You are on page 1of 3

GEA Heat Exchangers, Inc.

PHE Division
100 GEA Drive
York, PA 17406 USA
Ph: +717-268-6200
Fax: +717-268-6162
info.phe-systems.usa@gea.com
Website: www.gea-phe.com/usa
Double wall domestic hot water
Customer / Project SCH preparare ACCM Selection ID NUK2W8V2D
User name Crimu Print date 9/14/2014
Model: DW5x12-110 (1-1/4" MPT)
Load (kW) 290.0 Nominal surface (m) 3.7
Log mean temp. diff. (C) 32.7 Dimensions 124W x 332H x 276D
Overall HTC (W/mK) 3,215 Plate construction Double wall
Oversurface percent 32.9 Net weight (kg) 20.1
Model size DW5x12
Design Conditions Side A - Liquid Side B - Liquid
Fluid type Water Water
Fluid mass flow rate (kg/min) 208 83
Entering fluid temp. (C) 80.0 10.0
Leaving fluid temp. (C) 60.0 60.0
Fluid flow rate (L/min) 212.5 83.7
Fluid fouling factor (mK/W) 0.000018 0.000018
Model Parameters
Number of channels 54 55
Velocity (m/s) 0.3 0.1
Pressure drop (kPa) 31.9 5.5
Heat transfer coef. (W/mK) 17,663 8,244
Internal volume (L) 4.396 4.477
GEA Heat Exchangers, Inc. PHE Division
100 GEA Drive
York, PA 17406 USA
Ph: +717-268-6200
Fax: +717-268-6162
info.phe-systems.usa@gea.com
Website: www.gea-phe.com/usa
Ratings at Varying Conditions
Percent difference -15% -7% 0% 7% 15%
Pressure drop (kPa) (Side A) 23.3 27.4 31.9 36.7 41.7
Pressure drop (kPa) (Side B) 4.0 4.7 5.5 6.3 7.2
Load (kW) 246.5 268.3 290.0 311.8 333.5
Fluid flow rate (L/min) (Side A) 180.6 196.6 212.5 228.5 244.4
Fluid mass flow rate (kg/min) (Side A) 177 192 208 223 239
Fluid flow rate (L/min) (Side B) 71.1 77.4 83.7 90.0 96.3
Fluid mass flow rate (kg/min) (Side B) 71 77 83 89 96
Entering fluid temp. (C) (Side A) 80.0 80.0 80.0 80.0 80.0
Entering fluid temp. (C) (Side B) 10.0 10.0 10.0 10.0 10.0
Leaving fluid temp. (C) (Side A) 60.0 60.0 60.0 60.0 60.0
Leaving fluid temp. (C) (Side B) 60.0 60.0 60.0 60.0 60.0
Oversurface percent 46.2 39.2 32.9 27.3 22.3
Disclaimer
This software and the generated calculations provided herein are estimates only and should be treated as such. GEA PHE Systems North America, Inc. always strives to give
complete and accurate information, but cannot provide any guarantees. This software and its output are provided "as is" and any express or implied warranties, including, but
not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no event shall GEA PHE Systems North America, Inc. be liable
for any direct, indirect, incidental, special, exemplary, or consequential damages (including, but not limited to, procurement of substitute goods or services; loss of use, data,
or profits; or business interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including negligence or otherwise) arising in any
way out of the use of this software, even if advised of the possibility of such damage.
Contact:
Customer / Project:
Model Nomenclature:
Selection ID:
Dimension Sheet Brazed Plate Heat Exchanger
Technical Data
Allowable Working Pressure and Temperature:
Max pressure Circuit A:
Circuit B:
Max temperature
Min temperature
Standard construction materials:
Braze Alloy:
Connector:
Plate:
Code Approvals:
Note: Code approval applies to heat exchangers only.
Installation Notes:
Pipe in counter flow direction.
Water strainer should be installed in the fluid inlet circuit to protect the heat exchanger from blockage (20-40 mesh).
Thread Connections Use Teflon tape or other sealant on male threaded part of the connection to prevent leakage.
GEA PHE Systems North America, Inc.
100 GEA Drive, York, PA 17406
Toll Free: 1-800-774-0474
Phone: 1-717-268-6200
Fax: 1-717-268-6163
www.gea-phe.com
E-mail: info.geaphena@geagroup.com
A:
B:
C:
D:
F:
G:
H:
Dimensions - inches (mm): Reference only
GEA Heat Exchangers
Connections Volume per BPHE
Circuit A Circuit B
Position 1 Position 2 Position 3 Position 4
Circuit A Circuit B
Net Weight:
Mounting Bracket
(optional)
NUK2W8V2D
DW5x12-110 (1-1/4" MPT)
Copper 99.9%
304 Stainless Steel
316L Stainless Steel
650 psig (44.8 bar ga)
350.0 F (176.7 C)
-320.0 F (-195.6 C)
CRN
Optional: ASME (UM stamped), PED (CE)
SCH preparare ACCM
4.88 (124.0)
13.07 (332.0)
2.88 (73.2)
11.06 (280.9)
0.00 (0.0)*
0.00 (0.0)*
10.85 (275.6)
*Studs optional -
Available
upon request
0.155 ft (4.396 L) 0.158 ft (4.477 L)
44.2 lb (20.1 kg) 1-1/4" MPT 1-1/4" MPT 1-1/4" MPT 1-1/4" MPT
650 psig (44.8 bar ga)