You are on page 1of 34

42HQE - 38YE

SERVICE MANUAL
42HQE009N
42HQE012N
38YE009
38YE012N
42HQE018N
38YE018



Service Manual

Split Wall-Mounted Type
Room Air Conditioner
(ALLEGRO SERIES)


Model applied:
42HQE009N/38YE009
42HQE012N/38YE012N
42HQE018N/38YE018








Contents
1. Features 60
2. Specification 61
3. Dimensions 67
4. Refrigeration cycle diagram 70
5. Operation limits 71
6. Wiring diagram 72
2
7. Specification of electrical parts
8. Troubleshooting 80
3
4
6
8
9
10
13
14
14
21
9. Electronic function
10. Exploded view and spare parts list




3
1. Features
1.1 Compact design.
1.2 Quiet operation.
1.3 Anti-icing function at cooling mode.
1.4 Anti-cold air function at heating mode.
1.5 Auto-defrosting and heating recovering function at heating mode.
1.6 Outdoor unit overload current protection.
1.7 Restart function.
1.8 24 hours on/off mode time setting.
1.9 Error self diagnosis function.
4
2.Specification
Model 42HQE009N/38YE009 42HQE012N/38YE012N 42HQE018N/38YE018
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz
Capacity Btu/h 9000 12000 17000
Rated Input W 1040 1320 1980
Rated current A 4.6 5.8 8.9
Cooling
EER W/W 2.50 2.66 2.42
Capacity Btu/h

10500 14000 21000
Rated Input W

1150 1360 2200
Rated current A 5.0 6.0 9.9
Heating
COP W/W

2.7 3.02 2.82
Moisture Removal L/h 1.0 1.2 1.6
Max. input consumption W 1250 1700 2600
Max. current A 6 7.8 13.0
Starting current A 19.8 25 45
Model PG180X1C-4FT3 PG225X2C-4FT PG330*2CS-4KU3
Type Rotary Rotary Rotary
Brand TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 10800 13550/13700 20130/20267
Input W 1015 1290/1335 1980/2105
Rated current(RLA) A 4.5 6.1 9.7/10.3
Thermal protector UP3SE0591-T61 UP3RE0591-T56 Internal
Capacitor uF 30 35 40UF/370V
Compressor
Refrigerant oil ml
RB68AF/T68/68TF
400
RB68AF/T68/68TF
480
750
Model RPG13H RPG20D RPG25
Brand Welling Welling Welling
Input W 38.5 49.2 53
Capacitor uF 1.2 1.5 1.5
Indoor fan motor
Speed(hi/mi/lo) r/min 1100/1020/950 1060/900/800 1260/1100/1000
a.Number of rows 2 2 2
b.Tube pitch(a)xrow pitch(b) mm 21x13.37 2113.37 2113.37
c.Fin spacing mm 1.3 1.3 1.3
d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm 7 Innergroove tube 7, innergroove tube 7,innergroove tube
f.Coil length x height x width mm 578X252X26.74 63531527.34 66023127.34
Indoor coil
g.Number of circuits 2 2 3
Indoor fan Type mm Crossflow Crossflow Crossflow
Indoor air flow (Hi/Mi/Lo) m3/h 470/440/410 580/550/520 800/770/740
Indoor Sound pressure (Hi/Mi/Lo)
(LPA) @cooling
dB(A) 39/35/33 38/34/32 46/43/40
Indoor Sound power (Hi/Mi/Lo)
(LWA) @cooling
dB(A) 54/51/48 52/48/47
5
Dimension (W*H*D) mm 750x250x188 815X280X195 906X286X235
Packing (W*H*D) mm 830x336x280 915X360X275 1020X380X328 Indoor unit
Net/Gross weight Kg 8.5/10.5 10.5/13.5 13.5/16.5
Model YDK25-6C YDK25-6C YDK53-6K
Brand Welling WELLING WELLING
Input W 85 85 93
Capacitor uF 2.5 2.5F/450V 3.0F/450V
Outdoor fan motor
Speed r/min 900 900 640
a.Number of rows 1 2 2
b.Tube pitch(a)xrow pitch(b) mm 25.4X22 21x13.37 25.4x22
c.Fin spacing mm 1.4 1.5 1.7
d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm 9.53,innergroove tube 7,innergroove tube 9.53,innergroove tube
f.Coil length x height x width mm 754X508X22 75050826.74 797x660x44
Outdoor coil
g.Number of circuits 2 2 4
Outdoor fan Type and Diameter mm Propeller Propeller Propeller
Outdoor air flow m3/h 1900 1900 2300
Outdoor Sound pressure
(LPA) @cooling
dB(A) 52 52 54
Outdoor Sound power
(LWA) @cooling
dB(A) 62 62
Dimension(W*H*D) mm 780X540X250 780540250 845X695X335
Packing (W*H*D) mm 910X575X335 910575335 970X770X395 Outdoor unit
Net/Gross weight Kg 36/39 37/40 55/60
Refrigerant type R407c g 840 1150 2100
Design pressure MPa 2.8 2.8 2.8
Liquid side/ Gas side mm(inch) 6.35/9.53 6.35/12.7 6.35/12.7
Max. refrigerant pipe length m 10 10 15 Refrigerant piping
Max. difference in level m 5 5 8
Additional refrigerant
charge over 5m
g/m 30 30 30
Main mm 2.5*1.5*650 3.2*1.7*850 3.2*1.9*820 Expansion device
(Capillary) Sub mm 2.5*1.5*750 3.2*1.7*800 3.2*1.9*500
Operation temp 17-30 17-30 17-30
Ambient temp 7-43 7-43 7-43
Application area m2 14-21 18-26 30-40

