You are on page 1of 21

School of Electrical, Electronic

and Computer Engineering


EERI 213
Practical 1:
Wye and Delta Loads

by:
J.M. Crause

24117986

W. Wolmarans

24087459

North-West University Potchefstroom Campus


Lecturer:

Dr. Andre Grobler

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Contents
1

Introduction

Theoretical Calculation

Simulation Results

Practical Measurements

10

Results

15

Conclusion

15

1.1 Problem Statement


1.2 Literature review .
1.2.1 Wye loads .
1.2.2 Delta loads

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

2.1 Wye Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


2.2 Delta Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Wye Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Delta Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1
1
1
2

2
4
5
8

4.1 Wye Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


4.2 Delta Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

References

Practical 1

16

August 14, 2014

ii

School of Electrical, Electronic and Computer Engineering

List of Figures

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Circuit with Y-connected Load . . . . . . . . . . . . . . . . . . . . . . . . . .


Circuit with -connected Load . . . . . . . . . . . . . . . . . . . . . . . . . .
Phase and Amplitude Di erence Between Line and Phase voltage in Y -circuit
Similarity Between Phase and Line Currents in Y -circuit . . . . . . . . . . . .
Di erence Between Phase and Line Currents in -circuit . . . . . . . . . . . .
Similarity Between Phase and Line Voltages in -circuit . . . . . . . . . . . .
Y load connection graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Y connected load values for g 7 . . . . . . . . . . . . . . . . . . . . . . . . .
Y connected load - line vs. phase . . . . . . . . . . . . . . . . . . . . . . . . .
Y connected load values - line vs. phase . . . . . . . . . . . . . . . . . . . . .
 load - phase current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
 connected load - phase current and voltage values . . . . . . . . . . . . . . .
 load - current through line . . . . . . . . . . . . . . . . . . . . . . . . . . .
 load - current through line values . . . . . . . . . . . . . . . . . . . . . . . .
Y load - Phase and line voltage . . . . . . . . . . . . . . . . . . . . . . . . . .

2
4
6
7
8
9
10
10
11
12
13
13
14
14
16

List of Tables

Theoretical calculations, simulated values and practical measurements . . . . . 15

List of Acronyms

RMS Root Mean Square

Practical 1

August 14, 2014

iii

School of Electrical, Electronic and Computer Engineering

List of Symbols
V
I
R

t
f

Voltage
Current
Resistance
Phase angle
Time
Frequency

Practical 1

August 14, 2014

iv

School of Electrical, Electronic and Computer Engineering

1
1.1

Introduction
Problem Statement

The main aim of this practical is to investigate the e ect of wye and delta load (balanced)
con gurations on voltages and currents in phases and between lines in a three phase electrical
circuit.
1.2

Literature review

A three phase electrical power system has advantages over the traditional single phase alternating current, one being that the power transfer to the load is constant. This is ideal in
situations where high currents and voltages are used to power machinery. [1]
Two types of loads exist: Wye and Delta.
1.2.1

Wye loads

The wye load can be con gured by connecting three loads, consisting out of resistors, capacitors, inductors or a combination of the components in a three way star con guration. The
node where the three loads are connected can be assumed to be neutral. For now, the load
will be assumed to be balanced, indicating that each of the three loads are equal to the other
two.
The voltage over a phase refers to the voltage over one of the three loads that is connected
in a wye con guration, whereas the line voltage refers to the voltage di erence between to
transmission lines.
Because the load is balanced, the voltages over each phase will be equal, but the voltage phase
angle di erence between each phase voltage will be 120 in a wye connected load. [1]
p
The voltage between two transmission lines is 3 times larger than the phase voltage. The
phase angle di erence between the line voltage and the phase voltage between two transmission
lines and the voltage over a phase, will be 30.[1] Thus,
p
Veline = Vephase1 Vephase2 = 3Vephase 6 30
(1)
The line current (including phase angle) and the current through the connected phase will
be equal, because in a wye connected load, the line does not split when moving from the
transmission line to the phase line.
Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

