You are on page 1of 23

FIREBARRIER

SISTEMAS CORTA FUEGOS


FIREBARRIER
SILICONE SL
INTUMESCENT SEALANT INSERTS OR PUTTY PADS
FOR ELECTRICAL BOXES
MORTAR
CPVC/PVC/ABS PLASTIC PIPE
STEEL, IRON & COPPER METALLIC PIPE
MINERAL WOOL MINERAL WOOL SILICONE
ACRYLIC SEALANT OR
INTUMESCENT SEALANT
SPRAYACRYLIC
SPRAYACRYLIC COLLAR
FIRESTOP SYSTEMS
FIREBARRIER
Silicone & Silicone SL
Forms a durable, flexible,
water-tight bond
May be applied over a wide
temperature range, -18C
to 50C (0F to 120F)
Physical properties will
remain stable over time
Will not crack or crumble
Tools easily
SL = self-levels - no
tooling required
Neutral cure - low odour
Underside of floor
applications tested
Colours
Silicone: Red or Grey
Silicone SL: Red
Plumbing
Pipes, insulated pipes,
glass, copper, steel, iron
and combustible (plastic)
pipes
Electrical
Conduits, cables, cable
trays, bundled cables
Ducts
Steel ducts
Joint Systems
Horizontal and vertical
(horizontal only for SL)
Joints - Movement Capable
UL 2079 tested
Cartridges
10.3 fl.oz. (304 mL)
28.7 fl.oz. (850 mL)
Containers
2.64 US gal (10 L) pails
4.5 US gal (17 L) pails
Foil pack
20 fl oz (600 mL)
ULI, ULC, cUL, ITS (WH), FM
Intumescent
Sealant
Water based, intumescent
Economical
Forms a durable,
water-tight bond
Physical properties remain
stable over time
During a fire expands to
fill opening where
combustible piping was
located
Tools easily
Low odour
Ideal for caulk and walk
systems
Colour: Red
Plumbing
Copper, steel, iron
insulated, and combustible
(plastic) pipes
Ducts
Steel ducts
Electrical
Cables, cable trays,
bundled cables and
electrical conduits
Cartridges
10.1 fl.oz. (300 mL)
28.7 fl.oz. (850 mL)
Containers
5 US gal (18.9 L) pails
Foil Pack
20.3 fl.oz. (600 mL)
ULI, cUL
Acrylic Sealant
Water based
Economical
Forms a durable, flexible
water-tight bond
Applied by caulking or
trowel
Physical properties remain
stable over time
Colour: Red
Plumbing
Pipes, insulated pipes,
copper, steel, and
combustible (plastic) pipes
Electrical
Conduits, cables, cable
trays
Joint Systems
Horizontal and vertical
Joints - Movement Capable
UL 2079 tested
Cartridges
10.1 fl.oz. (300 mL)
28.7 fl.oz. (850 mL)
Containers
5 US gal (18.9 L) pails
Foil Pack
20.3 fl.oz. (600 mL)
ULI, cUL
P
R
O
D
U
C
T
S
F
E
A
T
U
R
E
S
U
S
A
G
E
S
I
Z
E
S
L
I
S
T
E
D
/
C
E
R
T
I
F
I
E
D
FIRESTOP SYSTEMS
A/D FIREBARRIER Silicone, Silicone SL,
Seal, Seal NS, Intumescent Caulk or Putty
A/D FIREBARRIER Seal, Seal NS,
SprayMastic, Silicone or Silicone SL
A/D Fire Protection Systems
ofrece un sistema completo
de productos requeridos
para sellos corta fuego.
Todos son certificados por
laboratorios independientes
y probados para asegurar
clasificaciones de proteccin
contra fuego en
penetraciones y aberturas en
pisos y paredes con
clasificaciones contra fuego.
A/D FIREBARRIER son
productos listados por
Underwriter Laboratories,
Intertek Testing Services
(Warnock Hersey), y Factory
Mutual, y son certificados
bajo rigurosos programas de
inspecciones a la fbrica.
Seal & Seal NS
Water based
Economical
Forms a durable,
water-tight bond
Seal may be poured,
pumped or sprayed
Underside of floor
applications tested
Physical properties remain
stable over time
Colours
Seal: Blue
Seal NS: White (may be
tinted in the field), and Red
Plumbing
Pipes, insulated pipes,
glass, copper, steel, and
CPVC
Electrical
Conduits, cables, cable
trays
Joint Systems
Horizontal and vertical
Joints - Movement Capable
UL 2079 tested
Cartridges
(Seal NS only)
10.3 fl.oz. (304 mL)
28.7 fl.oz. (850 mL)
Containers
(Seal & Seal NS)
5 US gal (19 L) pails
ULI, ULC, cUL, ITS (WH), FM
SprayAcrylic
Water based elastomeric
Economical
Forms a durable, water
tight bond
Physical properties will
remain stable over time
May be sprayed or
trowelled
Curtain wall / floor joints
tested
Colour: Red
Joint Systems
Horizontal and vertical,
curtain wall, head-of-wall,
perimeter and floor to wall
Joints - Movement Capable
UL 2079 tested
Containers
5 US gal (18.9 L) pails
ULI, cUL
Mortar
Foamed cement
Single component
Easy to use
Economical
Mixes easily with water to
form a lightweight
non-slumping paste that is
easy to place and tool
Self-supporting
Tested for very large
openings
Non-combustible
Colour: Grey
Plumbing
Glass, copper, steel, iron,
insulated pipes and multi-
ple penetrations
Electrical
Conduits, cables, cable
trays, multiple penetrations
Ducts
Steel ducts
Large openings
Containers
15.5 lb (7 kg) bags
ULI, ULC, cUL, ITS (WH), FM
Mineral Wool
Non-combustible
Pre-cut strips facilitate
easy installation and
provide a smooth surface
to help control depth of
sealant that is applied
High quality, proprietary
insulation blankets/strips
UL and ULC listed and
certified
General
A/D FIREBARRIER Mineral
Wool is the recommended
and/or required backing for
A/D FIREBARRIER sealants
in most firestop
applications
Packaged 25 lb (11 kg)
nominal in plastic bags in
various pre-cut x 4 ft strips
or blankets
ULI, ULC, ITS (WH), FM
A/D FIREBARRIER Intumescent Sealant
A/D FIREBARRIER Acrylic Sealant
A/D FIREBARRIER Silicone & Silicone SL
A/D FIREBARRIER SprayAcrylic
A/D FIREBARRIER Seal & Seal NS
A/D FIREBARRIER Mineral Wool
Pillows
Quick and clean single
product installation
No mesh or lath required
No sealant or putty
required
Ideal for cable retrofitting
Easy to install, remove or
replace
Electrical
Cables, cable trays,
bundled cables
General
Blank or temporary
openings
2 x 4 x 8 in.
(50 x 100 x 200 mm)
packaged 25 per box
ULI, ULC, cUL
Collars, Wrap Strip &
Collar Strips
Easy to install with
common tools
Collars - Convenient, ready
to install 3, 4 and 6-in.
nominal trade sizes
Wrap Strip - For use with
or without steel Collar Strip
Intumescent feature closes
off and seals plastic pipes
and pipe insulation
Passes 50 Pa test
requirement in Canada
(refer to test designs)
Plumbing
Combustible (plastic) pipes
and insulated pipes
through concrete or
gypsum wallboard, vertical
and horizontal
Collars
Nominal 3, 4 and
6 in. trade sizes
Wrap Strip
1 or 2 in. wide x 1/4 in.
thick x 12 ft strips
Collar Strip
50 ft coil
ULI, ULC, cUL
Putty
Easy to install
Single component
Intumescent
No mixing
Remains soft and pliable
Plumbing
Pipes through concrete
walls and floors
Electrical
Cables and conduits
through gypsum wallboard.
Sticks
66.2 in
3
(1085 mL)
packaged 12 per carton
ULI, cUL
Putty Pads & Inserts
Used to maintain hourly
fire resistance ratings of
fire resistive walls and
partitions containing
electrical boxes
Permit greater density of
outlet and switch boxes in
rated walls than would
otherwise be permitted by
codes for unprotected
boxes
Intumescent materials
expand when exposed to
fire to seal off the box
Single component
Easy to install
Electrical
Protect electrical outlet and
switch boxes
Inserts
2 x 4 in. or 4 x 4 in.
packaged 50 per carton
Putty Pads
6 x 7 x .2 in. &
9.25 x 9.25 x .2 in.
packaged 12 per carton
ULI, cUL
A/D FIREBARRIER Mortar
A/D FIREBARRIER Pillows
A/D FIREBARRIER Putty Pads & Inserts
A/D FIREBARRIER Putty
A/D FIREBARRIER Collars
A/D FIREBARRIER Wrap Strip & Collar Strips
FIREBARRIER INTUMESCENT SEALANT

