Overview

n
n
n
n
n
n
Range
Standards & Approvals
Structure & Features
Marking & Configuration
Trip Units
Accessories
16
18
19
20
21
22
State-of-the-art design, user-friendly features and a wide spectrum of protection releases form the hallmarks
of the dsine range. Also recognised for its ergonomics, aesthetics and compactness, it belongs to a new
generation of MCCBs. Specially designed and developed for extreme tropical conditions, it promises reliable
performance at highambient andhumidenvironment.
dsine, unfailingly, caters to the ever-evolving needs of customers, derived after in-depth analysis and customer
feedback. Because we understand our customers' requirements and demands, our contemporary range of
MCCBs never fall short of ensuring complete customer satisfaction. Moreover, complemented by a host of
accessories, the dsine range delivers comprehensive solutions to customer applications ensuring operational
safety, reliability andversatility.
16 Range
DN4 DN3 DN2 DN1 DN0
D
17
Features

Range available f
mal
MCCBs for Motor backup protection
MCCBs for Distribution and SD versions
Manual, Rotary or Motorised versions
Wide range of Internal and External accessories
rom 20A to 1250A
Available in 3 pole & 4 pole
Range of 25kA / 36kA / 50kA / 70kA breaking capacities
Microprocessor and Ther -Magnetic based protection releases
Breaking Capacities ( ) I
cu
Range
Rated Current 20, 25, 32, 40, 50, 63, 80, 100A
Release Thermal-Magnetic
Release Thermal-Magnetic
Rated Current 800, 1000, 1250A
Release Microprocessor
DN0
DN1
DN2
DN3
DN4
Rated Current 40, 63, 100, 160, 250A 63, 80, 100, 125, 160, 200, 250A
Rated Current 400, 630A 320, 400, 500, 630A
Release Microprocessor Thermal-Magnetic
Release Microprocessor Thermal-Magnetic
Rated Current 100, 125, 160, 200, 250A
18 Standards & Approvals
NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005
Standard. Accredited laboratories have the responsibility of satisfying the criteria of
laboratory accreditation at all times, which are verified during Surveillance and Re-
assessment visits by NABL. Further the accredited laboratories should prove their
technical competence by satisfactory participation in recognized Proficiency Testing
Programmes.
L&Ts Switchgear Testing Lab is NABL accredited subject to continued satisfactory
compliance toabove standard&additional requirements of NABL.
All dsine range of MCCBs are testedinL&T's NABL accreditedSwitchgear TestingLab.
IECEE CBSCHEME DEKRA(KEMA) certified
The IECEE CB SCHEME is a multilateral agreement among participating countries and
certification organizations. A manufacturer utilizing a CB test certificate issued by one
of the accepted National Certification Bodies (NCBs) can obtain certification marks of
the latter, within their scope of adherence, in the countries where the accepted NCBs
are located.
L&Ts dsine range of MCCBs are certified for IECEE CB scheme by DEKRA (KEMA) which
is a world renowned organisation with a heritage of 150 years in testing, inspections &
certification, risk management andverification.

IEC 60947-1, EN 60947-1, IS/IEC 60947-1


Low-voltage switchgear and controlgear, Part 1: General Rules
Low-voltage switchgear and controlgear, Part 2: Circuit-breakers
Low-voltage switchgear and controlgear, Part 3: Switches, disconnectors,
switch-disconnectors and fuse combination units
Low-voltage switchgear and controlgear, Part 4: Contactors and Motor-starters
Third party certificates (ERDA/CPRI) available for dsine range of MCCBs
IEC 60947-2, EN 60947-2, IS/IEC 60947-2
IEC 60947-3, EN 60947-3, IS/IEC 60947-3
IEC 60947-4, EN 60947-4, IS/IEC 60947-4
marking
A CE marking is a European marking of conformity that indicates a product complies
with the essential requirements of the applicable European laws or directives with
respect to safety, health and environment and consumer protection. Generally, this
conformity to the applicable directives is done through self-declaration and is required
on products in the countries of the European Economic Area (EEA) to facilitate trade
among the member countries. The manufacturer or their authorized representative
established in the EEA is responsible for affixing the CE marking to their product. The
CE marking provides a means for a manufacturer to demonstrate that a product
complies with a common set of laws required by all countries in the EEA to allow free
movement of trade withinthe EEAcountries.
L&Ts dsine range of MCCBs conform to the Low voltage directive 73/23/EEC as
amended by directive 93/68/EEC, provided if it is used in the application for which it is
made and is installed and maintained in accordance with professional practices with
relevant installationstandards andoperatinginstructions.
range of MCCBs and Accessories comply with following
international standards
19
Structure & Features
LowWatt Loss
The entire current carrying path
is optimally designed to achieve
lowwatt loss
Silver contacts offer low contact
resistance thus helping in low
watt loss
Release
Thermal & Microprocessor based
releases are available
Positive Isolation
Indicates the true position of the
contacts - ensures operator safety
NoLoadLine Bias
Either side of MCCB terminals
canbe usedas loador line
Knob
Designedfor better grip
Indicates "ON" "OFF" "TRIP"
positionof MCCB
MCCBMechanism
Quick make, quick break & trip
free mechanism
Current LimitingMCCBs
The unique speed contact system
with current limiting feature
accelerates the opening of
contacts during short circuit
resulting in very low let through
energy
Arc Chutes
Arc chutes are designed for
efficient andfaster arc quenching
20 Marking & Configuration
Terminal Connections
Indication of Open (O/OFF)
Indication of Closed (I/ON)
Standards
Standard Characteristics
:
:
:
}
}
}
}
Impulse withstand voltage
Rated operational voltage
Rated Ultimate breaking
capacity
Service breaking capacity
U
U
I
I
imp
:
e
cu
cs
Rated
Release Settings
Release
Brand
Operating Knob
"Push to Trip" button
Utilization Category
Company Logo
Terminal Shroud
Release name
Current Rating of MCCB
Frame Size
Symbol of suitability
for Isolation
Mark
21 Trip Units
Thermal Magnetic
Releases
Microprocessor
Releases
Isolator
Magnetic Release
Variable Thermal,
Fixed Magnetic
(DN0, DN1, DN3 )
Variable Thermal, Variable Magnetic (DN2, DN3)
MTX1.0 with LSI (DN2, DN3, DN4)
In
s
t
MTX2.0 with LSING + Current Metering (DN2, DN3, DN4)
Inst
MTX3.0 with LSING+ Communication capable +
Power Metering (DN2, DN3, DN4)
Motor Protection Release (DN0, DN2, DN3 -
Magnetic Protection only)
In 630 A
Switch Disconnector (DN2, DN3, DN4)
DN3-M
22
Accessories
Spreader Terminals 1
Phase Barriers 2
Undervoltage Release 3
Shunt Release 4
Auxiliary Contact 5
10 Panel Mounted Keylock
Direct Rotary Handle 8
Extended Rotary Handle 9
Stored Energy Electrically Operated Mechanism 11
Mechanical Interlock Kit 12
Communication Module 13
Voltage Module 14
Display Module 15
Trip Alarm Contact 6
Auxiliary + Trip Alarm Contact 7
External Neutral CT
(with Adaptor Kit)
16
8
2
1
3
4
12
16
9
10
11
1
2
5
6
7
13
14
15
23
Product Data
n
n
}
}
}
}
}
}
Technical Datasheet
Protection Releases
Motor Protection Application
Isolator Application
DC Application
Auto Source Transfer Application
MCCBs for Power Distribution
MCCBs for Different Applications
26
40
TM
C
40
25
100%
D
65
36
10 10
8 8
5 5
- -
50%
30000 30000
4000 4000
0.73 / 1 0.8 / 1.1
1 C / O or 2 C / O
240 / 415 Vac 50 Hz
Rated
Short
Circuit
Breaking
Capacity
I (
cu
kA)
240 Vac
415 Vac
500 Vac
550 Vac
600 Vac
690 Vac
I I
cs cu
as %
Mechanical
Electrical @1.0 In
Frame
Type
Release
Current Range (A)
Poles
Impulse Withstand Voltage (kV) U
imp
Rated Operational Voltage (V) (MAX) U
e
Rated Insulation Voltage (V) U
i
Utilization Category
Standard
Life
Operating Frequency (Hz)
Total Opening Time
Finger-proof Terminals
Suitable for Isolation
IP Protection
Pollution Degree
Load Line Bias
Ambient Temperature
Storage Temperature
Mounting Positions in Vertical Plane
Dimensions (WxDxH) mm
Weight (kg) (3/4 Pole)
A
C
C
E
S
S
O
R
I
E
S
INTERNAL
EXTERNAL
3-Pole
4-Pole
Auxiliary Contact
Trip Alarm Contact
Auxiliary & Trip Alarm Contact
Shunt Release
Under Voltage Release
Rotary Operating Mechanism (Direct/Extended)
Electrical Operating Mechanism
Mechanical Interlock Kit
Spreader Terminals
Key Lock
Neutral CT with Adaptor Kit
Current Metering Module
Display, Communication and Voltage Module
100A
DN0-100
20, 25, 32, 40, 50, 63, 80, 100
3/4
6
600
690
A
75 x 60 x 130
100 x 60 x 130