1.2.2

Delta loads

The delta load can be con gured by connecting the three loads in a triangular formation. This
means that each load has a connection to the remaining two loads. The delta load will also
be assumed to be balanced, indicating that the current phase angle di erence between each
phase is 120.citeGuru
p
With delta loads, the magnitude of the current in the transmission line is 3 times larger
than the phase current in the load. This is due to the transmission line that splits at the node
where the delta load is connected, causing the current to split as well, according to Kircho s
law.[2] The current phase angle di erence between the line current and the phase current will
be 30, assuming that the phase and line used is connected at a common node.[1] Thus,
p
(2)
Ieline = Iephase1 Iephase2 = 3Iephase 6 30
The line voltage and phase voltage will be equal in a delta connected load setup.
2
2.1

Theoretical Calculation
Wye Load

Figure 1: Circuit with Y-connected Load


Fig. 1 shows the circuit diagram for a load that has a wye con guration. All three resistors
are connected to a common grounded node. The value of each resistor is 128
. The sources
V1, V2 and V3 are also connected in wye con guration and is set to a voltage of 44:45V RMS.
All calculations will be in RMS.
Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Each alternating source will be set to a value of 44:45V with a phase angle di erence of 120
as mentioned in the literature review. The line voltage can be calculated:
= VeR1 VeR2
(3)


= 44:4556 0 44:4556 120
(4)

(5)
= 76:9986 p 30

6
= 44:455( 3) 0
(6)
p
The above calculation proves that the magnitude of the line to line voltage is 3 times larger
than the magnitude of the voltage over each load or phase voltage. The phase angle di erence
is 30 between the phase voltage and the line voltage, which proves the theory given in the
literature review. Because Vline is used as a reference in the calculation, the angle is calculated
to be negative, indicating that the phase voltage is trailing the line voltage with 30.
Since the load only consists of resistors and not capacitors or inductors, the load will not cause
a change in the phase angle of the phase voltage or phase current. Thus, the phase angle of
each load is identical to the phase angle supplied by the connected source in both voltage and
current.
The current through each load can be calculated:
Veline

Iephase

e
= Vphase
R

(7)

e
= VRR11
456 0
= 44:128
= 0:356 0A

(8)
(9)
(10)

= 0:356 120A

(11)

IeR1

Thus:
IeR2

= 0:356 120A
(12)
Since the transmission line from each source does not split up before connecting to each load, as
shown in gure 1, the current through the line will be identical to the current owing through
IeR2

Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

the phase that is connected to the speci c transmission line. Therefore, Il ine = Iphase in wye
load con gurations.
2.2

Delta Load

Figure 2: Circuit with -connected Load


The circuit in gure 2 shows the con guration of a delta load. The load still consists out of
resistors, each with a value of 128
. The source is connected in wye con guration, with a
common grounded node. Each source has a 120 phase angle di erence.
In a delta load con guration, as seen in gure 2, the line to line voltage is equal to the phase
voltage of the phase that is connected between the transmission lines. Since each phase is
connected between two transmission lines, the voltage between the transmission lines will be
equal to the voltage over the phase. Therefore, Vphase = Vline in the delta load con guration.
The current through each load in delta con guration can be calculated as follows:
Iephase
IeR1

e
= Vphase
R

e
= Vphase
R1

6
77
= 12830
= 0:66 30A

(13)
(14)
(15)
(16)

The current through the transmission line can be calculated:


Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Ieline

=
=
=
=

IeR1

IeR2

0:66 30 + 0:66


1:04p6 60A
0:6( 3)6 60

90

(17)
(18)
(19)
(20)

This calculation shows that the magnitude of the line current is 3 times larger than the
magnitude of the phase current. Kircho s law in terms of current states that the net current
at a node in a circuit should be zero [2]. Using this law in step 2 of the calculation, it can be
seen that the phase angle of the line voltage is 60 which is a 30 di erence from the phase
angle of IR1. This proves that there is a 30 phase angle di erence between the phase current
and connected line current in a delta con gured load.
3

Simulation Results

The following simulation results can be obtained using a Micro-Cap package.