1. PRODUCT NAME
A/D FIREBARRIER Intumescent
Sealant.
2. PRODUCT DESCRIPTION
Basic Use: A/D FIREBARRIER
Intumescent Sealant is a single
component intumescent acrylic
water based sealant intended for
use as a firestop system
component.
Composition and Materials:
A/D FIREBARRIER Intumescent
Sealant forms a durable, flexible,
watertight bond with most
construction materials. It is applied
independently for caulk and walk
systems or over mineral wool or
backer rod (refer to test design
details) to seal the openings where
building services such as pipes and
cables penetrate fire rated
assemblies. May be applied by
caulking gun or trowel. Clean up is
with water.
A/D FIREBARRIER Intumescent
Sealant contains water and is best if
protected from freezing.
Packaging: See table 2. Refer to
the A/D FIREBARRIER estimating
guide for complete volume and
coverage information.
Color: Red
Application Limitations:
A/D FIREBARRIER Intumescent
Sealant is intended for use at
interior locations in buildings only.
Protect from direct contact with
water until cured. Curing time will
vary with temperature and humidity.
Do not use where abrasion or
physical abuse is anticipated.
Installation in confined or air-free
spaces may inhibit cure.
Do not apply to surfaces with
special protective or cosmetic
coatings without prior consul-
tation with the manufacturer and
first testing adhesion.
A/D FIREBARRIER Intumescent
Sealant has been tested in
numerous firestop configurations.
For optimum economy and
performance, apply to a
thickness equal to or slightly
greater than the minimum test
design thickness. Excessive
depth to width ratios may cause
sealant failure DO NOT apply
excessive thickness. As a
guideline, A/D Fire Protection
Systems recommends the
minimum tested system thick-
nesses not be exceeded by more
than 25%.
3. TECHNICAL DATA
Physical Properties:
Refer to Table 1.
Standards: A/D FIREBARRIER
Intumescent Sealant has been
tested in accordance with the
following: ANSI/UL1479, ASTM
E814 and CAN4/ULC-S115M.
Systems certified for use in Canada
are available under the cUL mark.
FGG/BM/CZ System Compatible
indicates that this product has been
tested, and is monitored on an
ongoing basis, to assure its
chemical compatibility with
FlowGuard Gold, BlazeMaster
and Corzan pipe and fittings.
FGG/BM/CZ, FlowGuard Gold,
BlazeMaster, and Corzan are
licensed trademarks of the Lubrizol
Corporation.
Contact A/D Fire Protection
Systems for a current list of fire
rated systems.
4. INSTALLATION
Clean all openings to be firestopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, surface dirt, old
sealants glazing compound,
protective coatings, etc. Refer to fire
test design / system.
Priming: A/D FIREBARRIER
Intumescent Sealant does not
require any priming. In view of the
unpredictability of surface
characteristics, it is recommended
that a test sample of sealant be
applied on the surface to test
adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch the
clean surfaces to which the caulk is
to adhere. Remove masking tape
immediately.
Applications: For caulk and walk
systems, simply apply the product
where required and let cure.
Where backer material (mineral
wool, backer rod, etc.) is required by
fire test design or system, install
backer material as specified.
Surfaces of backer material to
receive caulk should be recessed in
the opening to a depth equal to the
required thickness of sealant.
Table 1
PHYSICAL PROPERTIES*

Properties Results
Color Red
Odor Mild
pH 7.0 - 10.0
VOC (grams/liter) 0
Flame Spread (ASTM E-84) 0
Smoke Developed (ASTM E-84) 0
Cure Time (ASTM C-679) 3 - 5 days
Skin over Time Overnight
Shore A Hardness (ASTM C-661) 15 - 20
Application Temperature 40 - 110F (5 - 43C)
Freeze Sensitive Yes
Paintable Yes

*Values given are not intended for specification preparation.
Where mineral wool is required
backer material, we recommend the
use of A/D FIREBARRIER Mineral
Wool this high quality material is
available pre-cut for easy installation
and allows a controlled depth of
caulk to be applied for maximum
economy. Apply A/D FIREBARRIER
Intumescent Sealant in a continuous
operation to fill and seal the
opening. Tool the sealant to spread
it against the backer material and
the opening surfaces.
Simply fill the annular space to the
required depth and form a smooth
bead or crown at the surfaces.
Excess sealant should be cleaned
with water.
CURED SEALANT IS USUALLY
VERY DIFFICULT TO REMOVE
WITHOUT ALTERING OR
DAMAGING THE SURFACE TO
WHICH THE SEALANT HAS BEEN
MISAPPLIED.
Precaution: On direct contact,
uncured sealant may irritate eyes.
Flush with water and call a
physician. Avoid prolonged contact
with skin. Keep out of reach of
children.
To safely use this product, read and
abide by Material Safety Data Sheet
(MSDS).
Shelf Life: A/D FIREBARRIER
Intumescent Sealant has shelf life of
one year from the date of
manufacture when stored in original
and unopened container at or below
110F (43C) and above 40F (5C).
See top of box or label on pail for
date of manufacture (day/ month/
year).
5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below)
6. MAINTENANCE
No maintenance should be required.
If intumescent sealant becomes
damaged, replace damaged portion.
Clean surfaces in damaged areas,
and repair with fresh A/D
FIREBARRIER Intumescent
Sealant.
7. TECHNICAL SERVICES
Contact nearest A/D representative.










March 10, 2008
Table 2
Type of
Packaging
Size Volume
Coverage at
deep x
1 wide
10.1 fl. oz.
(300 mL)
18.2 in
3

(300 cm
3
)
6.1 lineal ft.
(1.86 lineal m)
Cartridges
28.7 fl. oz.
(850 mL)
51.8 in
3

(850 cm
3
)
17.3 lineal ft.
(5.27 lineal m)

Foil packs
20 fl. oz.
(600 mL)
36 in
3

(600 cm
3
)
12.2 lineal ft.
(3.72 lineal m)

Pails
5 gal
(18.9 L)
1155 in
3

(18900 cm
3
)
384.4 lineal ft.
(117.18 lineal m)
FIREBARRIER INTUMESCENT CAULK

1. PRODUCT NAME
A/D FIREBARRIER Intumescent
Caulk.
2. PRODUCT DESCRIPTION
Basic Use: A/D FIREBARRIER
Intumescent Caulk is a water
based, single component
elastomeric sealant intended for
use as a firestop system
component.
Composition and Materials:
A/D FIREBARRIER Intumescent
Caulk forms a durable, flexible,
watertight bond with most
construction materials. It is applied
independently for caulk and walk
systems or over mineral wool or
backer rod (refer to test design
details) to seal the openings where
building services such as pipes and
cables penetrate fire rated
assemblies. May be applied by
caulking gun or trowel. Clean up is
with water.
A/D FIREBARRIER Intumescent
Caulk contains water and is best if
protected from freezing. If frozen,
thaw completely before use
Packaging: A/D FIREBARRIER
Intumescent Caulk is available in
10.3 fl. oz (304 ml) cartridges, 20 fl.
oz (600 ml) foil packs and nominal
4.5 gal (17 L) plastic pails. Contents
are 18.6 in
3
, 36.1 in
3
and 1050 in
3

respectively. Refer to the A/D
FIREBARRIER estimate guide for
volume and coverage information.
Color: Red
Application Limitations:
A/D FIREBARRIER Intumescent
Caulk is intended for use at interior
locations in buildings only. Protect
from direct contact with water until
cured. Curing time will vary with
temperature and humidity.
Do not use where abrasion or
physical abuse is anticipated.
Installation in confined or air-free
spaces may inhibit cure.
Do not apply to surfaces with
special protective or cosmetic
coatings without prior consul-
tation with the manufacturer and
first testing adhesion.
A/D FIREBARRIER Intumescent
Caulk has been tested in
numerous firestop configurations.
For optimum economy and
performance, apply to a
thickness equal to or slightly
greater than the minimum test
design thickness. Excessive
depth to width ratios may cause
sealant failure DO NOT apply
excessive thickness. As a
guideline, A/D Fire Protection
Systems recommends the
minimum tested system thick-
nesses not be exceeded by more
than 25%.
3. TECHNICAL DATA
Physical Properties:
Refer to Table 1.
Fire Resistance Ratings: A/D
FIREBARRIER Intumescent Caulk
has been tested and certified by ULI
and ULC in accordance with ULC-
S115, ASTM E814 and
ANSI/UL1479. The following tested
firestop systems were published at
the time of this writing:
ULI System Nos: C-AJ-1343,
-1344, -1345, -1365, -1492,
-1493, -2464, -5260, -7042
WL-1225, 1235, 1236
F-C-1086, -2195, -2206, -3061
and -5051.
ULC Systems Nos: SP961,
-962, -964, -965, -966, -967,
-968, -969, -984, -989, -1001,
-1002, -1003, -1076, -1077,
-1078 and 1079, SPC53, -58,
-98, -99 and -100.
Contact A/D Fire Protection
Systems for a current list of fire
rated systems.
4. INSTALLATION
Clean all openings to be firestopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, surface dirt, old
sealants glazing compound,
protective coatings, etc. Refer to fire
test design / system.
Priming: A/D FIREBARRIER
Intumescent Caulk does not require
any priming. In view of the
unpredictability of surface
characteristics, it is recommended
that a test sample of sealant be
applied on the surface to test
adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
PHYSICAL PROPERTIES*

