You are on page 1of 2

As asked for comments on NP-8, M/s Avana Electrosystems Pvt.

Ltd Bangalore may


please be asked to submit following test reports (in addition to the submitted tests) for
different types of relays, detail are as under:-
(A) For Numerical O/C & E /F relay

High Frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode.

High Frequency (1 MHz) disturbance test (IEC 60255-22-1), differential mode .

Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, class III), air discharge.

Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, class III), contact discharge

RF electromagnetic field test (IEC 61000-4-3 and ENV 50140)

Conducted RF disturbance test (IEC 61000-4-6 and ENV 50141).

Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), common mode.

Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), differential mode.

Conducted and radiated RF emission test (IEC 60255-25, Class A EN55011-CISPRII),
conducted and radiated emission (main)

Power frequency magnetic field immunity test (IEC 61000-4-8), continuous 100
A/m.

Power frequency magnetic field immunity test (IEC 61000-4-8), Short duration
300 A/m.

Power Supply Test (IEC 60255 - 11, IEC 61000-4-11)

Seismic test ( ANSI/IEEE C37.98-1987), operating basis earthquake test 0.55.25 g

Seismic test ( ANSI/IEEE C37.98-1987 ), safe shut down earthquake test 0.57.5 g

Shock response and endurance test ( IEC 60255-21-2 ) Class 1, 11ms

Service temperature range -10 C .+55 C

Dry heat test, (IEC 60068-22-2) +55 oC .+70 C

Cyclic (12+12 hour cycle) damp heat test , (IEC 60068-2-30 ) <95%, +40C, 96% Rh

Cold heat test, (IEC 60068-22-1) -10 oC . -20 C

Corrosion test Battelle test

Degree of protection by enclosure, IP test (IEC 60529) IP 54
(B) For Numerical sensitive E/F & REF relay
Dry heat test (IEC 60068-2-2)
Dry cold test (IEC 60068-2-1)
Damp heat test(IEC 60068-2-30)
MHz burst disturbance test, class III for Common mode & Differential mode(IEC
610004-4-18, IEC 60255-22-1).
Electrostatic discharge test for Contact discharge & Air discharge(IEC 61000-4-2,
IEC 60255-22-2)
Fast transient disturbance tests(IEC 61000-4-4, IEC 60255-22-4)
Radio frequency interference tests(IEC 61000-4-6,IEC 60255-22-6, class III, IEC
61000-4-3, IEC 60255-22-3, class III, ENV 50204, IEC 60255-22-3, class III, IEEE
C37.90.2-2004)
Surge immunity test for Communication & Other ports(IEC 61000-4-5, IEC
60255-22-5)
Power frequency (50 Hz) magnetic field for Continuous & 1-3 s (IEC 61000-4-8)
Voltage dips and short interruptions 30%/10 ms (According to IEC 61000- 4-11)
Power frequency immunity test for Common mode & Differential mode(IEC
61000-4-16 IEC 60255-22-7, class A)
Emission tests for Conducted & Radiated(EN 55011, class A, IEC 60255-25)
Impulse voltage test (IEC 60255-5 and IEC 60255-27)
Vibration tests (sinusoidal- IEC 60068-2-6 (test Fc) IEC 60255-21-1)
Shock and bump test (IEC 60068-2-27 (test Ea shock) IEC 60068-2-29 (test Eb
bump) IEC 60255-21-2)
Mechanical durability(IEEE C37.90-2005, IEC 602556-6)
(C ) Electromechanical Master trip & Auxiliary relay.
AUXILIARY RELAY
Impulse voltage test 5kV,1.2/50s. 0.5J., as per IEC 60255-5
Dry heat test (IEC 68000-2-2)
Dry cold test (IEC 68000-2-1)
Damp heat cyclic test (IEC 68000-2-30)
Storage test
Vibrations test (IEC 255-21-1)
Vibration response Test
Endurance test
Shock and Bump test (flush mounting case)( IEC 255-22-2)
Shock response test
Shock withstand test
Bump test
TRIP RELAY
Temperature-rise(IEC 60255-6)
Insulation resistance(IEC 60255-5)
Dielectric Test (IEC 60255-5)
Impulse voltage test (IEC 60255-5)
1 MHz burst disturbance Class III for common mode 2.5 kV, 1 MHz, 400 pls/s &
differential mode((IEC 60255-22-1)
Electro-static discharge test acc. Class III for contact discharge 6 kV, 150 pF/330
ohm & air discharge((IEC 60255-22-2)
Fast transient disturbance test Class IV for common mode((IEC 60255-22-4)
Surge immunity test acc. Class III for common mode 2 kV, 1.2/50 s, Rs = 10
ohm & differential mode((IEC 60255-22-5)
Vibration response and endurance test (IEC 60255-21-1)
Shock response and endurance (IEC 60255-22-2 )
Dry heat (IEC 60068-2-2)
Dry cold (IEC 60068-2-1)
Damp heat cyclic test (IEC 60068-2-30)
The firm may also be asked to certify that they have conducted all type
tests and routine/ acceptance tests which are mandatory as per IS/IEC standards.

AE/SS(D)
ASE/SS(D)

You might also like