You are on page 1of 44

Atlas Copco Stationary Air Compressors

GA5-7-11C-11-15-18-22-30C-30-37-45-55C-55-75-90C and
GA30 W-37 W-45 W-55C W-55 W-75 W-90C W
With Elektronikon I or Elektronikon II regulator
User manual for Elektronikon

I and II regulators
Downloaded from www.Manualslib.com manuals search engine
Compressor type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit serial No. compressor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air dryer type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit serial No. dryer: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor serial No.: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Delivery date: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . First start-up date: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Plan: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Owner's machine No.: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selected lubricants
Compressor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capacity: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bearing grease type, electric motor: . . . . . . . . . . . . . . . . . . . . . . . . .
Dryer gearbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Printed Matter Nos.
Atlas Copco compressor instruction book: . . . . . . . . . . . . . . . . . . . . Atlas Copco air dryer instruction book: . . . . . . . . . . . . . . . . . . . . . . . . . .
Atlas Copco compressor parts list: . . . . . . . . . . . . . . . . . . . . . . . . . . Atlas Copco air dryer parts list: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Atlas Copco logbook: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Atlas Copco Representative
Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Telephone: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contact persons: Service: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Telex: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-mail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY PRECAUTIONS
To be read attentively and acted accordingly before installing, operating or repairing the unit.
These recommendations apply to machinery processing or consuming air or inert gas. Processing of any other gas requires
additional safety precautions typical to the application which are not included herein.
If necessary, install a suction duct. Never obstruct the air inlet. Care
shall be taken to minimize the entry of moisture with the inlet air.
4. The aspirated air shall be free from flammable fumes or vapours,
e.g. paint solvents, that can lead to internal fire or explosion.
5. Air-cooled units shall be installed in such a way that an adequate
flow of cooling air is available and that the exhausted air does not
recirculate to the inlet.
6. Arrange the air intake so that loose clothing of people cannot be
sucked in.
7. Ensure that the discharge pipe from the compressor to the aftercooler,
air dryer or air net is free to expand under heat and that it is not in
contact with or close to flammable material.
8. No external force may be exerted on the air outlet valve; the connected
pipe must be free of strain.
9. If remote control is installed, the unit shall bear an obvious sign
reading:
DANGER: This machine is remotely controlled and may start
without warning.
As a further safeguard, persons switching on remotely controlled
units shall take adequate precautions to ensure that there is no one
checking or working on the machine. To this end, a suitable notice
shall be affixed to the start equipment.
10. On units with automatic start-stop system, a sign stating "This
machine may start without warning" shall be attached near the
instrument panel.
11. In multiple compressor systems manual valves shall be installed to
isolate each compressor. Non-return valves (check valves) shall not
be relied upon for isolating pressure systems.
12. Never remove or tamper with the safety devices, guards or insulations
fitted on the unit. Every pressure vessel or auxiliary installed outside
the unit to contain air above atmospheric pressure shall be protected
by a pressure-relieving device or devices as required.
13. Pipework or other parts with a temperature in excess of 80 degrees
celsius and which may be accidentally touched by personnel in nor-
mal operation shall be guarded or insulated. Other high-temperature
pipework shall be clearly marked.
OWNERSHIP DATA
In addition to normal safety rules which should be observed with stationary
air compressors and equipment, the following safety directions and
precautions are of special importance.
When operating this unit, the operator must employ safe working practices
and observe all related local work safety requirements and ordinances.
The owner is responsible for maintaining the unit in a safe operating
condition. Parts and accessories shall be replaced if unsuitable for safe
operation.
Installation, operation, maintenance and repair shall only be performed
by authorized, trained, competent personnel.
Normal ratings (pressures, temperatures, time settings, etc.) shall be
durably marked.
Any modification on the compressor or air dryer shall only be performed
in agreement with Atlas Copco and under supervision of authorized,
competent personnel.
If any statement in this book, especially with regard to safety, does not
comply with local legislation, the stricter of the two shall apply.
These precautions are general and cover several machine types and
equipment; hence some statements may not apply to the unit(s) described
in this book.
Installation
Apart from general engineering practice in conformity with the local
safety regulations, the following directives are specially stressed:
1. A compressor or air dryer shall be lifted only with adequate equipment
in conformity with local safety rules.
Loose or pivoting parts shall be securely fastened before lifting. It is
strictly forbidden to dwell or stay in the risk zone under a lifted load.
Lifting acceleration and retardation shall be kept within safe limits.
Wear a safety helmet when working in the area of overhead or lifting
equipment.
2. Any blanking flanges, plugs, caps and desiccant bags shall be
removed before connecting up the pipes. Distribution pipes and
connections shall be of correct size and suitable for the working
pressure.
3. Place the unit where the ambient air is as cool and clean as possible.
2920 1377 03 1/2 (continued on inside of cover)
Downloaded from www.Manualslib.com manuals search engine
Atlas Copco Stationary Air Compressors
Important
This book applies exclusively to the above-mentioned compressors with
Elektronikon I or II regulator from following serial numbers onwards:
GA5 up to GA11C: AII-145 000
GA11 up to GA30C: AII-268 500
GA30 up to GA55C: AII-380 000
GA55 up to GA90C: AII-474 000
No. 2920 1461 03
Replaces 2920 1461 02
Registration code: APC G5-11C/2002 / 38 / 984
APC G11-30C / 38 / 989
APC G30-55C / 38 / 980
APC G55-90C / 38 / 985
2003-09
GA5-7-11C-11-15-18-22-30C-30-37-45-55C-55-75-90C and
GA30 W-37 W-45 W-55C W-55 W-75 W-90C W
With Elektronikon I or Elektronikon II regulator
User manual for Elektronikon

