1 Description

SIL coupling relay


PSR-SCP- 24DC/ETP/1X1
PHOENIX CONTACT
Data sheet
The PSR-ETP SIL coupling relay can be used for power ad-
aptation and electrical isolation in low demand applications
up to SIL 3 according to IEC61508 as well as EN61511.
By filtering the control controller test pulses, premature failure
of the forcibly guided safety relay is prevented.
Features
SIL 3 coupling relays for safety-related switch on/F&G
application
Developed for low demand applications
Integrated DCS test pulse filter
Low inrush current
An undelayed enabling contact
Optional plug-in screw or spring-cage terminal blocks
Connectable, configurable open circuit and load monitor-
ing
Special design for avoiding spurious trips
WARNING: Risk of electric shock
Observe the safety instructions in the corresponding section.
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
105212_en_00 2012-08-24
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 2
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data......................................................................................................................... 3
5 Basic circuit diagram............................................................................................................... 5
6 Derating................................................................................................................................... 5
7 Safety notes............................................................................................................................. 7
8 Pin assignment ........................................................................................................................ 8
9 Startup..................................................................................................................................... 9
10 Application examples ............................................................................................................ 10
10.1 Two-channel load connection with diagnostics enabled............................................................... 10
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Coupling relay for SIL 3 low demand applications, couples digital output
signals to the periphery, 1 enabling current path, module for F&G applica-
tions, test pulse filter, plug-in screw connection, 17.5 mm width
PSR-SCP- 24DC/ETP/1X1 2986711 1
Coupling relay for SIL 3 low demand applications, couples digital output
signals to the periphery, 1 enabling current path, module for F&G applica-
tions, test pulse filter, plug-in spring-cage connection, 17.5 mm width
PSR-SPP- 24DC/ETP/1X1 2986562 1
3 Ordering data
Documentation Type Order No. Pcs. / Pkt.
User manual, German, for applications for PSR safety relay UM DE SAFETY RELAY APPLICA-
TION
2888709 1
4 Technical data
Input data
Nominal input voltage U
N
24 V DC
Input voltage range 20.4 V DC ... 26.4 V DC
Input voltage range (factor) 0.85 ... 1.1
Typical input current 75 mA
Typical inrush current 200 mA
Typical response time 30 ms
Recovery time 1 s
Status display Green LED (POWER)
Output data
Contact type 1 enabling current path
Contact material AgNi, gold-flashed
Minimum switching voltage 15 V AC/DC
Maximum switching voltage 250 V AC (125 V DC)
Limiting continuous current 5 A (N/O contact, pay attention to the derating)
Maximum inrush current 5 A
Inrush current, minimum 100 mA
Switching capacity min. 1.5 W
Mechanical service life Approx. 10
7
cycles
General data
Relay type Electromagnetic dust-proof relay
Nominal operating mode 100% operating factor
Degree of protection IP20
Min. degree of protection of inst. location IP54
Mounting position Any
Air and creepage distances between the power circuits DIN EN 50178
Rated surge voltage / insulation 6 kV/safe isolation (through protective impedance)
Dimensions Screw connection Spring-cage conn.
W x H x D 17.5 x 99 x 17.5 x 112 x
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 4
Connection data Screw connection Spring-cage conn.
Conductor cross section, solid 0.2 mm ... 2.5 mm 0.2 mm ... 1.5 mm
Conductor cross section, stranded 0.2 mm ... 2.5 mm 0.2 mm ... 1.5 mm
Conductor cross section AWG/kcmil 24 ... 12 24 ... 16
Stripping length 7 mm 8 mm
Ambient conditions
Ambient temperature (operation) -20 C ... 55 C
Ambient temperature (storage/transport) -40 C ... 65 C
Shock 15 g
Vibration (operation) 2 g
Certification / Approvals
Approvals
Safety data
Stop category 0
Safety parameters for IEC 61508 - High demand
Duration of use 120 Months
Alternative illustration of the device as 1001 structure for process customers
Equipment type Type A
Safety parameters for IEC 61508 - Low demand
SIL 3
Diagnostic coverage (DC) 0 %
PFD
avg
1,43 x 10
-4
Proof test interval 132 Months
Alternative illustration of the device as 1001 structure for process customers
Equipment type Type A
HFT 0
SIL 3
Safe Failure Fraction (SFF) 99.64 %
SD 0 FIT
SU 815.86FIT
DD 1.4FIT
DU 2.94FIT
Total 820.19FIT
MTBF 126.54 Years
PFD
avg
1.29x10
-5
(For T1 = 1 year)
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 5
5 Basic circuit diagram
Figure 1 Block diagram
6 Derating
Figure 2 Vertical installation derating curve
Figure 3 Horizontal installation derating curve
Designation Explanation
A1/A2 Safety relay input voltage
24 V Supply voltage for connectable load mon-
itoring
L/L' (Input) on-load voltage
N/N' 0V
LO/LO' Load input
NI/NI' Load output
A1 24V L
NI
LO
N
LO
N
L
NI
A2
Logic
Power
Error
-30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
5
0
100 mA
500 mA
T [C]
I
[
A
]
-30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
5
0
100 mA
T [C]
I