Remarks:
1.Cooling capacities are based on indoor air temp. 27 DB, 19 WB and outdoor air temp. 35 DB,
and 24 WB. Heating capacities are based on indoor air temp. 20 DB, 15 WB and outdoor air
temp. 7 DB, and 6 WB.
2. Indoor Sound Pressure level is measured in free field (JIS 9612 std) at 1m distance.
Outdoor Sound Pressure level is measured in hemispherical field, at 4m distance from the unit.
these values are normally somewhat different as a result of ambient condition.

3. Dimensions
3.1 Indoor unit 42HQE009N



3.2 Indoor unit 42HQE012N


6
3.3 Indoor unit 42HQE018N

3.4 Outdoor unit 38YE009 / 38YE012N

3.5 Outdoor unit 38YE018N
1
2
.
5

7

4. Refrigeration cycle diagram

Cooling & heating

Indoor unit outdoor unit
8

Auxiliary accumulator for 12K
Valve
Sensor of room temp
. 4 way valve

Heat exchanger Heat exchanger

Sensor of heat exchanger temp Accumulator
.
Compressor



Valve Capillary


5.Operation limits
5.1Cooling operation
Outdoor unit air temp. DB
45
9

40

35

30

25

20



10 15 20 25 30 35 40
Indoor air temp. DB
Note : The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.

5.2Heating operation
Indoor air temp. DB

30

25

20

15

10

5







DRY COOLING












-5 5 15 25
Outdoor unit air temp. DB
Note : The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.


6. Wiring diagram

6.1 42HQE009N / 38YE009




10
6.2 42HQE012N / 38YE012N










11
6.3 42HQE018N / 38YE018
Y
E
L
L
O
W
CN5
L
O
U
V
E
R

M
O
T
O
R

CN8
A
M
B
I
E
N
T

S
E
N
S
O
R
CN3
S
E
N
S
O
R
CN10 CN7
H
E
A
T

E
X
C
H
A
N
G
E
R
L
O
U
V
E
R

M
O
T
O
R

CN6
I NDOOR MOTOR
G
R
E
E
N
B
L
A
C
K
W
H
I
T
E
TRANSFORMER
D
I
S
P
L
A
Y

B
O
A
R
D
SWI TCH BOARD
C
N
1
2
CN9
COMPRESSOR RELAY
CURRENT DETECTOR
WHI TE
C
N
1
CN4
BROWN
BLUE
CN14
C
N
2






12
13
7. Specification of electrical parts
7.1 Temperature-resistance of room temp. sensor & pipe temp. sensor
Temperature