250 A
DN1-250
N
TM
100, 125, 160,
200, 250
3/4
6
600
690
A
65
50
10
8
5
-
50%
10000
3000
105 x 60 x 165
140 x 60 x 165
1.45 / 1.8

26
MCCBs for Power Distribution
$ :
* :
NO of control contactor to be connected in series for 220V DC application
Contains display module & metering module, separate cable required for connection
# : Only Extended ROM available
Note:
A
Separate earth fault module required for earth fault protection using TM releases
Rated ultimate short-circuit breaking capacity
Rated service short-circuit breaking capacity
Reference Temperature 40 C
ny two internal accessories can be mounted at a time
I
I
cu
cs
:
:
o
Technical Datasheet
400/630A
DN3-400
D
50
36
25
18
16
10
100%
N
70
50
36
25
18
15
100%
S
100
70
42
36
22
20
100%
D
50
36
25 25
15 15
12 12
8 8
100%
N
A
70
50
36
20
18
15
100%
S
100
70
42
25
22
20
100%
D
50
36
25
15
12
8
100%
N
70
50
36
20
18
10
100%
S
100
70
42
25
22
15
100%
N
70
50
25
20
16
10
100%
S
100
70
36
25
20
18
100%
TM/MP (MTX1.0/2.0/3.0)
320, 400
3/4
8
690
750
15000
4000
140 x 111.5 x 266
183.5 x 111.5 x 266
5.5 / 7.2
DN3-630
TM/MP (MTX1.0/2.0/3.0)
500, 630
3/4
8
690
750
A
15000
4000
140 x 111.5 x 266
183.5 x 111.5 x 266
6 / 7.8
1 C / O or 2 C / O
1 C / O
1 C / O + 1 C / O
110 / 415 Vac 50 Hz, 110 / 220 Vdc $
240 Vac 50Hz

DN3 -400
D
TM
320, 400
3/4
8
690
750
A
50
36
100%
10000
4000
140 x 111 x 205
184 x 111 x 205
4 / 5



250A
DN2-250
TM/MP (MTX1.0/2.0/3.0)
40, 63, 80, 100, 125,
160, 200, 250
3/4
8
690
750
A
25000
10000
105 x 96 x 179
140 x 96 x 179
2.5 / 3.3


800/1000/1250A
DN4-1250
MP (MTX1.0/2.0/3.0)
800, 1000, 1250
3/4
8
690
750
A
8000
750
#
210 x 143 x 370
278 x 143 x 370
16 / 20

IS/IEC 60947-2, IEC 60947-2, EN 60947-2


50 / 60
<10msec
Yes
Yes
IP40
III
No
-5 C to 55
O O
C
-35 to 70
O O
C C
Vertical and 90 in both directions
O
Available for 3P MCCBs with MTX2.0 & MTX3.0 release only
Available for MTX2.0 release for current metering only*
Available for MTX3.0 release for Communication & Power metering
<20msec
27
Microprocessor Release
Push to Trip button
Features of MTX1.0

inverse time delay


Adjustable Trip class
Short Circuit Protection with selectable
time delay
Provision of Thermal memory defeat
Port for release testing
Power ON LED
Self powered
True RMS sensing
Overload Protection with
Note: Factory Settings - O/L: 100% , Curves: 6 @10s, S/C: 5.5 @ Instantaneous

* Refer page 51
I I I
n r r
Release provides in-built instantaneous override protection fixed @ 10I
n
Thermal Memory: Off,
28
MCCBs for Power Distribution
MTX1.0
Short Circuit
Overload (Phase)
Rated Current, I
n
Current setting, ( = x ) I I I
r r n
Time delay, t (Inverse)
r
Protection mode
Thermal memory
Current setting, ( = x ) I I I
s s r
Protection mode
Time delay, t
s
From 40 to 1250A
40% to 100% in steps of 5% I
n
10s at 6 , 3s at 6 , 10s at 7.2 , 3s at 7.2 I I I I
r r r r
ON / OFF
Enable / Disable
1.5, 2.5, 4.0, 5.5, 6.5, 8.0I
r
ON / OFF
Instantaneous / 100ms
Thermal-Magnetic Release
Features of Thermal-Magnetic Release

Adjustable overload settings


Fixed / Adjustable short circuit settings
True RMS sensing
Push to Trip button
Protection
Overload
Short Circuit
Earth fault
DN0 & DN1
80% - 100%In
9In (fixed)
DN2 & DN3
80% - 100%In
6 - 10In
Settings
External GF Module required*
DN3
80% - 100%In
9In (fixed)
Microprocessor Release
Features of MTX2.0

Overload Protection with inverse time delay


Adjustable Trip class
Short Circuit Protection with
selectable time delay
Inbuilt Earth fault and
Neutral overload protection
Provision of Thermal memory defeat
Port for release testing
Power on LED
Panel mounted O-LED display for Current metering
Self powered
True RMS sensing
Push to Trip button
Note: Factory Settings - O/L: 100% , Curves: 6 @10s, S/C: 5.5 @ , Thermal Memory: Off, E/F: Off, Neutral: Off. I I I
n r r
Instantaneous
Release provides in-built instantaneous override protection fixed @ 10I
n
29
MCCBs for Power Distribution
Rated Current, I
n
Current setting, ( = x ) I I I
r r n
Time delay, tr(Inverse)
Protection mode
Current setting, ( = x ) I I I
N N r
Time delay, t
N
Protection mode
Current setting, ( = x ) I I I
s s r
Time delay, t
s
Protection mode
Current setting, ( = x ) I I I
g g n
Time delay, t
g
Protection mode
Thermal memory
From 40 to 1250A
40% to 100% in steps of 5% I
n
10s at 6 , 3s at 6 , 10s at 7.2 , 3s at 7.2 I I I I
r r r r
ON / OFF
50%, 100% and 150%I
r
200ms / Same as overload
ON / OFF
1.5, 2.5, 4.0, 5.5, 6.5, 8.0I
r
Instantaneous / 100ms
ON / OFF
20% to 50% in steps of 10% I
n
100ms / 200ms
ON / OFF
Enable / Disable
Overload (Phase)
Short Circuit
Overload (Neutral)
Earth Fault
MTX2.0
30
MCCBs for Power Distribution
Advanced features of MTX2.0
Panel Mounted Display for Current Metering
System currents & latest trip record can be viewed with
panel door closed.
Digital Current Metering
MTX releases are designed with protection class
CTs which measure true RMS values. Inbuilt
current metering does not require separate CTs
hence maintenance is no more tedious.

O-LED display allows the operator a wide


viewing angle
O-LEDs showing current metering has got faster
response time and also consumes less power,
saves more energy. It has better contrast ratio
also.
O-LED Display

MTX2.0 release with metering port is implemented with poka-


yoke technology using polarized connector to ensure correct
insertion of metering harness, thus avoiding unnecessary
errors.
Port with Polarized Connector
Metering Module
Display Module
31
MCCBs for Power Distribution

saving
Inbuilt EarthFault Protection
Thermal Memory
Inbuilt earth fault protection function does not require any separate trip coil & external CBCT, thus
panel space, cost & improving the overall hygiene. Earth fault protection limits expenses by preventing
damage toother equipment.
Thermal memory protects the system from thermal stresses generated by cumulative heating caused by
cyclic overloadconditions thus allowing the systemto return to a safe operating temperature. This function
also allows an optimization of cables or bus bar protection in case of low amplitude repetitive faults.
Advance trippingincreases the overall life andeliminates the productiondowntime incase of severe faults.

Enhances adjustability for better enhanced coordination with other devices to achieve correct motor
switchingandensures protectionof the starter elements inorder toguarantee the plant safety.
Overload & short circuit settings with minimum step change helps to maintain balance between nuisance
tripping and optimal protection resulting in high continuity of service and reduced call back periods. MTX
release canbe adaptedtospecific requirements of OEMor end-user.
DIP switches are provided on front side of the release for easy operations. These switches give you quicker
optiontoprecisely change selection, offeringhighlife.
Improves uptime and productivity by setting alarms for unbalanced loads so that proactive measures can
be takentoavoidoverloadconditions.
MTXreleases donot needany external power supply hence require noextra devices andwires topower up.
Multiple TripClass
Precise Selectionof Parameters
DIP Switches
OverloadIndication
Self Powered
30% Green LED
85% Faster blinking of green LED
115% Sequential ON/OFF of green LED
% of Ir Overload LED indication
1
2
3
4
Note: For wiring diagram, please refer page no. 62
1 3 2
4
I
n
s
t
@
6
I
r
@
7
.
2
I
r
1
0
s
3
s
In
s
t
@
6
Ir
@
7
.2
Ir
1
0
s
3
s
Overload Protection, ( = x ) I I
r n
Bypass
40% 45% 50% 55% 60% 65%
4
q
r
r
4
q
r
r
4
q
r
r
4
q
r
r
4
q
r
r
4
q
r
r
DIP Switch
Position
Setting
4
q
r
r
Bypass
ON
4
q
r
r
4
q
r
r
DIP Switch
Position
Setting
Thermal Memory
DIP Switch
Position
Setting
Overload Curves
3s @ 6I
r
10s @ 6I
r
3s @ 7.2I
r
10s @7.2I
r
4
q
r
r
4
q
r
r
4
q
r
r
4
q
r
r
DIP Switch
Position
Setting
Short Circuit Setting, ( = x ) I I
s r
1.5
In
s
t
2.5 4.0 5.5 6.5 8.0
In
s
t
In
s
t
In
s
t
In
s
t
In
s
t
Bypass
70% 75% 80%
4
q
r
r
4
q
r
r
4
q
r
r
85% 90% 100%
4
q
r
r
4
q
r
r
4
q
r
r
DIP Switch
Position
Setting 95%
32
MCCBs for Power Distribution
Various Protection Settings
4
q
r
r
In
s
t
33
MCCBs for Power Distribution
Instantaneous 100ms

