You are on page 1of 36

Air Technology Systems, Inc.

Mi ni -Spac e

Air Technology Systems, Inc.


Precision cooling
for server closets
and other tight spaces.
1 to 7 Tons - DX & CW
Vertical Floor Mounted
Precision Air Conditioners
(60 Hz Data)
Engineering Manual
Air Technology Systems, Inc.
Stulz Air Technology Systems, Inc.
1-1
Mini-Space vertical, oor mounted air
conditioning units provide precision tempera-
ture and humidity control for computer rooms
and other critical areas where continuous 24
hrs/day, 365 days/yr operation is required.
Designed for front only access, Mini-Space
systems require minimal oor space. The units
are designed with a wide range of options to
handle both precision and comfort cooling ap-
plications.
Typical applications include:
STULZ-ATS is dedicated to providing innovative
solutions for critical temperature and humidity
control needs. STULZ-ATS designs and manufac-
tures specialized environmental control equip-
ment for commercial, industrial and custom
military applications. STULZ-ATS serves a diverse
marketplace - including telecommunications,
information technology, medical, financial,
educational, industrial process and govern-
ment contracts - utilizing world-class island
manufacturing processes in a modern, 150,000
ft
2
facility. STULZ-ATS combines a global net-
work of sales and service companies with an
extensive factory engineering staff and highly
exible manufacturing resources dedicated to
providing world-class quality, innovation and
customer service.
ISO-9001:2001 Quality Registered
STULZ-ATS is committed to satisfying customer
expectations by meeting and exceeding require-
ments. Our Quality Policy ensures that every
Employee is committed to Customer Satisfac-
tion, Teamwork and utilizing Continuous Pro-
cess Improvement methods in order to deliver
an exceptional product. We will continually
measure our performance to improve the effec-
tiveness of our quality management system.
INDUSTRIES:
Internet / Web Hosting
Telecommunications
Financial / Banking
Insurance
Airlines / Mass Transit
Legal Services
Entertainment
Government
Colleges / Universities
APPLI CATI ONS:
Datacenters
Computer / LAN Rooms
Telecommunications Rooms
Co-location Centers
ISP (Internet Service Providers)
ASP (Applications Service Providers)
Hospital Operating & Isolation Rooms
Laboratories
Air Technology Systems, Inc.
Table of Contents
1-2
SECTION - 1
Introduction to SATS .................................................. 1-1
Table of Contents ...................................................... 1-2
SECTION - 2
Mini-Space SYSTEMS:
Outstanding Advantages ........................................... 2-1
User Oriented Features & Options .............................. 2-2
Available Congurations ......................................... 2-3/4
MODEL NOMENCLATURE:
Nomenclature Chart .................................................. 2-5
Model Nomenclature Specications ........................... 2-6
SECTION - 3
GUIDE SPECIFICATIONS:
Standard Features Index ............................................. 3-1
Standard Guide Specications ................................. 3-2/3
Optional Features Index ............................................. 3-4
Microprocessor Controls Specications ................... 3-5/6
Optional Features Guide Specications ................... 3-7/9
SECTION - 4
PERFORMANCE / CAPACITY SPECIFICATIONS:
DX - Air Cooled Systems ............................................ 4-1
DX - Water Cooled Systems ....................................... 4-3
DX - Glycol Cooled Systems ....................................... 4-4
Chilled Water Systems ............................................ 4-6/7
SECTION - 5
ELECTRICAL DATA: (FLA / MCA / MFS)
Electrical Data Index................................................... 5-1
DX - Compressorized Systems:
Air Cooled, Split Systems ........................................... 5-2
Water Cooled Systems ............................................... 5-2
Glycol Cooled Systems ............................................... 5-2
Chilled Water Systems:
Chilled Water Systems ............................................... 5-3

SECTION - 6
DIMENSIONAL / INSTALLATION DRAWINGS:
Dimensional Drawing Index ....................................... 6-1

Standard Mini-Space "CCU/D" Systems:
1 to 3.5 Ton, Up-Flow Systems ................................... 6-2
1 to 3.5 Ton, Down-Flow Systems .............................. 6-3
5 to 7 Ton, Up-Flow Systems ...................................... 6-4
5 to 7 Ton, Down-Flow Systems ................................. 6-5

Air Technology Systems, Inc.
Mini-Space

Systems
2-1
Mini-Space Systems Offer Outstanding Advantages
Mini-Space systems are designed to be
the compact solution to your smaller ca-
pacity precision air conditioning require-
ments. Systems are available 1 to 7 tons
in the following cabinet foot prints.
1 to 3.5 tons = 23.6 W x 23.6 D
5 to 7 tons = 39.4 W x x31.9 D
Mini-Space systems require front service
access for periodic general maintenance.
They are easily installed side by-side,
tucked into a corner or between cabinets.
The Mini-Space units are especially adapt-
able to raised oors and are available in
both down-ow and up-ow air pattern
congurations.
Down-Flow
Air Patterns
Up-Flow
Air Patterns
Microprocessor Controls
Precision temperature and/or humidity control with
user-friendly, C-5000 series controls, offer a wide range
of functions and alarms.
Complete Temperature & Humidity
Control
Electrode Canister Steam Humidication
Dehumidication Mode with
- Electric Reheat/Heat
- Optional Hot Gas Reheat (Energy $aver)
- Optional Hot Water & Steam Reheat/Heat
Capacity Modulation Options
Hot Gas Bypass Systems
Modulating Chilled Water Valves
Code (UL / CSA) Conformance

- NYC MEA Approved (MEA-163-88-E)
- CSA Compliance
Flexibility
A wide variety of cooling methods are available to meet
your unique requirements.
DX - Air Cooled (w/ Remote Air Cooled Condensers)
DX - Water Cooled (Packaged Units)
DX - Glycol Cooled (w/ Remote Drycoolers &
Pump Packages)
CW - Chilled Water Air Handling Units
Versatility
Plenum Box Spot Cooling & Ducted systems
Self-Contained & Split systems
Front Service Access
Designed for front service access. Mini-Space systems
require minimal oor space and can be installed side by-
side, tucked into a corner or between cabinets.
Wide Size Range
Systems from 1 to 7 tons, Mini-Space systems are de-
signed for 100% front service access. The compact 23.6
x 23.6 (1-3.5 tons) and 39.4 x 31.9 (5-7 tons) require
minimal oor space and are easily tucked into a corner,
between cabinetry or side-by-side.
Non-Proprietary Parts
Mini-Space systems incorporate nonproprietary compo-
nents where possible. Most major HVAC, refrigeration and
electrical distributors stock an exact model cross reference
or an alternate to most factory provided components.
BMS Connection
Unit Sequencing
...and many user friendly features!
Air Technology Systems, Inc. 2-2
User Oriented Features
Scroll Compressors
Mini-Space DX A/C's incorporate
Scroll Compressor Technology. Scroll
Compressors provide higher efciency,
higher reliability and lower sound
power than other compressor
technologies.
24/7 Year Round Operation
Option offerings available with Mini-Space air condition-
ers allow for year-round, 24 hours-a-day system operation
in any environment in the world:
Low Ambient Control (DX - Air Cooled)
-0F Fan Cycling / Fan Speed
-20F Variable Fan Speed
-30F Flooded Head Pressure
Modular Motor Controllers
Mini-Space systems incorporate modu-
lar motor controllers with motor circuit
breakers in lieu of inconvenient replace-
able fuses.
Quiet Operation
Low sound power Scroll compressors coupled with low
RPM blowers, acoustically lined cabinets and low velocity
grilles provide the optimum in quiet operation.
Warranty
- 2 Year Parts Standard
- Optional 5 Year Compressor
Selected Standard Features:
Main Power Non-Fused Disconnect Switch
Modular Motor Controllers (w/ motor circuit breakers)
Acoustical / Thermal Insulation
Aluminum Fin / Copper Tube Coils
Thermal Expansion Valves
Refrigerant Sight Glasses
Refrigerant Filter / Drier Strainers
Liquid Refrigerant Reclaim Valves
Non-Corroding Stainless Steel Drain Pan
High / Low Refrigerant Pressure Switches
Other Available Options:
- 2 & 3-way Grilled Plenum Boxes
- Floor Stands (with & without turning vanes, seismic)
- Condensate Pumps
- Smoke Detectors
- Firestats
- Water Leak Detectors
- Special High Efciency Filtration
- High Pressure DX - Water/Glycol Cooled
Condenser Regulating Valves
- Drycoolers & Pump Packages
- Many more options available!
Mini-Space