Resistance
K
Temperature

Resistance
K
Temperature

Resistance
K
-10 62.28 17 14.618 44 4.3874
-9 58.71 18 13.918 45 4.2126
-8 56.37 19 13.263 46 4.0459
-7 52.24 20 12.643 47 3.8867
-6 49.32 21 12.056 48 3.7348
-5 46.57 22 11.5 49 3.5896
-4 44 23 10.973 50 3.451
-3 41.59 24 10.474 51 3.3185
-2 39.82 25 10 52 3.1918
-1 37.2 26 9.5507 53 3.0707
0 35.2 27 9.1245 54 2.959
1 33.33 28 8.7198 55 2.8442
2 31.56 29 8.3357 56 2.7382
3 29.91 30 7.9708 57 2.6368
4 28.35 31 7.6241 58 2.5397
5 26.88 32 7.2946 59 2.4468
6 25.5 33 6.9814 60 2.3577
7 24.19 34 6.6835 61 2.2725
8 22.57 35 6.4002 62 2.1907
9 21.81 36 6.1306 63 2.1124
10 20.72 37 5.8736 64 2.0373
11 19.69 38 5.6296 65 1.9653
12 18.72 39 5.3969 66 1.8963
13 17.8 40 5.1752 67 1.830
14 16.93 41 4.9639 68 1.7665
15 16.12 42 4.7625 69 1.7055
16 15.34 43 4.5705 70 1.6469

7.2 Compressor windings resistance (run & start winding @20)
Compressor model PG180X1C-4DZ3 PG225X2C-4FT PG330*2CS-4KU3
Winding 1 (Main)
3.335% 2.355% 1.545%
Winding 2 (Sub)
3.785% 3.225% 3.045%

7.3 Indoor fan motor windings resistance (@20).
Motor model RPG13H RPG20D RPG25
Winding 1 (Main)
400 327 2098%
Winding 2 (Sub)
430 380 3768%
14

7.4 Outdoor fan motor windings resistance(@20).
Motor model YDK25-6C YDK53-6K
Winding 1 (Main)
170 738%
Winding 2 (Sub)
195 1348%

8. Troubleshooting
For all heat pump model
Failure phenomenon Operation lamp Timer lamp Defrosting lamp
Over current protection of the compressor occurs 4 times X
Indoor fan speed has been out of control for over 1 minute X
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short
circuit
X X
Indoor room temp. sensor is open circuit or short circuit X X
EEROM error On X
r Extinguish
Flash at 5Hz
9. Electronic function
9.1 Electric Control working environment
9.1.1 Input voltage: 175~253V
9.1.2 Input power frequency:50Hz
9.1.3 Ambient temperature: -7C~+43C
9.1.4 Indoor fan normal working amp is less than 1A,
9.1.5 Outdoor fan. Normal working amp is less than 1.5A
9.1.6 Four-way valve normal working amp is less than 1A.
9.1.7 Swing motor: DC12V.
9.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
9.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower
wind.
I
RESTORE
: Amp self-protection return value
TH
DEFROST
: High wind, defrosting temperature difference
TM
DEFROST
: Middle wind, defrosting temperature difference
TL
DEFROST
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
15
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature

9.3 Systematic functions
Remote receiving
Testing and forced run
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at heating mode
9.4 Protection
9.4.1 The compressor functions protection with a delay of three minutes.
9.4.2 Sensor protection at open circuit and breaking disconnection
9.4.3 Temperature Fuse break protection
9.4.4 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High
Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure
information and cant returns to normal operation automatically.
9.4.5 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and cant returns to normal operation automatically.
9.4.6 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark
I< I
RESTORE
On On On
On On Off Heating mode I
RESTORE
<I< I
FAN

