You are on page 1of 6

Controllers - Recorders

The following chapter contains reduced Product Specification of the instruments:

ECA60 Process Controllers

ER550 Electrical Line Recorder Compact E

F o r d e ta ile d te c h n ic a l s p e c ific a tio n s v is it o u r h o m e p a g e w w w .fo x b o r o -e c k a r d t.c o m o r a s k y o u r lo c a l d is tr ib u to r


fo r th e r e q u e s te d P r o d u c t S p e c ific a tio n s P S S lis te d in th e In d e x o n th e la s t p a g e .

12/2000
7-0
Controllers - Recorders ECA60

ECA60 Process Controllers


• PID control • Analog or pulse output
• Autotuner • Serial communication
• Adaptive control • Configuration from front or PC
• pPIcontrol • Process value alarm
• Gain scheduling • Single or dual loop
• Feed forward • Arithmetic and logic functions
• CLPM • Short sample time
• Deviation alarm

The ECA series is a family of general purpose process transferred via the communication link. The Baud rate
controllers suitable for industrial applications for con- is adjustable.
trolling temperature, pressure, flow, level, etc. The er-
gonomic design makes the controllers restful to the Configuration can be set during operation. The
eye and easy to use. All functions, including configu- controller units are factory preconfigured, enabling
ration, can be accessed from the controller front. practically immediate use. A configuration structure
combines simplicity with power. There are no codes
All units in the ECA family can communicate with a to memorize, and all the user needs to know is shown
computer using the standard COMLI protocol. Both on the full graphical LCD display in plain English.
realtime data and configuration information can be

ECA EMA Controller


6 60 600 60 Control functions . . . . . . . . . P, PD, PI, PID, pPI
Hardware Gain. . . . . . . . . . . . . . . . . . . 0.01 ... 99.99
Analog inputs 2 3 5 3 Integral time . . . . . . . . . . . . . 0.1 ... 9999.9 seconds
Analog outputs 1 2 3 1 Derivative time . . . . . . . . . . . 0.0 ... 9999.9 seconds
Digital inputs 1 3 4 2 Control action. . . . . . . . . . . . Direct, reversed
Digital outputs 2 4 6 4 Set point . . . . . . . . . . . . . . . Internal, external, ramp
RS 232 x x x x Control output . . . . . . . . . . . Analog, pulse
RS 485 x x x x Alarms . . . . . . . . . . . . . . . . . Process value, deviation
Control features Sample time. . . . . . . . . . . . . 30 ... 500 ms
Autotuner x x x
Analog Inputs
Adaptive control x
Input ranges. . . . . . . . . . . . . 0 ... 20 mA, 4 ... 20 mA,
pPI control x
0 ... 5 V, 0 ... 10 V, 2 ... 10 V
Gain scheduling x x
Input types . . . . . . . . . . . . . . Differential or single ended
Feed forward x x
(jumper selectable)
CLPM x
Cascade control x Input impedance . . . . . . . . . Current 250 Ω, Voltage 200 Ω 7
Dual-loop control x Alarm function for
Functions blocks out-of-range signal . . . . . . . . Yes, for 4 ... 20 mA, 1 ... 5 V,
2 ... 10 V, when the signal
Analog input 2 3 5 3
drops below the lower limit
Analog input communication 4 8 12 4
Functions. . . . . . . . . . . . . . . First-order software filter,
Analog user – 2 8 4
linear/square root
Digital input 1 3 4 2
Resolution . . . . . . . . . . . . . . 12 bits
Digital input communication 4 8 12 4
Digital user – 2 8 4 Accuracy . . . . . . . . . . . . . . . Max. ± 0.2 % of FS within
Operator 1 1 2 1 0 – 50 °C
PV alarm 1 1 2 1 Temperature stability . . . . . . 0.01 % FS per °C within
Deviation alarm – 1 2 1 0 ... 50 °C
Arithmetic 2 4 16 8 Analog Outputs
Logic – 2 8 8
Output ranges . . . . . . . . . . . 0 ... 20 mA, 4 ... 20 mA
Other – 2 8 4
Type . . . . . . . . . . . . . . . . . . Current source
Control 1 1 2 –
Max. output current . . . . . . . 22 mA
Analog output 1 2 3 1
Load resistance on
Analog output communication 4 8 12 4
current output. . . . . . . . . . . . Max. 650 Ω
Digital output 2 4 6 4
Short circuit protection . . . . . Feature
Digital output communication 4 8 12 4
Resolution . . . . . . . . . . . . . . 12 bits
System 1 1 1 1