100% Front Service Access


Air Technology Systems, Inc. 2-3
Conguration Choices
CHILLED WATER SOURCE SYSTEMS
AIR COOLED SYSTEMS
SPLIT AIR COOLED -
with REMOTE OUTDOOR or INDOOR Air Cooled Condenser
(compressor located with evaporator section)
WATER / GLYCOL COOLED SYSTEMS
WATER COOLED SYSTEMS
GLYCOL COOLED SYSTEMS
CCU/D-41/21-A
(Single Compressor - Split Evaporator)
(Up-Flow or Down-Flow Air Pattern)
Remote Water Source
(supplied by others)
SCS-( )-( )
(SATS Remote Outdoor
Propeller Condenser)
Remote Liquid Chiller
(supplied by others)
CCU/D-171/201-A
(Single Compressor - Split Evaporator)
(Up-Flow or Down-Flow Air Pattern)
SCS-( )-( )
(SATS Remote Outdoor
Propeller Condenser)
CCU/D-110-CW
(Chilled Water System)
(Up-Flow or Down-Flow Air Pattern)
CCU/D-41/21-G
(Single Compressor - Self Contained)
(Up-Flow or Down-Flow Air Pattern)
w/ Optional
Drycooler &
Pump Package
(By Stulz-ATS)
CCU/D-41/21-W
(Single Compressor - Self Contained)
(Up-Flow or Down-Flow Air Pattern)
Remote Liquid Chiller
(supplied by others)
CCU/D-200-CW
(Chilled Water System)
(Up-Flow or Down-Flow Air Pattern)
CCU/D-171/201-G
(Single Compressor - Self Contained)
(Up-Flow or Down-Flow Air Pattern)
CCU/D-171/201-W
(Single Compressor - Self Contained)
(Up-Flow or Down-Flow Air Pattern)
Air Technology Systems, Inc.
Flexible Air Patterns
2-4
Up-Flow Systems:
Down-Flow Systems:
Bottom Discharge
Into Raised Floor
Bottom Discharge
Into Raised Floor
Top "Free" Return with: Top "Ducted" Return with:
Floor Stand
(Optional)
3 4
5 6
1 2
Top "Ducted" Discharge with:
Front "Free" Return
Rear "Ducted" Return
Front "Free" Return
Rear "Ducted" Return
Top Discharge Through 2 or
3-way Grilled Plenum Box with:
Air Technology Systems, Inc. 2-5
Model Nomenclature - "CCU/D" Systems
M
o
d
e
l

N
o
m
e
n
c
l
a
t
u
r
e






-


M
i
n
i
-
S
p
a
c
e

C
C
U
/
D


S
y
s
t
e
m
s
Mini-Space
Floor Mounted Precision Air Conditioners
CC = Compact System
D = Down-Flow Air Pattern
U = Up-Flow Air Pattern
CCU-041-G
A = Remote (Split) Air Cooled
CW = Chilled Water System
G = Glycol Cooled
W = Water Cooled
* SATS Condensers & Condensing Units can be found
in our "Heat Rejection" engineering manual.
* SATS Pump Packages and Drycoolers can be found in
our "Glycol Systems" engineering manual.
Nominal Capacity in kW
Number of Refrigeration Circuits
CCU/D-41/121 & 110-( )
CCU/D-171/201 & 200-( )
Up-Flow Up-Flow Down-Flow Down-Flow
Air Technology Systems, Inc.
Model Nomenclature Specications
M
o
d
e
l

N
o
m
e
n
c
l
a
t
u
r
e














-


M
n
i
-
S
p
a
c
e

C
C
U
/
D


S
y
s
t
e
m
s
2-6
Model Nomenclature
Guide Specications
DX - EVAPORATOR SECTIONS
Air Cooled Remote Evaporator
(Models CCU/D-( )-A)
The system shall be a remote (split) air
cooled, oor mounted precision air
conditioner evaporator. The evapora-
tor section shall house, as a minimum,
the evaporator coil, expansion valve,
return air lter, compressor, evaporator
blower/motor and associated electrical
and refrigeration components.
The CCU/D-( )-A evaporator section
shall be located at some distance from
its corresponding STULZ-ATS model
SCS-( )-( ) outdoor air cooled con-
denser.
The evaporator system shall require
only a single point main power supply
connection; and the system shall ship
from the STULZ-ATS factory with a dry
nitrogen holding charge ready for eld
refrigerant (R407c) charging.
DX - WATER COOLED SYSTEMS
Integral Self-Contained
(Models CCU/D-( )-W)
The system shall be a self-contained,
oor mounted precision air conditioner
to include integral water cooled, plate-
n condenser with factory installed
head pressure water regulating control
valve(s). Condenser (source) water
shall be provided by a cooling tower or
some other remote water source.
The system shall require only single
point supply power connection and
shall ship from the STULZ-ATS fac-
tory with a full operating refrigerant
(R407c) charge.
Water Regulating Valves:
Head pressure shall be automatically
controlled by a factory installed 2-way
water regulating valve rated for 150
psig w.w.p.
(Note: 3-way and high pressure 350 and 400
psig rated valves are optionally available.)
DX - GLYCOL COOLED SYSTEMS

Integral Self-Contained
(Models CCU/D-( )-G)
The system shall be a self-contained,
oor mounted precision air conditioner
to include integral glycol cooled, plate-
n condenser with factory installed
head pressure glycol regulating control
valve(s). Condenser (source) glycol
solution shall be provided via a STULZ-
ATS remote glycol pump package and
drycooler system.
The system shall require only a single
point supply power connection and
shall ship from the STULZ-ATS fac-
tory with a full operating refrigerant
(R407c) charge.
Glycol Regulating Valves:
Head pressure shall be automatically
controlled by a factory-installed, 2-way
glycol regulating valve rated for 150
psig w.w.p.
(Note: 3-way and high pressure 350 and 400
psig rated valves are optionally available, page
3-9.)
CHILLED WATER AIR HANDLERS

Chilled Water System
(Models CCU/D-( )-CW)
The system shall be a oor mounted,
chilled water precision air conditioner
to include chilled water cooling coil,
evaporator blower and motor and
chilled water control valve. Chilled wa-
ter shall be provided by a remote liquid
chiller system.
Chilled Water Control Valve:
Cooling capacity shall be controlled
with a factory installed 3-way modulat-
ing control valve rated for 300 psig.
(Note: 2-way and 3-way and high pressure (to
400 psig) rated valves are optionally available.)
Air Technology Systems, Inc.
Selected Standard Features - "CCU/D" Series
G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s






-


S
t
a
n
d
a
r
d

F
e
a
t
u
r
e
s

"
Q
u
i
c
k
-
R
e
f
e
r
e
n
c
e
"

T
a
b
l
e
3-1
Mini-Space Model 41/61 81/110 121 171/201/200
SELECTED STANDARD FEATURES:
TEMPERATURE CONTROL
1-Stage Cooling Mode Standard Standard Standard Standard
1-Stage Electric Reheating / Heating Standard Standard Optional Optional
2-Stage Electric Reheating / Heating N/A N/A Standard Standard
Cooling &/or Heating Only (No Humidity Control) Optional Optional Optional Optional
HUMIDITY CONTROL
Electrode Canister Steam Humidier Standard Standard Standard Standard
Dehumidication Mode Electric Reheat Standard Standard Standard Standard
CONTROLS
C-5000 Advanced Micropressor w/ Alarms Standard Standard Standard Standard
CABINET
Galvannealed Steel, Powder Coated Finish Standard Standard Standard Standard
Insulated Aluminum Condensate Drain Pan Standard Standard Standard Standard
2 lb/ft
2
Density Thermal & Sound Insulation Standard Standard Standard Standard
Floor Stand (Adjustable, turning vanes optional) Optional Optional Optional Optional
FILTERS / PLENUMS
1, 20% Avg. Eff. Filter Media Standard Standard Standard N/A
2, 30% Avg. Eff. Pleated Filters N/A N/A N/A Standard
2, 60% Avg. Eff. Pleated Filters N/A N/A N/A Optional
2 or 3-way Plenum Box (Up-Flow Units) Optional Optional Optional Optional
DX-REFRIGERATION CIRCUIT
HFC-R407 Refrigerant Standard Standard Standard Standard
Scroll Compressors Standard Standard Standard Standard
Rotolock Service Valves Standard Standard Standard Standard
High Efciency, Aluminum Fin / Copper Tube Coils Standard Standard Standard Standard
Thermal Expansion Valves Standard Standard Standard Standard
Refrigerant Sight Glasses & Filter/Drier Strainers Standard Standard Standard Standard
BLOWERS / MOTORS
Direct-Drive Evaporator Blower / Motor Standard Standard Standard N/A
Belt-Drive Evaporator Blower / Motor N/A N/A N/A Standard
ELECTRICAL
1 or 3-Phase Power Supply - - -- - - - - - See Electrical Tables Section 5 - - - - - - - - - - - -
Multi-Voltage Control Transformer (24V Class 2) Standard Standard Standard Standard
SAFETY FEATURES
C5000 Visual Local & Remote Alarms Standard Standard Standard Standard
Main Power Non-Fused Disconnect, unit mounted Standard Standard Standard Standard
High / Low Refrigerant Pressure Switches (DX units) Standard Standard Standard Standard
Motor Overload Protection Standard Standard Standard Standard
SPECIFIC MODEL STANDARD FEATURES:
AIR COOLED
Low Ambient Head Pressure Control - - - - - - - - - -Three types 0F, -20F or -30F*- - - - - - - - - -
*Flooded head pessure control not available on all models.
Remote Air Cooled Condenser Standard Standard Standard Standard
WATER / GLYCOL COOLED
2-way, 150 psig Water/Glycol Regulating Valves Standard Standard Standard Standard
High Pressure &/or 3-way Valves Optional Optional Optional Optional
Stainless Steel Brazed Plate Heat Exchanger Standard Standard Standard Standard
CHILLED WATER SYSTEMS (CCU-110/200-CW)
3-way, 300 psig Modulating Valve N/A Standard N/A Standard
2-way, 300 psig Modulating Valve N/A Optional N/A Optional
2 or 3-way, 400 psig Modulating Valve N/A Optional N/A Optional
Air Technology Systems, Inc.
Guide Specications - Standard Equipment
G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s