3.1

Wye Load

The properties of voltage and current of a circuit with a wye connected load (as seen in gure
1) can be seen in the folling graphs.
Figure 3 shows the phase di erence between the loads, which can be calculated by multiplying
the time di erence, shown in the gure as 6:6ms, by the frequency, which is 50Hz, and then
multiplying that by 360, which gives an answer in degrees.




= 360tf
= 360(0:0066)(50)
 120

(21)
(22)
(23)

Which is consistent with the phase voltage in the literature review and the theoretical calculations.
The di erence in amplitude(Vmax) and RMS(VRMS ) voltage can also clearly be seen in gure
3, and the exact di erence can be calculated:
Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Figure 3: Phase and Amplitude Di erence Between Line and Phase voltage in Y -circuit
e
= Vpmax2
108p:87
Veline =
2
= 77V
62p:749
Vephase =
2
= 44V
VeRMS

(24)
(25)
(26)
(27)
(28)

and:
Veline

Vephase

p
= 77

44 3

(29)

p
which, again, proves the initial statement that the line to line voltage (Vline) is 3 times bigger
than the phase voltage (Vphase).

Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Furthermore it can be seen that the line voltage leads the phase voltage by an angle, , and to
calculate the phase angle of the line voltage with the reference to the phase voltage, the time
at the peaks of both curves are subtracted from one another, and multiplied by the frequency,
f , and 360 .




= 360tf
= 360(0:0066 0:0048)(50)
 30

(30)
(31)
(32)

Which shows that in a circuit with wye connected loads line voltage leads the phase voltage
by 30, and is therefore consistent with the theoretical information discussed earlier.

Figure 4: Similarity Between Phase and Line Currents in Y -circuit


In gure 4 it can be seen that the magnitude of the current is the same regardless whether
phase current (the blue and red curves) or line current (the green curve) is measured. Which
means Vline = Vphase, which agrees with the theoretical calculations and literature review.
Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

3.2

Delta Load

The following graphs are an indication of the voltages and currents in a delta connected load
(as seen in gure 2).

Figure 5: Di erence Between Phase and Line Currents in -circuit


There are several things to be noticed in gure 5. Firstly it can be seen that the phase
di erence between the di erent phase currents is 120, since they are equally spaced apart
and 360=3 = 120. Secondly it is evident that the magnitude of the line current is larger than
that of the phase current, and the exact di erence can be calculated as follows:
Ieline

Iephase

474  p3
= 01::8499

(33)

p
This implies Iline = 3Iphase, which is consistent with all the theoretical values.
Thirdly it can be seen that the line current is not in phase with the phase voltages. To
calculate the phase angle, represented by , of the line current with reference to the phase
current, the time at the peaks of both curves are subtracted from one another, and multiplied
by the frequency, f , and 360 in order to get an answer that is in degrees.

Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering





= 360tf
= 360(0:015 0:0132)(50)
 30

(34)
(35)
(36)

Which shows that in a circuit with delta connected loads line voltage trails the phase voltage
by 30, which agrees with the theoretical information discussed earlier.
When considering gure 6 it is apparent that the magnitude of phase voltage and line voltage
of a wye connected load are equal, since:
= Ve1 2
Vephase = Veline
VeR1

(37)
(38)

The phase di erence between the voltages could also be seen as 120 since the curves are
equally spaced apart and 360=3 = 120.

Figure 6: Similarity Between Phase and Line Voltages in -circuit


Practical 1

August 14, 2014

School of Electrical, Electronic and Computer Engineering

Practical Measurements

For the practical measurement of the circuit values, a TiePie toolkit was used to give accurate
feedback on the circuits currents and voltages. All the gures used in this section was supplied
by TiePie software. All voltages and currents used are in terms of RMS.
4.1

Wye Load

For the wye connected load, the following measurements were retrieved.

