KW 480/60Hz 400/50Hz 240/50Hz 208/60Hz

10 15 18 30 34 KW
20 30 36 60 69 V
30 45 54 90 104 I
40 60 72 120 138 PF
50 75 90 150 173
60 90 108 180 208
70 105 126 210 242
80 120 144 240 277
90 135 162 270 312
100 150 180 300 346
110 165 198 330 381
125 187 225 375 433
150 225 270 451 520
175 263 315 526 607
200 300 360 601 693 T1 and T4 U1 and U2
225 338 405 676 780 T2 and T5 V1 and V2
250 375 451 541 867 T3 and T6 W1 and W2
275 413 496 826 954 T7 and T10 U5 and U6
300 451 541 902 1040 T8 and T11 V5 and V6
325 488 586 977 1127 T9 and T12 W5 and W6
350 526 631 1052 1214
375 563 676 1127 1301
400 601 721 1202 1387
425 639 766 1278 1474 Disconnect Leads from the Diode Bridge Meggar Lead to
450 676 811 1353 1561 Ground. Then Meggar Lead to Lead
475 714 857 1428 1648
500 751 902 1503 1734
525 789 947 1578 1821 Disconnect the F1 and F2 Leads from AVR. Meggar F1 to
550 826 992 1653 1908 Ground then Meggar Lead to Lead.
575 864 1037 1729 1995
600 902 1082 1804 2081
625 939 1127 1879 2168 Disconnect the Leads from the Diodes. Maggar Leads to
650 977 1172 1954 2255 Ground Individually. Then Meggar Lead to Lead. Next
675 1014 1217 2029 2342 Check the Diodes with a Multimeter.
700 1052 1262 2104 2428
725 1090 1308 2180 2515
750 1127 1353 2255 2602
775 1165 1398 2330 2689
800 1202 1443 2405 2775
825 1240 1488 2480 2862
850 1278 1533 2556 2949
875 1315 1579 2631 3036
900 1353 1623 2706 3121
925 1390 1668 2781 3209
950 1428 1714 2856 3296
975 1465 1759 2931 3383
1000 1503 1804 3007 3469
1250 1879 2255 3758 4337
1500 2255 2706 4510 5204
Main Stator Winding Main Stator Winding
Main Stator Winding Main Stator Winding
Main Stator Winding Main Stator Winding
Testing Info on Main Gen Stator
Main Stator Winding Main Stator Winding
Main Stator Winding Main Stator Winding
Main Stator Winding Main Stator Winding
Formula
Voltage
Amperage
Power Factor
V*I*PF*1.732
KiloWatts
Note: 480VAC and 400VAC are high voltage connections
240VAC and 208VAC are low voltage connections.
V * PF * 1.732
Amperage Chart
Voltages Line to Line
at .8 Power Factor
KW*1000
KW =
I =
1000
Note: When Meggaring Windings Do Not Allow Yourself
to become the Ground it can be Fatal.
Testing Info on Main Gen Rotor
Testing Info on Excitor Stator
Testing Info on Excitor Rotor
Meggar each Winding Lead to Lead then to Ground.
T1 Connects L1 T1 Connects L1&T7 T1 Connects L1 T1 Connects L1 & T3
T2 Connects L2 T2 Connects L2 &T8 T2 Connects T3 T2 Connects Neutral
T3 Connects L3 T3 Connects L3&T9 T3 Connects T2 T3 Connects L1 & T1
T4 Connects T7 T4 Connects Neutral T4 Connects Neutral T4 Connects Neutral
T5 Connects T8 T5 Connects Neutral T5 Connects L2 T5 Connects L2 & T7
T6 Connects T9 T6 Connects Neutral T6 Connects T7 T6 Connects Neutral
T7 Connects T4 T7 Connects L1&T1 T7 Connects T6 T7 Connects L2 & T5
T8 Connects T5 T8 Connects L2&T2 T8 Connects Neutral T8 Connects Neutral
T9 Connects T6 T9 Connects L3&T3 T9 Connects L3 T9 Connects L3 & T11
T10 Connects Neutral T10 Connects Neutral T10 Connects T11 T10 Connects Neutral
T11 Connects Neutral T11 Connects Neutral T11 Connects T10 T11 Connects L3 & T9
T12 Connects Neutral T12 Connects Neutral T12 Connects Neutral T12 Connects Neutral
U1 Connects L1 U1 Connects L1&U5
V1 Connects L2 V1 Connects L2&V5
W1 Connects L3 W1 Connects L3&W5
U2 Connects U5 U2 Connects Neutral
V2 Connects V5 V2 Connects Neutral
W2 Connects W5 W2 Connects Neutral
U5 Connects U2 U5 Connects L1&U1
V5 Connects V2 V5 Connects L2&V1
W5 Connects W2 W5 Connects L3&W1
U6 Connects Neutral U6 Connects Neutral
V6 Connects Neutral V6 Connects Neutral
W6 Connects Neutral W6 Connects Neutral
Typical Generator Connections 90%
High Wye 480/400VAC Low Wye 240/208VAC
High Wye 480/400VAC Low Wye 240/208VAC
Typical Generator Connections 10%
High Wye 480/400VAC Low Wye 240/208VAC
Note: This only represents 10% of generators. If you are in
is a secondary check for this type of connection if it is still
open check between T1 and T4 if you get 0 Ohms you are in
doubt check continuity between T1 & T2 on this type of
connection, you will get 0 Ohms. If you get an open reading
check between T3 & T4 the reading should be 0 Ohms. This
the 90% of generators. Do not use this connection diagram.
Note: Adjust Voltage Regulator after Rewiring Generator.
Note: Check Wiring Diagram if any questions about
Voltage Connections.
Bus Bar T10, T11 & T12 Neutral
T6 & T9 T3 & L3 L3
T5 & T8 T2 & L2 L2
T4 & T7 T1 & L1 L1
T4, T5 & T6 Bus Bar T10, T11 & T12 Neutral
T9 Bus Bar T3 & L3 L3
T8 Bus Bar T2 & L2 L2
T7 Bus Bar T1 & L1 L1
Main Breaker
Typical Generator Connections 90% High Wye 480/400VAC
Typical Generator Connections 90% Low Wye 240/208VAC
Main Breaker
Bus Bar U6, V6 & W6 Neutral
W2 & W5 W1 & L3 L3
V2 & V5 V1 & L2 L2
U2 & U5 U1 & L1 L1
U2, V2 & W2 Bus Bar U6, V6 & W6 Neutral
W5 Bus Bar W1 & L3 L3
V5 Bus Bar V1 & L2 L2
U5 Bus Bar U1 & L1 L1
Main Breaker
Main Breaker
Typical Generator Connections 90% Low Wye 240/208VAC
Typical Generator Connections 90% High Wye 480/400VAC
Bus Bar T4, T8 & T12 Neutral
T10 & T11 T9 & L3 L3
T6 & T7 T5 & L2 L2
T2 & T3 T1 & L1 L1
T2, T6 & T10 Bus Bar T4, T8 & T12 Neutral
T11 Bus Bar T9 & L3 L3
T7 Bus Bar T5 & L2 L2
T3 Bus Bar T1 & L1 L1
Main Breaker
Typical Generator Connections 10% High Wye 480/400VAC
Main Breaker
Typical Generator Connections 10% Low Wye 240/208VAC