Professional Documents
Culture Documents
TROUBLE SHOOTING
• 300 A and above should be EF/OC that means earth fault and overcurrent type relay to use.
• 200 A and under should be ZCT and ELR Zero sequence Current Transformer and Earth Leakage Relay
to use.
• 1.5 mm2 to 16 mm2 Phase cables should use N-full size and E-half size
• 25 mm2 and above should use N-half size and E-half size.
0 - 150A 25KA
0 - 100A 10KA
Page No. 1
ELECTRICAL HAND BOOK 2
TROUBLE SHOOTING
0 - 100A 22KA
400A 36KA
150A 25KA
Page No. 2
ELECTRICAL HAND BOOK 3
TROUBLE SHOOTING
Permanently connected
equipment not exceeding
10A
J Appliances rated at more Not applicable 50%connected 50%connected 50%connected
than 10A and socket-outlets load load load
for the connection thereof-
(i) Clothes dryers, water
heaters, self heating washing
machines, wash boilers
(ii) Fixed spaces heating , air Not applicable 75%connected 75%connected 75%connected
conditioning equipment, load load load
saunas
(iii) Spa and swimming pool Not applicable 75% of the largest spa plus 75% of the largest
heaters swimming pool, plus 25% of the remainder
K Lifts In accordance No assessment for purpose of calculation of maximum
with Clause demand. In accordance with Clause 2.6.3, Table 2.4,
2.6.3 Table 2.4 determination of size of submains.
L Motors In accordance In accordance with Clause 2.6.3, Table 2.4, column 2
with Clause
2.6.3 Table 2.4
column 2
M Appliances, including Connected Connected load 10A or less. No assessment for
socket-outlets other than Load 5A or purpose of maximum demand.
those set out in group A to L less: No
above. e.g. pottery kin, assessment for
welding machines, radio purpose of
transmitters, X-ray maximum
equipment and the like demand.
Over 5A by Connected load over 10A. by assessment of the
local authority inspecting Authority
permission
Footnotes to table 2.3
a.For multiphase connections, divide the number of living units by the number of supply phases, e.g. 16units
on a three phase supply, 16/3 = 6 units on the heaviest loaded phase (Column 4)
b.Where only a portion of the number of units in a multiple installation is equipped with permanently
connected or fixed appliances, such as electric cooking ranges or space heating equipment, the number of
appliances in each category is divided over the number of phases, and the maximum demand determined as
shown in Example 3 of Appendix G.
c.Lighting track systems shall be regarded as 2 points per meter of track.
d.This load group is not applicable to socket-outlets installed in Communal area but not connected for the
individual living units. Su /ch socket outlets should be included in load group B.
e.For purpose of determining maximum demand, multiple combination socket-outlets shall be regarded as the
same number of points as the number of integral socket-outlets in combination.
f.Where an installation contains 15A or 20A socket outlets covered by load group B(ii) or B(iii), the base
loading of load group B is increased by 10A or 15A respectively; if both 15A and 20A socket-outlets are
installed. The increased is 15A.
g.Where and installation includes an air-conditioning system for use in hot weather and a heating system for
use in cool weather, only that system which has the greater load shall be taken into account.
h.Flood lighting, swimming pool lighting and tennis court lighting and like
i.Instananeous water heaters including 'quick recovery' heaters having element ratings greater than 100W/L
j.Storage type water heaters, including 'quick recovery' heaters not referred to in footnotes.
k.Controlled loading is taken to include only loading to which supply is controlled by the supply Authority so
that it is available only for limited period of time. Where the full load current of the controlled load exceeds
the maximum demand calculated using all appropriate items of this Table, the full load current of the
controlled load together with group A(ii) and group H shall be taken as the maximum demand for the
installation.
l.In the calculation of the connected load, the following rating shall be assigned to lighting.
(i) Incandescent lamps 60W or the actual wattage of the lamp to be installed, whichever is
greater,
except that if the design of the lumanrie associated with the lampholder
permits only lamps of less than 60W to be inserted in any lampholder, the
connected load of that lampholder shall be the wattage of the highest rated
lamp which may be accommodated. For multi-lamp luminaries, the load
for each lampholder shall be assessed on the above basis.
(ii) Fluorescent and Full connected load, i.e. the actual current consumed by the lighting
other discharge arrangement having regard to auxiliary equipment such as ballast and
lamp capacitors.
(iii) Lighting Tracks 0.5A/m per phase of track or the actual connected load, whichever is
greater.
m. A socket outlet installed more than 2.3 m above a floor for the connection an appliance rated at not
more than 100W or a lumanrie may be included as a lighting point in load group A(i). An appliance
having not exceeding 100W, which is permanently connected or connected by means of a socket
outlet installed more than 2.3m above a floor, may be considered as a lighting point.
n. Each item of permanently connected equipment not exceeding 10A may be included in load
group B(i) as an additional point.
Page No. 3
ELECTRICAL HAND BOOK 4
TROUBLE SHOOTING
1 2 3
Load group Residential Institutions, Factories, shops, stores,
hotels, boarding houses, offices, business
hospital, accommodation premises
houses, motels
A. Lighting other than in load group F 75% connected load Full connected load
B.
(i) GPOs and socket outlets not exceeding 1000W for first socket outlet 1000W for first socket
10A other than those in B(ii) plus 400W for each additional outlet plus 750W for each
outlet. additional outlet
(ii) GPOs and socket outlets not exceeding 1000W for first socket outlet 1000W for first socket
10A in building or potions of buildings plus 100W for each additional outlet plus 100W for each
provided with permanently installed outlet. additional outlet.
heating or cooling equipment or both.
(iii) Socket outlets exceeding 10A Full current rating of highest Full current rating of
rated socket outlets plus 50% of highest rated socket
full current rating of remainder outlets plus 75% of full
load of remainder
C. Appliances for cooking, heating and Full current rating of highest Full current rating of
cooling, including instantaneous water rated appliance plus 50% of highest rated appliance
heaters, but not appliances included in full current rating of remainder plus 75% of full current
group D & J. rating of remainder
D. Motor other than in E and F below Full load of highest rated motor Full load of highest rated
plus 50% of full load of motor plus 75% of
remainder second highest rated
motor plus 50% of full
load of remainder
E. Lifts (i) Largest lift motor - 125% full load
(ii) Next largest lift motor - 75% full load
(iii) Remaining motors - 50% full load
For the purpose of this load group, the full load current of a
lift motor shall mean the current taken from the supply
when lifting maximum rated load at maximum rated speed.
F. Fuel dispensing units (i) Motors : First motor - full load
Second motor - 50% full load
Additional motor - 25% of full load
(ii) Lighting - full connected load
G. Swimming pools, spas, saunas, thermal (i) Continuous elements - full load in all cases
storage heaters including water heaters, (ii) Controlled elements (including controlled element
space heaters, and similar arrangements which may be connected to the supply at other than
controlled times by means of a change over switch or load
controlled systems): 66% of full load where the demand of
the rest of the installation as calculated is not less than that
of the controlled element.
Full load in all other cases
H. Welding machines In accordance with clause 2.6.4, takings into account power
factor correction.
J. X-ray equipment 50% of the full load of the largest X-ray unit, additional
units being ignored.
K. Other equipment not covered by load By assessment of the inspecting Authority
group above
a. In the calculation of connected load, the following ratings shall be assigned to lighting:
(i) Incandescent lamp - 60W or the actual wattage of the lamp to be installed, whichever is the
greater, except that if the design of the luminaries associated with the lampholder permits only lamps
of less than 60W to be inserted in any lamp holder, the connected load of lamp holder shall be the
wattage of the highest rated lamp which may be accommodated. For multi - lamp luminaries, the
load for each lampholder shall be assessed on the above basis.
(ii) Fluorescent lamp - Full connected load, i.e. the actual current consumed by the lighting
arrangement having regard to auxiliary equipment such as ballast and capacitors.
b. Load group B(ii) applies to building or portion of building incorporating permanently installed
heating and/or cooling equipment specifically provided to render unnessary to the use of general-
purpose outlets for portable electric space heating or cooling appliances. Whether heating or cooling
or both is deemed necessary to avoid the use of portable heating or cooling equipment will depend on
the location and climate involved.
c. Controlled loading is taken to include only loading to which supply is available for a limited
Period of time.
d. A socket outlet installed more than 2.3m above a floor for the connection of an appliance rated at
not more than 100W or a luminary may be included as a lighting point in load group A. An
appliance having a rating not exceeding 100W, which is permanently connected, connected by
means of a socket outlet installed more than 2.3 m above a floor may be considered as a lighting
point.
e. See clause 2.5 9(ii) , Clause 2.8.2 and clause 2.9.3 for where the maximum demand for
consumers main and submains, and final subcircuits respectively may be determined by limitation.
