Professional Documents
Culture Documents
All longitudinal seam welds shall be fully radiographed and
acceptance limits shall be as per pipe specification as referred in
para 3.1.
The full circumference of both ends of each bend after bevelling
shall be ultrasonically tested for laminations over a length of 25mm
and acceptance limits shall be as per pipe specification as referred in
para 3.1.
5.2
Purchasers Representative reserves the right to perform stagewise inspection
and witness tests on all bends as indicated in para 5.1 at Manufacturers
works, prior to shipment.
Manufacturer shall give reasonable notice of time and shall provide without
charge reasonable access and facilities required for inspection, to the
Purchasers Representative. Inspection and test performed or witnessed by
Purchasers Representative shall in no way relieve the Manufacturers
obligation to perform the required inspection and tests. Under no
circumstances any action of the Purchasers Representative shall relieve the
Manufacturer of his responsibility for the material, design, quality and
operation of the equipment.
D:\TS\Lond Redius Bends - 015-R1.doc
MECON LIMITED
DELHI
PROCESS & PIPING
DESIGN SECTION
STANDARD SPECIFICATION
TITLE LONG RADIUS BENDS SPECIFICATION NO. PAGE 7 OF 8
MEC/TS/05/62/015 REVISION 1
5.3
Test Certificates
The Manufacturer shall produce the Certificates (in original) for all, but not
limited to, the following :
a)
Certificates of chemical analysis and mechanical tests carried out on
pipe and bends separately.
b)
Certificates of required non-destructive test inspection.
c)
Certificates of heat treatments, if any.
d)
Certificates of all other tests as required in this specification.
In case any of the above said certificates are not available during the final
inspection, the supply shall be considered incomplete.
6.0
MARKING, PACKING AND SHIPMENT
6.1 All bends shall be marked as per MSS-SP-75.
6.2
All loose and foreign material i.e. rust, grease, etc. shall be removed from
inside and outside of the bends.
6.3
All bends except bevelled ends shall be coated internally and externally with a
thin film of zinc chromate red oxide paint for protection against corrosion
during transit and storage. The coating shall be easily removable in the field.
Manufacturer shall furnish the details for the same.
6.4
Both ends of all bends shall be suitably protected to avoid any damage during
transit by means of metallic bevel protectors.
6.5
Package shall be marked legibly with suitable marking to indicate the
following:
a)
Order Number
b)
Package Number
c)
Manufacturers Name
d)
Size (Inches) and wall thickness (mm)
D:\TS\Lond Redius Bends - 015-R1.doc
MECON LIMITED
DELHI
PROCESS & PIPING
DESIGN SECTION
STANDARD SPECIFICATION
TITLE LONG RADIUS BENDS SPECIFICATION NO. PAGE 8 OF 8
MEC/TS/05/62/015 REVISION 1
7.0
WARRANTY
Purchaser will be reimbursed by Manufacturer for any bend furnished on this
order that fails under field hydrostatic test if such failure is caused by a defect
in the bend which is outside the acceptance limits of this specification. The
reimbursement cost shall include bend cost, labour cost and equipment rental
for searching, excavation, cutting out and installation of replaced bend in
position. The field hydrostatic test pressure will not exceed that value which
will cause a calculated hoop stress equivalent to 100% of specified minimum
yield strength of the attached pipe.
8.0
DOCUMENTATION
8.1 All documents shall be in English language.
8.2
At the time of bidding, bidder shall submit the following documents :
a)
Reference list of previous supplies of bends of similar specifications.
b)
Clause-wise list of deviation from this specification, if any.
c)
Brief description of manufacturing and quality control facilities of the
Manufacturers works.
8.3
Within one week of placement of order the Manufacturer shall submit four
copies, of the manufacturing process and quality assurance plan for pipe and
bends.
Once the approval has been given by Purchaser any change in material and
method of manufacture and quality control shall be notified to Purchaser
whose approval in writing of all such changes shall be obtained before the
bends are manufactured.
8.4
Within four weeks from the approval date Manufacturer shall submit one
reproducible and six copies of the documents as stated in para 8.3 of this
specification.
8.5
Prior to shipment, the Manufacturer shall submit one reproducible and six
copies of test certificates as listed in para 5.3 of this specification.
SPECIFICATION
FOR
SEAMLESS FITTINGS & FLANGES
[SIZE UPTO DN 400 mm (16 ) NB]
SPECIFICATION NO.: MEC/TS/05/21/025
(OIL & GAS SBU)
MECON LIMITED
DELHI 110 092
Rev. : 0
Edition : 1
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
C O N T E N T S
SL.NO. DESCRIPTION
1.0 SCOPE
2.0 REFERENCE DOCUMENTS
3.0 MANUFACTURERS QUALIFICATION
4.0 MATERIALS
5.0 DESIGN AND MANUFACTURE
6.0 INSPECTION AND TESTS
7.0 TEST CERTIFICATES
8.0 PAINTING, MARKING AND SHIPMENT
9.0 DOCUMENTATION
PREPARED BY:
(Shalini Singh)
CHECKED BY:
(Sunil Kumar)
APPROVED BY:
(A.K. Johri)
ISSUE DATE :
Dec. 2008
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
AMENDMENT STATUS
Sl.
No.
Clause / Paragraph /
Annexure / Exhibit / Drawing
Amended
Page
No.
Revision Date By
(Name)
Verified
(Name)
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 5
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
1.0 SCOPE
This specification covers the minimum requirements for the design, manufacture and
supply of following carbon steel flanges and fittings of size upto DN 400 mm (16") to
be installed in onshore pipeline systems handling non-sour hydrocarbons in liquid or
gaseous phase including Liquefied Petroleum Gas (LPG) :
- Flanges such as welding neck flanges, blind flanges, spectacle blinds,
spacers and blinds etc.
- Seamless fittings such as tees, elbows, reducers, caps, outlets etc.
2.0 REFERENCE DOCUMENTS
2.1 Reference has been made in this specification to the latest edition (edition enforce at
the time of issue of enquiry) of the following Codes, Standards and Specifications :
ASME B31.4 - Pipeline Transportation Systems for Liquid
Hydrocarbons and Other Liquids
ASME B31.8 - Gas Transmission and Distribution Piping Systems
ASME B16.5 - Pipe Flanges and Flanged Fittings
ASME B16.9 - Factory Made Wrought Steel Butt Welding Fittings
ASME B 16.11 - Forged Steel Fittings, Socket Welding and Threaded
ASME B 16.48 - Steel Line Blanks
ASME Sec VIII - Boiler and Pressure Vessel Code - Rules for
Construction of Pressure Vessels
ASME Sec IX - Boiler and Pressure Vessel Code - Welding and
Brazing Qualifications
ASTM A 370 - Standard Test Methods and Definitions for Mechanical
Testing of Steel Products.
MSS-SP-25 - Standard Marking System for Valves, Fittings, Flanges
and Unions
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 2 of 5
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
MSS-SP-97 - Forged Carbon Steel Branch Outlet Fittings - Socket
Welding, Threaded and Butt welding Ends.
2.2 In case of conflict between the requirements of this specification and the
requirements of above referred Codes and Standards, the requirements of this
specification shall govern.
3.0 MANUFACTURER'S QUALIFICATION
Manufacturer who intends bidding for fittings must possess the records of a
successful proof test, in accordance with the provisions of ASME B16.9 / MSS-SP-75
as applicable.
4.0 MATERIAL
4.1 The Carbon Steel used in the manufacture of flanges and fittings shall be fully killed.
Material for flanges and fittings shall comply with the material standard indicated in
the Purchase Requisition. In addition, the material shall also meet the requirements
specified hereinafter.
4.2 Each heat of steel used for the manufacture of flanges and fittings shall have Carbon
Equivalent (CE) not greater than 0.45 calculated from check analysis in accordance
with the following formula:
Mn Cr + Mo + V Ni + Cu
CE = C + ------- + --------------------- + ---------------
6 5 15
Carbon contents on check analysis shall not exceed 0.22%.
4.3 For flanges and fittings specified to be used for Gas service or LPG service, Charpy
V-notch test shall be conducted on each heat of steel. Unless specified otherwise,
the Charpy V-notch test shall be conducted at 0C in accordance with the impact test
provisions of ASTM A 370 for flanges and fittings.
The average absorbed impact energy values of three full-sized specimens shall be
27 joules. The minimum impact energy value of any one specimen of the three
specimens analysed as above, shall not be less than 22 J oules.
When Low Temperature Carbon Steel (LTCS) materials are specified for flanges and
fittings in Purchase Requisition, the Charpy V-notch test requirements of applicable
material standard shall be complied with.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 3 of 5
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
4.4 For flanges and fittings specified to be used for Gas service or LPG service,
Hardness test shall be carried out in accordance with ASTM A 370. Hardness testing
shall cover at least 10% per item, per size, per heat, per manufacturing method. A
full thickness cross section shall be taken for this purpose and the maximum
hardness shall not exceed 248 HV
10
.
4.5 In case of RTJ (Ring Type J oint) flanges, the groove hardness shall be minimum 140
BHN. Ring J oint flanges shall have octagonal section of Ring J oint.
5.0 DESIGN AND MANUFACTURE
5.1 Flanges such as weld neck flanges and blind flanges shall conform to the
requirements of ASME B16.5.
5.2 Spectacle blind and spacer & blind shall conform to the requirements of ASME B
16.48.
5.3 Fittings such as tees, elbows, reducers, etc. shall be seamless type and shall
conform to ASME B16.9 for sizes DN 50 mm (2") to DN 400 mm (16") (both sizes
included) and ASME B 16.11 for sizes below ON 50 mm (2").
5.4 Fittings such as weldolets, sockolets, nippolets, etc. shall be manufactured in
accordance with MSS-SP-97.
5.5 Type, face and face finish of flanges shall be as specified in Purchase Requisition.
5.6 Flanges and fittings manufactured from bar stock are not acceptable.
5.7 All butt weld ends shall be bevelled as per ASME B 16.5 / ASME B 16.9 / MSS-SP-
97 as applicable.
5.8 Repair by welding on flanges and fittings is not permitted.
5.9 Stub-in or pipe to pipe connection shall not be used in the manufacture of tees.
Tees shall be manufactured by forging or extrusion methods. The longitudinal weld
seam shall be kept at 90 from the extrusion. Fittings shall not have any
circumferential joint .
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 4 of 5
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
6.0 INSPECTION AND TESTS
6.1 The Manufacturer shall perform all inspections and tests as per the requirement of
this specification and the relevant codes, prior to shipment at his works. Such
inspections and tests shall be, not but limited to the following :
a) All flanges and fittings shall be visually inspected. The internal and external surfaces
of the flanges and fittings shall be free from any strikes, gauges and other
detrimental defects.
b) Dimensional checks shall be carried out on finished products as per ASME B16.5 for
flanges, ASME B16.48 for spacers and blinds and ASME B16.9 / MSS-SP-97 as
applicable for fittings and as per this specification.
c) Chemical composition and mechanical properties shall be checked as per relevant
material standards and this specification, for each heat of steel used.
d) All finished wrought weld ends subject to welding in field, shall be 100% tested for
lamination type defects by ultrasonic test. Any lamination larger then 6.35 mm shall
not be acceptable.
6.2 Purchaser's Inspector reserves the right to perform stage wise inspection and
witness tests, as indicated in clause 6.1 of this specification at Manufacturer's Works
prior to shipment. Manufacturer shall give reasonable notice' of time and shall
provide, without charge, reasonable access and facilities required for inspection, to
the Purchaser's Inspector.
Inspection and tests performed / witnessed by Purchaser's Inspector shall in no way
relieve the Manufacturer's obligation to perform the required inspection and tests.
7.0 TEST CERTIFICATES
Manufacturer shall furnish the following certificates:
a) Test certificates relevant to the chemical analysis and mechanical properties
of the materials used for manufacture of flanges and fittings as per relevant
standards and this specification.
b) Test Reports on non destructive testing.
c) Certificates for each fitting stating that it is capable of withstanding without
leakage a test pressure, which results in a hoop stress equivalent to 100 % of
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 5 of 5
TITLE MEC/ TS/ 05/ 21/ 025 REVISION : 0
SEAMLESS FITTINGS &
FLANGES [SIZE UPTO DN 400
mm (16) NB] EDITION : 1
the specified minimum yield strength for the pipe with which the fitting is to be
attached without impairment of serviceability.
8.0 PAINTING, MARKING AND SHIPMENT
8.1 After all inspection and tests required have been carried out; all external surfaces
shall be thoroughly cleaned to remove grease, dust and rust and shall be applied
with standard mill coating for protection against corrosion during transit and storage.
The coating shall be easily removable in the field.
8.2 Ends of all fittings and weld neck flanges shall be suitably protected to avoid any
damage during transit. Metallic or high impact plastic bevel protectors shall be
provided for fittings and flanges. Flange face shall be suitably protected to avoid any
damage during transit.
8.3 All flanges and fittings shall be marked as per applicable dimension / manufacturing
standard.
9.0 DOCUMENTATION
Documentation to be submitted by Manufacturer to Company is summarized below.
Number of Copies (Hard copies / soft copies etc.) shall be as indicated in
CONTRACT document / Material Requisition.
9.1 At the time of bidding, Manufacturer shall submit the following documents:
a) Reference list of previous supplies of similar fittings of similar specification.
b) Clausewise list of deviations from this specification, if any.
c) Brief description of the manufacturing and quality control facilities at
Manufacturer's works.
d) Manufacturer's qualification requirement as per clause 3.0 of this specification.
e) Quality Assurance Plan (QAP) enclosed with this tender duly signed, stamped
and accepted.
9.2 Prior to shipment, the Manufacturer shall submit test certificates as listed in clause
7.0 of this specification.
9.3 All documents shall be in English Language only.
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
PROCESS & PIPING DESIGN SECTION
MECON LIMITED
DELHI 110 092
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
SPECIFICATION NO. : MEC/TS/05/62/59A, R-0
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 1 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
C O N T E N T S
Sl.No. Description Page No.
1.0 GENERAL 2
2.0 IBR PIPES 4
3.0 HYDROSTATIC TEST 5
4.0 MARKING & DESPATCH 5
ANNEXURE-I : HYDROSTATIC TEST 7
Prepared By : Checked By : Approved By :
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 2 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
1.0 GENERAL
1.1 All pipes and their dimensions, tolerances, chemical composition, physical
properties, heat treatment, hydrotest and other testing and marking
requirements shall conform to the latest codes and standards specified in
the Material Requisition (MR). Deviation(s), if any, shall be clearly
highlighted in the offer.
1.2 Testing
1.2.1 Test reports shall be supplied for all mandatory tests as per the applicable
material specifications. Test reports shall also be furnished for any
supplementary tests as specified in the MR & Clauses 1.10 & 1.11.
1.2.2 Material test certificates (physical property, chemical composition &
treatment report) shall also be furnished for the pipes supplied.
1.3 Manufacturing Processes
1.3.1 Steel made by Acid Bessemer Process shall not be acceptable.
1.3.2 All longitudinally welded pipes other than IS:3589 should employ
automatic welding.
1.4 Pipe shall be supplied in single or double random length of 4 to 7 and 7 to
14 meters, respectively.
1.5 a) Seamless and E.R.W. pipes shall not have any circumferential seam
joint in a random length. However, in case of E.FS.W. pipe, in one
random length one welded circumferential seam of same quality as
longitudinal weld is permitted. This weld shall be at least 2.5 m
from either end. The longitudinal seams of the two portions shall
be staggered by 90. Single random length in such cases shall be 5
to 7m.
b) Unless otherwise mentioned in the respective material code,
E.FS.W. pipes < 36 shall not have more than one longitudinal
seam joint and E.FS.W. pipes 36 shall not have more than two
longitudinal seam joints.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 3 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
1.6 Pipe with screwed ends shall have NPT external taper pipe threads
conforming to ASME/ ANSI B1.20.1 upto 1.5 NB & IS:554 for 2 to 6 NB.
1.7 Pipe with bevelled ends shall be in accordance with ASME B16.25. Weld
contours shall be as follows:
Material Wall Thickness Weld Contour
Upto 22mm Figure 2 Type A Carbon Steel (Except Low
Temp. Carbon Steel) > 22mm Figure 3 Type A
Upto 10 mm Figure 4
>10 mm & Upto 25 mm Figure 5 Type A
Alloy Steel Stainless Steel &
Low Temp. Carbon Steel
> 25 mm Figure 6 Type A
1.8 Gavanished pipes shall be coated with zinc by hot dip process conforming
to IS:4736/ ASTM A 153.
1.9 All austenitic stainless steel pipes shall be supplied in solution annealed
condition.
1.10 I.G.C. Test for Stainless Steels
1.10.1 For all austenitic stainless steel pipes, intergranular corrosion test shall
have to be conducted as per following:
ASTM A262 practice B with acceptance criteria of 60 mils/ year
(max.)
OR
ASTM 262 practice E with acceptance criteria of No cracks as
observed from 20X magnification & Microscopic structure to be observed
from 250X magnification.
1.10.2 When specifically asked for in MR for high temperature application of
some grades of austenitic stainless steel (eg.SS 309, 310, 316, 316H etc.),
ASTM A262 practice C with acceptance criteria of 15 mils/ year (max.)
shall have to be conducted.
1.10.3 For the IGC test as described in 1.10.1 & 1.10.2, two sets of samples shall
be drawn from each solution annealing lot; one set corresponding to
highest carbon content and the other corresponding to the highest pipe
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 4 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
thickness. When testing in is conducted as per Practice E, photograph of
microscopic structure shall be submitted for record.
1.11 All welded pipes indicated as CRYO & LT in MR shall be impact tested
per requirement and acceptance criteria of ASME B31.3. The impact test
temperature shall be 196 C & -45 C for stainless steel and carbon
steel, respectively, unless specifically mentioned otherwise in MR.
1.12 Pipes under NACE category shall meet the requirements given in
MR-01-75.
1.13 Specified heat treatment for carbon steel & alloy steel and solution
annealing for stainless steel pipes shall be carried out after weld repairs.
Number of weld repairs at the same spot shall be restricted to maximum
two by approved repair procedure.
1.14 For black or galvanised pipes to IS:1239, the minimum percentage of
elongation shall be 20%.
2.0 IBR PIPES
2.1 IBR Documentation
2.1.1 Pipes under purview of IBR shall be accompanied with IBR certificate
original in Form IIIA, duly approved and countersigned by IBR authority/
local authority empowered by the Central Boiler Board of India. Photocopy
of the original certificate duly attested by the local boiler inspector where
the supplier is located is the minimum requirement for acceptance.
2.1.2 For materials 1 Cr- Mo (ASTM A335 Gr. P11/ A691 Gr. 1 Cr) & 2
Cr-1Mo (ASTM A335 Gr.P22/ A691 Gr. 2 Cr.), from III-A approved
by IBR shall include the tabulation of E
t
, S
c
& S
r
values for the entire
temperature range given below. E
t
, S
c
& S
r
values shall be such that
throughout the temperature range
E
t
/ 1.5
S
r
/ 1.5 S
a
S
c
where,
S
A
: Allowable stress at the working metal temperature.
E
t
: Yield point (0.2% proof stress at the working metal
temperature).
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 5 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
S
c
: The average stress to produce elongation of 1% (creep) in
1,00,000 hrs at the working metal temperature.
S
r
: The average stress to produce rupture in 1,00,000 hrs. at
the working metal temperature and in no case more than
1.33 times the lowest stress to produce rupture at this
temperature.
S
A
(psi)
Temperature (F)
Material
500 600 650 700 750 800 850 900 950 1000 1050 1100
A335 Gr. P11
17200 16700 16200 15600 15200 15000 14500 12800 9300 6300 4200 2800
A 691 Gr. 1 Cr
18900 18300 18000 17600 17300 16800 16300 15000 9900 6300 4200 2800
A335 Gr. P2/
A691 Gr. 2 Cr
17900 17900 17900 17900 17900 17800 14500 12800 10800 7800 5100 3200
Note: S
A
values given above are as per ASME B31.3-1999. Values shall be as per
the latest edition prevailing.
2.2 For carbon steel pipes under IBR, the chemical composition shall conform
to the following;
Carbon (max.) : 0.25%
Others (S, P, Mn) : As prescribed in IBR regulation.
The chemical composition as indicated in this clause is not applicable for
pipes other than IBR services.
3.0 HYDROSTATIC TEST
Refer Annexure I.
4.0 MARKING AND DESPATCH
4.1 All pipes shall be marked in accordance with the applicable codes,
standards and specifications. In addition, the purchase order number, the
item code & special conditions like IBR, CRYO, NACE, etc., shall also
be marked.
4.2 Pipes under IBR, CRYO, & NACE shall be painted in red stripes, light
purple brown stripes & canary yellow stripes, respectively, longitudinally
throughout the length for easy identification.
4.3 Paint or ink for marking shall not contain any harmful metal or metallic
salts such as zinc, lead or copper which cause corrosive attack on heating.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 6 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
4.4 Pipes shall be dry, clen and free from from moisture, dirt and loose
foreign materials of any kind.
4.5 Pipes shall be protected from rust, corrosion and mechanical damage
during transportation, shipment and storage.
4.6 Rust preventive used on machined surfaces to be welded shall be easily
removable with a petroleum solvent and the same shall not be harmful to
welding.
4.7 Both ends of the pipe shall be protected with the following material:
Plain end : Plastic cap
Bevel end : Wood, Metal or Plastic cover
Threaded end : Metal or Plastic threaded cap
4.8 End protectors to be used on bevelled ends shall be securely and tightly
attached with belt or wire.
4.9 Steel end protectors to be used on galvanised pipes shall be galvanised.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 7 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
ANNEXUREI
3.0 HYDROSTATIC TEST
3.1 All pipes shall be hydrostatically tested.
3.2 The mill test pressure shall be as follows:
3.2.1 Seamless, E.R.W. & Spiral Welded
a) Carbon Steel
Material Standard Test Pressure Standard
ASTM A 106 Gr. B ASTM A 530
API 5L Gr. B, Seamless API 5L
API 5L, E.R.W. API 5L
API 5L, Spiral API 5L
ASTM A333 Gr.3 & 6, Seamless ASTM A 530
ASTM A 333 Gr. 3 & 6, E.R.W. ASTM A 530
b) Seamless Alloy Steel
Material Standard Test Pressure Standard
ASTM A335 GR.P1, P12, P11, P22, P5,
P9
ASTM A 530
ASTM A268 TP 405, TP410 ASTM A530
c) Seamless Stainless Steel
Material Standard Test Pressure Standard
ASTM A312 Gr.TP304, 304L, 304H, 316,
316L, 316H, 321, 347
ASTM A 530
d) Seamless Nickel Alloy
Material Standard Test Pressure Standard
ASTM B161 UNS No.2200 ASTM B161
ASTM B165 UNS No.4400 ASTM B165
ASTM B167 UNS No.6600 ASTM B167
ASTM B407 UNS No.8800 ASTM B407
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 8 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
e) Welded Nickel Alloy
Material Standard Test Pressure Standard
ASTM B725 UNS No.2200, 4400 ASTM B725
ASTM B517 UNS No.6600 ASTM B517
ASTM B514 UNS No.8800 ASTM B514
3.2.2 Electric Fusion Welded
a) Carbon Steel & Alloy Steel E.FS.W. (16 & above)
Material Standard Test Pressure Standard
API 5L Gr.B
ASTM A 671 Gr.CC65, 70 (Cl.32)
ASTM A 672 Gr.C60, 65, 70 (Cl.12,22)
ASTM A 671 Gr.CF60, 65, 66, 70 (Cl.32)
ASTM A 691 Gr. Cr, 1Cr, 1 Cr, 2
Cr, 5Cr, 9Cr (Cl.42)
P=2ST/ D
S=90% of SMYS (except for API 5L
Gr.B)
S=85% of SMYS for API 5L Gr.B
T=Nominal Wall Thickness
D=O.D. of Pipe
b) Stainless Steel E.FS.W. (2 to 6)
The hydrostatic test pressure in kg/ cm
2
for the following materials
shall be as given below:
Material Gr.1: ASTM A312 TP304/ 304H/ 316/ 316H/ 321/
347 welded
Material Gr.2: ASTM A312 TP 304L/ 316L welded
Pipe Schedule: S10 Pipe Schedule : S40 Pipe Schedule : S80
Size Material
Gr.1
Material
Gr.2
Material
Gr.1
Material
Gr.2
Material
Gr.1
Material
Gr.2
2 100 80 155 130 230 190
3 80 60 155 130 230 190
4 80 50 155 130 230 190
6 65 35 90 75 155 130
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
ASSORTED PIPES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/59A REV-0 PAGE 9 OF 9
\\Akjha\work contrac\standard TS for Pipe Line WC (Vol-II) MASTER FOLDER\59A assorted pipe spec\Specification for Assorted Pipes 59A.doc
c) Stainless Steel E.FS.W. (8 and above).
Material Standard Test Pressure Standard
ASTM A358 TP 304L, 304, 304H,
316L, 316, 316H, 321, 347
(Classes 1, 3 & 4)
P = 2ST/D
S = 85% of SMYS
T = Nominal Wall Thickness
D = O.D. of Pipe
ASTM A358 TP 304L, 304, 304H,
316L, 316, 316H, 321, 347
(Classes 2 & 5)
P = 2ST/D
S = 72% of SMYS
T = Nominal Wall Thickness
D = O.D. of Pipe
3.2.3 Carbon Steel Pipes to I S Standards
Material Standard Test Pressure Standard
IS :1239 IS :1239
IS :3589 IS :3589
SPECIFICATION
FOR
BALL VALVES
SPECIFICATION NO.: MEC/ TS/ 05/ 21/ 002
(OIL & GAS SBU)
MECON LIMITED
DELHI 110 092
Rev. : 0
Edition : 1
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
ABBREVIATIONS :
ASME : American Society of Mechanical Engineers
ASTM : American Society for Testing and Materials
API : American Petroleum Institute
BHN : Brinell Hardness Number
DN : Nominal Size
HAZ : Heat Affected Zone
LC : Lock Close (valve locked in full close position)
LO : Lock Open (valve locked in full open position)
MSS-SP : Manufacturers Standardization Society Standard Practice
NDT : Non Destructive Testing
NPS : Nominal Pipe Size
RTJ : Ring Type J oint
SSPC : Steel Structures Painting Council
Pipeline Engineering Standards Committee
Convenor :
Members :
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
C O N T E N T S
Sl.No. Description Page No.
1.0 SCOPE
2.0 REFERENCE DOCUMENTS
3.0 MATERIALS
4.0 DESIGN AND CONSTRUCTION
5.0 INSPECTION AND TESTS
6.0 EXTENT OF INSPECTION & TESTING
7.0 TEST CERTIFICATES
8.0 PAINTING, MARKING AND SHIPMENT
9.0 SPARES AND ACCESSORIES
10.0 DOCUMENTATION
11.0 GUARANTEE
PREPARED BY:
(SHALINI SINGH)
CHECKED BY:
(GURDEEP SINGH)
APPROVED BY:
(A.K. J OHRI)
ISSUE DATE :
Oct. 2008
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 1
EDITION : 1
AMENDMENT STATUS
By Verified Sl.
No.
Clause / Paragraph /
Annexure / Exhibit /
Drawing Amended
Page
No.
Rev. Date
Name Sig. Name Sig.
1. Cl. No. 4.6 4 1 April 09 Gurdeep
Singh
KK De
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
1.0 SCOPE
This specification covers the minimum requirements for design, manufacture, testing
and supply of carbon steel ball valves of size DN 50mm (2) and above and ANSI
class 150 to 900 to be used in on-shore pipeline systems handling non-sour
hydrocarbons in liquid or gaseous phase, including Liquid Petroleum Gas (LPG).
This specification does not cover ball valves for sour hydrocarbon (liquid/ gas)
service as defined in NACE standard MR-01-75.
2.0 REFERENCE DOCUMENTS
2.1 All valves shall be manufactured and supplied in accordance with the Twenty Second
Edition, J anuary,2002, or the latest edition of American Petroleum Institute (API)
Specification 6D / ISO 14313 : 1999, with additions and modifications as indicated in
the following sections of this specification.
2.2 Reference has also been made in this specification to the latest edition of the
following Codes, Standards and Specifications :
ASME B 16.5 : Pipe flanges and flanged fittings
ASME B 16.25 : Butt welding ends
ASME B 16.34 : Valves Flanged, threaded and welding end
ASME B16.47 : Large diameter steel flanges
ASME B 31.3 : Chemical & process plant piping system
ASME B 31.4 : Liquid transportation systems for hydrocarbons and
other liquids
ASME B 31.8 : Gas transmission and distribution piping systems
ASME Sec.VIII/IX : Boiler and pressure vessel code
ASTM A 370 : Standard test methods and definitions for mechanical
testing of steel products
ASTM B 733 : Autocatalytic nickel phosphorous coating on metals
API 6FA : Fire test for valves
API 607 : Fire test for soft-seated quarter-turn valves
API 1104 : Welding of pipelines and related facilities
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 2 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
BS:6755 (Part-II) : Testing of valves Specification for fire type - testing
requirements
MSS-SP-6 : Standard finishes for contact faces of pipe flanges and
connecting-end flanges of valves and fittings
MSS-SP-44 : Steel pipeline flanges
SSPC-VIS-1 : Steel structures painting council-visual standard
ASMEB 16.10 : Face-To-Face and End-To-End Dimensions of valves.
2.3 In case of conflict between the requirements of this specification, API 6D and the
Codes, Standards and Specifications referred in clause 2.2 above, the requirements
of this specification shall govern. Order of precedence shall be as follows :
Data Sheets
This Specification
API 6D Specification
Other Referred Codes & Standards
Manufacturers Standard
3.0 MATERIALS
3.1 Material for major components of the valves shall be as indicated in Valve Data
Sheet. Other components shall be as per Manufacturers standard (suitable for the
service conditions indicated in Data Sheet) and shall be subject to approval by
Purchaser. In addition, the material shall also meet the requirements specified
hereinafter.