I and II regulators
Copyright 2003, Atlas Copco Airpower n.v., Antwerp, Belgium.
Any unauthorized use or copying of the contents or any part thereof is prohibited. This applies in
particular to trademarks, model denominations, part numbers and drawings.
This instruction book meets the requirements for instructions specified by the machinery
directive 98/37/EC and is valid for CE as well as non-CE labelled machines.
www.atlascopco.com
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 2
User manual
Page
7 Scrolling through all screens . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.1 Calling up outlet/dewpoint temperatures . . . . . . . . . . . . 9
7.2 Calling up running hours . . . . . . . . . . . . . . . . . . . . . . . . 9
7.3 Calling up loading hours . . . . . . . . . . . . . . . . . . . . . . . . 9
7.4 Calling up motor starts . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.5 Calling up/resetting service timer . . . . . . . . . . . . . . . . . 10
7.6 Automatic restart after voltage failure . . . . . . . . . . . . . 10
7.7 Set of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.8 Calling up/modifying unloading pressure . . . . . . . . . . 11
7.9 Calling up/modifying loading pressure . . . . . . . . . . . . 11
7.10 Calling up/modifying dewpoint warning temperature . 11
7.11 Calling up/modifying service timer setting . . . . . . . . . 12
7.12 Calling up/modifying unit for pressure . . . . . . . . . . . . 12
7.13 Calling up/modifying unit for temperature . . . . . . . . . 12
7.14 Selection between Y-D/DOL starting . . . . . . . . . . . . . . 12
7.15 Activating automatic restart after voltage failure. . . . . 13
7.16 Selecting local/remote control . . . . . . . . . . . . . . . . . . . 13
7.17 Modifying parameter set . . . . . . . . . . . . . . . . . . . . . . . . 13
8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.1 Unloading/loading pressures . . . . . . . . . . . . . . . . . . . . 14
8.2 Element outlet temperature . . . . . . . . . . . . . . . . . . . . . . 14
8.3 Dewpoint temperature. . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.4 Service timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Contents
PART 1 - ELEKTRONIKON I REGULATOR
Page
1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Automatic control of the compressor . . . . . . . . . . . . . . 3
1.2 Protecting the compressor . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Automatic restart after voltage failure . . . . . . . . . . . . . . 3
2 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.1 Pictographs used on the screen . . . . . . . . . . . . . . . . . . . 4
3.2 Main screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3 Scrolling through all screens . . . . . . . . . . . . . . . . . . . . . 5
4 Shut-down warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.1 Compressor element outlet temperature . . . . . . . . . . . . . 5
4.2 Dewpoint temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Shut-down
5.1 Compressor element outlet temperature . . . . . . . . . . . . . 6
5.2 Motor overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 Service warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PART 2 - ELEKTRONIKON II REGULATOR
Page
1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.1 Automatic control of the compressor . . . . . . . . . . . . . 15
1.2 Protecting the compressor . . . . . . . . . . . . . . . . . . . . . . 15
1.3 Automatic restart after voltage failure . . . . . . . . . . . . . 15
2 Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.1 LEDs/buttons/keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2 Pictographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3 Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3 Menu-driven control programs . . . . . . . . . . . . . . . . . . . . . 19
3.1 Function of control programs . . . . . . . . . . . . . . . . . . . . 19
3.2 Main screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 Calling up other menus . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 Quick look at actual compressor status . . . . . . . . . . . . . . . 20
5 Status data menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.1 No message exists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.2 A shut-down message exists . . . . . . . . . . . . . . . . . . . . . 20
5.3 A shut-down warning message exists . . . . . . . . . . . . . . 21
5.4 A service warning message exists . . . . . . . . . . . . . . . . 21
5.5 A warning message exists . . . . . . . . . . . . . . . . . . . . . . . 21
6 Measured data menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 Counters menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8 Test menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Page
9 Modify params menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10 Modifying parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.1 Modifying loading/unloading pressures . . . . . . . . . . . . 23
11 Modifying protection settings . . . . . . . . . . . . . . . . . . . . . . . 23
11.1 Modifying settings for compressor element . . . . . . . . . 24
12 Modifying service plans . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
13 Programming clock function. . . . . . . . . . . . . . . . . . . . . . . . 25
13.1 Programming start/stop/pressure band commands . . . 25
13.2 To activate/deactivate the timer . . . . . . . . . . . . . . . . . . 26
13.3 To modify a command . . . . . . . . . . . . . . . . . . . . . . . . . 26
13.4 To add a command . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
13.5 To delete commands . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
14 Configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
14.1 Programming compressor control modes . . . . . . . . . . . 28
15 Service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
16 Saved data menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
17 Programmable settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
17.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
17.2 Protections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
17.3 Service plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
3
User manual
PART 1
ELEKTRONIKON I REGULATOR
1.3 Automatic restart after voltage failure
For compressors leaving the factory, this function is made
inactive. If desired, the function can be activated. Consult
Atlas Copco.
Warning If activated and provided the module was in the
automatic operation mode, the compressor will
automatically restart if the supply voltage to the
module is restored.
2 Control panel
Ref. Designation Function
1 Stop button Push button to stop the
compressor. LED (10) goes out.
The compressor will stop after
running in unloaded condition for
about 30 seconds.
2 Start button Push button to start the
compressor. LED (10) lights up
indicating that the regulator is
operative (in automatic operation).
3 Display Indicates the compressor operating
condition, measured values and
programmed parameters.
1 General description
1.1 Automatic control of the compressor
The regulator maintains the net pressure between programmable
limits by automatically loading and unloading the compressor.
A number of programmable settings, e.g. the unloading and
loading pressures, the minimum stop time and the maximum
number of motor starts are taken into account.
The regulator stops the compressor whenever possible to reduce
the power consumption and restarts it automatically when the
net pressure decreases.
1.2 Protecting the compressor
Shut-down
If the compressor element outlet temperature exceeds the
programmed shut-down level, the compressor will be stopped.
This will be indicated on display (3). The compressor will
also be stopped in case of overload of drive motor (M1) and,
for air-cooled compressors, also the fan motor (M2).
Shut-down warning
If the compressor element outlet temperature or dewpoint
temperature (Full-Feature compressors) exceeds a programmed
value below the shut-down level, this will also be indicated to
warn the operator before the shut-down level is reached.
Service warning
If the service timer exceeds a programmed value, this will be
indicated on display (3) to warn the operator to carry out some
service actions.
Control panel
10 11 8 9 7 6
3 2 1 4
5
12
13
5
2
2
3
8
F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 4
User manual
Ref. Designation Function
4 Reset key Key to reset the service timer, a
shut-down condition, etc.
5 Enter key Key to select or validate a
parameter, to open a sub-display
or to return to a previous display.
6 Voltage on LED Indicates that the voltage is
switched on.
7 Pictograph Voltage on
8 General alarm LED Is alight if a warning condition
exists.
8 General alarm LED Blinks in case of a shut-down or
emergency stop condition.
9 Pictograph Alarm
10 Automatic Indicates that the regulator is
operation LED automatically controlling the
compressor: the compressor is
loaded, unloaded, stopped and
restarted depending on the air
consumption and the limitations
programmed in the regulator.
11 Pictograph Automatic operation
12 Downwards Key to scroll downwards through
scroll key the screens or to decrease a setting.
13 Upwards scroll key Key to scroll upwards through the
screens or to increase a setting.
S3 Emergency stop Push button to stop the compressor
button immediately in case of emergency.
After remedying the trouble,
unlock the button by pulling it out
and press reset key 4.
3 Display
The display shows:
- the compressor operating status by means of pictographs
- the air outlet pressure
- the actual temperature at the compressor element outlet
- the actual dewpoint temperature (FF compressors)
The display also shows all measured and programmed
parameters, see section 7.
3.1 Pictographs used on the screen
Pictograph Explanation
Compressor status UNLOAD
Running hours
Element outlet temperature
Dewpoint temperature
Motor or motor overload
3.2 Main screen
When the voltage is switched on, the Main screen is shown
automatically, showing in short the operation status of the
compressor and the outlet pressure:
bar
6.8
Main screen, typical example
The screen shows that the compressor is running loaded (the
horizontal arrow blinks) and that the outlet pressure is 6.8 bar(e).
Compressor status LOAD (during loaded running,
the horizontal arrow blinks)
10 11 8 9 7 6
3 2 1 4
5
12
13
52236F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
5
User manual
Important
Always consult Atlas Copco in case "t" or "test" appears on the
display
3.3 Scrolling through all screens
It is possible to scroll downwards and upwards through a
number of screens by means of the upwards/downwards arrow
keys (12 and 13). See section 7.
4 Shut-down warning
A shut-down warning message will appear in case of:
- too high a temperature at the outlet of the compressor
element
- too high a dewpoint temperature (FF compressors)
4.1 Compressor element outlet temperature
1. In case the outlet temperature of the compressor element
exceeds the shut-down warning level (110 C, not
programmable), alarm LED (8) will light up and the related
pictograph will appear blinking:
Blinking
bar
6.6
Warning screen, element outlet temperature
2. Press arrow key (12), r000 (register 000) appears.
3. Press arrow key (12), the actual compressor element
temperature appears:
Blinking
C
111
Warning screen, element outlet temperature
The screen shows that the temperature at the outlet of the
compressor element is 111 C.
4. It remains possible to scroll through other screens (using
keys 12 and 13) to check the actual status of other
parameters.
5. Press button (1) to stop the compressor and wait until the
compressor has stopped.
6. Switch off the voltage, inspect the compressor and remedy.
7. The warning message will disappear as soon as the warning
condition disappears.
4.2 Dewpoint temperature
1. In case the dewpoint temperature exceeds the shut-down
warning level (programmable), alarm LED (8) will light up
and the related pictograph will appear blinking:
Blinking
bar
6.6
Warning screen, dewpoint temperature
2. Press arrow key (12), r000 (register 000) appears.
3. Press arrow key (12), the actual dewpoint temperature
appears:
Blinking
C
9
Warning screen, dewpoint temperature
The screen shows that the dewpoint temperature is 9 C.
4. It remains possible to scroll through other screens (using
keys 12 and 13) to check the actual status of other
parameters.
5. Press button (1) to stop the compressor and wait until the
compressor has stopped.
6. Switch off the voltage, inspect the compressor and remedy.
7. The warning message will disappear as soon as the warning
condition disappears.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 6
User manual
5 Shut-down
The compressor will be shut down in case:
- the temperature at the outlet of the compressor element
exceeds the shut-down level
- of error of the outlet pressure sensor
- of overload of the drive motor and, on air-cooled
compressors, also the fan motor
5.1 Compressor element outlet temperature
1. In case the outlet temperature of the compressor element
exceeds the shut-down level (120 C, not programmable),
the compressor will be shut down, alarm LED (8) will blink,
automatic operation LED (10) will go out and following
screen will appear:
Blinking
Shut-down screen, element outlet temperature
2. Press enter key (5), r000 (register 000) appears.
3. Press arrow key (12), the actual compressor element
temperature appears:
Blinking
C
122
Shut-down screen, element outlet temperature
The screen shows that the temperature at the outlet of the
compressor element is 122 C.
4. Switch off the voltage and remedy the trouble.
5. After remedying and when the shut-down condition has
disappeared, switch on the voltage and restart the
compressor.
5.2 Motor overload
1. In case of motor overload, the compressor will be shut down,
alarm LED (8) will blink, automatic operation LED (10)
will go out and following screen will appear:
Blinking
Shut-down screen, motor overload
2. Switch off the voltage and remedy the trouble.
3. After remedying and when the shut-down condition has
disappeared, switch on the voltage and restart the
compressor.
10 11 8 9 7 6
3 2 1 4
5
12
13
52236F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
7
User manual
6 Service warning
A service warning will appear when the service timer has
reached the programmed time interval.
1. In case the service timer exceeds the programmed time
interval, alarm LED (8) will light up.
2. Press arrow key (12): r000 is shown (register 000).
Press enter key (5), S (S standing for Service)
appears. Use key (12) to scroll to r005 (register 005)
and press enter key (5), the actual reading of the service
timer will be shown in kHrs (hours x 1000) .
Example: 4.002 indicates that the compressor has run for
4002 hours since previous service.
3. Press enter key (5) and key (12) to scroll to r001
(register 001). Press key (5) to check the running hours,
which are shown in kHrs (hours x 1000).
Example of running hours screen:
kHrs
8.000
The screen shows that the number of running hours is 8000.
4. Stop the compressor, switch off the voltage and carry
out the service actions as explained in the maintenance
schedule in the related Instruction book.
Important
- The longer interval service actions must include the
shorter interval actions.
In the example above, carry out all service operations
belonging to the 8000 running hours interval as well as
those belonging to the 4000 running hours interval.
- If using mineral oil instead of Atlas Copco Roto-
injectfluid, the service timer interval has to be decreased:
500 running hours for 13 bar (175 psi) units and 1000
running hours for 7.5-10 bar (100-150 psi) units.
5. After servicing, reset the service timer (see section 7.5).
7 Scrolling through all screens
Scroll keys (12 and 13) can be used to scroll through all screens.
The screens are divided in register screens (numbered as r001,
r002,...) and parameter screens (numbered as P001,
P002,...).
During scrolling, the numbers of the screens appear consecutively.
For most screens, the unit of measurement and the related
pictograph are shown together with the screen number.
In case of a warning or shut-down, an extra register screen (r000)
is accessible.
Example:
kHrs
r001
The screen shows the screen number (r001), the unit used (kHrs
or hours x 1000) and the related pictograph for running hours.
Press enter key (5) to call up the actual running hours.
Overview of the screens
Register Show
screens
r001 Running hours (x1000 hrs)
r002 Loading hours (x1000 hrs)
r003 Motor starts (x1000)
r004 Motor starts (x1)
r005 Service timer reading
r006 Status of function "Automatic restart after voltage
failure"
r007 Programmed set of parameters
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 8
User manual
C
82
C
4
Bar
7.0
kHrs
r001
kHrs
4.039
r003
kHrs
3.161
3
158
kHrs
4.002
kHrs
"4.002"
r004
kHrs
r002
kHrs
r005
K
L
bar
P001
C
P003
kHrs
P004
C F
P006
P007
P008
P009
P010
Bar
7.0
Bar
6.4
C
8
kHrs
4.000
Mpa psi "bar"
"C " F
I
0000
"0"
0000
L
K L
K L
K L
K L
K L
K L
K L
K L
K L
K L
K L K L
kHrs
0.000
K L
K L
bar
P002
K L
K L
Mpa psi bar
P005
K L
52588PEN
K L
K L
r007
r006
1234
0
Simplified menu flow
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
9
User manual
Parameter Used for
screens
P001 Unload pressure setting
P002 Load pressure setting
P003 Warning level setting for dewpoint temperature
P004 Setting of service timer
P005 Setting of unit for pressure
P006 Setting of unit for temperature
P007 Selection between Y-D or DOL starting
P008 Selection for function "Automatic restart after
voltage failure" (active or not, only for Atlas
Copco)
P009 Selection between Local/Remote control
P010 Changing set of programmed parameters (only
for Atlas Copco)
7.1 Calling up outlet and dewpoint
temperatures
Starting from the Main screen:
bar
6.6
1. Press arrow key (12), the outlet temperature will be shown:
C
83
The screen shows that the outlet temperature is 83 C.
2. Press arrow key (12), the dewpoint temperature will be
shown:
C
3
The screen shows that the dewpoint temperature is 3 C.
3. Use keys (12 and 13) to scroll downwards or upwards
through the screens.
7.2 Calling up running hours
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until r001 is shown and then press
enter key (5):
kHrs
2.381
The screen shows the unit used (kHrs or hours x 1000) and
the value 2.381: the running hours of the compressor are 2381
hours.
7.3 Calling up loading hours
Starting from the Main screen:
bar
6.6
10 11 8 9 7 6
3 2 1 4
5
12
13
52236F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 10
User manual
1. Press arrow key (12) until r002 is shown and then press
enter key (5):
kHrs
1.755
The screen shows the unit used (kHrs or hours x 1000) and
the value 1.755: the loading hours of the compressor are 1755
hours.
7.4 Calling up motor starts
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until r003 is shown and then press
enter key (5):
3
This screen shows the number of motor starts times 1000. Press
enter key (5) to return to the register screens.
2. Press arrow key (12) until r004 is shown and then press
enter key (5):
226
This screen shows the number of motor starts to be added to
the reading in register r003. In this example, the number of
motor starts is 3226.
7.5 Calling up/resetting service timer
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until r005 is shown and then press
enter key (5):
kHrs
1.191
The screen shows the unit used (kHrs or hours x 1000) and
the value 1.191: the compressor has run for 1191 hours since
previous service.
Resetting the service timer
After servicing (see section 6), the timer has to be reset:
1. Scroll to register screen r005, the reading (e.g. 4.000)
will appear.
2. Press reset key (4), the reading will blink (indicating that
resetting is possible).
3. Press enter key (5) to reset the timer to "0.000" or press
reset key (4) to cancel the operation.
7.6 Automatic restart after voltage failure
Starting from the Main screen:
bar
6.6
Press arrow key (12) until r006 is shown and press enter key
(5):
- if 0 appears, the function Automatic restart after voltage
failure is not active
- if 1 appears, the function Automatic restart after voltage
failure is active
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
11
User manual
7.7 Set of parameters
Starting from the Main screen:
bar
6.6
Press arrow key (12) until r007 is shown and press enter key
(5): the number shown indicates the set of parameters which
are programmed ex-factory.
7.8 Calling up/modifying Unloading pressure
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P001 is shown and press the
enter key (5):
bar
7.0
The screen shows the setting of the unloading pressure: 7.0
bar(e).
2. Use arrow keys (12 and 13) to modify this setting.
3. Press enter key (5) to program the new value and to return
to the parameter screens.
7.9 Calling up/modifying Loading pressure
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P002 is shown and then press
enter key (5):
bar
6.4
The screen shows the setting of the loading pressure: 6.4 bar(e).
2. Use arrow keys (12 and 13) to modify this setting.
3. Press enter key (5) to program the new value and to return
to the parameter screens.
7.10 Calling up/modifying Dewpoint
warning temperature
Starting from the Main screen:
bar
6.6
10 11 8 9 7 6
3 2 1 4
5
12
13
52236F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 12
User manual
1. Press arrow key (12) until P003 is shown and press enter
key (5):
C
8
The screen shows the warning setting for the dewpoint
temperature: 8 C.
2. Use arrow keys (12 and 13) to modify this setting.
3. Press enter key (5) to program the new value and to return
to the parameter screens.
7.11 Calling up/modifying Service timer
setting
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P004 is shown and then press
"enter" key (5): the setting of the service timer is shown in
"kHrs" (hours x 1000). Example: 4.000 means the timer
is set at 4000 running hours.
2. Use arrow keys (12 and 13) to modify this setting.
3. Press enter key (5) to program the new value and to return
to the parameter screens.
7.12 Calling up/modifying unit for pressure
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P005 is shown and press enter
key (5): the possible settings are shown: MPa, psi and
bar; the actually used unit is blinking.
2. Use arrow keys (12 and 13) to select another unit for
pressure.
3. Press enter key (5) to program the new unit and to return to
the parameter screens.
7.13 Calling up/modifying unit for
temperature
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P006 is shown and then press
enter key (5): the possible settings are shown: C and
F; the actually used unit is blinking.
2. Use arrow keys (12 and 13) to select another unit for
temperature.
3. Press enter key (5) to program the new unit and to return to
the parameter screens.
7.14 Selection between Y-D or DOL starting
Starting from the Main screen:
bar
6.6
10 11 8 9 7 6
3 2 1 4
5
12
13
52236F
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
13
User manual
1. Press arrow key (12) until P007 is shown and press enter
key (5). The actually used starting mode is blinking: 1
for Y-D (star-delta) or 0 for DOL (direct-on line).
2. Use arrow keys (12 and 13) to select another starting mode.
3. Press enter key (5) to program the new starting mode and
to return to the parameter screens.
7.15 Activating Automatic restart after
voltage failure
This parameter, accessible in screen P008, can only be
modified after entering a password. Consult Atlas Copco if
this function should be activated.
7.16 Selecting between Local or Remote
control
Starting from the Main screen:
bar
6.6
1. Press arrow key (12) until P009 is shown and press enter
key (5). The actually used control mode is blinking: 0 for
Local control mode or 1 for Remote control mode.
2. Use arrow keys (12 and 13) to select another mode.
3. Press enter key (5) to program the new control mode and to
return to the parameter screens.
7.17 Modifying the Parameter set
This parameter, accessible in screen P010, can only be
modified after entering a password.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 14
User manual
8 Settings
8.1 Unloading/loading pressures
Minimum Nominal Maximum
Unloading pressure
13 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12.5 13
13 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12.5 12.8
10 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 9.5 10
10 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 9.5 9.8
7.5 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 7 7.5
7.5 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 7 7.3
100 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 6.9 7.4
100 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 6.9 7.2
125 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 8.6 9.1
125 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 8.6 8.9
150 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 10.3 10.8
150 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 10.3 10.6
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12 12.5
175 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12 12.3
Loading pressure
13 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.9 12.9
13 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.9 12.7
10 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8.9 9.9
10 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8.9 9.7
7.5 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.4 7.4
7.5 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.4 7.2
100 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.3 7.3
100 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.3 7.1
125 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8 9
125 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8 8.8
150 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 9.7 10.7
150 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 9.7 10.5
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.4 12.4
175 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.4 12.2
The recommended minimum pressure difference between loading and unloading is 0.6 bar.
8.2 Element outlet temperature
The settings for warning (110 C) and shut-down (120 C) are
not programmable.
8.3 Dewpoint temperature
The nominal warning setting is 8C.
8.4 Service timer
The nominal setting for compressors using Roto-injectfluid is
4000 running hours. If using mineral oil, the setting must be
decreased to 500 or 1000 running hours (see the related
Instruction book).
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
15
User manual
PART 2
ELEKTRONIKON II REGULATOR
- On GA Workplace FF with ICD the inlet temperature of the
compressed air into the dryer exceeds the warning level.
- On GA Workplace FF with ICD the pressure in the dryer
vessels is lower than the minimum or higher than the
maximum limit.
1.3 Automatic restart after voltage failure
For compressors leaving the factory, this function is made
inactive. If desired, the function can be activated. Consult
Atlas Copco.
Warning If activated and provided the module was in the
automatic operation mode, the compressor will
automatically restart if the supply voltage to the
module is restored within a programmed time
period.
The power recovery time (the period within which
the voltage must be restored to have an automatic
restart) can be set between 10 and 600 seconds
or to Infinite. If the power recovery time is set to
Infinite, the compressor will always restart after
a voltage failure, no matter how long it takes to
restore the voltage. A restart delay can also be
programmed, allowing e.g. two compressors to be
restarted one after the other.
1 General description
1.1 Automatic control of the compressor
The regulator maintains the net pressure between programmable
limits by automatically loading and unloading the compressor.
A number of programmable settings, e.g. the unloading and
loading pressures, the minimum stop time and the maximum
number of motor starts are taken into account.
For GA Workplace FF with ICD, the regulator also maintains
the pressure dewpoint of the dryer between programmable
settings by defining the switching time. A number of
programmable settings are taken into account.
The regulator stops the compressor whenever possible to reduce
the power consumption and restarts it automatically when the
net pressure decreases. In case the expected unloading period
is too short, the compressor is kept running to prevent too-
short standstill periods.
Warning A number of time-based automatic start/stop
commands may be programmed (see section 13).
Take into account that a start command will be
executed (if programmed and activated), even
after manually stopping the compressor.
1.2 Protecting the compressor
Shut-down
If the compressor element outlet temperature exceeds the
programmed shut-down level, the compressor will be stopped.
This will be indicated on display (3-Fig. 2.1). The compressor
will also be stopped in case of overload of the drive motor and,
on air-cooled compressors, also the fan motor.
Shut-down warning
If the compressor element outlet temperature exceeds a
programmed value below the shut-down level, this will also be
indicated to warn the operator before the shut-down level is
reached.
Service warning
A number of service operations are grouped in plans (called
Service plans A, B and C). Each Service plan has a programmed
time interval. If a time interval is exceeded, a message will
appear on display (3-Fig. 2.1) to warn the operator to carry out
the service actions belonging to that plan. Consult the related
Instruction book.
Warning
- A warning message also appears if:
- On water-cooled compressors the cooling water outlet
temperature exceeds the warning level.
- On Full-feature compressors the dewpoint temperature
exceeds the warning level.
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 16
User manual
2 Control panel
2.1 LEDs/buttons/keys
Ref. Designation Function
1 Stop button Push button to stop the
compressor. LED (8) goes out.
The compressor will stop after
running in unloaded condition for
about 30 seconds.
2 Start button Push button to start the
compressor. LED (8) lights up
indicating that the regulator is
operative (in automatic operation).
The LED goes out after unloading
the compressor manually.
3 Display Indicates messages concerning the
compressor operating condition, a
service need or a fault.
4 Scroll keys Keys to scroll through the display.
5 Tabulator key Key to select the parameter
indicated by a horizontal arrow.
Only the parameters followed by
an arrow pointing to the right are
accessible for modifying.
6 Voltage on LED Indicates that the voltage is
switched on.
Fig. 2.1 Control panel
Ref. Designation Function
7 General alarm LED Is alight if a warning, service
warning or shut-down warning
condition exists or if a sensor is
out of order.
7 General alarm LED Blinks in case of shut-down, if a
sensor with shut-down function is
out of order or after an emergency
stop.
8 Automatic Indicates that the regulator is
operation LED automatically controlling the
compressor: the compressor is
loaded, unloaded, stopped and
restarted depending on the air
consumption and the limitations
programmed in the regulator.
9 Function keys Keys to control and program the
compressor. See next page.
S3 Emergency stop Push button to stop the compressor
button immediately in case of emergency.
After remedying the trouble,
unlock the button by pulling it out.
5
2
2
3
9
F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
9
S3
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
17
User manual
2.2 Pictographs
10 Alarm
11 Automatic operation
12 Voltage on
2.3 Function keys
The keys are used:
- To manually load/unload the compressor
- To call up or to program settings
- To reset a motor overload, shut-down or service message,
or an emergency stop
- To have access to all data collected by the regulator
The functions of the keys vary depending on the displayed menu.
The actual function is abbreviated and indicated on the bottom
line of the display just above the relevant key. The most
common abbreviations are listed below.
Abbre- Desig- Function
viation nation
Add Add To add compressor start/stop
commands (day/hour)
Back Back To return to a previously shown
option or menu
Canc Cancel To cancel a programmed setting
when programming parameters
Del Delete To delete compressor start/stop
commands
Help Help To find the Atlas Copco internet
address
Lim Limits To show limits for a programmable
setting
Load Load To load the compressor manually
Main Main To return from a menu to the main
screen (Fig. 3.2)
Menu Menu Starting from the main screen (Fig.
3.2): to have access to submenus
Menu Menu Starting from a submenu, to return
to the previous menu
Mod Modify To modify programmable settings
Abbre- Desig- Function
viation nation
Prog Program To program modified settings
Rset Reset To reset a timer or message
Rtrn Return To return to a previously shown
menu
Unld Unload To unload the compressor
manually
Xtra Exta To find the module configuration
of the regulator
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 18
User manual
Compr Outlet
bar 7.0
Auto Loaded
Menu Unld
Auto Operation
Local Control
Timer Active
Main Help Xtra
Max Pressure
bar 7.5