Page No. 4
ELECTRICAL HAND BOOK 5
TROUBLE SHOOTING
Page No. 5
ELECTRICAL HAND BOOK 6
TROUBLE SHOOTING
: for 230V is good in 230K-ohms or 0.23M-ohms
: for 400V is good in 0.4M-ohms
: for 11KV is good in 11M-ohms
Insulation oil condition testing.: Get the sample oil which can get transformer bottom oil drain hole
• Testing by Insulation oil tester
• Wash to Sphere in instrument by oil.
• After no more bubble in oil, line switch on.
• Put until 11KV & slowly increase.
• Wait a moment when every 5KV increase.
• Nothing happen until 40KV - it is good.
• If oil is not pure spark between two sphere & automatic trip.
• It must be stand 1min in 40KV.
• When testing 5 times- 4 times were in good, oil is good.
• Some type of oil can stand 45KV to 50KV.
(Reference by U Pe Thein )
Earth testing or Ground testing.
Transformer Troubleshooting
Sr.no. Symptom Trouble Cause Remedy
1 Temperature of oil 1a. Overload 1a. Poor powerfactor 1a. Decrease load and
cooled transformer and overload powerfactor
rise until serious correction
level.
1b. Not enough oil in 1b. Leak in oil tank 1b. Repair it, or oil
oil tank or not enough fill until
filling transformer core
is under oil level
1c. Oil viscosity 1c. Cannot transfer 1c. If it was
grade so high. heat, it is so hot insulation
until windings damage, drain off
burn and old oil and clean
insulation it. new oil
damage replaces it.
2 Temperature of air- 2a. Over load 2a. Poor powerfactor 2a. Decrease load and
cooled transformer and overload powerfactor
rises until serious correction
level.
2b. Not enough air 2b. Air circulating or 2b. Increase air
volume air blowing very circulating rate.
weak or block in or clean air pipe
air pipe
3. Temperature of 3a. Over load 3a. Poor powerfactor 3a. Decrease load and
water-cooled and overload powerfactor
transformer rises correction
until serious level.
3b. Not enough water 3b. Something like 3b. Water force
flow in pipe oil dirt block in applied, cleaning
pipe by soap clean to
oil and oil dirt,
coils are under oil
level.
3c. Oil dirt is stuck 3c. Transformer 3c. If oil dirt on pipes
on the cooling working in so less cannot remove,
pipes surface. temperature. disassemble the
Transformer temp cooling coils and
must not less than the coolest pipes
10deg C. to clean by
scratch method.
4. Explode sound in Neighbor wire layers Cooling coil surface of Test to transformer oil
transformer tank. of HV winding are in air cooled or oil if cannot get standard
short circuit. cooled transformer are level, check again and
in small holes or refill it.
leakage moisture go
inside, so transformer
temperature drop
under 10deg.C
Short circuit between Insulation drops or Replace to damage
HV winding and LV damage. coil.
winding. Switch on/off when
full load condition.
End part connection Change to damage
Page No. 6
ELECTRICAL HAND BOOK 7
TROUBLE SHOOTING
of wire insulation coils and end parts'
trouble insulation should be
Actually that part replaced by thicker
insulation is 5 times size.
better than inner
parts.
Core construction not Sends back to
so nice. manufacturer and
repair it.
Transformer coils are It will become short
placed in not correct circuit, so repair and
position. re fitting.
No lightning Repair to damage
protection, so when coils, replace new
lightning times the coils.
effect of lightning Every transformer has
surge make it. lightning protection,
the lightning
protection are series
with choke coil,
reactor etc.
When storm coming, Replace damages coil
short circuit in line to and put thicker
line and short to insulation to end parts
transformer. of wire.
LV winding ground to By lightning strike, Replace damages coil
core. hit line to line and and put thicker
insulation weakness. insulation to end parts
of wire.
Send back to
manufacturer and
repair it
Short circuit on Oil mixed with Repair to terminal
terminal board moisture. board and repaint by
varnish.
It should separate oil
and moisture by filter.
Short circuit in HV or Damage in bushing. Replace to bushing.
LV bushing.
Not equal load Parallel operation to It must be same
sharing different characteristic characteristic
two transformers. transformer to parallel
operation, otherwise
put in reactance
between two
transformers.
Damage LV winding HV side in ground, Open to ground and
when there are no then repair to LV
ground neutral. winding.
Ground connection to
LV and HV neutral.
HV side in ground Open to ground and
and LV neutral then repair to LV
connect to ground. winding.
Ground connection to
LV and HV neutral
Page No. 7
ELECTRICAL HAND BOOK 8
TROUBLE SHOOTING
winding.
A transformer bucking Its polarity opposite To check polarity to
or counter acts to among other, if it is get correct and then
other transformers. not repaired one or change polarity of
more transformers transformer which is
will be burned out. trouble.
8. Very less voltage Wrong ratio It is not correctly Raise up tapping
calculated connected to correct numbers to get until
ratio tapping. necessary voltage.
9. Very high voltage Wrong ratio Same symptom as Drop down tapping
calculated above numbers to get until
necessary voltage
Parallel connected to Change transformers
transformers which until same ratios to
were in different ratio get, if cannot adjust,
replace and use to
same ratio new
transformers
Page No. 8
ELECTRICAL HAND BOOK 9
TROUBLE SHOOTING
• What is your iron core size in your hand or thinking the core size by rule of thumb.
• Calculate iron core CSA from formulae A = X" x Y"
• Depends on the iron core CSA, find out the turns per volt form N=8/A, 10/A or 12/A
• For 220V stable standard system, 80V should be at least point of input voltage in supply (primary side in
autotransformer). So decide the turns of required voltage tapping.
• Also find out the turns/layer.
• Draw the terminal schematic drawing for auto-step-up transformer.
• Decide that manual, semi-auto, fully auto control system to use in control.
1. Taking data.
Page No. 9
ELECTRICAL HAND BOOK 10
TROUBLE SHOOTING
12. For motor equipped with thermal
protection and for motor rated more than 1 h.p.
a type number.
13. Service factor.
4. Rewinding
• Hand winding method.
• Form winding method.
• Skein winding method.
5. Winding Connection
• Series connection or parallel
connection.
• Splicing and taping.
Page No. 10
ALTERNATOR
Alternator
Stationary Field & Rotating Armature Stationary Armature & Rotating Field
Note 1. Short circuit by centrifugal force can be tested by DC resistance measurement. Measurement should be start from
standstill to various rpm .If it is suddenly change in resistance to know as it is in short circuit. Also same way measure in pole
by pole to know which is defective.
Note 2. It should be fix necessary stability plate in exciter's field magnet. That means an iron sheet, smaller csa than pole csa,
is put between pole and yoke as magnetic circuit. Thickness and area of iron sheet is rule of thumb. Exciter's field switch must
be close otherwise residual flux will be loss.
Note 3. Stability test : Measure short circuit full load stator current excitation. Also measure open circuit normal voltage
excitation. Summation of above two is full load, zero lagging power factor load excitation for required voltage.
Note 4. Governors should be same characteristic so it can get useful load sharing.
Alternators should have same voltage regulation .Main mechanical force supply to filed regulators can get same voltage curves
of exciter. It should be same voltage regulation. It should be same steps in voltage regulator.
CONTACTOR THEORY
Contactor Theory
1. Normal Using : Surface of the contactor roughness depends upon the ratio of interruption and closing number of times that
means closing at 5 times of rated current , interruption at 2million times of rated current and so many time interruption and
closing contactors.
It is very little chance to compare that deformation in edge of the contactor by wear and tear.
Until color of contactor change to dark blue color, it is no problem so can use continuously.
2. Closing/Interruption at Overcurrent : Surface of roughness and deformation of contactor can be come out when 2 times of
rated current. Edges of the contactor spread out . It can see that silver spot on the dark blue contactor surface, but it is no need to
do any maintenance.