-


S
t
a
n
d
a
r
d

E
q
u
i
p
m
e
n
t
3-2
QUALITY ASSURANCE
(ISO-9001:2001 Registered)
STULZ-ATS operates in an ISO-
9001:2001 registered quality con-
trol environment. Each STULZ-ATS
employee is committed to satisfying
his or her customer expectations
with the highest level of consistent,
measurable and continuous quality
improvement.
GENERAL GUIDE
SPECIFICATION
General Description
The system shall be a oor mounted
air conditioner designed and built to
provide precision temperature and
humidity control. The system shall be
complete and factory run-tested before
shipment. The system shall be Intertek
Laboratory (an NRTL) listed and labeled
in compliance with UL 1995 and CSA
C22.2 No. 236.
The system shall be manufactured by
Stulz Air Technology Systems, Inc. in
Frederick, Maryland, USA.
Service Access
The air conditioner shall require front
access for all routinely serviced compo-
nents. In rare cases of critical compo-
nent failure, additional access shall be
required (CCU/D-41 to 121).
Cabinet Construction
Access panels shall be fabricated from
heavy gauge steel and shall be se-
curely attached to the base and top
plates. Access panels shall be powder
coated to match and provide corrosion
protection. The panels shall be lined
with 1/2 (13 mm), 2 lb/ft
2
(.90 kg),
high-density sound and thermal insula-
tion and sealed with self-extinguishing
gasketing conforming to NFPA 90A
and 90B.
Electrical System
Modular Motor Controllers
The system shall incorporate modular
motor controllers utilizing motor start
protectors and circuit breakers elimi-
nating the need for fusing, as well as
providing:
Motor branch circuit short circuit
protection
Motor load switching controllers
(contactors)
Motor overload protection
The system shall incorporate over-
current and overload protection in
accordance with UL 1995 require-
ments. Each blower motor, compres-
sor, electric heater stage and humidier
(if applicable) shall be provided with
a factory mounted and wired starter/
contactor.
The control circuit shall be a 24 VAC
Class 2 low voltage circuit including
a circuit breaker for protection. Low
voltage, high voltage and grounding
wires shall be color coded and shall be
individually numbered at each end for
ease of service tracing. All wiring shall
be in accordance with the National
Electric Code (NEC).
Main Power - Electric
Non-Fused Service Switch
As a factory standard, a unit-mounted
main power service switch shall be
provided. The service switch shall be a
dust-proof, non-fused type with lock-
able handle.
Evaporator Coils
Evaporator systems shall be congured
for a draw-thru air pattern to provide
uniform air distribution over the evapo-
rator coil face. The coils shall be seam-
less drawn copper tubes, mechanically
bonded to tempered aluminum ns
with n pattern designed for maximum
heat transfer. Coil end plates shall be
hot dipped galvanized.
The evaporator coil shall be mounted
in an insulated stainless steel
condensate drain pan.
DX-Refrigeration System
All refrigeration piping shall be refrig-
erant grade tubing. Each refrigerant
circuit shall include, as a minimum,
refrigerant drier/strainer, sight glass
with moisture detector, thermal expan-
sion valve with rapid bleed port feature
and external equalizer, evaporator coil,
compressor, high pressure switch with
manual reset and a low pressure switch
with automatic reset.
Split/Remote systems shall have a liquid
line solenoid for refrigerant isolation
to prevent liquid slugging. All high
pressure joints shall be brazed and the
entire system shall be pressure tested
at the factory with dry nitrogen, evacu-
ated to at least 50 microns and fully
charged with refrigerant.
Note: All split/remote DX systems ship with a
dry nitrogen holding charge. All self-contained
DX systems ship with a full refrigerant (R407c)
operating charge.

Scroll Compressors
Each compressor shall be a high ef-
ciency, high reliability and low sound
Scroll Compressor.
The compressor shall be complete with
charging and service schraeder ports,
internal vibration isolation, internal
thermal overloads, internal pressure re-
Air Technology Systems, Inc.
Guide Specications - Standard Equipment
G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s






-


S
t
a
n
d
a
r
d

E
q
u
i
p
m
e
n
t
3-3
lief valve, internal discharge gas vibra-
tion eliminator and external vibration
mounting isolation.
Chilled Water Systems
Cooling Coil:
The chilled water cooling coil shall
be contructed of seamleess drawn
copper tubes, mechanically bonded
to tempered aluminum ns for maxi-
mum heat transfer. Coil end plated
shall be hot dipped galvanized.
The cooling coil shall be mounted in
an insulated aluminum condensate
drain pan.
CW Control Valve
Cooling capacity shall be controlled
by a factory installed 3-way, mod-
lodulating control valve rated for a
mazimum 300 psig w.w.p.
(Note: 2-way and 3-way and high pressure (to
400 psig) rated valves are optionally available.)
Blowers/Motors
Direct Driven Systems
(Models CCU/D-41 to 121)
The blower shall be direct-driven with
double-width, double-inlet house-
ing and forward-curved blades. The
blower shall be dynamically and
statically balanced to minimize vibra-
tion and operate in in the Class 1
range. The blower shall be corrosion
protected. The blower motor shall
have internal overload protection.
Additionally, the fan speed shall have
a manual adjustment via a potetiom-
eter to meet specic air-ow require-
ments.
Belt Driven Systems
(Models CCU/D-171 to 201)
The blower shall be belt driven with
double width, double inlet housing
and forward curved blades and perma-
nently lubricated ball bearings sized for
an average 100,000 hours of service
life. The blowers shall be dynamically
and statically balanced to minimize
vibration and operate in the Class I
range.
The blower shall have an adjustable
base for belt tensioning and a locking
system to prevent the motors from
moving. The motors drive sheaves
shall have an adjustable pitch to
change the speed of the blowers. The
motor(s) shall be 1725 RPM and shall
have overload protection and a mini-
mum NEMA service factor of 1.15.
Evaporator Air Patterns
UP-FLOW:
(CCU-( )-( ))
The air conditioner shall be congured
for an up-ow air pattern with free
evaporator return air through front
ltered grille and conditioned supply
air through the top of the unit.
(A top 1" anged duct connection shall be
provided as a standard. 2 & 3-way top discharge
plenum boxes are optionally available)
DOWN-FLOW:
(CCD-( )-( ))
The air conditioner shall be cong-
ured for a down-ow air pattern with
free evaporator return air to the top
and conditioned supply air discharge
through bottom of the A/C into the
raised oor. (Floor Stands are option-
ally available.)
(A top 1" anged return air duct connection is
optionally available.)
Air Filtration
The air conditioner shall have slide out,
1 deep (CCU/D 41-121), or 2 deep
(CCU/D 171-201), lters. The lters
shall be easily accessed through the
front. (see page 3-7)
DX - Heat Rejection
Water/Glycol Cooled Condensers
SS Brazed-Plated:

Each evaporator refrigerant circuit shall
be provided with a factory installed
single pass, counterow congured
brazed plate heat exchanger, with inte-
gral subcooler, constructed of type 316
stainless steel; designed and tested for
a 450 psig. w.w.p.
2-Way, 150 psig Regulating Valve
Each refrigerant circuit's head pressure
shall be controlled by a factory installed
2-way water / glycol regulating valve
rated for 150 psig. w.w.p.
(Note: 3-way and high pressure water/glycol
regulating valves are optionally available)
Controls
The Standard Mini-Space system
includes the C5000 microprocessor
controller, canister steam humidier,
and dehumidication mode with elec-
tric reheat/heat providiong precision
temperature and humidity control. (see
page 3-5)
Air Technology Systems, Inc.
Optional Features - Guide Specications
O
p
t
i
o
n
a
l

F
e
a
t
u
r
e
s






-




I
n
d
e
x
3-4
OPTION ........................................ page
Microprocessor Controls
C-5000 Microprocessor (standard) ......................3-5/6
- User Interface ............................................................ 3-5
- Alarms ................................................................... 3-5
- Control Inputs/Outputs ........................................... 3-5
- Security .................................................................. 3-6
- Diagnostics & Services ............................................ 3-6
- Multi-Unit Sequencing ............................................ 3-6
Remote BMS communications .............................. 3-6
Humidity Control Options
Steam Humidier (standard) ................................. 3-7
Dehumidication Cycle
- Electric Reheat / Heat (standard) ............................. 3-7
- Hot Gas Reheat ...................................................... 3-7
- Hot Water Reheat / Heat ........................................ 3-7
- Steam Reheat / Heat ............................................... 3-7
- Electric SCR-Fired Reheat / Heat .............................. 3-7
High Efciency Filtration (IAQ)
IAQ High Efciency Filters .......................................... 3-7
Head Pressure Control Options
Air Cooled - Low Ambient Control
0F Ambient ........................................................... 3-8
-20F Ambient ........................................................ 3-8
-30F Ambient ........................................................ 3-8
Water/Glycol Cooled - Regulating Valves
2-way, 150 psig (standard) ..................................... 3-8
2-way, 350 psig ...................................................... 3-8
2-way, 400 psig ...................................................... 3-8
3-way, 150 psig ...................................................... 3-8
3-way, 350 psig ...................................................... 3-8
3-way, 400 psig ...................................................... 3-8
DX - Capacity Modulation
Snap-Acting, Hot Gas Bypass ................................ 3-8
Accessories
Adjustable Floor Stands ............................................. 3-8
- Seismic Floor Stand ................................................ 3-9
- Turning Vanes ......................................................... 3-9

2 or 3-Way Plenum Discharge Box ....................... 3-9
Condensate Pump .................................................. 3-9
Smoke Detector .................................................... 3-9
Firestat .................................................................. 3-10

Remote Water Detector:
- Qty. One, Spot Type .............................................. 3-10
- Qty. Two, Spot Type .............................................. 3-10
- 25 Ft. - Strip/Cable Type ....................................... 3-10
- Water Detector Auxiliary Contact ......................... 3-10

Acoustical Compressor Sound Jackets ............... 3-10
Optional Features Index
Air Technology Systems, Inc.
Microprocessor Controls
M
i
c
r
o
p
r
o
c
e
s
s
o
r

