile, exterior meeting stile high center
Glazing Details: The insulating glass was set against a double-sided adhesive tape and secured with rigid vinyl glazing beads.
Archi tectural Testi ng
86433.01-501-44 Page 4 of 10
Test Specimen Description: (Continued)
Drainage:
Description Quantity Location
1-1/4" wide by 1/4" high 2 Exterior sill face, weepslot with flap one at each end
1" wide by 1/4" high 2 Sill intermediate wall, weepslot one at each end
3/16" by 1/8" deep 4 Bottom rail (thru two walls), weep hole one at each end
1" wide by 3/16" deep 4 Interior and exterior sill tracks, weepslot one at each end
Hardware:
Description Quantity Location
Metal cam lock 2 Lock stile, one 7" in from each end with mating keeper
Dual metal roller assembly 4 Bottom rails, one on each end
Reinforcement: The lock stile and the exterior meeting stile contained a hollow, custom- shaped extruded aluminum, reference Drawing No. 746.
Screen Construction: The screen frame was constructed from extruded aluminum. The corners were square-cut and fixed with plastic corner keys. The fabric mesh was held-in- place with a flexible vinyl spline.
Installation (Specimen No. 1 and No. 3): The units were installed in wood bucks constructed from Spruce-Pine-Fir construction lumber and secured through the nail fin with #6 x 1-1/4" long screws, spaced approximately 8" on center and beginning 2" in from each end. The nail fin perimeter was sealed to the wood buck with a silicone sealant. A nominal 3/16" gap was maintained at the perimeter between the test frame and wood buck.
Archi tectural Testi ng
86433.01-501-44 Page 5 of 10
Test Specimen Description: (Continued)
Installation (Specimen No. 2 and No. 4): The units were installed in wood bucks constructed from Spruce-Pine-Fir construction lumber and secured through the frame with five #8 x 1-1/2" long pan head screws, one at mid-span of the head, and one 6" in from each end of each jamb. The exterior frame perimeter was sealed to the wood buck with a silicone sealant. A nominal 3/16" gap was maintained at the perimeter between the test frame and wood buck.
Test Results: The temperature during testing was 22.2 C (72 F). The results are tabulated as follows:
Paragraph Title of Test - Test Method Results Allowed
Test Specimen #1: HS-LC25 1803 x 1422 (71 x 56)
5.3.1 Operating Force per ASTM E 2068 Initiate motion 53 N (12 lbf) Report Only Maintain motion 36 N (8 lbf) 90 N (20 lbf) Latches N/A 100 N (22.5 lbf) Locks 22 N (5 lbf) 100 N (22.5 lbf)
5.3.2.1 Air Leakage Resistance per ASTM E 283 75 Pa (1.6 psf) 0.61 L/s/m 2 1.5 L/s/m 2
(0.12 cfm/ft 2 ) (0.3 cfm/ft 2 ) max.
Note #1: The tested specimen meets (or exceeds) the performance levels specified in AAMA/WDMA/CSA 101/I.S.2/A440-05 for air leakage resistance.
5.3.3.2 Water Penetration Resistance per ASTM E 547 See Note #2
Note #2: The client opted to start at a pressure higher than the minimum required. Those results are listed under "Optional Performance".
5.3.4.2 Uniform Load Deflection per ASTM E 330 (Deflections were taken on the exterior meeting stile) (Loads were held for 10 seconds) 1200 Pa (25.08 psf) (positive) 15.7 mm (0.62") See Note #3 1200 Pa (25.08 psf) (negative) 16.8 mm (0.66") See Note #3
Note #3: The deflections reported are not limited by AAMA/WDMA/CSA 101/I.S.2/A440-05 for this product designation. The deflection data is recorded in this report for special code compliance and information only.
Archi tectural Testi ng
86433.01-501-44 Page 6 of 10
Test Results: (Continued)
Paragraph Title of Test - Test Method Results Allowed
Test Specimen #1: HS-LC25 1803 x 1422 (71 x 56) (Continued)
5.3.4.3 Uniform Load Structural per ASTM E 330 (Permanent sets were taken on the exterior meeting stile) (Loads were held for 10 seconds) 1800 Pa (37.62 psf) (positive) 1.0 mm (0.04") 5.3 mm (0.21") max. 1800 Pa (37.62 psf) (negative) 1.8 mm (0.07") 5.3 mm (0.21") max.