10/2005 CA EIC2162 A-(en)


7-1
Controllers - Recorders ECA60

Analog Outputs (continued) Digital Inputs


Outp. signal break detection . Yes Type . . . . . . . . . . . . . . 24 V DC, common digital input
Accuracy . . . . . . . . . . . . . . . Max. ± 0.2 % of FS within ground, current sink, opto-isolated
0 ... 50 °C Voltage . . . . . . . . . . . . Max. 35 V, min. – 0.5 V
Logic levels. . . . . . . . . 0 < 3 V (IEC 1131-2, type 1)
Communication 1 > 15 V (IEC 1131-2, type 1)
Number of ports . . . . . . . . . . 2, RS 232 and RS 485
(2-wire) Digital Outputs
Bus system, communication Type . . . . . . . . . . . . . . 24 V DC, current source
protocol . . . . . . . . . . . . . . . . COMLI Load current . . . . . . . . Max. 250 mA per output
Speed of transfer . . . . . . . . . Max. 19 200 Baud Max. 500 mA total
Short-circuit current. . . Max. 500 mA transient current
Operator Interface during 1 µs
Presentation
Process value, set point, controller output indicated on Power supply
bar graphs and on LCD display. Alarms indicated on AC . . . . . . . . . . . . . . . 115/230 V AC ± 10 %,
process value bar graph. Set point type (internal/exter- 50 ... 60 Hz, 20 VA or
nal) indicated on LCD display. Computer/local status in- 19 V AC ± 10 %, 50 ... 60 Hz, 1 A
dicated on LCD display. DC . . . . . . . . . . . . . . . 24 V DC ± 10 %
Display . . . . . . . . . . . . Backlit LCD with 120 x 32 pixels Protection . . . . . . . . . . Secondary side of transformer and
Bar graphs . . . . . . . . . LED, Process value 30 segments, direct supply fused via thermo-type
Controller output 20 segments fuse
Keys . . . . . . . . . . . . . . Six keys: Cancel, Page, OK, Transmitter . . . . . . . . . Max. 24 V DC/150 mA
Hand, Increase and Decrease

Model Codes ECA6


Standard Controller ECA6 011004

Mounting kit
order as auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Z
Options
Master Instruction German. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -D
Master Instruction English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -E
Custom Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -T

Auxiliary and PC Software see EIC9160

Model Codes ECA60


Universal Controller ECA60
Mounting kit
order as auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Z
Options
Master Instruction German. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -D
Master Instruction English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -E
Custom Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -T

Auxiliary and PC Software see EIC9160

Model Codes ECA600


Multi Loop Controller ECA600
Mounting kit
order as auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Z
Options
Master Instruction German. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -D
Master Instruction English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -E
Custom Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -T

Auxiliary and PC Software see EIC9160

CA EIC2162 A-(en) 10/2005


7-2
Controllers - Recorders ECA60

Model Codes EMA60


Multi-Instrument EMA60
Mounting kit
order as auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Z
Options
Master Instruction German. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -D
Master Instruction English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -E
Custom Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -T

Auxiliary and PC Software see EIC9160

Model Codes Auxiliaries


PC-Software DOX60
for configuation via RS232 interface (for all devices) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -

Adapter for Shelf Housing compact E/P ADA


for shelf cE/cP 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -400
for shelf cE/cP 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -600

Mounting kit KIT


Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A
Cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -B

For complete specification, refer to Product Specification


Sheet PSS EIC2162 A-(en)

10/2005 CA EIC2162 A-(en)