Main Help Xtra


Status data
Measured data
Counters
Main
All Conditions
Are OK
Menu
Status data
Measured data
Counters
Main
Compr Outlet
Bar 7.0

Menu Xtra
Measured data
Counters
Test
Main
Counters
Test
Modify Params
Main
Test
Modify Params
Service
Main
Modify Params
Service
Saved data
Main
Running hours
hrs 2107

Menu
Parameters
Protections
Service Plan
Menu
Loading Press
Bar 6.4

Menu Mod
Parameters
Protections
Service Plan
Menu
Compr Outlet
Bar 6.8

Menu
Protections
Service Plan
Clock Function
Menu
Service Timer
Running hours
hrs 130
Menu
Service Timer
Running hours
hrs 130
Menu
Modify Params
Service
Saved data
Main
Last Shutdown 1
Last Shutdown 2
Last Shutdown 3
Menu
52948PEN
Service Plan
Clock Function
Configuration
Menu
Clock Function
Not Activated
Menu Mod Del
Service Plan
Clock Function
Configuration
Menu
Time
10:54

Menu Mod
-Running Hours
-Loaded Hours
-Motor Starts
-Module Hours
-Load Relay
-Compr Outlet
-DP Oil Separ
-Element Outlet
-Dryer LAT
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-DP Oil Separ
-Element Outlet
-Dryer LAT
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-Loaded Hours
-Motor Starts
-Module Hours
-Load Relay
-Unloading Press
-Loading Press 2
-Unloading Press 2
-Y-Time
-Load delay
-Nr Starts/Day
-Min Stop Time
-Progr Stop Time
-Commun Time-out
Display test
Safety valve