3.2 Carbon steel used for the manufacture of valves shall be fully killed.
3.3 The Carbon Equivalent (CE) of valve end connections which are subject to further
field welding by Purchaser, shall not exceed 0.45% (as calculated by the following
formula) on check analysis for each heat of steel used:
Mn Cr + Mo + V Ni + Cu
CE = C + -------- + ---------------------- + ---------------
6 5 15
3.4 For Valves specified to be used for Gas service or LPG service, Charpy V-notch test,
on each heat of base material shall be conducted as per API 6D Clause 7.5, for all
pressure containing parts such as body, end flanges and welding ends as well as
bolting material for pressure containing parts. Unless otherwise, the Charpy V-notch
test shall be conducted at 0 C. Test procedure shall conform to ASTM A370. The
average absorbed energy value of three full sized specimens shall be 27 J . The
minimum impact energy value for any one specimen of the three specimens analysed
as above, shall not be less than 22 J .
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 3 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
When Low Temperature Carbon Steel (LTCS) materials are specified in Valve Data
Sheet or offered by Manufacturer, the Charpy V-notch test requirements of applicable
material standard shall be complied with.
3.5 For all such valves where carbon steel is used as ball material, the ball shall have 75
micrometer (0.003 inch) thick Electroless Nickel Plating (ENP) as per ASTM B733 with
following classification : SC2, Type II, Class 2. The hardness of plating shall be
minimum 50 RC.
3.6 When specified in Valve Data Sheet, hardness test shall be carried out on each heat
of base material for all pressure containing parts of the valve. A full thickness cross-
section shall be taken for this purpose and the maximum hardness shall not exceed
248 HV
10
based on minimum four measurements representing the entire thickness.
3.7 All process-wetted parts, metallic and non-metallic, shall be suitable for the fluids and
service specified by the Purchaser. The service gas composition shall be as given in
Annexure-I.
3.8 Non-metallic parts of the valves (including O-rings, soft seals etc.) intended for
hydrocarbon gas service shall be resistant to explosive decompression.
4.0 DESIGN AND CONSTRUCTION
4.1 Valve design shall meet the requirements of API 6D and other referred codes and
shall be suitable for the service conditions indicated in Valve Data Sheet. The ASME
Boiler & Pressure Vessel Code, Section VIII, Division 1, shall be used to design the
valve body. Allowable stress requirements shall comply the provisions of ASME
B31.3. In addition, corrosion allowance indicated in Valve Data Sheet shall be
considered in valve design. However, the minimum wall thickness shall not be less
than the minimum requirement of ASME B16.34. The Manufacturer shall have a valid
license to use API 6D monogram for manufacture of ball valves.
4.2 Valve body shall be either fully welded or bolted. Valve body joints with threads are
not permitted.
4.3 Ball shall be of single piece, solid type construction.
4.4 Valves shall be Full Bore (FB) or Reduced Bore (RB) as indicated in Valve Data Sheet.
Full bore valves shall be suitable for the passage of all types of pipeline scraper and
inspection pigs on regular basis without causing damage to either the valve
component or the pig. The full bore valve shall provide an unobstructed profile for
pigging operations in either direction. Full bore valves shall be designed to minimize
accumulation of debris in the seat ring region to ensure that valve movement is not
impeded. In case of reduced bore valves, the nominal valve size indicated in Valve
Data Sheet corresponds to the end connection. Nominal valve size of reduced bore
shall be as per Table below:
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 4 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 1
EDITION : 1
Nominal Valve
Size
Nominal Valve
Size for Reduced
Bore
Nominal Valve
Size
Nominal Valve
Size for Reduced
Bore
DN
mm
(NPD
inches
) DN
mm
(NPD
inches
) DN
mm
(NPD
inches
) DN
mm
(NPD
inches
)
50 (2) 50 (2) 600 (24) 500 (20)
80 (2) 50 (2) 650 (26) 550 (22)
100 (4) 80 (3) 700 (28) 600 (24)
150 (6) 100 (4) 750 (30) 600 (24)
200 (8) 150 (6) 800 (32) 650 (26)
250 (10) 200 (8) 850 (34) 700 (28)
300 (12) 250 (10) 900 (36) 750 (30)
350 (14) 250 (10) 950 (38) 800 (32)
400 (16) 300 (12) 1000 (40) 850 (34)
450 (18) 350 (14) 1050 (42) 900 (36)
500 (20) 400 (16) 1200 (48) 1050 (42)
550 (22) 450 (18)
4.5 Ball mounting shall be trunnion/ pivot type or as indicated in Valve Data Sheet. Valve
design shall minimize the possibility of debris ingress into the trunnion as far as
practicable. Ball mounting either trunnion or floating may be as follows :
Sl. No. Rating Floating Ball Design Trunnion Mounted
Design
1. 150 Up to 8 More than 8
2. 300 Up to 4 More than 4
3. 600 Nil 2 & Above
4.6 Valve seats shall have metal to metal contact. O-rings or other seals, if used for drip
tight sealing, shall be encased in a suitable groove in such a manner that it can not
be removed from seat ring and there is no extrusion during opening or closing
operation of valve at maximum differential pressure corresponding to valve class
rating. The seat rings shall be so designed as to ensure sealing at low as well as high
differential pressures. Seat design with PTFE insert is not acceptable.
4.7 Valves shall have double block and bleed feature to facilitate complete flushing,
draining and venting of the valve body cavity.
4.8 For valves to be used in liquid service, the body cavity over-pressure shall be
prevented by self relieving seat rings/assemblies. A pressure relief hole in the ball is
not permitted. Self relieving seat rings shall relieve at a body cavity differential
pressure not exceeding 50% of the valve class rating pressure.
4.9 When specified in Valve Data Sheet, valves shall be designed to withstand a
sustained internal vacuum of at least 1 (one) milli-bar in both open and closed
positions.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 5 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
4.10 Full Bore Valves of nominal size DN 200mm(8) & above and Reduced Bore Valves of
nominal size DN 250mm(10) & above shall have provision for secondary sealant
injection under full line pressure for seat and stem seals. All sealant injection
connections shall be provided with a needle valve, a grease fitting and non-return
valve. Valve design shall have a provision to replace the sealant injection fitting
under full line pressure. Location and arrangement of sealant points shall be as per
Figure-1 (Annexure-II).
4.11 Valves shall be provided with vent and drain connections. Location and arrangement
of vents and drains alongwith provision of valves shall be as per Figure-1 (Annexure-
II).
4.12 Valve design shall ensure repair of stem seals / gland packing under full line
pressure.
4.13 a) Valve ends shall be either flanged or butt welded or one end flanged and one end
butt welded as indicated in Valve Data Sheet. Flanges of the flanged end cast/
forged body valves shall be integrally cast/forged with the body of valve. Face-to-
face/ end-to-end dimensions shall conform to API 6D. Face-to-face and end-to-end
dimensions for valve sizes not specified in API 6D shall be in accordance with ASME
B 16.10. Face-to-face and end-to-end dimensions not shown in API 6D or in ASME B
16.10 shall be as per Manufacturer Standard and shall be subject to approval by
Company.
b) Flanged end shall have dimensions as per ASME B16.5 for valve sizes upto DN
600mm (24 inches) excluding DN 550mm (22 inches) and as per MSS-SP-44 / ASME
B 16.47 series A for valve sizes DN 550mm (22 inches) & for DN 650mm (26 inches)
and above. Flange face shall be either raised face or ring joint type as indicated in
Valve Data Sheet. Flange face finish shall be serrated or smooth as indicated in Valve
Data Sheet. Smooth finish when specified shall be 125 to 200 AARH. In case of RTJ
flanges, the groove hardness shall be minimum 140 BHN.
c) Butt weld end preparation shall be as per ASME B16.25. The thickness of the pipe to
which the valve has to be welded shall be as indicated in Valve Data Sheet. Valves
shall be without transition pups. In case significant difference exists between
thickness of welding ends of valve and connecting pipe, the welding ends of valve
shall have bevel preparation as per ASME B31.4 or ASME B31.8, as applicable.
4.14 Design of weld end valves shall be such that during field welding operations, the soft
seals or plastic components of the valve (where ever used) are not liable to be
damaged. The manufacturer shall furnish necessary field welding instructions and
post-weld test procedure to demonstrate integrity and leak-tightness of valves after
field welding operations.
4.15 Valves shall be provided with ball position indicator and stops of rugged construction
at the fully open and fully closed positions.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 6 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
4.16 Full Bore Valves of nominal size DN 200mm(8) and Reduced Bore Valves of
nominal size DN 250mm(10) shall be equipped with support foot and lifting lugs.
Tapped holes and eye bolts shall not be used for lifting lugs. Height of support foot
shall be kept minimum. The location and size of support foot / lifting lugs shall
ensure unrestrictive operation of vent / drain valves.
4.17 Valve design shall be such as to avoid bimetallic corrosion between carbon steel and
high alloy steel components. Suitable insulation shall be provided as required.
4.18 When indicated in Material Requisition, valves shall have locking devices to lock the
valve either in full open (LO) or full close (LC) positions. Locking devices shall be
permanently attached to the valve operator and shall not interfere with operation of
the valve.
4.19 Valves shall be of fire resistant design as per API 607/BS:6755 (Part-II)/API 6FA, as
indicated in Valve Data Sheet.
4.20 Valves shall be provided with anti-static devices to ensure electrical continuity
between stem / ball and valve body. Valve design shall be such as to avoid bimetallic
corrosion between carbon steel and high alloy steel components. Suitable insulation
shall be provided as required.
4.21 Valves shall be suitable for either buried or above ground installation as indicated in
Valve Data Sheet.
4.22 When stem extension requirement is indicated in Valve Data Sheet, the valves shall
have the following provisions :
a) Valves provided with stem extension shall have water proof outer casing.
Length of stem extension shall be as indicated in Valve Data Sheet. The
length indicated corresponds to the distance between centreline of the valve
opening and the top of mounting flange for valve operating device (gear
operator / power actuator as applicable).
b) Vent and drain connections and sealant injection lines shall be terminated
adjacent to the valve operator by means of suitable piping anchored to the
valve body. Pipe used shall be API 5L Gr. B/ ASTM A 106 Gr. B, with Sch.
160. Fittings shall be ASTM A 105/ ASTM 234 Gr. WPB, Socket Welded, ANSI
class 6000.
c) Stem extension and stem housing design shall be such that the complete
assembly will form a rigid unit giving a positive drive under all conditions with
no possibility of free movement between valve body, stem extension or its
operator.
d) Outer casing of stem extension shall have 3/8 or NPT plugs at the top
and bottom, for draining and filling with oil to prevent internal corrosion.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 7 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
4.23 Operating Devices
a) Valves shall have a power actuator or manual operator as indicated in Valve Data
Sheet. In case of manual operator, valve sizes < DN 100mm (4 inches) shall be
wrench operated and valve sizes DN 150mm (6 inches) shall be gear operated.
Each wrench operated valve shall be supplied with wrench. Valve design shall be
such that damage due to malfunctioning of the operator or its controls will only
occur in the operator gear train or power cylinder and that damaged parts can be
replaced without the valve cover being removed.
b) The power actuator shall be in accordance with the Purchaser specification issued for
the purpose and as indicated in Valve and Actuator Data Sheet. Operating time shall
be as indicated in Valve Data Sheet. Valve operating time shall correspond to full
close to full open/full open to full close under maximum differential pressure
corresponding to the valve rating. For actuated valves, the actuator torque output
shall be 1.25 times the break torque required to operate the ball valve under the
maximum differential pressure corresponding to the valve class rating.
c) For manual operator of all valves, the diameter of the hand wheel or the length of
operating wrench shall conform to API 6D requirements and be such that under
maximum differential pressure, the total force required to operate the valve does not
exceed 350 N. Manufacturer shall also indicate the number of turns of hand wheel
(in case of gear operators) required for operating the valve from full open to full
close position.
d) Direction of operation of hand wheel or wrench shall be in clock-wise direction while
closing the valve. Hand wheels shall not have protruding spokes.
e) Gear operators, when provided, shall have a self locking provision and shall be fully
encased, in water proof/ splash proof/ dust proof/ weather proof enclosure and shall
be filled with suitable grease.
f) Operating devices shall be designed for easy operation of the valve under maximum
differential pressure corresponding to the valve rating.
4.24 All welds shall be made by welders and welding procedures qualified in accordance
with the provisions of ASME Section IX. The procedure qualification shall include
impact test and hardness test and shall meet the requirements of clauses 3.4 and
3.6 of this specification, respectively.
4.25 All welds shall be stress relieved in accordance with ASME Section VIII.
4.26 Repair by welding is not permitted for fabricated and forged body valves. However
repair by welding as per ASME B16.34 is permitted for cast body valves. Such repairs
shall be carried out at casting suppliers care only. Repair shall be carried out before
any heat treatment of casting is done. Repair welding procedure qualification shall
include impact test and hardness test and shall meet the requirements of clauses
3.4, 3.5 & 3.6 of this specification, respectively.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 8 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
4.27 The tolerance on internal diameter and out of roundness at the ends for welded end
valves shall be as per applicable connected pipe specification as indicated in Valve
Data Sheet.
4.28 When indicated in Material Requisition, valves shall have locking device to lock the
valve either in full open (LO) or full close (LC) positions. Locking devices shall be
permanently attached to the valve operator and shall not interfere with operation of
the valve.
4.29 Valve stem shall be capable of withstanding the maximum operating torque required
to operate the valve against the maximum differential pressure corresponding to
applicable class rating. The combined stress shall not exceed the maximum allowable
stresses specified in ASME Section VIII, Division I. In case of power actuated valves,
the valve stem shall be capable of withstanding maximum output of the power
actuator.
5.0 INSPECTION AND TESTS
5.1 The Manufacturer shall perform all inspection and tests as per the requirements of
this specification and the relevant codes, prior to shipment, at his works. Such
inspection and tests shall be, but not limited to, the following:
5.1.1 All valves shall be visually inspected. The internal and external surfaces of the valves
shall be free from any strikes, gouges and other detrimental defects. The surfaces
shall be thoroughly cleaned and free from dirt, rust and scales.
5.1.2 Dimensional check on all valves shall be carried out as per the Purchaser approved
drawings.
5.1.3 Chemical composition and mechanical properties shall be checked as per relevant
material standards and this specification, for each heat of steel used.
5.1.4 a) Non-destructive examination of individual valve material and components consisting
of, but not limited to castings, forgings, plate and assembly welds shall be carried
out by the Manufacturer.
b) Body castings of all valve shall be radiographically examined on 100% of the surface
of critical areas as per ASME B16.34. Procedure and acceptance criteria shall be as
per ASME B16.34. The extent of radiography shall be as follows:
ANSI class 150 - All sizes - Nil
ANSI class 300 - < DN 400mm (16) - Nil
> DN 450mm (18) - 100%
ANSI class 600 - All sizes - 100%
and above
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 9 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
All castings shall be wet magnetic particle inspected 100% of the internal surfaces.
Method and acceptance shall comply with ASME B.16.34.
c) All valves, with body fabricated from plates made or by forgings, shall be
ultrasonically examined in accordance with the procedure and acceptance standard
of Annexure E of ASME B16.34. All forgings shall be wet magnetic particle inspected
100% of the internal surfaces. Method and acceptance shall comply with ASME B
16.34
d) Bodies and bonnets made by welded assembly of segments of castings, forgings,
plates or combinations thereof shall be examined, as applicable, by methods of
clause 5.1.4 b) for cast components or clause 5.1.4 c) for forged components and
plates.
5.1.5 Full inspection by radiography shall be carried out on all welds of pressure containing
parts. Acceptance criteria shall be as per ASME B 31.4 or ASME B31.8, as applicable,
and API 1104.
5.1.6 Welds which in Purchasers opinion cannot be inspected by radiographic methods,
shall be checked by ultrasonic or magnetic particle methods and acceptance criteria
shall be as per ASME Section VIII, Division 1, Appendix 12 and Appendix 6,
respectively.
5.1.7 a) All finished wrought weld ends subject to welding in field shall be 100%
ultrasonically tested for lamination type defects for a distance of 50mm from the
end. Laminations shall not be acceptable.
b) Weld ends of all cast valves subject to welding in field shall be 100% radiographically
examined and acceptance criteria shall be as per ASME B16.34.
c) After final machining, all bevel surfaces shall be inspected by dye penetrant or wet
magnetic particle methods. All defects longer than 6.35 mm are rejected, as are
defects between 6.35 mm and 1.59mm that are separated by a distance less than 50
times their greatest length. Rejectable defects must be removed. Weld repair of
bevel surface is not permitted.
5.1.8 All valves shall be tested in compliance with the requirements of API 6D. During
pressure testing, valves shall not have sealant lines and other cavities filled with
sealant, grease or other foreign material. The drain, vent and sealant lines shall be
either included in the hydrostatic shell test or tested independently. Test pressure
shall be held for at least 30 minutes. No leakage is permissible during hydrostatic
testing. The body cavity self-relieving feature meeting the requirements of clause 4.8
of this specification shall also be checked.
5.1.9 A supplementary air seat test as per API 6D shall be carried out for all valves. A
bubble tight seal is required without the use of any sealant. No leakage is allowed.
Test pressure shall be held for at least 15 minutes.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 10 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
5.1.10 Manufacturer who intends bidding, must submit at bid stage, certificate and report
for successful fire type-tests for valves in accordance with API-607/ BS EN 10497 /
API 6FA, as applicable in Valve Data Sheet.
Failure to comply with this requirement shall be a cause of rejection of the offer.
5.1.11 Valves shall be subjected to Operational Torque Test as per supplementary test
requirement of API 6D (Appendix C, para C.3.3 Type-II) under hydraulic pressure
equal to maximum differential pressure corresponding to the valve rating.
For manually operated valves, it shall be established that the force required to
operate the valve does not exceed the requirements stated in clause 4.20(c) of this
specification.
5.1.12 Power actuated valves shall be tested after assembly of the valve and actuator at the
valve Manufacturers works. At least five open-close-open cycles without internal
pressure and five open-close-open cycles with maximum differential pressure shall be
performed on the valve actuator assembly. The time for full open to full close shall
be recorded during testing.
If required, the actuator shall be adjusted to ensure that the opening and closing
times are within the limits stated in Actuator Data Sheet issued for the purpose.
Hand operator provided on the actuator shall also be checked after the cyclic testing,
for satisfactory manual over-ride performance.
These tests shall be conducted on minimum one valve out of a lot of five(5) valves
of the same size, rating and the actuator model/ type. In case the tests do not meet
the requirements, retesting / rejection of the lot shall be decided by Purchasers
Inspector.
5.1.13 Subsequent to successful testing as specified in clause 5.1.11 and 5.1.12 above, one
(1) valve out of the total ordered quantity shall be randomly selected by the
Company Representative for cyclic testing as mentioned below :
a) The valve shall be subjected to at least 100 Open-Close-Open cycles with
maximum differential pressure corresponding to the valve rating.
b) Subsequent to the above, the valve shall be subjected to hydrostatic test and
supplementary air seat test in accordance with clause 5.1.8 and 5.1.9.
In case this valve fails to pass these tests, the valve shall be rejected and two more
valves shall be selected randomly and subjected to testing as indicated above. If
both valves pass these tests, all valves manufactured for the order (except the valve
that failed) shall be deemed acceptable. If either of the two valves fails to pass these
tests, all valves shall be rejected or each valve shall be tested at the option of
manufacturer.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 11 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
Previously carried out test of similar nature shall be considered acceptable if the
same has been carried out by Manufacturer in last two years. Valves of two sizes
below and two sizes above the size of valve previously tested, and rating similar or
one rating lower of valve tested previously, shall be qualified.
5.1.14 Checks shall be carried out to demonstrate that the dissimilar metal used in the
valves are successfully insulated as per the requirement of clause 4.17 of this
specification.
5.1.15 When indicated in Valve Data Sheet, valves shall be subjected to anti-static testing
as per supplementary test requirement of API 6D.
5.2 Purchaser reserves the right to perform stage-wise inspection and witness tests as
indicated in clause 5.1 above at Manufacturers works prior to shipment.
Manufacturer shall give reasonable access and facilities required for inspection to the
Purchasers Inspector.
Purchaser reserves the right to require additional testing at any time to confirm or
further investigate a suspected fault. The cost incurred shall be to Manufacturers
account.
In no case shall any action of Purchaser or his Inspector relieve the Manufacturer of
his responsibility for material, design, quality or operation of valves.
Inspection and tests performed/ witnessed by the Purchasers Inspector shall in no
way relieve the Manufacturers obligation to perform the required inspection and
tests.
6.0 EXTENT OF INSPECTION & TESTING
6.1 Purchasers Inspector shall perform inspection and witness tests on all valves or as
indicated in the Quality Assurance Plan (QAP) attached with this specification.
6.2 The hydrostatic testing and cyclic opening and closing of the valves with the
operator shall be witnessed by Purchasers Inspector.
7.0 TEST CERTIFICATES
7.1 Manufacturer shall submit the following certificates :
a) Mill test certificates relevant to the chemical analysis and mechanical
properties of the materials used for valve construction as per the relevant
standards.
b) Test certificates on hydrostatic and pneumatic tests complete with records of
timing and pressure of each test.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 12 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
c) Test reports on radiograph and ultrasonic inspection.
d) Test report on operation of valves conforming to clause 5.1.11 and 5.1.12 of
this specification.
e) All other test reports and certificates as required by API 6D and this
specification.
The certificates shall be valid only when signed by Purchasers Inspector. Only those
valves which have been certified by Purchasers Inspector shall be despatched from
Manufacturers works.
8.0 PAINTING, MARKING & SHIPMENT
8.1 Valve surface shall be thoroughly cleaned, freed from rust and grease and applied
with sufficient coats of corrosion resistant paint. Surface preparation shall be carried
out by shot blasting to SP-6 in accordance with Steel Structures Painting Council
Visual Standard SSPC-VIS-1. For valves to be installed underground, when
indicated in Valve Data Sheet, the external surfaces of the buried portion of valves
shall be painted with three coats of suitable coal tar epoxy resin with a minimum dry
film thickness of 300 microns.
8.2 Manufacturer shall indicate the type of corrosion resistant paint used, in the
drawings submitted for approval.
8.3 All valves shall be marked as per API 6D. The units of marking shall be metric
except Nominal Diameter which shall be in inches. Marking shall be done by die-
stamping on the bonnet or on the housing. However, for buried valves the marking
shall be done on the above ground portion of the stem housing only.
8.4 Valve ends shall be suitably protected to avoid any damage during transit. All
threaded and machined surfaces subject to corrosion shall be well protected by a
coat of grease or other suitable material. All valves shall be provided with suitable
protectors, for flange faces, securely attached to the valves. Bevel ends shall be
protected with metallic or high impact plastic bevel protectors.
8.5 All sealant lines and other cavities of the valve shall be filled with sealant before
shipment.
8.6 Packaging and shipping instructions shall be as per API 6D.
8.7 On packages, following shall be marked legibly with suitable marking ink :
a) Order Number
b) Manufacturers Name
c) Valve Size and Rating
d) Tag Number
e) Serial Number
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 13 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
9.0 SPARES & ACCESSORIES
9.1 Manufacturer shall furnish list of recommended spares and accessories for valves
required during start-up and commissioning and supply of such spares shall be
included in the price quoted by Manufacturer.
9.2 Manufacturer shall furnish list of recommended spares and accessories required for
two years of normal operation and maintenance of valves.
9.3 Manufacturer shall quote for spares & accessories as per Material Requisition.
10.0 DOCUMENTATION
10.1 At the time of bidding, Manufacturer shall submit the following documents :
a) General arrangement/assembly drawings showing all features and relative
positions and sizes of vents, drains, gear operator / actuator, painting,
coating and other external parts together with overall dimensions.
b) Sectional drawing showing major parts with reference numbers and material
specification. In particular, a blow-up drawing of ball-seat assembly shall be
furnished complying the requirement of clause 4.5 of this specification.
c) Reference list of similar ball valves manufactured and supplied in last five
years indicating all relevant details including project, year, client, location,
size, rating, service etc.
d) Torque curves for the power actuated valves along with the break torque and
maximum allowable stem torque. In addition, sizing criteria and torque
calculations shall also be submitted for power actuated valves.
e) Descriptive technical catalogues of the Manufacturer.
f) Installation, Operational and Maintenance Manual.
g) Copy of valid API 6D certificate.
h) Details of support foot, including dimensions and distance from valve centre
line to bottom of support foot.
i) Quality Assurance Plan enclosed with this tender duly signed, stamped and
accepted.
j) Clause wise list of deviations from this specification, if any.
k) List of recommended spares required during start-up and commissioning.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 14 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
l) List of recommended spares required for 2 years of normal operation and
maintenance.
IMPORTANT
The drawings to be submitted alongwith the bid shall be in total compliance
with the requirement of technical specification and data sheets of the
valves with no exception & deviation.
10.2 Within two weeks of placement of order, the Manufacturer shall submit six copies of,
but not limited to, the following drawings, documents and specifications for
Purchasers final approval :
a) Detailed sectional arrangement drawings showing all parts with reference
numbers and material specifications as referred to in clause 10.1 above.
b) Assembly drawings with overall dimensions and features. Drawing shall also
indicate the number of turns of hand wheel (in case of gear operators)
required for operating the valve from full open to full close position and the
painting scheme. Complete dimensional details of support foot (where
applicable) shall be indicated in these drawings as referred to in clause 10.1
above.
c) Welding, heat treatment and testing procedures.
d) Details of corrosion resistant paint to be applied on the valves.
e) Design calculation for Pressure containing parts.
f) Procedure for cyclic testing.
Manufacture of valves shall commence only after approval of the above
documents. Once the approval has been given by Purchaser, any changes in
design, material and method of Manufacture shall be notified to Purchaser
whose approval in writing of all changes shall be obtained before the valve is
manufactured.
10.3 Within 30 days from the approval date, Manufacturer shall submit to Purchaser one
reproducible and six copies of the approved drawings, documents and specifications
as listed in clause 10.2 above.
10.4 Prior to shipment, Manufacturer shall submit one reproducible and six copies of the
following:
a) Test certificates as per clause 7.0 of this specification.
b) Manual for installation, erection, maintenance and operation instructions,
including a list of recommended spares for the valves.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 15 of 15
TITLE BALL VALVE MEC/ TS/ 05/ 21/ 002 REVISION : 0
EDITION : 1
10.5 All documents shall be in English language.
11.0 GUARANTEE
11.1 Manufacturer shall guarantee that the materials and machining of valves and fittings
comply with the requirements in this specification and in the Purchase Order.
11.2 Manufacturer is bound to replace or repair all valve parts which should result
defective due to inadequate engineering or to the quality of materials and
machining.
11.3 If valve defect or malfunctioning cannot be eliminated, Manufacturer shall replace
the valve without delay,
11.4 Any defect occurring during the period of Guarantee shall be attended to by making
all necessary modifications and repair of defective parts free of charge to the
Purchaser as per the relevant clause of the bid document.
11.5 All expenses shall be to Manufacturers account.
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
PROCESS & PIPING DESIGN SECTION
MECON LIMITED
DELHI - 110 092
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
(NB 2)
SPECIFICATION NO.: MEC/TS/05/62/003, Rev-2
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 1 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
C O N T E N T S
Sl.No. Description Page No.
1.0 SCOPE 2
2.0 REFERENCE DOCUMENTS 2
3.0 MATERIALS & TEST PROCEDURES 3
4.0 DESIGN & CONSTRUCTION 4
5.0 INSPECTION & TESTS 7
6.0 EXTENT OF INSPECTION & TESTING 9
7.0 TEST CERTIFICATES 9
8.0 PAINTING, MARKING & SHIPMENT 10
9.0 SPARES & ACCESSORIES 10
10.0 DOCUMENTATION 11
11.0 GUARANTEE 12
PREPARED BY :
Gurdeep Singh
Date
CHECKED BY :
A.K. Sarkar
Date
APPROVED BY :
A.K. Johri
Date
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 2 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
1.0 SCOPE
This specification covers the minimum requirements for design, manufacture and supply
of carbon steel plug valves of size DN 50mm (2") and above and ANSI Class 150# thru
900# for use in onshore pipeline systems handling non sour hydrocarbons in liquid phase
or gaseous phase including Liquefied Petroleum Gas (LPG).
2.0 REFERENCE DOCUMENTS
2.1 All valves shall be manufactured and supplied in accordance with the Twenty Second
Edition, J anuary, 2002, or the latest edition of American Petroleum Institute (API)
Specification 6D, twenty first edition, 1994 including supplement 1 & 2 thereof with
additions and modifications as indicated in the following sections of this specification.
2.2 Reference has also been made in this specification to the latest edition of the following
Codes, Standards and Specifications :
ASME B 16.5 : Pipe flanges and flanged fittings
ASME B 16.25 : Buttwelding ends
ASME B 16.34 : Valves Flanged, threaded and welding end
ASME B16.47 : Large diameter steel flanges
ASME B 31.3 : Chemical & process plant piping system
ASME B 31.4 : Liquid transportation systems for hydrocarbons and
other liquids
ASME B 31.8 : Gas transmission and distribution piping systems
ASME Sec.VIII : Boiler and pressure vessel code
ASTM A 370 : Standard test methods and definitions for mechanical
testing of steel products
ASTM B 733 : Autocatalytic nickel phosphorous coating on metals
API 6FA : Fire test for valves
API 1104 : Welding of pipelines and related facilities
BS:6755 (Part-II) : Testing of valves Specification for fire type - testing
requirements
MSS-SP-6 : Standard finishes for contact faces of pipe flanges and
connecting-end flanges of valves and fittings
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 3 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
MSS-SP-44 : Steel pipeline flanges
SSPC-VIS-1 : Steel structures painting council-visual standard
2.3 In case of conflict between the requirements of this specification, API 6D and the
Codes, Standards and Specifications referred in clause 2.2 above, the requirements of
this specification shall govern. Order of precedence shall be as follows :
Data Sheets
This Specification
API 6D Specification
Other Referred Codes & Standards
Manufacturers Standard
3.0 MATERIALS & TEST PROCEDURES
3.1 Material for major components of the valves shall be as indicated in Valve Data Sheet.
Other components shall be as per Manufacturer's standard which will be subject to
approval by Purchaser.