Low speed On On Cooling mode
I
FAN
<I<I
5MIN
Off Off After 5 Minutes
Current up
I
5MIN
<I< I
3SEC
Off Off After 3 Seconds
I
5MIN
<I< I
3SEC
Off Off After 3 Seconds
I
FAN
<I<I
5MIN
Off Off After 5 Minutes
On On Off Heating mode I
RESTORE
<I< I
FAN

Low speed On On Cooling mode
Current down
I< I
RESTORE
On On On

If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and cant returns to
normal operation automatically.

9.5 Fan-only mode
16
Fan speed is high/mid/low/ Auto
9.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
T>Ts+1 On On Temp. up
T<Ts+1 Off Off
T>Ts On On Temp. down
T<Ts Off Off

Auto fan at cooling mode:
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<3 Low
3 <T<5 Med.
Temp. up
T>5 High
T>3 High
1 <T<3 Med.
Temp. down
T<1 Low

Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Condition
Temp. Time
Compressor Outdoor fan
T> TE6 On On Temp. up
T< TE6 >5 Minutes Off Off
T> TE5 On On Temp. down
T< TE5 >5 Minutes Off Off

9.7 Dehumidifying mode
9.7.1 The 4-way valve is off in dehumidifying mode
9.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
1 TA TS+2
LOW
BREEZE
ON 6minutes
OFF 4minutes
2 TS TATS+2
LOW
BREEZE
ON 5minutes
OFF 5minutes
3 TA TS
LOW
BREEZE
ON 4minutes
OFF 6minutes
Repeat on and off cycle.

9.7.3 Low room temperature protection:
When room temperature decreases to below 10, compressor and outdoor fan will
stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature
restores to over 13.

9.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as
that of cooling mode.
17
9.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
9.8 Heating mode
9.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way
valve must delay 2 minutes compared with compressor if the compressor changed into
non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode.
9.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost.
9.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off

9.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold
wind function prevails.
Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<TE1 Off
TE1<T<TE2 Breeze
Indoor exchanger temp. up
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
Indoor exchanger temp. down
T<TE4 Off
9.8.5 Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2 High Room temp. up
T>2 Med.
T>0 Med. Room temp. down
T<0 High

9.8.6 Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
9.8.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time

9.9 Defrosting operation (Available for heating only).
9.9.1 Defrosting condition: Defrosting starts when either of the following &:
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the
following:



Temp. of evaporator---room temp.
Fan speed is high TH
DEFROST
Fan speed is mid TM
DEFROST
Fan speed is low TL
DEFROST
Breeze Meet only if it is Breeze

Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor
fan with the compressor still running. Add up to 90 minutes.
9.9.2 Defrosting time
If the temp. difference condition is satisfied for less than 40 minutes, this can be regarded
as severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition is satisfied for more than 40 minutes, the defrosting time is
6 minutes.
If the temp. difference condition is satisfied out of 40 minutes, generally the defrosting time
is 6 minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost.
The circulation is as following:
6-minute defrost 6-minute defrost6-minute defrost10-minute defrost

9.9.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 6 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
DEROST
differs in different
models.
9.9.4 Defrosting Actions:

Defrost 10or 6minutes

45S 25S
Compressor

4-way Valve 23S
40S
Outdoor Fan

Indoor Fan

10S
18
19


9.10 Automatic operation mode
9.10.1 The air conditioner automatically selects one of the following operation modes: cooling,
heating or fan only according to the temp. difference between room temp. (TA) and set temp.
(TS).
TATS Operation mode
TATS>2 Cooling
-1TATS+2 Fan-only
TATS<-1 Heating (air-only for cooling only type)
9.10.2 The indoor fan blows automatically in corresponding selected mode.
9.10.3 The motion of indoor fans blade should accord with the selected operation mode.
9.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor
cannot start for 15 minutes, reselect the operation mode according to the room temp. and set
temp., or reselect when the set temp. varies.