Menu
-DP Oil separ
-Element outlet
-Dryer LAT
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-Date
-Date format
-Language in use
-Pressure Unit
-Temperat Unit
-Vibration Unit
-Level Unit
-Pres Band Used
-Start Mode
-CCM (control mode)
-Auto Restart
-Password
-Node ID
-MCC
-Digital PB Sel
Fig. 3.1a Simplified menu flow of GA Workplace Full-Feature with IFD
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
19
User manual
Fig. 3.1b Simplified menu flow of GA Workplace Full-Feature with ICD
Compr Outlet
bar 7.0
Auto Loaded
Menu Unld
Auto Operation
Local Control
Timer Active
Main Help Xtra
Max Pressure
bar 7.5

Main Help Xtra


Status data
Measured data
Counters
Main
All Conditions
Are OK
Menu
Status data
Measured data
Counters
Main
Compr Outlet
Bar 7.0

Menu Xtra
Measured data
Counters
Test
Main
Counters
Test
Modify Params
Main
Test
Modify Params
Service
Main
Modify Params
Service
Saved data
Main
Running hours
hrs 2107

Menu
Parameters
Protections
Service Plan
Menu
Loading Press
Bar 6.4

Menu Mod
Parameters
Protections
Service Plan
Menu
Compr Outlet
Bar 6.8

Menu
Protections
Service Plan
Clock Function
Menu
Service Timer
Running hours
hrs 130
Menu
Service Timer
Running hours
hrs 130
Menu
Modify Params
Service
Saved data
Main
Last Shutdown 1
Last Shutdown 2
Last Shutdown 3
Menu
52950PEN
Service Plan
Clock Function
Configuration
Menu
Clock Function
Not Activated
Menu Mod Del
Service Plan
Clock Function
Configuration
Menu
Time
10:54

Menu Mod
-Running Hours
-Loaded Hours
-Motor Starts
-Module Hours
-Load Relay
-Compr Outlet
-DP Oil Separ
-Element Outlet
-Vessel A
-Vessel B
-Inlet Dryer
-Dryer Dewpoint
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-DDp filter
-DP Oil Separ
-Element Outlet
-Vessel A
-Vessel B
-Inlet Dryer
-Dryer Dewpoint
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-DDp filter
-Loaded Hours
-Motor Starts
-Module Hours
-Load Relay
-Unloading Press
-Loading Press 2
-Unloading Press 2
-Y-Time
-Load delay
-Nr Starts/Day
-Min Stop Time
-Progr Stop Time
-Commun Time-out
-PDP Level
Display test
Safety valve