5.3.5 Forced Entry Resistance per ASTM F 588 Type: Grade: 10
Disassembly Test No entry No entry Tests A1 through A7 No entry No entry Sash/Panel Manipulation Test No entry No entry Lock Hardware Manipulation Test No entry No entry
5.3.6.2 Thermoplastic Corner Weld Test Meets as stated Meets as stated
5.3.6.3 Deglazing Test In operating direction - 320 N (72 lbf)
Interior sash / pull stile 1.5 mm (0.06") 11.4 mm (0.45") Interior sash / lock stile 2.0 mm (0.08") 11.4 mm (0.45") Exterior sash/ pull stile 2.8 mm (0.11") 11.4 mm (0.45") Exterior sash / keeper stile 2.5 mm (0.10") 11.4 mm (0.45")
In remaining direction - 230 N (52 lbf)
Interior sash / top rail 1.8 mm (0.07") 11.4 mm (0.45") Interior sash / bottom rail 2.3 mm (0.09") 11.4 mm (0.45") Exterior sash / top rail 2.3 mm (0.09") 11.4 mm (0.45") Exterior sash / bottom rail 1.8 mm (0.07") 11.4 mm (0.45")
Optional Performance
4.4.2.6 Water Penetration Resistance per ASTM E 547 (with and without insect screen) 290 Pa (6.06 psf) No leakage No leakage
Archi tectural Testi ng
86433.01-501-44 Page 7 of 10
Test Results: (Continued)
Paragraph Title of Test - Test Method Results Allowed
Test Specimen #2: HS-LC30 1803 x 1422 (71 x 56)
Optional Performance
4.4.2.6 Uniform Load Deflection per ASTM E 330 (Deflections were taken on the exterior meeting stile) (Loads were held for 10 seconds) 1440 Pa (30.09 psf) (positive) 19.3 mm (0.76") See Note #3 1440 Pa (30.09 psf) (negative) 19.8 mm (0.78") See Note #3
4.4.2.6 Uniform Load Structural per ASTM E 330 (Permanent sets were taken on the exterior meeting stile) (Loads were held for 10 seconds) 2160 Pa (45.14 psf) (positive) 1.5 mm (0.06") 5.3 mm (0.21") max. 2160 Pa (45.14 psf) (negative) 1.3 mm (0.05") 5.3 mm (0.21") max.
Test Specimen #3: HS-LC40 1600 x 1118* (63 x 44*)
Optional Performance
4.4.2.6 Uniform Load Deflection per ASTM E 330 (Deflections were taken on the exterior meeting stile) (Loads were held for 10 seconds) 1920 Pa (40.13 psf) (positive) 7.6 mm (0.30") See Note #3 1920 Pa (40.13 psf) (negative) 7.9 mm (0.31") See Note #3
4.4.2.6 Uniform Load Structural per ASTM E 330 (Permanent sets were taken on the exterior meeting stile) (Loads were held for 10 seconds) 3240 Pa (67.71 psf) (positive) 1.5 mm (0.06") 4.1 mm (0.16") max. 3240 Pa (67.71 psf) (negative) 1.3 mm (0.05") 4.1 mm (0.16") max.
Archi tectural Testi ng
86433.01-501-44 Page 8 of 10
Test Results: (Continued)
Paragraph Title of Test - Test Method Results Allowed
Test Specimen #4: HS-LC40 1600 x 1118* (63 x 44*)
Optional Performance
4.4.2.6 Uniform Load Deflection per ASTM E 330 (Deflections were taken on the exterior meeting stile) (Loads were held for 10 seconds) 1920 Pa (40.13 psf) (positive) 7.6 mm (0.30") See Note #3 1920 Pa (40.13 psf) (negative) 7.9 mm (0.31") See Note #3
4.4.2.6 Uniform Load Structural per ASTM E 330 (Permanent sets were taken on the exterior meeting stile) (Loads were held for 10 seconds) 3600 Pa (75.24 psf) (positive) 0.5 mm (0.02") 4.1 mm (0.16") max. 3600 Pa (75.24 psf) (negative) 0.5 mm (0.02") 4.1 mm (0.16") max.
Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test.
Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein.
This report is reissued in the name of Ideal Window Manufacturing through written authorization of Chelsea Building Products to whom the original report was rendered. The original Chelsea Building Products Report No. is 86433.01-501-44.
Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire.
Results obtained are tested values and were secured by using the designated test methods. No conclusions of any kind regarding the adequacy or inadequacy of the glass in the test specimen can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc.
For ARCHITECTURAL TESTING, INC.
_________________________________________________ ____________________________________________________ J ames P. Grippo Lynn George Technician Director-Regional Operations
J PG:sld
Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Alteration Addendum (1) Appendix-B: Drawings : Complete drawings packet on file with Architectural Testing, Inc.
Archi tectural Testi ng
86433.01-501-44 Page 10 of 10
Revision Log
Rev. # Date Page(s) Revision(s) 0 07/27/10 N/A Original report issue Reissued Report No. 86433.01-501-44 in the name of Ideal Window Manufacturing.
This report produced from controlled document template ATI 00156, revised 12/01/07.
Archi tectural Testi ng
86433.04-501-44
Appendix A
Alteration Addendum
Note: No alterations were required.