Properties Results
Color Red
Odor Mild

Uncured
Flow rate (ASTM C920) 175 mL/min
Volatile by Volume 35.7%
Tack Free Time 30 min. (@ 70F (21C) 50% RH)
Specific Gravity 1.25
VOC (ASTM D 3960-92) 0.14 lb/gal US (16 g/L)
Cured
Flow, Sag or Slump 0
Hardness (A) (ASTM D2240) 35-40
Elongation at Break (ASTM D412) 85%
Tensile Strength (ASTM D412) 145 psi
Effects of Accelerated Weathering
UV Exposure (ASTM C920) No Cracking
Cold Temperature (ASTM C920) No Cracking
*Values given are not intended for specification preparation.

May 2004
appearance. The masking tape
should not be allowed to touch the
clean surfaces to which the caulk is
to adhere. Remove masking tape
immediately.
Applications: For caulk and walk
systems, simply apply the product
where required and let cure.
Where backer material (mineral
wool, backer rod, etc.) is required by
fire test design or system, install
backer material as specified.
Surfaces of backer material to
receive caulk should be recessed in
the opening to a depth equal to the
required thickness of sealant.
Where mineral wool is required
backer material, we recommend the
use of A/D FIREBARRIER Mineral
Wool this high quality material is
available pre-cut for easy installation
and allows a controlled depth of
caulk to be applied for maximum
economy. Apply A/D FIREBARRIER
Intumescent Caulk in a continuous
operation to fill and seal the
opening. Tool the caulk to spread it
against the backer material and the
opening surfaces.
Simply fill the annular space to the
required depth and form a smooth
bead or crown at the surfaces.
Excess sealant should be cleaned
with water.
CURED SEALANT IS USUALLY
VERY DIFFICULT TO REMOVE
WITHOUT ALTERING OR
DAMAGING THE SURFACE TO
WHICH THE SEALANT HAS BEEN
MISAPPLIED.
Precaution: A/D FIREBARRIER
Intumescent Caulk is a water-based
product. No acetic acid or
objectionable byproducts are
evolved during application. On
direct contact, uncured caulk may
irritate eyes. Flush with water and
call a physician. Avoid prolonged
contact with skin. Keep out of
reach of children.
To safely use this product, read and
abide by Material Safety Data Sheet
(MSDS).
Shelf Life: A/D FIREBARRIER
Intumescent Caulk has shelf life of
one year from the date of
manufacture when stored in original
and unopened container at or below
90F (32C) and above 32F (0C).
See top of box or label on pail for
date of manufacture (day/ month/
year).
5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below)
6. MAINTENANCE
No maintenance should be required.
If intumescent caulk becomes
damaged, replace damaged portion.
Clean surfaces in damaged areas,
and repair with fresh A/D
FIREBARRIER Intumescent Caulk.
7. TECHNICAL SERVICES
Contact nearest A/D representative.












FIREBARRIER ACRYLIC SEALANT

1. PRODUCT NAME
A/D FIREBARRIER Acrylic Sealant
2. PRODUCT DESCRIPTION
A/D FIREBARRIER Acrylic Sealant
is a single component, water-based
acrylic sealant intended for use as a
firestop system component.
Basic Use: A/D FIREBARRIER
Acrylic Sealant is designed for
economical use in joint and service
penetration firestop configurations.
It forms a durable, flexible,
watertight bond with most
construction materials. In most
cases, no primer is required. May
be applied by caulking gun or
trowel. Physical properties will
remain stable over time.
Composition and Materials:
A/D FIREBARRIER Acrylic Sealant
is designed to tool easily. It is water
based and must be protected from
freezing and from water until fully
cured. Store and install at
temperatures above 40F (5C).
Color: Red
Packaging: See table 2. Refer to
the A/D FIREBARRIER estimating
guide for complete volume and
coverage information.
Application Limitations:
Do not install when ambient
temperature or temperature of
substrate is below 40F (5C).
Protect from freezing and water
until sealant is fully cured.
Do not install to surfaces with
special protective or cosmetic
coatings without prior consul-
tation with manufacturer and
first testing adhesion.
Do not install where abrasion or
physical abuse is anticipated.
For best economy and
performance the product should
be applied to a thickness equal
to or slightly greater than the
minimum test design thickness.
Excessive depth to width ratios
may cause sealant failure do
not apply excessive thick-
ness. As a guideline, we
recommend that the minimum
test system thicknesses not be
exceeded by more than 25%.
Standards: A/D FIREBARRIER
Acrylic Sealant has been tested in
accordance with the following:
ANSI/UL1479, ANSI/UL 2079,
ASTM E814 and CAN/ULC-S115M.
3. TECHNICAL DATA
A/D FIREBARRIER Acrylic Sealant
is listed by ULI. For details of rated
firestop systems see ULI s Fire
Resistance Directory, Volume 2.
Systems certified for use in Canada
are available under the cUL mark.
4. INSTALLATION
Clean all openings to be firestopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, surface dirt, old
sealants, glazing compounds,
protective coatings etc. Cleaning of
all surfaces should be done on the
same day in which the sealant is
applied.
Priming: A/D FIREBARRIER
Acrylic Sealant does not require
priming. In view of the
unpredictability of surface
characteristics, it is recommended
that a test sample of sealant be
applied on the surface to test
adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch the
clean surface to which the sealant is
to adhere. Remove masking tape
immediately.
Install backup materials as
specified. Excess sealant should be
wiped from glass, metal and plastic
surfaces while uncured. Clean up is
with water.
CURED SEALANT IS USUALLY
VERY DIFFICULT TO REMOVE
WITHOUT ALTERING OR DAM-
AGING THE SURFACE TO WHICH
THE SEALANT HAS BEEN
APPLIED.
Precaution: May cause irritation.
May be harmful if swallowed. Avoid
getting in eyes. Wash hands
thoroughly after handling. Use only
as directed.
Keep out of reach of children.
To safely use this product, read and
abide by Material Safety Data Sheet
(MSDS).
Shelf Life: When stored at or below
110F (43C) and above 40F (5C),
A/D FIREBARRIER Acrylic Sealant
has a shelf life of one year from
date of manufacture.
Note: Protect from freezing.






Table 1 PHYSICAL PROPERTIES*
Color Red
pH 7.0 - 9.0
VOC (grams/liter): 65
Flame Spread (ASTM E84) 15
Smoke Developed (ASTM E84) 0
Cure Time 3 - 5 days
Skin over Time Overnight
Movement Capability: (UL 2079; class I, II, III) + 25 %, maximum
Shore A Hardness (ASTM C-661) 15 - 20
Application Temperature 40 - 110F (5 - 43C)
Freeze Sensitive Yes
Paintable Yes
*Values given above are not intended for specification preparation.


5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below)
6. MAINTENANCE
No maintenance should be required.
If sealant becomes damaged,
replace damaged portion. Clean
surfaces in damaged area and
repair with fresh A/D FIREBARRIER
Acrylic Sealant. Damage by other
trades should be patched at the
expense of trade causing damage.
7. TECHNICAL SERVICES
Contact nearest A/D office.





