Menu
-DP Oil separ
-Element outlet
-Vessel A
-Vessel B
-Inlet Dryer
-Dryer Dewpoint
-Emergency Stop
-RemStart/Stop
-RemLoad/Unl
-RemPressure
-Overload Motor
-Overl Fanmotor
-P1 open/P2 closed
-DDp filter
-Date
-Date format
-Language in use
-Pressure Unit
-Temperat Unit
-Vibration Unit
-Level Unit
-Pres Band Used
-Start Mode
-CCM (control mode)
-Auto Restart
-Password
-Node ID
-MCC
-Digital PB Sel
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 20
User manual
3 Menu-driven control programs
To facilitate programming and controlling the compressor,
menu-driven programs are implemented in the electronic
module.
Simplified menu flows are shown in Figs. 3.1.
3.1 Function of control programs
Program/
Function Description
Main screen Shows in short the operation status of the
compressor. It is the gateway to all functions.
See Fig. 3.2.
Status data Calling up the status of the compressor
protection functions:
- shut-down
- shut-down warning
- service warning
- warning
Resetting of a shut-down, motor overload
and service condition.
Measured data Calling up:
- actually measured data
- status of some inputs such as the motor
overload protection
Counters Calling up the:
- running hours
- loaded hours
- number of motor starts
- regulator (module) hours
- number of load cycles
Test Allows a display test.
Modify params Modifying the settings for:
- parameters (e.g. loading and unloading
pressures)
- protections (e.g. air temperature shut-
down level)
- service plans (see related Instruction
book)
- clock functions (automatic compressor
start/stop/pressure band commands)
- configuration (time, date, display
language, )
Service Calling up service plans and resetting the
timers. See section 15.
Saved data Calling up the saved data: last shut-down,
last emergency stop data
3.2 Main screen
When the voltage is switched on, the Main screen is shown
automatically, showing in short the operation status of the
compressor.
Compressor out
bar 7.0
Auto Loaded
Menu Unld
F1 F2 F3
Fig. 3.2 Main screen, typical example
If the function keys or arrow keys are not used for some minutes,
the display will automatically return to the Main screen.
Whenever displayed on a submenu screen, press the key Main
to return to the Main screen.
3.3 Calling up other menus
Starting from the Main screen:
- Use the key for a quick look at the actual compressor
status (see section 4)
- Press the key Menu (F1), the option Status data will
be followed by a horizontal arrow:
- either press the tabulator key (5) to select this menu
- or use the key to scroll until the desired submenu is
followed by a horizontal arrow and then press the
tabulator key (5) to select this menu
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
21
User manual
4 Quick look at actual compressor
status
Procedure
1. Starting from the Main screen (see section 3.2), press the
key: A screen similar to the one below appears:
Auto Operation
Local Control
Timer Active
Main Help Xtra
F1 F2 F3
Fig. 4.1 Example of an actual compressor status display
Line 1 indicates the automatic or manual operation status of
the regulator:
Auto operation means that the regulator automatically
adapts the operation of the compressor, i.e. loading,
unloading, stopping and automatic restarting according to
the programmed parameters.
Man operation means that the automatic pressure control
function of the regulator is interrupted after pressing the
Unload key on the Main screen.
Line 2 indicates whether the regulator operates in local control
or remote control mode:
Local control means that the start/stop and load/unload
buttons on the keyboard are activated.
Remote control means that these functions are controlled
remotely. Consult Atlas Copco.
Line 3 indicates whether the timer which generates time-based
start and stop commands is activated or not. See section 13.
See section 2.3 for the functions of the keys Main, Help
and Xtra.
2. Press the key to get other data (actual compressor
conditions of the compressor) as shown in Figs. 3.1.
5 Status data menu
The status data submenu gives information regarding the status
of the compressor protection functions (shut-down, shut-down
warning, service warning and warning) and allows resetting of
a shut-down, motor overload and service condition.
Procedure
Starting from the Main screen (see section 3.2):
- Press the key Menu (F1), the option Status data will be
followed by a horizontal arrow
- Press the tabulator key (5)
5.1 No message exists
In this case, LED (7) is out and the message on the display
indicates that all conditions are normal (Fig. 5.1):
All conditions
are OK
Menu
F1 F2 F3
Fig. 5.1 Example of a status data screen
5.2 A shut-down message exists
In case the compressor is shut down, LED (7) will blink.
In case of a shut-down due to too high a temperature at the
compressor element outlet, a screen similar to the one below
will appear:
Element outlet
C 122
Shd Max 120
Menu ** ** Rset
F1 F2 F3
Fig. 5.2 Example of a status data screen
1. The indicators (**) are blinking. The screen shows the
sensor (compressor element outlet), the actual reading (122
degrees Celsius), that the compressor is shut down (Shd),
and the shut-down setting (120 degrees Celsius).
2. It remains possible to scroll through other menus, e.g. to
check the values of other parameters.
When returning to the Status data menu, the option
Shutdowns will blink. This option can be selected by
pressing the tabulator key (5) to return to the shut-down
screen (Fig. 5.2).
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 22
User manual
Shut-down reset
1. Switch off the voltage and remedy the trouble. After
remedying and when the shut-down condition has
disappeared, switch on the voltage and press the key Rset.
2. Press the keys Menu and Main to return to the Main
screen and restart the compressor by means of button I.
Motor overload reset
1. Switch off the voltage and remedy the trouble. The overload
relay (F21) is automatically reset after cooling off but the
fan circuit breaker (Q15) must be reset manually. Switch
on the voltage and press the key Rset.
2. Press the keys Menu and Main to return to the Main
screen and restart the compressor by means of button I.
5.3 A shut-down warning message exists
A shut-down warning level is a programmable level below the
shut-down level.
1. If a shut-down warning exists, LED (7) is alight. The Main
screen will change into a screen similar to the one below:
Compressor out
bar 7.0
*Shutd Warn*
Menu ** ** Unld
F1 F2 F3
Fig. 5.3 Example of a shut-down warning screen
2. The indicators (**) are blinking and the message *Shutd
Warn* appears alternately with the messages indicating
whether the compressor runs unloaded or loaded.
3. Press the key Menu (F1) and the tabulator key (5) to select
the Status data menu, the option Protection is blinking.
4. Scroll to this option and select it by pressing the tabulator
key (5): option Warnings blinks. A screen similar to the
one in Fig. 5.4 appears:
Element outlet
C 116
Shdw Max 110
Menu ** **
F1 F2 F3
Fig. 5.4 Example of a shut-down warning screen
The screen shows that the temperature at the outlet of the
compressor element (116 degrees Celsius) is too high.
5. Stop the compressor by means of button O and wait until
the compressor has stopped.
6. Switch off the voltage, inspect the compressor and remedy.
7. The warning message will disappear automatically as soon
as the warning condition disappears.
5.4 A service warning message exists
1. LED (7) is alight and the main screen will change into a
screen similar to that shown in Fig. 5.5.
Compressor out
bar 7.0
*Serv Requir *
Menu ** ** Unld
F1 F2 F3
Fig. 5.5 Example of a warning screen
2. The indicators (**) are blinking and the service warning
message appears alternately with the messages indicating
whether the compressor runs unloaded or loaded.
3. Press the key Menu (F1) and the tabulator key (5) to select
the Status data menu: the option Service is blinking.
4. Scroll to this option and select it by pressing the tabulator
key (5), two options may blink:
Inputs: if the programmed service level of a component
is exceeded (e.g. the maximum pressure drop of the oil
separator). See section 17.2.
Plans: if a service plan interval is exceeded. See the
related Instruction book.
5. Stop the compressor and switch off the voltage.
6. In case the service message was referring to Inputs (oil
separator): replace the separator, switch on the voltage,
scroll in the Status data menu to Inputs and press the
Rset key to reset the service message.
7. In case the service message was referring to Plans: carry
out the service actions related to the indicated plans. Reset
the timers of the related plans as described in section 15.
5.5 A warning message exists
1. LED (7) is alight and a warning message will appear on the
screen.
2. The indicators (**) are blinking and the warning message
appears alternately with the messages indicating whether
the compressor runs unloaded or loaded. This warning
indicates that:
- On water-cooled compressors, the cooling water outlet
temperature exceeds the programmed warning level.
- On Full-feature compressors (compressors with
integrated air dryer), the dewpoint temperature exceeds
the warning level.
- On GA Workplace FF with ICD the inlet temperature
of the compressed air into the dryer exceeds the warning
level.
- On GA Workplace FF with ICD the pressure in the
dryer vessels is lower than the minimum or higher than
the maximum limit.
3. Stop the compressor.
4. Switch off the voltage, inspect the compressor and remedy.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
23
User manual
6 Measured data menu
Function
To call up information regarding the actually measured data
and the status of some inputs such as the motor overload
protection.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Measured data is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
Compressor out
bar 7.0
Menu
F1 F2 F3
Fig. 6.1 Example of a measured data screen
2. By pressing the key, a number of actually measured data
can be found (see Figs. 3.1).
3. If one of the sensors is linked to a shut-down, service or
warning function, both the actually measured value as well
as the corresponding shut-down, warning or service level
can be called up by pressing the tabulator key (5).
7 Counters menu
Function
To allow the operator to call up the:
- running hours
- loaded hours
- number of motor starts
- regulator (module) hours (the hours the module has been
under tension)
- number of load cycles
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Counters is followed
by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. By pressing the key, the above-mentioned data can be
found (see also Figs. 3.1).
8 Test menu
Function
To carry out a display test, i.e. to check whether the display
and LEDs are still intact.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Test is followed by a
horizontal arrow
- press the tabulator key (5) to activate the menu
2. The option Display test will be followed by a horizontal
arrow.
3. After pressing the tabulator key (5), the regulator will
generate a series of patterns on the display which enable
the operator to check that each pixel still functions normally;
at the same time the LEDs are lit.
9 Modify params menu
Function
The menu allows the operator to program:
- Parameters, see section 10.
- Protection settings, see section 11.
- Service plan settings, see section 12.
- Clock settings, see section 13.
- Configuration settings, see section 14.
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 24
User manual
2. The screen shows that the current setting is 6.0 bar(e). To
modify this setting, press the key Mod (F2):
Loading Press
Bar 6.0 (blinks)
Prog Lim Canc
F1 F2 F3
Fig. 10.2 Modify parameters menu
3. The key Lim (F2) can be used to find the limitations for
the parameter. Use the or arrow key to change the value.
4. Press the key Prog (F1) to program the new setting or the
key Canc (F3) to cancel the modification operation.
5. The procedure to modify the Unloading pressure is similar
to the description above.
6. If required, repeat the procedure for the Loading pressure 2
and Unloading pressure 2 (pressure band 2).
11 Modifying protection settings
Function
1. To modify protection settings:
- shut-down (Shd), for element outlet temperature
- shut-down warning (Shdw), for element outlet
temperature
- warning (Warn), e.g. for cooling water outlet or
dewpoint temperature
- service warning (Serv), e.g. DP oil separator (max.
pressure drop)
2. To check some compressor conditions, e.g. the status of the
motor overload contacts. The list of parameters is shown
in Figs. 3.1.
Note
Some parameters are not modifyable.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Protections is
followed by a horizontal arrow.
3. Press the tabulator key (5): the first item (Compressor out)
and its value will appear.
4. Use the key to scroll until the parameter to be modified is
followed by a horizontal arrow.
10 Modifying parameters
Function
To modify a number of parameters as mentioned in Figs. 3.1.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. The first option (Parameters) will be followed by a
horizontal arrow.
3. Press the tabulator key (5): the first item (Loading
pressure) and its setting will appear.
4. Use the key to scroll until the parameter to be modified is