3. Suddenly and So many times open and closing at Inrush Current: When it is motor inching time that means speed up and
little time running, is 5 times bigger than rated current, contactor are closed and/or open can cause following defects or
symptoms
3.1 wear and tear
3.2 dis-uniforming
3.3 Silver alloy melts and spread out
3.4 Silver melted liquid drop down in fixed contact
3.5 many wear tear at the top of the moving contact
3.6 it can see melted silver uniformly spread on the base plate of moving contact
3.7 Also it can see blue color silver sulfate, well known that silver brightness parts
3.8 crack lines on the contactor when it is open/close time so much.
Find out the basic trouble and maintain as so many times to get correctly.
4. Close/Open at Over rush current : Contactors are open/close at 10 times of rated current can get following defects or
symptoms.
4.1 it is rising that surface roughness.
4.2 All surface become brightly silver color.
4.3 It can see arcing amount.
It may be interrupted at harzard severe time like short circuit.
Find out the basic trouble/reason and remove it furthermore normal maintaining.
5. Un-completely Closing : There are following three reason of the contactors' nature.
5.1 Less voltage and incompletely closing
5.2 Under voltage supply and incompletely closing contact symptom
5.3 Wear and tear for contactor vibrating.
5.1 Less voltage and incompletely closing: It can get enough magnetic attractive force that 85% of rated voltage. But supply
side drops severely causes very low magnetic attractive force and happen that incompletely closing of contactor.
Also motor vibrating can get that loss voltage and contactor vibrated. So that contactor closes and opens so fast and contact
burnt by arcing heat.
Although supply voltage enough or complete , wire so long and/or under size(very small, very high resistance) can also be
incompletely closing.
It is bigger than 5 times of rated current when 3 phase induction motor direct starting time. If it is used very small size wire in
circuit, terminal voltage of magnetic coil may be lower than 85% of rated supply voltage. So it's voltage loss cause can not close
completely and can see contacts vibration.
Normally motor start to run slowly and smoothly, very short time current flow like that and then starting time finish and current
drop until normal rated current. In this way voltage becomes normal rated voltage and electro magnetic contactors are in enough
voltage and continue.
Sometime it may be combine effect that supply voltage drop and wire size so small.
5.2 Under voltage supply and incompletely closing contact symptom : Wear and tear at contact top part that means it is can
not move to top part until contactor are suppressed.
Wear and tear the whole surface.
Especially center area roughness is higher.
It can see specially un-uniforming.
Edge of the contacts becomes like flowers.
Sometime base plate of the contact burn by heat flow by contact.
Sometime it is change in color.
5.3 Wear and tear for contactor vibrating: A electro magnetic contactor performs together with auxiliary relay, plugging
relay, and thermostat. So if their vibrations effect to contactor vibration by voltage unstable. Until good condition of contactor is
unstable close and vibrate in very short period and then completely close.
It is bigger arcing in starting than stopping.
6. Contact Changing or Replacing: Normally it is assume that contact changing time by daily using times and number of days.
But it should not decide that normal performing facts.
It should decide contact changing time by wiping drop and amount of wear and tear.
Normally top part of contact wear and tear is small so that it must decide by wipe condition.
If something special using also consider that top part wearing.
7. Wipe : Moving of contact base starts to end. Until contact moving finished, base continuously moves therefore spring
pressure increase until base stop. The moving force can get from electro magnet.
When contact wear , wipe less and pressure drop.
Rated lowest level of wipe value is 0.3mm or 1mm or 1.5mm to 2mm etc.
Note: Arc shield should change new one when contact changing otherwise short circuit in normal condition.
If it rust on contact of electromagnet surface, clean by dry clothes . Don't scratch surface, otherwise it can be humming.
Normal rusting also does normal performance.
If it wants to stop long time, it is to coat little by low viscosity transformer oil to prevent rusting.
It is not stick dirt on electromagnet axis by blower. Otherwise it is humming by dirt on surface.
CONTACTORS TROUBLE SHOOTING
Sr.No Problem Relation Possible Case To Operate Remark
1. Contact not Coil very hot 1.1. Supply voltage Discuss with • Voltage drop so high by not only loa
close so low Electrical supply but also current.
department. • Power line very long or very small s
1.2. Unstable of wire.
supply voltage
CAPACITOR MOTOR
Rewinding
1. Taking data.
2. Stripping the winding
3. Insulating the slots.
4. Rewinding
5. Connects the winding.
6. Testing.
7. Braking and varnishing.
1. Fuse burn out test for shorted capacitor. 10A fuse across 115V, 60Hz power line .
2. Shorted by screwdriver.
3. Capacity test : Using ac voltmeter (||) & ac ammeter (series).
Capacity in uF = 159300 x Amperes / (Frequency x Volts)
4. Test for open : Using ammeter.
5. Test for shorts : Fuse burn out
Using test lamp in series
6. Test for Ground : Using test lamp.
7. Test for winding : * Grounds test
• Shorts test
• Opens test
• Reverse test.
• Permanent split capacitor motor expects the centrifugal switch will not be encountered.
Short Circuit : 1. Windings are very hardly pressed inside the slots and very hardly tightened until cover enamel damage.
2. Excessive heat by overload symptom : Smoke from windings and overcurrent in noload.
Testing Procedure : 1. Motor run in short time and find out that which winding is the hottest.
2. Use internal growler.
3. V drops test.
4. Measure field strength by iron strip.
5. Use ammeter
Reverse or Rotation : 1. The compass method.
2. The nail method.
1.7.5 Frozen bearing • Loose to shaft by blow touch and then rep
(little grease in bearing so bearing.
molten by bearing heat)
1.8. End plate 1.8.1 The bearing is out • If end plate does not fit, all screwed shoul
improperly of alignment. loosened and each one tightened a little a
mounted. 1.8.2 The rotor turned by and drawing the plate evenly and securely
hand difficulty or not stator. In assembling first screw on, adjac
at all. on not tightly first and step by step tight.
1.8.3 Using mallet
hammer or lead
hammer and listen
The sound solid.
1.9 Bent rotor 1.9.1 Rotor doesn't turn • Rotor is removed from stator and placed i
shaft. easily by hand. (see in page 45.)
2 Motor run slower 2.1 Short circuit in 2.1.1 To run at a lower • To find the short and after it is found.
than normal speed running winding. speed. • Insulate it if possible.
2.1.2 Humming or • If it cannot be insulated, rewind the coil o
growling noise
entire winding.
2.1.3 The pole contains
the short will usually
become excessive hot
and smokes.
2.1.4 To locate the
shorted pole by an
internal glower is
used.
2.1.5 Pole may be located
by merely feeling for
the hot coil.
2.2 Starting 2.2.1. Same symptom for • Replace new c.w switch.
winding shorted running • Place fiber washer as correct position.
remains in the winding.
circuit. 2.2.2. Take off starting
winding and run it, if
cw s/w ok and run
properly means
starting winding not
properly working.
2.2.3. Contact points
were welded or stuck.
2.2.4. Fiber washer is
not proper position
on the shaft.
2.3. Reversed 2.3.1 Incorrect polarity. • When the improper polarity is located, th
running winding 2.3.2 Growling noise. wire of the pole are disconnected, reverse
poles. 2.3.3 Each pole tested by reconnected.
compass or nail test.
2.4. Other incorrect 2.4.1 Induced current to • To connect all poles exactly as required by
stator connections. flow in the pole coils
overheated, smoke and
burn out.
2.5 Worn in 2.5.1 Noisy in operation. • Same as upper worn bearing case.
bearing 2.5.2 Sluggish in
rotation.
2.5.3 Rotor rubs against
the stator while
running.
2.5.4 Motor shaft moved
up and down test.
2.6 Loose rotor bars 2.6.1 The motor runs • Solder or welded to the end rings.
with reduced power. • Rotor with a die cast aluminum squirrel
2.6.2 Growling noise. • Cage does not have this defect.
2.6.3 Visual inspection.
2.6.4 Using armature
glower (or external
glower) flicker of the
series lamp indicates
open bar.
3 Motor runs hot 3.1 Shorted winding 3.1.1 Shorted pole will • Can be repaired and insulated the pole.
become excessive • The entire winding must be rewound.
hot.
3.1.2 Growling noise.
3.1.3 Testing shorts for
locate and short
circuit exists.