DIP Switch
Position
Setting
Time Delay for Short Circuit Protection
Bypass
20% 30%

40% 50%

DIP Switch
Position
Setting
Earth Fault Setting, ( = x ) I I
g n
100ms 200ms

DIP Switch
Position
Setting
Time Delay for Earth Fault Protection
Bypass
50% 100% 150%


DIP Switch
Position
Setting
Neutral Setting, ( = x ) I I
N r


200ms


Follows O/L Curve
DIP Switch
Position
Setting
Time Delay for Neutral Protection
34
MCCBs for Power Distribution
* Can be set using display module
Microprocessor Release
Features of MTX3.0

Overload Protection with inverse time delay


based over load curves
Short Circuit Protection with selectable time delay
Instantaneous protection with fine settings
Advanced current and voltage based protection function
Protection against current unbalance and single phasing
Comprehensive current, power and energy metering
Inbuilt Earth fault and Neutral overload protection
Provision of Thermal memory defeat
Panel mounted O-LED display
MODBUS RTU & Bluetooth protocol
Wireless metering and
communication through Bluetooth
True RMS sensing
Power on LED
Push to Trip button
Self powered
I t, I t, SI, LI-VI
2 4
Current setting, ( = x ) I I I
N r N
Time delay, tN
Protection mode
Current setting, ( = x ) I I I
s s r
Time delay, ts
Protection mode
Preset trip alarm setting
Current setting, ( = x ) I I I
i i n
Protection mode
Preset trip alarm setting
Current setting, I I I
g g n
( = x )
Time delay, tg
Protection mode
Rated Current, I
n
Current setting, ( = x ) I I I
r r n
Time delay, tr(Inverse)
Protection mode
Preset trip alarm setting
Thermal memory
50% to 150% in steps of 1%* I
r
0.2s / same as overload
ON / OFF
1.5 to 8 in steps of 0.1* I
r
100ms, 200ms, 300ms, 400ms*
ON / OFF
50% to 90% in steps of 1%* I
s
1.5 to 8 in steps of 0.1* I
n
ON / OFF
50% to 90% in steps of 1%* I
i
10% to 50% in steps of 5%* I
n
100ms to 500ms in steps of 50ms*
ON / OFF
From 40 to 1250A
40% to 100% in steps of 1%* I
n
0.5s to 30s in steps of 0.1s*
ON / OFF
50% to 90% in steps of 1%* I
r
Enable/Disable
Short Circuit
Overload (Neutral)
Earth Fault
Instantaneous
MTX3.0
Overload (Phase)
Note:
Release provides in-built instantaneous override protection fixed @ 10In
Factory Settings - Address:0000, O/L: 100% , Curves: 6 @10s, S/C: 5.5 @ Instantaneous, Thermal Memory: Off, E/F: Off,
Neutral: Off.
I I I
n r r
MTX3.0 Additional features with Display Module
35
MCCBs for Power Distribution
Frequency Protection
Under Frequency
Over Frequency
Current Protection
Under Current
Current Unbalance
Frequency setting (Hz)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Frequency setting (Hz)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Current setting (A) ( = x I
ui
I I
ui r
)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Current setting (A)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Voltage setting (V) ( = x ) V V U
uv uv n
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Voltage setting (V) ( = x ) V V U
ov ov n
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Voltage setting (V)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Voltage setting (V)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Voltage Protection
Under Voltage
F-0.5 to F-5.0 in steps of 0.5
0.1 to 30 in steps of 0.1
ON / OFF
50 to 90% of set freq in steps of 1%
F+0.5 to F+5.0 in steps of 0.5
0.1 to 30 in steps of 0.1
ON / OFF
50 to 90% of freq in steps of 1% set
20 to 85% in steps of 1% I
r
1 to 255 in steps of 1
ON / OFF
110% to 150% in steps of 1% I
ui
30 to 90% in steps of 1% I
r
0.5 to 60 in steps of 0.1
ON / OFF
50 to 90% of set value in steps of 1%
45 to 80% in steps of 1% U
n
0.5 to 60 in steps of 0.1
ON / OFF
110 to 150% in steps of 1% V
uv
105 to 150% in steps of 1% U
n
0.5 to 60 in steps of 0.1
ON / OFF
50 to 90% in steps of 1% V
ov
5 to 20% in steps of 1% U
n
0.5 to 60 in steps of 0.1
ON / OFF
50 to 90% of set value in steps of 1%
5 to 40%U
n
in steps of 1%
0.5 to 60 in steps of 0.1
ON / OFF
50 to 90% of set value in steps of 1%
Over Voltage
Voltage Unbalance
Residual Voltage
36
MCCBs for Power Distribution
Lead Pf
Lag Pf
Power Protection
Reverse Power
0.5 to 0.99 in steps of 1%
100 to 500 in steps of 1
ON / OFF
50 to 90% of set value in steps of 1%
0.5 to 0.99 in steps of 1%
100 to 500 in steps of 1
ON / OFF
50 to 90% of set value in steps of 1%
1 to 5000kW in steps of 1kW
0.5 to 60 in steps of 0.5
ON / OFF
50 to 90% in steps of 1% P
R
Pf setting
Time delay (ms)
Protection Mode
Preset Trip Alarm setting
Pf setting
Time delay (ms)
Protection Mode
Preset Trip Alarm setting
Power setting (W) P
R
Time delay (s)
Protection Mode
Preset Trip Alarm setting
MD Active
MD Reactive
MD Apparent
Phase sequence
THD Current
1 to 5000kVA in steps of 1kVA
ON / OFF
50 to 90% of set value in steps of 1%
123 or 132
1 to 5 in steps of 0.1
ON / OFF
5 to 50% in steps of 1% I
r
5 to 15 in steps of 5
ON / OFF
50 to 90% of set value in steps of 1%
1 to 5000kW in steps of 1kW
ON / OFF
50 to 90% of set value in steps of 1%
1 to 5000kVAr in steps of 1kVAr
ON / OFF
50 to 90% of set value in steps of 1%
Demand settings
Protection Mode
Preset Trip Alarm setting
Phase seq setting
Time delay (s)
Protection Mode
Current setting (A)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Demand settings
Protection Mode
Preset Trip Alarm setting
Demand settings
Protection Mode
Preset Trip Alarm setting
Other Protection
37
MCCBs for Power Distribution
Advanced features of MTX3.0

One of the first steps towards energy efficiency is energy and power measurement. In MTX3.0 release, in
additiontocurrent & voltage measurement, active, reactive and apparent energy & power can also be
measured. This wouldenable monitoringenergy at individual feeder level and thus help in implementing
effective energy management practices in the plant. Moreover, using communication module, different
parameters readings canbe viewedondisplay module.
Energy &Power measurement
History
THD voltage
Metering & Display
Communication
Voltage setting (V)
Time delay (s)
Protection Mode
Preset Trip Alarm setting
Current
Voltage
Frequency & power factor
Power
Energy
Protocol
Event History
Trip History
5 to 50% in steps of 1% U
n
5 to 15 in steps of 0.1
ON / OFF
50 to 90% of set value in steps of 1%
Phase, Neutral & Earth
Phase & Line
True RMS
Active, Reactive & Apparent
Active, Reactive & Apparent
MODBUS RTU & Bluetooth
Last 10 event records with non volatile memory
Last 10 trip records with non volatile memory
Other Protections
Energy and Power management functionality using voltage module
Display Module Power Supply
Module
Communication
Module
MCCB with MTX3.0 release
Voltage
Module
3 ph 4 wire
AC supply
38
MCCBs for Power Distribution
Reverse Phase:
This function detects the phase reversal of current from
the set sequence. It is especially important in motor
feeder applications
One can set the direction of power flow in a system from
source to load and in case the direction of power flow
reverses, the reverse power protection can be activated to
trip the system. This is especially important in a DG set or
ina ringmains system.
Reverse Power:

MTX3.0 release measures the frequency, power factor and


offers protection against leading and lagging values thereby
assisting in maintaining the power quality. This release
measures THDof current &voltages andgives an alarm/ trip in
case it exceeds the set thresholds.
Power Quality Control
CommunicationCapable
Most advanced release of MTX series, MTX3.0 is communication capable on MODBUS RTU network. Using
MODBUS com module the MCCB release can be connected to a Personal Computer. All metering values of
MCCB can be read and changed remotely. These releases are also made compatible with HMI (Human Machine
Interface) &DCS (Data Control Systems)
Convertor
(RS485 to RS232)
Laptop or HMI
Wireless RemoteDisplay(Bluetooth)
Wireless display module based on
Bluetooth technology, eliminates the need
of wiring between the MCCB and the
display unit on the door.
Communication
through Bluetooth
Advanced Current and Voltage based protections
3 ph 4 wire
AC supply
3 ph 4 wire
AC supply
39
MCCBs for Power Distribution
Multi-looping
Note: For wiring diagram, please refer page no. 63
A single display module can be connected to 15 MCCBs with MTX3.0 releases through MODBUS network.
Highly reliable data yet extremely simple looping reduces operational headaches and enhances
remote accessibility.
MODBUS Communication through MODBUS looping
Maintenance functionality
MTX3.0 release can store last 10 trip records & last 10 event records which can be used for the system
analysis later on. These recordedvalues canbe viewedfromdisplay unit as well as PC.
Convertor
(RS485 to RS232)
Laptop or HMI
DN3-M
Motor ProtectionApplication
Selection of MCCB using our Type 2 charts give reliable
performance of the motors.
AC induction motors are the vital elements in any production process and hence constitute majority of
loads in Industry and other installations. The M version MCCBs in dsine range are developed specially to
give short circuit protection for all types of motors.
40 MCCBs for Different Applications
Isolator Application
dsine MCCBs with Switch Disconnector version offer solution for switching various loads such as UPS,
Battery Banks etc. with various advantages. These MCCBs differ from regular MCCBs only in terms of
absence of protectiontripunits. These MCCBs canbe usedfor many applications for isolationpurpose.
For local isolation- suchas very close toMotor load
Generally usedat the incomingof any sub-distribution
As anIsolator for Bus coupler
As anautomatic switch
For switchingapplications of motors withVFDs, soft starters
Followingare the specifications of SDMCCBs

SD MCCBs are always backed up by the Short Circuit Protection Device (SCPD) to protect downstream
loads/installations against short circuit. Our dsine SDMCCBs offer followingadvantages.
Suitable for Positive isolation
Available with3P &4P versions
Canbe usedwithUnder Voltage Protection
Remote trippingthroughShunt release
Motor operatedMCCBs
Status feedback possible
Note: cw - Rated short-time withstand current
* To be set at 10In only
I
Frame 100A 250A 400A 630A
Type DN0-100M DN2-250M DN3-400M DN3-630M
Current Range (A) 32-100 100-250 320-400 500-630
Poles
3P
I
cu
(kA) at 415 Vac, 50 Hz 50
Magnetic Setting 9I
n
6-10 * I
n
250A 400A 630A 800A 1000A 1250A
DN2-250SD DN3-400SD DN3-630SD
1000
DN4-1250SD
1250 100-250 320-400 500-630 800
3/4 3/4 3/4 3/4 3/4 3/4
Frame
Type
Current Range (A)
Poles
I
cw
(kA) 3.6 5.5 5.5 10 12 15
1 1 1 1 0.5 0.1 Duration (sec)
41 MCCBs for Different Applications
DCApplication
DC power distribution is an upcoming technology in this modern era due to its most rigorous network
power applications suchas
AC-DCPower System
DC-DCConverter Systems
DC-ACInverter Systems
DCUPS
Batteries &Accessories
Solutiontoalternative energy-Solar Power
We offer dsine MCCBs for the protection of DC systems in variety of current ratings from 20A-630A, voltage
ratings upto500Vandvarious breakingcapacities rangingfrom5kAto36kA.
Switching of DC currents is much severe phenomenon than switching AC currents due to non occurrence
of natural zero. Hence DC MCCBs are desired to give less breaking capacity than AC MCCBs for the same
voltage & currents. As per the earthing of the system, we recommend following connections for breaking
the fault currents.
Any one polarity is earthed Midpoint of the system is earthed No earthing
Earthed system Insulated system
No. of poles required to
perform the break must
be in series on one polarity
No. of poles required to
perform the break must
be on both the polarities
No. of poles required to
perform the break can be
shared between two polarities
+
-
2
5
0
/
5
0
0
V
LOAD
+
-
2
5
0
/
5
0
0
V
+
-
2
5
0
/
5
0
0
V
Earthed system
LOAD LOAD
3P in series
<15msec
100A
Type
Frame
Number of poles
Rated Voltage (Vdc)
I
cu
(kA RMS)
Type of connection
L/R (msec)
Rated current In (A)
DN1-250N
3/4
250
15
500
10
100, 125, 160,
200, 250
250
15
500
10
DN0-100C/D
3/4
20, 25, 32, 40,
50, 63, 80, 100
DN2-250D/N/S
3/4
100, 125, 160,
200, 250
250
15/25/36 5/10/20
500
DN3-400D/N/S
3/4
320, 400
15/25/36
250
5/10/20
500
DN3-630D/N/S
3/4
500, 630
15/25/36
250
5/10/20
500
250A 400A 630A
DN3 400D -
10
500
320, 400
3/4
250
25
Note: Suitable for Thermal Magnetic release only
42

Motorised MCCBs
Mechanical Interlocking device (usually a base plate)
Automatic Transfer Controller
The AuXC-1000 controller brings simplicity and flexibility to an auto source transfer system. It has been
developed to control and supervise the automatic or manual transfer of a utility load from a principal
power supply source to a stand-by and vice-versa. It sets a newbenchmark in Auto Source Transfer Switch
Controller technology. It includes all the necessary features to supervise and control power supply sources,
composed by energy distribution systems or generating sets, and the relative transfer equipment, such as
contactors, motorizedmouldedcase circuit breakers andair circuit breakers.
AutoSource Transfer Application
ASTS solution basically consists of
ASTS withAuXC-1000 controller
In this modern era of automation, ASTS (Automatic Source Transfer Systems) are very widely used in many
places suchas commercial buildings, IT parks for quick changeovers and also in Utilities for uninterrupted
supplies for critical loads.
These solutions can give you optimum energy management.

MCCBs for Different Applications


Note: For wiring diagram, please refer page no.60
Key features:
Utility-to-utility, utility-to-generator or generator-to-generator changeover possible
Three-phase, two-phase or single-phase voltage controls
Controls of minimum voltage, maximum voltage, phase loss, asymmetry, minimum frequency,
maximum frequency, with independent enable and delay
Voltage thresholds with programmable hysteresis
Manual control of Circuit Breakers
Main line failure simulation
Communication Capable
Front display for monitoring the system voltage and frequency and for onsite controller
programming
Six programmable inputs and five programmable outputs
Front test feature to simulate the operation of the diesel generator set
Status indication through 22 LEDs
Flush mounting arrangement

