RET650 SITE TEST REPORT

ABB Ref. no. 4200175820


4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


1




UAT 4A DIFFERENTIAL














PROJECT : 250MW UNIT-4 GENERATOR PROTECTION


CUSTOMER : RRVUNL




















RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


2



Protection Relay Data

Make ABB Type RET650
Auxiliary Supply 220 V DC Rating

Un=110 V AC, 50 Hz
Software version 1.1 rev 01 Location of relay GRP4C
Serial No I1216032 Drawing Reference YN1M301705CAA

W1:
Rated voltage 16.5 KV
Rated current 700 A
Adopted CT 1000/1 A
W2:
Rated voltage 6.9 KV
Rated current 1673 A
Adopted CT 2000/1 A

Vector group Dyn1



CT TERMINALS: W1-X01-01,02,03,04.
W2-X01-06,07,08,09





Measured Values


A/D Channel No.
A/D
Chann
el
Rating
[A];
CT/PT ratio
[A/A] ; [kV/V]
Injected
Values [A]
; [V]
A/D Py Display

HV SIDE
1
1000/1 1 1002.2 A
HV SIDE
1 1000/1 1
1002.7 A
HV SIDE
1 1000/1 1
1002.7 A
LV SIDE 1
2000/1 1
2004.5 A
LV SIDE
1 2000/1 1
2002.7 A
LV SIDE
1 2000/1 1
2004.0 A
UAT PRT L1
1 1000/1 1
1001.7
UAT PRT L2
1 1000/1 1
1000.8
UAT PRT L3
1 1000/1 1
1001.3




RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


3






1. Differential Set Value between W1 and W2.

Idmin=0.12Ib End section 1 =0.4*IB Slope Section 2 =40%
Pickup= (700*0.12)/(1000/1) End section 2 =5.0 *IB Slope Section 3 =55%

Differential Pickup Test

Phase W1 I Calculated
Pickup in
A
W1 I Operated
Pickup in
A
W2 I Injected in
A
Time in
sec
R 0.084 0.084 - 0.030
Y 0.084 0.084 - 0.030
B 0.084 0.084 - 0.030


W2 pickup= (1762*0.12)/(2000/1)
Phase W2 I Calculated
Pickup in
A
W2 I Operated
Pickup in
A
W1 I Injected in
A
Time in
sec
R 0.100 0.100 - 0.026
Y 0.100 0.100 - 0.026
B 0.100 0.100 - 0.026

Stability:

Current Diff current Bias
W1 side (Amp) W2 (Amp)
0.7000 0.836150 0.64 702
0.700-120 0.83630 1.67 702
0.700120 0.836270 0.62 702








Slope Test(Carried Through Omicron Control Panel):
Slope 1-Point 1

RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


4

Current Diff Bias
W1 (Amp) W2(Amp)
0.7000 0.836150 0.64 702
0.700-120 0.83630 1.67 702
0.700120 0.836270 0.62 702


Keep W2 constant and increase W1.
Current Diff Bias
W1 (Amp) W2 (Amp)
1.1180 0.836150 420 1120
1.118-120 0.83630 419 1120
1.118120 0.836270 418 1120
Point 2: 1.5*FLC

Current Diff Bias
Phase side (Amp) Neutral (Amp)
1.050 1.25150 1.6 735
1.05-120 1.2530 1.7 735
1.05120 1.25270 1.6 735
Keep W2 side constant and increase W1 side current until operate
Current Diff Bias
W1 (Amp) W2 (Amp)
1.7010 1.25150 653 1704
1.701-120 1.2530 653 1704
1.701120 1.25270 653 1704

Slope = (ID2-ID1)/(IB2-IB1)
= (653-420)/(1704-1120)
= 39.8 %
Slope 2-Point 1

Current Diff Bias
W1 side (Amp) W2 (Amp)
6.5500 4.18150 3055 6564
6.550-120 4.1830 3055 6564
6.550120 4.18270 3055 6564




Point 2:

Current Diff Bias
RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


5

W1 (Amp) W2 (Amp)
7.320 4.59150 3484 7336
7.32-120 4.5930 3481 7336
7.32120 4.59270 3478 7336

Slope = (ID2-ID1)/(IB2-IB1)
=55.7 %
2 nd Harmonics:
Current Remarks
W1 (Amp) W1 (Amp)
1.0 at 50 Hz 1.0 at 100 Hz Not operated
1.0 at 50 Hz 1.0 at 100 Hz
1.0 at 50 Hz 1.0 at 100 Hz
Decrease W1 current of 100Hz until operate.
Current Remarks
W1 (Amp) W1 (Amp)
1.0 at 50 Hz 0.15 at 100 Hz operated
1.0 at 50 Hz 0.15 at 100 Hz
1.0 at 50 Hz 0.15 at 100 Hz



5
th
Harmonics:
Current Remarks
W1 (Amp) W1 (Amp)
1.0 at 50 Hz 1.0 at 250 Hz Not operated
1.0 at 50 Hz 1.0 at 250 Hz
1.0 at 50 Hz 1.0 at 250 Hz
Decrease W1 current of 250Hz until operate.
Current Remarks
W1 (Amp) W1 (Amp)
1.0 at 50 Hz 0.27 at 250 Hz operated
1.0 at 50 Hz 0.27 at 250 Hz
1.0 at 50 Hz 0.27 at 250 Hz
2. Phase overcurrent protection:

Base Current : 700 A
Current IN1> : 130% of IB
TMS K1 : 0.25
Curve : IEC Normal inverse


CURRENT Theoretical Operating Operating Time in Sec


RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


6

INJECTED(mA) Time in Sec. Expected pickup in
ma
Actual Pickup in ma
2x 2.50 2.52
0.910 0.910 5x 1.07 1.10
10x 0.74 0.784

3. Backup Earth fault protection:

Base Current : 1673 A
Current IN1> : 5% of IB
TMS K1 : 0.25
Curve : Extremely Inverse


CURRENT
INJECTED(mA)
Theoretical Operating
Time in Sec.
Operating Time in Sec


Expected pickup in
ma
Actual Pickup in ma
2x 71.90 71.89
0.209 0.209 5x 8.90 8.90
10x 2.18 2.20

4. Inst. Overcurrent protection:

Set Value Phase I Pickup in
A
Trip Relay

T pickup in
sec
I>> 200% ofIB
t = 0.0 S

R 1.400
CLASS-A
G1&2 Opd

0..056
Y 1.40-120
B 1.40120



5. Additional Checks:

Binary I/p & LED Indications : Checked OK

Signal O/p & LED Indications : Checked OK

Trip O/p & LED Indications : Checked OK

Logics Functions (AND, OR, Delay) : Checked OK

Tripping Logics : Checked OK

Relay Event Recorder & Trip value recorder : Checked OK

Relay Disturbance recorder : Checked OK

RET650 SITE TEST REPORT


ABB Ref. no. 4200175820
4200136400
4200136400
Customer .

Doc. Kind Commissioning Test Report Station.

No. of p.
Prep.

Relay Type RET650
7
Resp. dept. INPSNM-SA Protected Obj. UAT
Tested By:


Customer: Page
ABB India Ltd


7

Relay Found Healthy : Checked OK