C
o
n
t
r
o
l
s
3-5
C5000 Microprocessor
Temperature & Humidity Controller
with Alarms
The Mini-Space oor mounted A/C
shall be provided with STULZ-ATS
C5000 Microprocessor based Tem-
perature and Humidity controller with
Alarms. The controller shall incorporate
a user-friendly operating environ-
ment, to allow easy system setup and
operation.
The C5000 is a complete microproces-
sor based control system designed for
operating, controlling and monitoring
the precision air conditioning unit.
The C5000 controller shall include a full-
featured LED display for visual indication
of the units operating conditions.
User Interface
The user interface shall feature an easy
to read, liquid-crystal alpha-numerical
display. The keypad/display allows
the operator to visually monitor and
customize unit functions and settings.
The controller is operated via a 4-key
menu-driven windows type structure,
in three different modes: Information,
Operation, and Servie.
Field Congurable
The C5000 controller is eld program
congurable and capable of matching
the unique needs of any data center,
telecommunication or other critical
area.
Sensor Location Options
As a standard, the C5000 temperature
and humidity sensor shall be factory unit
mounted in the return air stream of the
Precision AC unit, after the return air
lter(s).
System Setup & Adjustments
The C5000 shall be completely factory
preprogrammed, and therefore, most
applications will require no eld setup.
However, the default set points and
their ranges are easily adjusted from
C5000 keypad/display.
Unit Status Display
The C5000 keypad displays current unit
functions and room status:
Current Dry Bulb Temp Set Point
Current Relative Humidity Set Point
Current Unit Status
System ON/OFF
Cooling
Heating
Humidifying
Dehumidifying
Reheating
Run Times
The historical run-time in hours of the
following major components shall be
available directly from the C5000 key-
pad/display: (if applicable)
Blower Motor(s)
Humidier
Chilled Water Valve
Alarm Conditions
Alarm conditions activate an audible
and visual indicator. An alarm shall be
acknowledged through a Reset button
located on the keypad display.
The C5000 alerts to the following alarm
conditions (if applicable):
High Temperature
Low Temperature
High Humidity
Low Humidity
Smoke Detection
Firestat
Leak Detection
Sensor Failure
Dirty Filter
Loss of Air Flow
Summary Alarm Contact
A summary alarm dry-contact (n/o) con-
nection shall be available for remote
annunciation of an alarm condition.
Alarm History
The C5000 controller provides users with
a recorded history of the last 80 alarms,
including the time and date of the alarm
occurance.
Control Inputs/Outputs
The C5000 is capable of both digital
(on/off) and analog input and output
device control. Prior to shipment, each
Precision AC units C5000 is factory
program congured to match the unit
system operational requirements.
Temperature Anticipation
The C5000 shall incorporate a self-cali-
brating and self-adjusting control logic
that adjusts the response of the STULZ-
ATS air conditioner to changes in tem-
perature and humidity. The system shall
provide premium setpoint accuracy while
controlling the room conditions rate
of change, minimizing the equipment
energy consumption and maximizing the
systems operating life and reliability.
Power Loss Restart
In the event of a loss of power to the
system, the C5000 can be congured
for Automatic or Manual Restart. The
C5000s non-volatile memory enables
the system to restart when power is
restored, without the loss of the last
stored set points and other system con-
guration settings.
Sequential Load Activation
To minimize the total in rush current
Air Technology Systems, Inc.
Microprocessor Controls
M
i
c
r
o
p
r
o
c
e
s
s
o
r

C
o
n
t
r
o
l
s
3-6
loads during system startup/restart, the
C5000 controller shall be congured for
time-delay sequence startup. The user
can designate specic unit restart time-
delays, as well as, each units respective
electric heater and/or humidier. Unit
restart delay can be adjusted from 0 to
10 minutes.
Recovery Delay
After a power loss, the C5000s Recovery
Delay feature allows the system to oper-
ate without initiating any high or low
temperature or humidity alarms for a
delayed period. This feature allows time
(15 to 60 minutes adj.) to pull-down
the conditioned spaces load without
nuisance alarms during initial startup or
power loss restart.
Security
Multiple security levels prevent unauthor-
ized adjustment of critical system control
parameters.
Diagnostic & Service Mode
The C5000 shall incorporate a unique
self-diagnostics algorithm that continu-
ally tests systems functions and hardware
operation. In the event of such a failure,
the user will be alerted to the condition
via a visual and audible alarm.
Control Board
The Control Board shall initiate a self-test
of the control system.
Input Diagnostics
All system inputs and output devices shall
be continuously monitored for proper
operation.
Night Set-back
The C5000 shall include Night Set-Back
occupied/non-occupied energy saving
modes. This feature enables the user
to customize each units daily 5-day/
weekly and 2-day/weekend operational
schedule.
Remote BMS Connection
MIB GATEWAY (Optional)
C5000 Inputs & Outputs shall be
remotely monitored (address read-
able) and remotely controlled (address
writable) via any building management
system (BMS)/local area network (LAN)
control system that can communicate
via a ModBus protocol. Each C5000
congured for BMS communication
shall incorporate an RS-485 Serial
Communication Port that is eld con-
nected to a factory-provided wall-
mounted MIB Gateway.

MIB-FS GATEWAY (Optional)
C5000 Inputs & Outputs shall be
remotely monitored (address read-
able) and remotely controlled (address
writable) via a building management
system (BMS)/local area network (LAN)
control system. Available Protocols,
Modbus RTU, Modbus TCP/IP, Bacnet
IP, Bacnet MSTP, Bacnet Ethernet,
Metasys N-2, and Lonworks.
Each C5000 congured for BMS com-
munication shall incorporate an RS-485
Serial Communication Port that is eld
connected to a factory-provided, wall-
mounted MIB Gateway. The MIB-FS
requires eld conguration. Number
of units, type of protocol employed,
and individual data-points monitored
must be congured in the MIB-FS prior
to use.
Air Technology Systems, Inc.
Optional Features - Guide Specications
O
p
t
i
o
n
a
l

F
e
a
t
u
r
e
s

-


G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s
3-7
Mini-Space oor systems include
the or C5000 Microprocessor
Controller, Electrode Canister Steam
Humidier and Dehumidication
Mode with Electric Reheat/Heat
for total temperature and humidity
control, as a standard.
However, these standard features
can be deleted and/or substituted
with alternate features to allow you
the exibility to select the congu-
ration best suited for your unique
application.
SELECTED OPTIONS
Humidity Control
Canister Steam Humidication:
(standard)
The humidier shall be an electrode
steam canister type and shall have
an adjustable humidity output setting
from 25 to 100% of the full rated
humidier capacity. The humidi-
er shall incorporate an automatic
ush cycle that senses the current
consumption of the humidier and
controls mineral concentration of the
water. A Change Cylinder light
shall notify service personnel when
the humidication output is below
rated requirements and when mainte-
nance is due.
Dehumidication Cycle:
(standard)
The oor A/C shall be provided with a
refrigeration based dehumidication
mode. Moisture is condensed on the
cooling coil and discharged through
the condensate drain. Reheat (electric,
hot gas, steam or hot water) shall be
provided to offset sensible cooling dur-
ing the dehumidication cycle.
Electric Heat/Reheat:
(standard)
CCU/CCD-41/121-( )
A factory-mounted and wired electric
resistance heater shall be included to
provide automatic sensible reheating
mode during the dehumidication
cycle and automatic heating mode
as required. Electric heaters shall be
provided with thermal/magnetic circuit
breakers which shall protect each con-
ductor. Included shall be one automatic
resetting and one manual resettable,
over-temperature safety device (pilot
duty).
CCU/CCD-171/201-( )
A factory mounted and wired low-
watt density, plated n-tubular design
electric resistance heater shall be
included to provide automatic sen-
sible re-heating as required during the
dehumidication cycle and automatic
heating mode. Electric heaters shall
be provided with miniature thermal/
magnetic circuit breakers, which shall
protect each ungrounded conductor.
Also included will be one automatic
reset and one manual reset over-tem-
perature safety device (pilot duty). Two
stages of electric reheat/heat shall be
provided as standard.
Reheat Options
Hot Gas Reheat:
(Models CCU/D-( )-A, W, & G only)
A factory piped and wired hot gas
reheat valve shall be provided to divert
the hot compressor discharge gas from
the condenser to the hot gas reheat
coil during the dehumidication cycle.
This energy saving feature shall require
no additional energy to assist in offset-
ting the sensible cooling capacity while
in the dehumidication mode.
Hot Water Reheat/Heat
A factory-installed, copper tube,
aluminum n heat/reheat coil and
2-way control valve shall be provided
to control the ow of hot water for
automatic sensible reheating mode
during the dehumidication cycle and
automatic heating mode as required.
Air Filtration
Mini-Space vertical oor A/C's are
available with the following standard
and optional high efciency IAQ con-
scious ltration:
F1: 1", 20% Eff. Filter Media
F2: 2", 30% Eff. Pleated Filters
F2: 2", 60% Eff. Pleated Filters
Air Pattern Type Filters Avail.
Up-Flow Units:
CCU-41/121-A/W/G & CCU-110-CW
w/ front free return F1
w/ ducted rear return F2
CCU-171/201-A/W/G & CCU-200-CW
w/ front free return F2, F3 (optional)
w/ ducted rear return F2, F3 (optional)
Down-Flow Units
CCD-41/121-A/W/G & CCD-110-CW
w/ top return F1
CCD-41/121-A/W/G & CCD-110-CW
w/ top return F2, F3 (optional)
Filter ratings are based on dust spot
efciency ratings per ASHRAE Test
Standard 52-76.
Air Technology Systems, Inc.
Optional Features - Guide Specications
O
p
t
i
o
n
a
l