MIL with Base Plate & EOM


+
AuXC-1000
43
With the newAuXC-1000L controller in addition to its predecessor, ASTS have just become lot simpler &easier.
Some of the salient features of the controller are as follows:
Utility-to-utility, utility-to-generator changeover facility
Single supply input frombattery supply 12-48VDC
Display toviewmainandsecondary line parameters
15 status LEDindicators
6 programmable digital inputs
3 programmable relay outputs
RS232 communicationinterface
Modbus RTUandModbus-ASCII communicationprotocols
Status display of circuit breakers
Emergency demandsupervisionparameter programmingfor standby generator sets
Event logging
Alarmcode &descriptiondisplay
The automatic transfer takes place through AuXC-1000L / AuXC-1000 whenever following conditions are
predefinedby the user
SystemVoltage not inline withprogrammedlimits
The needtohave a very reliable power source
The needtouse the most economical power source
These controllers are compatible with U-POWER OMEGA range of Electrical ACBs, dsine range of Motorized
MCCBs andMCXrange of contactors.
MCCBs for Different Applications
ASTS with AuXC-1000L Controller Smarter, Simpler, Easier
MIL with Base Plate & EOM
+
AuXC-1000L
Accessories
n
n
Internal accessories
External accessories
- Auxiliary Contact
- Trip Alarm Contact
- Auxiliary Trip Alarm Contact
- Shunt Release
- Under Voltage Release
- Rotary Operating Mechanism
- Mechanical Interlocking Kit
- Keylock
- Spreader Terminals
- External Neutral CT
- Stored Energy Electrically Operated
Mechanism
46
47
- MTX Modules
- Earth Fault Module
46 Accessories
Internal Accessories
Frame
DN0, DN1
DN2, DN3, DN4 DN3 ,
DN0, DN1
DN2, DN3, DN4 DN3 ,
DN0, DN1
DN2, DN3, DN3 , DN4
DN0, DN1
DN0, DN1
DN2, DN3, DN3 , DN4
DN0, DN1
DN2, DN3, DN3 , DN4
DN0, DN1
DN2, DN3, DN3
DN4
Contacts/Supply Voltage
1 C/O
1 C/O + 1 C/O
2 C/O
2 C/O
1 C/O
240/415V AC 50Hz
110/415V AC , 110/220V DC 50Hz
240V AC
Cavity
Right
Right
Right
Right
Right
Right
Right
Right/Left
Right/Left
Right/Left
Left
Left
Internal Accessories
Auxiliary Contact
Trip Alarm Contact
Under Voltage Release
Shunt Release
Auxiliary + Trip Alarm Contact
Shunt Release
It allows opening of MCCB by means of an electrical command. Operation of the release is guaranteed for a
voltage between70%and110%of the ratedpower supply voltage value Ue, bothinAC&DC.
Note: Low VA Shunt Release available
Frame
240 / 415V AC, 50Hz Dn0 / DN1
Operational Voltage Power Consumption
1500VA
110 / 415V AC, 50Hz
DN2 / DN3 /
DN3 / DN4
110 / 220V DC 85W
1500VA
Shunt Release UV Release Auxiliary Contact TAC
MCCB with mid cover opened & Internal
accessories fitted
dsine range of MCCBs are offered with -fit type, easily
installable internal accessories. There is no need to open main
cover and no live parts are accessed during installation. TAC,
Aux+TAC to be fitted in the right cavity & under voltage
release tobe fittedinleft cavity.
snap
The internal accessories are housed in
insulated casingsto ensurefirst level of insulation. Whenthe front
coverisopenedfor thefixingof internal accessories, the MCCB is
totallyinsulatedensuring thedoubleinsulation.
Double Insulation:
47 Accessories
UVRelease
The Under-voltage release causes the MCCB to trip if the operational voltage falls to a value between 35%and
70%of its ratedvoltage or not applied. UVrelease mechanically locks the closingmechanismof MCCB &makes
it impossible to close on under-voltage or no voltage, both manually & electrically. With the under-voltage
release de-energized, it is not possible to close the MCCB. UV release can also be used for interlocking schemes
(for DGsynchronization, parallelingof transformers etc) also.
240V AC, 50Hz
Operational Voltage
240V AC, 50Hz
240V AC, 50Hz
Frame
DN0 / DN1
DN2 / DN3 / DN3
DN4
Power consumption
5VA
5VA
5VA
1. Direct Rotary Handle (MCCBmounted)
These versions are available for the entire family of MCCBs with in-built
padlockingfeature.
dsine
External Accessories
Rotary OperatingMechanism
Rotary Operating Mechanism (ROM) for MCCBs are available in Direct &
Extendedversions.
dsine
2. Extended Rotary Handle (Panel Mounted)

Clear ON/OFF/TRIP indication

ROM mounts directly on MCCB without


removal of mid cover
Clear view of MCCB rating label
Direct access to Push to Trip button
IP 54 degree of protection with
extended rotary handle
Unique coupling to allow 3mm tolerance
Door interlock in ON position,
with defeat facility
Door interlock in OFF condition
with padlock feature
Auto restoration of door interlock
External keylock for mechanical interlocking
Direct Rotary Handle
(MCCB mounted)
Extended
Rotary Handle:
Panel Mounted
Panel Door Mounted
Key lock (To be used along
with Extended Rotary Handles)
48 Accessories
Lock 1
Incommers
(I/C)
Bus couplers
(B/C)
I/C
1
I/C
2
I/C
3
B/C
1
B/C
2
Lock 2 Lock 3
Lock 12 Lock 23
Type of lock
1
2
3
12
23
Exclusively operable by Key Nos.
1
2
3
1, 2 & 12
2, 3 & 23
Note: Phase barriers are supplied along with MCCBs ; Copper termination recommended for enhanced performance
Mechanical Interlocking Schemes
Key Lock Selection:
1. Mechanical Interlocking Kit:
2. Mechanical Interlocking using Key Locks:
Two MCCBs can be interlocked using base plate mechanism,
in side-by-side configuration.
For 3P & 4P versions
For DN2 & DN3 frames
Site fittable
For mechanical interlocking through extended
rotary operating mechanism, a panel mounted
key lock is available. The selection of the key
lock as per the table:
Features
MIL with Base Plate
Any 1 type of lock for both MCCBs
Lock 1 and Lock 2 for I/C and Lock 12 for B/C
Locks 1, 2, 3 for I/Cs and Locks 12, 23 for B/Cs
2 l/C
2 I/C and 1 B/C
3 I/C and 2 B/C
I/C or B/C Key Lock
Spreader Terminals
Used for enhancing termination capacity
Made of silver plated copper
Terminal capacity without spreader terminals
800-1250 320-630 125-250 16-100
Cable (mm )
2
35
Link(mm)
17
Cable (mm )
2
120
95
Link(mm)
<26
25
dsine Frame
Rating (A)
DN0
DN1
DN2
DN3
DN3
DN4
Cable (mm )
2
-
Link(mm)
2X40
Cable (mm )
2
120
185
Link(mm)
27
<32
Terminal capacity with spreader terminals
Link(mm) Cable (mm )
2
Link(mm) Cable (mm )
2
Link(mm) Cable (mm )
2
Link(mm) Cable (mm )
2
800-1250 320-630 125-250 16-100 Rating (A)
50 22
185
185
35
35
2X180 2X40
DN0
DN1
DN2
DN3
DN3
DN4 2X300 2X60
2X240 2X40
dsine Frame
Power Supply(PS) Module
PS module is used to power ON dsine MTX modules when
auxiliary 24Vdc supply is not available.
Specifications AC DC
Input
Output 1
Output 2
85-265V 125-300V
- 650mAat 24VDC
- 200mAat 24VDC
#
#
For using Output 2, Output 1 should be loaded
49 Accessories
Note: For wiring diagram, please refer page no. 63
* At rated voltage
Specification
Operating voltage (V AC)
Operating voltage (%)
Closing time (ms)
Opening time (ms)
Power consumption (VA)
Life / No. of operations
Door cut out (mm )
2
IP protection, on the front
Operating frequency
Min. control impulse time (ms)*
240
85-110%
90
450
500
15000
96x96
IP30
1/min
450
DN3
240
85-110%
60
300
350
16000
96x96
IP30
2/min
300
DN2
Stored Energy Electrically Operated Mechanism

ON / OFF & Charged/Discharged indication


Foolproof mounting
Selector switch for Auto/Manual operation
Padlock facility for locking in OFF position (3 nos. locks)
Higher mechanical & electrical endurance
Back up fuse for extended motor protection
Easy access to the protection setting on MCCB
True indication for ON/OFF & Trip
External Neutral CTs

Used to provide neutral protection to 3P MCCBs in 3 phase 4 wire system


Available for 3P MCCBs with MTX2.0 & 3.0 releases
Adapters for NCT available
50 Accessories

It consists of 2 parts viz. Metering module & Display module. Metering module collects the data from the
release and sends the same to the Display module. The panel mounted O-LED Display module shows
various parameters viz. 3 phase currents, neutral and ground fault currents, if any. We can also viewlast trip
records.
Current MeteringModulefor MTX2.0

The communication module is the solution for connecting


dsine MCCBs to a Modbus network for remote supervision and
control of circuit breaker. It is suitable for the MTX3.0
electronic trip units across DN2/DN3/DN4 frames. It is available
with DIN rail mounting facility. 2 LEDs in front of the module
indicates
The Power LED -the presence of auxiliary power supply to
the module.
The Data LED - transmission of data.
Its operating temperature is -25 C to 70 C and
consumption is 43mA.
Communication Module for MTX3.0
O O

This accessory when connected to MTX3.0 release in


DN2/DN3/DN4 frames is able to provide the various
measurements of the electrical values of the plant. It has to be
mounted just beside the MCCB on a DIN plate. Its operating
temperature is -25 Cto70 C.
VoltageModulefor MTX3.0
O O
Note: For wiring diagram, please refer page no. 63
MTX Test Kit

Universal Test Kit for all MTX releases


Simulation of overload, short-circuit & earth fault
Single phase AC supply

It is a panel mounted O-LEDdisplay unit that can be integrated


with MTX3.0 release in DN2/DN3/DN4 frames. It has one
navigation key, a select button & an exit button. Its operating
temperature is -25 Cto70 Candconsumptionis 12mA.
Phase current, ground current, earth leakage current
Phase / Line voltage
Active / Reactive / Apparent Power
Power factor, Frequency
Energy
DisplayModulefor MTX3.0
O O
The module displays wide range of parameters
as follows
51 Accessories
Earth Fault Modules Type GF1, GF2 and GF11.
These modules are to be used with MCCBs for
earth fault protection. The principle of operation
is based on detection of the residual current in
the system. They combine safety and versatility,
conforming to the high performance standards,
the characteristic of all L&T products.
Features:
Compact in size
Solid state design.
Built-in moulded CBCT for GF1 & GF2.
External CTs are to be used for GF11.
Suitable for both 3 phase 3 wire & 3 Phase 4
wire systems.
Built-in test facility.
Selection facility for nominal current rating (In).
Earth fault setting is adjustable from 10% to
50% of set current
Selectable trip times (100 ms, 200 ms).
Manual reset for positive fault
acknowledgment.
Potential free NO contact to trip MCCB
(through 240 V shunt release).
Window dimensions suitable for
Cable / Link connection in GF1 and GF2.