9.11 Forced cooling function
9.11.1 Select forced cooling function with the forced cooling button or the switch.
9.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan
mode is set as low, the A/C operates at the DRY mode with a set temp. of 24.
9.11.3 All protections of remote control cooling are available at forced cooling operation.
9.12 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24.
9.13 Timer Function

9.14 Economic Running
9.14.1 The economic running function is available at cooling, heating or auto mode.
9.14.1 Cooling:
The set temperature rise 1 per hour. Two hours later, the set temperature will maintain as
a constant and the fan speed is kept at low speed.
9.14.2 Heating:
The set temperature decrease 1 per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed (Cold air proof function
takes precedence over all).
9.14.3 Auto:
The economic running function operates in accordance with selected running mode by auto
mode.
9.15 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings
before the power failure when power returns.





20
9.16 Models and Parameters

Model 42HQE009N
38YE009
42HQE012N
38YE012N
42HQE018N
38YE018
I3SEC 10.0A 14.5A 17.0A
I5MIN 7.5A 13.5A 16.0A
IFAN 5.5A 9.5A 15.0A
IRESTORE 4.5A 8.5A 13.0A
IDEFROST 3.5A 6.5A 7A
TE1 28C 34C 34C
TE2 32C 37C 36C
TE3 30C 33C 30C
TE4 26C 22C 20C
TE5 4C 2C 3C
TE6 10C 7C 10C
TE7 60C 62C 64C
TE8 51C 51C 53C
TE9 49C 49C 49C
ANGLCOOL 200 40 50
ANGLHEAT 0 197 105
ANGLOFF 124 100 0
TH
DEFROST
14C 19C 20C
TM
DEFROST
15C 20C 21C
TL
DEFROST
16C 21C 22C