followed by a horizontal arrow.
10.1 Modifying the loading and unloading
pressures
Pressure bands
If desired, the operator can program two pressure bands (band
1 and band 2) with different loading and unloading pressures.
The settings for band 1 are indicated as Loading pressure
and Unloading pressure, the settings for band 2 are indicated
as Loading pressure 2 and Unloading pressure 2.
Example:
For pressure band 1:
- Loading pressure: 6.4 bar
- Unloading pressure: 7.0 bar
For pressure band 2:
- Loading pressure 2: 4.0 bar
- Unloading pressure 2: 6.0 bar
Procedure
1. Consult the section above to select the parameter Loading
pressure:
Loading Press
Bar 6.0
Menu Mod
F1 F2 F3
Fig. 10.1 Modify parameters menu
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
25
User manual
11.1 Modifying settings for compressor
element
1. Consult the section above to select the parameter Element
outlet:
Element Outlet
C 94
Shd Max 120
Menu Mod
F1 F2 F3
Fig. 11.1 Modify parameters menu
2. The screen shows that the current temperature is 94 degrees
Celsius and that the shut-down setting is 120 degrees
Celsius. To modify this setting, press the key Mod (F2):
Element Outlet
C 120 (blinks)
Prog Lim Canc
F1 F2 F3
Fig. 11.2 Modify parameters menu
3. The key Lim (F2) can be used to find the limitations for
the parameter. Use the or arrow key to change the
value.
4. Press the key Prog (F1) to program the new setting or the
key Canc (F3) to cancel the modification operation.
5. The screen shown in Fig. 11.1 shows an arrow pointing to
the right to call up the screen to modify the shut-down
warning value:
Element Outlet
C 94
Shdw Max 110
Back Mod
F1 F2 F3
Fig. 11.3 Modify parameters menu
6. The screen shows that the current temperature is 94 degrees
Celsius and that the shut-down warning setting is 110
degrees Celsius. The modifying procedure is similar to the
description above.
Note:
The modifying procedure for other settings is similar. For some
settings, a delay can be programmed. See section 17.
12 Modifying service plans
Function
To modify the hour intervals for the Service plans.
Service plans
The service operations to be carried out are grouped in plans
called Service plan A, B, C or D. Consult section 4 in the related
Instruction book. When reaching an interval, a message will
appear on the screen indicating which Service plans are to be
carried out.
Important
Always consult Atlas Copco in case any timer setting should
be changed. The intervals must not exceed the periods below
and must coincide logically.
Programmed service plan intervals
Service plans Intervals
Service plan A Each 4000 running hours
Service plan B Each 4000 running hours
Service plan C Each 8000 running hours
Service plan D Each 40000 running hours
Resulting service actions to be carried out
Service actions according to At
Service plan A and B 4000 running hours
Service plan A, B and C 8000 running hours
Service plan A and B 12000 running hours
Service plan A, B and C 16000 running hours
.
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 26
User manual
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Service plan is
followed by a horizontal arrow.
3. Press the tabulator key (5): a screen similar to the one below
will appear:
Service Timer
Running hours
hrs 2130
Menu
F1 F2 F3
Fig. 12.1 Service plan menu
The screen shows the actual running hours (2130).
4. Press the tabulator key (5): a screen similar to the one below
will appear:
Service Timer
Level A
hrs 4000
Menu Mod
F1 F2 F3
Fig. 12.2 Service plan menu
5. The screen indicates that the level for Service plan A is set
at 4000 running hours.
6. Press the Mod key. The key Lim (F2) can be used to
find the limitations for the parameter. Use the or arrow
key to modify the interval.
7. Press the key Prog (F1) to program the new setting or the
key Canc (F3) to cancel the modification operation.
8. The procedure to modify the Service plans B, C and D are
carried out in a similar way.
13 Programming Clock function
To program:
- time-based start/stop commands for the compressor
- time-based change-over commands for the net pressure band
(see also section 10.1)
13.1 Programming start/stop/pressure band
commands
In this example, the compressor will be programmed as follows:
- On Monday at 06:15 starting in pressure band 1
- On Friday at 18:00 changing over to pressure band 2
- On Saturday at 18:00 stopping
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Clock function is
followed by a horizontal arrow. Press the tabulator key (5),
following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
3. Press the tabulator key (5), following screen appears:
Monday
Tuesday
Wednesday
Menu Mod Del
F1 F2 F3
4. Use the or key until the day on which a command must
be programmed is followed by a right pointing arrow. Press
the tabulator key (5), following screen appears:
--:-- ---------------
--:-- ---------------
--:-- ---------------
Menu Mod Del
F1 F2 F3
5. Press the key Mod (F2). The first two dashes will flash.
Use the or key to enter 06. Press the tabulator key to
jump to the following two dashes. Use the or key to
enter 15. Press the tabulator key to jump to the row of
dashes. Use the or key to enter the command Start.
Press the key Prog to program the command: 06:15 Start
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
27
User manual
6. Press the key: the right pointing arrow key indicates that
the second line is accessible. Press the key Mod and
modify this line to the following command line: 06:15 Band
1 in a similar way
7. Press the key Menu (F1) and scroll to Friday:
Thursday
Friday
Saterday
Menu Mod Del
F1 F2 F3
8. Programming the command to change over at 18 oclock to
Band 2 is carried out in a similar way as described above.
9. Press the key Menu (F1) and scroll to Saterday.
Programming the command to stop at 18 oclock is carried
out in a similar way as described above.
13.2 To activate/deactivate the timer
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Clock function is
followed by a horizontal arrow. Press the tabulator key (5),
following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
2. Press the key Mod, Not activated starts blinking.
3. Press the key, Not activated changes into Activated.
4. Press the key Prog.
Important:
1. It is necessary to program the start/stop/pressure band
commands in successive order timewise, e.g.:
07.30 start
07.30 band 1
08.30 band 2
17.00 stop
etc.
2. Make sure that the clock function is activated (indicated as
Activated). If not, the programmed start/stop commands
will not be executed.
13.3 To modify a command
Suppose the command to stop the compressor on Saturday 18:00
is to be modified: stopping at 17 oclock instead of 18 oclock:
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Clock function is
followed by a horizontal arrow. Press the tabulator key (5),
following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
3. Press the tabulator key (5), following screen appears:
Monday
Tuesday
Wednesday
Menu Mod Del
F1 F2 F3
4. Scroll through the display until Saturday is followed by a
horizontal arrow. Press the tabulator key (5). If necessary,
scroll through the compressor start/stop/pressure band
commands until the command to be modified is followed
by the horizontal arrow on the screen. Press the key Mod,
the first two digits of the command start blinking. Modify
as required using the scroll keys, i.e. in the example above
change 18 into 17 using the key.
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 28
User manual
5. If necessary, press the tabulator key (5) to go to the next
field to be modified, the minutes indication and the start/
stop/pressure band indication.
6. Press the key Prog to program the new command or the
key Canc to quit without reprogramming.
13.4 To add a command
Adding a command at the end of an existing list
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Clock function is
followed by a horizontal arrow. Press the tabulator key (5),
following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
Suppose the command to stop the compressor at 18:00 must be
added to the list of Monday:
- 06:15 start
- 06:15 band 1
3. Press the tabulator key (5), following screen appears:
Monday
Tuesday
Wednesday
Menu Mod Del
F1 F2 F3
4. Scroll through the display until Monday is followed by a
horizontal arrow. Press the tabulator key (5). Scroll through
the compressor start/stop/pressure band commands until the
first empty command line is indicated by the horizontal
arrow on the screen.
5. Press the key Mod, the first two digits of the command
start blinking. Enter 18:00 stop using the scroll keys or
to modify a field and the tabulator key (5) to jump from
one field to another.
6. Press the key Prog to program the new command or the
key Canc to quit without reprogramming.
Adding a command between two existing commands
1. Suppose the command 17:00 band 2 must be added to
following list:
- 06:00 start
- 06:00 band 1
- 18:00 stop
2. The regulator does not allow to enter a new command which
is situated timewise before the last command in the list.
3. Scroll through the display until the command before which
the new command must be entered is followed by the
horizontal arrow (in the example above: 18:00 stop) and
press the key Mod. Change this command to the new
command (in the example above: 17:00 band 2) and press
the Prog. Press the key, add the last command of the
list (in the example above: 18:00 stop) and press the key
Prog.
13.5 To delete commands
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Clock function is
followed by a horizontal arrow. Press the tabulator key (5),
following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
Deleting all commands
Press the key Del (F3) in the screen above. A question to
confirm the deleting operation will appear.
Deleting all commands related to a specific day
Scroll through the display until the desired day is followed by
a horizontal arrow. Press the key Del (F3). A question to
confirm the deleting operation will appear.
Deleting a specific start/stop/pressure band command
Scroll through the display until the desired start, stop, band 1
or band 2 command line is followed by a horizontal arrow.
Press the key Del (F3). A question to confirm the deleting
operation will appear.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
29
User manual
14 Configuration menu
Function
To reprogram a number of parameters. See Figs. 3.1.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Configuration is
followed by a horizontal arrow.
3. Press the tabulator key (5): The first option shown is Time.
If another option is desired, scroll through the display (using
or keys) and select it using the tabulator key (5).
4. In case of option Time, the second line on the screen
indicates the actual setting, e.g. 14:30.
5. If it is desired to modify the time, press the key Mod. If
not, press the key Menu to return to the submenu.
6. After pressing the key Mod, the first field (14) will blink.
Modify the hours using the or keys. Then press the
tabulator key (5) to go to the next field (i.e. 30). The setting
of this field can now be modified with the or keys.
7. The bottom line of the display will show two options:
- Prog to program the new setting
- Canc to cancel the new setting
8. Proceed in a similar way for the other parameters to be
modified.
14.1 Programming compressor control
modes
Compressor control modes
The compressor can be controlled locally, remotely or via a
local area network (LAN). See the related Instruction book,
section 3.2.
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Modify params is
followed by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. Use the key to scroll until the option Configuration is
followed by a horizontal arrow.
3. Press the tabulator key (5): The first option shown is Time.
Scroll through the display (using or keys) until the option
CCM is followed by a horizontal arrow and select it using
the tabulator key (5). Following screen is shown:
CCM
Local control
Menu Mod
F1 F2 F3
Fig. 14.1 Compressor control mode menu
4. Press the key Mod and use or keys to select the desired
control mode. Press the Prog key to program or the
Cancel key to cancel the modification.
15 Service menu
Function
- To reset the service plans which are carried out.
- To check for both the next service plans to be carried out
and to find which service plans were carried out previously.
Service plans
- Consult the related Instruction book to find which service
actions are related to these plans.
- Consult section 12 if any modification to the intervals should
be required.
When the service plan interval is reached, a message will appear
on the screen. See section 5.
Example
Programmed service plan intervals ex-factory
Service plans Intervals
Service plan A Each 4000 running hours
Service plan B Each 4000 running hours
Service plan C Each 8000 running hours
Service plan D Each 40000 running hours
Resulting service actions to be carried out
Service actions according to At
Service plan A and B 4000 running hours
Service plan A, B and C 8000 running hours
Service plan A and B 12000 running hours
Service plan A, B and C 16000 running hours
.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 30
User manual
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Service is followed
