Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
List of equipment not included in the following plant schedule:
- WC extract fan : twin fan at 2 m-/s plus grilles and ductwork.
- Distributed ventilation system across the floor plate including floor or ceiling mounted fans

Note:
- Cooling plant and heating plant are in abeyance: discussion on the level of natural ventilation / passivhaus design in discussion with the architect.
- Fire provisions are in abbeyance
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Heating Plantroom 7400 mm wide x 6000 mm deep x 3000 mm high (overall)

Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Plantroom
Reference Area Location Notes
Heating Plantroom 44 m Ground Floor -
Equipment
Reference Duty Selection
Sidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high,
100 kg, 100 kg
Enwamatic, TBC
www.enwamatic.com
Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacity
Venting: unvented
Arrangement: vertical
Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060
mm deep x 2050 mm high, 850 kg
IMI Rycroft semi storage vertical, model MX440V, 1760 litres/hr
http://www.rycroft.com/
HRS semi storage vertical, model Aquasave AS515, 2500 litres/hr
http://www.hrs.co.uk/
Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519
mm high, 56 kg
Armstrong in-line vertical pump, model Starline50-150
www.armstrongpumps.com
Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753
mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200
www.armstrongpumps.com
Calorifiers expansion vessels 2 No. expansion vessels
3350 litres system volume
3.00 bar g feed pressure
3.55 bar g final pressure
75C maximum system temperature
0% glycol
370 litres expansion volume
Generic expansion vessel, 500 litres, 581 kg
Rycroft expansion vessel, model EXP500V, 500 litres
http://www.rycroft.com/
Smedegaard expansion vessel, model Type 2 500, 500 litres
http://www.smedegaard.com/
MCC 200 Amp incomer, 8 starters
415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNS
http://www.abb.co.uk/
Eaton Moeller MCC, model Modan
http://www.moeller.net/en/index.jsp
Primary Heating circulating
pumps
1 No. duty / 1 No. standby @ 15.22 l/s, 250 kPa
Pump type: in-line vertical
Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564
mm high, 73 kg
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Pump arrangement: single
Pump fluid: water
Armstrong in-line vertical pump, model Starline50-200
www.armstrongpumps.com
Boilers 3 No. boilers @ 400 kW to meet 700 kW load
Minimum natural gas efficiencies:
- Maximum output: 90.0% (nett)
- Seasonal (UK): 86.0% (gross)
Minimum oil efficiencies:
- Maximum output: 90.0% (nett)
- Seasonal (UK): 84.0% (gross)
Boiler type: condensing
Fuel: natural gas
Generic condensing boiler, 410 kW, 1110 mm wide x 1755 mm
deep x 2095 mm high, 1342 kg
Hoval condensing boiler, model UltraGas450, 410 kW
http://www.hoval.co.uk/
Boiler shunt pumps 1 No. duty per boiler @ 8.7 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519
mm high, 56 kg
Armstrong in-line vertical pump, model Starline50-150
www.armstrongpumps.com
Heating pressurisation
unit(upper floors)
1 No. pressurisation unit
9000 litres system volume
8.0 bar g maximum working pressure
1.6 bar g maximum system pressure
60C maximum system temperature
0% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1170 mm wide x 800 mm deep
x 1660 mm high, 802 kg
Hoval standard pressurisation unit, model PressVal Micron SM600,
600 litres
http://www.hoval.co.uk/
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Boilers vents Vent type: Natural high level, natural low level
High level vents to provide 0.27 m/s ventilation air exhaust
Low level vents to provide 0.52 m/s combustion and ventilation air
intake
(Based on BS6644, BS5410-2 and manufacturer recommendations)
2 No. generic vents at high level, 800 mm wide x 200 mm high, 50
% free area
2 No. generic vents at low level, 800 mm wide x 400 mm high, 50 %
free area
Notes

Auditorium AHU 8200 mm wide x 3500 mm deep x 1700 mm high
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP

Plantroom
Reference Area Location Notes
Auditorium AHU 28 m Ground Floor -
Equipment
Reference Duty Selection
Basement AHU Air flow 1.2 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
Generic modular AHU, SFP 1.6 W/l/s (estimated), 7000 mm wide x
1404 mm deep x 1548 mm high, 1820 kg
Flakt Woods modular AHU, model EU22
http://www.flaktwoods.com/products/air-handling-units/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
- Access (short)
- Humidifier (steam)
- Fan (backward curved)
- Panel filter
- Access (short)
- Attenuator (600 mm)
- Connection
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Main AHU 11300 mm wide x 8500 mm deep x 5400 mm high
Plantroom
Reference Area Location Notes
Main AHU 96 m Ground Floor -
Equipment
Reference Duty Selection
Basement AHU Air flow 8.5 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x
2650 mm deep x 4100 mm high, 9630 kg
Flakt Woods modular AHU, model EU62
http://www.flaktwoods.com/products/air-handling-units/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
- Access (short)
- Humidifier (steam)
- Access (short)
- Fan (backward curved)
- Panel filter
- Attenuator (600 mm)
- Connection
Basement AHU Air flow 8.5 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x
2650 mm deep x 4100 mm high, 9630 kg
Flakt Woods modular AHU, model EU62
http://www.flaktwoods.com/products/air-handling-units/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
- Access (short)
- Humidifier (steam)
- Access (short)
- Fan (backward curved)
- Panel filter
- Attenuator (600 mm)
- Connection
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Sump Pump 2000 mm wide x 2000 mm deep x 1200 mm high (overall)

Plantroom
Reference Area Location Notes
Sump Pump 4 m Roof -
Equipment
Reference Duty Selection
Sump pump 1 No. @ 2 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446
mm high, 21 kg
Armstrong in-line vertical pump, model Starline32-120
www.armstrongpumps.com
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Rain Water Storage Plantroom 8000 mm wide x 4600 mm deep x 4000 mm high (overall)

Plantroom
Reference Area Location Notes
Rain Water Storage Plantroom 37 m Ground Floor -
Equipment
Reference Duty Selection
Rain water pre-treatment tank 1 No. water tanks @ 7,000 litres Generic water tank, 2000 mm wide x 2000 mm deep x 3000 mm
high
300 mm bund height requirement
Treated Rain Water booster 1 No. booster @ 2 l/s, 20 mwg
1 No. pump + standby
Generic cold water booster, 665 mm wide x 1034 mm deep x 1565
mm high, 270 kg
Grundfos cold water booster, model Multi E 1 CRE10
http://www.grundfos.com/
AquaTech Pressmain cold water booster, model Aquamatic BTE2
10
http://www.aquatechpressmain.co.uk/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Rain water booster pre-
treatment
1 No. booster @ 2 l/s, 20 mwg
2 No. pumps + standby
Generic cold water booster, 920 mm wide x 1034 mm deep x 1565
mm high, 310 kg
Grundfos cold water booster, model Multi E 2 CRE5
http://www.grundfos.com/
AquaTech Pressmain cold water booster, model Aquamatic BTE3 5
http://www.aquatechpressmain.co.uk/
Treated Rain water tank 1 No. water tanks @ 7,500 litres Generic water tank, 3000 mm wide x 2000 mm deep x 2000 mm
high
300 mm bund height requirement
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)

Plantroom
Reference Area Location Notes
HV Plantroom 35 m Ground Floor -
Equipment
Reference Duty Selection
RMU Rating 200 Amps
12000 V, TP&N, 50 Hz
Generic RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300
kg
ABB RMU, model SafeRing
http://www.abb.com/
Schneider RMU, model Ringmaster RN2
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
HV switchpanel 12000 V, TP&N, 50 Hz
Module type: withdrawable
Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300
mm high
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Modules:
- Incomer
- Bus section
- Feeder
Future expansion 25%
Note: For some manufacturers VTs are integral to other components
ABB HV switchpanel, model Unigear ZS1
http://www.abb.com/
Schneider HV switchpanel, model MCSet
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
Notes
...

Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)
lantroom
Reference Area Location Notes
LV Plantroom 21 m Ground Floor -
Equipment
Reference Duty Selection
LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)

Plantroom
Reference Area Location Notes
Life Safety LV Plantroom 21 m Ground Floor -
Equipment
Reference Duty Selection
LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)
Plantroom
Reference Area Location Notes
Gas Meter Plantroom 3 m Ground Floor -
Equipment
Reference Duty Selection
Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg,
100 kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall)

Plantroom
Reference Area Location Notes
Telecoms Plantroom 8 m Ground Floor -
Equipment
Reference Duty Selection
Copper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100
kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)

Plantroom
Reference Area Location Notes
Transformers Plantroom 22 m Ground Floor -
Equipment
Reference Duty Selection
Transformers supply duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 4.0
Insulation: none
(Air flow requirement based on transformers losses)
500 mm wide x 300 mm deep
No insulation
Transformers 1 No. @ 800 kVA
HV 12000 V, LV 415 V, TP&N, 50 Hz
Transformer type: dry
Derating factor: 1.25
Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deep
x 2400 mm high, 2870 kg
ABB dry transformer, model Cast resin 1000, 1000 kVA
http://www.abb.com/
Schneider dry transformer, model Cast Resin 1000, 1000 kVA
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
Transformers extract duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 4.0
Insulation: none
500 mm wide x 300 mm deep
No insulation
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
(Air flow requirement based on transformers losses)
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)

Plantroom
Reference Area Location Notes
Satellite 9 m Roof -
Equipment
Reference Duty Selection
SATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kg
SATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Computer AC Units 10100 mm wide x 2200 mm deep x 1200 mm high

Plantroom
Reference Area Location Notes
Computer AC Units 22 m Roof -
Equipment
Reference Duty Selection
Computer Room AC units 5 No. condensers @ 10 kW
Condenser type: vertical air flow
Mean condensing temperature: 50C
Ambient temperature: 35C
Noise: 70 dBA @ 10 m
Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mm
deep x 1076 mm high, 62 kg
Airedale vertical condenser, model CR12, 14 kW
http://www.airedale.com/
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)

Plantroom
Reference Area Location Notes
MER Room 25 m Ground Floor -
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100
kg, 100 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,
500 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,
500 kg
Electrical board 160 Amp incomer, 12 ways
Type: MCCB
415 V, TP&N, 50 Hz
Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mm
wide x 230 mm deep x 1605 mm high, 168 kg
Moeller mccb electrical board, model PB12-400, 12 way, 400 Amp
incomer
http://www.moeller.co.uk/
MEM mccb electrical board, model PBJG1240M, 12 way, 400 Amp
incomer
http://www.eaton.com/uk
UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100
kg
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)

Plantroom
Reference Area Location Notes
Security Room 20 m Ground Floor
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100
kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30
kg, 30 kg
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100
kg
Electrical board 100 Amp incomer, 12 ways Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Type: MCB
415 V, TP&N, 50 Hz
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30
kg, 30 kg

Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)

Plantroom
Reference Area Location Notes
AV Room 7 m Ground Floor
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100
kg
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP

BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)

Plantroom
Reference Area Location Notes
BEMS and Maintenance Room 9 m Ground Floor
Equipment
Reference Duty Selection
Desk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100
kg
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Sprinkler Tank 8800 mm wide x 7300 mm deep x 4000 mm high (overall)
Plantroom
Reference Area Location Notes
Sprinkler Tank 64 m Basement -
Equipment
Reference Duty Selection
Water tank 1 No. water tanks @ 70,000 litres Generic water tank, 6000 mm wide x 5000 mm deep x 3000 mm
high
Bunding requirement exceeds 1000 mm
Sprinkler Pump Set 1a 1 No. sprinkler pump set 1a(s) Sprinkler pump set 1a, 750 mm wide x 2200 mm deep x 1000 mm
high, 100 kg, 100 kg
TBC, TBC
TBC
Sprinkler Pump Set 2a 1 No. sprinkler pump set 2a(s) Sprinkler pump set 2a, 600 mm wide x 600 mm deep x 1000 mm
high, 100 kg, 100 kg
TBC, TBC
TBC
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
http://www.eaton.com/uk
MCC 200 Amp incomer, 5 starters
415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNS
http://www.abb.co.uk/
Eaton Moeller MCC, model Modan
http://www.moeller.net/en/index.jsp
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Chillers Plantroom 9600 mm wide x 8200 mm deep x 3200 mm high (overall)