F
e
a
t
u
r
e
s

-


G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s
3-8
Head Pressure Control
AIR COOLED - Low Ambient
0F, Pressure Fan Cycling
The air cooled system shall incorporate
a low ambient fan cycling / fan speed
head pressure control for year-found
air conditioning system operation
down to 0F DB minimum ambient air
temperature.
-20F, Variable Fan Speed Control
The air cooled system shall incorporate
a low ambient variable speed fan head
pressure control for year-found air
conditioning system operation down
to -20F DB minimum ambient air
temperature.
-30F, Flooded Control
The air cooled system shall incorporate
a low ambient ooded head pres-
sure control for year-round system
operation down to -30F DB minimum
ambient air temperature.
This option shall include factory
installed crankcase heaters, cold-start
relays, liquid refrigerant receivers with
receiver liquid level sight glass and
head pressure regulating valves for
ooded condenser operation.
(Note: Flooded head pressure control is available
on CCU/D-171/201-A/W/G models only.)
WATER / GLYCOL COOLED

DX Water Cooled and Glycol Cooled
systems are available with following
standard (V1) and optional (V2-V6)
head pressure regulating control valves:
V1: 2-way, 150 psig (standard)
V2: 2-way, 350 psig
V3: 2-way, 400 psig
V4: 3-way, 150 psig
V5: 3-way, 350 psig
V6: 3-way, 400 psig
Each refrigerant circuit's head pressure
shall be controlled by a factory installed
____-way water / glycol regulating
valve rated for ____ psig. w.w.p.
DX - Capacity Modulation/
Freeze Protecion
SNAP-ACTING, Hot Gas Bypass
(Models CCU/D-( )-A, W & G only)
The Mini-Space oor A/C shall incor-
porate a snap acting hot gas bypass
system to provide modulation of the
units cooling capacity and evaporator
coil freeze protection under low load
conditions.
Chilled Water Control Valves

Chilled water cooling shall be con-
trolled by the following standard and
optinal control valves:
Models CCU/D-110/200-CW:
V1: 3-way, 300 psig (standard)
V2: 3-way, 400 psig
V3: 2-way, 300 psig
V4: 2-way, 400 psig
Standard Valve Control:
A ____-way modulating CW cooling
control valve rated for a maximum
______ psig w.w.p. shall be factory
installed. Precision cooling control
shall be accomplished via a modulating
control signal to th control valve.
ACCESSORIES
Adjustable Floor Stand
A _____ " high adjustable oor stand
shall be provided to allow for ease of
installation of the Mini-Space A/C onto
a raised oor. The oor stand shall be
eld installed.
DIMENSIONAL DATA - FLOOR STAND HEIGHTS
A DIMENSION
TURNING VANE
NOMINAL HEIGHT
ADJUSTABLE HEIGHT
MAX MIN
4 upow only 3.5 4.5 Not available
6 5.0 7.0 Not available
12 11.0 15.0 Optional
15 14.0 18.0 Optional
18 17.0 21.0 Optional
24 23.0 26.0 Optional
Note: For additional oor stand heights, please
contact your local SATS sales representative.
Additional Floor Stand
Options:
Seismic Zone-4 Rate:
The adjustable oor stand shall be
certied rated for seismic zone-4 instal-
lation.
Air Technology Systems, Inc.
Optional Features - Guide Specications
O
p
t
i
o
n
a
l

F
e
a
t
u
r
e
s

-


G
u
i
d
e

S
p
e
c
i


c
a
t
i
o
n
s
3-9
Turning Vanes:
Turning vanes shall be factory pro-
vided for eld installation to each
unit's oor stand.
Top Discharge Plenum Box
(Up-Flow units only)
A 2 or 3-way (please specify) plenum
discharge box shall be provided. The
plenum box shall include double-
deecting, adjustable grilles. The
plenum box shall ship separately for
rigging purposes.
Condensate Pump
(Factory Mounting Available)
A condensate pump shall be
factory- installed on models CCU/D-
171/201-A/W/G, and shall ship loose
on all other models for automatic
removal of condensate and humidi-
er ush water (if applicable).
The condensate pump shall include
an internal overow safety oat
switch which, when wired to the
A/C's remote stop/start terminals,
shall open the A/C's control circuit,
thereby shutting the A/C down in the
event of a condensate overow.
The condensate pump shall be
specically designed to operate with
the higher condensate temperatures
caused by the ush and drain cycle of
the electrode canister humidiers.
The condensate pump shall be rated
for 145 GPH at 40 ft. of head with a
shut-off at 50 ft. of head.
Smoke Detector
A photo-electric smoke detector shall
be factory-installed in the Mini-Space
evaporator section on the suction side
of the evaporator blower.
The smoke detector shall be rated for
high air velocity applications, and shall
shut down the air conditioner upon
sensing smoke in the return air stream.
Optional Auxiliary Contact:
An auxiliary dry-contact (n/o) termi-
nal connection shall be provided for
remote notication of a smoke detec-
tion alarm.
Firestat
The air conditioner shall be provided
with a factory wired and mounted r-
estat. The restat shall shut down the
air conditioner upon sensing a high
return air temperature.
Remote Water Detectors
Single (one) - Spot Type Detector:
Quantity 1-(one) remote spot type
water/leak detector per A/C unit shall
be factory provided for remote eld
installation. Upon sensing a water
leak, the normally closed water detec-
tor control circuit shall open, thereby
shutting down the air conditioner's
water producing operations.
25 Ft. - Strip/Cable Type Detector:
A 25 ft. in length remote strip/cable
type water/leak detector shall be
factory provided for remote eld in-
stallation. Upon sensing a water leak,
the normally closed water detector
control circuit shall open, thereby shut-
ting down the air conditioner's water
producing operations.
Optional Auxiliary Contact:
An auxiliary dry-contact (n/o) termi-
nal connection shall be provided for
remote notication of a water detec-
tion alarm.
Low Entering
Condenser Water Kit
For Water/Glycol systems that require
entering condenser water tempera-
tures from 65F to 45F, the system
shall be provided with a factory in-
stalled in-line liquid refrigerant receiver
to help reduce the negative effect the
low condenser source can have on the
evaporator. A compressor crankcase
heater shall also be provided standard
with this option. (Compressor Sound
Jackets are not available with this op-
tion due to the crankcase heater).
Air Technology Systems, Inc.
Performance/Capacity Specications - Index
P
e
r
f
o
r
m
a
n
c
e
/
C
a
p
a
c
i
t
y

S
p
e
c
i


c
a
t
i
o
n
s



-




I
n
d
e
x
4-1
MODEL TYPE ................................ page
Air Cooled
Air Cooled Systems
- CCU/D-041/201-A .................................................. 4-2
Water Cooled
Water Cooled Sytems
- CCU/D-041/201-W ................................................. 4-3
- Water Cooled Condenser Data ............................... 4-3
Glycol Cooled
Glycol Cooled Sytems
- CCU/D-041/201-G ................................................. 4-4
- Glycol Cooled Condenser Data ............................... 4-4
Chilled Water
Chilled Water Systems
- CCU/D-110/200-CW ........................................... 4-6/7

Index
Air Technology Systems, Inc.
Air Cooled - 1 to 7 Ton "CCU/D"
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