7-3
Controllers - Recorders ER550

ER550 Electrical Line Recorder Compact E

• Deliverable as 1-, 2- or 3-pen recorder with fibre-tip


pens or steel pens with refillable reservoir
• Transmitter power supply from the recorder
• Signal range 0 to 20 mA / 4 to 20 mA, selectable
• Electronic limit units at minimum and maximum
input value
• Damping continuously adjustable
• Power supply 24, 127, 240 V AC selectable
• Versions for 24 V DC supply
• Power switch
For recording and indication of one, two or three mea- • Reset to zero on power failure
sured values. The Recorder is specially designed as
slide-in module for panel mounting, and from part of • Automatic chart take-up
the compact E system. • Foreward and reverse take-up of chart roll
• Chart speed selectable
• Disturbance-free replacement of recorder module
can be converted from 72 x 144 to 144 x 144 mm
• Mounting into 600 or 400 type housing optional
For complete specification, refer to Product Specification
Sheet PSS EIC3211 A-(en) • Housings and terminal blocks can be pre-
assembled

Input Recording system


Signal range . . . . . . . . . . . . 4 to 20 mA (0.6 to 3 V) / Recording speed . . . . . . . . . max. 100 mm/s
0 to 20 mA (0 to 3 V) Recording width . . . . . . . . . . 100 mm
Input resistance: Chart width . . . . . . . . . . . . . 110 mm
with current signals . . . . . . . 150 Ω, at terminal block Chart speed . . . . . . . . . . . . . 10, 20, 30, 60, 120, 180, 360,
with voltage signals . . . . . . . > 1 M Ω 600, 1200, 1800, 3600 mm/h;
Inputs are galvanically separated both from each other selectable
and earth. Chart drive . . . . . . . . . . . . . . synchronous motor/quartz
controlled stepping motor,
Transmitter power supply time plotting deviation:
Signal range . . . . . . . . . . . . 4 to 20 mA < 5.5 minutes/month
Supply voltage: Chart length:
Rated supply voltage UN . . . min. 19 V, max. 23.3 V Recorder 72 x 144 . . . . . . . . 16 m
Recorder 144 x 144 . . . . . . . 16 m or 32 m, corresponding
Measuring system to 4 or 8 weeks at 20 mm/h
Principle. . . . . . . . . . . . . . . . servo-system, feedback chart speed
via conductive-plastic element
Conformity . . . . . . . . . . . . . . ≤ 0.5 % Power supply
Scale . . . . . . . . . . . . . . . . . . 100 mm long, replaceable Alternating voltage . . . . . . . . 240 / 220 / 127 / 110 / 24 V,
selectable
Tolerance . . . . . . . . . . . . . +10 %, –15 %
Nominal frequency . . . . . . 50 Hz / 60 Hz
Direct voltage. . . . . . . . . . . . 24 V
Tolerance . . . . . . . . . . . . . +25 %, –15 %
Residual ripple Vpp . . . . . . ≤ 20 % within tolerance range
The device can be operated with a power supply Class
AC 3; DC 2 as per IEC 654 Part 2.
Power supply influence . . . . 0.1 %/10 % voltage change

CA EIC3211 A-(en) 10/2005


7-4
Controllers - Recorders ER550

Model Codes
Electr. Line Recorder Compact E ER550
Version
Compact 72 x 144 mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A
Compact 144 x 144 mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -B
Measuring systems
1 system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ink-system
Fibre pen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
Refillable system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
Signal Range
0 - 20 mA (0 - 3 V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 - 20 mA (0.6 - 3 V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Response time
1 to 12.5 s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S
Power supply
240 V, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
127 V, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
24 V, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
240 V, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
127 V, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H
24 V, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L
24 V DC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M
Options
Scale indicating range for system 1 (Standard 0-100%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -1
Scale indicating range for system 2 (Standard 0-100%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -2
Scale indicating range for system 3 (Standard 0-100%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -3
Nameplate with inscription (a) (for all Measuring systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -N
Instrument Identification (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -S

(a) Specify inscription

Housings /Shelves see EIC9001


Terminal block see EIC9001

10/2005 CA EIC3211 A-(en)


7-5