Plantroom
Reference Area Location Notes
Chillers Plantroom 78 m Basement -
Equipment
Reference Duty Selection
Water cooled chillers 2 No. chillers @ 850 kW to meet 300 kW total load
Minimum EER (or CoP):
- 3.85 kW/kW <750 kW
- 4.65 kW/kW =>750 kW
Chiller types: scroll, screw, centrifugal
Chilled water: 12C on / 7C off
Condenser water: 30C on / 35C off
Generic water cooled chiller, 892 kW, 3924 mm wide x 1600 mm
deep x 2060 mm high, 6202 kg
Trane screw water cooled chiller, model RTHD C2-D5-E4, 892 kW
http://www.trane.com/
Carrier screw water cooled chiller, model 30HXC0260, 897 kW
http://www.carrieraircon.co.uk/
Cooling primary pumps 1 No. duty / 1 No. standby @ 11.96 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753
mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200
www.armstrongpumps.com
Heat rejection pumps 1 No. duty / 1 No. standby @ 17.43 l/s, 250 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622
mm high, 82 kg
Armstrong in-line vertical pump, model Starline100-150
www.armstrongpumps.com
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Heat rejection pressurisation
unit
1 No. pressurisation unit
2190 litres system volume
1.9 bar g maximum working pressure
1.6 bar g maximum system pressure
50C maximum system temperature
35% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1199 mm wide x 634 mm deep
x 1446 mm high, 347 kg
Hoval standard pressurisation unit, model PressVal Micron SM200,
200 litres
http://www.hoval.co.uk/
Mikrofill standard pressurisation unit, model Maxi N200, 200 litres
http://www.mikrofill.com/
MCC 200 Amp incomer, 6 starters
415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNS
http://www.abb.co.uk/
Eaton Moeller MCC, model Modan
http://www.moeller.net/en/index.jsp
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Cooling circulating pumps 1 No. duty / 1 No. standby @ 14.35 l/s, 250 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564
mm high, 73 kg
Armstrong in-line vertical pump, model Starline50-200
www.armstrongpumps.com
Cooling pressurisation unit 1 No. pressurisation unit
2700 litres system volume
1.9 bar g maximum working pressure
1.6 bar g maximum system pressure
40C maximum system temperature
0% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1077 mm wide x 600 mm deep
x 1095 mm high, 207 kg
Hoval standard pressurisation unit, model PressVal Micron SM80,
80 litres
http://www.hoval.co.uk/
Mikrofill standard pressurisation unit, model Maxi N80, 80 litres
http://www.mikrofill.com/
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)