In case of 3 phase 4 wire


system, the neutral cable/twisted link should
also be passed through the CBCT along with
the 3 phase links / cables.

Note: MCCBs need to be fitted with 110 V / 240 V AC shunt


release for Earth Fault Module operation.
Earth Fault Module
Note: For wiring diagram, please refer page no. 61
10% to 50%In in steps of 10%
240V AC 20%
100 / 200ms Field selectable
10% Is
1 NO contact manual reset Type
contact rating 5A 240V AC
a) Power On LED
b) Trip LED (manual reset)
+10 C to +55 C
0 0
2 kV 50Hz for one minute across independent circuit
1 kV 50Hz for one minute across open contacts
Base plate mounting type
GF1 - 110 x 32
GF2 - 165 x 61.5
GF1 - 1.2, GF2 - 2.2, GF11 - 0.9
Type GF1 / GF2 / GF11
Current Setting Range, Is(Is=x In)
Auxiliary Supply
Time Delay (ms)
Pick-up Accuracy
Output Contact
Indication
Operating Temperature
Insulation
Mounting
Window for Cable / Busbar entry (mm )
2
Weight (kg)
Specification
Earth Fault Module GF1
GF1 is suitable upto 200A MCCBs
Earth Fault Module GF11
GF11 is suitable upto 800A MCCBs
Earth Fault Module GF2
GF2 is suitable upto 250A-400A MCCBs
Technical Data
Characteristic Curves
n
n
}
}
}
}
}
}
}
DN0
DN1
DN2
DN3
DN3
MTX1.0/2.0 (O/L curves)
- at 6 , 7.2
MTX3.0 (O/L curves)
- at 1.5 , 6 , 7.2
- at 1.5 , 6 , 7.2
- at 1.5 , 6 , 7.2
- - at 1.5 , 6 , 7.2
- Short circuit, Earth fault & Neutral
curves for MTX1.0/2.0/3.0
Thermal Magnetic Release
Microprocessor Release

I T I I
I T I I I
I T I I I
SI I I I
LI VI I I I
2
2
4
r r
r r r
r r r
r r r
r r r
54
55
DN3 MCCB
Current multiples (x ) I
n
10
-1
1 10 10
2
10
3
0.001
0.01
0.1
1
10
100
1000
10000
6-10I
n
T
r
i
p

T
i
m
e

(
s
)
t<10ms
Current multiples (x ) I
n
t < 10 ms
9I
n
0.001
10
-1
1 10
2
10
3
10
0.01
0.1
10000
1000
100
10
1
T
r
i
p

T
i
m
e

(
s
)
DN3 MCCB DN2 MCCB
Current multiples (x ) I
n
10
-1
1 10 10
2
10
3
0.001
0.01
0.1
1
10
100
1000
10000
6-10I
n
T
r
i
p

T
i
m
e

(
s
)
t<10ms
54
Characteristic Curves
Thermal-Magnetic Release
Note: Curves are Ir based till overload zone.
DN1 MCCB
10
-1
1 10 10
2
10
3
0.001
0.01
0.1
1
10
100
1000
10000
9I
n
Current multiples (x ) I
n
T
r
i
p

T
i
m
e

(
s
)
t<10ms
DN0 MCCB
9I
n
10
-1
1 10 10
2
10
3
0.001
0.01
0.1
1
10
100
1000
10000
Current multiples (x ) I
n
T
r
i
p

T
i
m
e

(
s
)
t<10ms
55 Characteristic Curves
Microprocessor Release
0.1
1
10
100
1000
10000
1 10
10s
3s
Current multiples (x ) I
r
I T
2
@ 6Ir
T
r
i
p

T
i
m
e

(
s
)
0.1
1
10
100
1000
10000
1 10
10s
3s
Current multiples (x ) I
r
I T
2
@ 7.2Ir
T
r
i
p

T
i
m
e

(
s
)
MTX1.0 / 2.0 - DN2 / DN3 / DN4 (O/L curves - ) I t
2
30s
20s
10s
0.01
0.1
1
10
100
1000
1 10
5s
3s
I T I
2
@ 1.5
r
Current multiples (x ) I
r
T
r
i
p

T
i
m
e

(
s
)
0.1
1
10
100
1000
10000
1 10
30s
20s
10s
5s
3s
I T I
2
@ 6
r
Current multiples (x ) I
r
T
r
i
p

T
i
m
e

(
s
)
10000
0.1
1
10
100
1000
1 10
30s
20s
10s
5s
3s
Current multiples (x ) I
r
I T I
2
@ 7.2
r
T
r
i
p

T
i
m
e

(
s
)
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - ) I t
2
56 Characteristic Curves
Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - ) I t
4
T
r
i
p

T
i
m
e

(
s
)
0.1
1
10
100
1000
10000
100000
1 10
30s
18s
10s
6s
3s
Current multiples (x ) I
r
I T
4
@7.2I
r
0.1
1
10
100
1000
10000
100000
1 10
30s
18s
10s
6s
3s
Current multiples (x ) I
r
I T
4
@ 6I
r
T
r
i
p

T
i
m
e

(
s
)
0.01
0.1
1
10
100
1000
1 10
30s
18s
10s
6s
3s
Current multiples (x ) I
r
I T I
4
@ 1.5
r
T
r
i
p

T
i
m
e

(
s
)
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - ) Short Inverse
T
r
i
p

T
i
m
e

(
s
)
1
10
100
1 10
30s
24s
12s
4s
Current multiples (x ) I
r
SI I @ 7.2
r
1
10
100
1 10
30s
24s
12s
4s
Current multiples (x ) I
r
SI I @ 6
r
T
r
i
p

T
i
m
e

(
s
)
1
10
100
1 10
30s
24s
12s
4s
Current multiples (x ) I
r
SI I @1.5
r
T
r
i
p

T
i
m
e

(
s
)
57 Characteristic Curves
* Only Short Circuit setting available in MTX1.0
Under Short Circuit fault conditions, MCCBs will clear the fault in less then 10 msec
Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4
(O/L curves - Long Inverse / Very Inverse)
0.1
1
10
100
1 10
Current multiples (x ) I
r
30s
24s
12s
4s
LI-VI I @ 1.5
r
1
10
100
1000
1 10
Current multiples (x ) I
r
30s
24s
12s
4s
LI-VI @ 6I
r
30s
24s
12s
1
10
100
1000
1 10
Current multiples (x ) I
r
4s
LI-VI @ 7.2I
r
T
r
i
p

T
i
m
e

(
s
)
T
r
i
p

T
i
m
e

(
s
)
T
r
i
p

T
i
m
e

(
s
)
Invs
OFF*
MTX1.0* / 2.0 / 3.0 (S/C, E/F & Neutral Curves)
Inst
100ms
200ms
300ms
400ms
1 10
1
0.1
0.01
1.5 8
For MTX3.0 only
Short Circuit Curves
1
0.1
0.01
0.1 1
200ms
100ms
500ms
For MTX3.0 only
0.2 0.5
Earth Fault Curves
Current multiples (x ) I
r
Current multiples (x ) I
n
Current multiples (x ) I
r
0.1 1 10
*: IDMT disable in case of MTX3.0
0.5 1.5
0.01
0.1
1
200ms
Neutral Curves
T
r
i
p

T
i
m
e

(
s
)
T
r
i
p

T
i
m
e

(
s
)
T
r
i
p

T
i
m
e

(
s
)
Wiring Diagrams
n
n
n
n
Motorised Circuit Breakers Control
through AuXC - 1000 & AuXC - 1000L
Earth Fault Modules
MTX2.0 with Current Metering Display
MTX3.0 with Communication
through Modbus
60
61
62
63
60 Wiring Diagrams
Motorised Circuit Breakers Control through AuXC - 1000L
Motorised Circuit Breakers Control through AuXC - 1000
1
.
1
1
.
2
1
.
3
2
.
1
2
.
2
2
.
3
3
.
1
3
.
2
3
.
3
3
.
4
3
.
5
3
.
8
3
.
7
3
.
6
4
.
5
4
.
4
4
.
3
4
.
2
4
.
1
4
.
6
4
.
7
4
.
8
5
.
2
5
.
1
5
.
3
9.4
9.3
9.2
9.1
8.4
8.3
8.2
8.1
7.1
7.2
DIGITAL INPUT S SUPPLY
DC
+
_ _
L1 L2 L3 N
LINE 1
L1
LINE 2
L3 L2 N
L2 L1 L3 N
LOAD
Q2 Q1
K2
K2 K1
K1
K2 K2 K1 K1
QF1
QF2
WITHDRAWN
C
L
O
S
I
N
G
P
O
W
E
R