3.2 Carbon steel used for the manufacture of valves shall be fully killed.
3.3 Chemical composition (check analysis) of valve end connection which are subject to
further welding by Purchaser shall meet the following requirements for each heat of steel
used:
a) Carbon : 0.22% (max.)
b) Manganese : 1.70 % (max.)
c) Silicon : 0.55 % (max.)
d) Phosphorus : 0.030 % (max.)
e) Sulphur : 0.030 % (max.)
Total percentage of Vanadium, Niobium and Titanium shall not exceed 0.20. Residual
elements shall not exceed the following limits :
a) Nitrogen : 0.019 %
b) Nickel : 0.30 %
c) Copper : 0.20 %
d) Aluminum : 0.070 %
e) Chromium : 0.15 %
f) Molybdenum : 0.05 %
Carbon equivalent (CE) as calculated by the following shall not exceed 0.45%.
Mn Cr + Mo + V Ni + Cu
CE = C + -------- + ---------------------- + ---------------
6 5 15
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 4 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
3.4 For valves specified for Gas Service or high vapour pressure liquid service, charpy V-
Notch test on each heat of base material shall be conducted as per API 6D, for all
pressure containing parts such as body, end flanges and welding ends as well as the
bolting material for pressure containing parts. Unless specified otherwise in Valve Data
Sheets, the Charpy impact test shall be conducted at 0C. The Charpy impact test
specimen shall be taken in the direction of principal grain flow and notched perpendicular
to the original surface of plate or forging.
Unless specified otherwise in Valve Data Sheets, the minimum average absorbed
energy per set of three specimens shall be 27 J with an individual minimum per
specimen of 22 J .
3.5 For valves specified for Gas Service or high vapour pressure liquid service, the hardness
of base material of body and principal parts of the valve such as plug, stem, etc., shall
not exceed 22 RC.
3.6 Plug for valve size DN 200mm (8) and above or as specified in Valve Data Sheets shall
have Electroless Nickel Plating (ENP) or equivalent. The hardness of plating shall be
minimum 50 RC. Manufacturer shall ensure that the adhesive strength of plating is
sufficient so as to prevent peeling of plating during operation of the valve.
3.7 All process-wetted parts, metallic and non-metallic, shall be suitable for the fluids and
service specified by the Purchaser. The service gas composition when applicable shall be
as given in Annexure-I.
4.0 DESIGN & CONSTRUCTION
4.1 The Manufacturer shall have a valid license to use API 6D monogram for manufacture of
Plug Valves.
4.2 Valve pattern shall be short, regular or venturi as specified in the following table:
Class Size Range, NB mm (inch) Pattern
50-100 (2-4) Short
150 150-300 (6-12) Regular
350 (14) & above Venturi
50-100 (2-4) Short
300 150-250 (6-10) Regular
300 (12) & above Venturi
50-250 (2-10) Regular
600 300 (12) & above Venturi
50-250 (2-10) Regular
900 300 (12) & above Venturi
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 5 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
4.3 Valve shall have an inherent feature using line pressure to ensure that the line pressure
cannot cause taper locking of the plug/ plug movement into taper i.e. valves shall be of
pressure balanced design.
4.4 Cover shall be bolted to the body and screwed connections are not acceptable.
4.5 Soft seats to achieve a seal between plug and body are not permitted.
4.6 All valves shall have provisions for secondary sealant injection under full line pressure for
seat and stem seals. Sealant injection points shall be provided with a ball type check
valve or needle valve to replace the sealant injection fitting under full line pressure.
4.7 Valves shall have vent and drain connections as per API 6D.
4.8 When specified in the Valve Data Sheet, valves shall be designed to withstand a
sustained internal vacuum of at least one milli-bar in both open and closed position.
4.9 Valve design shall ensure repair of gland packing under full line pressure.
4.10 a) Valve ends shall be either flanged or butt welded or one end flanged and one end butt
welded as indicated in Valve Data Sheet. Flanges of the flanged end cast/ forged body
valves shall be integrally cast/forged with the body of valve. Face-to-face/ end-to-end
dimensions shall conform to API 6D.
b) Flanged end shall have dimensions as per ASME B16.5 for valve sizes upto DN 600mm
(24 inches) excluding DN 550mm (22 inches) and as per MSS-SP-44 for valve sizes DN
550mm (22 inches) & for DN 650mm (26 inches) and above. Flange face shall be either
raised face or ring joint type as indicated in Valve Data Sheet. Flange face finish shall be
serrated or smooth as indicated in Valve Data Sheet. Smooth finish when specified shall
be 125 to 200 AARH. In case of RTJ flanges, the groove hardness shall be minimum 140
BHN.
c) Butt weld end preparation shall be as per ASME B16.25. The thickness of the pipe to
which the valve has to be welded shall be as indicated in Valve Data Sheet. Valves
shall be without transition pups. In case significant difference exists between
thickness of welding ends of valve and connecting pipe, the welding ends of valve
shall have bevel preparation as per ASME B31.4 or ASME B31.8, as applicable.
4.11 Valves shall be provided with position indicator and stops at the fully open and fully
closed positions.
4.12 Valves of size DN 200mm (8) and above shall be equipped with lifting lugs. Tapped
holes and eye bolts shall not be used for lifting lugs.
4.13 Valves shall have locking devices to be locked either in full open or full close position
when indicated in the Valve Data Sheets. Locking devices shall be permanently attached
to the valve operator and shall not interfere with operation of the valve.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 6 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
4.14 Valves shall be of fire safe design as per BS:6755 (Part-II)/ API 6FA, if indicated in Valve
Data Sheet.
4.15 Valves shall be suitable for either buried or above ground installation as indicated in the
Valve Data Sheet.
4.16 Valves with stem extension, when indicated in Valve Data Sheet shall have following
provisions :
a) Valves provided with stem extension shall have water proof outer casing. Length
of stem extension shall be as indicated in the Valve Data Sheet. The length
indicated corresponds to the distance between the centreline of the valve opening
and the top of the mounting flange for valve operating device (gear operator/
power actuator as applicable).
b) Vent and drain connections shall be terminated adjacent to the valve operator by
means of suitable piping anchored to the valve body. Pipe used shall be API 5L
Gr. B/ ASTM A106 Gr. B, with Sch. 160. Fittings shall be ASTM A105/ ASTM A
234 Gr. WPB, Socket Welded, ANSI class 6000.
c) Sealant injection lines shall be extended and terminated adjacent to the valve
operator in manner as indicated in (b) above.
d) Stem extension and stem housing design shall be such that the complete
assembly will form a rigid unit giving a positive drive under all conditions with no
possibility of free movements between valve body stem extension or its operator.
e) Outer casing of stem extension shall have 3/8" or " NPT plugs at the top and
bottom, for draining and filling with oil to prevent internal corrosion.
4.17 Operating Devices
a) Valves shall have a power actuator or manual operator as indicated in the
Valve Data Sheet. Manual operated valves of size < DN 100mm (4) shall be
wrench operated and valves of sizes > DN 150mm (6") shall be gear operated.
Each wrench operated valve shall be supplied with wrench. Valve design shall be
such that damage due to malfunctioning of the operator or its controls will only
occur in the operator gear train or power cylinder and damaged parts can be
replaced without the bonnet being removed.
b) The power actuator shall be in accordance with the specification issued for the
purpose and as indicated in the valve and actuator data sheet. Operating time
shall be as indicated in valve data sheet. Valve operating time shall correspond to
full close to full open / full open to full close under maximum differential pressure
corresponding to the valve rating. For actuated valves, the actuator torque shall
be atleast 1.25 times the maximum torque required to operate the valve under
maximum differential pressure corresponding to the valve class rating.
c) Operating device shall be designed for easy operation of valve under maximum
differential pressure corresponding to the valve rating.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 7 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
d) For manual operation of all valves, the diameter of the hand wheel or the length
of operating lever shall be such that under the maximum differential pressure, the
total force required to operate the valve does not exceed 350 N. Manufacturer
shall also indicate the number of turns of hand wheel (in case of gear operator),
required to operate the valve from full open to full close position.
e) Direction of operation of hand wheel or wrench shall be in clock-wise direction
while closing the valve. Hand wheels shall not have protruding spokes.
f) Gear operators, if specified, shall have a self locking provision and shall be fully
encased in waterproof/ dustproof/ weatherproof/ splashproof enclosure and shall
be filled with suitable grease.
4.18 Repair by welding is not permitted for fabricated and forged body valves. However repair
by welding as per ASME B16.34 is permitted for cast body valves. Repair shall be carried
out before any heat treatment of casting is done. Repair welding procedure qualification
shall also include impact test and hardness test when required as per Clause 3.4 and 3.6
of this specification and shall meet the requirements as specified therein.
4.19 The tolerance on internal diameter and out of roundness at the ends for welded ends
valves shall be as per connected pipe specification as indicated in the Valve Data Sheet.
4.20 Valve stem shall be capable of withstanding the maximum operating torque required to
operate the valve against the maximum differential pressure corresponding to applicable
class rating. The combined stress shall not exceed the maximum allowable stresses
specified in ASME section VIII, Division-1.
For Power Actuated Valves, the valve stem shall be designed for maximum output torque
of the selected power actuator (including gear box, if any) at the valves stem.
5.0 INSPECTION & TESTS
5.1 The Manufacturer shall perform all inspection and tests as per the requirements of this
specification and the relevant codes, prior to shipment at his works. Such inspection and
tests shall be, but not limited to, the following :
5.1.1 All valves shall be visually inspected.
5.1.2 Dimensional check shall be carried out as per the Purchaser approved drawings.
5.1.3 Chemical composition and mechanical properties shall be checked as per relevant
material standards and this specification, for each heat of steel used.
5.1.4 a) Non-destructive examination of individual valve material and component
consisting of but not limited to castings, forgings, plates and assembly welds shall
be carried out by the Manufacturer.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 8 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
b) Valves castings shall be radiographically examined at the cover and body portion,
seat location, flanged body ends and circumference of ends to be field welded.
Procedure and acceptance criteria shall be as per ASME B16.34. The extent of
radiography shall be as follows :
ANSI Class 150 - All Sizes - Nil
ANSI Class 300 - DN 400mm (16") - Nil
DN 450mm (18") - 100%
ANSI Class 600 - All Sizes - 100%
and above
All castings shall be wet magnetic particle inspected 100 % of the internal
surfaces. Method and acceptance shall comply with ASME B16.34.
c) Valve forgings shall be examined by ultrasonic method. Inspection procedure and
acceptance criteria shall be as per Annexure E of ASME B16.34.
5.1.5 Areas which, in Purchaser's Inspectors opinion, cannot be inspected by radiographic
methods shall be checked by ultrasonic or magnetic particle methods and acceptance
criteria shall be as per ASME Sec-VIII, Division I, Appendix 12 and Appendix 6
respectively.
5.1.6 a) Weld ends of all cast valves shall be 100% radiographically examined and
acceptance criteria shall be as per ASME B16.34.
b) After final machining all bevel surfaces shall be inspected by dye penetrant, or
wet magnetic particle methods. Any defects longer than 6.35mm shall be rejected
and also defects between 6.35mm and 1.59mm that are separated by a distance
less than 50 times their greatest length. Weld repair of bevel surface is not
permitted. Rejectable defects must be removed.
c) All finished wrought weld ends subject to welding in the field shall be 100%
ultrasonically tested for lamination type defects for a distance of 50mm from the
end. Laminations shall not be acceptable.
5.1.7 All valves shall be tested in compliance with the requirements of API 6D. Hydrostatic
shell testing shall ensure that the whole of the shell is subjected to the test pressure. If
necessary, the empty shell shall be pressure tested prior to assembly of the plug. The
drain, vent and sealant lines shall be either included in the hydrostatic shell test or tested
independently. No leakage is permissible during hydrostatic testing.
5.1.8 A supplementary air seat test as per API 6D shall be carried out for all valves. No leakage
is allowed. Test pressure shall be held for at least 15 minutes.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 9 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
5.1.9 Manufacturer who intends bidding must submit at bid stage, certificate and report for
successful fire safe tests for all types of valves in accordance with BS:6755 (Part-II)/ API
6FA, as applicable in Valve Data Sheet.
Failure to comply with the requirement shall be a cause of rejection of the offer.
5.1.10 Valve shall be subjected to Operational Torque Test as per supplementary test
requirement of API 6D under hydraulic pressure equal to the maximum differential
pressure corresponding to the valve rating. The maximum handwheel force shall not
exceed 350 N.
5.1.11 Power actuated valves shall be tested after assembly at the valve Manufacturer's works.
Actuator shall be capable to allow minimum five consecutive "opening" and "closing"
cycles. To achieve this, the Manufacturer shall provide "closing" and "opening"
operations. This test shall be conducted on one valve out of a lot of five valves of the
same size, rating and actuator type. In case the test result dose not meet the
requirements, retesting/ rejection of the lot shall be as decided by Purchaser's Inspector.
The actuator shall be adjusted to ensure that opening and closing time is within the limits
stated in Actuator Data Sheet issued for the purpose.
The hand operator installed on the actuator shall also be checked after the cyclic testing,
for satisfactory manual over-ride performance.
5.2 Purchaser reserves the right to perform stagewise inspection and witness tests as
indicated in para 5.1 at Manufacturer's works prior to shipment. Manufacturer shall give
reasonable access and facilities required for inspection to Purchaser's Inspector.
Purchaser reserves the right to request additional testing at any time to confirm or further
investigate a suspected fault. If the suspected fault is confirmed, the cost incurred shall
be to Manufacturer's account.
In no case shall any action of Purchaser or his representative relieve the Manufacturer of
his responsibility for material, design, quality or operation of valves.
Inspection and tests performed/ witnessed by the Purchaser's Inspector shall in no way
relieve the Manufacturer's obligation to perform the required inspection and tests.
6.0 EXTENT OF INSPECTION & TESTING
6.1 Purchaser's Inspector shall perform inspection and witness test on all valves as indicated
in the Quality Assurance Plan (QAP) attached with this specification.
6.2 The hydrostatic testing and cyclic opening and closing of the valves with the operator
shall be witnessed by Purchaser's Inspector.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 10 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
7.0 TEST CERTIFICATES
7.1 Manufacturer shall submit the following certificates :
a) Mill test certificates relevant to the chemical analysis and mechanical properties of
the materials used for valve construction as per the relevant standards.
b) Test certificates on hydrostatic and pneumatic test complete with records of
timing and pressure of each test.
c) Test reports conforming to clause 5.1.9 of this specification, if applicable.
d) Test reports on radiographic and ultrasonic inspection.
e) Test reports on operation of valves conforming to clause 5.1.10 and 5.1.11 of this
specification.
f) All other test reports and certificates as required by API 6D and this specification.
The certificates shall be valid only when signed by Purchaser's Inspector. Only those
valves which have been certified by Purchasers Inspector shall be dispatched from
Manufacturer's works.
8.0 PAINTING, MARKING & SHIPMENT
8.1 Valve surface shall be thoroughly cleaned, freed from rust and grease and applied with
sufficient coats of corrosion resistant paint. Surface preparation shall be carried out by
shot blasting to SP 6 in accordance with "Steel Structures Painting Council - Visual
Standard - SSPC-VIS-1". For the valves to be installed underground, when indicated in
Valve Data Sheet, external surfaces of the buried portion of valves shall be painted with
three coats of suitable coal tar epoxy resin with a minimum dry film thickness of 300
microns.
8.2 Manufacturer shall indicate the type of corrosion resistant paint used, in the drawings
submitted for approval.
8.3 All valves shall be marked as per API 6D. The units of marking shall be metric except
Nominal Diameter which shall be in inches. Marking shall be done by die-stamping on the
bonnet or on the housing. However for buried valves the marking shall be done on the
above ground portion of the stem housing only.
8.4 Valve ends shall be suitably protected to avoid any damage during transit. All threaded
and machined surfaces subject to corrosion shall be well protected by a coat of grease or
other suitable material. All valves shall be provided with suitable protectors, for flange
faces, securely attached to the valves. Bevel ends shall be protected with metallic bevel
protectors.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 11 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
8.5 All sealant lines and other cavities of the valves shall be filled with sealant before
shipment.
8.6 Packaging and shipping instructions shall be as per API 6D.
8.7 Packages shall be marked legibly, with suitable marking ink, the following.
a) Order Number
b) Manufacturer's Name
c) Valve Size and Rating
d) Tag Number
e) Serial Number
9.0 SPARES & ACCESSORIES
9.1 Manufacturer shall recommend and quote separately the spares for valves required for
commissioning and two years of normal operation. List of such spares without price shall
be indicated alongwith technical bid and separately with price.
9.2 Manufacturer shall recommend and quote unit price separately for the accessories (like
wrench, sealant injector, etc.), sealant and special tools required for maintenance of
valves.
10.0 DOCUMENTATION
10.1 At the time of bidding, the bidder shall submit the following documents :
a) General arrangement/ assembly drawings showing all features and relative
positions & sizes of vents, drains, gear box & other external parts together with
overall dimensions.
b) Sectional drawing showing major parts with reference numbers and material
specification.
c) Reference list of similar plug valves manufactured and supplied in last five years,
indicating all relevant details including project, year, client, location, size rating,
service, etc.
d) Torque curves for the power actuated valves alongwith break torque and
maximum allowable stem torque. In addition, sizing criteria and torque
calculations shall also be submitted for power actuated valves.
e) Descriptive technical catalogues of the Manufacturer.
f) Copy of valid API 6D certificate, wherever applicable.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 12 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
g) Details of support foot, including dimensions and distance from valve centre
line to bottom of support foot.
h) Quality Assurance Plan enclosed with this tender duly signed, stamped and
accepted.
IMPORTANT
The drawings to be submitted alongwith the bid shall be in total compliance
with the requirement of technical specification and data sheets of the valves
with no exception & deviation.
10.2 Within two weeks of placement of order, the manufacturer shall submit six copies of, but
not limited to, the following drawings, documents and specifications for approval :
a) Design drawings and relevant calculations for pressure containing parts and other
principle parts.
b) Detailed sectional arrangement drawing showing all parts with reference numbers
and materials specification.
c) Assembly drawings with overall dimensions & clearances required and showing all
features. Drawing shall also indicate the numbers of turns of handwheel (in case
of gear operator) required for operating the valve from full open to full close
position and the painting scheme.
d) Welding, heat treatment, testing and quality control procedures.
e) Details of corrosion resistant paint to be applied on the valves.
f) Design calculation for pressure containing parts.
Manufacture of valves shall commence only after approval of the above documents. Once
approval has been given by Purchaser, any change in design, material and method of
manufacture shall be notified to the Purchaser, whose approval in writing for all changes
shall be obtained before the valves are manufactured.
10.3 Within 30 days from the approval date, Manufacturer shall submit one reproducible and
six copies of the approved drawings, documents and specification as listed in clause 10.2
of this specification.
10.4 Prior to shipment, Manufacturer shall submit one reproducible and six copies of following
:-
a) Test certificates as listed in clause 7.0 of this specification.
b) Manual for installation, erection instructions, maintenance and operation
instructions, including a list of recommended spares for the valves.
10.5 All documents shall be in English Language.
MECON LIMITED
Delhi
PROCESS & PIPING
DESIGN SECTION
TECHNICAL SPECIFICATION
FOR
PLUG VALVES
TECHNICAL SPECIFICATION NO. : MEC/TS/05/62/003 REV-2 Page 13 of 13
D:\old data\Vijyant\Spec master\Final Spec\SUPPLY ITEMS\03 PLUGVALVE\003 - Plug Valves - TS-R2.doc
11.0 GUARANTEE
11.1 Manufacturer shall guarantee that the materials and machining of valves and fittings
comply with the requirements in this specification and in the Purchase Order.
11.2 Manufacturer is bound to replace or repair all valve parts which should result defective
due to inadequate engineering or to the quality of materials and machining.
11.3 If valve defect or malfunctioning cannot be eliminated, Manufacturer shall replace the
valve without delay.
11.4 Any defect occurring during the period of Guarantee shall be attended to by making all
necessary modifications and repair of defective parts free of charge to the Purchaser as
per the relevant clause of the bid document.
11.5 All expenses shall be to Manufacturers account.
Page 1 of 7
TECHNI CAL NOTES FOR GATE & GLOBE
VALVES
Page 2 of 7
(A) TECHNICAL NOTES FOR GATE & GLOBE VALVES
1.0 General
1.1 Valves shall be designed, manufactured, tested, inspected, marked and
supplied as per the specifications, applicable design standards & codes and
manufacturing standards (latest editions) as specified.
1.2 Material test certificates (Physical property, Chemical composition & Heat
treatment report) of the pressure containing parts shall be furnished for the
valves supplied. Material test certificates of other parts shall also be furnished
for verification during inspection.
1.3 For heavy valves, provision for lifting shall be made by way of lugs, eyebolts,
or similar standard devices.
1.4 Unless otherwise stated, all flanged valves shall have end flanges integral
with valve body. Weld on flanges are not acceptable. Flange finish shall be
serrated finish 250 AARH (250 AARH to 500 AARH) or 125 AARH (125
AARH to 250 AARH) or 63 MRH (32 AARH to 63 AARH) as per valve
specification sheet.
1.5 For all weld end valves, with bevel end as per ANSI B 16.25, the bevel
contour shall be as follows:
Material
Wall Thickness Weld Contour
Carbon Steel (Except Low
Temp. Carbon Steel)
Upto 22 mm
> 22 mm
Figure 2 Type A
Figure 3 Type A
Alloy Steel Upto 10 mm Figure 4
Stainless Steel &
Low Temp Carbon Steel
> 10 mm & upto 25 mm
> 25mm
Figure 5 Type A
Figure 6 Type A
1.6 If an overlay weld-deposit is used for the body seat ring, seating surface, the
seat ring base material shall be at least equal to the corrosion resistance of
the materials of the shell.
1.7 For valve body/ bonnet, forging is acceptable where castings are specified but
not vice versa.
1.8 Material of construction of yoke shall be as a minimum equivalent to body/
bonnet material.
1.9 Stem shall be forged or machined from a forged bar. Castings are not
permitted except integral stem.
1.10 Stelliting/ hard facing by deposition shall have minimum 1.6mm thickness.
Renewable seat rings shall be seal welded.
1.11 Face to face dimension of flanged valves shall conform to ANSI B 16.10 to
the extent covered. For valves not covered in the ANSI specification,
Contractor shall furnish certified dimensional drawings.
Page 3 of 7
1.12 Flange dimensions of steel, alloy steel and stainless steel flanged valves
shall conform to ANSI B 16.5 for sizes up to 24 and API 605 for size 26
and above.
1.13 Flange dimensions for cast iron flanged valves shall conform to ANSI B
16.1 for size up to 24 class 125 and API 605 with flat face for sizes
greater than 24.
1.14 Unless otherwise mentioned, various valves should conform to following
standards / codes.
SW gate valves (1 1/2 and below) : API 602
SW Globe/Check valves (1 1/2 and below) : BS 5352
Flanged gate valves : API 600
Flanged Globe valves : BS 1873
Flanged check valves : BS 1868
Diaphragm valves : BS 5156
Butterfly valves : BS5155/AWVVA C504
1.15 Wherever stellite is specified, it means facing of seat and disc are welded by
Cr-Co-W alloy. Stellite facing shall maintain minimum hardness of 375 BHN at
high temperature.
1.16 All weld end valves shall have bevel ends as per ANSI B 16.25.
1.17 If an overlay weld deposit is used for the body seat ring or seating surface,
the seat ring base material shall be at least equal to corrosion resistance of
the material of the shell.
1.18 By Pass
- Unless otherwise noted, by-pass requirement for gate valves shall be
under -
150 Class : on sizes 26 and above
300 Class : on sizes 16 and above
600 Class : on sizes 6 and above
900 Class : on sizes 4 and above
1500 Class : on sizes 4 and above
2500 Class : on sizes 3 and above
- By-pass valve shall be a globe valve.
- Contractor shall supply the by-pass valve duly tested and fitted to the
main valve. By-pass attachment to the main valve body shall not be
screwed. All fillet welds for by-pass installation shall be 100%
examined by DP / MP test.
1.19 Spiral wound bonnet gasket is to be provided with inner / outer ring except
when encapsulated gaskets type body bonnet joints are employed. Outer ring
may be avoided in case of non-circular spiral wound gasket used in 150#
Page 4 of 7
valve provided the outermost layer of spiral touches the bolts ascertaining the
centering.
1.20 Pressure Test
- Valves covered under API codes shall be tested as per API 598 unless
otherwise specified in the applicable valve code.
- Valves covered under BS code shall be tested as per BS 6755 unless
otherwise specified in the applicable valve codes.
1.21 For all austenitic stainless valves, inter-granular corrosion test shall have to
be conducted as per following: -
- ASTM A 262 Practice E with acceptance criteria of 60 mils / year
(max.).
OR
- ASTM A 262 practice E with acceptance criteria of No cracks as
observed from 20X magnification U & Microscopic structure to be
observed from 250X magnification.
1.22 When specifically asked for high temperature application of some grades of
austenitic stainless steel (like SS 309, 310, 316, 316H etc.) ASTM A 262
practice C with acceptance criteria 15 MILS/YEAR shall have to be
conducted. When testing is conducted as per practice E photograph of
microscopic structure shall be submitted for record.
1.23 For the IGC test as described in 1.16.1 & 1.16.2 two sets of samples shall be
drawn from each solution treatment lot, one set corresponding to highest
carbon content and other set corresponding to the highest rating/ thickness.
2.0 OPERATION
2.1 Valves shall be supplied with gear operations based on the following
requirements:
Valve Types
Class Size Requiring Gear
Operation
150 14 and larger
300 14 and larger
600 12 and larger
900 6 and larger
1500 3 and larger
Gate & Diaphragm Valves
2500 3 and larger
900 6 and larger
1500 3 and larger
Globe Valves
2500 3 and larger
Butterfly Valves 150 10 and larger
300 6 and larger
Page 5 of 7
2.2 Gear operator shall be as under with position indicators for open / close
positions, with limit stops.
For Gate / Globe / Diaphragm
Valves
Totally enclosed bevel gear in
grease case with grease nipples/
plug
For Butterfly Valves Totally enclosed helical worm gear
or combination of helical worm and
spur gear in grease case with
grease nipples/ plugs.
2.3 Gear operators shall be so designed to operate effectively with the differential
pressure across the closed valve equal to the cold non-shock pressure rating.
2.4 Butterfly valves even with wrench or lever operators shall have open and
closed position indicators with limit stops.
2.5 Hand wheel diameter shall not exceed 750 mm and effort to operate shall not
exceed 35 kg at hand wheel periphery. In case these limits cannot be
satisfied for any valve, a gear operation shall be provided.
3.0 INSPECTION AND TESTING
3.1 All valves and valves operators shall be subject to stage wise and final
inspection by third party inspection agency (at Contractors cost).
However, Company reserves the right to depute its authorized /
representative in addition to third party inspection agency. Minimum 15
days notice shall be given to Company for all shop inspection and testing.
3.2 All the mandatory shop tests and inspection required by the respective data
sheet and applicable standards & codes etc. shall be carried out.
3.3 The extent of inspection by shall be as under. However the exact extent with
hold points shall be decided during review of the inspection plan to be
submitted to Company as part of the post-order documentation.
3.4 Valves under NACE should follow the requirements of MR-01-75
FORGED VALVES
- Visual and dimensional inspection
- Review of material test certificates
- Any mandatory or supplementary test
- Hydrostatic test of all valves
- Strip check on 1% of total ordered quantity of valves at random to
verify compliance with specification requirements.
CAST STEEL VALVES
- Visual and dimensional inspection
- Review of material test certificates
Page 6 of 7
- Review of radiographs / radiographic reports and reports of any other
NDT tests, wherever applicable as per data sheets
- Any mandatory or supplementary tests
- Hydrostatic test 100% for body
- Strip check on 1% of total ordered quantity of valves at random to
verify compliance with specification requirements.
3.5 For motor /actuator operated valves, functional / operational checks as per
the requirements of the specifications shall be made on each valve.
4.0 RADIOGRAPHY OF CAST VALVES
4.1 When specifically not mentioned in individual data sheets, valves castings
shall undergo radiographic examination as specified hereunder:
MATERIAL
RATING SIZE RANGE RADIOGRAPHY
All 150# 24 and below Nil
150# 26 and above 100%
300# 16 and below Nil
300# 18 and above 100%
600# and above All sizes 100%
4.2 Radiography procedure areas of casting to be radiographed shall be as per
ANSI B 16.34 and acceptance criteria shall be as per ANSI B 16.34 Annexure
-B. However for areas of casting to be radiographed for types of valve not
covered in ANSI B 16.34, Contractor shall enclose details of areas to be
radiographed in line with ANSI B 16.34.
5.0 IBR VALVES
5.1 All valves described as IBR Valves shall be in accordance with the latest IBR
(Indian Boiler Regulations) as well as the other requirements specified in the
specification.
5.2 For BW / SW end carbon steel valves under IBR, the chemical composition
shall conform to the following:
Carbon (Max.) : 0.25%
Others (S, B, Mn) : As per IBR
Above composition is not applicable for non-IBR valves.
5.3 For all IBR Valves, test certificate in form III-C shall be furnished duly
signed by IBR inspection authority or an IBR approved representative.