Figure 7: Y load connection graph

Figure 8: Y connected load values for g 7


The rst measurements made on the wye connected load, was the line to line voltage and the
current through the phase and transmission line. In Figure 7, the dark blue line and the green
line represents the line to line voltages and the red graph indicates the current.
Practical 1

August 14, 2014

10

School of Electrical, Electronic and Computer Engineering

The dark blue line and green line are identical to one another in size, indicating that the
amplitude of each line to line voltage is equal to one another and that they have equal RMS
values as well. This is proved by the values supplied by Figure 8. The only di erence between
these graphs, is that each graph peaks at a di erent time. The time di erence between the
dark blue and green graph is about 7 ms. The corresponding phase angle di erence can be
calculated:


= 360tf
= 0:007  50  360
= 126

(39)
(40)
(41)

This answer is roughly equal to 120, proving the fact that the line to line voltages are
separated by a phase angle of 120 in a wye connected con guration.
The current represented by the red graph is equal to 0:341A (Ch4 from gyre 8). This current
is equal throughout the circuit in both transmission lines and phase lines.

Figure 9: Y connected load - line vs. phase


The dark blue graph in g 9 represents the phase voltage of phase 3, the light blue line
represents the voltage of phase 2 and the green line represents the line to line voltage connected
to phase 1. The green graph has a bigger amplitude and a RMS value of 76:7V and the phase
voltages is measured to be around 44:4V RMS, as shown in g.4. Thus:
Practical 1

August 14, 2014

11

School of Electrical, Electronic and Computer Engineering

Figure 10: Y connected load values - line vs. phase


:7
= 76
(42)
44:4
= 1p:72
(43)
 3
(44)
p
This calculation shows that the measured amplitude of the line to line voltage is 3 times
bigger than the measured amplitude of the phase voltage, proving that the theoretical calculations and the simulated values are accurate.
In gure 9, the green graph is slightly moved to the right of the dark blue graph and red
graph, indicating a phase angle di erence between the measured line to line voltage and the
phase voltages. Using Eq 39 to calculate the phase angle di erence between line 1 and phase
2 voltages:
Ratio

= 360tf
(45)
= 0:005  50  360
(46)

= 90
(47)
Using Eq 39 to calculate the phase angle di erence between line 1 and phase 3 voltages:


= 360tf
(48)
= 0:007  50  360
(49)

= 126
(50)
It is already proven with gure 7 that the phase voltages have a phase angle di erence of 120.
Therefore, to calculate the phase angle di erence between line 1 and phase 1 voltages:


Dif f erence

Practical 1

= 126 90
 30

August 14, 2014

(51)
(52)
12

School of Electrical, Electronic and Computer Engineering

This calculation proves that there is a 30 phase angle di erence between line 1 voltage and
phase 1 voltage and correlates with both the theoretical calculations and the simulation results.
This will also be the case for line 2 and phase 2; line 3 and phase 3 voltages.
4.2

Delta Load

Figure 11:  load - phase current

Figure 12:  connected load - phase current and voltage values


Figure 11 shows the current through line 1 and the line and phase voltages, but this gure
will be discussed with the focus on the phase current. The current through phase 1 is 0:585A
, as shown by gure 12. It is represented by channel 4, which has to be converted to get the
current instead of the voltage as given.
The light blue and dark blue graphs in gure 5, representing a line and a phase voltage
respectively are the same size. This indicates that the phase voltage is equal to the line to
line voltage in a delta load con guration, proving the theoretical predictions and simulated
results.
Practical 1

August 14, 2014

13

School of Electrical, Electronic and Computer Engineering

Figure 13:  load - current through line

Figure 14:  load - current through line values


Figure 13 is identical to gure 11, except that the red graph shows the current through the
transmission line that is connected to phase 1. The current graph in Fig 7 has a larger
amplitude than the graph in g 5, with an RMS value of 1:002A as indicated in gure 14.
The current graph is also shifted to the right with about 2ms.
Using Figures 12 and 14, the ratio between the RMS values of the line current and the phase
current can be calculated:
Ratio