3.2 Grounded 3.2.1 Two or more ground • Re-insulating if possible.
winding is equal to short. • If impossible the grounded pole must be r
3.2.2 To run very hot. • If one point ground immediately repair is
3.2.3 Severe damage.
essential.
3.2.4 Use test lamp.
3.3 Short circuit 3.3.1 Will be burn out • The starting
between running the starting winding . winding is moved away from running winding
and starting • Winding and various places in the stator .
winding. 3.3.2 Use test lamp to shorted point is moved, the lamp will flic
starting winding terminal out.
and running winding • Use short point method to find the locatio
leads.
cannot use other method as take off startin
winding and find out.
• A strip of varnish cambric or Armo paper
between two windings.
3.4 Worn bearing. 3.4.1 Rotor touches to • Polish surface on it.
stator. • If rubbing against the stator, replacing the
3.4.2 Over heat when it bearing.
is just run.
3.4.3 Move rotor shaft
up and down.
3.5 Overload 3.5.1 Draw more than • The load should be reduced.
rated current . • Motor replaced with large one.
3.5.2 Procedure
excessive heat.
3.5.3 Ammeter test.
4. Motor runs noisily 4.1 Shored winding. |
that means unusual 4.2 Poles are |
amount of noise. connected | Produce magnetic hum Follow above methods.
improperly |
4.3 Loose rotor bar |
4.4 Worn bearing Allow the rotor to rub Follow above methods
against the stator.
4.5 Worn 4.5.1 Some parts of • Disassemble rotor and check centrifugal s
centrifugal switch centrifugal switch are not which you suspected.
separate in high speed, so • Repair the damage part.
it is touch to rotor and • If cannot repair replace by new one..
noise.
4.5.2 Loose member of
rotating part hit or rubs to
one part of motor.
4.6 Too much end Something plays more Put Fiber washer in require place of rotor shaf
play.. than 1/64" become noise.
4.7. Foreign It may be pieces of wire Disassemble motor and remove by pliers or sc
material in rotor. or insulation touch to driver carefully that its don't damage the wind
rotor and it makes noise.
POLYPHASE INDUCTION MOTOR
#Testing
Worn Bearings:
@ Cause :* Rotor will ride on the stator and cause noisy operation.
• If bearing are so worn rotor rest firmly on the stator and impossible to run.
Overload:
@ Check: * Remove the load or belt.
• Turn on the shaft by hand usually a broken past or dirty mechanism will prevent the shaft from moving freely.
• To connect the ammeter in series with each live wire ( snap-around-voltmeter and ohmmeter to test ). The current in
the nameplate is same as the reading. Excessive reading is one phase short.
• To test voltage, resistance and current.
Open Phase
@ Cause: * Motor will continue to run but have less power.
• Broken wire in-group of coil or a loose connection.
Frozen Bearing
@Cause: * Oil or Lubrication oil is not supplied or not sufficient.
• Expansion the bearing by heat and may weld to the shaft.
• Impossible to rotate.
@Remedy: * The shaft has to be turned down on a lathe to the new size and new bearing made.
• If ball bearing are used replace with new ones.
Defective Controller
@Cause: * The contacts on the controller do not make good contact.
• The motor will fail to start.
Grounded Windings
@Cause: * When motor is touched, it will produce shock.
• Grounds are more than one place, it is equal to short circuit and fuse will blow.
@Check: * Use by test lamp.
@Remedy: * Repair by rewinding.
• Replacing the defective coil.
Reverse Phase
@Cause: * To run more slowly than rated speed.
• Produce an electrical hum indicative of wrong connection.
@Remedy: * Check the connections and reconnect them according to plan.
AC MOTOR CONTROLLER
Sr.No. Trouble Possible Cause
1. Motor doesn't start when the 1.1.Open OL heater coil or poor connection.
main contact close. 1.2.Main contacts not making.
1.2.1. One or contacts wear sufficiently.
1.2.2. Dirty.
1.2.3. Gritty.
1.2.4. Burned.
1.3. Broken, Loose or dirty terminals connection.
1.4. Dirty or broken pigtail connection.
1.5. Open resistance unit or open autotransformer.
1.6. Obstruction on the magnet core, preventing the contacts from closing.
1.7. Mechanical trouble, mechanical interlocks, gummy pivots, poor spring tension s
on.
2. If the contact does not closed 2.1. Open holding coil ( Test by test lamp )
when the start button is 2.2. Dirty start button contacts or poor contact
pressed. 2.3. Open or dirty stop button contacts ( More than one station, check each station.
For forward-reverse station, interlocked, check all contacts )
2.4. Loose or open terminal connection.
2.5. Open OL relay contacts.
2.6. Low voltage.
2.7. Shorted coil.
2.8. Mechanical trouble.
3. The contacts open when start 3.1. Maintaining contacts that don't close completely or are dirty, pitted, or loosed.
button is released. 3.2. Wrong connection of station to the controller.
4. Fuse blow when start button is 4.1. Grounded contacts.
pressed. 4.2. Shorted coil.
4.3. Shorted contact.
5. The magnet coil is noisy in 5.1. Broken shaded pole causing chattering.
operation. 5.2. Dirty core face.
6. Magnet coil is burned or 6.1. Overvoltage.
shorted. 6.2. Excessive current due to a large magnetic gap caused by dirt, grit or mechanical
trouble.
6.3. Too frequent operation.
Testing
• Opens • Shorted resistance
• Shorts • Low voltage
• Grounds • High voltage
• Continuity • Excessive amperes.
• Shorted coils • Broken connection
• Open coils • Dirty connection
• Grounded coils • Loose connection
• Open resistance • Many other mal-functioning component may be tested with comparativ
case
Lightning Calculation
1. There are 2 types in lightning cable, Cu and Aluminum.
2. When roof is metal sheet , It should use Aluminum cable .
3. Lightning tape standard size is 25mm width x 3mm thickness.
4. Earthing should be normal earthing system, then standard amount of resistance is Re < 10Ω
5.
BI (Junction)
CSA Cables
Space factor =
CSA Conduit
e.g. What size of conduit is required for 4x2.5mm2 & 4x6mm2 PVC cables.
Power Distribution
IEE Definition Range of voltage
1. Extra Low Voltage (ELV)
0-50 VAC or 0-120VDC between conductor to earth.
2. Low Voltage (LV)
above ELV to 1KV AC(1500Vdc) between conductors or 600V AC (900Vdc) between
conductors & earth.
3. Extra high pressure : above 3KV
4. Variation : ± 6% for voltage.
± 1% for frequency.
Illumination Theory
Luminious Flux φ : Total emission of light within 1sec.
unit : 1 lumen = 1/60 watt .or. 0.00147 watt
Luminious Intensity I : I = φ/w where w= 4π radian
unit : candela (cd) .or. candle power ( cp)
Standard Candle : make by pure wax (ysm;za,mif;ppfppf)
7/8 in diameter
120 grains .or. 7.776 gm burning within 1 hr. time
Illumination ( E ) .or. ( P )
E = φ/A where φ = Flux in lumen on surface area.
A = Working surface
unit : lumen /ft2 => F.C .or. lumen/m2 => Lx (Lux) where 1 lux=0.093 F.C
Inverse Square Law Light Source
E ∝ I / r2 r
Working Surface
Maintenance Factor
Maintenance factor depends upon cleaning condition of lighting fixture.
This clearance depends upon amount of soiling(dust).