5.4 All valves shall be painted red.
6.0 MARKING
6.1 Valves markings, symbols, abbreviations, etc. shall be in accordance with
Page 7 of 7
MSS-SP-25 or the standard referred to in the specifications as applicable
Manufacturers name, valve size and rating, material designation, nominal
size, direction of flow (if any) etc. shall be integral on the body.
6.2 Each valve shall have a corrosion resistant tag giving size and valve tag/code
no. securely attached on the valve body.
6.3 Paint or ink used for marking shall not contain any harmful metal or metal
salts such as zinc, lead or copper which may result in corrosive attack on
heating.
6.4 Carbon steel valves shall be painted with two coats of red oxide zinc
chromate primer.
6.5 All alloy steel high temp valves shall be painted with heat resistant silicone
paint suitable for intended temperature.
7.0 DESPATCH
7.1 Valves shall be dry, clean and free from moisture, dirt and loose
foreign material of any kind.
7.2 Valves shall be protected from rust, corrosion and any mechanical
damage during transportation, shipment, and storage.
7.3 Rust preventative applied on machined surfaces to be welded shall be
easily removable with a petroleum solvent or shall not be harmful to
welding.
7.4 Each end of valves shall be protected as follows:
Flange Face : Wood, plastic or metal cover
Beveled End : Wood, plastic or metal cover
SW / Screwed End : Plastics cap
7.5 End protectors to be used on flange faces shall be attached by at least
three bolts or wires through bolt holes and shall not be smaller than
the outside diameter of the flange. Plastic caps for SW / Screwed and
valves shall be press fit type.
7.6 End protectors to be used on beveled ends shall be securely attached.
SPECIFICATION
FOR
INSULATING JOINTS
SPECIFICATION NO.: MEC/ TS/ 05/ 21/ 009
(OIL & GAS SBU)
MECON LIMITED
DELHI 110 092
Edition : 1
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 1
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
C O N T E N T S
Sl.No. Description
1.0 SCOPE
2.0 REFERENCE DOCUMENTS
3.0 MATERIALS
4.0 DESIGN & CONSTRUCTION REQUIREMENTS
5.0 INSPECTION AND TESTS
6.0 TEST CERTIFICATES
7.0 PAINTING, MARKING AND SHIPMENT
8.0 GUARANTEE
9.0 DOCUMENTATION
PREPARED BY:
(Amit Lavania)
CHECKED BY:
(A.K. Gupta)
APPROVED BY:
(A.K. J ohri)
ISSUE DATE :
Oct. 2008
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 1 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
1.0 SCOPE
This specification cover the basic requirements for design manufacture, testing and
supply of carbon steel insulating joints to be installed in onshore pipeline systems
handling hydrocarbons in liquid or gaseous phase including Liquefied Petroleum Gas
(LPG).
2.0 REFERENCE DOCUMENTS
2.1 Reference has been made in this specification to the latest edition of, the following
Codes, Standards and Specifications.
a) ASME B 31.8 Gas Transmission & Distribution piping System
b) ASME B 31.4 Liquid transportation systems for hydrocarbons,
LPG, Anhydrous Ammonia and Alcohols
c) ASME B 16.5 Steel Pipe Flanges & Flanged Fittings
d) ASTM A 370 Mechanical testing of Steel Product
e) ANSI B 16.25 Butt Welding Ends
f) ASME Section Boiler & pressure Vessel Code viii & ix
g) API 1104 Standard for welding pipelines and Related
facilities.
h) SSPC-VIS-1 Steel Structures painting Council Visual Standard.
i) MSS-SP-53 Quality standard for steel castings and forgings
for valves flanges and fittings and other piping
components - magnetic particle examination
method.
j) MSS-SP-75 Specification for high test wrought welding
fittings.
k) NACE RP 0286 The electrical isolation of cathodically protected
pipelines.
2.2 In case of conflict between the requirements of this specification and any code,
Standard and Specification referred in Clause 2.1 above. Order of precedence shall be
as follows :
Data Sheets
This Specification
Other Referred Codes & Standards
Manufacturers Standard.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 2 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
3.0 MATERIALS
3.1 Material for the pressure containing parts of the insulating joints shall be as indicated
in the data sheets. Material for pups shall be equivalent or superior to the material of
connecting pipeline which is indicated in the data sheets. Other part shall be as per
manufacturer's standard suitable for the service condition indicated in Insulating J oint
Data Sheets and shall be subject to approval by purchaser.
All process-wetted parts, metallic & non-metallic shall be suitable for the
commissioning fluids & service specified by the purchaser. Manufacturer shall confirm
that all wetted parts are suitable for treated water/seawater environment, which may
be used during field testing.
3.2 Insulating joints which are subject to field welding by purchaser, shall have carbon
equivalent (CE) not exceeding 0.45 based on check analysis for each heat of steel
calculated according to the following formula :
CE = C + Mn/6 + (Cr+Mo+V)/5 + (Ni +Cu)/15
3.3 When specified in the IJ Data Sheet, charpy V-notch test shall be conducted on each
heat of base material, weld metal and heat affected zone of all pressure containing
parts such as body, welding ends in accordance with the impact test provisions of
ASTM A 370 at a temperature of 0 C. The charpy impact test specimens shall be taken
in the direction of principal grain flow and notched perpendicular to the original surface
of the plate of forging. Average impact energy value of three full sized specimens shall
be 27 joules. Minimum impact energy value of any one specimen shall not be less than
80% of the average impact energy specified. No specimen shall exhibit less than 80%
shear area.
When Low Temperature Carbon Steel (LCTS) materials are specified in Datasheet or
offered by Manufacturer, the Charpy V-notch test requirements of applicable material
standard shall be complied with.
3.4 Carbon steel used for the manufacture shall be fully killed
3.5 When specified in data sheet, hardness test shall be carried out as per ASTM A370 for
each heat of steel used. The maximum hardness of base metal, weld metal and heat
affected zone of all pressure parts shall be 248 HV
10
, unless specified otherwise.
3.6 Insulation material shall be minimum 20 mm thick and shall comply section 5, NACE RP
0286.
4.0 DESIGN & CONSTRUCTION REQUIREMENTS
4.1 Mechanical
4.1.1 Insulating joints shall be of integral type fabricated by welding and with pups on either
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 3 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
side as shown in data sheet. A corrosion allowance as indicated in data sheet shall be
considered in design. Bolted and threaded joints are not acceptable. Insulating J oints
of design, not having closing welds, are not acceptable.
4.1.2 All materials used for the manufacture of the insulating joint shall be in accordance
with clause 3.0 of this Specification.
4.1.3 Insulating joints shall be designed using the design principles of ASME Section-VIII Div.
1. The design shall be checked for the following two cases:
Case-I : Design Pressure (as per Data Sheet) + Axial Force (F)
The Axial force shall be calculated as under :
F = 0.1 x S x A
Where
S = SMYS of connected pipe (refer Data Sheet)
A = Metal cross-sectional area of connected pipe.
The allowable stress in this case shall be less than or equal to 0.5 x SMYS of insulating
joint material.
Case-II : Hydrostatic Test Pressure
The allowable stress in this case shall be less than or equal to 95% of SMYS of
insulating joint material.
All design parameters shall be as per Insulating J oint Data Sheet. Detailed calculations
shall be submitted for Purchasers approval.
4.1.4 Insulating joint design and materials shall be capable of being vacuum tested to 1
millibar.
4.1.5 The joint between pipe pup pieces and main forging shall be full penetration butt weld
type. Weld design shall be such as resulting in a weld joint factor of 1.0.
4.1.6 Butt weld ends shall have ends as per ASME B16.25. However, end preparation for
butt welding ends having unequal thickness with respect to connecting pipe, shall be
as per ASME B31.4/ B31.8 as applicable.
4.1.7 The reinforcement of inside weld seam, in case pups fabricated from LSAW pipes, shall
be removed for a distance of at least 50mm from each end.
4.1.8 Insulating joints shall allow free passage of scraper/ instrumented pigs. The internal
bore shall be same as that of connecting pipe including its tolerances.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 4 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
4.1.9 The insulating joint shall be formed by sandwiching and locking in positions the
insulating material in a bell and spigot type of joint. The joint shall be assembled in
such a way that its various components are firmly locked in position and the completed
joint is capable of withstanding stresses due to designed operating conditions and field
hydrostatic testing.
4.1.10 Insulating joints shall be suitable for aboveground or underground installations as
indicated in the data sheets.
4.1.11 All welds shall be made by welders and welding procedures qualified in accordance
with the provisions ASME section IX. The procedure qualification shall include impact
test and hardness test and shall meet the requirements of clause 3.3, 3.5 of this
specification.
4.1.12 Repair welding on parent metal is not allowed. Repair of welds shall be carried out
only after specific approval by purchaser's representative for each repair. The repair
welding shall be carried out by welders and welding procedures duly qualified as per
ASME section IX and records for each repair shall be maintained. Repair welding
procedure qualification shall also include impact test & hardness test when required
as per Cl. No. 3.3 & 3.5 of this specification & shall meet the requirements as
specified therein.
4.1.13 The Tolerance on Internal diameter at the welding end shall be as per applicable
connected pipe specification as indicated in the datasheet.
4.1.14 Out of roundness measured at the root face of the welding ends shall not be more
than 0.5% of the specified inside diameter.
4.2 Electrical
4.2.1 The average dielectric strength of the insulating joint shall be minimum 15 kilo Volts.
4.2.2 Two cleats as shown in data sheet shall be provided on the pups on either side of the
insulating joint for connecting 10 mm
2
and 50 mm
2
cables for measurement/ shorting
purposes. Cleats shall be attached to the insulating joint by welding.
5.0 INSPECTION AND TESTS
5.1 The manufacturer shall perform all inspection and tests as per the requirements of this
specification and the relevant codes, prior to shipment at his works. Such inspection
and tests shall be, but not limited to the following:
5.1.1 All insulating joints shall be visually inspected. The internal & external surfaces shall be
free from any strikes, gauges & other detrimental & defects. The surfaces shall be
thoroughly cleared & free from dirt, rust & scales.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 5 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
5.1.2 Dimensional checks shall be carried out as per the purchaser approved drawings.
5.1.3 Chemical composition and mechanical properties including hardness shall be checked
as per relevant material standards and this specification, for each heat of steel used.
5.1.4 Non-destructive inspection of insulating joints shall be carried out as given below:
a) 100% radiography shall be carried out on all butt & repair welds of pressure
containing parts. Acceptance limits shall be as per API 1104.
Welds, which in purchaser's Representative opinion cannot be inspected by
radiographic methods, shall be checked by ultrasonic or magnetic particle
methods. Acceptance criteria shall be as per ASME Section VIII Appendix-12
and Appendix-6 respectively.
b) All finished weld ends shall be 100% ultrasonically tested for lamination type
defects for a distance of 5Omm from the ends. Any lamination larger than 6.35
mm shall not be acceptable.
c) All forgings shall be wet magnetic particle inspected on 100% of forged
surfaces. Method and acceptance shall comply MSS-SP-53.
d) All fillet weld of thickness < 6mm shall be examined 100% by magnetic particle
inspection and 6mm shall be examined 100% by UT. Acceptance criteria for
MPI & UT shall be as per ASME Sec.VIII Appendix-6 & Appendix-12
respectively.
5.1.5 Insulating joint shall be hydrostatically tested to a pressure as indicated in data sheet.
The test duration shall be of 15 minutes.
5.1.6 After the hydrostatic test insulating joints shall be tested with air at 5 kg/cm
2
for 10
minutes. The tightness shall be checked by immersion or with a frothing agent. No
leakage will be accepted.
5.1.7 Dielectric Test
a) Insulation resistance of each insulating joint shall be atleast 25 mega-ohms
when checked with 500-1000 V DC.
b) Insulating joint before and after the hydrostatic test, shall be tested for
dielectric integrity for one minute at 5000 V A.C., 50 cycles and the leakage
current before and after hydrostatic test shall be equal. Testing time voltage
and leakage shall be recorded and certified. No repair shall be permitted to the
insulating joints failed in the above-mentioned tests.
5.2 Purchaser reserves the right to perform stage wise inspection and witness test as
indicated in Para 5.1 at Manufacturer's works prior to shipment. Manufacturer shall
give reasonable notice of time and shall provide without charge reasonable access and
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 6 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
facilities required for inspection to the purchaser's Representative.
Inspection and tests performed/witnessed by the Purchaser's Representative shall in
no way relieve the Manufacturer's obligation to perform the required inspection and
test.
6.0 TEST CERTIFICATES
6.1 Manufacturer shall submit following certificates to Purchaser's Representative.
a) Test certificates relevant to the chemical analysis and mechanical properties
including hardness of the materials used for construction of insulating joint as
per this specification and relevant standards.
b) Test reports on non-destructive testing.
c) Test certificates for hydrostatic and air tests.
d) Test certificate for electrical test.
e) Test report on vacuum test.
7.0 PAINTING, MARKING AND SHIPMENT.
7.1 Insulating joint surface shall be thoroughly cleaned, freed from rust and grease and
applied with sufficient coats of corrosion resistant paint. Surface preparation shall be
carried out by shot blasting to SP-6 in accordance with "steel structures painting
council - Visual standard SSPC-VIS-l.". External surfaces of burried insulating joints
shall be painted with three coats of suitable coal tar epoxy resin with a minimum dry
film thickness of 300 microns.
Manufacturer shall indicate the type of corrosion resistant paint used, in the drawings
submitted for approval.
7.2 Insulating joints shall be marked with indelible paint with the following data:-
a. Manufacturer's name
b. Suitable for _____ inch nominal diameter pipeline
c. End thickness in mm
d. Material
e. Design Pressure/ Hydrostatic Test Pressure
f. ANSI Class Rating
g. Tag No.
h. Year of Manufacture
7.3 Insulating joints shall be suitably protected to avoid any damage during transit.
Metallic or high-impact plastic bevel protectors shall be provided to weld ends.
7.4 Only those insulating joints which have been inspected and certified by Purchaser shall
be shipped.
STANDARD TECHNICAL SPECIFICATION MECON LIMITED
REGD. OFF: RANCHI
834002
OIL & GAS SBU, DELHI
DOCUMENT NO. Page 7 of 7
TITLE INSULATING J OINTS MEC/ TS/ 05/ 21/ 009 REVISION : 0
EDITION : 1
8.0 GUARANTEE
8.1 The manufacturer shall guarantee that the materials used comply with the
requirements of this specification.
8.2 Manufacturer shall replace or repair insulating joints found defective due to inadequate
engineering or quality of material.
8.3 Manufacturer shall replace the insulating joint without delay if the defect or
malfunctioning can not be eliminated.
8.4 Any defects occurring within 12 months from the date of installation or within 30
months from the date of despatch, whichever is earlier, shall be repaired making all
necessary modifications and repair of defective parts free of charge to the purchaser.
9.0 DOCUMENTATION
9.1 All documents shall be in English Language.
9.2 At the time of bidding, Bidder shall submit the following documents:-
a) General arrangement drawing along with cross sectional view, overall
dimensions and details of insulating materials recommended.
b) Reference lists of previous supplies of insulating joint of similar specification.
c) Clause wise list of deviation from this specification, if any.
9.3 Within three weeks of placement of order, the Manufacturer shall submit four copies of
but not limited to the following drawings, documents and specifications for approval.
a) Fabrication drawings and relevant calculations for pressure containing parts.
b) Welding procedure and method of manufacture for all phases of manufacture.
c) Quality Control Manual & Quality Control Plan.
Once the approval has been given by purchaser any changes in design, material and
method of manufacture shall be notified to the Purchaser whose approval in writing of
all changes shall be obtained before the insulting joint are manufactured.
9.4 Within four weeks from the approval date Manufacturer shall submit one reproducible
and six copies of the approved drawings, documents and specifications as listed in 9.3
of this specification.
9.5 Prior to shipment, the manufacturer shall submit one reproducible and six copies of the
test certificates as listed in Clause 6.0 of this specification.
D:\LPG\TS\STRAINER\STRAINER011.doc
Rev. : 0
Edition: 0
SPECIFICATION
FOR
Y / T TYPE STRAINERS
SPECIFICATION NO. : MEC/TS/05/21/010
(OIL & GAS SBU)
MECON LIMITED
DELHI - 110 092
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 2 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
AMENDMENT STATUS
Sl.
No.
Clause / Paragraph / Annexure /
Exhibit / Drawing Amended
Page
No.
Status of Revision and Date
Rev-1 Rev-2 Rev-3 Rev-4
PREPARED BY :
CHECKED BY :
APPROVED BY :
ISSUE DATE :
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 3 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
C O N T E N T S
Sl. Description Page No.
No.
1.0 GENERAL 02
2.0 SCOPE OF WORK OF VENDOR 02
3.0 DESIGN 03
4.0 TECHNICAL REQUIREMENTS 03
5.0 INSPECTION AND TESTING 04
6.0 PROTECTION AND PAINTING 05
7.0 PACKAGING AND IDENTIFICATION 06
8.0 SPARE PARTS AND TOOLS 07
9.0 INFORMATION/ DOCUMENTS/DRAWINGS 07
TO BE SUBMITTED WITH OFFER
10.0 WARRANTY 08
PREPARED BY :
(SHESH RAM)
CHECKED BY :
(G. V. WALIMBE)
APPROVED BY :
(A. K. JOHRI)
ISSUE DATE :
JULY 2008
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 4 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
1.0 GENERAL
1.1 This specification alongwith data sheets, other specifications & attachments to
inquiry / order describes and constitutes the minimum requirement according
to which vendor / manufacturer shall design, manufacture, test and supply the
Y/T type strainer for removing solid contaminants from the liquid / gaseous
stream.
The intent of these requirements is to supplement the requirements as given
in data sheets/other specifications and other applicable codes / standards
referred to in data sheets / specifications.
1.2 Except as specified herein, the strainers shall be designed, manufactured,
tested and supplied in accordance with data sheets, specifications and
applicable codes / standards (latest edition).
1.3 Manufacturer / Vendor shall seek Purchaser / Consultants approval regarding
such features which are not specified by Purchaser / Consultant but
requirements call for purchaser decision on these matters.
1.4 Strainer model offered shall be from the existing regular manufacturing range
of the strainer vendor. Vendor's / manufacturer's catalogue and general
reference list shall be furnished along with the offer.
1.5 The offered strainer shall be of a proven design in similar service.
2.0 SCOPE OF WORK OF VENDOR
2.1 Engineering, design, manufacturing and supply of strainer.
2.2 Procurement of raw materials etc. from sub-vendors.
2.3 Preparation and submission of documentation for design approval by purchaser/
consultant.
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 5 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
2.4 Supply of recommended spare parts needed for start-up and commissioning and
special tools or fixtures, if any.
2.5 Inspection and testing as per T.S.
2.6 Surface preparation, protective coating and painting as per T.S.
2.7 Packaging and transportation to site.
3.0 DESIGN
3.1 Following standards and codes (latest edition) shall be followed for design,
fabrication, testing etc. of the equipment.
ASME SEC. II & ASTM : Material specification
ASME SEC. VIII DIV. I : Boiler and pressure vessel code
ASME SEC. IX : Welding and brazing qualifications
ANSI B 16.5 : Pipe flanges
ANSI B 16.9 : Butt-welded fittings.
ANSI B 16.11 : Forged steel fittings socket welded
and threaded.
3.2 Material of construction shall be as per data sheet. Manufacturer / Vendor
shall however assume responsibility for suitability of selected material for
specified service. If necessary, vendor should furnish superior materials than
specified.
4.0 TECHNI CAL REQUIREMENTS
4.1 The equipment shall be of the type as mentioned in the data sheet; and shall
meet the duty requirements and performance parameters as mentioned
therein.
4.2 Material of construction of body, filter medium, etc. of Y/T strainer shall be as
compatible with connecting pipe specification and as per data sheets.
4.3 Effective free area of basket shall be minimum 3 times of the inlet nozzle area.
4.4 Corrosion allowance of 3 mm shall be considered for all carbon steel parts,
unless otherwise mentioned in the data sheets.
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 6 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
4.5 Dimensions of flanges including shell flanges, nozzle flanges and blind cover
flanges shall be as per ANSI B 16.5. Larger flanges not covered by ANSI shall
be as per MSS-SP-44.
4.6 Drain and vent connections wherever provided shall be with matching blind
cover flanges alongwith necessary gaskets, bolts and nuts.
4.7 Pressure parts joined by butt, Welds shall be with full penetration welds.
Where both sides welding is not accessible, root run by tungsten Inert gas
process or backing strip, shall be used to ensure full penetration. Backing, strip
if used shall be removed after welding.
4.8 Fabricated body shall be post weld heat treated, whenever it is required due to
service requirement or due to code requirements. Body shall be post weld heat
treated as a complete unit and no welding shall be permitted after the post
weld heat treatment is completed.
5.0 INSPECTI ONS AND TESTING
5.1 Equipment shall be subjected to stagewise expediting, inspection and Testing at
vendor's/ sub-vendor's works by purchaser/ its authorised inspection agency.
Vendor shall submit Quality Assurance (QA) procedures before commencement
of fabrication. Approved QA procedures shall form the basis for equipment
inspection. The QAP shall generally be in done with one, which is enclosed with
the tender enquiry.
5.2 Testing at vendor's works shall include but not limited to the following:
Non-destructive tests such as radiography, dye penetration tests as per
data sheet and other requirements,
Hydrostatic test at a pressure not less than 150% of design pressure for
the body.
Any other tests as per data sheets / codes / standards and covered under
approved QAP.
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 7 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
5.3 Any or all the tests, at purchaser's option, shall be witnessed by purchaser/ its
authorised inspection agency. However, such inspection shall be regarded as
check-up and in no way absolve the vendor of his responsibility
5.4 Extent of radiography shall be 100%.
6.0 PROTECTIONS AND PAINTING
6.1 All exposed carbon steel parts to be painted shall be thoroughly cleaned from
inside and outside to remove scale, rust, dirt and other foreign materials by
wire brushing and sand blasting as applicable. Minimum acceptable standard
in case of power tool cleaning shall be St.3 and in case of blast cleaning shall
be Sa 2 as per Swedish Standard SIS 0055900.
6.2 Non-ferrous materials, austenitic stainless steels, plastic or plastic coaled
materials and insulated surfaces of equipment shall not be painted.
6.3 Stainless steel surfaces both inside and outside shall be pickled and
passivated.
6.4 Machined and bearing surface shall be protected with rust preventive agent
like varnish or thick coat of grease.
6.5 Depending on the environment, following primer and finish coats shall be
applied:
Environment (Description).
i) Normal Industrial Surface : Sa 2
Preparation
Primer : 2 coats of Red oxide zinc chromate
each 25 microns ( min. ) thick
Finish : 2 coats of Synthetic enamel,
Each 25 microns (min. ) thick.
ii) Corrosive Industrial Surface : Sa 2
Preparation
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 8 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
Primer : 2 coats Epoxy zinc chromate,
each 35 microns ( min. ) thick
Finish : 2 coats of Epoxy high build
paint, each 100 microns (min.) thick.
iii) Coastal and Marine Surface : Sa 2
Preparation
Primer : 2 coats of High build chlorinated rubber zinc
phosphate, each 50 microns (min.) thick.
Finish : 2 coats of Chlorinated rubber plant
each 35 microns ( min. )thick.
(All values refer to dry film thickness).
6.6 The colour of finish coat shall be as indicated in datasheet / approved by the
Purchaser / Consultant.
7.0 PACKAGING AND IDENTIFICATI ON
7.1 All packaging shall be done in such a manner as to reduce the volume. The
equipment shall be dismantled into major components suitable for shipment
and shall be properly packed to provide adequate protection during shipment.
All assemblies shall be properly match marked for site erection.
7.2 Attachments, spare parts of the equipment and small items shall be packed
separately in wooden-cases. Each item shall be appropriately tagged with
identification of main equipment, item denomination and reference number of
the respective assembly drawing.
7.3 Detailed packing list in waterproof envelope shall be inserted in the package
together with equipment.
7.4 Each equipment shall have an identification plate giving salient equipment
detail / data, name of manufacturer, make / model, equipment number, year
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 9 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
of manufacture etc.
8.0 SPARE PARTS AND TOOLS
8.1 Vendor shall provide spare parts needed for start-up and commissioning.
Vendor shall furnish a separate itemized priced list of recommended spares for
one as well as two (2) years normal operation and maintenance. Lists shall
include part number, part description, serial number and normal delivery lead
time. Vendor shall ensure listed parts are available for shipment at the time of
equipment shipment.
8.2 Recommended spares should take into account related factors of equipment
reliability, effect of equipment downtime upon production or safety, cost of
parts and, availability of equipment service facilities. Recommend spares shall
be limited to basket( s) and gasket( s) / O-rings only.
8.3 All spare parts furnished by Vendor should be wrapped and packaged so that
they will be preserved in original as new condition under the normal conditions
of storage to be anticipated in India. Spare parts shall be properly tagged and
coded so that later identification as to intended equipment usage will be
facilitated. They shall be packaged separately clearly marked as "spare parts"
and shipped at the same time as the equipment. Packing lists shall be
furnished so that the parts can be handled without uncrating, if required.
Start-up spares shall be packed and identified separately.
8.4 Vendor shall provide two sets of special tools or fixtures as required, for
installation / erection, operation & maintenance and disassembly of the
furnished equipment.
8.5 All such tools shall be permanently tagged with information pertaining to their
use. Any special drawings or instructions pertaining to the use of such tools
shall be included in the instruction manual.
9.0 INFORMATIONS/ DOCUMENTS/ DRAWINGS TO BE SUBMITTED WITH
THE OFFER
Contractor shall submit with the offer four copies each of the following:
STANDARD TECHNICAL SPECIFICATION
MECON LIMITED DELHI
REGD. OFF. : RANCHI
OIL & GAS SBU, DELHI
Page 10 of 10
Rev.0
TITLE
Y/ T TYPE
STRAINER
DOCUMENT NO.
MEC/ TS/ 05/ 21/ 010
Edition: 0
D:\LPG\TS\STRAINER\STRAINER011.doc
9.1 Manufacturer's complete descriptive and illustrative catalogue/ literature and
identification of model selected.
9.2 Completely filled up data sheet enclosed with the Tender document.
In case of failure to submit the documents listed above, the offer may be
rejected.
10.0 WARRANTY
Vendor shall have final and total responsibility for the design and mechanical
performance of all equipment supplied under this specification. Vendor shall
warrant the equipment furnished by him and the performance of the said
equipment in accordance with this specification and with warranty
requirements given elsewhere in bid package.
STANDARD SPECIFICATION
FOR
FI RE DETECTION AND
ALARM SYSTEM
CONTENTS
1.0 SCOPE
2.0 CODES AND STANDARDS
3.0 SITE CONDITIONS
4.0 GENERAL REQUIREMENTS
5.0 FIRE MONITORING AND ALARM PANELS
6.0 AUTOMATIC FIRE DETECTORS AND ACCESSORIES
7.0 ADDITIONAL REQUIREMENTS FOR FIRE ALARM SYSTEM TO BE
INSTALLED IN HAZARDOUS AREA
8.0 SPECIFIC REQUIREMENTS FOR CLEAN AGENT / CO
2
RELEASE SYSTEM
9.0 ENGINEERING REQUIREMENTS
10.0 TESTING AND ACCEPTANCE
11.0 PACKING AND DESPATCH
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 1
1.0 SCOPE
1.1 This specification covers the design, engineering, manufacture, testing,
packing and supply of automatic and manual Fire Alarm System
incorporating manual call points (break glass boxes), automatic detectors,
release and inhibit switches for fire suppressant clean agent, data
gathering, fire alarm and central fire alarm panels, conventional or
computer aided (microprocessor based) mimic panels and associated
equipments as specified hereunder and in data sheets / drawings.
2.0 CODES AND STANDARDS
2.1 The fire alarm system and the components used shall confirm to the
latest edition of the following and also the other Indian and international
Standards as applicable.
2.1.1 IS-5 Colours for ready mixed paints and enamels
2.1.2 IS-513 Specification for cold rolled low carbon steel sheets and
trips.
2.1.3 IS-2175 Specification for heat sensitive fire detectors for use in
automatic fire alarm system.
2.1.4 IS-2189 Code of practice for selection, installation and
maintenance of automatic fire detection and alarm
system.
2.1.5 IS-3700 Essential ratings and characteristics of semiconducting
devices.
2.1.6 IS-3826 Part-I Connectors for frequencies below 3 Mhz General
requirements and tests.
2.1.7 IS-5469 Code of practice for the use of semi-conductor junction
devices
2.1.8 IS-5780 Intrinsically safe electrical apparatus and circuits
2.1.9 IS-11360 Specification for smoke detectors for use in automatic
electrical fire alarm system.
2.1.10 BS-5839 Specification for manual call points
Part-2
2.1.11 NFPA 72 National Fire Protection Association
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 2
2.1.12 LPC Loss Prevention Council Recommendation
2.2 Wherever the requirements of this specification are in conflict with any of
the standards mentioned above, the requirements of this specification
shall be binding.
2.3 In addition to the above, all equipment shall confirm to the provisions of
Indian Electricity rules, Tariff Advisory Committee and other statutory
regulations in force from time to time.
3.0 SITE CONDITIONS
3.1 All the equipments shall be suitable for the site conditions specified in the
enquiry document / data sheets. If not specifically mentioned therein, a
design ambient of 55`C and an altitude not exceeding 1000m above
mean sea level shall be considered with a minimum temperature of (-)5`C
for battery sizing.
4.0 GENERAL REQUIREMENTS
4.1 Unless otherwise specified in the enquiry documents, all the equipments
shall be suitable for installation in safe, non-hazardous area and shall
confirm to the recommendations of Tariff Advisory Committee.