June 25, 2007
Table 2
Type of
Packaging
Size Volume
Coverage at
deep x
1 wide
10.1 fl. oz.
(300 mL)
18.2 in
3

(300 cm
3
)
6.1 lineal ft.
(1.86 lineal m)
Cartridges
28.7 fl. oz.
(850 mL)
51.8 in
3

(850 cm
3
)
17.3 lineal ft.
(5.27 lineal m)

Foil packs
20 fl. oz.
(600 mL)
36 in
3

(600 cm
3
)
12.2 lineal ft.
(3.72 lineal m)

Pails
5 gal
(18.9 L)
1155 in
3

(18900 cm
3
)
384.4 lineal ft.
(117.18 lineal m)

FIREBARRIER SILICONE

1. PRODUCT NAME
A/D FIREBARRIER Silicone
2. PRODUCT DESCRIPTION
A primerless single component
silicone sealant. The sealant
cures to a durable, flexible,
silicone rubber when exposed to
atmospheric moisture.
Basic Use: A/D FIREBARRIER
Silicone is designed for
economical use in joint and
service penetration firestop
configurations. It forms a durable,
flexible, watertight bond with most
construction materials. In most
cases, no primer is required.
Composition and Materials:
A/D FIREBARRIER Silicone is
designed to tool easily. Its'
physical properties will remain
stable over time. It may be
applied over a wide temperature
range, 0F to 120F (-18C to
50C), allowing the sealant to be
applied in any season.
Packaging: A/D FIREBARRIER
Silicone is available in nominal
10.3 fl. oz. (304 mL) and 28.7 fl.
oz. (850 mL) cartridges, 20 fl. oz
(600 mL) foil packs and 2.64 US
gallon (10L) and 4.5 US gallon
(17L) bulk containers. Contents
are 18.6 in
3
, 49 in
3
, 36.1 in
3
, 634
in
3
and 1050 in
3
respectively.
Refer to the A/D FIREBARRIER
estimate guide for volume and
coverage information.
Color: Red or Grey*
(*Note: requires special order)
Application Limitations:
Do not use where abrasion or
physical abuse is anticipated.
Installation in confined or air-
free spaces may inhibit cure.
Silicones may be painted, but
movement of the silicone may
cause the paint film to crack
and peel. We recommend the
sealant be applied after
painting is completed.
Do not apply to surfaces that
will be in direct contact with
food.
Do not apply to surfaces with
special protective or cosmetic
coatings without prior consul-
tation of the manufacturer
and first testing adhesion.
For optimum economy and
performance the product
should be applied to a
thickness equal to or slightly
greater than the minimum test
design thickness.
Excessive depth to width
ratios may cause sealant
failure Do not apply
excessive thickness. As a
guideline, A/D Fire Protection
Systems recommends that
the minimum test system
thicknesses not be exceeded
by more than 25%.
Standards: A/D FIREBARRIER
Silicone has been tested in
accordance with the following:
ULC-S115, Standard Method of
Fire Tests of Firestop Systems.
ASTM E814-83, Standard
Method of Fire Tests of Through-
Penetration Fire Stops
ANSI/ULC 2079, Tests for Fire
Resistance of Building J oint
Systems.
FGG/BM/CZ System
Compatible indicates that this
product has been tested, and is
monitored on an ongoing basis, to
assure its chemical compatibility
with FlowGuard Gold,
BlazeMaster and Corzan pipe
and fittings. FGG/BM/CZ,
FlowGuard Gold,
BlazeMaster, and Corzan are
licensed trademarks of the
Lubrizol Corporation.
3. TECHNICAL DATA
A/D FIREBARRIER Silicone
sealant remains flexible
indefinitely between temperatures
of -50F and 300F (-45 and
149C). It will not crack or
crumble.
A/D FIREBARRIER Silicone
conforms to the requirements of
ASTM C 920 for Elastomeric joint
sealants, Type S, Grade NS,
class 25, use NT, G, A and M.
A/D FIREBARRIER Silicone is
listed by ULC, ULI, ITS (Warnock
Hersey) and Factory Mutual.
For details of rated firestop
systems see ULCs List of
Equipment and Materials, Fire-
stop System and Components,
ULIs Fire Resistance Directory,
Volume 2, ITS' s Listings Book
PHYSICAL PROPERTIES

Properties Results

Uncured
Tool/Work Time 5 minutes
Skin Over Time @ 25C (77F) Less than 60 minutes @ 50% RH
Curing Time @ 25C (77F) 48 hours @ 50% RH
Flow, Sag or Slump Nil
Specific Gravity 1.13
Maximum strength After 21 days
VOC (ASTM D 3960-92) Less than 0.69 lb/gal US

Cured 7 days @ 25C (77F) 50% RH.
Hardness (A) (ASTM D2240) 12
Tear Strength (ASTM D624, Die B) 3.5 kN/m (20 ppi)
Elongation at Break (ASTM D412) 600%
Shrink Factor Negligible
ASTM C 920 Type S, NS, 25, NT, G, A & M
*Values given above are not intended to be used in specification preparation.

August 2008
and Factory Mutual s Approval
Guide.
4. INSTALLATION
Clean all openings to be
firestopped by removal of foreign
matter and contaminants such as
oil, dust, grease, frost, water,
surface dirt, old sealants glazing
compound, protective coatings,
etc.
Priming: A/D FIREBARRIER
Silicone generally does not
require priming. In view of the
unpredictability of surface
characteristics, it is recommended
that a test sample of sealant be
applied on the surface to test
adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch
the clean surfaces to which the
silicone is to adhere. Remove
masking tape immediately.
A/D FIREBARRIER Mineral Wool
is the required backup material in
most systems. The material
allows a controlled depth of
sealant to be applied for
maximum economy.
Install backup material as
specified. Surfaces of mineral
wool to receive sealant should be
recessed in the opening to a
depth equal to the required thick-
ness of sealant. Apply A/D
FIREBARRIER Silicone in a
continuous operation to fill and
seal the opening. Tool the
sealant to spread it against the
backup material and the opening
surfaces.
Individual penetrations through
drywall may not require a backing
material for the silicone. Simply
fill the annular space to the
required depth and form a smooth
bead or crown at the surfaces.
Excess sealant should be dry-
wiped from glass, metal and
plastic surfaces while still
uncured, followed with a
commercial solvent such as xylol,
toluol, or methyl ethyl ketone.
CURED SEALANT IS USUALLY
VERY DIFFICULT TO REMOVE
WITHOUT ALTERING OR
DAMAGING THE SURFACE TO
WHICH THE SEALANT HAS
BEEN MISAPPLIED.
Precaution: On direct contact,
uncured sealant may irritate eyes.
Flush with water and call a
physician. Avoid prolonged
contact with skin. Keep out of
reach of children.
To safely use this product, read
and abide by Material Safety Data
Sheet (MSDS). Provide adequate
ventilaion.
Shelf Life: When stored in
original and unopened container
at or below 32C (90F), A/D
FIREBARRIER Silicone has a
shelf life of one year from date of
manufacture.
5. AVAILABILITY AND COST
Availability: A/D sales offices
and technical representatives are
located throughout North
America. (See below)
6. MAINTENANCE
No maintenance should be
required. If silicone sealant
becomes damaged, replace dam-
aged portion. Clean surfaces in
damaged areas, and repair with
fresh A/D FIREBARRIER
Silicone.
7. TECHNICAL SERVICES
Contact nearest A/D
representative.













FIREBARRIER SILICONE SL

1. PRODUCT NAME
A/D FIREBARRIER Silicone SL
2. PRODUCT DESCRIPTION
Basic Use: A primerless single
component self-leveling silicone
sealant. It cures to a durable,
flexible, silicone rubber when
exposed to atmospheric moisture. It
is designed for economical use in
joint and service penetration firestop
configurations. It forms a durable,
flexible, watertight bond with most
construction materials. In most
cases, no primer is required.
Composition and Materials:
A/D FIREBARRIER Silicone SL is
designed to self-level. No tooling is
required. Physical properties will
remain stable over time. It may be
applied over a wide temperature
range, 0F to 120F (-18C to 50C),
allowing the sealant to be applied in
any season.
Packaging: A/D FIREBARRIER
Silicone SL is available in nominal
10.3 fl. oz. (304 mL) and 28.7 fl. oz.
(850 mL) cartridges, 20 fl. oz (600
mL) foil packs and 2.64 US gallon
(10L) and 4.5 US gallon (17L) bulk
containers. Contents are 18.6 in
3
, 49
in
3
, 36.1 in
3
, 634 in
3
and 1050 in
3

respectively. Refer to the A/D
FIREBARRIER estimate guide for
volume and coverage information.
Color: Red

Application Limitations:
Do not use where abrasion or
physical abuse is anticipated.
Installation in confined or air-free
spaces may inhibit cure.
Silicones may be painted, but
movement of the silicone may
cause the paint film to crack and
peel. We recommend the
sealant be applied after painting
is completed.
A/D FIREBARRIER Silicone SL
is self-leveling and is therefore
limited to horizontal applications.
Do not apply to surfaces with
special protective or cosmetic
coatings without prior consul-
tation of the manufacturer and
first testing adhesion.
Do not apply to surfaces that will
be in direct contact with food.
For optimum economy and
performance the product should
be applied to a thickness equal
to or slightly greater than the
minimum test design thickness.
Excessive depth to width ratios
may cause sealant failure. Do
not apply excessive thick-
ness. As a guideline, A/D Fire
Protection Systems recom-
mends the minimum tested
system thicknesses not be
exceeded by more than 25%.
Standards: A/D FIREBARRIER
Silicone SL has been tested in
accordance with the following:
ULC-S115, Standard Method of
Fire Tests of Firestop Systems.
ASTM E814-83, Standard Method
of Fire Tests of Through-Penetration
Fire Stops.
ANSI/UL 2079, Tests for Fire
Resistance of Building J oint
Systems.
FGG/BM/CZ System Compatible
indicates that this product has been
tested, and is monitored on an
ongoing basis, to assure its
chemical compatibility with
FlowGuard Gold, BlazeMaster
and Corzan pipe and fittings.
FGG/BM/CZ, FlowGuard Gold,
BlazeMaster, and Corzan are
licensed trademarks of the Lubrizol
Corporation.
3. TECHNICAL DATA
A/D FIREBARRIER Silicone SL
sealant remains flexible indefinitely
between temperatures of -50F and
300F (-45C to 149C). It will not
crack or crumble.
A/D FIREBARRIER Silicone SL is
listed by ULC, ULI, ITS and FM. For
details of rated firestop systems see
ULIs Fire Resistance Directory,
Volume 2, ULCs List of Equipment
and Materials, Firestop Systems and
Components, ITS's Listings Book
and FMs Approval Guide.