I. Slight soiling .or. soiling rate low shops, office & schools.
II. Normal soiling all other factories.
III. Heavy soiling .or. soiling rate high blast, furnace factories, smith, mine & some department of textile factories.
# Hospital
1. Ward & private room - 3 F.C or 32.26 lux
2. Waiting & receiving room - 7 F.C or 75.27 lux
3. Operating table - 300 F.C or 3225.8 lux
4. Operating room - 30 F.Cor 322.58 lux
5. Laboratories - 20 F.Cor 215.05 lux
# Industries
1. Assembling shop ( Rough work ) - 7 F.C or 75.27 lux
2. Assembling shop ( Ordinary work ) - 10 F.C or 107.5 lux
3. Assembling shop ( Medium work ) - 20 F.C or 215 lux
4. Assembling shop ( Small m/cs ) - 50 F.C or 537.6 lux
5. Assembling shop ( very small works) - 100 F.C or 1075.2 lux
# Glass work
1. Mix & Furnace room - 5 F.C or 53.7 lux
2. Glass Blowing m/c, Grinding, cutting / Glass to size, Silvering, Pressing - 10 F.C or 107.53 lux
3. Fine, Grinding, Beveling, Inspection, Etching & decorating - 20 F.C or 215 lux
4. Glass cutting, Fine inspection - 50 F.C or 537.6 lux
# Hotel
1. Lounge & Dining Room - 7 F.C or 75.27 lux
2. Writing Room - 7 F.C or 75.27 lux
3. General - 7 F.C or 75.27 lux
4. Tables / Kitchen - 7 F.C or 75.27 lux
5. Bedroom - 5 F.C or 53.76 lux
# Chemical works
1. Hard Furnace, Boiling Tanks, Stationary dries, Stationary or Gravity Crystallizing, Mechanical
Furnace, Generators & Still, Mech. Dryers, Evaporator, Filtration, Mech. Crystallizing, Bleaching- 7 F.C or 75.27 lux
2. Tanks for cooking, Extractors, Percolators, Nitrators, Electrolytic Cells - 10 F.C or 107.52 lux
# School
1. Day Classroom - 15 F.C or 161.29 lux
2. Drawing & Art - 20 F.C or 215 lux
3. Gymnasiums - 10 F.C or 107.52 lux
4. Laboratories - 15 F.C or 161.29 lux
5. Lecture / Theatre - 10 F.C or 107.52 lux
6. Manual Training - xxxxxxxxxxxxxxxxxxxxx
7. Sewing - 20 F.C or 215 lux
# Machine Shop & Fitting Shop
1. Ordinary bench & m/c work - 10 F.C or 107.52 lux
2. Rough bench & m/c work - 10 F.C or 107.52 lux
3. Medium bench & m/c work, ordinary automatic m/c, rough grinding m/c, Fine Buffing & Polishing - 20 F.C or 215 lux
4. Very Fine Bench & m/c works, Grinding (fine) - 100 F.C or 1075.2 lux
FLUORESCENT
LAMPS ( S.E.E.)
Lamp Type Watt Nominal
luminous flux Standard Fluorescent Lamp in Market
after 100 hrs
of burning in
Lux
White Warmwhite Daylight Warmwhite White
33 29 55
deluxe 32 deluxe 34
"TL" 4W 100
6W 230
8W 370
13W 710
20W 1080 1080 820 750 750
25W 1650 1650 1250 1130 1130
40W 2800 2800 2120 1880 2000
65W 4400 4400 3300 3000 3200
"TL" D 15W 550 580
30W 1350 1300
"TL" E 22W 750
32W 1600 1700 1220 1300
"TL" EM 40W 2250 2380 1660 1800
"TL" F 40W 2460
65W 4000
"TL" M 40W 2650 2650 1780 1900
65W 4400 4400 3000 3100
125W 7300
"TL" MF 40W 2460
65W 4000
"TL" S 20W 900 900 620
40W 2300 2300
Comparison of light sources ( Following figures are an approximate general guide only)
Efficacy Approx. Lamp Relative
Source (l/W) life hrs source cost
Incandescent 14 1000 60W Low
Coiled coil
Tubular fluorescent 65 7500 40W Medium
White
Mercury vapor (clear) 45 8000 250W Medium
Mercury vapor color-corrected 50 8000 250W Medium
MV Metal halide 75 8000 400W High
LP sodium 130 6000 100W High
HP sodium 95 8000 400W High
Tungsten halogen 28 2000 1000W Low
TROUBLESHOOTING FOR COMMON FAULTS IN LUMINAIRES
( Adapted from table supplied by GTE Australia )
Problem System Possible Case Corrective maintenance
Lamp fail to All Blown fuse or Replace or reset as necessary. Look for possibles short-circuit in wiring or
light open circuit -
breaker
Pre - heat Reset type starter Reset manual type. If automatic type, extinguish circuit or remove starter
not reset. approximately one minute, then re-energize circuit. If starter cuts out agai
further. ( See other possible case in this section. )
All Wrong lamps Check ballast label, replace with correct lamp. Whenever practical, it is ad
the power off before making a replacement.
All Poor contact • Adjust lamp to seat it properly. Some two-pin lamps have two pits or
between lamp and , which are aligned at right angle s to a line between the pins.
lampholder • A checks of the position of the pips will indicate whether or not the la
rotated into the socket correctly. In the conventional tombstone type o
or mark should line up with the center of the socket opening.
• Gently twist lamps with recessed double contactor bases to assure pro
• Thoroughly clean dirty sockets.
• If sockets are loose, adjust or replace them.
• Replace sockets which are corroded, broken, or show evidence of arci
• Check spacing and alignment of lampholder. If they are too far apart,
poor contact.
• Adjust them or replace the fixture.
Quick start . Lack of proper In a rapid start or quick start system, a lamp which has one or two blacke
Rapid start. cathode heat. be receiving adequate cathode heating. This may be caused by poor conta
problems within the ballast, by use of ballast which do not deliver minim
requirements, by improper wiring or low-line voltage . Each of these is d
following pages.
Various devices are available to test cathode heater voltage. Among these
mounted in lamp bases. These are go/no-go types of indicators which show
presence or absences of cathode heat, but which give no indication of qua
reason , they will not necessarily reveal insufficient heat. It is better to use
voltmeter with a lamp base attachment containing a resistor for a " dumm
the proper cathode current. With this type of indicator. cathode, heater vo
obtained from lamp manufacturers. They are also indicated on most tester
The insertion of a tester into a dirty or corroded socket often scrapes the c
enough to obtain a proper reading. Make sure that the contacts are in goo
that the lamp was sealed as well as the tester. If the tester shows improper
investigate further.
All Normal end of life Cathode coating is exhausted .
of lamps. This is characterized by dense end blackening, extending from the end of
the lamp wall for 5-8 cm . Lamps may flash for a short period of time or a
shimmer. Instant start lamps may swirl.
The ends of pre-heat lamp may flash on and off. If an arc strikes, it may b
by a shimmering effect during the short time it exists.
In some two-lamp circuits, particularly series sequence instant start and ra
circuits, a good lamp may burn at reduced brightness, in a glow state, pos
the cathodes. Also both lamps may be out when only one has failed. Chec
individually. Replace failed lamps promptly to avoid ballast damage cause
and overheating. If a good lamp is known to have burn at low brightness f
show indications of being near the end of life, it should also be replaced, s
have been significantly reduced because of cathode damage. With any typ
simplest procedure is usually to test lamps in an adjacent fixture which is
operating properly and then replace as necessary.
Pre-heat Welded starter This is usually indicated bay a lamp glowing at the ends, but not attempti
contacts or starter in an adjacent fixture known to be operating properly and replace i
shorted starter ends of the lamp have been glowing and it starts immediately upon remov
capacitor replace the starter.
Pre-heat Starter at end of Check the starter in an adjacent fixture known to be operating properly, o
life with one of the following: A new starter, a starter from a fixture operating
dummy starter can be made from an old starter simply by shorting the pin
inserted into the starter socket and removed when the lamp ends begin to
should be repeated three or four times if necessary. If the lamp has not be
does start on any one of these attempts, the troubles is in the previous star
A manual starter can be made by connecting a hand switch with 300mm o
series with the two posts in a starter base . It is used in the same manner
starter except that the switch is opened rather than the base being remove
Lamp fail to All Ballast not All ballasts must satisfactorily limit the flow of current in the lamp to a va
light delivering within reasonable limits of the lamp rating. In addition, pre-heat ballasts
minimum lamp sufficient pre-heat current and starting voltage; instant start ballast must p
requirements starting voltage and starting current; quick start and rapid start ballast m
sufficient voltage between lamp terminals, from lamp terminal to starting
currents for cathode heat. These values may be obtained from lamp suppl
To check, use suitable ammeters and voltmeters as directed in AS specific
ballast manufacturer's publications. Some simple tests can be made with
following the ballast manufacturer's recommendations.
Replace ballast. It is highly recommended that approved ballasts be used
possible.
Instant start High humidity or Remove , clean and replace the lamps, Use a mild soap solution rather tha
Trigger start accumulation of which can remove the lamp's silicone coating. If it is advertently removed
Rapid start dirt on lamps be wiped with a silicone cloth. It is advisable to let lamps air dry since wi
cloth may create static electricity which will attract dust.