Equipments to be located in hazardous areas shall have certification for
use in such areas by the recognised testing and certification authorities,
such as CMRI, Dhanbad, BASEEFA (UK), UL (USA) etc., or the relevant
authorities of the country of origin. Equipment for hazardous areas shall
be approved by CCE / DGMS / DGFASLI, as applicable, and all indigenous
flameproof equipment shall be covered under a valid BIS licence.
4.2 Power Supply
The Fire Alarm System shall be suitable to receive the power supply as
given below:
a) Voltage : 110V / 240V 6% (field selectable),
b) Frequency : 50Hz 3%, 1 phase
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 3
Further distribution shall be vendors responsibility. Any voltage, other than
the above shall be internally derived by the vendor within the system.
4.1.2 The battery back-up shall be capable of maintaining the system in normal
operation for a period of not less than 48 hours after the failure of normal
mains supply, after which sufficient capacity shall remain to provide full
load operation for at least 30 minutes.
The full load shall be considered as the load caused by the operation of all
alarm sounders operating simultaneously, operation of detectors in at least
25 percent of the zones and the operation of fault indicators.
The switch over from mains to batteries shall be automatic, in the event of
a mains failure.
Ni-Cd / Lead Acid / Sealed maintenance free batteries, as specified in data
sheets and suitable battery charger chall be provided for each system.
5.0 FIRE MONITORING AND ALARM PANEL
5.1 Fire sensed by the field equipments shall be monitored by Fire Alarm
Panels located in plant control rooms. Fire Alarm panels can be either
conventional type using digital electronic techniques or computer aided
microprocessor based analogue addressable type, as specified in the
enquiry documents / data sheets.
5.1.1 The conventional system shall generally comprise of the following
equipments used in conjunction with conventional automatic fire alarm
detectors and manual call points. Exact requirements shall be specified in
enquiry documents data sheets.
a) Central Fire Alarm Panel with Mimic
b) Zonal Fire Alarm Panel
c) Repeat Alarm Panel / Annunciation Panel
5.1.2 Microprocessor based system shall generally comprise of the following
equipments used in conjunction with analogue addressable automatic fire
alarm detectors and manual call points. Exact requirements shall be
specified in enquiry documents / data sheets.
a) Central Fire Alarm Panel / Central Processing Unit
b) Data Gathering cum Fire Alarm Panel (DGFAP)
c) Repeat Alarm Panel
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 4
5.2.2 Conventional Fire Alarm System
5.2.1 Central Fire Alarm Panel
5.2.1.1 Central fire alarm panel shall gather information from various Zonal Alarm
panels regarding the status of activation of detectors / manual call points
etc. on an overall basis.
5.2.1.2 Central fire alarm panel shall house starter control(s) for siren(s), in order
to generate an alarm audible in the entire plant in the event of fire.
5.2.1.3 If specified in the enquiry document / data sheets, the central fire alarm
panel shall have provision for signals, alarms etc. as specified under
clauses 5.2.5.1.
5.2.4 A mimic, unless otherwise specified in the enquiry document shall form an
integral part of the central fire alarm panel and shall be located at the top
of the panel. If separate, mimic panel shall either be wall mounting or
free standing floor mounted type. Two nos. LEDs shall be provided for
each zone on mimic panel. It shall derive the power supply from Fire
Alarm panel. Mimic panel shall be illuminated through potential free
contacts available in fire alarm panel.
LEDs on the mimic panel shall be arranged on a graphic mimic of the
plant/area covered by the mimic panel. The LEDs shall be arranged on
the basis of zones, unit wise, building wise, detector / manual call point
wise or a combination of the above as described in the enquiry
document/data sheets.
5.2.2 Circuit Description and Operational Requirements
5.2.2.1 The system shall be modular in construction to facilitate future
extension/modification and shall include fire monitoring PCB, output
relays, annunciatiors, indicating lamps, switches, push buttons etc.
5.2.2.2 Static components shall be mounted on plug-in type printed circuit boards
(PCBs). PCBs for identical logic circuits shall be interchangeable.
Connections to and from the PCBs shall be taken through gold plated
edge connectors only. Plug and sockets of heavy duty type shall be used
for PCBs. Card edge connecting pins shall not be acceptable. PCBs shall
be coated with the antifungus chemicals on both sides and shall be
suitable for tropical climate.
5.2.2.3 Fail Safe feature to signal the failure in the circuitry shall be
incorporated in the logic circuit and operation of the alarm system shall
be on opening normally closed field contact.
5.2.2.4 Test facility through common Test push button shall be provided for
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 5
complete functional test of each group of logic circuits, audio and visual
flasher circuit, lamps etc.
5.2.2.5 The annunciation circuit design shall ensure that momentary short circuit
in the lamp circuit does not adversely affect the performance of the
system. Visual and audible alarm circuits shall be independent i.e. the
failure of one will not affect the other.
5.2.2.6 The circuit shall be so designed that silencing of the current alarm by
ACCEPT push button shall not prevent initiation of fire alarm in case of
subsequent FIRE signal received from any other location.
5.2.2.7 The field contact wiring will be carried out by using multicore, copper
conductor, PVC insulated and armoured cable which may be running close
to power cables. Hence the logic circuitry shall be designed with
sufficiently high signal-to noise ration to avoid spurious actuation due to
noise induced in the field wiring because of proximity with power cables.
Adequate noise filters and time delay shall be incorporated at the input
stages to reduce the effect of the noise.
5.2.2.8 A minimum of two lamps shall be provided in parallel for each fire loop to
increase the reliability of the visual alarm.
5.2.2.9 Fire alarm loop card shall be capable to receive the signal from break
glass box, Heat, UV, IR, ionisation, optical type detector, heat sensing
cable, linear beam detector and any combination thereof.
5.2.2.10 Whenever the fire is detected in any zone, both audible and visual
(flashing) alarm shall be raised in the fire alarm panel indicating the
corresponding location of fire zone. On pressing the ACCEPT push
button, the audible alarm shall stop and the lamp shall glow steadily. The
panel shall be brought to normal condition by pressing RESET push
button (only after the field conditions are normalised). It shall be possible
to manually initiate the audio alarm in addition to automatic operation.
If specified in the material requisition / data sheet, the system shall be
provided with a siren to be located at a suitable location in the plant. The
controls for the siren shall form an integral part of the Fire Alarm Panel.
The starter for the siren shall be direct-on-line type, weather proof shall
be in an IP-55 enclosure, suitable for outdoor installation. The enclosure
shall be epoxy painted fire red, to shade 536 of IS-5.
5.2.3 Zonal Fire Alarm Panel
5.2.3.1 Zonal Fire Alarm Panel shall gather information from various detectors /
manual call points connected to its loop. It shall monitor the status of
detectors, cable faults etc.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 6
Zonal Fire Alarm Panel shall have provision to annunciate the fire/fault
signals received from the detector/manual call points connected to its
loops. LEDs shall be provided for visual annunciation and electronic
hooters as audible alarm.
5.2.3.2 Additionally LEDs shall be provided for power ON, fault, fire, multiple
alarm indication etc. Push buttons shall be provided for alarm accept,
hooter reset, LED test etc. Power ON switch shall be provided.
5.2.3.3 Zonal Fire Alarm Panel shall generate output contacts for signals to repeat
alarm panels, central fire alarm panel etc. It shall generate potential free
contacts for energisation of hooters, exit signs, tripping of owners AHU
and pressurisation system etc.
5.2.3.4 If specified in the enquiry document/data sheets, the zonal fire alarm
panel shall have provision for the signals, alarms etc. as specified under
clause 5.2.5.1
5.2.4 Repeat Alarm Panel
5.2.4.1 Repeat alarm panels shall generally be constructed as specified in clause
5.4 and shall be wall mounting type.
Repeat alarm panel shall receive signals from Central Fire Alarm Panel or
Zonal Fire Alarm Panel shall have provision to annunciate the same using
audio-visual annunciation. LEDs shall be provided for visual annunciation
and electronic hooters as audible annunciation. Additionally LEDs shall be
provided for power ON, fault, fire, multiple alarm indication etc. Push
buttons shall be provided for alarm accept and hooter reset, as well as,
for LEDs test. Switch shall be provided for power ON.
5.2.4.2 Repeat alarm panels may either have
a) LEDs arranged in a matrix (rows and columns) along with text
engraved alongside each LED indicating the zone where the fault/fire
has occured.
OR
b) LEDs arranged on a graphic mimic of the zones/areas covered by the
repeat alarm panel.
5.2.4.3 Repeat alarm panels shall derive power from the associated fire alarm
panel.
5.2.5 Alarm, Signal and Control Requirements
5.2.5.1 In addition to the initiation of fire alarm, zonal, central fire alarm panels
shall have the facility for following status signals, status alarms and
shutdown signals if specified in data sheets / drawings.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 7
i. Automatic signal for release of clean agent/CO
2
release for protected
area and release alarm in control room.
ii. Selector switches for primary or secondary clean agent/CO
2
supply for
each skid / protected area.
iii. Manual push button for discharge of clean agent/CO
2
in each
protected area (after alarm and 30 seconds time delay).
iv. Clean agent/CO
2
discharge inhibit push button for each protected
area.
v. Deluge valve activation push buttons, deluge valve test push buttons
and deluge valve activated status lamps.
vi. Shutdown signals to various air handling units relative to the zone of
fire.
vii. Fire water pumps running indications.
viii. Fire water pumps start push buttons.
ix. Controls of sirens.
x. Repeat alarm signal to various control rooms.
xi. Repeat alarm signal to mimic panel.
xii. Repeat alarm signal to repeat alarm panel.
xiii. Status of Battery Conditions.
5.3 Computer Aided Fire Alarm System
The microprocessor based analogue addressable fire detection and alarm
system shall be computer aided utilising distributed processing
techniques. The system shall include the following as a minimum.
5.3.1 Central Fire Alarm Panel (CFAP)
5.3.1.1 The CFAP or central processing unit shall be a special purpose
microprocessor operating under software program which shall provide
central control and monitoring functions of the entire fire alarm system.
5.3.1.2 CFAP shall communicate with various Input / output devices, DGFAPs,
repeat alarm panels, I/O multiplexer, mimic panels, industrial grade PCs,
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 8
Visual Display Units (VDU), key boards, printers etc. located at central /
various locations in the plant.
5.3.1.3 CFAP shall have the facility to scan the data received from the DGFAPs
and shall send necessary information to the respective DGFAPs, repeat
alarm panels, VDUs etc. through bi-directional communication network.
5.3.1.4 CFAP shall be modular in design and shall contain 100% redundant
microprocessor based master unit, processing units, signalling module
and power suppl unit. The CFAP shall serve as an interface and controller
for connected PCs having graphics/text facility, located at central location
and DGFAP panel(s) distributed in various control rooms.
5.3.1.5 CFAP shall be designed specifically for fire alarm and protection system
applications and shall provide status, alarm, shutdown signals in
predefined manners, initiate alarms, synchronise all activities, provide
repeat alarms and other signals as specified.
5.3.1.6 The CFAP shall have non-volatile memory for reliability and shall permit
reprogramming by authorised personnel.
5.3.1.7 The CFAP shall provide various event initiated programmes (EIP). EIP
shall be initiatred by any of the following user defined parameters; day,
time, alarm, return to normal, change of status and hardware failure.
The system shall provide multi levels of command priority to assure that
high level commands are not overriden by lower level commands.
5.3.1.8 CFAP shall have the facility to display the affected area on the VDU and
provide the instructions to suppress the cause. High resolution graphic
software shall be provided for display. The graphics shall have many
layers of penetration. The VDU shall either be touc screen type or menu
driven using mouse/keyboard. However, instead of graphic display, VDU
with only text display shall be provided, if specified in the data sheets.
5.3.1.9 Unless otherwise specified in the data sheet CFAP shall be designed to
provide multicolour display on the VDU.
5.3.1.10 Suitable communication interface cards shall be provided in CFAP to
interface with DGFAPs, repeat alarm panels etc.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 9
5.3.1.11 PC shall be with a pentium or higher processor with a minimum 100MHZ
clock rate, with 8GB hard disk, 3.5 floppy drive, CD drive, 512MB RAM,
64 KB cache memory, serial and parallel ports suitable for the devices
connected. PC shall be complete with 101 key key-board with English
language characters, 17 colour monitor with SVGA compatibility, non-
glare screen with front mounted power switch, brightness/contrast
control, horizontal/vertical position and size control etc. The monitor shall
be on a swivel base.
5.3.1.12 Monitor screen shall have dedicated areas for the following functions:
- Alarms and returns to normal
- Menus, commands, reports and programming
- Time, day and date
5.3.1.13 Alarms and all other changes of status shall be displayed on the screen
area reserved for this information. The following information shall be
provided as a minimum:
- Condition of detector (Alarm / Trouble)
- Type of detector
- Location of detector and numerical system address
- Emergency instructions.
On receipt of alarm, an audible alarm shall sound and the condition and
detector type shall flash until acknowledged by the operator. Return to
normal shall also be annunciated and shall require operator
acknowledgement.
5.3.1.14 The system shall have multiple levels of priority for displaying alarms.
Should multiple alarms occur, the first received, highest priority alarm
shall be displayed on the screen until acknowledged by the operator.
Then the next highest priority alarm shall be displayed until acknowledged
etc. Should a higher priority alarm occur, the higher priority alarm shall
replace the lower priority alarm on the screen and the lower priority alarm
shall be retained in memory and re-displayed after the higher priority
alarm is acknowledged.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 10
5.3.1.15 The system shall provide sufficient memory so that no alarm shall be lost.
A message highlighted in reverse video, shall advise the operator when
other unacknowledged alarms are present in the system.
5.3.1.16 The VDU keyboard shall use function keys with English descriptions to
initiate all system functions. Typing abbreviations or using unlabeled or
numerical function buttons is unacceptable. When a function key is
pressed, the monitor shall lead the operator through the function by
asking him to choose one of several clearly defined options (menu
penetration). When a specific detector must be addressed, a distinct
numerical keypad shall be used to speedup and simplify the operation. On
command from the operator, system reports either shall be displayed on
the VDU screen or output on the printer, as desired by the operator.
5.3.1.17 Multiple levels of access to the system shall be provided for operators and
supervisors via user defined passwords. The following functions shall be
provided for each levels:
a) Operator level access functions
- Display system directory, definable by detector type
- Display status of an individual detector
- Manual command (alarm with an associated command i.e. secure /
accesses / alarm shall use the same system address for both
functions)
- Report generation, definable by detector type. Reports shall be output
on either the monitor or printer, as desired by the operator.
b) Supervisor Level Access Functions
- Reset time and date
- Holiday scheduling
- Enable / disable event initiated programmes, printouts, initiators.
- Enable / disable individual hardware points and system components.
5.3.1.18 Printer used in the system shall provide real time records of the system
events and provide system reports on demand.
5.3.1.19 Printer shall be microprocessor controlled, high speed, read only (RO)
type.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 11
5.3.1.20 The system printer (PTR) shall be a letter quality dot-matrix printer, 132
character wide and shall have a 96 character set. The printer shall have a
microprocessor controlled bi-directional logic seeking head. The printing
speed shall not be less than 300 cps in draft mode.
5.3.1.21 The printer shall automatically record in English all alrams, troubles,
acknowledgements, return to normal, manual commands, plus those
automatic commands selected by the user.
5.3.1.22 Alarms shall be highlighted differently than other traffic and shall be
recorded in English, including type, location, time, date and numerical
address of alarm detector. Multiple alarms shall be recorded in the order
received, regardless of alarm priority. If an alarm is received during the
preparation of reports, the printer shall interrupt the report to record the
alarm and afterwards resume the report automatically.
5.3.1.23 Automatic (EIP) commands shall be recorded automatically. All changes
to system programming shall be recorded automatically.
5.3.1.24 Printer shall use fanfold paper and shall accomodate an original and two
copies. Paper shall be tractor fed. Each page shall be automatically timed,
dated and page numbered to detect unauthorised removal.
5.3.1.25 Printer shall be desk top unit and shall be styled to match the VDU.
5.3.1.26 The printer shall have an indicator to alert the operator that pape has run
out.
5.3.1.27 The printer shall have a self test feature to verify printer operability even
when off line.
5.3.1.28 To achieve 100% redundancy, 2PCs, VDUs, keyboards and printers shall
be provided for communication with the 100% redundant central
processing unit of the CFAP, if specified in the material requisition / data
sheets.
5.3.1.29 The central processing unit, along with PCs and their peripherals shall be
housed in a console type enclosure made out of minimum 16 guage CRCA
sheets..
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 12
5.3.1.30 All cabling between the central processing unit, PCs and their peripherals
shall be in the vendors scope. Arrangements shall be made within the
console enclosure for distribution of power supply to various equipments.
5.3.2 Data Gathering Cum Fire Alarm Panel (DGFAP)
5.3.2.1 The DGFAP shall act as a control and interface point between
manual/automatic fire detectors and the CFAP.
The DGFAP shall be UL listed and FM approved, suitable for application in
fire detection and alarm systems. Approvals from agencies other than
UL/FM shall be subject to MECON review.
5.3.2.2 All manual/automatic fire detectors shall be connected to DGFAP. Input
signals shall be processed by the DGFAP. It shall also have the facility to
control all the input data received from different field devices. Field
devices can be automatic fire detectors, break glass boxes, switches and
process parameters.
5.3.2.3 The DGFAP shall have its own microprocessor and non-volatile memory.
5.3.2.4 The DGFAP shall have the facility to transfer all data to CFAP. It shall be
possible to re-programme the operations at site. The DGFAP shall have
the capability of stand alone operation in case of communication failure
with the CFAP/other DGFAPs.
5.3.2.5 The DGFAP shall have at least the following facilities:
- External power supply with standby backup (Integral charger and
battery may be accepted in case SMF batteries are specified in data
sheets).
- Alarm and trouble / fault indications, through 2x40 character
fluorescent alphanumeric display.
- Self diagnostic facility.
- Interface for data communication to other DGFAPs, CFAP, remote text
or graphics displays, repeat alarm panels etc.
- Detector or loop disablement and restoration.
- Message, data storage in non-volatile memory.
- Change/examination of sensitivity of various detectors.
- Hooter with reset facility
- Battery low indication
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 13
- Hardwired potential free contacts for shutdown signals etc. as defined
in clause 5.2.5.1
5.3.2.6 Simultaneous display of Fire and Fault indication on DGFAP shall be
provided on the alpha-numeric display (LED type) with the action
message that is to be taken by the operator.
5.3.2.7 All the data gathering panels shall have alarm verification capability.
5.3.2.8 DGFAP shall have repeating facility to remote area. Necessary hardware /
software shall be provided for thsi purpose.
5.3.2.9 DGFAP shall provide indications for communication with the CFAP, as well
as, alarm and trouble conditions in the sensor loops.
5.3.3 Repeat Alarm Panels
5.3.3.1 Repaet alarm panels shall be fabricated out of 16 gauge CRCA sheets.
The panels shall have IP-41 enclosure protection as a minimum. The
repeat alarm panel shall be suitable for wall mounting. Cable entry
provision shall be from bottom by means of cable glands. The panels shall
be epoxy painted fire red to shade 536 of IS-5.
5.3.3.2 Repeat alarm panel shall be capable to receive signals from either the
CFAP or the DGFAP and shall have provision to annunciate the same using
audio-visual annunciation.
5.3.3.3 Visual annunciation shall be by means of 2x40 character fluorescent
display on the panel front. The display shall indicate the detector address,
its location, action to be taken in case of fire etc. The display shall
indicate the instances of fire and fault.
5.3.3.4 Electronic hooters shall be provided for audible annunciation.
5.3.3.5 Additionally LEDs shall be provided for power ON, fault, fire, multiple
alarm indication etc. Push buttons shall be provided for alarm accept and
hooter reset, as well as, for LED test. Switch shall be provided for power
ON.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 14
5.3.3.6 Repeat alarm panel shall derive power from the associated fire alarm
panel.
5.3.4 Data Highway
5.3.4.1 Communication betwen CFAP, DGFAPs, repeater panels etc. shall be
realised by means of data highway. Unless specified otherwise, data
highway shall consist of 1.5mm
2
copper conductor, twisted pair, PVC
insulated, PVC inner sheathed, overall screened and overall PVC sheathed
cables. Data highway cables shall be 100% redundant, to ensure
reliability of communication.
Wherever required, due to cable capacitance limitation, modems shall be
employed for data highway communication. In such cases, modems shall
be powered as well as located in the respective DGFAPS or CFAP.
5.3.4.2 Alternately, optical fibre cables, may be used as data highway. The fibres
shall be as per latest CCITT recommendation for single mode optical
fibres and shall be laid in slots/tubes filled-up with moisture resistant jelly.
Polymer coated aluminium tape around the cable core shall provide a
moisture barrier. Optical fibre cables shall have an inner polyethylene
sheath with corrugated steel tape armouring and a polyethylene outer
sheath.
5.4 Panel Construction(Central Fire Alarm Panel, Zonal Fire Alarm
Panel, Data Gathering cum Fire Alarm Panel, Repeat Alarm Panel
etc.)
5.4.1 Panel(s) shall be free standing/wall mounting type, made out of minimum
16 gauge CRCA sheets. Doors and covers shall be made out of 14 gauge
CRCA sheets. The panel shall be naturally ventilated totally enclosed dust
and verminproof with IP-41 enclosure as a minimum. The construction of
the panel enclosure shall be designed to allow for at least 10% expansion
for future additions without involving any major modifications in the
system. In general, these panels, shall generate/receive/display the
required signals for Fire Alarm and Suppression systems.
5.4.2 Equipment Mounting
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 15
5.4.2.1 All apparatus, instruments and alarm facias mounted on the panel front
shall be flush mounted type. The panel wiring shall not be terminated
directly on the base connector of PCBs. It shall either be terminated
through a separate terminal block or multipin connectors. Routine
calibration and adjustments shall be accessible from the front of the panel
without having to remove any wiring or causing loss of the panel function.
In addition, total removal of the instrument(s) and replacement with a
spare shall be possible from the front of the panel.
5.4.2.2 All annunciator components except the alarm horn and auxiliary contact
relays (if used) shall be mounted integrally in a protective enclosure.
Sufficient spare terminals shall be provided to accommodate all spare /
future alarm points in the display. Access shall be provided to permit
checking and / or changing the wiring at these terminal strips.
5.4.2.3 Lamps shall be capable for removal and replacement from the panel front
via individual snap out windows or a swing out hinged door on which all
windows are mounted.
5.4.2.4 There shall be separate hooters for faults/ malfunction and fire alarm
having distinct audible tones.
5.4.2.5 Fluroscent lamp(s) shall be installed within the panel to provide adequate
lighting for maintenance of equipments. Door interlock switch shall be
provided for this purpose.
5.4.2.6 Cable entry shall be from bottom unless otherwise specified in the enquiry
document / data sheet. A terminal strip shall be provided for incoming /
outgoing cables. Supporting facilities shall be provided for clamping the
cables.
5.4.3 Wiring and Terminals
5.4.3.1 Wiring within the panel shall be in slotted plastic raceways enclosed with
cover. Interconnecting wiring shall be done with 1 sq. mm. Cross-section,
copper conductor, PVC insulated, 660V wires. Power circuit wiring shall be
with minimum 2.5 sq.mm. cross section, copper conductor. Panels shall
be supplied completely pre-wired including spare points of modules /
controllers etc. so that only field termination is required before
energisation.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 16
5.4.3.2 Cables shall be terminated on terminal blocks. Clamp type terminals shall
be of spring-loaded, stacking type, mounted on rails. Terminals shall be
sized to accept as a minimum 2.5 sq.mm. cross section conductors. Not
more than one conductor shall be terminated on the outgoing side of
each terminal. At least 20% spare terminals shall be provided in each
panel.
5.4.3.3 Suitably sized terminals shall be provided for terminating main power
supply cables.
5.4.4 Cable Glands
5.4.4.1 All the cable glands for outdoor application shall be weatherproof, nickel
plated brass and double compression type, whereas those for indoor
application shall be single compression type.
5.4.4.2 Cable glands for hazardous area equipment shall be flameproof,
weatherproof and nickel plated brass double compression type.
5.4.5 Earthing
5.4.5.1 A common earth bar of minimum 25 x 3 mm copper or equivalent
aluminium shall be provided throughout the length of the panel. All non
current carrying metallic parts of the panel mounted equipment shall be
earthed. All doors and movable parts shall be connected to the earth bus
by flexible jumpers. 2Nos. earth lugs shall be provided outside the panel.
5.4.6 Name Plates
5.4.6.1 All name plates for panel shall be engraved out of 3 ply (black-white-
black) lamicoid sheets or anodised aluminium. Back engraved perspex
sheet nameplates will also be acceptable. Engraving shall be done with
square groove cutters. Hard paper or self-adhesive plastic tape
nameplates will not be acceptable.
5.4.6.2 All panels mounted equipments (e.g. lamps, push buttons, switches PCBs
etc.) shall be provided with suitable nameplates.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 17
5.4.6.3 Labels shall be provided for every component on the cards, connecting
wires as well as for the terminals in the terminal strip inside the panel.
5.4.6.4 Special warning plates shall be provided on all removable covers or doors
giving access to energised metallic parts above 24 volts.
5.4.7 Painting
5.4.7.1 All metal surfaces shall be thoroughly cleaned and degreased to remove
mill scale, rust, grease and dirt. Fabricated structures shall be pickled and
then rinsed to remove any trace of acid. The under surface shall be
prepared by applying a coat of phosphate paint and a coat of yellow zinc
chromate primer. The undersurface shall be made free from all
imperfection before undertaking the finishing coat.
5.4.7.2 After preparation of the undersurface, the panel shall be epoxy painted
with two coats of final paint. Alternatively the panels may be powder
coated. The colour shade of final paint shall be as specified in the data
sheet. If not specified therein, the final paint shall be fire red, shade 536
of IS-5. The finished panels shall be dried in stoving oven in dust free
atmosphere. Panel finish shall be free from imperfections like pin holes,
orange peels, run-off paint etc.
All unpainted steel parts shall be cadmium plated or suitably treated to
prevent rust-corrosion. Moving elements shall be greased.
6.0 AUTOMATIC FIRE DETECTORS AND ACCESSORIES
6.1 General Specifications
6.1.1 All the detectors shall be plug-in type and shall have twist lock action
fitting. An LED shall be incorporated which shall normally flicker indicating
alertness and should turn steady when a fire is sensed, enabling
immediate identification of the affected detector.
6.1.2 The mounting base of all type of detectors shall be identical. It should be
possible to plug-in any type of detector at any location without changing
the base and without distributing the external wiring. The detector
housing shall be damage resistant made of polycarbonate or aluminium
with plug-in housing base of universal type suitable for either surface or
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 18
recess mounting. J unction boxes for detector mounting shall be complete
with terminal block, etc. Additional terminals shall be provided to fit end
of line resistance, wherever applicable.
6.1.3 The detectors, which employ a Radio Active source shall be such that the
strength of the Radio Active material shall not exceed 1 micro curie.
6.1.4 It shall be possible to install all type of detectors (manual as well as
automatic) in the same fire alarm circuit/loop.
6.1.5 All the detectors shall have inbuilt safety device to monitor the removal
and pilferage of the detector.
6.1.6 All the detectors shall be on the approved list of Loss Prevention Council,
Under Writers Laboratory (USA) / Factory Mutual (USA) / Tariff Advisory
Committee.
6.1.7 All detectors shall be suitable for operation at DC power supply. All
analogue addressable detectors shall be suitable for installation using
fault tolerant wiring (class-A, style-6 wiring as per NFPA). Tapping shall
not be permitted in the case of such wiring.
6.2 All automatic detectors for microprocessor based fire alarm system shall
be analogue addressable type. The analogue addressable detectors shall
be continuously monitored to measure any change in their sensitivity due
to the environment (dirt, dust, temperature, humidity etc.). These
detectors shall give an advance indication to the panel regarding the need
for maintenance. The analogue reading sent by the detectors shall be
sensed and if there is a rapid increase, an alarm shall be generated.
However, if there is a gradual increase in the analogue reading, a
maintenance alert shall be generated by the DGFAP. It shall be possible to
generate maintenance reports from DGFAP.
6.3 All analogue addressable detectors shall preferably have the facility to set
the addresses from the DGFAP. Alternately dip switches in the detector
base shall be used for setting the detector address.
6.4 Manual call points/break glass boxes for microprocessor based fire alarm
system shall be addressable type. Each device shall have its own address
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 19
module which shall send a status signal to the DGFAP regarding its state
of actuation.
6.5 Heat Detectors
6.5.1 Heat detectors shall be of dual thermistor (negative temperature
coefficient resistor)/bimetallic/electro-pneumatic/thermo electric type,
working on the two methods i.e. rate of rise and fixed temperature.
6.5.2 The rate of rise element shall be carefully calibrated to ignore any normal
fluctuation in temperature, but to respond quickly when the temperature
rise is 9`C or more per minute.
6.5.3 The fixed temperature feature should be entirely independent of the rate
of rise element. The operating temperature of fixed temperature element
should be factory set at 57`C 5`C.
6.5.4 The detector shall be self-restoring type ensuring repeated use and easy
maintenance.
6.6 Ionisation Type Smoke Detector
6.6.1 Smoke detector shall be solid state type, working on ionisation principle
and shall preferably be of dual chamber and dual source type.
6.6.2 The radioactive source used in the detector shall not emit beta and
gamma rays and the strength of Radioactive material shall not be more
than 1 micro curie.
6.6.3 The detector shall be able to sense incipient fire by detecting the
presence of visible and invisible products of combustion like wood, paper,
ammonia processing paper, cloth, PVC, bakelite, nylon, foam, acrylic,
thermocole, Photo film, nylon, polyester, painted sheets, Teflon, leather
etc.