=
=


1:002
0:585
1p:71
3

(53)
(54)
(55)

p
The ratio is equal to 3 , proving that the results of the theoretical calculations and the
simulation are correct.
The approximate 2ms di erence between graphs in gure 11 and gure 13 can be converted
into degrees:

Practical 1

August 14, 2014

14

School of Electrical, Electronic and Computer Engineering

=
=
=


360tf
0:002  50  360
36
30

(56)
(57)
(58)
(59)

The calculation shows that the phase angle di erence between the line current and the phase
current is 30, indicating that the theoretical and simulation results are accurate.
5

Results

Table 1: Theoretical calculations, simulated values and practical measurements


Value Theoretical Simulated Practical Error Margin


(line - phase)(V)
30
30
30
0%
p
p
Amplitude di erence (V)
3
3
1; 72
0; 69%
Wye Load

Delta Load

Value Theoretical Simulated Practical Error Margin




(line - phase) (I)
30
30
30
0%
p
p
Amplitude di erence (I)
3
3
1; 71
1; 27%
From the information in table 1, it can be concluded that the calculations, the simulation and
the practical measurements were all done correctly and precisely.
A trend can be seen in these values which have been depicted in the following phaser diagram
( gure 15) which shows the size and phase angle di erence between phase and line current in
a circuit with a wye connected load.
6

Conclusion

The e ects of 3 phase power on a load di ers as the connection type of the load di ers. From
the calculated, simulated and practically measured results a clear and consistent trend can be
seen as to what these e ects are.
In a wye connected load the current stays constant, whether it is line current orp phase current
being measured. Whereas the line to line voltage in a wye connected circuit is 3 times bigger
Practical 1

August 14, 2014

15

School of Electrical, Electronic and Computer Engineering

Figure 15: Y load - Phase and line voltage


than the phase voltage. The phase angle of the line voltage also di ers with that of the phase
voltage with 30.
In a delta connected load it is the voltage that stays constant regardless ofp line to line or
phase voltage being measured. But for this connection the line current is 3 times bigger
than the phase current, and the phase angle of the line current is 30 with respect to the
phase current.
References

[1] S. Guru and R. Huiseyin, Electric Machinery and Transformers, 3rd ed. Oxford University
Press, 2001.
[2] J. Nilsson and S. Riedel, Electric Circuits. New Jersey: Pearson, 2011.

Practical 1

August 14, 2014

16

School of Electrical, Electronic and Computer Engineering

Appendix A: Matlab Code

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36

clear all
close all
clc
t1 = 0: 0.1 : pi/6;
t2 = (2/3)*pi : 0.1 : (5/6)*pi;
t3 = (4/3)*pi: 0.1 : (3/2)*pi;
vp1 = 77/sqrt(3) ;
x = 77*cos(pi/6);
y = 77*sin(pi/6);
vectarrow([0;0],[x;y])
hold on;
vectarrow([0;0],[vp1;0])
hold on;
vectarrow([0;0],[vp1*cos((2/3)*pi);vp1*sin((2/3)*pi)])
hold on;
vectarrow([0;0],[77*cos((5/6)*pi);77*sin((5/6)*pi)])
hold on;
vectarrow([0;0],[vp1*cos((4/3)*pi);vp1*sin((4/3)*pi)])
hold on;
vectarrow([0;0],[0;(-77)])
hold on;
plot(20*cos(t1), 20*sin(t1));
hold on;
plot(20*cos(t2), 20*sin(t2));
hold on;
plot(20*cos(t3), 20*sin(t3));
title ('Phasor Diagram of Phase Voltage versus Line Voltage');
xlabel ('Re-Axis');
ylabel ('Im-Axis');
hold o ;