by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. A screen similar to the one below appears:
Service Timer
Running Hours
hrs 7971
Menu
F1 F2 F3
Fig. 15.1 Service menu
The screen shows that the total compressor running time is 7971
hrs.
3. Press the tabulator key (5):
Next Timer
Level A B C
hrs 8000
Back Rset
F1 F2 F3
Fig. 15.2 Service menu
The screen shows that the next service plans to be carried out
are plans A, B and C and that these plans are to be carried out
each 8000 running hours.
4. Press the key to find which service plans were carried out
previously:
Previous Timer
Level A B
hrs 4008
F1 F2 F3
Fig. 15.3 Service menu
The screen shows that service plans A and B were carried out
at 4008 running hours.
5. Stop the compressor, switch off the voltage and carry out
the service operations related to plans A, B and C. See the
related Instruction book.
6. Switch on the voltage and scroll to the service screen shown
in Fig. 15.2. Press the Rset button (F3) to reset the timer.
Confirm the question for resetting.
Notes
- The Rset button only appears when the next Timer level
is almost reached (from 400 running hours before elapsing
of the service plan interval).
- After pressing the key in Fig. 15.1, the Life time hours
are shown (i.e. the number of hours elapsed since initial
programming ex-factory). This counter is not taken into
account.
16 Saved data menu
Function
To call up some compressor data saved by the regulator. These
data are:
- Last shut-down data
- Last emergency stop data
Procedure
1. Starting from the Main screen (see section 3.2):
- press the key Menu (F1)
- press the key until the option Saved data is followed
by a horizontal arrow
- press the tabulator key (5) to activate the menu
2. The list of last shut-down and emergency stop cases is
shown.
3. Scroll through the items to select the desired shut-down or
emergency stop item.
4. Press the tabulator key (5) to find the date, time and other
data reflecting the status of the compressor at the last shut-
down occurred.
52237F
8 11 7 10 6 12
3 2 1
9
4
5
4
9
S3
9
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
31
User manual
17 Programmable settings
17.1 Parameters
Minimum Nominal Maximum
Motor running time in star . . . . . . . . . . . . . . . . . . . . sec 5 10 10
Load delay time . . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 0 10
Number of motor starts . . . . . . . . . . . . . . . . . . . . . . starts/day 0 240 240
Minimum stop time . . . . . . . . . . . . . . . . . . . . . . . . . sec 1) 20 30
Power recovery time . . . . . . . . . . . . . . . . . . . . . . . . . sec 10 10 3600 12)
Restart delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 0 1200
Communication time out 7) . . . . . . . . . . . . . . . . . . . sec 10 30 60
For Full-feature with ICD also:
Pressure dewpoint dryer (-40 C PDP version) . . . . C -45 -40 -20
Pressure dewpoint dryer (-70 C PDP version) . . . . C -75 -70 -20
Unloading pressure 3)
GA Pack, GA Workplace
13 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12.5 13
10 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 9.5 10
7.5 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 7 7.5
100 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 6.9 7.4
125 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 8.6 9.1
150 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 10.3 10.8
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12 12.5
GA Pack FF, GA Workplace FF with IFD
13 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12.5 12.7
10 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 9.5 9.7
7.5 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 7 7.2
100 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 6.9 7.1
125 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 8.6 8.8
150 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 10.3 10.5
175 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4.1 12 12.2
GA Workplace FF with ICD (see table below)
Loading pressure 3)
GA Pack, GA Workplace
13 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.9 12.9
10 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8.9 9.9
7.5 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.4 7.4
100 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.3 7.3
125 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8 9
150 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 9.7 10.7
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.4 12.4
GA Pack FF, GA Workplace FF with IFD
13 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.9 12.6
10 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8.9 9.6
7.5 bar Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.4 7.1
100 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 6.3 7
125 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 8 8.7
150 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 9.7 10.4
175 psi Full-feature . . . . . . . . . . . . . . . . . . . . . . . . . bar(e) 4 11.4 12.1
GA Workplace FF with ICD (see table below)
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 32
User manual
Unloading/loading pressures for GA Workplace Full-Feature with ICD
Dewpoint -40 variant 50Hz
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA30 - 7.5 CD100 6.5 6.9 6.9 6.4 6.4 6.8
GA30 - 7.5 CD140 5.4 6.5 6.8 5.3 6.0 6.7
GA30 - 7.5 CD170 4.8 6.5 6.8 4.7 6.0 6.7
GA30 - 8 CD100 6.4 7.0 7.3 6.3 6.5 7.2
GA30 - 8 CD140 5.2 7.0 7.3 5.1 6.5 7.2
GA30 - 8 CD170 4.6 7.0 7.3 4.5 6.5 7.2
GA30 - 10 CD100 5.9 9.0 9.3 5.8 8.5 9.2
GA30 - 10 CD140 4.8 9.0 9.3 4.7 8.5 9.2
GA30 - 10 CD170 4.3 9.0 9.3 4.2 8.5 9.2
GA30 - 13 CD100 8.7 12.0 12.3 8.6 11.5 12.2
GA30 - 13 CD140 7.1 12.0 12.3 7.0 11.5 12.2
GA30 - 13 CD170 6.4 12.0 12.3 6.3 11.5 12.2
GA37 - 7.5 CD140 6.1 6.5 6.8 6.0 6.0 6.7
GA37 - 7.5 CD170 5.4 6.5 6.8 5.3 6.0 6.7
GA37 - 8 CD140 5.9 7.0 7.3 5.8 6.5 7.2
GA37 - 8 CD170 5.3 7.0 7.3 5.2 6.5 7.2
GA37 - 10 CD100 6.8 9.0 9.3 6.7 8.5 9.2
GA37 - 10 CD140 5.5 9.0 9.3 5.4 8.5 9.2
GA37 - 10 CD170 4.9 9.0 9.3 4.8 8.5 9.2
GA37 - 13 CD100 9.7 12.0 12.3 9.6 11.5 12.2
GA37 - 13 CD140 8.0 12.0 12.3 7.9 11.5 12.2
GA37 - 13 CD170 7.1 12.0 12.3 7.0 11.5 12.2
GA45 - 7.5 CD170 6.0 6.5 6.8 5.9 6.0 6.7
GA45 - 8 CD140 6.3 7.0 7.3 6.2 6.5 7.2
GA45 - 8 CD170 5.6 7.0 7.3 5.5 6.5 7.2
GA45 - 10 CD100 8.5 9.0 9.3 8.4 8.5 9.2
GA45 - 10 CD140 6.3 9.0 9.3 6.2 8.5 9.2
GA45 - 10 CD170 5.6 9.0 9.3 5.5 8.5 9.2
GA45 - 13 CD100 11.2 12.0 12.3 11.1 11.5 12.2
GA45 - 13 CD140 9.2 12.0 12.3 9.1 11.5 12.2
GA45 - 13 CD170 8.2 12.0 12.3 8.1 11.5 12.2
GA55C - 7.5 CD170 6.5 6.9 6.9 6.4 6.4 6.8
GA55C - 10 CD140 6.9 9.0 9.3 6.8 8.5 9.2
GA55C - 10 CD170 6.1 9.0 9.3 6.0 8.5 9.2
GA55C - 13 CD140 10.2 12.0 12.3 10.1 11.5 12.2
GA55C - 13 CD170 9.2 12.0 12.3 9.1 11.5 12.2
GA55 - 7.5 CD230 5.8 6.5 6.8 5.7 6.0 6.7
GA55 - 7.5 CD280 5.1 6.5 6.8 5.0 6.0 6.7
GA55 - 8 CD170 6.6 7.0 7.3 6.5 6.5 7.2
GA55 - 8 CD230 5.6 7.0 7.3 5.5 6.5 7.2
GA55 - 8 CD280 5.0 7.0 7.3 4.9 6.5 7.2
GA55 - 10 CD170 6.2 9.0 9.3 6.1 8.5 9.2
GA55 - 10 CD230 5.2 9.0 9.3 5.1 8.5 9.2
GA55 - 10 CD280 4.6 9.0 9.3 4.5 8.5 9.2
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
33
User manual
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA75 - 7.5 CD280 6.2 6.6 6.8 6.1 6.1 6.7
GA75 - 8 CD230 6.6 7.0 7.3 6.5 6.5 7.2
GA75 - 8 CD280 6.0 7.0 7.3 5.9 6.5 7.2
GA75 - 10 CD170 8.1 9.0 9.3 8.0 8.5 9.2
GA75 - 10 CD230 6.3 9.0 9.3 6.2 8.5 9.2
GA75 - 10 CD280 5.6 9.0 9.3 5.5 8.5 9.2
GA75 - 13 CD170 11.0 12.0 12.3 10.9 11.5 12.2
GA75 - 13 CD230 9.3 12.0 12.3 9.2 11.5 12.2
GA75 - 13 CD280 8.4 12.0 12.3 8.3 11.5 12.2
GA90C - 7.5 CD280 6.4 6.8 6.8 6.3 6.3 6.7
GA90C - 8 CD280 6.4 7.0 7.3 6.3 6.5 7.2
GA90C - 10 CD230 6.7 9.0 9.3 6.6 8.5 9.2
GA90C - 10 CD280 6.0 9.0 9.3 5.9 8.5 9.2
GA90C - 13 CD170 11.6 12.0 12.3 11.5 11.5 12.2
GA90C - 13 CD230 10.0 12.0 12.3 9.9 11.5 12.2
GA90C - 13 CD280 8.9 12.0 12.3 8.8 11.5 12.2
Dewpoint -40 variant 60Hz
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA30 - 100 CD140 5.4 6.4 6.7 5.3 5.9 6.6
GA30 - 100 CD170 4.8 6.4 6.7 4.7 5.9 6.6
GA30 - 125 CD100 6.2 8.1 8.4 6.1 7.6 8.3
GA30 - 125 CD140 5.1 8.1 8.4 5.0 7.6 8.3
GA30 - 125 CD170 4.5 8.1 8.4 4.4 7.6 8.3
GA30 - 150 CD100 5.6 9.8 10.1 5.5 9.3 10.0
GA30 - 150 CD140 4.6 9.8 10.1 4.5 9.3 10.0
GA30 - 150 CD170 4.1 9.8 10.1 4.0 9.3 10.0
GA30 - 175 CD100 8.9 11.5 11.8 8.8 11.0 11.7
GA30 - 175 CD140 7.3 11.5 11.8 7.2 11.0 11.7
GA30 - 175 CD170 6.5 11.5 11.8 6.4 11.0 11.7
GA37 - 100 CD140 6.0 6.4 6.7 5.9 5.9 6.6
GA37 - 100 CD170 5.5 6.4 6.7 5.4 5.9 6.6
GA37 - 125 CD100 7.2 8.1 8.4 7.1 7.6 8.3
GA37 - 125 CD140 5.7 8.1 8.4 5.6 7.6 8.3
GA37 - 125 CD170 5.1 8.1 8.4 5.0 7.6 8.3
GA37 - 150 CD100 6.6 9.8 10.1 6.5 9.3 10.0
GA37 - 150 CD140 5.4 9.8 10.1 5.3 9.3 10.0
GA37 - 150 CD170 4.8 9.8 10.1 4.7 9.3 10.0
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 34
User manual
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA37 - 175 CD100 10.1 11.5 11.8 10.0 11.0 11.7
GA37 - 175 CD140 8.3 11.5 11.8 8.2 11.0 11.7
GA37 - 175 CD170 7.4 11.5 11.8 7.3 11.0 11.7
GA45 - 100 CD170 6.1 6.5 6.7 6.0 6.0 6.6
GA45 - 125 CD140 6.4 8.1 8.4 6.3 7.6 8.3
GA45 - 125 CD170 5.7 8.1 8.4 5.6 7.6 8.3
GA45 - 150 CD100 8.0 9.8 10.1 7.9 9.3 10.0
GA45 - 150 CD140 6.1 9.8 10.1 6.0 9.3 10.0
GA45 - 150 CD170 5.4 9.8 10.1 5.3 9.3 10.0
GA45 - 175 CD100 11.1 11.5 11.8 11.0 11.0 11.7
GA45 - 175 CD140 9.3 11.5 11.8 9.2 11.0 11.7
GA45 - 175 CD170 8.3 11.5 11.8 8.2 11.0 11.7
GA55C - 100 CD170 6.4 6.8 6.8 6.3 6.3 6.7
GA55C - 125 CD140 7.1 8.1 8.4 7.0 7.6 8.3
GA55C - 125 CD170 6.2 8.1 8.4 6.1 7.6 8.3
GA55C - 150 CD100 9.4 9.8 10.1 9.3 9.3 10.0
GA55C - 150 CD140 6.6 9.8 10.1 6.5 9.3 10.0
GA55C - 150 CD170 5.9 9.8 10.1 5.8 9.3 10.0
GA55C - 175 CD140 10.4 11.5 11.8 10.3 11.0 11.7
GA55C - 175 CD170 9.3 11.5 11.8 9.2 11.0 11.7
GA55 - 100 CD230 5.8 6.4 6.7 5.7 5.9 6.6
GA55 - 100 CD280 5.1 6.4 6.7 5.0 5.9 6.6
GA55 - 125 CD170 6.4 8.1 8.4 6.3 7.6 8.3
GA55 - 125 CD230 5.4 8.1 8.4 5.3 7.6 8.3
GA55 - 125 CD280 4.8 8.1 8.4 4.7 7.6 8.3
GA75 - 100 CD280 6.1 6.5 6.7 6.0 6.0 6.6
GA75 - 125 CD230 6.5 8.1 8.4 6.4 7.6 8.3
GA75 - 125 CD280 5.8 8.1 8.4 5.7 7.6 8.3
GA75 - 150 CD170 7.8 9.8 10.1 7.7 9.3 10.0
GA75 - 150 CD230 6.1 9.8 10.1 6.0 9.3 10.0
GA75 - 150 CD280 5.4 9.8 10.1 5.3 9.3 10.0
GA75 - 175 CD170 11.1 11.5 11.8 11.0 11.0 11.7
GA75 - 175 CD230 9.4 11.5 11.8 9.3 11.0 11.7
GA75 - 175 CD280 8.5 11.5 11.8 8.4 11.0 11.7
GA90C - 100 CD280 6.4 6.8 6.8 6.3 6.3 6.7
GA90C - 125 CD230 7.0 8.1 8.4 6.9 7.6 8.3
GA90C - 125 CD280 6.2 8.1 8.4 6.1 7.6 8.3
GA90C - 150 CD170 9.0 9.8 10.1 8.9 9.3 10.0
GA90C - 150 CD230 6.6 9.8 10.1 6.5 9.3 10.0
GA90C - 150 CD280 5.9 9.8 10.1 5.8 9.3 10.0
GA90C - 175 CD230 10.1 11.5 11.8 10.0 11.0 11.7
GA90C - 175 CD280 9.1 11.5 11.8 9.0 11.0 11.7
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
35
User manual
Dewpoint -70 variant 50Hz
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA30 - 7.5 CD140 6.1 6.5 6.8 6.0 6.0 6.7
GA30 - 7.5 CD170 5.5 6.5 6.8 5.4 6.0 6.7
GA30 - 8 CD140 6.0 7.0 7.3 5.9 6.5 7.2
GA30 - 8 CD170 5.3 7.0 7.3 5.2 6.5 7.2
GA30 - 10 CD100 6.7 9.0 9.3 6.6 8.5 9.2
GA30 - 10 CD140 5.5 9.0 9.3 5.4 8.5 9.2
GA30 - 10 CD170 4.9 9.0 9.3 4.8 8.5 9.2
GA30 - 13 CD100 9.9 12.0 12.3 9.8 11.5 12.2
GA30 - 13 CD140 8.1 12.0 12.3 8.0 11.5 12.2
GA30 - 13 CD170 7.2 12.0 12.3 7.1 11.5 12.2
GA37 - 7.5 CD170 6.1 6.5 6.8 6.0 6.0 6.7
GA37 - 8 CD140 6.8 7.2 7.3 6.7 6.7 7.2
GA37 - 8 CD170 6.0 7.0 7.3 5.9 6.5 7.2
GA37 - 10 CD100 8.6 9.0 9.3 8.5 8.5 9.2
GA37 - 10 CD140 6.3 9.0 9.3 6.2 8.5 9.2
GA37 - 10 CD170 5.6 9.0 9.3 5.5 8.5 9.2
GA37 - 13 CD100 11.0 12.0 12.3 10.9 11.5 12.2
GA37 - 13 CD140 9.1 12.0 12.3 9.0 11.5 12.2
GA37 - 13 CD170 8.1 12.0 12.3 8.0 11.5 12.2
GA45 - 8 CD170 6.4 7.0 7.3 6.3 6.5 7.2
GA45 - 10 CD140 7.4 9.0 9.3 7.3 8.5 9.2
GA45 - 10 CD170 6.4 9.0 9.3 6.3 8.5 9.2
GA45 - 13 CD140 10.4 12.0 12.3 10.3 11.5 12.2
GA45 - 13 CD170 9.3 12.0 12.3 9.2 11.5 12.2
GA55C - 10 CD170 7.1 9.0 9.3 7.0 8.5 9.2
GA55C - 13 CD140 11.6 12.0 12.3 11.5 11.5 12.2
GA55C - 13 CD170 10.4 12.0 12.3 10.3 11.5 12.2
GA55 - 7.5 CD280 5.9 6.5 6.8 5.8 6.0 6.7
GA55 - 8 CD230 6.4 7.0 7.3 6.3 6.5 7.2
GA55 - 8 CD280 5.7 7.0 7.3 5.6 6.5 7.2
GA55 - 10 CD170 7.4 9.0 9.3 7.3 8.5 9.2
GA55 - 10 CD230 6.0 9.0 9.3 5.9 8.5 9.2
GA55 - 10 CD280 5.3 9.0 9.3 5.2 8.5 9.2
GA75 - 8 CD280 6.9 7.3 7.3 6.8 6.8 7.2
GA75 - 10 CD230 7.4 9.0 9.3 7.3 8.5 9.2
GA75 - 10 CD280 6.4 9.0 9.3 6.3 8.5 9.2
GA75 - 13 CD230 10.6 12.0 12.3 10.5 11.5 12.2
GA75 - 13 CD280 9.5 12.0 12.3 9.4 11.5 12.2
GA90C - 10 CD230 8.5 9.0 9.3 8.4 8.5 9.2
GA90C - 10 CD280 6.8 9.0 9.3 6.7 8.5 9.2
GA90C - 13 CD230 11.3 12.0 12.3 11.2 11.5 12.2
GA90C - 13 CD280 10.1 12.0 12.3 10.0 11.5 12.2
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 36
User manual
Dewpoint -70 variant 60Hz
Combination UNLOADING LOADING
GA and ICD
GA Model ICD model Minimum Nominal Maximum Minimum Nominal Maximum
Unloading Unloading Unloading Loading Loading Loading
Pressure Pressure Pressure Pressure Pressure Pressure
bar bar bar bar bar bar
GA30 - 100 CD140 6.1 6.5 6.7 6.0 6.0 6.6
GA30 - 100 CD170 5.5 6.4 6.7 5.4 5.9 6.6
GA30 - 125 CD100 7.4 8.1 8.4 7.3 7.6 8.3
GA30 - 125 CD140 5.8 8.1 8.4 5.7 7.6 8.3
GA30 - 125 CD170 5.2 8.1 8.4 5.1 7.6 8.3
GA30 - 150 CD100 6.4 9.8 10.1 6.3 9.3 10.0
GA30 - 150 CD140 5.3 9.8 10.1 5.2 9.3 10.0
GA30 - 150 CD170 4.7 9.8 10.1 4.6 9.3 10.0
GA30 - 175 CD100 10.0 11.5 11.8 9.9 11.0 11.7
GA30 - 175 CD140 8.3 11.5 11.8 8.2 11.0 11.7
GA30 - 175 CD170 7.4 11.5 11.8 7.3 11.0 11.7