6.6.4 The sensitivity of the detector shall not vary with change in ambient
temperature, humidity, pressure or permissible voltage variation. Its
performance shall not be affected by an air current of 5 meter per
second. It shall have an inbuilt arrangement such that puffs of smoke or
hot air pockets do not inadvertently trigger the alarm. The detector shall
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 20
be protected against dust accumulation / ingress. It shall have insect
resistant screen to prevent nuisance alarms. All detectors shall be
identical in construction, design and characteristics to facilitate easy
replacement.
6.7 Photo Electric / Optical Type Smoke Detector
6.7.1 Photo electric/optical type smoke detectors shall work on the principle of
light scattering, utilising a light emitting diode. The sensitivity of the
detector shall be preset by the supplier to suit the site conditions.
6.8 UV Flame Detector
6.8.1 UV flame detectors shall work on the principle of a vacuum photodiode
tube to detect the UV radiation that is produced by a flame.
6.8.2 UV flame detectors shall react to ultraviolet rays of a flame. The detector
shall not be actuated by artificial lights, sunlight incident through a
window pane. False alarm check circuit shall be incorporated to prevent
false due to intermittent flash or lightning.
6.9 IR Detectors
6.9.1 IR detectors shall work on the principle of a single wavelength infrared
flame detector using one of several different photocell types to detect the
infrared emissions in a single wave length band that are produced by a
flame.
6.9.2 IR detectors shall react to the infrared rays of a flame. It should be
sensitive enough to detect smoky fires in which flame is hardly
recognisable. The detector should not react to extremely glaring artificial
light or direct sunlight. The detector shall be completely solid state type.
6.10 Linear Beam Detector
6.10.1 The linear beam detector shall work on the principle of obscuration of
infrared light beam by particles of smoke. The sensitivity shall be such as
to enable operation at 30% to 50% obscuration.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 21
6.10.2 Linear beam detector shall consist of separate transmitter and receiver.
Linear beam detector shall be suitable for application in high roofed
locations such as ware houses etc. The detector shall preferably be
powered from the loop signal itself. However if external power supply is
required the same shall be explicitly stated by the vendor and the supply
shall be supplied from source with battery back-up as specified in clause
4.1.2.
6.11 Heat Sensing Cables
6.11.1 Heat sensing cable shall be analogue type. It shall consist of four copper
conductors, each covered with a colour coded, negative temperature co-
efficient material. The cores shall be twisted together and protected by an
outer sheath of high temperature flame retardent PVC insulation. External
mechanical protection shall be provided over the sensor cables. Vendor
shall provide control unit for each 10 mtr. Length of the sensor cable.
6.12 Manual Break Glass Boxes
6.12.1 The break glass box shall be fabricated out of 14 gauge cold rolled sheet
steel. Alternately the break glass box may be made of die cast aluminium
alloy such as LM6. It shall have IP-55 enclosure and weatherproof
construction suitable for outdoor installation. The break glass box shall
have a minimum dimension of 100x100x80mm.
6.12.2 The box shall be fabricated in such a way so that it can be mounted, flush
to the wall or on the surface without any modification. Two nos. 19mm
knock outs shall be provided at the bottom of the box to facilitate the
cable/conduit entry. The glass shall cover at least 30cm
2
area and shall
have a thickness not exceeding 2mm.
6.12.3 The break glass box shall have a push button element kept in pressed
condition by a glass sheet fitted in the front of the box.
6.12.4 The break glass box enclosure shall be painted with fire red colour (shade
536 of IS-5) epoxy painting and an inscription Break Glass in Case of
Fire, shall be painted in white letters or rivetted on the enclosure by a
steel nameplate. A suitable nickel plated brass hammer, duly chained to
the box with stainless steel chain shall be provided with each box for
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 22
breaking the glass. Each box shall have a distinct identification number
boldly painted on it.
6.12.5 If specified in the enquiry documents / data sheets, the break glass box
shall have a suitably wired telephone hand set to facilitate communication
between the break glass box and the central annunciation panel. In such
a case the telephone hand set mounted on hook switch shall be provided
in a separate lockable weather proof enclosure.
6.13 Response Indicator
6.13.1 If specified in the enquiry documents/data sheets, response indicators
shall be provided in a weatherproof box which shall be suitable for wall
mounting. The response indicators shall be connected to the detectors
directly and shall be complete with terminal blocks suitable to accept
cables with upto 2.5 sq.mm. copper conductor. In the normal state of
detector, the LED shall flicker, but in the event the detector goes into
alarm condition, the LED shall glow steadily. LEDs shall be red in colour
with 5mm dia as a minimum.
6.13.2 Response indicators shall be employed only in case of non-addressable
systems.
6.14 Exit Signs
6.14.1 Exit signs shall be fabricated out of 16 gauge cold rolled sheet steel. This
shall be suitable for wall mounting or hanging from ceiling.
6.14.2 Fire Exit / No Fire Exit shall be displayed on opposite of the exit sign by
means of 5mm dia. Red LEDs or back-lit text. It shall derive power from
data gathering cum fire alarm panel and shall operate on DC power
supply.
6.15 Hooters
6.15.1 The unit shall consist of solid state circuitry on a printed circuit board, a
loudspeaker and a flashing lamp housed in a weatherproof dust tight, wall
mounting type enclosure. The hooters shall, at least, have 102db(A)
output measured at 1 meter distance. The nit shall derive power from the
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 23
fire alarm panel and operate on DC power. In the event of fire, the hooter
shall raise pulsating audio alarm and the lamp shall flash.
6.16 Flashing Lights
6.16.1 The unit shall consist of solid state circuitry on a printed circuit board and
a red caped incandescent lamp and audio unit housed in a dust tight, wall
/ ceiling mounting type enclosure. It shall derive power from the data
gathering cum fire alarm panel and operate on DC supply.
6.16.2 Flashing lights shall be installed in the enclosed areas where clean agent /
CO
2
is to be dumped. In the event a signal for clean agent / CO
2
release is
given, the lamp shall start blinking with a warning sound enabling
operating personnel to evacuate the area. The audio unit (hooter) shall
have 102 db (A) output measured at 1 meter distance.
6.17 Clean Agent / CO
2
Release And Inhibit Switches
6.17.1 This unit shall consist of pull type release and inhibit switches clean agent
/ CO
2
. The unit shall be fabricated out of 18 gauge cold rolled sheet
suitable for wall mounting. Switches shall be pulled to release or inhibit
clean agent / CO
2
.
Release switches shall have inscription:
PULL TO RELEASE CLEAN AGENT / CO
2
And inhibit switches shall have inscription:
PULL TO RELEASE CLEAN AGENT / CO
2
6.18 Zener Barrier
6.18.1 Zener barriers, located necessarily in unclassified/non hazardous areas,
may be employed for wiring detectors/break glass boxes installed in
hazardous areas. These shall render the circuit beyond the zener barrier
intrinsically safe.
6.18.2 Not more than 10 detectors shall be connected to one zener barrier.
Zener barriers may be located either in the Zonal panel or DGFAP, if
permitted by geographic proximity of detectors and zonal panel or DGFAP
or may be located close to the detectors / manual call points.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 24
6.18.3 Wherever zener barriers are provided, in safe area outside the zonal panel
or DGFAP, they shall be housed in their own enclosure and shall be dust
and vermin proof, weatherproof with IP-55 degree of protection as a
minimum.
6.19 Short Circuit Isolator/ Fault Isolator
6.19.1 Short circuit isolator/Fault isolator shall be installed, if specified in the
enquiry document/data sheets.
Fault isolator shall be designed to provide short circuit protection to an
analogue addressable detector loop. It shall be possible to wire the fault
isolator at any point in the detector loop.
6.19.2 On occurrence of a fault (short circuit), the isolator shall cut power to all
devices installed beyond the isolator in the loop.
6.19.3 The fault isolator shall have the capability to continuously check the
faulted side of the loop to determine if the fault still exists. On
rectification of the fault, the isolator shall automatically reset itself.
6.19.4 In case the fault isolator nearest to the fault does not activate first, the
isolator shall query other isolators nearest to the short circuit and then
de-activate/restore itself. The restoration shall continue along the loop
until only the isolator closest to the fault is left activated.
6.19.5 The DGFAP panel shall be capable of accessing detectors/devices installed
outside the zone covered by the fault isolator modules.
6.19.6 Fault isolator modules shall be housed in a dust and vermin proof,
weather proof enclosure, with IP-55 degree of protection as a minimum.
6.20 Sirens
6.20.1 Sirens shall be industrial type with minimum 2.5km unidirectional range
(i.e. 5km diametrical range) against the wind direction.
6.20.2 The decibel level of the siren shall, at least be, 132db(A) at 1 meter, to
meet the audibility requirement for the above range. Unless otherwise
specified, Sirens shall operate at 240V, 3ph. AC. Sirens shall be housed in
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 25
weatherproof enclosure and shall be supplied along with direct-on-line
starters. Power supply for sirens shall be derived from a source with
battery back-up as specified in clause 4.1.2.
7.0 ADDITIONAL REQUIREMENTS FOR FIRE ALARM SYSTEM TO BE
INSTALLED IN HAZARDOUS AREA
7.1 In general the CFAP, DGFAPs, Zonal fire alarm panels, mimic panels and
repeat alarm panels shall be located in control room environment which is
non-hazardous. However, if specified in the enquiry document/data
sheets, the enclosure for the detectors, panels and other equipment shall
have flameproof construction, conforming to IS-2148 and shall be suitable
for installation in hazardous areas classified as Zone-1 and/or Zone-2,
with gas group IIB or as specified in the material requisition/data sheet.
All equipment for hazardous area installation shall be complete with cable
glands as specified in clause 5.4.4.2.
7.2 Equipments which can not have flameproof construction shall be
intrinsically safe in design and Zener barriers shall be provided to restrict
the energy levels.
7.3 For analogue addressable fire alarm systems, manual call points, address
interface units, automatic detectors etc. which are to be installed in
hazardous area shall preferably have flame proof construction to permit
the use of class-A, style-6 fault tolerant wiring as per NFPA-72, without
employing T-tapping. As an alternative,intrinsically safe address interface
units, automatic detectors etc. may be permitted provided they are wired
beyond zener barriers, located in non-hazardous area. Fire Alarm Circuit
beyond zener barrier shall be intrinsixcally safe type confirming to IS-
5780.
7.4 For conventional fire alarm systems, manual call points, automatic
detectors etc. which are to be installed in hazardous area shall preferably
have flameproof construction. As an alternative, intrinsically safe
automatic detectors may be permitted provided they are wired beyond
zener barriers, located in non-hazardous area and meet the requirements
of IS-5780.
7.5 Manual call points shall, however, be in flameproof construction only for
either of the above fire alarm systems.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 26
8.0 SPECIFIC REQUIREMENTS FOR INTERFACE WITH CLEAN AGENT
/ CO
2
RELEASE SYSTEM
8.1 In the case of conventional fire alarm system, clean agent / CO
2
dumping
area shall be divided at least into two zones for fire detection purposes.
The detectors shall be installed in cross zoning manner. Signals for clean
agent / CO
2
release shall be sent only when at least two zones have
detected the fire. The blinking lights shall operate in the affected area.
Two type of detectors in cross zones shall be provided in each dumping
area.
On detection of fire (Min. two detectors), a signal from zonal Fire Alarm
Panel shall be generated which shall open the valves for dumping clean
agent / CO
2
.
8.2 In the case of analogue addressable fire alarm system, cross-zoning may
not be necessary as the system shall be deemed to be capable of filtering
out false alarms due to dust, dirt and other atmospheric changes. Signals
for clean agent / CO
2
release shall be initiated on receipt of fire alarm
from any detector in the protected area. The blinking lights shall operate
in the affected area.
8.3 Clean agent / CO
2
can be released or inhibited by the Clean Agent/ CO
2
release and inhibit switch located outside the protected area or from the
fire alarm panel. The contact for clean agent / CO
2
release alarm shall be
taken from the pressure switch provided in the clean agent / CO
2
manifold. Provision in F.A. panel shall be kept to wire pressure switch
contacts.
9.0 ENGINEERING REQUIREMENTS
9.1 The vendor shall perform basic and detailed engineering activities, unless
specified otherwise in the material requisition/data sheets.
9.1.1 Conventional Fire Alarm System
9.1.1.1 For conventional fire alarm systems basic engineering shall include the
development of block-diagram furnished by MECON/Owner.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 27
9.1.1.2 The detailed engineering shall broadly include the preparation of
MCP/detector layout drawings, based on MECON/Owners building / plant
layout drawings. Preparation of cable schedules, interconnection
drawings, equipment installation drawings, sizing of various equipment
such as batteries, battery chargers etc. preparation of G.A. drawings of
various equipment.
9.1.2 Analogue Addressable Fire Alarm System
9.1.2.1 For microprocessor based analogue addressable fire alarm systems basic
engineering shall include the development of block-diagram, finalising the
requirement of maximum permissible lengths for data highway/detector
loops, configuring the central fire alarm panel requirements etc.
9.1.2.2 The detailed engineering shall broadly include the preparation of
MCP/detector laout drawings, based on MECON/Owners building/plant
layout drawings. Preparation of cable schedules, interconnection
drawings, equipment installation drawings, sizing of various equipment
such as batteries, battery charger, UPS etc. allocating addresses to
various detectors and defining their sensitivity settings.
10.0 TESTING AND ACCEPTANCE
10.1 During fabrication, panel shall be subject to inspection by MECON/Owner
or by any authorised representative, to assess the progress of work. The
manufacturer shall furnish all necessary information concerning the
supply to MECON/Owners representative. MECON/Owners representative
shall be given free access in the manufacturers works from time to time
to inspect the progress of the work. Three weeks notice shall be given by
the vendor to MECON/Owner for witnessing the final routine tests of
complete assembly to ensure satisfactory working of all components.
10.2 All routine tests as specified by the applicable codes and standards shall
be carried out at the manufacturers work under his care and expense.
10.3 Type test certificates, from a recognised testing organisation, shall be
furnished alongwith the bids. Type test certificates for hazardous area
equipment shall also be furnished alongwith the bids.
MECON LI MITED
Delhi
TECHNICAL SPECIFICATION
FOR FIRE DETECTION AND
ALARM SYSTEM
MEC/ TS/ 05/ 21/ 081H
MECON LIMITED
TS FDA - 28
10.4 Panels shall be tested for functional adequacy, at manufacturers works by
simulation of fire/fault condition. Minimum testing shall include tests as
specified in IS-2189 or as per the standards prevalent in the country of
origin.
10.5 If specified in the enquiry document/data sheets, vendor shall conduct
tests at site, after the entire fire alarm system is installed and inter
connected by cables. These tests shall establish the operational
correctness of the system i.e. all panels, detectors etc. Minimum testing
shall included tests as specified at clause 11.2 of IS-2189.
11.0 PACKING AND DESPATCH
11.1 All the equipment shall be divided into several sections for protection and
ease of handling during transportation. The equipment shall be properly
packed for transportation by ship/rail or trailer. The panel shall be
wrapped in polythene sheets before being placed in crates to prevent
damage to finish. Crates shall have skid bottom for handling. Special
notations such as Fragile, This side up, Centre of gravity, Weight etc.
shall be clearly marked on the package together with Tag nos. P.O. Nos.
etc.
11.2 The equipment may be stored outdoors for long periods before erection.
The packing shall be completely suitable for outdoor storage in areas with
heavy rains/high ambient temperature.
Page 1 of 5
STANDARD
SPECIFICATION
FOR
MEDIUM VELOCITY WATER SPRAY SYSTEM
MECON LIMITED
Delhi
TECHNICAL
SPECIFICATION MEDIUM
VELOCITY WATER SPRAY
SYSTEM
MEC/ TS/ 05/ 21/ 081K
MECON LIMITED
Page 2 of 5
1.0 SCOPE OF SUPPLY OF EQUIPMENT AND SERVICES
1.1 GENERAL
This specification lays down the broad technical specification for the medium velocity
water spray system to be provided for various areas as specified in SOR, specifications.
For fluids flashing at below 65
o
C (150
o
F), extinguishments is always not possible or
even desirable and for these, Medium Velocity Water Sprayers need to be installed to
provide cooling, controlling the burning and/or exposure protection to protect
processing blocks, processing equipments, structures, flammable liquid and gas
vessel, piping and equipment LPG bottling plants, spot protection etc..
1.2 SCOPE
This specification covers design, supply, fabrication, erection, testing and
commissioning complete with all mechanical and electrical items as elaborated in the
following paragraphs. The system shall consist of the following as mechanical part of
the system.
Deluge valve assembly
Piping for Water, pipe support, flanges etc.
Sprinkler based detectors
Medium velocity spray nozzles or sprayers
Fittings and valves viz. sluice valve, non-return valve, float valve, drain valve
etc.
2.0 DESCRIPTION OF THE SYSTEM
This is a special fixed pipe system connected to a reliable source of fire protection
water supply and equipped with water spray nozzles for specific water discharge and
distribution over the surface or area to be protected. The piping system is connected
to the water supply through an automatically actuated Deluge Valve, which initiates
flow of water. Automatic actuation is achieved by operation of automatic detecting
equipment installed alongwith water spray nozzles. The system comprises of:
a) SPRAY NOZZLE
MECON LIMITED
Delhi
TECHNICAL
SPECIFICATION MEDIUM
VELOCITY WATER SPRAY
SYSTEM
MEC/ TS/ 05/ 21/ 081K
MECON LIMITED
Page 3 of 5
It is normally open water discharging device called Sprayers which, when supplied
with water under pressure will distribute the water in a special, directional pattern
peculiar to the particular device. These nozzles are made in a range of orifice sizes
with varying discharge angles so that discharge can be controlled for optimum
protection.
b) DELUGE VALVE
Deluge valve is quick opening valve, which admits water automatically to a system of
projectors or sprayers and is operated by a system of detectors and/or sprinklers
installed in the same areas as nozzles.
c) DETECTION SYSTEM
In case of water spray systems, detection systems are required for activating the
Deluge system for spot protection (outdoors and indoors).
For the above protections, sprinklers are found in extensive application in view of
their reliability. However the contractor can recommend / suggest other types of
detection systems. The design of detection system by sprinklers varies from risk to
risk in case of water spray systems and shall be governed in accordance with TAC
guidelines for rules of water spray systems.
The system shall comprise water supply at high pressure, adequate number of spray
nozzles and quartzoid bulb detectors to be located at strategic points, deluge valve,
piping, audio-visual alarm system, control panel etc. Water shall be tapped from
nearby sprinkler line. Water from static water tank shall be pumped to the system by
means of the main pump to obtain the required minimum pressure at the remotest
nozzle. Provision for 100% standby pump set to meet the emergency requirement
shall be made. The delivery side of the pump shall be connected through a set of back
pressure valves and stop valves to the Emulsifier System. These pumps shall have
automatic starting facility, which will start the pumps whenever the delivery pressure
drops below a preset valve.
High velocity water spray nozzles shall be installed all around the transformers. The
number, spacing and discharge angles shall be so decided as to give effective
coverage.
The quartzoid bulb heat detectors shall be placed on all sides of the transformer. The
detectors shall be planned to be mounted on independent pipe line of compressed air.
The heat sensing quartzoid bulb detectors shall shatter at 79 deg. C in case of a fire,
creating a drop in the air pressure in the detector pipe line.
MECON LIMITED
Delhi
TECHNICAL
SPECIFICATION MEDIUM
VELOCITY WATER SPRAY
SYSTEM
MEC/ TS/ 05/ 21/ 081K
MECON LIMITED
Page 4 of 5
Under normal condition the system shall be kept in automatic mode. Due to leakage of
water in the system, the water level in the tank shall fall resulting in pressure drop in
the system. This shall actuate the pressure switch to start the pump. The jockey pump
shall be automatically started by the actuation of level switch. When the water level
rises beyond a preset level, the jockey pump shall be stopped automatically by the
actuation of the level switch.
In case of fire, the temperature will rise and the gas inside the quartzoid bulb detector
will expand to shatter the bulb. Water will then be released through the detector
openings reducing the pressure rapidly. This will cause the deluge valve clack to get
lifted by the hydraulic thrust on the downside of the deluge valve, which in turn shall
allow water to get sprayed through the nozzles. This will result in rapid fall in pressure
in the water line, which will actuate the pressure switch to start the main electrically
driven pump. In case of power failure the pressure shall drop further to actuate the
pressure switch for starting the standby pump.
3.0 EQUIPMENT DETAILS (MECHANICAL)
3.1 AUTOMATIC DELUGE VALVE
The deluge valve shall be a basically hydraulically operated water valve actuated by
release of water in the detector pipe work. The deluge valve assembly shall be
provided with `Y' type strainers in order to segregate foreign matter.
3.2 QUARTZOID BULB DETECTORS
Quartzoid bulb detectors shall be provided as heat sensing elements. The detectors
shall be placed encompassing the entire surface of the transformer. The detectors shall
be mounted on independent pipeline charged with water at pressure of about 4
kg/sq.cm. The heat sensing quartzoid bulb shall operate at 79 deg. C. Area covered by
each detector shall not be more than 9.0 sq.m.
3.3 SPRAY NOZZLES
High velocity water spray nozzles shall be installed all around the transformer in such a
manner that the entire surface of the transformers is encompassed for uniform spray
of water. For this a piping cage shall be erected around the transformer. The number,
spacing and discharge angles of the nozzles shall be so decided as to give effective
coverage with an optimum discharge of water (11 l/sq.m/minute) to minimise the
extent of damage to the equipment.
MECON LIMITED
Delhi
TECHNICAL
SPECIFICATION MEDIUM
VELOCITY WATER SPRAY
SYSTEM
MEC/ TS/ 05/ 21/ 081K
MECON LIMITED
Page 5 of 5
3.4 VALVES
All the valves shall be provided with matching flanges, bolts, nuts, gaskets, washers
etc. Gate valves shall conform to the relevant class of IS: 780/ IS: 2906 while non-
return valves shall be as per IS: 5312. All the valves shall be provided with proper
support.
3.5 PIPES AND FITTINGS
Pipes upto DN 150 shall be ERW steel pipes as per IS: 1239 Part-I (medium) and pipes
above DN 150 shall be ERW steel pipes as per IS: 3589. Pipe fittings such as bends,
tees, reducers of size less than DN 150 shall be as per IS: 1239 Part-II and of sizes
above DN 150 shall be fabricated. All the pipes shall be adequately supported.
The underground pipe shall be laid 1 m below the ground. The MS pipes to be laid
underground shall have suitable coating and wrapping with 2 coats of coal tar, hot
enamel paint and two wraps of reinforced fibre glass tissue or bitumenised Hessian.
The piping shall be capable of withstanding for two hours a pressure of 3.5 kg/sq.cm
in excess of the maximum working pressure.
All the flanges shall be faced and have jointing of rubber insertion or asbestos
compound. Wherever the underground pipes cross the road, suitable encasing pipes
shall be provided.
The laying of pipes shall be included in the tenderer's scope of work.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
STANDARD SPECIFICATION
FOR
DELUGE VALVE
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
TS-DV- 1
CONTENTS
1.0 SCOPE
2.0 CODES AND STANDARDS
3.0 DESIGN REQUIREMENT
4.0 MATERIAL OF CONSTRUCTION
5.0 CONSTRUCTION AND PERFORMANCE
6.0 INSPECTION AND MARKING
7.0 INFORMATION REQUIRED FROM VENDOR
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
TS-DV- 2
1.0 SCOPE
This standard lays down requirements regarding construction, material, shape, and
method of operation, performance and test of automatic deluge valve for fire water
distribution.
2.0 CODES AND STANDARDS
The following codes and standards shall be followed for deluge valve:
1. Rules for automatic sprinkler installation published by TAC.
2. Applicable ISI codes
3. NFPA guidelines
3.0 DESIGN REQUIREMENT
3.1 An automatic deluge valve shall consist of following:
a) Deluge Valve unit
b) Diaphragm Unit
c) Integral Test and drain valve manifold
d) Alarm System
e) Priming Equipment
f) Installation stop valve with pressure guage and outlet valve
g) Detector pipe work manifold
h) Emergency release box
i) Solenoid valve system for remote actuation of deluge valve
3.2 Size and capacity of deluge valve shall be as under:
Size Rated Flow Working Pressure
Inch(mm) M3/hr Kg/cm2 g.
2(50) 10 to 30 7.0 to 10.5
3 (75) 30 to 50 7.0 to 10.5
4(100) 51 to 80 7.0 to 10.5
6(150) 81 to 150 7.0 to 10.5
8(200) 151 to 300 7.0 to 10.5
3.3 The deluge valve shall be provided with solenoid operated air release valve for
remote operation. If deluge valve in located in hazardous area, alarm switch shall be
intrinsically safe and flameproof.
4.0 MATERIAL OF CONSTRUCTION
4.1 For non saline water service, the material of construction shall be as follows:
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
TS-DV- 3
Body : Cast Iron to Is 210 Gr. FG 200
Seat : Bronze
Clapper : Bronze
Clack : Graphite Iron
Diaphragm spindle & hinged pin : SS 304
Test and drain valve : Cast Iron
Installation stop valve & outlet valve : Cast Iron to Is:780 Class PN 1.6
Check Valve : IS:5312 Part-II
Diaphragm & Seat Rubber : Neoprine
4.2 For saline water service, aluminium bronze material shall be used in place of cast
iron.
5.0 CONSTRUCTION AND PERFORMANCE
5.1 The deluge valve unit shall be provided with a clack to keep the valve close through
a diaphragm unit.
5.2 The deluge valve shall also be fitted with an integral test and drain manifold. It shall
consist of 50mm test and drain valve, air body drain valve and a drip valve.
5.3 The test valve shall allow water to flow through the deluge valve to drain during
testing of deluge valve and to drain water from distribution pipe after fire. At open
position the valve clack shall be held against its seating by an internal compression
spring of sufficient strength to keep it in closed position till the pressure acting on
underside of it does not exceed approx. 0.3 Kg/cm2. The clack will open at pressure
exceeding 0.3 Kg/cm2.
5.4 The drain valve shall drain all the water from the deluge valve body and the outlet
connections during maintenance of the deluge valve. The drain pipe work is to be
designed to periodically check the rate of flow available in the system to satisfy the
requirements appropriate to the hazard class for which the deluge valve is provided.
Flow measurement shall be checked with differential pressure.
Water operated alarm motor gang shall be connected to the test and drain valve so
that it gives an alarm as the deluge valve opens.
5.5 On detector pipe work manifold, test valve shall be provided at one end while on air
supply pipe one air pressure regulator, check valve and gate valve shall be provided.
Both detector pipe work and air supply line shall be terminated with flanged ends.
Piping shall be GI to IS 1239 medium grade. Instrument air shall be supplied at a
specified pressure by the owner. Vendor shall supply suitable air pressure regulator.
In addition to above an electric pressure switch shall be provided to give alarm at
Low air pressure and fire condition. Low air pressure alarm shall be set at
1.7Kg/cm2 while for fire it shall be set at 0.7Kg/cm2. When fire occurs and deluge
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
TS-DV- 4
valve opens, the two alarms shall be given in rapid succession.
Provision for changing the set pressure of both the alarms shall also be provided. A
test plunger shall be provided to test the alarm switches without disturbing the
valves.
An additional low air pressure alarm shall be provided to indicate low-low air
pressure at approx. 1.4 Kg/cm2. The alarm switches shall thus activate at low
pressure of 1.7 Kg/cm2 and dangerously low pressure of 1.4 Kg/cm2 along with
alarm to initiate warning of fire. Vendor shall confirm these set pressure based on
inlet water supply pressure.
For manual remote operation of the valve, solenoid operated air release valve or gas
based detection system activated valve shall be provided.
5.6 Installation stop valve and outlet valve above deluge valve shall be as per IS:780
class PN 1.6. In addition following provision shall be made:
Both the valve must be strapped (not chained) and padlocked in open position at all
normal times. End flanges of both the valves shall be flat face, dimensions
confirming to ANSI B 16.5 150 lb rating.
5.7 The deluge valve shall be tested for operation / opening at set pressure and
operation of the alarms at set pressures.
5.8 For testing and setting of deluge valve, a priming valve and a vent shall be provided
with deluge valve assembly. At all normal times and when testing the deluge valve
according to various tests required, the body of the deluge valve shall remain full of
water.
5.9 Pressure guage shall be fitted immediately above the deluge valve on water supply
line. Another pressure guage shall be provided on detector pipe work manifold.
Pressure gauge shall be bourdon type and shall be weather proof to NEMA-4. Vendor
shall specify the range of the pressure gauge and also submit detailed specification /
data sheet of the instrument.
5.10 The complete valve assembly shall be of good workmanship and furnish and shall be
free from burrs and sharp edges. All waterways shall have smooth finish.
5.11 The deluge valve shall be tested for a test pressure of 25Kg/cm2.
6.0 INSPECTION AND MARKING
6.1 Owner / MECON shall have access at all reasonable times to the manufacturers
works where the deluge valve assembly are being manufactured or being tested.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
DELUGE VALVE
MEC/ TS/ 05/ 21/ 081F/ B
MECON LIMITED
TS-DV- 5
6.2 Deluge valve assembly shall be clearly permanently marked with the purchasers
name, design and test pressure.
7.0 INFORMATION REQUIRED FROM VENDOR
7.1 The vendor shall furnish the following information alongwith the offer and for
approval, prior to fabrication-
a) General arrangement of deluge valve assembly and elevation.
b) Constructional features of deluge valve assembly
c) Data sheet of the deluge valve
d) Initial setting procedure and details of deluge valve
e) Automatic and manual operational procedures
f) Periodic testing and safety procedures.
7.2 Following information shall be furnished by the vendor along with the supply of the
deluge valve :
7.2.1 Instruction books for the guidance of the user including both the operating and
normal maintenance procedures. The books shall include an itemised and illustrated
part list / spare parts list giving reference no. of all the wearing parts.