Contact A/D Fire Protection Systems
for a current list of tested systems.
4. INSTALLATION
Clean all openings to be firestopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, surface dirt, old
sealants, glazing compound,
protective coatings, etc.
Priming: A/D FIREBARRIER
Silicone SL generally does not
require priming. In view of the
PHYSICAL PROPERTIES

Properties Results

Uncured
Color Red
Skin Over Time @ 25C (77F) 75 minutes
Curing Time @ 25C (77F) 48 hours
Flow, Sag or Slump Self-leveling
Specific Gravity 1.15
VOC (ASTM D 3960-92) <0.50 lb/gal US (59.9 g/L)

Cured (21 days @ 25C (77F) 50% RH)
Color Red
Hardness (A) (ASTM D2240) 5
Elongation at Break (ASTM D412) 600%
Movement Capability (ASTM C719) +100/-50 %
Tensile strength (ASTM D412) 98.5 kg/cm
2
(140 psi)
Adhesion in peel (ASTM C794)

15.7 lbs. (180 , 2 in. per min.,
mortar, cohesive failure)
*Values given above are not intended for specification preparation.
August 2008
unpredictability of surface charac-
teristics, it is recommended that a
test sample of sealant be applied on
the surface to test adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch the
clean surfaces to which the silicone
is to adhere. Remove masking tape
immediately.
A/D FIREBARRIER Mineral Wool is
the required backer material in most
tested systems. The material allows
a controlled depth of sealant to be
applied for maximum economy.
Install backer material as specified.
Surfaces of mineral wool to receive
sealant should be recessed in the
opening to a depth equal to the
required thickness of sealant. Apply
A/D FIREBARRIER Silicone SL in
sufficient quantity to fill and seal the
opening to the specified depth. It is
self-leveling and therefore no tooling
is required.
Excess sealant should be dry-wiped
from glass, metal and plastic
surfaces while still uncured, followed
with a commercial solvent such as
xylol, toluol, or methyl ethyl ketone.
Cured sealant may be very difficult
to remove without altering or
damaging the surface to which the
sealant has been misapplied.
Precaution: On direct contact,
uncured sealant may irritate eyes.
Flush with water and call a
physician. Avoid prolonged contact
with skin. Keep out of reach of
children.
To safely use this product, read and
abide by Material Safety Data Sheet
(MSDS). Provide adequate
ventilation
Shelf Life: When stored in original
and unopened container at or below
90F (32C), A/D FIREBARRIER
Silicone SL has a shelf life of one
year from date of manufacture.
5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are located
throughout North America. (See
below)
6. MAINTENANCE
No maintenance should be required.
If silicone sealant becomes
damaged, replace damaged portion.
Clean surfaces in damaged areas,
and repair with fresh A/D
FIREBARRIER Silicone SL.
7. TECHNICAL SERVICES
Contact nearest A/D representative.
















FIREBARRIER SPRAYACRYLIC

1. PRODUCT NAME
A/D FIREBARRIER SprayAcrylic
2. PRODUCT DESCRIPTION
A/D FIREBARRIER SprayAcrylic is
a single component, water-based
elastomeric that cures to a durable,
flexible, fire resistant seal.
Basic Use: A/D FIREBARRIER
SprayAcrylic is designed for use as
a firestop sealant in joint firestop
configurations including head-of-
wall, curtain wall, perimeter and
floor to wall construction joints.
Composition and Materials:
A/D FIREBARRIER SprayAcrylic is
water-based. It is designed for spray
and trowel application to vertical and
horizontal surfaces. It forms durable,
flexible, watertight bonds with most
materials. Physical properties will
remain stable over time. Product
contains mold growth inhibiters.
A/D FIREBARRIER SprayAcrylic
contains water and is best if
protected from freezing. If frozen,
thaw completely before use. Store,
transport and install at temperatures
above 40F (5C).
Packaging: A/D FIREBARRIER
SprayAcrylic is available in 5 US
gallon (18.9 L) pails. Coverage per
pail is approximately 67 ft
2
(6.3 m
2
)
at 1/8-in. (3 mm) wet thickness.
Color: Red
Application Limitations:
Do not install when ambient
temperature or temperature of
substrate is below 40F (5C).
Protect from freezing and water
until sealant is fully cured.
Do not apply to surfaces with
special protective or cosmetic
coatings without first testing
adhesion and prior consultation
with manufacturer.
Not intended for immersion or
continuous exposure to water.
Do not install on hot surfaces
above 200F (90C).
A/D FIREBARRIER SprayAcrylic
has been tested in numerous
firestop joint firestop systems.
For optimum economy and
performance, the product should
be applied to a thickness equal to
or slightly greater than the
required minimum test design
thickness. Excessive depth to
width ratios may cause sealant
failure do not apply excessive
thickness. As a guideline, we
recommend that the minimum
test system thicknesses not be
exceeded by more than 25%.
3. TECHNICAL DATA
Standards: A/D FIREBARRIER
SprayAcrylic has been tested and in
accordance with the following:
ANSI/UL1479, ANSI/UL2079, ASTM
E814 and CAN4/ULC-S115M.
For details of rated firestop systems
see UL s Fire Resistance Directory,
Volume 2. Systems certified for use
in Canada are available under the
cUL mark.
Surface Burning Characteristics:
(ASTM E84 )
Flame Spread: 15
Smoke Developed: 0
4. INSTALLATION
No dilution or mixing is required for
use. Clean all openings to be
firestopped by removal of foreign
matter and contaminants such as
oil, dust, grease, frost, water,
surface dirt, old sealants, glazing
compounds, protective coatings,
etc.
Priming: Generally, a primer will
not be required. It is recommended
that a test sample of sealant be
applied on the surface to test
adhesion.
Masking: Surfaces adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch the
clean surface to which the sealant is
to adhere. Remove masking tape
immediately.
Forming/Backing: Install forming /
backing material as specified by the
tested firestop system. Unless
otherwise specified, A/D FIREBAR-
RIER Mineral Wool is the
recommended backup material.
Application: A/D FIREBARRIER
SprayAcrylic may be applied by
spray or trowel to vertical and
horizontal surfaces.
Refer to tested firestop system for
minimum wet film thickness that is
required - usually 1/8 (3.2 mm).
Use a wet film gauge to measure
wet film thickness. Apply A/D
FIREBARRIER SprayAcrylic so as
to seal the mineral wool backer with
the required thickness and overlap
adjacent surfaces a minimum of
in. (13 mm) or as otherwise
specified in tested firestop system.
Excess sealant should be wiped
from glass, metal and plastic
surfaces while uncured. Clean up
with water. Follow equipment
manufacturers instructions for clean
up and use. Protect adjacent
surfaces from overspray and
unintended contact - Cured Sealant
May Be Very Difficult To Remove
Without Altering Or Damaging
The Surface To Which The
Sealant Has Been Applied.

Table 1 PHYSICAL PROPERTIES*
Color Red
pH 7.0 - 9.0
VOC (grams/liter): 65
Flame Spread (ASTM E84) 15
Smoke Development (ASTM E84) 0
Cure Time 3 - 5 days
Skin over Time Overnight
Movement Capability: (UL 2079; class I, II, III) +25 %, maximum
Shore A Hardness (ASTM C-661) 15 - 20
Application Temperature 40 - 110F (5 - 43C)
Freeze Sensitive Yes
Paintable Yes
*Values given above are not intended for specification preparation.