A
i
r

C
o
o
l
e
d

(
1

t
o

7

T
o
n

S
y
s
t
e
m
s
)
4-2
CCU/D Model CC( )-41-A CC( )-61-A CC( )-81-A CC( )-121-A CC( )-171-A CC( )-201-A
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH
Total 17,500 24,020 31,960 41,510 47,490 64,180
Sensible 15,900 21,080 22,460 36,920 47,490 64,180
72FDB/60FWB, 50% RH
Total 17,000 22,640 30,180 39,290 45,300 60,570
Sensible 15,500 20,040 22,560 36,060 45,300 60,570
70FDB/58.5FWB, 50% RH
Total 16,000 21,980 29,200 38,210 43,400 58,980
Sensible 14,800 19,830 22,060 35,060 43,400 58,980
75FDB/61FWB, 45% RH
Total 16,700 23,340 30,580 39,640 48,100 65,150
Sensible 15,600 22,360 25,170 39,310 48,100 65,150
72FDB/58.5FWB, 45% RH
Total 16,300 21,920 28,870 38,410 45,320 62,030
Sensible 15,300 21,860 24,670 38,100 45,320 62,030
70FDB/57FWB, 45% RH
Total 16,000 21,120 27,900 37,400 43,420 59,990
Sensible 15,100 21,120 24,080 36,810 43,420 59,990
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat
ELECTRIC REHEAT / HEAT - (Standard)
Htr Kw Rating (No. of Stages) 2 Kw (1-stg) 2 Kw (1-stg) 2 Kw (1-stg) 4 Kw (2-stg) 12 Kw (2-stg) 12 Kw (2-stg)
Tot BTU/H (Kw) w/ Evap Mtr Ht: 8,730 (2.6) 8,730 (2.6) 8,730 (2.6) 15,560 (4.6) 48,580 (14.2) 48,580 (14.2)
HOT GAS REHEAT - (Optional)
BTU/H 8,769 8,100 11,471 13,430 13,982 19,892
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional)
BTU/H 31,465 31,465 63,475 63,475 114,450 124,902
GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) 12.8 / (2.8)
Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
Humidication - Electrode Steam Canister Humidier with Adjustable Output, (Standard)
Lbs/Hr, (Kw Input) 2-5, / (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4)
Std Control Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 3/4 Hp 3/4 Hp 3/4 Hp 3/4 Hp 3.0 Hp 3.0 Hp
CFM @ ext. st. press. 1,180 @ 0.2 1,180 @ 0.2 1,180 @ 0.2 1,890 @ 0.2 3,450 @ 0.3 4,130 @ 0.3
Drive Method Direct Direct Direct Direct Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 4/ 3.25 4/ 3.25 4/ 3.25 4/ 3.25 4/ 8.3 4/ 8.3
Face Velocity, fpm 363 363 363 581 415 498
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1)
Power Input (Watts, Input ea) 2,570 2,374 3,362 3,936 4,098 5,830
Tot. Heat of Rej. (BTU/H) 28,000 34,220 45,540 56,520 69,880 92,480
Filters - 1 deep (41/121) & 2 deep (171/201), 30% Average Efciency, throwaway
Up-Flow (Free-Front Return):
Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return):
Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1) 25x22, (1) 25x22, (1) 20x25, (2) 20x25, (2)
Connection Sizes - Copper, (Please refer to Mini-Space IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
Liquid Line, (Qty.) 3/8 OD, (1) 3/8 OD, (1) 1/2 OD, (1) 1/2 OD, (1) 1/2 OD (1) 5/8 OD (1)
Hot Gas Line, (Qty.) 1/2 OD, (1) 5/8 OD, (1) 5/8 OD, (1) 7/8 OD, (1) 7/8 OD (1) 7/8 OD (1)
Condensate Drain, (w/ pump) 7/8 OD 7/8 OD 7/8 OD 7/8 OD 7/8 OD(1/2 OD) 7/8 OD(1/2 OD)
Humidier Inlet 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD
Physical Data
Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs
Dimensions: (HxWxD), includes access panels, w/o Plenum Box option.
CCU-( )-A (up-ow) 73x 24x 24 73x 24x 24 73x 24x 24 73x 24x 24 73x 39 x 32 73x 39 x 32
CCD-( )-A (down-ow) 73x 24x 24 73x 24x 24 73x 24x 24 73x 24x 24 73x 39 x 32 73x 39 x 32
Air Technology Systems, Inc.
Water Cooled -DX - 1 to 7 Ton "CCU/D"
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


W
a
t
e
r

C
o
o
l
e
d

-

D
X
-

(
1

t
o

7

T
o
n

S
y
s
t
e
m
s
)
4-3
CCU/D Model CC( )-41-W CC( )-61-W CC( )-81-W CC( )-121-W CC( )-171-W CC( )-201-W
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH
Total 18,800 26,430 35,270 45,220 52,940 71,930
Sensible 16,900 21,070 22,770 36,500 52,940 69,110
72FDB/60FWB, 50% RH
Total 18,200 24,750 33,560 43,650 49,790 68,020
Sensible 16,500 20,560 22,070 38,160 49,790 67,330
70FDB/58.5FWB, 50% RH
Total 16,600 23,890 32,360 42,310 47,860 65,750
Sensible 15,200 19,900 21,900 36,410 47,860 65,500
75FDB/61FWB, 45% RH
Total 18,800 25,630 34,000 44,060 53,270 70,980
Sensible 16,900 23,120 26,300 40,740 53,270 70,980
72FDB/58.5FWB, 45% RH
Total 18,200 24,460 32,140 41,630 50,380 68,370
Sensible 16,500 22,960 25,980 39,880 50,380 68,370
70FDB/57FWB, 45% RH
Total 16,500 23,620 31,090 40,320 48,480 66,230
Sensible 15,100 22,410 25,470 38,970 48,480 66,230
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat
ELECTRIC REHEAT / HEAT - (Standard)
Htr Kw Rating (No. of Stages) 2 Kw (1-stg) 2 Kw (1-stg) 2 Kw (1-stg) 4 Kw (2-stg) 12 Kw (2-stg) 12 Kw (2-stg)
Tot BTU/H (Kw) w/ Evap Mtr Ht: 8,730 (2.6) 8,730 (2.6) 8,730 (2.6) 15,560 (4.6) 48,580 (14.2) 48,580 (14.2)
HOT GAS REHEAT - (Optional)
BTU/H 5,148 6,162 8,816 10,297 10,549 15,531
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional)
BTU/H 31,465 31,465 63,475 63,475 114,450 124,902
GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) 12.8 / (2.8)
Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
Humidication - Electrode Steam Canister Humidier with Adjustable Output, (Standard)
Lbs/Hr, (Kw Input) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4)
Std Control Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 3/4 Hp 3/4 Hp 3/4 Hp 3/4 Hp 3.0 Hp 3.0 Hp
CFM @ ext. st. press. 1,180 @ 0.2 1,180 @ 0.2 1,180 @ 0.2 1,890 @ 0.2 3,450 @ 0.3 4,130 @ 0.3
Drive Method Direct Direct Direct Direct Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 4/ 3.25 4/ 3.25 4/ 3.25 4/ 3.25 4/ 8.3 4/ 8.3
Face Velocity, fpm 363 363 363 581 415 498
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1)
Power Input (Watts, Input ea.) 1,509 1,806 2,584 3,018 3,092 4,552
Water Cooled Condenser Data - Based on 0% Glycol Solution
Total Heat of Rejection (BTU/H) 28,460 34,700 46,200 57,410 71,890 95,860
GPM @ 85F EWT/95F LWT 5.7 GPM 7.0 GPM 9.3 GPM 11.5 GPM 14.4 GPM 19.3 GPM
Total Unit Pressure Drop (Ft. of H2O) 5.6 6.9 10.0 13.5 19.3 25.5
Type Plate-Finned Plate-Finned Plate-Finned Plate-Finned Plate-Finned Plate-Finned
Head Pressure Control
Standard Control - - - - - 2-way, 150 psig DX Water Source Regulating Valve - factory installed - - - - -
Valve size / Cv 3/4 (5.5) 3/4 (5.5) 3/4 (5.5) 1 (5.5) 1 (8.5) 1 (8.5)
Connection Sizes - Copper
Condensate Drain, (w/ pump) 7/8 OD 7/8 OD 7/8 OD 7/8 OD 7/8 OD(1/2 OD) 7/8 OD(1/2 OD)
Humidier Inlet 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD
Condenser In/Out 7/8 OD 7/8 OD 7/8 OD 1-1/8 OD 1-1/8 OD 1-1/8 OD
Filters - 1 deep (41/121) & 2 deep (171/201), 30% Average Efciency, throwaway
Upow: Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 38x16, (1) 16x24, (2)
Down-ow: Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1) 25x22, (1) 20x25, (2) 25x22, (1) 20x25, (2)
Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs
Dimensions: (HxWxD), includes access panels, w/o Plenum Box option.
CCU-( )-W (up-ow) 73x24x24 73x24x24 73x24x24 73x24x24 73x39xx32 73x39xx32
CCD-( )-W(down-ow) 73x24x24 73x24x24 73x24x24 73x24x24 73x39xx32 73x39xx32
Air Technology Systems, Inc.
Glycol Cooled - DX - 1 to 7 Ton "CCU/D"
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


G
l
y
c
o
l

C
o
o
l
e
d

(
1

t
o

7

T
o
n

S
y
s
t
e
m
s
)
4-4
CCU/D Model CC( )-41-G CC( )-61-G CC( )-81-G CC( )-121-G CC( )-171-G CC( )-201-G
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH
Total 16,900 23,290 30,980 39,630 46,630 61,950
Sensible 15,400 20,310 22,590 35,430 46,630 61,950
72FDB/60FWB, 50% RH
Total 16,400 22,050 29,250 37,350 43,880 59,840
Sensible 15,000 19,990 22,280 34,650 43,880 59,830
70FDB/58.5FWB, 50% RH
Total 16,000 21,270 28,280 36,140 42,080 58,040
Sensible 14,800 19,450 21,760 33,750 42,080 58,040
75FDB/61FWB, 45% RH
Total 16,700 22,580 29,650 38,650 46,650 63,310
Sensible 15,600 22,050 24,810 37,640 46,650 63,310
72FDB/58.5FWB, 45% RH
Total 15,600 21,190 28,100 36,950 43,900 60,230
Sensible 14,800 21,190 24,280 36,340 43,900 60,230
70FDB/57FWB, 45% RH
Total 15,400 20,410 26,920 35,810 43,100 58,210
Sensible 14,600 20,410 23,760 35,360 43,100 58,210
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat
ELECTRIC REHEAT / HEAT - (Standard)
Htr Kw Rating (No. of Stages) 2 Kw (1-stg) 2 Kw (1-stg) 2 Kw (1-stg) 4 Kw (2-stg) 12 Kw (2-stg) 12 Kw (2-stg)
Tot BTU/H (Kw) w/ Evap Mtr Ht: 8,730 (2.6) 8,730 (2.6) 8,730 (2.6) 15,560 (4.6) 48,580 (14.2) 48,580 (14.2)
HOT GAS REHEAT - (Optional)
BTU/H 7,117 8,666 12,269 14,344 15,009 21,174
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional)
BTU/H 31,465 31,465 63,475 63,475 114,450 124,902
GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) 12.8 / (2.8)
Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
Humidication - Electrode Steam Canister Humidier with Adjustable Output, (Standard)
Lbs/Hr, (Kw Input) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4)
Std Control Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 3/4 Hp 3/4 Hp 3/4 Hp 3/4 Hp 3.0 Hp 3.0 Hp
CFM @ ext. st. press. 1,180 @ 0.2 1,180 @ 0.2 1,180 @ 0.2 1,890 @ 0.2 3,450 @ 0.3 4,130 @ 0.3
Drive Method Direct Direct Direct Direct Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 4/ 3.25 4/ 3.25 4/ 3.25 4/ 3.25 4/ 8.3 4/ 8.3
Face Velocity, fpm 363 363 363 581 415 498
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1)
Power Input (Watts, Input ea.) 2,086 2,540 3,596 4,204 4,399 6,206
Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution
Total Heat of Rejection (BTU/H) 27,900 34,070 45,350 56,090 70,060 91,530
GPM @ 110F EGT/120F LGT 6.3 GPM 7.6 GPM 10.2 GPM 12.6 GPM 15.7 GPM 20.5 GPM
Unit Pressure Drop (Ft. of H2O) 6.4 8.0 11.8 16.0 24.2 30.5
Type Plate-Finned Plate-Finned Plate-Finned Plate-Finned Plate-Finned Plate-Finned
Head Pressure Control
Standard Control - - - - - 2-way, 150 psig DX Glycol Source Regulating Valve - factory installed - - - - -
Valve size / Cv 3/4 (5.5) 3/4 (5.5) 3/4 (5.5) 1 (5.5) 1 (8.5) 1 (8.5)
Connection Sizes - Copper
Condensate Drain, (w/ pump) 7/8 OD 7/8 OD 7/8 OD 7/8 OD 7/8 OD(1/2 OD) 7/8 OD(1/2 OD)
Humidier Inlet 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD 1/4 OD
Condenser In/Out 7/8 OD 7/8 OD 7/8 OD 1-1/8 OD 1-1/8 OD 1-1/8 OD
Filters - 1 deep (41/121) & 2 deep (171/201), 30% Average Efciency, throwaway
Upow - Front Free Return Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 38x16, (1) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return): Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1) 25x22, (1) 20x25, (2) 25x22, (1) 20x25, (2)
Physical Data
Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs
Dimensions: (HxWxD), includes access panels, w/o Plenum Box option.
CCU-( )-G (up-ow) 73x24x24 73x24x24 73x24x24 73x24x24 73x39xx32 73x39xx32
CCD-( )-G (down-ow) 73x24x24 73x24x24 73x24x24 73x24x24 73x39xx32 73x39xx32
Air Technology Systems, Inc.
Notes:
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