7.2.2 Duly approved final drawings listed above in clause 7.1
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
LANDING VALVE
MEC/ TS/ 05/ 21/ 081E
MECON LIMITED
STANDARD
SPECIFICATION
FOR
LANDING VALVE
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
LANDING VALVE
MEC/ TS/ 05/ 21/ 081E
MECON LIMITED
TS-LV- 1
1.0 SCOPE :
The specification covers the general requirement regarding the material, design and
construction, performance, test and type of landing valve.
The single / double outlet landing valve mainly consists of landing valve with complete
set.
2.0 MATERIAL:
SL. NO. ITEM / COMPONENT MATERIAL OF CONSTRUCTION
1. Valve body Shall be of corrosion resistant alloy steel or
nickel brass casting conforming to IS: 3444
2. Bonnet, check-nut, stop
valve, instantaneous
female outlet and blank
cap
Shall be of leaded tin bronze conforming to
grade LT B-2 of IS: 318 or aluminium alloy
conforming to IS designation 4225, 4450
and 4600 of IS: 617. All aluminium parts
shall of be die-cast.
3. Valve spindle Shall be made of brass rod conforming to
IS: 320 for valve body of leaded tin bronze
and of stainless steel conforming to IS:
6603 for valve body of aluminium.
4. Handle wheel Shall be made of M.S. conforming to IS:
1030.
5. Seat valve and washer Shall be of leather conforming to IS: 581
6. Gland packing Shall be asbestos threaded conforming to
IS: 4687.
7. Spring Shall be of phosphor wire conforming to
IS: 7608 for valve body of leaded tin
bronze and of stainless steel wire
conforming to IS: 6528 for valve body of
aluminium.
8. Tooth Shall be forged from forged brass material
conforming to grade FLB of IS: 6912 of IS:
291
9. Blank cap ABS plastic
The materials shall be as per IS: 5290. The various alternatives available in the BIS
for landing valve body are aluminium alloy, LeadTin-Bronze and stainless steel.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
LANDING VALVE
MEC/ TS/ 05/ 21/ 081E
MECON LIMITED
TS-LV- 2
However, materials selection shall be as per data sheet (if available) / Companys
approval.
Flanges for hydrant valve shall have dimensions conforming to ANSI B 16.5 150 lbs
rating flat slip-on type or MS plate flange as per IS 6392 table 17.
3.0 Design and Construction:
The design and construction of landing valve shall be as per IS:5290, TAC guidelines
and other government codes / regulations and as mentioned in this specification.
1. Water mains coming to post shall be of 150 & 100mm M.S construction and
provided with Double outlet landing valve.
2. All hydrant outlets shall be situated 1m above floor level.
3. Only oblique hydrants with outlet angled towards floor shall be used. The
hydrant couplings shall be of the instantaneous spring lock (female) type of
60mm dia and valves shall be of the slow down type.
4.0 Performance Requirements
4.1 Water Tightness Test for the valve
The stop valve shall be fully closed by screwing down the spindle. A hydrostatic
pressure of 1.4 MN/m
2
(14 kgf/cm
2
) shall then be applied to each valve on its inlet
side. There shall be no leakage through the valve and its seat.
4.2 Hydrostatic Pressure Test.
Each assembled landing valve shall be subjected to a hydrostatic pressure of 2.1
MN/mm
2
(21 kg/cm
2
) as per IS:5290 with the valve open and outlet closed for a period
of 2 minutes for the purpose of locating porosity in the casting when so tested, it
shall not fail or show any sign of leakage either through the valve body or through the
gland of the spindle.
4.3 Flow Test
Test shall be discharged through the valve assembly and its flow shall be measured
using flow meter or V-notch. The flow shall not be less than 900 LPM for Type A and
1800 LPM for Type B at 7MN/m
2
(7kgs/cm
2
) provided feed to the valves is not less
than these figures.
5.0 Workmanship and Finish
5.1 All parts shall be of good finish, clear of burrs and sharp edges. All castings shall clean
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
LANDING VALVE
MEC/ TS/ 05/ 21/ 081E
MECON LIMITED
TS-LV- 3
and sound and shall be free from plugging, welding or repair of any defects.
The valve top except the face of the flange and the instantaneous outlet shall be
painted fire red of shade no. 536 of IS: 5. The outside of instantaneous outlet shall
be highly polished. The hand wheel shall be painted black. Paints shall conform to
IS: 2932: 1974.
6.0 Anticorrosive Treatment and Painting
6.1 All steel components subject to direct water contact shall be hot dipped galvanised to
minimum thickness of 0.12mm. The thickness of coating shall be measured as per IS
3203. External surfaces and non-ferrous components may be wetted with lead tin alloy
by electrical deposition process.
6.2 The stand post and its arms, valve top except the face of the flange and the
instantaneous outlet from outside shall be painted with three coats of anti corrosive
fire red paint of shade No. 536 of Is 5. The outside of instantaneous outlet shall be
highly polished. The hand wheel shall be painted black. Paints shall confirm to Is 2932.
Internal surface shall be painted with three coats of chlorinated rubber based rasin
paint or zinc chromate paint.
7.0 Marking
1. Each assembled valve shall be clearly and permanently marked on the valve
body as follows:
a) Manufacturers name or trade-mark
b) Code letter indicating the type of valve (Inscribing type of
instantaneous female outlet),
c) Year of manufacture
d) The valve assembly shall also be marked with the BIS certification mark
and IS: 5290.
8.0 Inspection
There shall be provision for inspection by third party inspection agency at contractors
cost. The agency shall have access at all reasonable times to the manufacturers
works, where hydrants are being manufactured and / or tested. However specifically
prior call for inspection shall be communicated for performance test of hydrants.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
WATER MONITOR
MEC/ TS/ 05/ 21/ 081C/ A
MECON LIMITED
STANDARD SPECIFICATION
FOR
WATER CUM FOAM MONITOR
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
WATER MONITOR
MEC/ TS/ 05/ 21/ 081C/ A
MECON LIMITED
CONTENTS
1. SCOPE
2. MATERIAL
3. DESIGN AND CONSTRUCTION
4. HYDRAULIC PERFORMANCE
5. WORKMANSHIP AND FINISH
6. ANTICORROSIVE TREATMENT AND PAINTING
7. TEST
8. MARKING
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
WATER MONITOR
MEC/ TS/ 05/ 21/ 081C/ A
MECON LIMITED
TS-WM-1
1.0 SCOPE
This specification covers the general requirements regarding the material, design and
construction, performance and test for stand post type water cum foam monitor.
2.0 MATERIAL
2.1 Monitor body, swivel joints, worm wheel, base flange and change over valve
assembly shall be made of copper alloy confirming to IS:8442 Cl. 3.3.1. Body
shall be of C.S. pipe heavy grade to IS: 1239 and base flange shall be of M.S.
to IS 226 or IS 6392.
2.2 Foam and water barrel shall be extruded aluminium pipe to IS:1285. Water
barrel can be from M.S. seamless pipe to IS:1239 heavy grade.
2.3 Water nozzle shall be made from aluminium alloy to IS:617 designation 4450
when water barrel is made from extruded aluminium pipe. It shall be made
from copper alloy as specified in IS: 8442 Cl. 3.3.1 when water barrel is of
MS pipe to IS: 1239 H. gr.
2.4 Pick up tube shall be made from rubber hose with chrome plated brass
strainer.
2.5 Worm gear for traverse mechanism shall be made from phosphorus bronze or
copper alloy as per Cl. 3.3.1 of IS: 8442.
2.6 Nuts and bolts for base flange and change over valve shall confirm to
IS:1367 Cl.10.9 and 12 respectively while gasket shall be of CAF 40 to
IS:2712.
2.7 Drain valve shall confirm to IS: 778 class 2. Locks on swivels shall be made of
brass to IS:291.
3.0 DESIGN AND CONSTRUCTION
3.1 Monitor shall be capable of discharging 1750 lpm at a pressure of 7 Kg/cm2.
3.2 It shall have traversing mechanism to give 360` in either direction in
horizontal plane and 125` in vertical plane (80`, -45`) through geared unit
with worm wheel operated by separate hand wheel for horizontal and vertical
rotation. Swival joints shall be provided both for horizontal and vertical
rotation. The arrangement shall be such that monitor shall be self locking
type and operated by a single person.
3.3 The monitor shall be provided with a change over valve along with its
assembly for instantaneous switch over of discharge from water to foam or
vice versa as desired. The valve shall be lever operated type.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
WATER MONITOR
MEC/ TS/ 05/ 21/ 081C/ A
MECON LIMITED
TS-WM-2
3.4 A foam inductor shall be provided behind the air intake chamber of foam
maker in foam monitor. A flexible rubber pick up tube of 3m length having
strainer at the inlet shall be provided. A foam compound control valve
capable of metering and inducing 3% to 6% of foam compound shall also be
provided.
3.5 The monitor shall be mounted on a 100mm (4) N.B. flat face slip on type
flange confirming to ANSI B 16.5 150lbs rating. Bolts and nuts for base flange
shall have dimension confirming to ANSI B 16.5 Gasket shall be full face 3mm
thick with drilling dimension same as for flange.
3.6 Near the base flange a drain connection shall be provided with a 15mm
(1/2) NB drain valve at the end of pipe. The drain pipe shall be long enough
to drain water away from the base flange.
3.7 The threaded end of the water nozzle shall be hexagonal to facilitate
screwing of the nozzle on the water barrel with nozzle spanner. Threads shall
confirm to IS:2643 (Pt.-1) with class A tolerance.
3.8 The inner surface of the nozzle shall be finished smooth and polished for the
converging length of the nozzle.
4.0 HYDRAULIC PERFORMANCE
4.1 Monitor shall be capable of discharging 1750lpm at a pressure of 7 Kg/cm2.
4.2 The horizontal ranges for water and foam jet shall be 60m and 45m
respectively while the vertical throw shall be 30m and 20 to 25m respectively.
5.0 WORKMANSHIP AND FINISH
5.1 All the parts shall have good workmanship and finish. All burrs and sharp
edges shall be removed particularly water way foam way and nozzle shall
have smooth finish.
6.0 ANTICORROSIVE TREATMENT AND PAINTING
6.1 All steel components subject to direct water or foam contact shall be hot
dipped galvanized to a minimum thickness of 0.12mm. The thickness of
coating shall be measured as per IS:3203. External surfaces and non ferrous
components may wetted with lead tin alloy by electrical deposition process.
6.2 Monitors steel part shall be painted with fire red colour confirming to IS: 5
shade no. 536 and the paint shall confirm to IS:2932 and copper alloy part
shall be polished.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
WATER MONITOR
MEC/ TS/ 05/ 21/ 081C/ A
MECON LIMITED
TS-WM-3
7.0 TEST
7.1 Monitor shall be tested to fulfill requirements at clause 4.0.
7.2 The entire assembly shall be hydraulically tested to a pressure of 2.1 MN/M2
(21 Kgf/Cm2) for 5 minutes without any leakage.
8.0 MARKING
8.1 Each monitor shall be clearly and permanently marked with the following:
a) Manufacturers name or trade mark
b) Year of manufacture
c) Purchasers name
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE CABINET
MEC/ TS/ 05/ 21/ 081O
MECON LIMITED
STANDARD SPECIFICATION
FOR
HOSE CABINET
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE CABINET
MEC/ TS/ 05/ 21/ 081O
MECON LIMITED
TS-PE-CO2-6.8- 1
CONTENTS
1.0 SCOPE
2.0 DESCRIPTIONS
3.0 MATERIAL OF CONSTRUCTION
4.0 PAINTING AND MARKING
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE CABINET
MEC/ TS/ 05/ 21/ 081O
MECON LIMITED
TS-PE-CO2-6.8- 2
1.0 SCOPE
This standard lays down overall requirements regarding construction, material,
design, shape and fixing arrangements of fire hose cabinet to be installed near fire
hydrants and to be used for keeping fire fighting accessories.
2.0 DESCRIPTION OF CABINET
2.1 Depending upon place of installation to suit the requirement, hose cabinets shall be
of two sizes and types for accommodating delivery hose, jet nozzle with branch pipe,
or universal branch pipe, fireman axe (if required). The two types of hose cabinets
have been defined as Type-A and Type-B.
2.2 Type-A hose cabinets are suitable for wall mounting installations. They shall be able
to accommodate, one 63mm delivery hose having length 15m with end male /
female coupling, one jet nozzle with branch pipe or alternately one universal branch
pipe.
2.3 Type-A cabinet shall have single panel glass door. Necessary hangers and brackets
for proper keeping / positioning of delivery hose, nozzles and branch pipe or
universal branch pipe inside shall be provided with the cabinet.
2.4 Type-B hose cabinet shall be of self-supporting type and shall be suitable for
outside installation. They shall be capable to accommodate two 63mm delivery
hoses of 15m length with end couplings, two jet nozzles with branch pipe or two
universal branch pipes.
2.5 Type-B hose cabinet shall have double panel glass door. Necessary hangers and
brackets for proper keeping / positioning of delivery hose, nozzles and branch pipe
or universal branch pipe inside shall be provided with the cabinet.
2.6 Both types of hose cabinets shall be provided with handle type lock, a small recess
to keep cabinet key under glass cover, a small hammer secured to the cabinet with a
chain to break open the key glass cover.
3.0 MATERIAL OF CONSTRUCTION
3.1 The hose cabinet shall be made of 16 gauge M.S. sheet suitably welded with single /
double MS door frame glass covered, depending upon the type of hose cabinet.
Glass shall be fitted to the door with gasket and rubber bidding so that it fits
securely.
3.2 Door of the hose cabinet shall be provided with standard handle type lock Godrej,
Mortise or equivalent with prior approval of owner / MECON.
3.3 Hammer shall be made of M.S. whereas Chain for securing purpose of hammer shall
be made of G.I.
3.4 Angle iron or M.S. round pipe of suitable size as per instruction of owner / MECON
shall be provided for supporting Type-B cabinet.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE CABINET
MEC/ TS/ 05/ 21/ 081O
MECON LIMITED
TS-PE-CO2-6.8- 3
3.5 Universal branch pipe shall confirm to IS: 2171. End coupling jet nozzle and branch
pipe shall confirm to IS:903.
4.0 MARKING AND PAINTING
4.1 Each hose cabinet shall be painted with 3 coats of anti-corrosive paint of fire red
colour from outside and white paint from inside. Each cabinet shall be clearly and
permanently marked as following:
i. The word in bold letters marked as FIRE HOSE CABINET
ii. Method of operation regarding opening and operation of equipments
placed inside.
iii. List of equipments placed inside the fire cabinet.
iv. Year of manufacture.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
NON-PERCOLATING FLEXIBLE FIRE
FIGHTING DELIVERY HOSE WITH
COUPLING
MEC/ TS/ 05/ 21/ 081C/ B
MECON LIMITED
SPECIFICATION
FOR
NON-PERCOLATING FLEXIBLE
FIRE-FIGHTING DELIVERY HOSE
WITH COUPLING
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
NON-PERCOLATING FLEXIBLE FIRE
FIGHTING DELIVERY HOSE WITH
COUPLING
MEC/ TS/ 05/ 21/ 081C/ B
MECON LIMITED
TS-HOSE-1
1.0 Scope :
This specification covers the general requirement regarding the material, design and
construction, performance and test for non-percolating flexible fire fighting delivery
hose with gunmetal male & female type instantaneous coupling.
2.0 Material:
2.1 The material for Delivery hose shall be rubberised fabric lined as per IS: 636 TYPE A.
2.2 The material for Male and Female instantaneous type coupling shall be of Gunmetal as
per IS: 903.
3.0 Design and Construction:
3.1. The hose shall be constructed from a circular woven jacket having a waterproof
rubberised fabric lining on the inside, facing the waterway.The jacket shall be seamless
and compactly woven from good quality cotton yarn or from yarn made from suitable
synthetic fibre of polyamide or polyester type of good quality or from their
combinations.
3.2. Fire hose with outer coating/covering shall be manufactured using synthetic yarn only.
3.3. The Fire hose shall be of 15m length and of 63mm.
3.4. If cotton yarn is used in the construction of jacket, this shall be rootproofed as per IS:
636 and method as per IS: 11662.
3.5. The average mass of hose per metre length shall not exceed 0.425kg.
3.6. The delivery hose couplings shall be of 63mm and consist of male half and female
half coupling assembled with washer as per IS: 903.
4.0 Performance Requirements
4.1 The delivery hose pipe shall be tested for kink, hydrostatic burst pressure, change in
length and diameter, adhesion, abrasion resistance, moisture absorption and heat
resistance as per methods and parameters mentioned in IS: 636.
4.2 The couplings shall be subjected to a hydraulic pressure of 2.1MN/mm
2
for a period of
2.5 minutes for the purpose of locating porosity in the casting and other defects.The
couplings shall not show any sign of leakage or sweating.
5.0 Workmanship and Finish
5.1 The jacket shall be practically free from dirt, knots, lumps, irregularities of the yarn and
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
NON-PERCOLATING FLEXIBLE FIRE
FIGHTING DELIVERY HOSE WITH
COUPLING
MEC/ TS/ 05/ 21/ 081C/ B
MECON LIMITED
TS-HOSE-2
other visible defects.
5.2 Inner lining shall be of rubberised fabric and shall be generally smooth and practically
free from pitting and other imperfections.
5.3 All fittings shall be of good workmanship, finish, clear of burrs and sharp edges. All
forgings and castings shall be clean and sound and shall be free from porosity,
blowholes, scales, cracks and other imperfections and shall not be repaired or filled so
as to hide casting defects.The water way of the fillings shall have a smooth finish.
6.0 Packing and Marking
6.1 Packing
The hoses may be dusted with French Chalk as per IS: 380 on the inside and shall be
packed and delivered in a length of 15M in neat, clean and dry condition in
Polyethylene bags.
6.2 Marking
A) Fire Hose
Beginning at a point not less than one metre from each end, each length of
hose shall be marked with clear and indelible letters at least 20mm in height
indicating :
a) Manufacturers name or trade-mark or both
b) Type, length and size of Hose
c) Month and year of manufacture
d) The Fire Hose shall also be marked with the BIS certification mark.
B) Delivery Couplings
The male and female instantaneous couplings shall be separately, clearly and
permanently marked with following information:
a) Manufacturers name and trade-mark
b) Size of couplings
c) Year of manufacture
d) The Couplings shall also be marked with the BIS certification mark.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
MEC/ TS/ 05/ 21/ 081D/ A
MECON LIMITED
STANDARD
SPECIFICATION
FOR
PORTABLE EXTINGUISHERS
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
MEC/ TS/ 05/ 21/ 081D/ A
MECON LIMITED
TS PEDCP - 1
DRY CHEMICAL POWDER EXTINGUISHER Technical Specification
1.0 SCOPE
This standard lays down requirements regarding construction, material, shape,
anticorrosive treatment and test for ordinary dry powder type fire extinguisher.
2.0 MATERIAL, SHAPE TYPES, CONSTRUCTION, ANTICORROSIVE
TREATMENT, PAINTING AND TESTS.
The construction, material, shape, anticorrosive treatment, painting, and test
shall comply with IS: 2171 (latest edition).
Extinguisher body shall be made out of M.S. sheet of not less than 1.6mm
thickness as per IS: 513. All the fire extinguishers shall be of welded
construction fitted with leaded tin bronze (Gunmetal) cap as per IS: 318, high
pressure discharge hose and squeeze grip nozzle. Plastic or PVC fittings will not
be provided with initial fittings.
Dry chemical powder supplied with extinguisher shall be non-toxic as per IS:
4308 and ISI marked. The extinguisher shall have gas cartridge of pressure
type. CO
2
gas cartridge shall be ISI marked and shall not be less than a
capacity of 120gms as per IS: 4947.
The extinguisher shall have cap having vent holes, gas cartridge holder, plunger
rod & piercing mechanism cap joint washers siphon tubes, braided hose of
sufficient length and discharge nozzle.
All the extinguishers shall be treated with lead - tin alloy for anti-rust,
anti-corrosive treatment by electrolytic deposition process. Extinguishers coated
by dip coating process will not be acceptable.
3.0 PRINCIPLE
The method of expulsion of dry powder shall be as per IS: 2171 (latest
edition) with either of the method of operation specified therein. Vendor shall
indicate clearly the method adopted for operation.
4.0 CAPACITY
Nominal capacity of the extinguisher and the dry powder contents of the
assembled body or dry powder container shall be as follows when charged
with dry powder conforming to IS: 4308 (latest edition.)
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
MEC/ TS/ 05/ 21/ 081D/ A
MECON LIMITED
TS PEDCP - 2
NOM. CAPACITY OF DRY POWDER CONTENTS
EXTINGUISHER ( KG) WHEN CHARGED MIN (KG)
1 1
2 2
5 5
10 10
Only dry powder confirming to IS: 4308 (latest edition) shall be used for
charging the extinguisher.
5.0 ACCESSORIES
Each extinguisher shall be supplied with a suitable wall bracket or holder into
which it may be mounted and from which it may be removed for use in an
emergency and screws and spanner as may be necessary. Extinguishers shall
be supplied with all accessories, initial charge etc.
6.0 MARKING
Each extinguisher shall be clearly and permanently marked with the information
specified in IS: 2171 along with BIS certification mark and purchasers name.
Each extinguisher shall be painted fire red and clearly marked with following:
i. Manufacturer's name and trade mark.
ii. Method of operation.
iii. A large size picture showing a man operating the extinguisher in
the correct manner.
iv. The word "DCP Type (Capacity)".
v. The size of gas cartridge used.
vi. Liquid level to which the extinguisher is to be checked.
vii. The word "Tested to a hydraulic pressure 2.5 MN/m2".
viii. The word "Keep this end up".
ix. Year of manufacture.
7.0 INSPECTION
Third party inspection agency at Contractors cost shall have access at all
reasonable times to the Manufacturers work where extinguishers are being
manufactured and / or tested. Samples from lots under a quality control
system shall be done as per Appendix B of IS: 2171. The cylinder shall be
hydraulically tested for 30kg/cm
2
of pressure.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
CARBON DI OXIDE TYPE (6.8 KG)
MEC/ TS/ 05/ 21/ 081D/ B
MECON LIMITED
STANDARD SPECIFICATION
FOR
PORTABLE FIRE
EXTINGUISHERS
CARBON DI OXIDE TYPE (6.8KG)
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
CARBON DI OXIDE TYPE (6.8 KG)
MEC/ TS/ 05/ 21/ 081D/ B
MECON LIMITED
TS-PE-CO2-6.8- 1
CO
2
PORTABLE EXTINGUISHER TECHNICAL SPECIFICATION
1.0 SCOPE
This standard lays down requirements regarding construction, material, shape, and
method of operation, performance and test of portable fire extinguisher of carbon
dioxide type.
2.0 MATERIAL, SHAPE, CONSTRUCTION, METHOD OF OPERATION,
PERFORMANCE, CONTENTS AND TESTS
2.1 The construction, material, shapes, method of operation, performance, and test shall
comply with IS: 2878 (latest edition) with ISI mark and approved by C.C.E. Nagpur.
2.2 Nominal size.
2.2.1 The extinguisher shall be following nominal sizes in kg: 1,2,3,4,5 and 6. The sizes
being denoted as per clause 4.11 of IS: 2878.
2.4 Carbon Di-oxide gas used shall conform to IS: 307 and extinguisher shall be filled as
per IS 2878 CI. 6.0.
2.5 The cylinder shall be made of cold drawn seamless steel cylinders as per IS: 7285
and fitted with screw down type high pressure control valve as per IS: 3224 with a
provision of safety release. Riveted joints will not be acceptable.
2.6 The extinguishers shall be fitted with discharge tube with swivel joint of atleast 1m
length with elect. non-conductor discharge horn.
3.0 APPROVALS
3.0 Approval/clearance certificate of filling the extinguisher from chief controller
explosive govt. of India, Nagpur shall be submitted for each cylinder. Testing of the
extinguisher, painting, markings etc. shall be as per IS: 2878 with ISI marked
4.0 MARKING
4.1 Each extinguisher shall be clearly and permanently marked as per IS: 2878 along
with BIS certification mark and following:
i. Manufacturer's name and trade mark.
ii. Method of operation.
iii. A large size picture showing a man operating the extinguisher in the correct
manner.
iv. The word " CO
2
Type (Capacity)".
v. The size of gas cartridge used.
vi. Liquid level to which the extinguisher is to be checked.
vii. Year of manufacture.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
PORTABLE EXTINGUISHERS
CARBON DI OXIDE TYPE (6.8 KG)
MEC/ TS/ 05/ 21/ 081D/ B
MECON LIMITED
TS-PE-CO2-6.8- 2
5.0 ACCESSORIES
Each extinguisher shall be supplied with M.S. bracket and spanner as may be
necessary. The details of the same shall be submitted. The extinguisher shall be
complete with wall mounting brackets and screws.
5.0 INSPECTION
6.1 Third party inspection agency at Contractors cost shall have access at all reasonable
times to the manufacturers work where extinguishers are being manufactured and /
or tested.
MECON LIMITED
Delhi
TECHNI CAL SPECI FI CATION FOR
FIRE BUCKETS
MEC/ TS/ 05/ 21/ 081D/ D
MECON LIMITED
STANDARD SPECIFICATION
FOR
FIRE BUCKETS
MECON LIMITED
Delhi
TECHNI CAL SPECI FI CATION FOR
FIRE BUCKETS
MEC/ TS/ 05/ 21/ 081D/ D
MECON LIMITED
TS BKT - 1
1.0 Scope
The specification covers the general requirement regarding the material,
shape, design, dimensions, manufacture, finish and tests of galvanised mild
steel fire bucket.
2.0 Material
2.1 Buckets shall be of mild steel black sheets confirming to grade ST42 of
IS:1079.
2.2 Rod used for top & bottom handles shall be of mild steel confirming to IS:
226.
2.3 Wires used for stiffening of top rim shall be of mild steel, confirming to IS:
280.
2.4 Painting of fire bucket shall be as follows :
a) Inside - Two coats of white paints (enamel
finish), as per IS: 2932.
b) Outside - Two coats of fire red paints,
confirming to Shade No. 536 of IS:
5 (enamel finish), as per IS: 2932.
c) Ears, Handles & Letters - Two coats of black paints, as per
IS: 2932.
3.0 Shape, Dimensions and Construction
3.1 The shape and dimensions of the fire bucket shall be as per IS: 2546.
3.2 The body of fire bucket shall be in two halves and to be joined together by
butt welding. Top rim of the body shall be wired and uniformly beaded
without gaps. Thickness of body shall be 1.0 mm & dia of beading wire 3.55
mm.
3.3 Bottom sheet of fire bucket shall be 1.0 mm thick and dished. It shall be
joined to the body by butt welding to avoid raw edge on the inside of the
bucket.
MECON LIMITED
Delhi
TECHNI CAL SPECI FI CATION FOR
FIRE BUCKETS
MEC/ TS/ 05/ 21/ 081D/ D
MECON LIMITED
TS BKT - 2
3.4 Thickness of mild steel sheet for ears shall be 2.8 mm and shall be fitted to
the body at the top by welding with the flat head on the side.
3.5 Top & bottom handle shall be of mild steel rod of 10.0 mm dia. The grip
shall have no sharp edges.
4.0 Performance Test
4.1 The bucket shall be fully filled with water and kept for 15 minutes, there
shall not be any leakage for the period.
4.2 The dry empty bucket with its top facing upward shall be pressed down the
water in a water tank of suitable size vertically. In such a way that top of
the bucket shall be minimum 6.0 mm above the water level. Water shall not
enter inside the bucket.
4.3 After taking out the bucket, the bucket shall be reversed and pressed inside
the water tank vertically. There shall not be any air bubble seen escaping
through the water.
5.0 Workmanship and Finish
5.1 All parts shall be of good finish, clear of burrs.
5.2 All gas welds shall clean and sound and shall be free from porosity, blow-
holes, scales and brittleness.
5.3 The bucket shall be galvanised after manufacturing with thickness of zinc
coating on any portion not less than 0.06 gm./cm2 (both sides inclusive), as
per IS: 2629.
6.0 Marking
Each fire bucket shall be clearly and permanently marked with the following
information:
a) Manufacturers name or trade-mark,
b) Year of manufacture & capacity,
c) Word "FIRE" shall be painted in black centrally on outside with letters
75 mm high & 12 mm thick.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
FIREMAN AXE
MEC/ TS/ 05/ 21/ 081C/ C
MECON LIMITED
STANDARD
SPECIFICATION
FOR
FIREMAN'S AXE
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
FIREMAN AXE
MEC/ TS/ 05/ 21/ 081C/ C
MECON LIMITED
TS AXE - 1
1.0 Scope
The specification covers the general requirement regarding the material, shape,
dimensions and construction of fireman's axe.
2.0 Material
2.1 Axe head shall be of steel made by forging. The chemical composition and
requirements of steel shall be as per IS: 926.
2.2 Axe handle shall be of steel confirming to IS: 1977.
2.3 The axe handle shall be insulated. The insulated handle shall be of vulcanised
rubber.
3.0 Shape, Dimensions and Construction:
1. The shape and dimensions of the axe shall be as per IS:926.
2. The axe head shall be soundly forged to shape and the steel handle
shall be welded to the head.
3. The pick and the blade shall be well and evenly hardened and tempered.
4. The handle grip shall be of knurled surface to make it non-slippery.
4.0 Performance Test
4.1 The cutting edge of the axe shall not show any sign of damage when tested for
single heavy blow as per the procedure mentioned in IS:926.
4.2 The cutting edge of the axe shall receive no damage when tested for load and
buckling as per IS:926.
4.3 The insulated handle shall be capable of withstanding 20,000 volts for 60
seconds.