If humid and dusty conditions prevail, it is advisable to enclose the lamps
All Extreme ambient Correct ambient, if particle. Otherwise, change to a ballast rated for exist
temperatures In conditions of extreme cold, although the lamps do light, their output m
(either hot or they appear to be unlighted.
cold)
All Voltage at fixture Measure with a suitable voltmeter. Correct, or change to a ballast rated fo
too low
Quick start . Inadequate Rapid start and quick start systems require metal starting aids in close pro
Rapid start starting aid lamp and running the length of the lamp. This metal must be at earth pot
the fixture reflector serves as the starting aid.
Provide suitable starting aid. Requirement can be obtained from the lamp
All Improper wiring Examine the wiring to see that it is in accordance with the diagrams on th
Ensure that active, neutral and earthing conductors are correctly connecte
connections to see they are secure. Occasionally, fixtures using the newer
are found with loose leads - leads which were not properly pushed into the
which are used for wire connections instead of lugs and screws. Leads wit
insulation removed has also been found. In some cases, one slot is used fo
although there are two spring clips inside the socket, both wires go under
result in a loose connection for one of them.
Check the socket arrangement. In some sockets wires from adjacent holes
be connected to opposite pins while in others they are connected in paralle
Make sure there are no short circuit such caused by leads contacting the fi
There should be nearly full line voltage between the active lead and the m
Measure voltage across the lamp from the lamp holder on one end to the l
other ( where only one connection at each end is live being sure to measur
ones). Use a voltmeter which has an input impedance of 100 ohms per vo
there is no voltage or extremely low voltage, measure at succeeding point
power line to determine the location of the problem.
In some installations, particularly those using instant starts lamps which r
circuit voltages, an interlocking type of socket is used for safety . With th
the primary ballast circuit is not completed unless a lamp is inserted in th
obtain readings of ballast output it is necessary to complete this circuit.
In a pre-heat system, with dummy starter installed, both ends of one lamp
not, or if in three or four attempts there is no effort to start when the dumm
there could be an open circuit.
If one end of each lamp glows, the wiring is crossed.
In each case, check the wiring and correct it in accordance with ballast la
All Leak in lamp Indicated by absence of fluorescent glow when lamp is exposed to a spark
lamp.
Pre-heat, Open circuit in Improper earthing, improper wiring, broken lampholder, or insufficient b
Quick start lamp electrodes which can cause excessively high voltage to be impressed across the catho
Rapid start this. Other causes are transportation damage, poor weld, broken coils and
leaks.
Test with continuity tester or by connecting adjacent lamp contacts in seri
resistance such as a 25-watt incandescent lamp on a 240V line .
Another method of inspecting the cathode is to use a simple shadowgraph
readily constructed by making a small hole in a square of cardboard or oth
material that is held in front of shielded filament lamp. The lamp to be ex
against the pinhole and a shadow of the cathode will be projected on the s
opposite the cardboard. By tuning the lamp slowly, the cathode, leads, etc
examined and any breaks, distortions, or missing cathodes will be easy to
lamp.
All Short circuit If one lamp is out and the other is operating at full brightness in a rapid s
within ballast sequence circuit, there is probably a shorted starting capacitor. This can b
checking continuity between the leads to the lamp that is out. If any tow l
ends show continuity, there is a short circuit. Replace the ballast.
All Ballast end of life when the insulation on the ballast windings fails, the ballast will no longe
requirements and has , therefore , reached the end of its life. Time and te
the life of the insulation. If the ballast is subject to high operating temper
temperatures over 90 deg C, its life will be substantially reduced. Genera
that each increase of 10 deg C above 90 deg C rating will halve ballast lif
Leaking compound , expect for a small amount at the lead holes, which is
or brittle insulation; and discoloration on the metal case are all indication
approaching or having reached end of life. The simple fact that a ballast s
a true indication that the ballast is functioning properly. Often many succ
appear t have short life in a given fixture before it is realized that the balla
the end of useful life.
Check with appropriate continuity testers, ammeters and voltmeters as de
manufacturers' publications. Replace the ballast.
Slow of erratic All Wrong lamp See appropriate section in "Lamps fail to light"
starting
All Poor contact See appropriate section in "Lamps fail to light"
between lamp and
lampholder
Quick start Lack of proper See appropriate section in "Lamps fail to light"
Rapid start cathode heat
Pre-heat Sluggish starter, Test starter in adjacent fixture known to be operating properly. Replace st
causing prolonged
flashing at each
start
All Ballast not See appropriate section in "Lamps fail to light"
delivering
minimum lamp
requirements
All High humidity or See appropriate section in "Lamps fail to light"
accumulation of
dirt on lamp
All Extreme ambient See appropriate section in "Lamps fail to light"
temperatures
(either hot or
cold)
All Voltage at Measure with suitable voltmeter. If fluctuating voltage is suspected, a reco
luminaries low or will be helpful. Correct supply.
fluctuating
Quick start Inadequate See appropriate section in "Lamps fail to light"
Rapid start starting aid
All Improper wiring See appropriate section in "Lamps fail to light"
New lamps fail All Wrong lamps See appropriate section in "Lamps fail to light"
within the first
few days of
operation
All Wrong ballast Verify that proper ballast is used for the fixture and for existing electrical
environmental conditions. Ballast must be a.c. or d.c., depending on supp
and must be of correct line voltage and frequency rating . If low temperatu
exist, a low temperature ballast should be used. Replace with appropriate
Pre-heat reset-type starter See appropriate section in "Lamps fail to light"
not reset
All Improper wiring See appropriate section in "Lamps fail to light"
All Leak in lamp: See appropriate section in "Lamps fail to light"
may develop so
slowly that lamp
will operate
satisfactory for a
short period of
time
Pre-heat Open circuit in See appropriate section in "Lamps fail to light"
Quick start lamp electrodes
Rapid start
All Short circuit See appropriate section in " Lamps fail to light" short circuit can occur wh
within ballast to operate at excessive current. To check , follow ballast manufacturers' s
procedures.
As a general rule, the following can be done: however, there are some exc
Place an ammeter in series with the lamp and if the meter reads more tha
rated lamp current, replace the ballast. For pre-heat and instant start syste
ammeter in series with the lamp, preferably between the lamp and the bal
lead which is at earth potential. For quick start and rapid start systems do
however, after the lamp is ignited remove the adjacent secondary lead to a
cathode heating current in the reading.
Short lamp life All Wrong lamps Although some lamps may operate for a period of time on the wrong type
will nearly always be serious disadvantages to such operation. For examp
milliampere (high-output) lamps will operate on 1500 milliampere ballast
substantial sacrifice in lamp and ballast life, lamp maintenance and efficie
Operating 1500 milliamperes(VHO) lamps on 800 milliampere ballast ca
effects reducing ballasts and possibly lamp life and efficiency.
All Normal failures Although rated life is usually many thousand hours, it is by definition the
which 50 percent of the lamps in a statistically large sample have failed. A
lamp will fail before this time and some after . One must expect a small p
comparatively early failures.
All Short burning Rated life of fluorescent lamps is based on an average burning period of th
cycle start. If the burning period per start is lengthened, the life of the lamp wil
the other hand, if the average burning periods decreased, lamp life will be
the operating schedule and the local economics. It is often found that turn
for the short period of time, to reduce the electrical consumption, actually
increase in installation operating costs because of the adverse effects on la
All Poor contact See appropriate section in "Lamps fail to light"
between lamp and
lampholder
Quick start Lack of proper See appropriate section in "Lamps fail to light"
Rapid start cathode heat
All Ballast not See appropriate section in "Lamps fail to light"
delivering
minimum lamp
requirements
All Voltage at fixture If the voltage delivered to a pre-heat to rapid start fluorescent luminaries
too high to too normal , light output will increase, but the lamp will frequently instant sta
low without proper cathode preconditioning, causing rapid deterioration of the
resulting in reduced lamp life. Occasionally with preheat circuits, this ins
be recognized. The lamps will start without preheating or will sometimes
then start normally, that is preheating the cathode and then striking the ar
its effects on the lamps, a high line voltage can cause the ballast to run at
high currents, thereby reducing its life. The high current will also decrea
maintained light output.
If the voltage at the luminary is low, light output will be reduced, lamp o
unstable, and starting can become slower, more strained or prolonged, w
to the cathodes and decreases lamp life.