N
o
t
e
s
4-5
Air Technology Systems, Inc.
Chilled Water - 3 to 7 Tons - CCU/D
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


C
h
i
l
l
e
d

W
a
t
e
r


(
3

t
o

7

T
o
n

S
y
s
t
e
m
s
)
4-6
CCU/D Model CC( )-110-CW CC( )-200-CW
Chilled Water Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
3-way (standard) - Modulating
Size / (Cv) (Optional High Pressure) 1/2 / (4.0 Cv) 3/4 / (7.5 Cv)
Valve Pressure Rating (Optional High Pressure) 300 psig (400 psig) 300 psig (400 psig)
2-way (optional) - Modulating
Size / (Cv) (Optional High Pressure) 1/2 / (4.0 Cv) 3/4 / (7.5 Cv)
Valve Pressure Rating (Optional High Pressure) 300 psig (400 psig) 300 psig (400 psig)
Chilled Water Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 4 / 3.25 4 / 8.3
Face Velocity, fpm 581 498
Evaporator Blower / Motor - DWDI Centrifugal
CFM @ ext. st. press. 1,890 @ 0.2 4,130 @ 0.3
Horsepower 3/4 Hp 3.0 Hp
Drive Method Direct Belt
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat
ELECTRIC REHEAT / HEAT (Standard)
Htr Kw Rating (No. of Stages) 4 Kw (1-stg) 12 Kw (2-stg)
Tot BTU/H (Kw) w/ Evap Mtr Ht: 15,560 (4.6) 48,580 (14.2)
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional)
BTU/H 63,475 124,902
GPM / Press. Drop (ft.wg) 6.5 / (.8) 12.8 / (2.8)
Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
Humidication - Electrode Steam Canister Humidier with Adjustable Output, (Standard)
Lbs/Hr, (Kw Input) 2-5, (1.7) 4-10, (3.4)
Std Control Cycling Cycling
Filters - 1 deep (110) & 2 deep (200), 30% Average Efciency, throwaway
Up-Flow (Free-Front Return):
Nom. Size (in.), (Qty.) 36x16, (1) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return):
Nom. Size (in.), (Qty.) 25x22, (1) 20x25, (1)
Connection Sizes - Copper, (Water connections are sized for ow rates at 75FDB/62.5FWB EAT conditions.)
Condensate Drain, (w/ pump) 7/8 OD 7/8 OD
Humidier Inlet 1/4 OD 1/4 OD
Water In/Out 5/8 OD
Physical Data
Approx. Weight 370lbs 440lbs
Dimensions: (HxWxD), includes access panels, w/o Plenum Box option.
CCU-( )-CW (up-ow) 73x2424 73x39x32
CCD-( )-CW (down-ow) 73x2424 73x39x32
Air Technology Systems, Inc.
Chilled Water - 3 to 7 Tons - CCU/D
P
e
r
f
o
r
m
a
n
c
e

D
a
t
a


-


C
h
i
l
l
e
d

W
a
t
e
r


(
3

t
o

7

T
o
n

S
y
s
t
e
m
s
)
4-7
CCU/D Model CC( )-110-CW CC( )-200-CW CC( )-110-CW CC( )-200-CW CC( )-110-CW CC( )-200-CW
NET COOLING CAPACITY - (includes motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH BTU/H @ 45F EWT, 0% Glycol Solution BTU/H @ 42F EWT, 0% Glycol Solution BTU/H @ 50F EWT, 0% Glycol Solution
High Flow Total 41,670 99,820 46,650 116,840 29,170 68,970
(8F Tw) Sens. 38,540 89,200 35,570 97,330 29,170 68,970
GPM / (pd. Ft.) 10.3/(6.1) 24.8/(9.4) 11.6/(7.6) 29/(12.7) 7.3/(2.3) 17.1/(4.8)
Med. Flow Total 32,990 86,700 39,440 104,470 23,680 58,090
(10F Tw) Sens. 32,990 81,540 32,010 90,790 23,680 58,090
GPM / (pd. Ft.) 6.6/(2.6) 17.2/(4.9) 7.8/(3.7) 20.8/(6.9) 4.7/(0.9) 11.6/(2.3)
Low Flow Total 27,020 67,230 33,190 91,740 19,390 44,200
(12F Tw) Sens. 27,020 37,230 28,600 83,400 19,390 44,200
GPM / (pd. Ft.) 4.5/(1.2) 11.1/(2.1) 5.5/(1.8) 15.2/(3.9) 3.2/(0.4) 7.3/(0.9)
72FDB/60FWB, 50% RH
High Flow Total 32,190 75,660 40,590 97,310 23,020 55,320
(8F Tw) Sens. 32,190 75,660 37,990 88,090 23,020 55,320
GPM / (pd. Ft.) 8/(3.9) 18.8/(5.7) 10.0/(5.9) 24.1/(9.1) 5.8/(1.4) 13.8/(3.2)
Med. Flow Total 26,510 64,760 32,130 84,020 17,600 42,570
(10F Tw) Sens. 26,510 64,760 33,890 80,820 17,600 42,570
GPM / (pd. Ft.) 5.3/(1.6) 12.9/(2.8) 6.4/(2.4) 16.7/(4.6) 3.5/(0.5) 8.5/(1.2)
Low Flow Total 21,870 51,660 26,010 64,910 15,500 33,380
(12F Tw) Sens. 21,870 51,660 26,010 64,910 15,500 33,380
GPM / (pd. Ft.) 3.6/(0.8) 8.6/(1.2) 4.3/(1.1) 10.7/(1.9) 2.6/(0.3) 5.5/(0.5)
70FDB/58.5FWB, 50% RH
High Flow Total 28,040 66,740 33,940 85,110 18,590 45,690
(8F Tw) Sens. 28,040 66,740 33,890 80,820 18,590 45,690
GPM / (pd. Ft.) 6.9/(2.9) 16.6/(4.5) 8.4/(4.3) 21.1/(7.1) 4.7/(0.9) 11.3/(2.2)
Med. Flow Total 22,310 55,100 27,850 67,670 15,020 32,220
(10F Tw) Sens. 22,310 55,100 27,850 67,670 15,020 32,220
GPM / (pd. Ft.) 4.5/(1.2) 10.9/(2.0) 5.5/(1.3) 13.4/(3.1) 3.0/(0.4) 6.4/(0.7)
Low Flow Total 19,290 41,410 23,100 54,680 12,960 27,890
(12F Tw) Sens. 19,290 41,410 23,100 54,680 12,960 27,890
GPM / (pd. Ft.) 3.2/(0.7) 6.9/(0.8) 3.8/(0.6) 9.1/(1.3) 2.2/(0.2.) 4.6/(0.4)
75FDB/61FWB, 45% RH
High Flow Total 38,150 88,400 46,180 109,700 29,080 68,780
(8F Tw) Sens. 38,150 88,400 43,850 101,050 29,080 68,780
GPM / (pd. Ft.) 9.5/(5.2) 21.9/(7.5) 11.4/(5.4) 27.2/(11.3) 7.2/(2.3) 17.1/(4.7)
Med. Flow Total 32,880 78,630 38,280 96,740 23,530 57,870
(10F Tw) Sens. 32,880 78,630 38,280 93,150 23,530 57,870
GPM / (pd. Ft.) 6.5/(2.6) 15.6/(4.1) 7.6/(2.5) 19.2/(6.0) 4.7/(0.9) 11.5/(2.2)
Low Flow Total 26,910 66,970 32,610 79,440 19,330 43,950
(12F Tw) Sens. 26,910 66,970 32,610 79,440 19,330 43,950
GPM / (pd. Ft.) 4.5/(1.2) 11.1/(2.0) 5.4/(1.2) 13.2/(2.9) 3.2/(0.4) 7.3/(0.8)
72FDB/58.5FWB, 45% RH
High Flow Total 32,910 75,460 37,450 86,970 22,950 55,150
(8F Tw) Sens. 32,910 75,460 37,450 86,970 22,950 55,150
GPM / (pd. Ft.) 8.0/(3.8) 18.7/(5.7) 9.3/(3.7 21.5/(7.4) 5.8/(1.4) 13.7/(3.2)
Med. Flow Total 26,420 64,550 32,030 76,800 17,560 42,370
(10F Tw) Sens. 26,420 64,550 32,030 76,800 17,560 42,370
GPM / (pd. Ft.) 5.2/(1.6) 12.8/(2.8) 6.4/(1.7) 15.3/(3.9) 3.5/(0.5) 8.4/(1.2)
Low Flow Total 21,810 51,410 25,910 64,810 15,450 33,280
(12F Tw) Sens. 21,810 51,410 25,910 64,810 15,450 33,280
GPM / (pd. Ft.) 3.6/(0.8) 8.5/(1.2) 4.3/(0.7) 10.7/(1.9) 2.6/(0.3) 5.5/(0.5)
70FDB/57FWB, 45% RH
High Flow Total 32,010 66,560 33,440 78,440 18,520 45,530
(8F Tw) Sens. 32,010 66,560 33,440 78,440 18,520 45,530
GPM / (pd. Ft.) 7.9/(3.8) 16.5/(4.5) 8.3/(0.3) 19.5/(6.1) 4.6/(0.9) 11.3/(2.1)
Med. Flow Total 26,340 54,900 27,750 67,460 14,980 32,130
(10F Tw) Sens. 26,340 54,900 27,750 67,460 14,980 32,130
GPM / (pd. Ft.) 5.2/(1.6) 10.9/(2.0) 5.5/(1.2) 13.4/(3.0) 3.0/(0.4) 6.4/(0.7)
Low Flow Total 21,750 41,300 23,050 54,440 12,910 37,810
(12F Tw) Sens. 21,750 41,300 23,050 54,440 12,910 37,810
GPM / (pd. Ft.) 3.6/(0.8) 6.8/(0.7) 3.8/(0.6) 9.0/(1.3) 2.2/(0.2) 4.6/(0.4)
Air Technology Systems, Inc.
Electrical Data - Index
E
l
e
c
t
r
i
c
a
l