S
U
P
P
L
Y
I
N
T
E
R
L
O
C
K
O
P
E
N
I
N
G
T
R
I
P
SE-EOM Q1
3 1
5
4 2
C
O
M
M
O
N
WITHDRAWN
C
L
O
S
I
N
G
P
O
W
E
R

S
U
P
P
L
Y
I
N
T
E
R
L
O
C
K
O
P
E
N
I
N
G
T
R
I
P
SE-EOM Q2
3 1
5
4 2
C
O
M
M
O
N
S
T
A
T
U
S
S
T
A
T
U
S
Parameter setting
for the wiring diagram in picture.
Contactors
Mechanical
Interlocking
Circuit Breaker
(Q1, Q2)
MCB
1.1
1.3
2.1
2.3
4.1
4.2
4.3
4.4
Terminal
P6.01
P6.02
P6.03
P6.04
P5.01
P5.02
P5.03
P5.04
Parameter code
Setting
OP.1
CL.1
OP.2
CL.2
Fb.1
Fb.2
Tr.1
Tr.2
3 1 4 2
5
C
L
O
S
I
N
G
P
O
W
E
R

S
U
P
P
L
Y
I
N
T
E
R
L
O
C
K
O
P
E
N
I
N
G
T
R
I
P
C
O
M
M
O
N
S
T
A
T
U
S
3 1 4 2
C
L
O
S
I
N
G
P
O
W
E
R

S
U
P
P
L
Y
I
N
T
E
R
L
O
C
K
O
P
E
N
I
N
G
T
R
I
P
C
O
M
M
O
N
S
T
A
T
U
S
5
Contactors
Mechanical
Interlocking
Circuit Breaker
(Q1, Q2)
MCB
4.1
4.3
5.1
5.3
2.1
2.2
2.3
2.4
Terminal
P6.1.1
P6.2.1
P6.3.1
P6.4.1
P5.1.1
P5.2.1
P5.3.1
P5.4.1
Parameter code
Setting
OP.1
CL.1
OP.2
CL.2
Fb.1
Fb.2
Tr.1
Tr.2
Parameter setting
for the wiring diagram in picture.
DIGITAL INPUT S
RS232
61 Wiring Diagrams
Earth Fault Modules
GF1 & GF2
R Y B N
FROM MCCB
SENSING
CIRCUIT
RELAY
RECTIFIER
TO LOAD
240 Vac
MCCB
SHUNT
RELEASE
AUX.
SUPPLY
240 Vac
1
2
5
3
4
L
N
TO LOAD
S1
S2
S1
S2
S1
S2
S1
S2
R Y B N
FROM MCCB
CT Sec.
SENSING
CIRCUIT
RELAY
240 Vac
MCCB
SHUNT
RELEASE
1
2
5
3
4
L
N
RECTIFIER
AUX
SUPPLY
240 Vac
GF11
62 Wiring Diagrams
MTX2.0 with Current Metering Module
Display Module
Metering
Module
L
N
240 Vac
50 Hz
Auxiliary
Power Supply
Module
MTX2.0 Release
In
s
t
to other
MTX2.0
24 Vdc
63 Wiring Diagrams
MTX3.0 with Communication through Modbus
Display Module
Communication
Module
Auxiliary
Power Supply
Module
Laptop / SCADA
System
L
N
240 Vac
50 Hz
D+
Gnd
D-
Convertor
+Vs
RS232 RS485
Inst
MTX3.0 Release
Voltage Module
3 Phase
415 Vac Supply
24 Vdc 24 Vdc
Dimensions
n
n
}
}
}
}
}
}
}
}
}
}
}
}
}
}
DN0
DN1
DN2
DN3
DN4
Rotary Operating Mechanism
Stored Energy Electrically
Operated Mechanism
Panel Mounted Key Lock
MTX Modules
Auto Source Transfer Switch: AuXC-1000
and
Dimensions of MCCB
Dimensions of Accessory
66
72