5.0 Workmanship and Finish
5.1 All parts shall be of good finish, clear of burrs.
5.2 All forgings shall clean and sound and shall be free from porosity, blow-holes,
scales and cracks.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
FIREMAN AXE
MEC/ TS/ 05/ 21/ 081C/ C
MECON LIMITED
TS AXE - 2
6.0 Marking
1. Each axe shall be clearly and permanently marked with the following
information:
a) Manufacturers name or trade-mark,
b) Year of manufacture,
c) Tested to 20,000 volts and
d) ISI certification mark.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 1 of 11
STANDARD
SPECIFICATION
FOR
GAS FLOODING SYSTEM
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 2 of 11
1.0 SCOPE OF SUPPLY OF EQUIPMENT AND SERVICES
1.1 GENERAL
Fire in strategically important places like computer rooms, control rooms, switch gear
rooms, data storage rooms, server rooms, museum, data storage archives, libraries,
laboratories etc. is a serious hazard to highly precious and irretrievable items and
properties. Occurrence of fire besides leading to personnel injuries and property
damage also leads to loss of productivity and precious time. The primary cause of fire
may be due to short circuit / overheating of certain components somewhere in the
areas. Since most of the areas are unmanned and completely closed, fire inside is not
visible and accessible from outside till it becomes too big, dangerous and
unmanageable.
Fire suppression with conventional water-based systems such as hydrant or sprinkler
system can damage the assets permanently. Therefore for these costly & critical areas,
the Fire Protection System envisaged calls for early detection of fire and quenching the
same by flooding the area with gas based fire suppression system besides giving out
an audio visual alarm. The system considers and addresses possible Fire Hazards
within the protected volume at the incipient stage and provide for highest degree of
protection and minimum extinguishing time..
1.2 SCOPE
1.2.1 This specification for clean agent (environment friendly) based fire suppression system
covers design, supply, fabrication, erection, testing and commissioning complete with
all mechanical and electrical items as elaborated in the specification. The system shall
consist of the following as mechanical / electrical / instrumentation / hardware /
software part of the system.
Gas agent
Agent storage container with cylinder valve, pressure gauge
Discharge Nozzle(s)
Solenoid valve(s) and Pneumatic Actuator(s)
Manual Release Valve / Manual Actuator(s) for discharging of gas in case
automatic actuation fails
Check valves
Mounting brackets
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 3 of 11
Discharge hoses
Audio-visual Alarm Unit for indicating incidence of fire
Manifolds and piping with fittings
Inter-connecting Actuation hoses
Electrical Cables from alarm initiating devices to the panels with required
conduits as per the direction of purchaser / consultant.
Gas Release Panel
Detectors
Any other item(s) required for the completeness of the system
1.2.2 The system shall have an interfacing with Main Fire Alarm & Control Panel of the plant.
In case of fire in the concerned panel, indication & alarm should come in Main Fire
Alarm & Control Panel.
2.0 REQUIREMENTS FROM BIDDERS AND SPECIFIC TECHNICAL
REQUIREMENTS
2.1 The bidder shall be either Original Equipment Manufacturer (OEM) or any one of the
approved International / National Distributor authorised and certified by the parent
company for manufacture and / or marketing of their Fire Protection Systems.
2.2 The distributor shall have an established relationship with the OEM and they should
hold the distributorship prior to submission of bid.
2.3 The bidder should have received technical training on design, installation and
commissioning of the systems from the principal and training certificate to this account
from the principals should be submitted.
2.4 The OEM / Bidder shall give a certificate stating that their system as a whole along
with equipments, components, flow calculation software etc. is approved by UL / FM /
ULC / LPCB.
2.5 The gas being used for the system shall have a Chief Controller of Explosives, Nagpur
Certified filling station in India. The filling station should also be UL approved. The
filling station should have Gas Chromatography facility to test the purity and chemical
properties of the gas, if required.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 4 of 11
2.6 The system flow calculation shall be carried out on certified software, suitable for the
Seamless Steel Cylinder being offered for the project. Such system flow calculations
shall also be approved by UL / FM / LPCB / ULC. The system flow calculation software
developed The system flow calculation software developed for Welded Cylinder
parameters, and subsequently modified to suit the Seamless Cylinder parameters, shall
not be admissible unless the modifications too, are tested, certified and listed by UL /
FM / LPCB/ULC.
2.7 The system shall UL/FM/LPCB/ULC certified technology that allows for a higher
capacity to overcome frictional losses and allow for higher distances of the agent flow
and also allow for better agent penetration in enclosed electronic equipments such as
Server Racks/ Electrical Panels etc.
2.8 All system components shall be new and of current manufacture. These shall be
installed in accordance with local codes. Systems containing components that have a
dated life span and need periodical replacement shall not be acceptable.
2.9 The bidder shall provide all documentation such as Cylinder Manufacturing Certificates,
Test and Inspection Certificates and Fill Density Certificates.
2.10 The tender drawings and Schedule of Quantities enclosed are for basic guidance of the
bidder. It shall be the responsibility of the individual bidder to ensure the completeness
of the gas flooding system as per area and volume of the protected risk.
2.11 The Contractor shall specifically prepare all the shop drawings. These drawings shall
show the quantity, location, and marking of all system components included. The
drawings shall also describe and indicate the routing of all piping, wiring for detectors
and conduit layouts.
2.12 System electrical schematics and diagrams shall be provided, including a description of
all interlock functions.
3.0 DESCRIPTION OF THE SYSTEM
3.1 Gas based flooding system (Clean Agent System) mainly consists of pressurized Gas
cylinder filled with clean gas (FM200 / NAF / HFC227/ Inert Gas / Halon replacement
system etc.) and automatic detection (through smoke and heat detectors) and release
of extinguishing media / suppression agent. The suppression system shall provide for
high-speed release of Gas on the concept of total Flooding of the enclosed areas. A
Uniform extinguishing concentration shall be maintained inside the protected area all
over as applicable and approved by the manufacturer/NFPA 2001/UL/LPCB/ULC.
3.2 The temperature of gases considered for extinguishing shall be 70 deg F, or higher as
recommended by the system / agent manufacturer.
Extinguishing Agent Design Concentration
v/v%
Design Concentration
Kg/m3
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 5 of 11
FM 200 / HFC 125, 227 - NAF
S125/ Inert Gas / Halon
replacement (Environment
Friendly)
8 or as per UL
approval
0.441 Or as per UL.
3.3 The system discharge time shall be 10 seconds or less, in accordance with NFPA
standard 2001. Sub floor and the ceiling void to be included in the protected volume.
Care should be taken to locate all agent storage containers as close to the protected
area as possible to ensure complete liquid discharge of the suppression agent within
10 seconds.
3.4 The Fire Suppression System shall include a detection and control system provision for
both pre-alarm and automatic agent release. The detection and control system that
shall be used to trigger the Fire suppression shall employ cross zoning of Laser and
Multi-criteria smoke detectors. A single detector in one zone activated, shall cause in
alarm signal to be generated. Another detector in the second zone activated, shall
generate a pre-discharge signal and start the pre-discharge condition.
3.5 The discharge nozzles shall be located in the protected volume in compliance to the
limitation with regard to the spacing, floor and ceiling covering etc. The nozzle
locations shall be such that the uniform design concentration will be established in all
parts of the protected volumes. Aluminum / Brass Discharge nozzles shall be used to
disperse the clean gas agent. The nozzles shall be brass / Aluminum with female
threads and available in sizes as advised by the OEM system manufacturer. Each size
shall come in two styles: 180 and 360 dispersion patterns. The nozzles provided shall
be UL listed /LPC/ULC/Vds approved. The final number of the discharge nozzles shall
be according to the OEMs patented and certified software, which shall also be UL / FM
/ LPCB / ULC approved.
3.6 In the event of fire, the signal through detectors reaches Gas Release Panel. The Gas
discharge shall be activated by an output directly from the Gas Release Control Panel,
which will activate the solenoid valve and the gas stored in the cylinder will get
released through the discharge nozzles located in the protected volume. The Gas agent
is stored in the container as a liquid. The drop of pressure in the cylinder followed by
reduction in the weight of the gas cylinder due to discharge of gas will activate an
audio-visual alarm unit which will be interfaced / connected with the main fire control
system.
3.7 The required gas quantity and size of the cylinder is selected based on the volume
(Cu.M.) of the protected area. The gas should be environment friendly and should not
leave any residue, has less refilling cost, local availability and no damage to protected
equipment after fire suppression.
4.0 EQUIPMENT DETAILS
The main features of the system are:-
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 6 of 11
Automatic Detection of Fire
Automatic Flooding of Carbon Dioxide
Activation of Audio Visual Alarm Unit
Manual Release Valve option
Indication & Alarm in main fire alarm & control panel
4.1 STORAGE CYLINDER ASSEMBLY
4.1.1 A self-activating pressure valve and a cyfen tube inside the cylinder shall be fitted to
the cylinder through which the piping shall be connected. The valve shall contain a
pressure regulator, to retain gas pressure in the cylinder.
4.1.2 In the event of detection by Smoke / Heat Detectors, the Control Panel will energise
solenoid valve (electric operated) or pneumatically operated device which releases
the agent through the pneumatic operated pressure valve.
4.1.3 The storage cylinders offered shall be Seamless type (UL listed), meant for exclusive
use in the above gas systems, with FM/UL/LPCB/ULC component approval. Welded
cylinders are not permitted.
4.1.4 The storage cylinders shall be made of Manganese steel DS658 using hot spinning
process and heat-treated at 860`Centigrade for 30 minutes. These cylinders should
have satisfactorily undergone air leakage test, bend test etc.
4.1.5 The cylinders should have concave bottom and neck threading to IS:3224-1979 14TPI
Type-4.
4.1.6 The design drawings etc. including the cylinders shall be approved by CCOE, Nagpur.
4.1.7 The cylinders shall confirm to IS:7285 specifications, inspected and certified by BIS for
permission for filling the gas.
4.1.8 The cylinders shall be individually numbered and subject to hydrostatic stretch test at a
pressure of 250 Kg/Cm2 as required under rules 39 to 42 of the Gas Cylinder Rules
1981.
4.1.9 Gas storage cylinders shall be provided with a safety rupture disc. An increase in
internal pressure due to high temperature shall rupture the safety disc and allow the
content to vent before the rupture pressure of the container is reached. The contents
shall not be vented through the discharge piping and nozzles.
4.1.10 Gas containers shall be equipped with a pressure gauge to display internal pressure.
The gauge shall be an integral part of the container and shall be color-coded for fast
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 7 of 11
referencing of pressure reading.
4.2 MULTI-CRITERIA DETECTOR
4.2.1 The Multi-criteria detector shall have multi sensor, which combines optical, and heat
detection along with microprocessor controls with analogue communications. The
detectors shall have 2 auto learn sensitivity settings, 3 fixed photo thermal settings and
thermal only detection mode, Twin LED for 360deg visibility.
4.2.2 The technical parameters for smoke and heat detector should be as follows:
Supply Voltage : 9 to 33V
Average Quiescent Current at 24V : 45A
Average Quiescent Current at 9V : 21A
Alarm Current at 24V : 52A
Alarm Current at 9V : 17A
Alarm Indication : red LED
Normal Operating Temperature : -20 to +60C
Max wind continuous : 10 m/s
4.3 MANUAL RELEASE VALVE
4.3.1 The Manual Release Valve is intended for activation of the Gas system manually. The
releasing of Gas Cylinder(s) shall also be possible through direct mechanical
actuation, providing a means of discharge in the event of total electrical malfunction.
It shall consist of a Ball valve actuator mechanism. The valve shall be operated by
pulling out the locking pin and turning the knob to the "ON position to actuate the
system instantaneously.
4.3.2 The manual release device fitted on the Gas Cylinder(s) shall be of a manual lever
type and a faceplate with clear instruction of how to mechanically activate the
system. In all cases, gas cylinders shall be fitted with a manual mechanical operating
facility that requires two-action actuation to prevent accidental actuation.
4.3.3 Manual Gas Discharge stations and Manual Abort Stations, in conformance to the
requirements put forth in NFPA 2001 shall be provided.
4.4 MASTER CONTROL UNIT / GAS RELEASE PANEL (GRP)
4.4.1 Master Control Unit / Gas Release Panel shall be Micro Controller based intelligent /
Addressable control panel with battery charger and stand-by batteries located in
control room. The PCBs controls, Displays, switches etc. shall be housed in this
prefabricated anodised aluminium structure. It should be capable of monitoring the
status of Solenoid valve and overall Gas flooding system in all the preset different
zones on continuous basis.
4.4.2 The Panel shall have 2 x 40 character LCD display and have a capacity of 198 devices
per loop .The panel should have LED indications for all zones, complete with internal
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 8 of 11
sounder and alarm/fault indications The panel shall be capable of enhanced features
such as inbuilt printer and auto dialer interface, by addition of extra cards/ field
modules on the motherboard.
4.4.3 The system shall operate on 230V-AC and shall have battery backup for atleast 6
hours. GRP shall communicate with all the audio-visual alarm units once in every 70
Msec to understand their status. If there is any fault / fire condition sensed by the
Smoke / Heat detector, the GRP will indicate zone area.
4.4.4 In case there is loss of gas in any Gas cylinder, the system shall give fault indication.
4.4.5 The GRP shall have LED indicators for power on, zone wise indication for fire, zone
wise indication for fault, bigger fire indication, test & isolate condition, Gas cylinder
status, power backup status, charger on, battery low conditions etc.
4.4.6 It should also have switches for lamp / alarm test, buzzer mute, and power on and fire
acknowledgement.
4.4.7 Release of Gas agent shall be accomplished by an electrical output from the Gas
Release Panel to the solenoid valve and shall be in accordance with the requirements
set forth in the current edition of the National Fire Protection Association Standard
2001.
4.5 AUDIO-VISUAL ALARM UNIT
4.5.1 The Audio-Visual Alarm Unit is located at the respective zones at convenient place near
the panels fitted with Gas flooding system. This unit shall also be micro controller
based and shall be housed in prefabricated anodised aluminium rack.
4.5.2 The unit shall monitor the status of all the Gas cylinders and the piping system
installed inside the rooms to be protected. In case of fire, there shall be loud audio-
visual alarm and the sound level shall be 100db.
4.5.3 The unit works on 24 V DC supply provided from the master control unit. It should
have LED indication for power on, fault, Gas cylinder status, power backup status and
also switches for lamp / alarm test, buzzer mute and fire acknowledgement. The AVA
Unit shall respond to the Master Control Unit / Gas Release Panel based on the
commands received.
4.6 POWER BACKUP WITH BATTERIES, CHARGER UNIT
4.6.1 The main control unit shall be provided with a power backup so that it is operational in
case of 230V-AC power supply failure. The power backup shall not be less than four
hours. Two nos. of 12 Volts maintenance free Batteries backup of Exide make
connected in series (24V) shall be provided to the system.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 9 of 11
4.6.2 Built in battery charging facility shall be provided using high quality charging ICs. The
system shall continuously maintain the status of the battery. If the battery level
becomes less than the predefined level of 20volt, the charging circuit will start charging
the battery. At that time, charger on indication shall be displayed on the MCU.
4.6.3 In case the battery voltage becomes less than 18 volt, it should give a battery low
indication and also charger on indication. When battery voltage reaches 27 volt, the
charger circuit shall display the fully charged indication. When the system works on
emergency battery backup, the battery backup working indication should glow.
4.7 HARDWARE ITEMS (Brackets, Manifolds, Hoses, piping with fittings, Fasteners)
4.7.1 Standard fittings of reputed manufacturers should be used for completing the job. All
the Major components of the Gas suppression system shall be supplied by one single
manufacturer under the same brand name to the extent possible.
.
4.8 ELECTRICAL CABLES
4.8.1 Electrical cables as per Indian Standard specification shall be used for inter connection
of the master control unit to audio visual alarm unit, from audio visual alarm unit to
various Gas / Clean agent cylinders. Cables shall be made up of 3 nos. twisted pair
copper wire of 1.5 sq.mm. Cables shall be routed through M.S. conduit pipes, which
shall be painted red.
4.9 WEIGHT MONITORING SYSTEM
4.9.1 The weight monitoring system shall be designed to monitor the weight of the Clean
agent gas filled in the cylinders. It shall have load cell of high quality and precision
with associated electronics and a cylindrical ring for holding the cylinder in place.
4.9.2 The load cell shall operate in the 5` Centigrade to 70` Centigrade range. The temp.
affect on the span should not be more than 0.006% and the effect on tare shall be
0.008%. The safe overload provision is 200% of the rated capacity of 100 Kgs. The
protection class code is IP-68. The system shall use beam type load cell.
4.9.3 In the event of reduction in the weight of the gas in the cylinder (either due to
leakage or release of gas) beyond the preset limit (1.5Kg in the preset condition),
the electronic circuitry provided in the unit shall activate the respective audio visual
alarm unit and annunciates the occurrence of fault or fire.
5.0 TESTING
5.1 The Fire panel and Detectors will be tested as per the testing procedure of
Intelligent Fire Alarm and Detection System.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 10 of 11
5.2 The alarm will be generated from the fire alarm panel and the gas release panel
should start the timer and the signal to valves.
5.3 The gas release panel will also be tested for its functioning of the manual override
and the manual discharge.
5.4 The valves will be removed from the cylinder and the actuation of valves will be
tested for its performance.
5.5 The bidder has to provide required quantity of colored nitrogen gas for testing the
release of gas in each area.
5.6 The bidder will provide testing with one cylinder of Gas for testing the complete
system & quenching the fire. After testing the bidder will refill and fix the cylinder in
the main system at no additional cost.
5.7 Acceptance for the System installation, inclusive of the piping and requisite cabling
shall be strictly in accordance with the installation acceptance guidelines as put forth in
the NFPA 2001. The bidder shall be required to carry out a simulation test [with the
Electrical Solenoid on the Gas bank (/ Cylinder) disenabled / disengaged so as to
prevent discharge of gas], and prove the functionality of the System.
6.0 REFILLING AND MAINTENANCE
In case of any leakage or accidental discharge of the agent, it should be possible to
refill the cylinders in a UL Listed Filling Station or an UL Approved Alternate
Manufacturing Location (AML) in India itself. The contractor should indicate the source
of refilling and time that will be taken for refilling and replacement.
7.0 WARRANTY
System shall be warranted for parts and labour for a period of one (1) year from the
date of commissioning of the system. The Contractor shall specify the maintenance to
be performed during the warranty period to maintain warranty conditions.
8.0 CODES & STANDARDS, DESIGN CRITERIA
STANDARDS
8.1 All materials, equipments, piping, valves, fittings etc. dimensional standards, tolerance,
prices of manufacture and testing procedure shall be in accordance with the latest
revision of relevant Indian, British, American standards wherever applicable.
8.2 The material used and equipment supplied shall be new and the best of their kind and
shall comply with the latest revisions of all relevant standards. The tenderer shall
indicate in his tender the relevant standards to which the equipment, piping, fittings,
etc. offered by him shall comply with. The latest revisions of applicable standards
indicated in the technical specification shall be used for the design, manufacture,
inspecting and testing of the items covered in this specification. The following codes
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR PANEL
FLOODING SYSTEM
MEC/ TS/ 05/ 21/ 081L
MECON LIMITED
Page 11 of 11
and standards shall be considered for design: -
a) UL: Underwriters Laboratory
b) FM: Factory Mutual
c) NFPA 2001 standard on Clean Agent Fire Extinguishing System;
d) SMPV Rules 1981, CCE Nagpur (for storage of cylinders)
e) Clean agent manufacturers recommendation
f) Relevant OISD Standards
g) National Building Code of India
h) TAC Guidelines
DESIGN CRITERIA
FOR GAS BASED FIRE SUPPRESSION SYSTEM
System Design for the Control Room of size: 12.5M x 20M X 3.15 Mtr. hight
S.No. Description Calculation
1. Overall Room Dimensions including all rooms to
be protected approx. (Mtrs)
12.5M x 20M X 3.15 Mtr.
hight
2. Total Volume (M3) 788
3. Design Concentration (% by Volume) 6-8 or as recommended
by Gas agency
4. Design Concentration (Kg./M3) 0.441 or as
recommended
5. Design Temperature 21 deg C
6. Basic Gas quantity required (Kg.) To be furnished by bidder
7. Adjusted Agent Gas quantity Required (Kg.) To be furnished by bidder
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE REEL
MEC/ TS/ 05/ 21/ 081P
MECON LIMITED
TECHNICAL SPECIFICATION
FOR
FIRST AID HOSE REEL
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE REEL
MEC/ TS/ 05/ 21/ 081P
MECON LIMITED
TS-LV- 1
CONTENTS
1.0 SCOPE
2.0 DESCRIPTION
3.0 CONSTRUCTION, MATERIAL AND TESTS
4.0 SIZE
5.0 OPERATING INSTRUCTIONS
6.0 MARKING
7.0 INSPECTION
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE REEL
MEC/ TS/ 05/ 21/ 081P
MECON LIMITED
TS-LV- 2
1.0 SCOPE :
The specification covers the requirements regarding constructional details, Material and
test for first aid hose reel intended for installation in buildings as Emergency fire
fighting component / equipment.
2.0 DESCRIPTION:
The hose reel shall comply to IS: 884 ( latest edition ).
3.0 CONSTRUCTION, MATERIAL AND TEST
3.1 The construction, material and test shall be as per IS: 884 ( latest edition ).
3.2 Washer shall be of leather conforming to IS: 581 ( latest edition ).
3.3 A suitable guide or hose runner as per IS: 884 Cl. 6.1.7 shall be provided.
3.4 When installing hose reel outside building dust cover as per IS: 884 Cl. 6.2 shall be
provided.
3.5 Fixing bracket shall be swinging type.
3.6 Stop valve shall be manually operated.
4.0 SIZE
It shall carry 20mm bore 40 m long hose.
5.0 OPERATING INSTRUCTIONS
A metal plate showing in clear legible letters, the instructions for operating the first
aid hose reel shall be fixed preferable near the bracket for nozzle.
6.0 MARKING
Each hose reel shall be clearly and permanently marked with the following
information along with Purchasers name.
a. Manufacturers name or trade mark.
b. Year of manufacture
c. Instruction for use
d. The letters Ref. IS: 884 and
e. Length and size of tube carried on hose reel.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
HOSE REEL
MEC/ TS/ 05/ 21/ 081P
MECON LIMITED
TS-LV- 3
7.0 INSPECTION
Third party inspection agency at Contractors cost shall have access at all reasonable
times to the manufacturers works where the first aid hose reel or its components
are being manufactured, assembled and / or tested.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TECHNICAL SPECIFICATION
FOR
STAND POST TYPE FIRE HYDRANT
FIRST AID HOSE REEL
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 1-
CONTENTS
STAND POST TYPE WITHOUT PUMPER CONNECTION
1.0 SCOPE
2.0 CODES AND STANDARDS
3.0 MATERIAL
4.0 DESCRIPTION
5.0 WORKMANSHIP AND FINISH
6.0 TESTING
7.0 PAINTING
8.0 MARKING
9.0 INSPECTION
STAND POST TYPE FIRE HYDRANT WITH PUMPER CONNECTION
1.0 SCOPE
2.0 CODES AND STANDARDS
3.0 MATERIAL
4.0 DESCRIPTION
5.0 WORKMANSHIP AND FINISH
6.0 TESTING
7.0 PAINTING
8.0 MARKING
9.0 INSPECTION
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 2-
STAND POST TYPE FIRE HYDRANT WITHOUT PUMPER CONNECTION
1.0 SCOPE :
This standard lays down the requirements of type, shape, materials, dimensions
and test for vertical stand post type fire hydrant to be installed on fire water main with
an isolation valve.
2.0 CODES AND STANDARDS :
The applicable codes and standards to be followed are as follows:
- TAC Manual
- IS: 5290 and IS: 903
- Other Government regulations / Codes
- All codes / standards mentioned elsewhere in this specification.
3.0 MATERIAL :
3.1 Hydrant vertical post and hydrant arms shall be from pipe conforming to IS: 1239
heavy grade and shall be with welded construction.
3.2 Flange shall be of M.S. plate to IS: 2062 F/F, slip-on type.
3.3 Hydrant valves 75 mm size shall comply to IS: 5290 type B.
3.4 63 mm coupling shall comply to IS: 903.
3.5 Bolts and nuts for flanges shall comply to IS: 1367 clause 10.9 and 12.0
respectively while gasket 2 mm thick full face shall be made of CAF 40 to IS:
2712.
4.0 DESCRIPTION :
4.1 The hydrant shall be of stand post type. The vertical post shall be of 100 mm diameter
with two horizontal hydrant arms each 80 mm diameter on which independent
hydrant valve shall be fixed. Hydrant valve shall comply to IS: 5290 type B.
4.2 63 mm coupling to hydrant valve shall comply to IS: 903 except that the lug shall be
twist release type.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 3-
4.3 All flanges for hydrant valve and base shall have drilling dimensions conforming to
ANSI B 16.5 # 150 lbs rating flat face, slip on type.
5.0 WORKMANSHIP AND FINISH :
5.1 All parts shall be of good workmanship and finish. All parts and sharp edges shall be
removed. The water ways shall have smooth finish.
5.2 Wherever IS has been specified the latest edition of the same shall be followed.
6.0 TESTING :
Hydrant assembly with hydrant valves closed shall be satisfactorily tested and
proved water tight under a hydraulic pressure of 18.0 kg / cm2.
7.0 PAINTING :
7.1 The stand post and its arms shall be painted with three coats of anti corrosive fire red
paint conforming to IS: 2932 from outside while internal surface shall be painted with
three coats of chlorinated rubber based resin paint or zinc chromate paint. The
paint shall conform to shade no. 536 of IS: 5 and IS: 2982.
7.2 All steel parts coming in direct contact with water shall be hot dipped galvanized to a
thickness of not be less than 0.12 mm. The thickness of the coating shall be measured
as per IS: 3203. External surfaces and non-ferrous components may be coated with
lead-tin alloy by electrical deposition process.
8.0 MARKING :
8.1 Each hydrant shall be clearly and permanently marked with the
a. Manufacturers name or trade mark.
b. Year of manufacture
c. Purchasers name
d. IS: 5290 on hydrant valve
8.2 The assembly shall also be marked with the required BIS marking.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 4-
9.0 INSPECTION :
Third party inspection agency at Contractors cost shall have access at all
reasonable times to the manufacturers work where hydrants are being
manufactured and / or tested.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 5-
STAND POST TYPE FIRE HYDRANT WITH PUMPER CONNECTION
1.0 SCOPE :
This standard lays down the requirements of type, shape, materials, dimensions
and test for vertical stand post type fire hydrant to be installed on fire water main with
an isolation valve.
2.0 CODES AND STANDARDS :
The applicable codes and standards to be followed are as follows:
- TAC Manual
- IS: 5290 and IS: 903
- Other Government regulations / Codes
- All codes / standards mentioned elsewhere in this specification.
3.0 MATERIAL :
3.1 Hydrant vertical post and hydrant arms shall be from pipe conforming to IS: 1239
heavy grade and shall be with welded construction.
3.2 Flange shall be of M.S. plate to I.S. 226 F/F, slip-on type.
3.3 Hydrant valves 75 mm size shall comply to IS: 5290 type B.
3.4 63 mm coupling shall comply to IS: 903.
3.5 63 mm coupling to hydrant valve shall comply to IS: 903 while blind cap with its lugs
shall be of gun metal complying to IS: 318 Gr. II. Chain shall be of mild steel.
3.6 Bolts and nuts for flanges shall comply to IS: 1367 clause 10.9 and 12.0
respectively while gasket 2 mm thick full face shall be made of CAF 40 to
IS:2712.
4.0 DESCRIPTION :
4.1 The hydrant shall be of stand post type. The vertical post shall be of 100 mm
diameter with two horizontal hydrant arms each 80 mm diameter on which
independent hydrant valve shall be fixed. Hydrant valve shall comply to IS: 5290 type
B.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 6-
4.2 63 mm coupling to hydrant valve shall comply to IS: 903 except that the lug shall be
twist release type.
4.3 The vertical post shall have 100 mm outlet as pumper connection and provided with a
blind cap. The 100 mm outlet shall have round male threads conforming to IS: 902
and blind up shall have round female matching threads. The cap shall be provided with
four fixing lugs and 500 mm long M.S. chain.
4.4 All flanges for hydrant valve and base shall have drilling dimensions conforming to
ANSI B 16.5 # 150 lbs rating flat face, slip-on type.
5.0 WORKMANSHIP AND FINISH :
5.1 All parts shall be of good workmanship and finish. All parts and sharp edges shall be
removed. The water ways shall have smooth finish.
5.2 Wherever IS has been specified the latest edition of the same shall be followed.
6.0 TESTING :
Hydrant assembly with hydrant valves and pumper connection closed shall be
satisfactorily tested and proved water tight under a hydraulic pressure of 18.0 kg/cm2.
7.0 PAINTING :
7.1 The stand post and its arms shall be painted with three coats of anti corrosive fire red
paint conforming to IS: 2932 from outside while internal surface shall be
painted with three coats of chlorinated rubber based resin paint or zinc chromate paint.
7.2 All steel parts coming in direct contact with water shall be hot dipped galvanized to a
thickness of not less than 0.12 mm. The thickness of the coating shall be measured as
per IS: 3203. External surfaces and non-ferrous components may be coated with lead-
tin alloy by electrical deposition process.
8.0 MARKING :
8.1 Each hydrant shall be clearly and permanently marked with the
a. Manufacturers name or trade mark.
MECON LIMITED
Delhi
TECHNICAL SPECIFICATION FOR
STANDPOST TYPE FIRE HYDRANT
MEC/ TS/ 05/ 21/ 081N
MECON LIMITED
TS-SPH- 7-
b. Year of manufacture
c. Purchasers name
d. IS: 5290 on hydrant valve
8.2 The assembly shall also be marked with the required BIS marking.
9.0 INSPECTION :
Third party inspection agency at Contractors cost shall have access at all
reasonable times to the manufacturers work where hydrants are being
manufactured and / or tested.