Precautions: May cause irritation.
May be harmful if swallowed. Avoid
contact with eyes. Wash hands
thoroughly after handling. Use only
as directed. Keep out of reach of
children. To safely use this product,
read and abide by Material Safety
Data Sheet (MSDS).
Shelf Life: A/D FIREBARRIER
SprayAcrylic has a shelf life of 1
year from the date of manufacture
when stored in original and
unopened container below 110F
(43C) and above 40F (5C).
5. MAINTENANCE
No maintenance should be required.
If product becomes damaged, rep-
lace with new A/D FIREBARRIER
SprayAcrylic. All surfaces should be
clean and free of any material that
would prevent adhesion.
6. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below).
7. TECHNICAL SERVICES
Contact nearest A/D office or
representative























J une 25, 2007
Table 2 Quick Reference Guide
Spray Application of SprayAcrylic
Hoses 50 ft of 1/4 in. (I.D.) Blue Max
Whip line 6 ft - (I.D.) whip line with swivel
Tips
419 - 423 heavy-duty self cleaning reversible type
621 - 625 heavy-duty self cleaning reversible type
Spray machine
Airless sprayer capable of 3300psi pressure and min.
delivery of 0.95 gpm without surging
Filters 60-80 mesh in gun & 60-80 in manifold
Mixing Heavy-duty drill with paddle for 30 seconds
Application Rate 1/8 in. (3 mm) wet
Finish Follows profile of backer material
Trowel May be toweled
Clean-up Water

FIREBARRIER MORTAR

1. PRODUCT NAME
A/D FIREBARRIER Mortar
2. PRODUCT DESCRIPTION
A non-combustible fiber reinforced,
foamed cement mortar.
Basic Use: A/D FIREBARRIER
Mortar is intended to provide non-
combustible and tight fitting
firestops at openings and
penetrations through fire-rated wall
and floor assemblies. A/D
FIREBARRIER Mortar powder
mixes easily with water to form a
mousse or shaving cream-like non-
slumping paste. This feature
permits easy installation with a
minimum of damming. When
cured, A/D FIREBARRIER Mortar
is self-supporting and therefore
may be used for large openings
where other firestopping materials
are impractical.
Composition and Materials:
A/D FIREBARRIER Mortar mixes
and trowels easily. Tools are
cleaned with water. A/D
FIREBARRIER Mortar requires and
contains no solvents. It is
comprised of materials of low
toxicity. Dust protection is recom-
mended see INSTALLATION.
Color: A distinctive charcoal (dark
grey).
Packaging: A/D FIREBARRIER
Mortar is packaged in 15.5 lb. (7
kg) bags. A 275 mL measuring cup
is provided in each bag of product
for convenience. One bag will yield
approximately 850 in.
3
(13,930cm
3
)
- approximately enough for a 1 x 2
ft. (305 x 610 mm) opening at an
installed depth of 3 in. (75 mm).
Note: Ignores volume occupied by
penetrating items. Yield calculation
is based on product mixed in
accordance with our installation
instructions.
Application Limitations:
Do not install when temperature is
below 40F (5C).
In horizontal applications, inter-
mediate support may be required.
Do not permit pedestrian or other
traffic.
Where A/D FIREBARRIER Mortar
will be subject to acidic exposure,
like other Portland cement-based
products it may require a protective
coating.
3. TECHNICAL DATA
Physical Properties: Refer to
Table 1.
Fire Resistance Ratings: A/D
FIREBARRIER Mortar has been
tested and certified by ULI, ULC,
ITS and FM in accordance with
ANSI / UL 1479, ASTM E814 and
ULC-S115-95. For details of rated
firestop systems see ULIs Fire
Resistance Directory, Volume 2,
ULCs List of Equipment and
Materials, Firestop Systems and
Components, ITS' s Listing Book
and Factory Mutual s Approval
Guide. Current systems include:
ULI: CAJ-1126, -1128, -1195, -
1196, -2249, -5095, -7029, -7030, -
8029 and WL-8005.
ULC: SP196, -229, -230, -326, -
341, -396, -422, -423, -424, -758, -
765 and -767.
FM: 91, 92, 94 and 205
ITS: AD/PHV 180-01, -02 and -03.


4. INSTALLATION
Clean openings to be fire-stopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, dirt, old
sealants or glazing compounds,
protective coatings, original
formwork, etc.
Priming: Surfaces to receive A/D
FIREBARRIER Mortar generally do
not require priming.
Keying: For large horizontal
openings, it is recommended that
A/D FIREBARRIER Mortar be
mechanically keyed into the
concrete surround and/or that
intermediate support be provided.
Mixing: A/D FIREBARRIER Mortar
is mixed with water in the ratio of
2.6 quarts US (2.5 L) of water to
each 15.5 lb. (7 kg) bag. An empty
milk container makes a convenient
measuring device for water at the
job site. A measuring cup is
supplied in each bag for
convenience when mixing less than
a full bag. Portion water and Mortar
powder in accordance with Table 2.
Forming or Damming:
Horizontal openings may be
dammed temporarily with any
Table 1 - PHYSICAL PROPERTIES
Properties Results
Before Curing
Mix Time 1.5 to 5 min.
Pot Life 50 min. (max.)
Workability Excellent
Wet Density 43.7 + 0.6 pcf (700+10 kg/m)
Set Time 10 to 15 hr.
After Curing
Density 40 + 2.5 pcf (640 + 40 kg/m)
Compressive Strength (28 days) 478 + 44 psi (3.3 + 0.3 MPa)
Shrinkage None
Noncombustibility (ASTM E136) Noncombustible
Noncombustibility (CAN4-S114) Noncombustible
Thermal Conductivity (ASTM C-518)
0.197 W/m.K @ 24C
(1.365 Btu. in/ft.h.F)

*Values given are not intended to be used in specification preparation.
October 2004
convenient material (i.e. plywood,
polystyrene insulation boards, wire
mesh, etc.). Damming is generally
not required for vertical openings
due to the low slump, dimensional
stability and cohesive strength of
the mortar paste. Forms, if used,
may be removed after 24 hours.
Placement: Apply A/D FIRE-
BARRIER Mortar paste into
opening with trowel, or pour into
large horizontal openings from
mixer or mixing container. Work
paste with trowel to ensure that all
voids are filled. Give particular
attention to voids between multi-
cable/pipe installations. Product
may be vibrated for this purpose.
Tool surface to desired finish.
Clean up with water.
Re-Penetration: Should it become
necessary to penetrate cured A/D
FIREBARRIER Mortar for new or
additional building services (i.e.
cables or pipes), simply drill or poke
through mortar to provide opening
of sufficient size. After installation
of new penetrating item(s), firestop
remaining voids with fresh A/D
FIREBARRIER Mortar or with A/D
FIREBARRIER Mineral Wool and
Silicone where permitted by fire
tested system.
Precaution: Avoid inhalation of
dust or contact with eyes. Use of
dust mask and eye protection is
recommended. Thoroughly wash
skin after contact and before eating,
etc.
To safely use this product, read and
abide by Material Safety Data
Sheet (MSDS).
5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below)

6. MAINTENANCE
No maintenance should be
required. If mortar becomes dam-
aged replace damaged portion.
Damage by other trades should be
patched at the expense of trade
causing damage.
7. TECHNICAL SERVICES
Contact nearest A/D office.



















A/D FIRE PROTECTION SYSTEMS
Table 2
A/D FIREBARRIER Mortar Powder Water
Full bag, 7 kg (15.5 lb.) 2.5 L (9 cups*)
(2.6 quarts US)
bag (32 cups*) 1.875 L (6 cups*)
(2 quarts US)
bag (21 cups*) 1.25 L (4 cups*)
(1.3 quarts US)
bag (10 cups*) 0.625 (2 cups*)
(0.7 quarts US)

*Note: Refers to 275 mL cup supplied in bag. Use clean potable water.
Add mortar powder to water in mixer or mixing container. Mix until the
mortar paste takes on a consistent mousse-like or shaving cream-like
texture. DO NOT ADD MORE WATER continue to mix until mixture
wets out. Mixing time will depend on method used - 1 to 3 minutes for
mortar mixer, 3 to 5 minutes with electric hand-held mixer. Hand mixing
may take longer.
NOTE: DO NOT ADD MORE WATER. IT IS NORMAL FOR MIX TO
APPEAR QUITE DRY AT FIRST. CONTINUE TO MIX.