In either case check line voltage at the luminaries with a standard voltme
voltmeter if fluctuating is suspected. Correctly supply as necessary or us
designed for the specific voltage being supplied. Consult ballast manufac
recommended practical limits.
All Wrong ballast See appropriate section in "New lamps fail to light within the first few da
Pre-heat Wrong starter Consult starter manufacturers' publication or package and replace with co
manual or automatic reset type is advisable for installations where a failed
replaced within one hour.
Pre-heat Sluggish starter See appropriate section in "Slow or erratic starting"
Pre-heat Premature The lead lamp in a two-lamp circuit is often prone to start before its catho
starting preheated. Since this characteristic cannot often be visually recognized, w
lamps have shorter life than the lag, it is advisable to use a starter designe
effect.
Series Lamp operating When one lamp in a two -lamp series sequence circuit has failed, the othe
sequence in the glow state reduced brightness, in a glow state. This may damage the cathode of the
reduce its life. Replace failed lamps promptly. If a lamp that has burned
exhibits signs of being near the end of life (see "Normal end of life of lam
idea to replace it at the same time the failed lamp is being replaced.
All Improper wiring See appropriate section in "Lamps fail to light"
All Open circuit in See appropriate section in "Lamps fail to light"
lamp electrodes
All Short circuit See appropriate section in "Lamps fail to light"
within ballast
Snaking All Impurities At the arc in a fluorescent lamp may swirl and twist within the lamp. Thi
blinking or in a new lamp and will disappear when the lamp has been operated a few
flickering and off a few times one half hour or more apart. Occasionally, this "sneak
in a lamp during normal operation. Turning the lamp off and on usually
not, replace the lamp. If other lamps in the same luminaries also swirl, in
All Normal Although this is not often a problem with the holding properties of today's
stroboscopic effect can be reduced by using the warm colors, which have the slowest rate of d
due to alternating operating on lead-lag circuit or by operating on three-phase power supplie
current
All Poor contact See appropriate section in "Lamps fail to light"
between lamp and
lampholder
All Normal end of life See appropriate section in "Lamps fail to light"
of lamps
All Low lamp wall Low lamp wall temperature caused by draughts from outside air, air-cond
temperature cause flickering or blinking. Protect or enclose the lamp.
All Wrong ballast If the ballast frequency rating is not the same as the line frequency, flicker
Replace with ballast of proper rating.
Pre-heat Wrong starter Remove the starter while the lamp is lighted. If the flashing stops, the sta
size, or is defective. Replace it.
Pre-heat Sluggish starter See appropriate section in "Slow or erratic starting"
Pre-heat Starter not cycling Characterized by rapid blinking of lamp ends. Test starter in adjacent circ
correctly to proper
preheats
electrodes.
All Ballast not See appropriate section in "Lamps fail to light"
delivering
minimum load
requirements
All Voltage at Measure with suitable voltmeter and correct. See appropriate section in "L
luminaries too light"
high or too low
All Improper wiring See appropriate section in "Lamps fail to light"
All Open circuit in See appropriate section in "Lamps fail to light"
lamp electrode
• PLC Maintenance
1. Periodically check the tightness of I/O module terminal screws. They can become loose over a period of time.
2. Periodically check the corrosion of connecting terminals. Moisture and corrosive atmospheres can cause poor electrical
connections. Internally end connectors of PCB also may become corroded.
3. Make sure that components are free of dust. Properly cooling the PLC through a layer of dust is impossible.
4. Stock commonly needed spare parts. Input and output modules are the PLC components that fail most often. Stocking is
especially essential there is no convenient manufacturer's service station and part depot. Maintaining proper levels of spare
parts inventory is a trade-off between costly inventory and prolonged downtime without parts.
5. Keep a duplicate record of operating programs being used. These records should be kept the plant location away from the
PLC operational area. Copies of long expensive programs should be kept off the premises to prevent their loss in case of
fire and theft.
6. Replace the PLC backup batteries more often than their usable life would indicate. The lithium batteries used for backup in
case of lost electrical service are usable for 3-5 years. However, many companies replace them on the yearly on a written
maintenance procedure. The cost of the batteries small price to pay to prevent the loss of lengthily PLC program.
7. Have a written checklist control sheet for each PLC. The sheet should have the dates on which the work is performed and
the dates for the next preventative maintenance due. The next due dates should be entered on a future worksheet listing to
make sure it is done on the date due.
8. Keep a log sheet on maintenance for each PLC in addition to the check-sheet. Records of what, who, and when should be
kept. This log is often combined with the troubleshooting log discussed in the previous section. The combined log sheet
gives a valuable history record and is a guide to buying future PLCs based on performance or nonperformance.
This is typical drawing for Forward Reverse motor control unit in United Cement Project (Singapore). There are 2-type control,
first direct electrical power control by local control selector switch and second automatic PLC computerize control by Siemen
(Germany) technology.
Typical Control Circuit Diagram
Above typical Drawing is Star Delta starter and automatic PLC computerizes control. unit in United Cement Project
(Singapore).There are 2-type control, first direct electrical power control by local control selector switch and second automatic
PLC computerize control by Simen(Germany) technology.
