Current carrying capacity considering voltage drop of 3% (steady state) and 12% (starting) at 415 Volt

Cable size

3C X 2.5 Sq
MM (Cu)
3C X 4 Sq MM
(Cu)
3C X 10 Sq MM
(Al)
3C X 16 Sq MM
(Al)
3C X 25 Sq MM
(Al)
3C X 35 Sq MM
(Al)
3C X 50 Sq MM
(Al)
3C X 70 Sq MM
(Al)
3C X 95 Sq MM
(Al)
3C X 120 Sq
MM (Al)
3C X 150 Sq
MM (Al)
3C X 185 Sq
MM (Al)
3C X 240 Sq
MM (Al)
3C X 300 Sq
MM (Al)

Current carrying
capacity
considering group
derating factor
(0.6)
18.6

0 mtr

50 mtr

100 mtr

150 mtr

200 mtr

250 mtr

300 mtr

350 mtr

400 mtr

450 mtr

500 mtr

18.6

18.6

9.43

6.28

4.71

3.77

3.14

2.69

2.35

2.09

1.88

24.6

24.6

24.6

15.10

10.06

7.55

6.04

5.03

4.31

3.77

3.35

3.02

27

27

27

21.19

14.12

10.59

8.47

7.06

6.05

5.29

4.70

4.23

40.2

40.2

40.2

33.96

22.64

16.98

13.58

11.32

9.70

8.49

7.54

6.79

53.4

53.4

53.4

53.4

35.69

26.76

21.41

17.85

15.29

13.38

11.89

10.70

65.4

65.4

65.4

65.4

48.64

36.48

29.18

24.32

20.84

18.24

16.21

14.59

79.2

79.2

79.2

79.2

65.07

46.80

39.04

32.53

27.88

24.40

21.69

19.52

100.8

100.8

100.8

100.8

92.29

69.21

55.37

46.14

39.55

34.60

30.76

27.68

122.4

122.4

122.4

122.4

122.4

93.21

74.57

62.14

53.26

46.60

41.42

37.28

144

144

144

144

144

144

140.58

117.15

100.41

87.86

78.10

70.29

166.8

166.8

166.8

166.8

166.8

136.73

109.38

91.15

78.13

68.36

60.77

54.69

191.4

191.4

191.4

191.4

191.4

165.41

132.33

110.27

94.52

82.70

73.51

66.16

228

228

228

228

228

205.25

164.20

136.83

117.29

102.62

91.22

82.10

266.4

266.4

266.4

266.4

266.4

243.00

194.40

162.00

138.86

121.50

108.00

97.20