ABB Lummus Global Best Operating Practices INTRODUCTION Tower trays, internals, and heat exchanger tubes are normally coated with oil or grease to prevent rust and assist manufacture. If the oil is still present on start-up, then it may cause problems. In non-cryogenic service, the main issue is contamination of process streams with oil. In cryogenic towers the oil will become very viscous or freeze, and has low solubility in the process fluids. Resulting problems include: Liquid/vapor capacity may be restricted and downstream equipment may become fouled. Foaming is also possible in some services. If oil is present in a reboiler or condenser, either from tower start-up or tube coating, then heat transfer coefficients or thermosiphon flows can be restricted. MITIGATION Equipment manufacturers must be contacted to obtain the physical properties of the oil, particularly the relationship between viscosity and temperature. If it is determined that equipment performance could be impaired, then the oil must be removed before start-up. It is preferred that this be done with a solvent such as toluene and wiped clean before the trays are installed in the tower. If the trays are already installed, then the oil must be removed in situ. There are several possibilities to consider: Solvent wash Steaming Detergents/Additives Solvent Wash Either toluene or iso-hexane is typically used. There is a need to consider how to ensure good contact between solvent and oil, and how to dispose of contaminated solvent. Solvent wash must be done before dry out, as both solvents are saturated with water. The typical approach would be to part fill the tower, then circulate from bottom to reflux line. Process pumps may be used depending on suitability for this service compared to normal service. The pump manufacturer would have to be contacted. Toluene freezes at 95 o C, so it would have to be fully removed before start-up if used in the demethanizer. In this case iso-hexane would be recommended as it has a freezing point of 154 o C. Note: The freezing point of -154 o C given for iso-hexane is the freezing point of pure 2- Methylpentane. Many commercial iso-hexane products are a mixture of: 2-Methylpentane FP = -154 o C 3-Methylpentane FP = -118 o C 2,2-Dimethylbutane FP = -100 o C 2,3-Dimethylbutane FP = -128 o C Steaming There is a need to consider the mechanical design of tower and suitability for high temperature compared to design. When steam is used the oil viscosity reduces significantly and falls to the bottom with any BOPETH-009 Page 2 of 2 steam condensate. The tower internals must be reviewed for low points and liquid traps. The oil/condensate mixture would then have to be disposed of through the sour water system a route to this system would have to be provided. A steaming period of 12-36 hours to atmosphere is recommended. Keep the tower under nitrogen when steaming is complete to avoid air entering the equipment leading to rusting. Detergents/Additives Biodegradable detergents or other additives can also be used. The detergent is sprayed on in situ. However in the case of tray designs that have low accessibility once installed, this may not be possible. Hot water is then circulated for 12-24 hours, however pump suitability must first be investigated. Disposal of the water/detergent/oil mix must be considered. Use of the sour water stripper may be possible but there is a risk of foaming. Additives, such as those offered by Ondeo Nalco, can be either water or hydrocarbon soluble. The water soluble additives could be disposed of through the sour water system depending on downstream impact, although there is potential for foaming. The hydrocarbon-based additives would need to be investigated for potential downstream process or product quality impact. These additives have been typically used for removal of fouling deposits for tower internal access and cleaning during a turnaround. About 12 hours circulation is recommended, check process pumps for suitability.