Plantroom
Reference Area Location Notes
Generators Plantroom 38 m Basement -
Equipment
Reference Duty Selection
LV generators board 1 No. incomer
1 No. feeder
415 V, TP&N, 50 Hz
Access: front
Generic generators LV switchboard, 2650 mm wide x 655 mm deep
x 2429 mm high
GE Power Controls generators LV switchboard, model System 4
http://www.ge.com/
Eaton generators LV switchboard, model Bill Classic Form 4
http://www.eaton.com/
Minimum connection space above: 600 mm
Generators 1 No. generators @ 400 kVA
415 V, TP&N, 50 Hz
Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mm
deep x 2158 mm high, 3700 kg
Broadcrown diesel generator, model BCC 440-50 E2, 440 kVA,
Emissions compliance EU Stage 2
http://www.broadcrown.com/
FG Wilson diesel generator, model P350P4, 400 kVA, Emissions
compliance EU Stage 2
http://www.fgwilson.com/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Day tanks 1 No. day tanks @ 8 hours storage
Generator fuel tank capacity : 650 litres
Day tank capacity (nett): 38 litres
Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x
1250 mm high
Joseph Ash day tank, model D01, 1364 litres
http://www.jaenvirotanks.com/
Blake day tank, model TEBU FO 1000, 1000 litres
http://www.blakegroup.co.uk/
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Hybrid Coolers 13000 mm wide x 4400 mm deep x 2600 mm high

Plantroom
Reference Area Location Notes
Hybrid Coolers 58 m Roof To reject 500 kW of heat to roof
Equipment
Reference Duty Selection
Hybrid Cooler 1 1 No. hybrid cooler 1(s) Hybrid cooler 1, 5000 mm wide x 2400 mm deep x 2500 mm high,
100 kg, 100 kg
Hybrid Cooler 2 1 No. hybrid cooler 2(s) Hybrid cooler 2, 5000 mm wide x 2400 mm deep x 2500 mm high,
100 kg, 100 kg
Notes
...


Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Chillers Plantroom 9000 mm wide x 6100 mm deep x 3000 mm high (overall)

Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
Plantroom
Reference Area Location Notes
Chillers Plantroom 54 m Basement -
Equipment
Reference Duty Selection
Water cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total load
Minimum EER (or CoP):
- 3.85 kW/kW <750 kW
- 4.65 kW/kW =>750 kW
Chiller types: scroll, screw, centrifugal
Chilled water: 12C on / 7C off
Condenser water: 30C on / 35C off
Generic water cooled chiller, 244 kW, 3510 mm wide x 980 mm
deep x 1929 mm high, 2664 kg
Trane screw water cooled chiller, model RTWD70, 244 kW
http://www.trane.com/
Carrier screw water cooled chiller, model 30HXC080, 286 kW
http://www.carrieraircon.co.uk/
Cooling primary pumps 1 No. duty / 1 No. standby @ 15.95 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753
mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200
www.armstrongpumps.com
Heat rejection pumps 1 No. duty / 1 No. standby @ 23.92 l/s, 250 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622
mm high, 82 kg
Armstrong in-line vertical pump, model Starline100-150
www.armstrongpumps.com
Heat rejection pressurisation
unit
1 No. pressurisation unit
3000 litres system volume
1.9 bar g maximum working pressure
1.6 bar g maximum system pressure
50C maximum system temperature
35% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1199 mm wide x 634 mm deep
x 1480 mm high, 447 kg
Hoval standard pressurisation unit, model PressVal Micron SM300,
300 litres
http://www.hoval.co.uk/
Mikrofill standard pressurisation unit, model Maxi N250, 250 litres
http://www.mikrofill.com/
MCC 200 Amp incomer, 6 starters
415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNS
http://www.abb.co.uk/
Eaton Moeller MCC, model Modan
http://www.moeller.net/en/index.jsp
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
Chapman Bathurst Plantroom & Riser Schedule

Chapman BDSP
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Cooling circulating pumps 1 No. duty / 1 No. standby @ 19.14 l/s, 250 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622
mm high, 82 kg
Armstrong in-line vertical pump, model Starline100-150
www.armstrongpumps.com
Cooling pressurisation unit 1 No. pressurisation unit
3600 litres system volume
1.9 bar g maximum working pressure
1.6 bar g maximum system pressure
40C maximum system temperature
0% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1077 mm wide x 600 mm deep
x 1095 mm high, 231 kg
Hoval standard pressurisation unit, model PressVal Micron SM110,
110 litres
http://www.hoval.co.uk/
Mikrofill standard pressurisation unit, model Maxi N100, 100 litres
http://www.mikrofill.com/
Notes
...