You are on page 1of 2

Jalal Engineering Page 1 of 2

ServiceFactors

ByOvaisShuja,ProjectManager
JalalEngineering,Karachi

Servicefactorsorsafetyfactorsareusedinthepreparationofspecificationsformostindustrial
equipment.Thesecanbethoughtofasmultiplierstohelpensurethatthedevicewillequalor
exceedthedesiredperformance.Insomecases,thefactorsareusedtoincreaseflexibility.
Operationatconditionsappreciablydifferentfromthedesignissometimesmadepossibleinthis
manner.
CTIGearStandardSTD-111specifiesaminimumservicefactorof2.0forcoolingtower
rightanglespiralbevelgears.Insomeinstances,electricalmotorsarespecifiedwitha1.1or
1.15servicefactorforcoolingtowerduty.Likewise,quiteoftenduringthedesignstageofa
coolingtower,itisconsideredappropriatethataservicefactorbebuiltintothethermal
performancecapabilityofthecoolingtower.
Consequently,inmanyinstancesthenumberspresentedinacoolingtowerinquiryfor
thermalperformancedesignrepresentasomewhatmorestringentconditionthanthatactuallyto
beencounteredintheoperationoftheunit.Thisconservative"factor"inthecoolingtower
design'sparametersiscertainlynotanunjustifiablefactor;however,weshouldgivesomeclose
attentiontowherethisfactorshouldbeappliedanditsconsequenteffectontheoverallcostof
theinstalledcoolingtower.

1. LowerColdWaterTemperatureorHigherWetBulbTemperature:Acommon
misconceptionistotakethesafetyfactorintheformoflowercoldwatertemperatureor
higherwetbulbtemperature,whichineithercasereducestheapproach(coldwater
temperatureminuswetbulbtemperature).This,ofcourse,isaneffectivemannerinwhich
totakeasafetyfactor.
However,itquiteoftencanbemisleadingduetothefactthatthoseunfamiliarwith
coolingtowerratingproceduresareunawarethatclosingtheapproachdoesnotvary
linearlywithcoolingtowersizeandcost.Forexample,adecreaseinapproachfrom20Fto
19Fwouldresultinanincreaseincostofabout5%,whileadecreasefrom5Fto4F
wouldrequireabout20%morecoolingtower.

Jalal Engineering Page 2 of 2



2. HigherWaterFlowRate:Anotherschemethatisoftenusedtoobtain"safety"istostatea
largerGPM(gallonsperminute)thanwillactuallyberequired.Wherethismethodisused,
theeffectonthecoolingtowersizeandpriceisessentiallyaone-to-oneorstraight-line
effect.Hence,a10%servicefactorstatedasa10%increaseaboveactualcirculatingwater
flowrequirementsisfairlyrepresentativeofbothtowersizeandtowercost.
Nevertheless,onecautionmustbeobserved;competentmanufacturerswill
endeavortodesignforoptimumperformanceattheinquiryconditions.Iftheactual
operatingwaterloadingisappreciablylower,theefficiencyofthetowermaybemarkedly
reducedduetopoorwaterdistributionand/orimproperwettingofthefill.Thus,an
overzealousefforttoobtainasafetyfactorinthismannercould,insomeinstances,resultin
anactuallossinperformance.

3. HigherRange:Thethirdmethodusedtoobtainaservicefactoristooverstatetherange
(hot-watertemperatureminuscold-watertemperature)byarbitrarilyraisingthehotwater
temperature(HWT)requirement.Withthismethod,itismucheasierforthetowertoaccept
additionalloadandperformsatisfactorilywhenthisloadisbeingaddedintheformofhigher
hot-watertemperature.Formostordinaryconditions,anappreciableincreaseinHWT
requiresonlyarelativelysmallincreaseinthesizeandcostofthecoolingtower.
Consequently,thisisusuallyagoodmethodofobtainingsafety.
Again,thereisacautiontobeobserved.Becertainthatthecondenser,or
equipmentbeingservedwiththiscoolingtowerwater,iscapableoftakingthehigherhot-
watertemperaturesontheleavingsidesofthecondenserwithoutlargeadverseeffects.
Thiswillallowtheadvantagetobetakenofextraperformancecapabilitiesbuiltintothe
coolingtower.

Insummary,asafetyfactorinapproachwillcauseanincreaseinthecoolingtowersizeandprice
ataratiothatmaybeeitherhigherthanorequivalenttoone-to-one,anincreaseinGPMisona
one-to-oneratio,andanincreaseinrangeisusuallylessthanone-to-oneratio.Themost
realisticmethod,then,isasafetyfactorinwaterflow.Althoughnotthecheapest,itgivesthe
mostflexibilityinconnectionwithpossiblefutureneeds.

Thankyou!Ifyouhavequestionsorcomments,feelfreetoemailmeatoshuja@cyber.net.pk,or
callmeatJalalEngineeringat[021]636-1960,680-6374.