DN3
Mechanical Interlock Kit
External Neutral CTs
AuXC-1000L
Earth Fault Modules
All dimensions are in mm
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity
DN0-100 MCCB
DN0-100 with Spreader Links
66
Dimensions of MCCB
Recommended cat. nos.
for DN0 spreaders
4P
CM97921OOOO
3P
CM97785OOOO
25 25 25
25 25 25 12.5
1
3
0
1
1
6
.
4
1
1
2
100(4P)
75(3P)
N
7
5
86
64
60
6
2
.
5
6
5
.
5
5
8
6
1
.
5
3
8
4
5
Mounting &
Door Cut-out Details
29.5
2.25
4
8
.
5
5
2
3
9
4
6
1
1
2
50.5 50.5
101
CUT OUT 1
MCCB MOUNTING HOLES
M3 SCREW 6 Nos.
CUT OUT 2
76
27.25
N
25.5
25 25
13 13
92
1
7
2
.
2
1
9
4
.
2
22
9
35 35
2
8
1
1
N
2
8
1
1
127.2
35 35 35
22
3
0
.
2
1
7
2
.
2
1
9
4
.
2
13 13 13 8.5
7
5
86
64
60
2
3
2
20
6
2
.
5
6
5
.
5
2
20
3
2
.
2
5
8
6
1
.
5
3
8
4
5
67 Dimensions of MCCB
DN1-250 with Spreader Links
All dimensions are in mm
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity
Recommended cat. nos.
for DN1 spreaders
3P
ST98053OOOO
4P
CM92007OOOO
10.2 19.5 19.5
54.5 54.5
2
2
1
2
5
7
3
8
1
8
35
144
18
4
6
4
6
18
64.5
60
4
4
93.7
4
5
7
8
.
6
5
9
5
.
7
Mounting &
Door Cut-out Details
1
2
6
35 35
141
5
8
.
6
4
6
70.5 70.5
17.5 17.5
88 53
MCCB MOUNTING
HOLES 6 Nos.
2 5 0 - 4 P
2 5 0 - 4 P
N
250-4P 250-4P
54 54 54
2
5
7
1
4
7
10.2
18
4
7
.
5
4
7
.
5
35
2
2
1
197
19 19 19
DN1-250 MCCB
64.5
60
93.7
4
5
7
8
.
6
5
9
5
.
7
N
35
35 35 17.5
1
4
5
1
6
5
140 (4P)
35 35 35
1
2
6
105(3P)
144
54.5 54.5
2
7
5
2
3
9
3
8
1
8
19.5 19.5
35
10.2
4
1
19 19 19
2
7
5
2
3
9
10.2
54 54 54
197
1
8
38
35
N
28.65
4
7
2
.
7
45
A
4
4
8
96.5
4
8
119.57
8
9
.
2
7
68
Dimensions of MCCB
DN2-250 MCCB
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity.
DN2-250 with Spreader Links
All dimensions are in mm
4P
CM92007OOOO
3P
ST98053OOOO
Recommended cat. nos.
for DN2 spreaders
Rating
125-250A TM
63-100A TM
32-50A TM
MTX breakers
Dimension (A)
26
25.5
26.25
28
35 35 35
140(4P)
17.5
8
35 35 35
1
7
9
1
6
3
1
5
7
105(3P)
N
7
2
.
7
45
96.5
119.57
8
9
.
2
7
Mounting &
Door Cut-out Details
4
6
.
5
6
1
35
60.5
1
5
7
25.5
86
CUT OUT
MCCB
MOUNTING HOLES
M4 SCREW 6 Nos.
35
69 Dimensions of MCCB
DN3 -400 MCCB
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity.
DN3 -400 with Spreader Links
All dimensions are in mm
3P
ST980650000
4P
ST980660000
Recommended cat nos.
for DN3 spreaders
44.5 44.5 44.5 25.25
44.5 44.5 47.5
184(4P)
1
7
6
1
8
2
2
0
5
139.5(3P)
44.50 44.50
5
2
.
5
0
MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
1
7
6
7
9
CUT OUT
121
38.25 82.75
110
115
140
6
8
9
8
7
7
Mounting &
Door Cut-out Details
13
23 21.5 23
2
3
4
5
3
1
8
2
7
2
63 61.5
40
227.5
63
23.5 23.5
13
2
3
4
5
2
7
2
3
1
8
63.5
40
63.5
167
5
6
.
5
26.5
5
26.5
5
110
115
140
6
8
9
8
7
7
5
6
.
5
70 Dimensions of MCCB
DN3-400/630 MCCB
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity.
All dimensions are in mm
Recommended cat nos.
for DN3 spreaders
Rating
400A
630A
4P
ST98066OOOO
CM92004OOOO
3P
ST98065OOOO
ST98054OOOO
DN3-400/630 with Spreader Links
Type
A
B
C
D
E
F
DN3-400
39
37*
45
324
370
13
DN3-630
43
39#
55
344
390
10.5
G 13 11
* 38 for MTX
# 38 for 500A TM
43,5 43,5 43,5
2
6
6
183.5(4P)
43,5
2
2
4
2
3
4
26,5
43,5
140(3P)
Mounting &
Door Cut-out Details
2
2
4
7
8
8
2
,
7
121
43,5 43,5
CUT OUT
MCCB MOUNTING HOLES
M5 SCREW 6 Nos.
8
2
.
2
5
3
8
.
7
5
143
103
120
180
7
7
1
0
4
165
E
40
F
22,5 22,5
62,5
C
D
2
3
62,5
22 20,5
22
2
3
62 60,5 62
40
C
E D
G
224,5
B
143
A
103
120
5
180
7
7
1
0
4
H
H
H 52 62
4P
ST90362OOOO
ST98058OOOO
3P
ST90361OOOO
ST98055OOOO
Rating
800A
1000/1250A
Recommended cat nos. for DN4 spreaders
Note: Spreaders are available as spare.
It is recommended to use spreader links for enhancing termination capacity.
DN4-800/1000/1250 MCCB
All dimensions are in mm
DN4-800/1000/1250 with Spreader Links
4P Frame
D
46
42
Type
N version
S version
3/4P Frame
A
88
80
B
236
220
C
6
20
3P Frame
Type
1000/
1250A
800A
E
28
20
A
88
80
B
324
300
C
6
20
Type
1000/
1250A
800A
E
28
20
278 (4P)
210 (3P)
68 68 68
24
68 71 68 71
180
3
2
6
3
3
0
3
7
0
1
3
2
.
5
197
143
1
0
5
1
9
8
.
5
Mounting &
Door Cut-out Details
68 68
57
3
2
6
182
1
0
7
1
0
9
.
5
CUT OUT
MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
125
D
1
3
2
.
5
197
46
143
8
5
8
5
1
0
5
C
1
9
8
.
5
24
A A
60
B
1
5
5
1
0
5
4
0
E E
9
0
A A A
60
24
B
1
5
5
1
0
9
0
E E E
5
4
0
12.5
12.5
71 Dimensions of MCCB
72 Dimensions of Accessories
Extended ROM Door Cut-out Detail
All dimensions are in mm
Rotary Operating Mechanism (ROM)
Direct ROM Door Cut-out Detail
L1
L1 = Mounting Depth
L2/L3 = Panel Cut-out
L4/L5 = Breaker Mounting Refer
L2
L4
L3
L5
N
Mounting &
Door Cut-out Details
L1 L2 L3 Type L4 L5
DN0
DN1
DN2
DN3
96.5
96.5
122
146
146
58
73
96
121
121
52
52
63
87
87
43.5
56.5
53
78
49
37
54
66
82
82.5
L = Length of Shaft Required
for Panel Depth L1
Total Length of Shaft =275mm
L
L1=Minimum Panel Depth suggested
Mounting & Door Cut-out Details
L2
L
3
45
0
50
N
76
4
DN3
L1
169
169
202
233
233
302
L2
7.5
24.5
27
39
39
69
L3
69.5
81.7
84
122
92
170
Type
DN0
DN1
DN2
DN3
DN4
L
L1 - 119
L1 - 119
L1 - 152
L1 - 183
L1 - 183
L1 - 252
DN3
73 Dimensions of Accessories
MCCB with Stored Energy Electrically
Operated Mechanism (SE-EOM)
Panel Mounted Key Lock
Type 1 / 2 / 3 / 12 / 23
All dimensions are in mm
DN2
DN3
Note: Panel Mounted key lock can be used only with extended ROM
237.5
245.5
156
Door
94
35
Door
Cut-out
N
=
=
=
=
ON TRIP
Cat. No.
CM98132OOOO DN2 SE-EOM
256
264
Door
43.5
2
2
4
6
2
.
1
9
4
94
Mounting
holes for MCCB
Door
Cut-out
N
= =
49
45
ON TRIP
Cat. No.
CM98130OOOO DN3 SE-EOM
1
2
72
50
1
3
6
6
8
58
48.5
52
45
0
2 Holes, 4.2
76
50
6
8
29
2.2
Cut-out for
Handle Assembly
Cut-out for
Panel Mounted Key Lock
Mounting &
Door Cut-out Details
9
4
1
8
.
7
1
5
7
74 Dimensions of Accessories
2
6
6
56
Holes for Breaker Mounting
10 Mounting Holes
436
161 161
161 161
3
1
6
3
4
6
Mounting Details
DN2
DN3
All dimensions are in mm
Mechanical Interlocking Kit
Holes for Breaker Mounting
10 Mounting Holes
1
7
7
35
372
141
141
141
141
2
0
9
2
3
9
Mounting Details
75 Dimensions of Accessories
External Neutral CTs
Note: Adaptor Terminals shown are not available with product.
Kindly refer accessories data for ordering separately.
Circuit Breaker shown for reference only.
All dimensions are in mm
DN2/DN3
K
L
Bottom
Side
D A
B
C
F
E
J H G
Bottom
Side
ON
TRIP
OFF
>M
Bottom
Side
Adaptor Terminal
Frame
DN2 250A
DN3 400A
DN3 630A
A
93
93.5
93.5
B
59
58
58
C
47
46
46
D
81
81.5
81.5
E
35
40
40
F
10.2
13
10.5
Frame
DN2 250A
DN3 400A
DN3 630A
G
77
63.5
63.5
H
153
153.5
173.5
J
189
199.5
219.5
K
26
39
39
L
4
5
5
M
55
60
60
76 Dimensions of Accessories
All dimensions are in mm
DN4
External Neutral CTs
Special Note: Adaptor Terminals for DN4 range of product are not symmetrical.
Kindly ensure proper orientation in assembly as shown in figure.
Note: Adaptor Terminals shown are not available with product.
Kindly refer accessories data for ordering separately.
Circuit Breaker shown for reference only.
M P
A D
C
B
J K G
H
E
F
>L
DN4
800A
1000/1250A
A
132
132
B
88.5
88.5
C
73.5
73.5
D
117
117
E
60
60
F
12.5
12.5
G
92
92
DN4
800A
1000/1250A
H
24
24
J
302
302
K
272
272
L
80
80
M
73.5
73.5
P
12.5
12.5
Bottom
Side
Bottom
Side
Bottom
Side
77 Dimensions of Accessories
23
3
81
3
14.3
73.3
23
Door Cut-out
Details
65
60
73.3 87
51
96
44.5
10
36
91.5
4
4
.
5
91.5
Door Cut-out Details
Display Module
Voltage/Communication/Metering Module
MTX Modules
All dimensions are in mm
78 Dimensions of Accessories
Auto Source Transfer Switch: AuXC-1000 and AuXC-1000L
All dimensions are in mm
82
94
92
9
2
96
9
6
9
6
AuXC-1000L
94 31
79
144
1
4
4
138.5
1
3
8
.
5
AuXC-1000
79 Dimensions of Accessories
All dimensions are in mm
Earth Fault Modules - GF1, GF2, GF11
50
Terminal Block
158
195
24 110
108
Cable / Busbar entry
(110mm X 32mm)
32
20
175
USE M4 SCREW
30
GF1
Cable / Busbar entry
(165 mm X 61.5 mm)
175 15
274.5 8.5
7
1
.
5
5
54
7
1
.
5
1
0
5
.
5
60
=
90
=
90
30
7
4
9
6
USE M6 SCREW
Terminal
Block
GF2
50
Terminal Block
158
195
108
175
USE M4 SCREW
30
Terminals for external CT
secondary connection
GF11
Notes
80
, & Vadodara
The typical training programmes cover:
N
e
w
Low Voltage & Medium Voltage Switchgear
Switchboard Electrical Design
AC Drives & Building Management Solutions
Protective Relays, Earthing & Harmonics
Energy Conservation & Management
Aimed at maximising productivity, conserving energy, minimising costs and enhancing safety, our
Electrical & Automation training programmes have benefitted 1.12 Lakh professionals over
25 years. These training programmes impart knowledge on selection, installation, maintenance and
testing of electrical & automation products.
the last
Please contact any of our training centres to register and
to obtain the detailed training programme schedule.
Vadodara
Larsen & Toubro Limited
Switchgear Training Centre
Behind L&T Knowledge City
Near Village Ankhol
Vadodara 390 019
Tel.: +91 265 245 7805
Fax: (0423) 251 7158
E-mail: STC-VADODARA@LNTEBG.COM
Pune
Larsen & Toubro Limited
Switchgear Training Centre
T-156/157, MIDC, Bhosari
Pune 411 026
Tel.: (020) 2712 0037 / 2712 0653
Fax: (020) 2712 2933
E-mail: STC-PUNE@LNTEBG.COM
Lucknow
Larsen & Toubro Limited
Switchgear Training Centre
C-6&7, UPSIDC, P.O. Sarojini Nagar
Lucknow 226 008
Tel.: (0522) 247 6110 / 09935563239
Fax: (0522) 247 6015
E-mail: STC-LUCKNOW@LNTEBG.COM
Coonoor
Larsen & Toubro Limited
Switchgear Training Centre Ooty-Coonoor
Main Road, Yellanahalli
P.O. The Nilgiris 643 243
Tel.: (0423) 251 7107
Fax: (0423) 251 7158
E-mail: STC-COONOOR@LNTEBG.COM