You are on page 1of 2

28

CURRENT MONITORING
800.354.8556 503.598.4564 www.veris.com 2006Veris Industries 800.354.8556 503.598.4564 www.veris.com 2006Veris Industries

On/o status for direct-drive fans, pumps, and process motors


More reliable for status than relays across auxiliary contacts
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans and other
xed loads
Great for lighting statusless expensive than 277V relays
Low 0.15A turn-on ( H600)ideal for small exhaust fans (Not intended to
detect belt loss)
Mounting bracket provides installation exibility
Monitor status of fans, pumps, motors & other electrical loads
Split-core 600 for fast retrot installation
Mini solid-core 800 ts in tight en clo sures
100% solid-state, no moving parts to fail
Polarity insensitive output
5-year limited warranty
The Hawkeye 600/800 Series go/no current switches provide a cost-eective
solution for mon i tor ing status on unit vents, exhaust fans, recirculation pumps
and other xed loads where belt loss is not a concern.
Veris has applied new technology to the H600 and H800 models to achieve
impressive improvement in turn-on levels. The Hawkeye 600 now has the lowest
turn-on current in the industry at a mere 150mA!
APPLICATIONS
Monitoring on/o status of electrical loads
Monitoring direct drive units, exhaust fans and other xed loads
Verifying lighting run times
Mini Split- & Solid-Core Fixed Setpoint
Digital Output Current Switches
LOW-COST STATUS!
600/800
H800
H600
See the H500 series on page 26 for Start/Stop & Status of fractional HP loads
*See temperature specications on next page
**CE not currently available on this product
LO
W
EST
TU
R
N
-O
N
IN

TH
E IN
D
U
STR
Y!
LO
W
EST
TU
R
N
-O
N
IN

TH
E IN
D
U
STR
Y!
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
OUTPUT TYPE OUTPUT RATING (MAX.)
Solid-Core
H800 0.25 - 200A* N.O., Solid-state 1.0A@30VAC/DC
H800HV** 0.75 - 200A* N.O., Solid-state 0.5A@250VAC/DC
H800NC 0.5 - 200A* N.C., Solid-state 0.1A@30VDC
Split-Core
H600 0.15 - 200A* N.O., Solid-state 1.0A@30VAC/DC
Maximize Reliability
Minimize Installed Cost
ACCESSORIES
DIN Rail Clip Set...See page 234
800.354.8556 503.598.4564 www.veris.com 2006Veris Industries
CURRENT MONITORING
29
800.354.8556 503.598.4564 www.veris.com 2006Veris Industries
600/800
H600/800
SPECIFICATIONS
Amperage Range Fixed 0.25 max. to 200A ( H800), 0.15 max. to 200A ( H600)
Sensor Power Induced
Output Digital switch (see ordering table)
Insulation Class 600VAC rms
Frequency Range 50/60Hz.
Temperature Range:
H600* 15 to 40C (0-200A)*; -15 to 60C (0-150A)
H800/800NC* -15 to 60C.
H800HV** -40 to 75 C. (0.75-100A), contacts to 0.25A@250VAC/DC
-40 to 50 C. (0.75-200A), contacts to 0.5A@250VAC/DC
*Use min. 75C insulated con duc tor
** Use min. 90 C. insulated conductor
Humidity Range 0 - 95% non-con dens ing
Trip Setpoint:
H600 Fixed 0.15A max.
H800 Fixed 0.25A max.
H800HV Fixed 0.75A max.
H800NC Fixed 0.50A max.
Dimensions ( H600)(L x W x H) 2.34" (60mm) x 2.15" (55mm) x .92" (24mm)
Sensor Hole Size ( H600)(L x W ) 0.52"(13mm) x 0.68" (17mm)
Dimensions ( H800)(L x W x H) 2.77" (71mm) x 1.80" (46mm) x 1.02" (26mm)
Sensor Hole Size ( H800) 0.71" (18mm) diameter
APPLICATIONS/WIRING EXAMPLE DIMENSIONAL DRAWINGS
0.71"
(18 mm)
0.21"
(5.3 mm)
1.80"
(46 mm)
2.77"
(71 mm)
1.02"
(26 mm)
1.79
(46 mm)
2.25"
(58 mm)
0.90"
(23 mm)
0.20" (5.1mm)
Removable/Adjustable Mounting Bracket
POWER
SOURCE
CONTROLLER
POWER
SOURCE
Unit Vent Heater
DI
DI
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8556
Hawkeye 600
H600
H800
2.34"
(60 mm)
2.0"
(51 mm)
2.15"
(55 mm)
3.52"
(90 mm)
2.87"
(73 mm)
1.28"
(33 mm)
Removable Mounting Bracket
0.68"
(17 mm)
0.52"
(13 mm)
2.0"
(51 mm)
0.92"
(24 mm)
Do not use the LED status indicators as evidence of applied voltage.