21
HI-WALL split air conditioner
42HQE009N
(product. 2005)
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
1
7
1
8
1
9
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
8
2
9
3
0
3
1
3
2
3
4
3
3
3
6
3
5
3
7
3
8
3
9
1
6
4
0
4
1
4
2
22
HI-WALL split air conditioner
Pos. Description Part No. 009N
Front panel 10312121229 1
Air filter 10309121202 2
Screw cap 10309121203 3
Panel frame 10309121204 1
Air cleaner 10109121226 1
Air cleaner holder 10109121225 1
Window for receiver 10309121207 1
LED indicator 10309121208 1
Horizontal louver 10309121209 1
Vertical louver 10309121210 1
Air out frame 10309121211 1
Louver holder 10309121212 1
Louver rocker 10309121213 1
Rocker gasket 10309121214 1
Louver motor 10121121218 1
Drain hose 10109121215 1
Evaporator temp sensor 10109121242 1
Left holder for evaporator 10309121217 1
Evaporating coil 10409121201 1
Waterproof board 10718121002 1
Bearing holder 10309121220 1
Blower assembly 10309121221 1
Chassis 10309121222 1
Back cover for chassis 10309121223 1
Installation Plate 10909121009 1
Connecting pipe clamp 10309121225 1
Fan motor 10309121226 1
Motor cover 10309121227 1
E-part box cover 10309121228 1
Indicator holder 10309121229 1
Display board assy 10309121240 1
Display board enclosure 10309121231 1
Main control board 10409121001 1
Transformer 10718121006 1
Control box 10718121007 1
Wire clamp 10112121234 1
Wire joint, 5p 10309121242 1
Infrared remote control 10109121207 1
Holder, Remote Controller 10109121208 1
Indoor temp sensor 10109121243 1
Copper nut TLM-B02 10909121013 1
Copper nut TLM-A01 10909121012 1
Electric control ass'y 10409121003 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Models
42HQE Notes
42HQE009N
(product. 2005)
23
Outdoor unit
38YE009
(product. 2005)
2
3
1
2
3
4
5
6
2
4
2
6
7
8
1
8
1
0
1
1
2
8
2
7
1
3
1
6
1
2
1
4
1
5
2
0
9
2
2
2
1
2
5
1
9
1
7
24
Outdoor unit
Pos. Description Part No. 009
Clamp for front net 10112121801 6
Front net 10109121801 1
Front clapboard 13012111801 1
Propeller fan 10112121803 1
Fan Motor 10112121804 1
Holder for fan motor 50312121801 1
Chassis 10209121807 1
Compressor 10718121817 1
Installation plate for valves 10118113805 1
Gas pipe valve 10409121806 1
4-way valve 10409121808 1
Liquid pipe valve 50118121802 1
Fan motor capacitor 10112121815 1
Installation board for E-parts 15009111801 1
Compressor capacitor 11812113811 1
Capacitor Clamp 10109121822 1
Wire terminal 10109121823 1
Left supporter 13012111803 1
Separating board 10116113813 1
Condenser coil 51609121801 1
Water collector 10118121832 1
Right clapboard 13012111808 1
Big Handle 10112121808 1
Cover 13012111805 1
Small Handle 10830121811 1
Rear net 13012111806 1
Supporter for motor holder 13012111807 1
Copper nut TLM-B02 10909121013 1
Copper nut TLM-A01 10909121012 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Models
38YE Notes
38YE009
(product. 2005)
25
HI-WALL split air conditioner
42HQE012N
(product. 2005)
1
2
3
4
5
6
7
8
9
1
0
1
2
1
3
1
4
1
1
1
5
1
6
1
7
1
8
1
9
2
0
2
1
2
2
2
3
2
4
2
5
3
4
3
0
3
1
3
2
3
3
2
9
2
8
2
6
2
7
3
5
3
6
4
0
3
9
4
1
3
7
3
8
26
HI-WALL split air conditioner
Pos. Descrizione / Description Part No. 012N
Front Panel 10312121228 1
Air Filter 10312121202 2
Screw cap 10312121203 3
Panel frame 10912121002 1
Air cleaner 10109121226 1
Air cleaner holder 10109121225 1
Window for receiver 10412121201 1
Display Panel 10912121003 1
Horizontal louver 10312121205 1
Vertical louver 10312121206 1
Louver motor 10312121207 1
Air out frame 10912121004 1
Louver holder 10312121219 1
Louver rocker 10312121218 2
Rocker gasket 10309121214 2
Drain hose 10112121213 1
Left holder for evaporator 10312121209 1
Evaporator 10412121204 1
Waterproof board 10718121002 1
Bearing holder 10309121220 1
Cross flow fan, assy 10312121213 1
Chassis 10312121214 1
Installation Plate 10312121215 1
Connecting pipe clamp 10309121225 1
Fan motor 10312121216 1
Motor cover 15012113006 1
Remote Controller 10109121207 1
Holder, Remote Controller 10109121208 1
Wire joint, 5p 10109121244 1
Wire clamp 10309121235 1
Display board 10412121001 1
Main control board 10412121002 1
E-Parts Box 10312121223 1
Transformer 10718121006 1
E-part box cover 10312121224 1