FIREBARRIER SEAL and SEAL NS

1. PRODUCT NAME
A/D FIREBARRIER Seal and
Seal NS
2. PRODUCT DESCRIPTION
Single component, water based
elastomeric sealants intended for
use as firestop system components.
Basic Use: A/D FIREBARRIER
Seal and Seal NS are designed for
economical use in joint and service
penetration firestop configurations.
They form durable, flexible,
watertight bonds with most
construction materials. In most
cases, no primer is required.
Physical properties will remain
stable over time.
Composition and Materials:
A/D FIREBARRIER Seal may be
pumped or poured into the opening.
A/D FIREBARRIER Seal NS (non-
slumping) is designed for trowel and
spray applications.
A/D FIREBARRIER Seal and Seal
NS contain water and must be
protected from freezing and from
water until fully cured. Store,
transport and install at temperatures
above 40F (5C).
Colors: A/D FIREBARRIER Seal is
blue in color. Seal NS is available in
white or red please specify when
ordering. The white version of Seal
NS in 5 gal (18.9 L) pails may be
tinted in the field with a variety of
color tint pastes. Refer to Seal NS
Tinting data sheet.
Packaging: A/D FIREBARRIER
Seal and Seal NS are available in 5
US gallon (18.9 L) pails. Theoretical
coverage per pail is 40 ft
2
(3.8 m
2
) at
an applied wet film thickness of 0.2
in. (5 mm) and approximately 64 ft
2

(5.7 m
2
) at 1/8-in. (3 mm) wet
thickness. Seal NS is also available
in 10.3 fl. oz. (304mL) and 28.7 fl.
oz. (850 mL) tubes.
Application Limitations:
Do not install when ambient
temperature or temperature of
substrate is below 40F (5C).
Protect from freezing and water
until sealant is fully cured.
Do not install to surfaces with
special protective or cosmetic
coatings without prior consul-
tation with manufacturer and
first testing adhesion.
Do not install where direct
contact with food will occur.
Do not install where abrasion or
physical abuse is anticipated.
Seal is intended for horizontal
applications only. Seal NS can
be used for vertical and
horizontal applications.
Seal and Seal NS have been
tested in numerous firestop joint
and through-penetration firestop
systems. For best economy and
performance the product should
be applied to a thickness equal
to or slightly greater than the
minimum test design thickness.
Excessive depth to width ratios
may cause sealant failure do
not apply excessive thick-
ness. As a guideline, we
recommend that the minimum
test system thicknesses not be
exceeded by more than 25%.
Standards: A/D FIREBARRIER
Seal and Seal NS have been fire
tested in accordance with the
following: ULC-S115-M, Standard
Method of Fire Tests of Firestop
Systems, ASTM E814-83 and
ANSI/UL 1479, Standard Method of
Fire Tests of Through - Penetration
Fire Stops and ANSI/UL 2079,
"Tests for Fire Resistance of
Building Joint Systems."
3. TECHNICAL DATA
A/D FIREBARRIER Seal and Seal
NS are listed by ULC, ULI, ITS and
FM. For details of rated firestop
systems see ULI s Fire Resistance
Directory, Volume 2, ULC s List of
Equipment and Materials, Firestop
Systems and Components, ITS' s
Listings Book and FM s Approval
Guide.
ULC: JF9, -29, -50, -51, -93, -99
and -100. HW36, -38, -39, -40,
-41, -42, -43, -44, -45, -46, -47,
-48, -49, -50, -51, -52, -53, -54,
Table 1 - PHYSICAL PROPERTIES
Result Property
Seal Seal NS
Uncured
Color blue white or red
VOC (ASTM D3960) 0.2 lb/gal US (26 g/L) 0.23 lb/gal US (27 g/L)
% Volatile by volume (ASTM D2697) 43.0 41.9
Tack Free Time*, hours 4 1
Curing Time*, hours 24 96
Brookfield Viscosity (nominal),
centipoises
10,000
(LVF, spindle 4
@ 5 rpm)
200,000
(RVT, spindle E
@ 10 rpm)
pH 9.1 8.5 8.8
Weight per Gallon, lb / imp. gal. 13.5
Cured
Color blue white or red
Dirt Resistance Excellent
Tensile Strength (ASTM D412), psi 330 365
Tensile Strength (ASTM D2370), psi 385
Elongation at break (ASTM D412), % 255 350
Elongation at break (ASTM D2370), % 370
* Curing time will vary with temperature, humidity and thickness.
Values given above are not intended for specification preparation.

-55 and -56.
SP218, -219, -220, -221, -759,
-761, -881, -882 and -1080.
ULI: CAJ-1125, -1127, -1324 and
1450. FF-D-1032 and -1038. FW-D-
1029 and -1036.
HW-D-0060, -0061, -0118, -0119,
-0120, -0247, -0249, -0250, -0254,
-0282, -0301, -0302, -0303, -1012,
-1020 and -1029. WW-D-1033.
FM: 90, 93, 95.
ITS: AD/PH 180-01, -02 and -03.
AD/PHV 120-01, -02 and -03,
180-09, -10, -11 and -12.
4. INSTALLATION
Clean all openings to be firestopped
by removal of foreign matter and
contaminants such as oil, dust,
grease, frost, water, surface dirt, old
sealants, glazing compounds,
protective coatings etc.
Cleaning of all surfaces should be
done on the same day in which the
sealant is applied.
Priming: A/D FIREBARRIER Seal
and Seal NS generally do not
require priming. In view of the
unpredictability of surface charac-
teristics, it is recommended that a
test sample of sealant be applied on
the surface to test adhesion.
Masking: Areas adjacent to
openings to be firestopped can be
masked to assure a neat
appearance. The masking tape
should not be allowed to touch the
clean surface to which the seal is to
adhere. Remove masking tape
immediately.
A/D FIREBARRIER Mineral Wool is
the required backup material for
firestops.
Install backup materials as
specified.
A/D FIREBARRIER Seal is
intended only for horizontal
applications. Check fire test design
for required thickness - usually 0.2
in. (5 mm) wet. Pour or pump Seal
in a continuous operation to fill and
seal the opening. A light pass with
a trowel over the surface of the seal
will ensure a smooth surface.
A/D FIREBARRIER Seal NS is non-
slumping and may be sprayed or
trowelled for vertical and / or
horizontal applications. For spray
applications refer to Table 2. Check
fire test design for required
minimum wet film thickness -
usually 0.2 in. (5 mm) or 1/8 in. (3.2
mm).
Excess sealant should be wiped
from glass, metal and plastic
surfaces while uncured. Clean up is
with water.
CURED SEALANT IS USUALLY
VERY DIFFICULT TO REMOVE
WITHOUT ALTERING OR DAM-
AGING THE SURFACE TO WHICH
THE SEALANT HAS BEEN
APPLIED.
Precaution: May cause irritation.
May be harmful if swallowed. Avoid
getting in eyes. Wash hands
thoroughly after handling. Use only
as directed.
Keep out of reach of children.
To safely use this product, read and
abide by Material Safety Data Sheet
(MSDS).
Shelf Life: When stored at or below
80F (27C) and above 40F (5C),
A/D FIREBARRIER Seal and Seal
NS have a shelf life of one year
from date of manufacture.
Note: Protect from freezing.
5. AVAILABILITY AND COST
Availability: A/D sales offices and
technical representatives are
located throughout North America.
(See below)
6. MAINTENANCE
No maintenance should be required.
If seal becomes damaged, replace
damaged portion. Clean surfaces in
damaged area and repair with fresh
A/D FIRE-BARRIER Seal or Seal
NS. Damage by other trades
should be patched at the expense of
trade causing damage.
7. TECHNICAL SERVICES
Contact nearest A/D office.


A/D FIRE PROTECTION SYSTEMS
Head Office: 420 Tapscott Road, Scarborough, Ontario, M1B 1Y4
Tel: (800) 263-4087 or (416) 292-2361 Fax: (416) 298-5887
www.adfire.com
Contact By State or Province
AK, AR, AZ, CA, CO, HI, ID, LA, MT, NM, NV, OK, OR, TX, WA, WY, UT: Tel: (888) 323-3473, Fax: (949) 458-9220
AL, CT, DC, DE, FL, GA, IA, IL, IN, KS, KY, MA, MD, ME, MI, MN, MO, MS, NC, ND, NE, NH, NJ, NY,
OH, PA, RI, SC, SD, TN, VA, VT, WI, WV: Tel: (800) 650-0881, Fax: (613) 841-7768
NB, NF, NS, PE, QC: Tel: (800) 914-6506, Fax: (450) 661-8776
AB, BC, MB, ON, SK: Tel: (800) 263-4087, Fax: (416) 298-5887
Table 2 Quick Reference Guide - Spray Application of Seal NS
Hoses
300 ft max.
50ft of 3/8 in. dia. & 250 ft of 1/4 in. dia.
Whip line 9 ft whip line with swivel
Tips 5/17 heavy-duty self cleaning reversible type
Spray machine
Airless sprayer capable of 3000psi pressure and min. delivery
of 1.0 gpm without surging
Filters 60-80 mesh in gun & 60-80 in manifold
Mixing Heavy-duty drill with paddle for 2 min.
Application Rate 1/8 in. (3 mm) wet
Finish Follows profile of backer material
Trowel May be toweled
Clean-up 10 gal water