[
A
]
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 6
Relay load curve
Figure 4 Relay load curve
No Explanation
1 DC inductive Load cos=0,4
2 AC resistive Load
3 DCresistive Load
4 DC induktive Load L/R=7ms
Kontaktspannung [V]
K
o
n
t
a
k
t
s
t
r
o
m
[
A
]
10 100 1000
0,1
1
5
10
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 7
7 Safety notes
WARNING: Risk of electric shock
During operation, parts of electrical switching
devices carry hazardous voltages.
Before working on the switching device, dis-
connect the power.
Please observe the safety regulations of elec-
trical engineering and industrial safety and lia-
bility associations.
Disregarding these safety regulations may re-
sult in death, serious personal injury or damage
to equipment.
Startup, mounting, modifications, and up-
grades should only be carried out by a skilled
electrical engineer!
WARNING: Danger due to faulty devices!
The devices may be damaged following an er-
ror and correct operation can no longer be en-
sured.
In the event of an error, replace the device im-
mediately.
Repairs to the device, especially if the housing
must be opened, may only be carried out by the
manufacturer or authorized persons. Other-
wise the warranty is invalidated.
NOTE: Risk of damage to equipment due to
incorrect installation
For reliable operation, the safety relay must be
installed in housing protected from dust and
humidity (IP54).
Carry out wiring according to the application.
Use the Application Examples section for this
purpose.
NOTE: Risk of damage to equipment due to
noise emissions
When operating relay modules the operator
must meet the requirements for noise emission
for electrical and electronic equipment (EN
61000-6-4) on the contact side and, if required,
take appropriate measures.
NOTE: Electronics may be damaged when
overloaded
Take measures outside the device to limit tran-
sient surge voltages to the respective value for
surge voltage category II.
WARNING: risk of electric shock!
The safety relay may only be connected to de-
vices which meet the requirements of
EN60950.
Suitable devices are available online at
www.phoenixcontact.net/catalog.
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 8
8 Pin assignment
Operating and indication element
Figure 5 PSR-SCP-24DC/ETP/1x1
Figure 6 PSR-SPP-24DC/ETP/1x1
Designa-
tion
Explanation
1 COMBICON plug-in screw terminal blocks
2 COMBICON plug-in spring-cage terminal
blocks
3 Metal lock for mounting on the DIN rail
4 LED status indicator, red - error
5 LED status indicator, green - Power
6 Switch 1
Switch 2
5
6
2
1
2
1
L
L' LO
LO
P
ow
er E
rror
P
S
R
-E
T
P
N N
'
N
A
1
A
2
N
I
24V
A
P
P
R
O
V
A
L
S
T
y
p
e
A
p
p
r
o
v
e
d
T

V
R
h
e
i n
la
n
d
R
L
A
1
A
2
L
'
N
I
N
I'
N
N
'
L
o
g
ic
L
0
'
L
0
R
1
4
L
L' LO
LO
P
ow
er E
rror
P
S
R
-E
T
P
N N
'
N
A
1
A
2
N
I
24V
A
P
P
R
O
V
A
L
S
T
y
p
e
A
p
p
r
o
v
e
d
T

V
R
h
e
i n
la
n
d
R
L
A
1
A
2
L
'
N
I
N
I'
N
N
'
L
o
g
ic
L
0
'
L
0
R
L
L
O
N
'
L
'
N
N
LO
N
I
A
2
24V
5
6
1
4
PSR-SCP- 24DC/ETP/1X1
105212_en_00 PHOENIX CONTACT 9
9 Startup
Once the nominal input voltage of 24VDC has been enabled
at terminals A1 and A2, the Power LED lights up.
The contacts L, L', LO, LO' as well as NI, NI' and N, NI' close.
The 24V connection should only be wired if the diagnostic
function is to be used and should be set to A2.
The diagnostic function can be switched on or off using the
lower DIP switch (29 on the rear of the device.
Switch in left position: diagnostic function off
Switch in right position: diagnostic function on
The upper DIP switch (1) enables the diagnostic threshold to
be switched from 15Ohms (left switch circuit) to 35KOhms
(right switch circuit).
0-15K load OK or 0-35K load OK
If the diagnostics respond, the minimum current consumption
is pushed and a bad channel is generated via A1.
The load is not monitored when the contacts are closed on the
output side.
Figure 7 DIP switches
Perform a full function and diagnostic test during startup.
1
2
PSR-SCP- 24DC/ETP/1X1
105212_en_00 10
PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany
www.phoenixcontact.com
10 Application examples
10.1 Two-channel load connection with diagnostics
enabled
Suitable for low demand applications up to SIL3
M(N)
K1
K2
0V
24V DC
A1 24V L L
LO LO
N N
NI NI A2
PSR-ETP/1x1
L+(L1)
24V DC
Line/Load
Sicher PLC mit
Diagnose
oder oder