Indoor temp sensor 10109121243 1
Evaporator temp sensor 10109121242 1
Connection pipe for drainage 11609121003 1
Sealing ring 31009321021 1
Copper nut TLM-A01 10909121012 1
Copper nut TLM-C03 10912121019 1
Electric control ass'y 10118111005 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
Models
42HQE Notes
42HQE012N
(product. 2005)
27
Outdoor unit
38YE012N
(product. 2005)
3
1
2
4
5
6
7
2
4
8
9
1
9
1
1
1
2
2
6
2
7
1
4
1
7
1
3
1
5
1
6
2
1
1
0
2
3
2
2
2
5
2
0
1
8
28
Outdoor unit
Pos. Description Part No. 012N
Clamp for front net 10112121801 6
Front net 10109121801 1
Small Handle 10830121811 1
Front clapboard 11612121804 1
Propeller fan 10112121803 1
Fan Motor 10312111801 1
Holder for fan motor 20409111802 1
Chassis 10312111802 1
Compressor 10721121807 1
Installation plate for valves 10309121809 1
Gas pipe valve 50118121803 1
Four-Way Valve 50118121804 1
Liquid pipe valve 10307121801 1
Fan motor capacitor 10112121815 1
Installation board for E-parts 10312111831 1
Compressor capacitor 30324313020 1
Capacitor clamp 10112121814 1
Wire terminal 10109121823 1
Installation board left 11612121805 1
Separating board 10312121809 1
Condenser coil 20409121801 1
Water collector 10312121811 1
Right clapboard 13012111808 1
Big Handle 10112121808 1
Cover 11612121806 1
Rear net 11612121807 1
Copper nut TLM-A01 10909121012 1
Copper nut TLM-C03 10912121019 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Models
38YE Notes
38YE012N
(product. 2005)
29
HI-WALL split air conditioner
42HQE018N
( product. 2005)
30
HI-WALL split air conditioner
Pos. Description Part No. 018N
Front Panel 10321111047 1
Air filter 10318121202 2
Air cleaner 10109121226 1
Air cleaner holder 10109121225 1
Panel frame 10318121203 1
Display cover 10418111001 1
Evaporator temp sensor 13107121002 1
Clip temperature sensor 10321111036 1
Horizontal louver up 10321111039 1
Horizontal louver down 10321111040 1
Louver motor 10316121202 2
Air outlet frame 10318121208 1
Louver motor cover 10321111045 1
Left holder for evaporator 10318121210 1
Evaporator 10418121201 1
Bearing holder 10318121212 1
Cross flow fan, assy 10318121213 1
Cover left 10318121214 1
Chassis 10318121215 1
Installation Plate 10318121216 1
Connecting pipe clamp 10318121217 1
Relay holder 10318121218 1
Cover right 10318121219 1
Relay proection box 10318121220 1
Fan motor 10318121221 1
Fan motor cover 10318121222 1
Drain hose 10318121223 1
Bush 10318121224 2
louver 10318121225 12
Connect louvers 10318121226 2
Louvers holder 10318121227 1
E-part box cover 10318121228 1
Transformer 10109121204 1
E-Parts Box 11318113002 1
Main control board 10321111041 1
Display board assy 10316121205 1
Cover, indicator light 10318121233 1
Wire clip 10321111042 1
Terminal block 10321111043 1
Wire clamp 10112121234 1
Electric control assembly 10318121209 1
Holder, Remote Controller 10109121208 1
Remote Controller 10109121207 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Models
42HQE Notes
42HQE018N
(product. 2005)
31
Outdoor unit
38YE018
(product. 2005)
32
Outdoor unit
Pos. Description Part No. 018
Guard fan 10321111044 1
Front panel 10924121801 1
Front cabinet assy, right 10118121803 1
Propeller fan 10118121804 1
Fan Motor 12818111807 1
Base pan assembly 10121121802 1
Foam, motor holder 10118121807 1
Cover assembly 10118121827 1
Holder for fan motor 10118121809 1
Separating board 10118111806 1
Small Handle 10109121802 1
Condenser coil assy 10218121801 1
Rear net 10924121809 1
Installation board left 10924121808 1
Right clapboard 10118113804 1
Big Handle 10118121817 1
Installation plate for valves 10118113805 1
Capacitor clamp 10112121814 1
Compressor capacitor 10312121813 1
Fan motor capacitor 10112121815 1
Electric installation plate 12818111803 1
Terminal block 10109121823 1
Washer for wire joint 10112121817 1
Wire clamp 10118121823 1
Liquid pipe valve assy 10218121805 1
Four-Way Valve assy 50418121805 1
Gas pipe valve 50118121803 1
Compressor 50418121806 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Models
38YE Notes
38YE018
(product. 2005)
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1
The manufacturer reserves the right to change any product specifications without notice.

You might also like