April 2004
SELLOS CORTA FUEGO Y HUMO
ESPECIFICACIN SECCIN 07860
1 General
1.1 LA SECCION INCLUYE
0.1 Cumplir con la Divisin 1, Requisitos General y Documentos referidos aqu
0.2 Es la intencin de esta seccin de las especificaciones de establecer una nica,
y competente fuente que sea responsable de proveer toda la mano de obra,
materiales, productos, equipos y servicios, para suministrar e instalar el trabajo
del sistema de corta-fuego y sello de humo para toda la obra.
1.2 TRABAJO RELACIONADO ESPECIFICADO EN OTRO LUGAR
(Especificar)
1.3 SECCIONES RELACIONADAS
(Especificar)
1.4 ESTANDARES DE REFERENCIA
0.1 (ANSI/UL 1479 - Pruebas de Fuego de Corta Fuego a Travs de Penetraciones)
(CAN4-S115-M85 - Mtodo Estndar de Pruebas de Fuego de Sistemas Corta
Fuego) (ASTM E814 - Mtodo de Prueba de Pruebas de Fuego de Corta Fuego
a Travs de Penetraciones) (ANSI/UL 2079 - Pruebas para Resistencia al Fuego
de Sistemas de Juntas para Edificios).
1.5 DESCRIPCION DEL SISTEMA
0.1 Materiales Corta Fuego: Proveer Sistema(s) Corta Fuego para proveer y
mantener una clasificacin de resistencia al fuego, como est indicado en los
Planos y de acuerdo a los detalles de diseo de UL, WH, ULC, cUL o FM.
1.6 REMISIONES (Submittals)
0.1 (Especificar) (datos del fabricante) (planos de taller) (muestras)
1.7 ASEGURAR CALIDAD
0.1 Fabricante: Compaa especializada en fabricacin de productos de esta Seccin
con un mnimo de tres (3) aos de experiencia documentada, y un sistema de
gerencia de calidad registrado de acuerdo con los requisitos de ISO 9001:2000.
0.2 Aplicador: Compaa que tenga un mnimo de tres (3) aos de experiencia en
la instalacin de los materiales aqu especificados en proyectos comparables a
este proyecto.
1.8 REQUISITOS DE NORMAS
0.1 Cumplir con (Cdigos de Construccin locales), listados de (UL) (ULC) (cUL)
(ITS) (FM) y (ANSI/UL 2079) (CAN4-S115) (ASTM E814) prueba de fuego
estndar para obtener la clasificacin de proteccin al fuego requerida.
1.9 REQUISITOS AMBIENTALES
0.1 Cumplir con las recomendaciones de instalacin del fabricante en cuanto a
temperatura, humedad, y condiciones de ventilacin.
1.10 ENTREGA, ALMACENAJE Y MANEJO
0.1 Entregar materiales al sitio de la obra en los envases originales del fabricante,
intactos sellados y etiquetados por el fabricante. Manejar y almacenar los
materiales de acuerdo a las instrucciones del fabricante.
1.11 CONDICIONES DEL PROYECTO/SITIO DE OBRA
0.1 Cumplir con los requisitos recomendados del fabricante en cuanto a
temperatura, humedad relativa y condiciones del substrato durante la aplicacin
y curado de los materiales.
1.12 SECUENCIA Y PROGRAMACIN
0.1 Coordinar con otras Secciones relacionadas. Programar el trabajo de otras
actividades de manera que las aplicaciones de corta fuego puedan ser
inspeccionadas antes de ser cubiertas por construccin subsecuente.
2 Productos
2.1 FABRICANTES ACEPTADOS
0.1 Proveer corta fuego de selladores de silicona, selladores a base de agua, morteros,
o sistemas corta fuego del siguiente fabricante: A/D Fire Protection Systems.
2.2 MATERIALES
0.1 Los material(es) deben ser: A/D FIREBARRIER Mineral Wool (Lana Mineral) A/D
FIREBARRIER Silicone and Silicone SL (Silicona) A/D FIREBARRIER Mortar
(Mortero) A/D FIREBARRIER Collars (Collarines) A/D FIREBARRIER
Intumescent Caulk (Calafateo Intumescente) A/D FIREBARRIER Pillows
(Almohadas) A/D FIREBARRIER Seal and Seal NS A/D FIREBARRIER
SprayMastic A/D FIREBARRIER Wrap Strip (Banda para Enrollar) A/D
FIREBARRIER Putty (Masilla) A/D FIREBARRIER Putty Pads (Pads de Masilla)
A/D FIREBARRIER Inserts (Pads de Masilla pequeos).
0.2 Clasificaciones de Sistemas Corta Fuego: Cumplir con los requisitos de cdigo
de construccin aplicable para las ubicaciones y horas de clasificacin contra
fuego de las designaciones (F) (T) (FT) (FH) (FTH).
0.3 Materiales de relleno y soporte trasero, soportes y anclajes deben ser de
acuerdo a las recomendaciones del fabricante, del sistema/diseo de corta
fuego probado, y aceptable a las autoridades que tienen jurisdiccin.
0.4 Base antioxidante: como sea requerido por el fabricante, y que sea compatible
con el sistema y los materiales contiguos.
0.5 Agua: Potable
3 Ejecucion
3.1 EXAMINACION
0.1 Examinar substratos, aberturas, espacios, construccin adyacente, y
condiciones bajo las cuales el corta fuego va a ser instalado. Confirmar
compatibilidad con las superficies.
0.2 Verificar artculos que penetran estan fijados en forma segura, y ubicados
debidamente dejando el debido espacio entre las penetraciones y las superficies
de las aberturas.
3.2 PREPARACION
0.1 Las superficies que van a recibir el corta fuego deben estar libres de sucio,
polvo, grasa, aceite, xido, materiales sueltos, agentes de separacin,
congelacin, humedad o cualquier otro material que impida la unin del
material corta fuego al substrato o artculo penetrante(s).
0.2 Aplicar base antioxidante a los substratos de acuerdo con las instrucciones
escritas del fabricante.
0.3 No aplique corta fuego y sellos de humo a superficies previamente pintadas o
tratadas con selladores, compuestos de curado, repelentes de agua o otros
revestimientos a menos que se hayan hecho pruebas que aseguren
compatibilidad de materiales. Remueva los revestimientos que sean requeridos.
0.4 Asegurar que los anclajes, materiales de soporte, clips, mangas, soportes y
otros materiales relacionados usados en las pruebas de fuego sean utilizados.
0.5 Cubrir cuando sea necesario, para prevenir que los materiales corta fuego
hagan contacto con superficies adyacentes que quedarn expuestas durante el
trabajo. Remover la cinta adhesiva tan pronto sea posible sin daar el material
corta fuego o el substrato.
3.3 INSTALACION
0.1 Cumplir con los listados de (UL) (ULC) (cUL) (ITS) (FM), y con las
instrucciones del fabricante para el tipo de material y condicin de la abertura
en cada caso. Consultar con el fabricante para determinar el procedimiento
adecuado para las condiciones no totalmente cubiertas en las instrucciones
escritas. Registrar por escrito cualesquiera instrucciones recibidas, con copia
al fabricante.
0.2 Remover material corta fuego excedente prontamente en lo que el Trabajo
avanza y cuando sea terminado.
0.3 Proveer bloqueos a prueba de goteos tal como sean requeridos para sellar
aberturas y contener el material corta fuego hasta que se haya curado. Instalar
los bloqueos de acuerdo al diseo de prueba y las instrucciones del fabricante.
3.4 CONTROL DE CALIDAD DE CAMPO
0.1 Notificar al Consultor cuando las instalaciones terminadas estn listas para ser
inspeccionadas antes de encerrar o tapar las reas que contienen los materiales
corta fuego.
0.2 Organizar las inspecciones por la compaa de inspecciones y pruebas
independiente del Propietario, seleccionada y pagada por el Propietario.
0.3 Siguiendo las inspecciones de campo, proveer toda reparacin como sea
requerido para asegurar cumplimiento con los Documentos del Contrato.
3.5 LIMPIEZA Y PROTECCIN
0.1 Al terminar este trabajo, remover todos los materiales, equipo y materiales
sobrantes del sitio de la obra. Dejar el rea de trabajo y superficies adyacentes
en una condicin aceptable al Consultor.
StonCor South Cone con ms de 30 aos de experiencia en el pas, empresa del Grupo RPM,
ofrece al mercado industrial una solucin integral en la proteccin anticorrosiva.
Dicha solucin est compuesta por tres lneas de productos:
Stoncor South Cone S.A.
Einstein 1095 - Parque O.K.S.
(B1619JWA) Garn-Bs.As.
(54) 03327-442222 - Fax:442223
stoncor@stoncor.com.ar
www.stoncor.com
www.stoncor.com.ar
Argentina Brasil Chile Peru Uruguay Bolivia Paraguay
South Cone
Carboline Company
350 Hanley Industrial Court
St. Louis, MO 63144-1599
1-800-848-4645
Fax. 1-314-644-4617
www.carboline.com
Planta Industrial Garin - Argentina

You might also like