How to select CT’s for modern

protection relays?

The Siemens Answer: CT Dimensioning

Innovation for Generations

Copyright © Siemens. Innovation for generations.


CT – Measuring vs Protection

Measuring CT Protection CT

• Under over current, the CT • In case of over current, the


should limit the secondary CT should maintain the
current to avoid thermal secondary current within
overload of the connected the rated limit to enable
equipment proper protection operation

• At rated burden (cosφ = • At rated burden (cosφ =


0.8) and rated security 0.8) and rated accuracy
factor, the composite error limit factor, the composite
should be > 10% error should be less than
5% or 10%

Copyright © Siemens. Innovation for generations.


CT – Standards

• IEC/AS 60044-1: Instrument transformers - Part 1 -


Current transformers (ed. 1.2 – 2003)
• IEC/AS 60044-6: Instrument transformers - Part 6 –
Requirements for protective current transformers for
transient performance
• IEC/AS 60044-8: Instrument transformers -Part 8 -
Electronic current transformers
• AS 1675: Current Transformers – Measurement &
Protection (now superseded)
• BS7626 (BS 3938): Specification for current
transformers (now superseded)

Copyright © Siemens. Innovation for generations.


CT – AS 60044 - 1 – Class P

Rated Composite Error at ALF IEC/AS 60044-1 / BS3938:


(turn ratio error, iron / copper multiple of rated current at
losses, saturation) which, with rated burden, will
maintain the accuracy
AS 60044: 5P20 5VA IEC/AS 60044-1 / BS3938
specify Rated Burden
AS 1765: 5P 100 F20

Rated Secondary Reference Voltage Accuracy Limit Factor (ALF)


Vref (the RMS secondary voltage (the factor which, when applied
upon which the performance is based) to at rated primary current,
gives the accuracy limit primary
current)
Conversion:
Vref ⋅ I sec = VA ⋅ ALF

Copyright © Siemens. Innovation for generations.


CT – AS 60044 - 1 – Class PX

(similar to BS 3938 Class X


AS 1675 Class PL)

0.05PX 450 R3 10VA Kx Rb


Max. exciting Dimensioning
current (Iexc) at factor (Kx) Rated resistive
rated knee point burden (Rb)
voltage
Rated knee point Max. secondary winding
o
voltage (Ek or Vk) resistance (Rct) at 75 C

Turn ratio error within ± 0.25%


AS 1675: or ±50/Ns whichever the greater,
where Ns = number of secondary turns

Copyright © Siemens. Innovation for generations.


CT Dimensioning

Operational Accuracy Limit Factor – ALF’

Pi + PN Ri + RN
ALF' = ALF ⋅ = n⋅
Pi + PB Ri + RB

P + PB Ri + RB
ALF = ALF' ⋅ i = ALF'⋅
Pi + PN Ri + RN

Rated CT burden: PN
Internal CT burden: Pi=Ri ⋅ I2N2
Actually connected
burden : PB= RB ⋅ I2N2

with: RB=RL+RR= total burden resistance


RL= resistance of connecting cable
RR= relay burden resistance
Copyright © Siemens. Innovation for generations.
CT Dimensioning

Operational Accuracy Limit Factor – ALF’


I Theory:
ALF ' ≥ K OD ⋅ SC
IN No saturation during BMax XN
total fault duration: K' TF = = 1 + ωTN = 1 +
Where KOD is the total ˆ B~ RN
over-dimensioning factor:
 tM tM 
No saturation for ω ⋅ TN ⋅ TS
− −

K OD ≥ K TF ⋅ K Rem the specified time tM: K ' 'TF = 1+ (e TN − e TS 


 TN − TS 
 
% remanence
K Rem = 1+
100 Practice:
K OD = KTF

Remanence only considered in extra high


voltage systems (EHV)
KTF-values acc. to relay manufacturers‘ guides
Copyright © Siemens. Innovation for generations.
CT Dimensioning

Choice of CT rated power

• Rated burden > total connected burden


• For GIS and MV switchboard with modern
relays/measuring devices, class P 1A CTs
with small rated burden are sufficient, e.g.
5VA, 10VA

Choice of Accuracy Limit Factor

• Relay manufacturer’s recommendation


should be followed + engineering secuirty
factor
• CT performance depends on operational
ALF

Copyright © Siemens. Innovation for generations.


CT Dimensioning

Choice of CT Ratio

• CT ratio should be based on the protected object,


however, it may need to be go higher:
• limitation of difference in CT ratio for low impedance
differential protection as recommended by the relay
manufacturer
• Avoid excessive over-dimensioning:
• Imax, switchgear / Ipri-rated > 100 !
• Such CT can damage the relay because there is no CT saturation

If a more precise estimation of the CT performance is


necessary, then RCT and the magnetising curve is required.

Copyright © Siemens. Innovation for generations.


CT Dimensioning

Choice of Measuring CT

• For classes 0.1 – 1, the accuracy is based on a total connected


burden between 25% to 100% of the rated burden
• For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an
extended range of burden can be specified (from 1VA to 100% of
the rated burden)
• For classes 3 and 5, the accuracy is based on a total connected
burden between 50% to 100% of rated burden

• Instrument security factor (FS) defines the maximum secondary


current that will flow under short circuit of primary circuit
• Instrument security factor (FS) is based on the rated burden
• Under-burdened measuring CT can damage connected
instrument during short circuit or overload of the primary circuit

Copyright © Siemens. Innovation for generations.


CT Dimensioning
Overcurrent Protection

CT saturation is allowable provided the remaining fundamental current is


higher than I>> setting

Isec, fundamental > I >

Isec,funfamental > I >>

Pn + PCT I >>
ALF' = ALF ⋅ >
P'+ PCT In

Copyright © Siemens. Innovation for generations.


CT Dimensioning
Differential Protection
Differential protection should be stable on external faults
High sensitivity for internal fault
Relay
Protected Object Requirement for Internal Faults Requirements for External Faults
Type

min. over min. over


min. saturation min. saturation
dimensioning dimensioning CT symmetry
free time (ms) free time (ms)
KTF KTF

Generator 7UM6 4 0.75 5 1.20

Transformer 7UT6 4 0.75 5 1.20

O/H Line, Cable - 7SD52 3 0.50 5 1.20


with digital
communication 7SD61 3 0.50 5 1.20

O/H Line, Cable -


7SD600 5 1.20 1 1.00 0.75
with pilot wires

Busbar 7SS52 3 0.50 3 0.50

7SS600 4 0.75 4 0.75


Copyright © Siemens. Innovation for generations.