As asked for comments on NP-8, M/s Avana Electrosystems Pvt.
Ltd Bangalore may
please be asked to submit following test reports (in addition to the submitted tests) for different types of relays, detail are as under:- (A) For Numerical O/C & E /F relay
High Frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode.
High Frequency (1 MHz) disturbance test (IEC 60255-22-1), differential mode .
Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, class III), air discharge.
Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, class III), contact discharge
RF electromagnetic field test (IEC 61000-4-3 and ENV 50140)
Conducted RF disturbance test (IEC 61000-4-6 and ENV 50141).
Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), common mode.
Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), differential mode.
Conducted and radiated RF emission test (IEC 60255-25, Class A EN55011-CISPRII), conducted and radiated emission (main)
Power frequency magnetic field immunity test (IEC 61000-4-8), continuous 100 A/m.
Power frequency magnetic field immunity test (IEC 61000-4-8), Short duration 300 A/m.
Power Supply Test (IEC 60255 - 11, IEC 61000-4-11)
Seismic test ( ANSI/IEEE C37.98-1987), operating basis earthquake test 0.55.25 g
Seismic test ( ANSI/IEEE C37.98-1987 ), safe shut down earthquake test 0.57.5 g
Shock response and endurance test ( IEC 60255-21-2 ) Class 1, 11ms
Degree of protection by enclosure, IP test (IEC 60529) IP 54 (B) For Numerical sensitive E/F & REF relay Dry heat test (IEC 60068-2-2) Dry cold test (IEC 60068-2-1) Damp heat test(IEC 60068-2-30) MHz burst disturbance test, class III for Common mode & Differential mode(IEC 610004-4-18, IEC 60255-22-1). Electrostatic discharge test for Contact discharge & Air discharge(IEC 61000-4-2, IEC 60255-22-2) Fast transient disturbance tests(IEC 61000-4-4, IEC 60255-22-4) Radio frequency interference tests(IEC 61000-4-6,IEC 60255-22-6, class III, IEC 61000-4-3, IEC 60255-22-3, class III, ENV 50204, IEC 60255-22-3, class III, IEEE C37.90.2-2004) Surge immunity test for Communication & Other ports(IEC 61000-4-5, IEC 60255-22-5) Power frequency (50 Hz) magnetic field for Continuous & 1-3 s (IEC 61000-4-8) Voltage dips and short interruptions 30%/10 ms (According to IEC 61000- 4-11) Power frequency immunity test for Common mode & Differential mode(IEC 61000-4-16 IEC 60255-22-7, class A) Emission tests for Conducted & Radiated(EN 55011, class A, IEC 60255-25) Impulse voltage test (IEC 60255-5 and IEC 60255-27) Vibration tests (sinusoidal- IEC 60068-2-6 (test Fc) IEC 60255-21-1) Shock and bump test (IEC 60068-2-27 (test Ea shock) IEC 60068-2-29 (test Eb bump) IEC 60255-21-2) Mechanical durability(IEEE C37.90-2005, IEC 602556-6) (C ) Electromechanical Master trip & Auxiliary relay. AUXILIARY RELAY Impulse voltage test 5kV,1.2/50s. 0.5J., as per IEC 60255-5 Dry heat test (IEC 68000-2-2) Dry cold test (IEC 68000-2-1) Damp heat cyclic test (IEC 68000-2-30) Storage test Vibrations test (IEC 255-21-1) Vibration response Test Endurance test Shock and Bump test (flush mounting case)( IEC 255-22-2) Shock response test Shock withstand test Bump test TRIP RELAY Temperature-rise(IEC 60255-6) Insulation resistance(IEC 60255-5) Dielectric Test (IEC 60255-5) Impulse voltage test (IEC 60255-5) 1 MHz burst disturbance Class III for common mode 2.5 kV, 1 MHz, 400 pls/s & differential mode((IEC 60255-22-1) Electro-static discharge test acc. Class III for contact discharge 6 kV, 150 pF/330 ohm & air discharge((IEC 60255-22-2) Fast transient disturbance test Class IV for common mode((IEC 60255-22-4) Surge immunity test acc. Class III for common mode 2 kV, 1.2/50 s, Rs = 10 ohm & differential mode((IEC 60255-22-5) Vibration response and endurance test (IEC 60255-21-1) Shock response and endurance (IEC 60255-22-2 ) Dry heat (IEC 60068-2-2) Dry cold (IEC 60068-2-1) Damp heat cyclic test (IEC 60068-2-30) The firm may also be asked to certify that they have conducted all type tests and routine/ acceptance tests which are mandatory as per IS/IEC standards.