GA37 - 100 CD170 6.2 6.6 6.7 6.1 6.1 6.6
GA37 - 125 CD140 6.6 8.1 8.4 6.5 7.6 8.3
GA37 - 125 CD170 5.8 8.1 8.4 5.7 7.6 8.3
GA37 - 150 CD100 8.2 9.8 10.1 8.1 9.3 10.0
GA37 - 150 CD140 6.1 9.8 10.1 6.0 9.3 10.0
GA37 - 150 CD170 5.5 9.8 10.1 5.4 9.3 10.0
GA37 - 175 CD100 11.4 11.8 11.8 11.3 11.3 11.7
GA37 - 175 CD140 9.4 11.5 11.8 9.3 11.0 11.7
GA37 - 175 CD170 8.4 11.5 11.8 8.3 11.0 11.7
GA45 - 125 CD140 7.8 8.2 8.4 7.7 7.7 8.3
GA45 - 125 CD170 6.6 8.1 8.4 6.5 7.6 8.3
GA45 - 150 CD140 7.0 9.8 10.1 6.9 9.3 10.0
GA45 - 150 CD170 6.2 9.8 10.1 6.1 9.3 10.0
GA45 - 175 CD140 10.5 11.5 11.8 10.4 11.0 11.7
GA45 - 175 CD170 9.4 11.5 11.8 9.3 11.0 11.7
GA55C - 125 CD170 7.3 8.1 8.4 7.2 7.6 8.3
GA55C - 150 CD140 8.3 9.8 10.1 8.2 9.3 10.0
GA55C - 150 CD170 6.7 9.8 10.1 6.6 9.3 10.0
GA55C - 175 CD170 10.6 11.5 11.8 10.5 11.0 11.7
GA55 - 100 CD280 5.9 6.4 6.7 5.8 5.9 6.6
GA55 - 125 CD170 7.8 8.2 8.4 7.7 7.7 8.3
GA55 - 125 CD230 6.1 8.1 8.4 6.0 7.6 8.3
GA55 - 125 CD280 5.5 8.1 8.4 5.4 7.6 8.3
GA75 - 125 CD230 7.9 8.3 8.4 7.8 7.8 8.3
GA75 - 125 CD280 6.6 8.1 8.4 6.5 7.6 8.3
GA75 - 150 CD230 7.1 9.8 10.1 7.0 9.3 10.0
GA75 - 150 CD280 6.2 9.8 10.1 6.1 9.3 10.0
GA75 - 175 CD230 10.7 11.5 11.8 10.6 11.0 11.7
GA75 - 175 CD280 9.6 11.5 11.8 9.5 11.0 11.7
GA90C - 125 CD280 7.2 8.1 8.4 7.1 7.6 8.3
GA90C - 150 CD230 8.2 9.8 10.1 8.1 9.3 10.0
GA90C - 150 CD280 6.7 9.8 10.1 6.6 9.3 10.0
GA90C - 175 CD230 11.4 11.8 11.8 11.3 11.3 11.7
GA90C - 175 CD280 10.3 11.5 11.8 10.2 11.0 11.7
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
37
User manual
17.2 Protections
Minimum Nominal Maximum
Compressor element outlet temperature 4) . . . . . . . Celsius 9) 110 119
(shut-down warning level)
Compressor element outlet temperature 4) . . . . . . . Celsius 111 120 120
(shut-down level)
For GA30 up to GA90C
Oil separator (pressure difference) . . . . . . . . . . . . . . bar 0 1 5)
Oil separator (delay at signal) 6) . . . . . . . . . . . . . . . sec 0 10 20
For Full-feature with IFD also 11):
Delay at signal 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 3 10
Delay at starting 8) . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 255 255
On water-cooled compressors also:
Cooling water inlet temperature (warning level) . . . Celsius 0 50 99
Cooling water outlet temperature (warning level) . . Celsius 0 60 99
Delay at warning signal 6) . . . . . . . . . . . . . . . . . . . . sec 0 0 255
Delay at start 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 0 255
For Full-feature with ICD also:
Minimum dryer vessel pressure when drying
(warning level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0 3.5 4
Delay at signal 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 5 10
Maximum dryer vessel pressure when regenerating
(warning level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . bar 0.5 0.7 1
Delay at signal 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 30 40
Maximum pressure dewpoint (warning level) . . . . . C -45 -30 0
Delay at signal 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 3 10
Delay at starting 8) . . . . . . . . . . . . . . . . . . . . . . . . . . sec 0 0 255
17.3 Service plan
Minimum Nominal Maximum
Service plan A (running hours) . . . . . . . . . . . . . . . . . hr 10) 4000 10)
Service plan B (running hours) . . . . . . . . . . . . . . . . hr 10) 4000 10)
Service plan C (running hours) . . . . . . . . . . . . . . . . hr 10) 8000 10)
Footnotes chapter 17
1) Once the compressor is automatically stopped, it will remain stopped for the minimum stop time, whatever happens with the air net pressure. It is
recommended to program this setting at minimum 20 seconds to prevent too-short stopping periods. If a lower setting should be required, consult Atlas
Copco.
2) Is the period after starting which must expire before generating a warning. This setting should be less than the setting for delay at signal.
3) The regulator does not accept illogical settings, e.g. if the unloading pressure is programmed at 7.0 bar(e), the maximum limit for the loading pressure
changes into 6.9 bar(e). The recommended minimum pressure difference between loading and unloading is 0.6 bar.
4) The regulator does not accept illogical settings, e.g. if the warning level is programmed at 95 degrees Celsius, the minimum limit for the shut-down level
changes into 96 degrees Celsius. The recommended difference between the warning level and shut-down level is 10 degrees Celsius.
5) Use Atlas Copco oil separators. The recommended maximum pressure difference is 1 bar.
6) Is the time period during which the warning signal must exist before the warning message appears.
7) In case of LAN control. See related Instruction book, section 3.2. Consult Atlas Copco.
8) Is the time period during which the warning signal is ignored after starting to allow the dryer to reach the dewpoint temperature.
9) Recommended minimum setting: 70 degrees Celsius. For testing the temperature sensor, this setting can be decreased to 50 degrees Celsius. Reset the
setting value after testing.
10) Always consult Atlas Copco in case any timer setting should be changed. The intervals must not exceed the nominal intervals and must coincide
logically. See section 12.
11) Full-feature (FF): with integrated air dryer.
12) See section 1.3.
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 38
User manual
Notes:
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03
39
User manual
Notes:
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
Downloaded from www.Manualslib.com manuals search engine
2920 1461 03 40
User manual
Notes:
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
..........................................................................................................................................................................................................
Downloaded from www.Manualslib.com manuals search engine
14. If the ground is not level or can be subject to variable inclination,
consult Atlas Copco.
15. The electrical connections shall correspond to the local codes. The
units shall be grounded and protected against short circuits by fuses.
Operation
1. Air hoses shall be of correct size and suitable for the working pressure.
Never use frayed, damaged or deteriorated hoses. Use only the correct
type and size of hose end fittings and connections. When blowing
through a hose or air line, ensure that the open end is held securely.
A free end will whip and may cause injury. Make sure that a hose is
fully depressurized before disconnecting it.
Never play with compressed air. Do not apply it to your skin or
direct an air stream at people. Never use it to clean dirt from your
clothes. When using it to clean equipment, do so with extreme caution
and use eye protection.
2. The compressor is not considered as capable of producing air of
breathing quality. For breathing air quality, the compressed air must
be adequately purified according to local legislation and standards.
3. Never operate the units when there is a possibility of taking in
flammable or toxic fumes.
4. Never operate the units at pressures below or in excess of their limit
ratings as indicated on the Principal Data sheet.
5. Keep all bodywork doors shut during operation. The doors may be
opened for short periods only, e.g. to carry out checks. Wear ear
protectors when opening a door.
6. People staying in environments or rooms where the sound pressure
level reaches or exceeds 90 dB(A) shall wear ear protectors.
7. Periodically check that:
a. All guards are in place and securely fastened
b. All hoses and/or pipes inside the unit are in good condition, secure
and not rubbing
c. There are no leaks
d. All fasteners are tight
e. All electrical leads are secure and in good order
f. Safety valves and other pressure-relief devices are not obstructed
by dirt or paint
g. Air outlet valve and air net, i.e. pipes, couplings, manifolds,
valves, hoses, etc. are in good repair, free of wear or abuse
8. If warm cooling air from compressors is used in air heating systems,
e.g. to warm up a workroom, take precautions against air pollution
and possible contamination of the breathing air.
9. Do not remove any of, or tamper with, the sound-damping material.
Maintenance
Maintenance and repair work shall only be carried out under supervision
of someone qualified for the job.
1. Use only the correct tools for maintenance and repair work.
2. Use only genuine spare parts.
3. All maintenance work, other than routine attention, shall only be
undertaken when the unit is stopped, the main power supply is
switched off and the machine has cooled down. Take positive
precaution to ensure that the unit cannot be started inadvertently.
In addition, a warning sign bearing a legend such as "work in
progress; do not start" shall be attached to the starting equipment.
4. Before removing any pressurized component, effectively isolate the
unit from all sources of pressure and relieve the entire system of
pressure.
5. Never use flammable solvents or carbon tetrachloride for cleaning
parts. Take safety precautions against toxic vapours of cleaning
liquids.
6. Scrupulously observe cleanliness during maintenance and repair.
Keep dirt away by covering the parts and exposed openings with a
clean cloth, paper or tape.
7. Never weld or perform any operation involving heat near the oil
system. Oil tanks must be completely purged, e.g. by steam-cleaning,
before carrying out such operations.
Never weld on, or in any way modify, pressure vessels.
Whenever there is an indication or any suspicion that an internal
part of a machine is overheated, the machine shall be stopped but no
inspection covers shall be opened before sufficient cooling time
has elapsed; this to avoid the risk of spontaneous ignition of the oil
vapour when air is admitted.
Never use a light source with open flame for inspecting the interior
of a machine, pressure vessel, etc.
8. Make sure that no tools, loose parts or rags are left in or on the unit.
9. Before clearing the unit for use after maintenance or overhaul, check
that operating pressures, temperatures and time settings are correct
and that the control and shut-down devices function correctly. If
removed, check that the coupling guard of the compressor drive shaft
has been reinstalled.
10. Every time the separator element is renewed, examine the discharge
pipe and the inside of the oil separator vessel for carbon deposits; if
excessive, the deposits should be removed.
11. Protect the motor, air filter, electrical and regulating components,
etc. to prevent moisture from entering them, e.g. when steam-cleaning.
12. Make sure that all sound-damping material, e.g. on the bodywork
and in the air inlet and outlet systems of the compressor, is in good
condition. If damaged, replace it by genuine Atlas Copco material
to prevent the sound pressure level from increasing.
13. Never use caustic solvents which can damage materials of the air
net, e.g. polycarbonate bowls.
14. The following safety precautions are stressed when handling
refrigerant:
a. Never inhale refrigerant vapours. Check that the working area
is adequately ventilated; if required, use breathing protection.
b. Always wear special gloves. In case of refrigerant contact with
the skin, rinse the skin with water. If liquid refrigerant contacts
the skin through clothing, never tear off or remove the latter;
flush abundantly with fresh water over the clothing until all
refrigerant is flushed away; then seek medical first aid.
c. Always wear safety glasses.
15. Protect hands to avoid injury from hot machine parts, e.g. during
draining of oil.
Note: With stationary machine units driven by an internal combustion
engine, allowance has to be made for extra safety precautions, e.g. spark
arrestors, fuelling care, etc. Consult Atlas Copco.
All responsibility for any damage or injury resulting from neglecting
these precautions, or by non-observance of ordinary caution and due
care required in handling, operating, maintenance or repair, even if
not expressly mentioned in this book, will be disclaimed by Atlas
Copco.
SAFETY PRECAUTIONS (continued)
2920 1377 03 2/2
Downloaded from www.Manualslib.com manuals search engine
N
o
.

2
9
2
0

1
4
6
1

0
3

/

D
C
2
0
0
3
-
0
9
What sets Atlas Copco apart as a company is our
conviction that we can only excel in what we do if we
provide the best possible know-how and technology to
really help our customers produce, grow and succeed.
There is a unique way of achieving that - we simply
call it the Atlas Copco way. It builds on interaction, on
long-term relationships and involvement in the customers
process, needs and objectives. It means having the
flexibility to adapt to the diverse demands of the people
we cater for.
Its the commitment to our customers business that
drives our effort towards increasing their productivity
through better solutions. It starts with fully supporting
existing products and continuously doing things better, but
it goes much further, creating advances in technology
through innovation. Not for the sake of technology, but
for the sake of our customers bottom line and peace-of-
mind.
That is how Atlas Copco will strive to remain the first
choice, to succeed in attracting new business and to
maintain our position as the industry leader.
*2920146103*
Downloaded from www.Manualslib.com manuals search engine

You might also like