Above circuit is typical AutoTransformer starter circuit which is useful to control motor starting current by voltage transition,
and which is in two-type first open transition and second close transition.
ILLUMINATION DESIGN TABLE
Incandescent Room Utilization Factor New Conditions Mainte
Lamps Index nance
Factor
Type of fitting v% k rc 0.7 0.5 0.3 Clean Clean Clean
rw 0.5 0.3 0.1 0.5 0.3 0.1 0.5 0.3 0.1 Once once once
Direct 1 0.27 0.21 0.17 0.26 0.21 0.17 0.26 0.21 0.17 Yearly every every
1.2 0.32 0.26 0.21 0.31 0.25 0.21 0.3 0.25 0.21 2 Years 3 Years
1.5 0.38 0.32 0.27 0.37 0.32 0.27 0.36 0.31 0.27
2 0.46 0.4 0.36 0.45 0.4 0.36 0.44 0.39 0.36
0 2.5 0.51 0.46 0.42 0.5 0.46 0.42 0.49 0.45 0.42 Soiling
rate low
| 3 0.55 0.5 0.46 0.54 0.5 0.46 0.53 0.46 0.46
80 4 0.61 0.56 0.53 0.6 0.56 0.53 0.59 0.55 0.53 Soiling
rate
normal
| 5 0.64 0.6 0.57 0.63 0.6 0.57 0.62 0.6 0.57 1.35 1.55
80 6 0.67 0.63 0.61 0.66 0.63 0.6 0.65 0.62 0.6
8 0.7 0.67 0.65 0.69 0.67 0.65 0.68 0.66 0.65 Soiling
rate
high
10 0.72 0.7 0.68 0.71 0.69 0.67 0.71 0.69 0.67 1.65 2.15
Fitting at center of room
1 0.29 0.23 0.19 0.28 0.23 0.19 0.28 0.23 0.19
1.2 0.35 0.29 0.25 0.34 0.29 0.25 0.33 0.28 0.25
1.5 0.42 0.37 0.33 0.41 0.36 0.33 0.41 0.36 0.33
2 0.52 0.47 0.44 0.51 0.47 0.44 0.5 0.47 0.44
SEMI DIRECT 1 0.27 0.21 0.17 0.25 0.2 0.16 0.23 0.19 0.15
1.2 0.32 0.26 0.21 0.3 0.24 0.2 0.27 0.23 0.19
1.5 0.38 0.32 0.27 0.35 0.3 0.26 0.33 0.28 0.24
2 0.46 0.4 0.35 0.43 0.37 0.33 0.39 0.35 0.32
2.5 0.51 0.45 0.41 0.47 0.43 0.39 0.44 0.4 0.36 Soiling
rate for
low
20 3 0.55 0.5 0.45 0.51 0.47 0.43 0.47 0.44 0.4 1.25 1.4
| 4 0.6 0.56 0.52 0.56 0.52 0.49 0.52 0.49 0.46
88 5 0.64 0.6 0.56 0.6 0.56 0.53 0.56 0.53 0.5 Soiling
rate
normal
| 6 0.66 0.63 0.59 0.62 0.59 0.56 0.58 0.56 0.53 1.45 1.8
68 8 0.7 0.67 0.64 0.66 0.63 0.61 0.61 0.59 0.57 Soiling
rate
high
10 0.72 0.69 0.67 0.68 0.65 0.63 0.64 0.62 0.6
Fitting at Room Center
1 0.29 0.23 0.19 0.27 0.22 0.18 0.25 0.2 0.17
1.2 0.34 0.28 0.24 0.32 0.27 0.23 0.3 0.25 0.22
1.5 0.41 0.36 0.31 0.39 0.34 0.3 0.36 0.32 0.28
2 0.51 0.46 0.42 0.48 0.43 0.4 0.45 0.41 0.38
DIRECT 1 0.27 0.21 0.17 0.23 0.19 0.15 0.2 0.16 0.13
INDIRECT 1.2 0.31 0.25 0.21 0.27 0.22 0.19 0.23 0.19 0.17
1.5 0.37 0.31 0.27 0.32 0.27 0.24 0.8 0.24 0.21
2 0.44 0.39 0.35 0.39 0.34 0.31 0.33 0.3 0.27
2.5 0.49 0.44 0.4 0.43 0.39 0.36 0.32 0.34 0.31 Soiling
rate low
41 3 0.53 0.48 0.44 0.47 0.43 0.39 0.4 0.37 0.35 1.25 1.4
| 4 0.58 0.54 0.5 0.51 0.48 0.45 0.44 0.42 0.39
90 5 0.62 0.58 0.55 0.54 0.51 0.49 0.47 0.45 0.43 Soiling
rate
normal
| 6 0.64 0.61 0.58 0.56 0.54 0.51 0.49 0.47 0.45 1.45 1.8
49 8 0.67 0.64 0.62 0.59 0.57 0.55 0.52 0.5 0.49 Soiling
rate
high
10 0.69 0.67 0.65 0.61 0.59 0.58 0.53 0.52 0.51
DIRECT 1 0.29 0.24 0.2 0.29 0.23 0.2 0.28 0.23 0.2
Through fitting 1.2 0.35 0.29 0.25 0.34 0.28 0.25 0.33 0.28 0.24
with fluorescent 1.5 0.41 0.36 0.31 0.41 0.35 0.31 0.4 0.35 0.31
lamps 2 0.5 0.45 0.41 0.49 0.44 0.41 0.48 0.44 0.41
2.5 0.55 0.5 0.47 0.54 0.5 0.46 0.53 0.5 0.46 Soiling rate
low
0 3 0.59 0.55 0.51 0.58 0.54 0.51 0.58 0.54 0.51 X X X
| 4 0.65 0.61 0.58 0.64 0.6 0.56 0.65 0.6 0.57
82 5 0.68 0.65 0.62 0.67 0.64 0.62 0.66 0.64 0.62 Soiling rate
normal
| 6 0.7 0.67 0.65 0.69 0.67 0.65 0.69 0.67 0.65 1.4 1.7 1.9
82 8 0.73 0.71 0.69 0.72 0.71 0.69 0.7 0.7 0.69 Soiling rate
high
10 0.75 0.73 0.71 0.74 0.73 0.71 0.74 0.72 0.71 1.85 2.55 3.1
Fitting at Room Center
1 0.32 0.26 0.22 0.31 0.26 0.22 0.3 0.26 0.22
1.2 0.38 0.33 0.29 0.37 0.32 0.29 0.37 0.32 0.29
1.5 0.46 0.41 0.38 0.46 0.41 0.38 0.45 0.41 0.38
2 0.57 0.53 0.5 0.57 0.53 0.5 0.56 0.53 0.5
DIRECT 1 0.25 0.2 0.17 0.22 0.18 0.15 0.19 0.15 0.13
INIRECT 1.2 0.3 0.24 0.21 0.26 0.21 0.18 0.22 0.18 0.13
with louver 1.5 0.35 0.3 0.26 0.3 0.26 0.23 0.26 0.23 0.2
2 0.42 0.37 0.33 0.36 0.33 0.29 0.31 0.28 0.26
2.5 0.47 0.42 0.38 0.4 0.37 0.34 0.34 0.32 0.29 Soiling rate low
43 3 0.5 0.46 0.42 0.43 0.4 0.37 0.37 0.34 0.32 1.35 1.55 1.75
| 4 0.55 0.51 0.48 0.47 0.44 0.42 0.4 0.38 0.36 Soiling rate
normal
85 5 0.58 0.54 0.51 0.5 0.47 0.45 0.43 0.41 0.39 1.65 2.15 2.5
| 6 0.6 0.57 0.54 0.52 0.5 0.48 0.44 0.43 0.41 Soiling rate
high
42 8 0.62 0.6 0.58 0.54 0.53 0.51 0.47 0.45 0.44 X X X
10 0.64 0.68 0.6 0.56 0.54 0.53 0.48 0.47 0.46
Fitting at Room Center
1 0.27 0.22 0.18 0.23 0.19 0.16 0.2 0.17 0.14
1.2 0.31 0.26 0.23 0.27 0.23 0.2 0.24 0.2 0.18
1.5 0.38 0.33 0.29 0.33 0.29 0.26 0.28 0.25 0.23
2 0.45 0.41 0.37 0.4 0.38 0.34 0.34 0.32 0.3
SEMI- 1 0.24 0.19 0.15 0.2 0.16 0.13 0.16 0.13 0.11
INDIRECT 1.2 0.28 0.23 0.19 0.23 0.19 0.16 0.19 0.16 0.13
with louver 1.5 0.33 0.28 0.24 0.28 0.23 0.2 0.22 0.19 0.17
2 0.4 0.35 0.31 0.33 0.29 0.26 0.27 0.24 0.22
2.5 0.44 0.39 0.35 0.37 0.33 0.3 0.3 0.27 0.25 Soiling rate
low
51 3 0.47 0.43 0.39 0.4 0.36 0.33 0.32 0.3 0.8 1.4 1.65 1.85
| 4 0.52 0.48 0.45 0.44 0.41 0.38 0.36 0.33 0.31 Soiling
rate normal
85 5 0.55 0.51 0.48 0.46 0.44 0.41 0.38 0.36 0.34 1.7 2.25 2.65
| 6 0.57 0.54 0.51 0.48 0.46 0.44 0.39 0.38 0.36 Soiling
rate high
34 8 0.6 0.57 0.55 0.51 0.49 0.47 0.41 0.4 0.39 X X X
10 0.62 0.59 0.57 0.52 0.51 0.49 0.43 0.42 0.41
Fitting at Room Center
1 0.25 0.2 0.16 0.21 0.17 0.14 0.17 0.14 0.12
1.2 0.29 0.24 0.2 0.25 0.21 0.18 0.2 0.17 0.15
1.5 0.35 0.3 0.26 0.29 0.25 0.23 0.24 0.21 0.19
2 0.42 0.37 0.34 0.35 0.32 0.29 0.29 0.27 0.25
INDIRECT 1 0.12 0.1 0.08 0.08 0.06 0.05 0.04 0.04 0.03
Recess with 1.2 0.14 0.11 0.09 0.09 0.07 0.06 0.05 0.04 0.04
Fluorescent lamps 1.5 0.17 0.13 0.12 0.11 0.09 0.08 0.06 0.05 0.04
2 0.2 0.17 0.15 0.13 0.11 0.1 0.07 0.06 0.06
2.5 0.21 0.2 0.17 0.14 0.13 0.12 0.08 0.07 0.07 Soiling rate
low
70 3 0.23 0.21 0.18 0.15 0.14 0.12 0.08 0.08 0.07 1.25 1.45 X
| 4 0.25 0.23 0.21 0.17 0.15 0.14 0.09 0.09 0.08 Soiling rate
normal
70 5 0.27 0.25 0.23 0.18 0.16 0.15 0.1 0.09 0.09 X X X
| 6 0.28 0.26 0.24 0.18 0.17 0.16 0.1 0.1 0.09 Soiling rate
normal
0 8 0.29 0.27 0.25 0.19 0.18 0.17 0.11 0.1 0.1 X X X
10 0.31 0.28 0.27 0.2 0.19 0.18 0.11 0.11 0.1
SELECTION OF MOTOR STARTER & FUSE FREE BREAKER
340 250 823 K600N-EP3 TR20- 2.5-5.0 K400N-EP K600N-EP 800 N/A U-1200 1200 325
1E_with_C
T100N