D
a
t
a











-


I
n
d
e
x
5-1
Mini-Space Floor Air Conditioners
FLA / MCA / MFS
MODEL TYPE ...........................................page
DX - Compressorized Systems
Single Compressor Systems:
CCU/D-041/201 - A, W, & G .....................................5-2
CW - Air Handling Units
CCU/D-110-200 - CW ..............................................5-3
Electrical Data Calculation Examples
Example 1:
CCU/D-61-A ................................................................... 5-3
Example 2:
CCU/D-200-CW........................................................5-3
1) Electrical Data is based on standard performance and component selection per Section 4 of this brochure. Please
consult your local Sales Representative for "special" equipment electrical data.
2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's and
External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data
for this Option.
<< Electrical Data Notes >>
Air Technology Systems, Inc.
Electrical Data - DX Compressorized Systems
E
l
e
c
t
r
i
c
a
l

D
a
t
a











-


D
X

C
o
m
p
r
e
s
s
o
r
i
z
e
d

S
y
s
t
e
m
s
5-2
Table Legends:
FLA = Full Load Amps
(OEM Rated Load Amps)
MCA = Minimum Circuit Amps
(wire size amps)
MFS = Maximum Fuse Size
Consult the Factory for electrical data
for 50Hz power supply requirements.
Model
CCU/D-41-A/W/G CCU/D-61-A/W/G CCU/D-81-A/W/G
FLA
MCA MFS
FLA
MCA MFS
FLA
MCA MFS
A W G A W G A W G
Cooling w/ Electric Reheat/Heat & Humidication
208/1/60 26.7 24.7 27.3 33.4 40 29.6 26.8 30.4 36.7 50 34.7 31.1 35.8 42.2 50
208/3/60 23.9 20.8 24.9 25.7 30 23.3 22 23.6 28 35 26.3 24.5 26.8 32.3 40
460/3/60 CONSULT FACTORY 11.3 10.8 11.5 14.5 15 11.7 11.1 11.9 14.7 15
Cooling w/ Electric Reheat /Heat Only (No humidier)
208/1/60 26.7 24.7 27.3 33.4 40 29.6 26.8 30.4 36.7 50 34.7 31.1 35.8 42.2 50
208/3/60 23.9 20.8 24.9 25.7 30 23.3 22 23.6 28 35 26.3 24.5 26.8 32.3 40
460/3/60 CONSULT FACTORY 11.3 10.8 11.5 14.5 15 11.7 11.1 11.9 14.7 15
Cooling w/ Humidication (No Heat/Reheat)
208/1/60 25.3 23.3 25.9 29.6 40 28.2 25.4 29 32.9 50 33.3 29.7 34.4 38.4 50
208/3/60 24.9 21.8 25.9 25.9 30 24.3 23 24.6 27.3 35 27.3 25.5 27.8 31.5 40
460/3/60 CONSULT FACTORY 10.6 10.1 10.8 12.7 15 11 10.4 11.2 12.9 15
Cooling Only
208/1/60 17.1 15.1 17.7 21.4 30 20 17.2 20.8 24.7 35 25.1 21.5 26.2 30.2 50
208/3/60 16.7 13.6 17.7 17.7 20 16.1 14.8 16.4 19.1 25 19.1 17.3 19.6 23.3 35
460/3/60 CONSULT FACTORY 6.9 6.4 7.1 9 15 7.3 6.7 7.5 9.2 15
Model
CCU/D-121-A/W/G CCU/D-171-A/W/G CCU/D-201-A/W/G
FLA
MCA MFS
FLA
MCA MFS
FLA
MCA MFS
A W G A W G A W G
Cooling w/ Electric Reheat/Heat & Humidication
208/1/60 N/A N/A N/A
208/3/60 34.9 33.2 35.4 44.2 50 57.4 54 58.4 69.1 70 58.8 55.3 59.8 70.7 80
460/3/60 18.6 17.5 18.9 23.5 25 27.4 26 27.9 33.9 35 28.3 26.9 28.7 34.9 40
Cooling w/ Electric Reheat /Heat Only (No humidier)
208/1/60 N/A N/A N/A
208/3/60 34.9 33.2 35.4 44.2 50 57.4 54 58.4 69.1 70 58.8 55.3 59.8 70.7 80
460/3/60 18.6 17.5 18.9 23.5 25 27.4 26 27.9 33.9 35 28.3 26.9 28.7 34.9 40
Cooling w/ Humidication (No Heat/Reheat)
208/1/60 N/A N/A N/A
208/3/60 28.7 27 29.2 34.4 50 43.5 40.1 44.5 47.6 60 44.9 41.4 45.9 49.2 60
460/3/60 13.5 12.4 13.8 16.2 20 19.6 18.2 20.1 22.3 30 20.5 19.1 20.9 23.3 30
Cooling Only
208/1/60 N/A N/A N/A
208/3/60 20.5 18.8 21 26.2 40 27.2 23.8 28.2 31.3 50 28.6 25.1 29.6 33 50
460/3/60 9.8 8.7 10.1 12.5 15 12.2 10.8 12.7 14.9 20 13.1 11.7 13.5 15.9 20
Air Technology Systems, Inc.
Electrical Data - Chilled Water
E
l
e
c
t
r
i
c
a
l

D
a
t
a



-

C
h
i
l
l
e
d

W
a
t
e
r
5-3
Table Legends:
FLA = Full Load Amps
(OEM Rated Load Amps)
MCA = Minimum Circuit Amps
(wire size amps)
MFS = Maximum Fuse Size
Consult the Factory for electrical data
for 50Hz power supply requirements.
Example 1:
Suppose an application calls for a model CCU-61-A with
the following standard features:
CCU-61-A
- 460/3/60 Main Power Supply (both evap and cond)
- Electric Reheat/Heat (2-stages), (Standard)
- Steam Humidier, (Standard)
Solution:
From DX Compressorized Electrical Data table page 5-2 for
model CCU-61-A incorporating COOLING with ELECTRIC
REHEAT/HEAT and HUMIDIFIER:

CCU-61-A @ 460/3/60 w/ above options:
FLA (OEM Rated) = 11.3
MCA = 14.5
MFS = 15
Example 2:
Suppose an application calls for a model CCD-200-CW
system with the following features:
CCD-200-CW
- 208/3/60 Main Power Supply
- Electric Reheat/Heat (2-stages), (Standard)
- No Humidier
Solution:
From DX Compressorized Electrical Data table page 5-2 for
model CCD-200-CW incorporating COOLING with ELEC-
TRIC REHEAT/HEAT and NO HUMIDIFIER:
CCD-200-CW @ 208/3/60 w/ above options:
FLA (OEM Rated) = 39.9
MCA = 49.9
MFS = 50
EXAMPLES - Electrical Data Calculation
Model
CCU/D-110-CW CCU/D-200-CW
FLA MCA MFS FLA MCA MFS
Cooling w/ Electric Reheat/Heat & Humidication
208/1/60 35.2 44 45 N/A
208/3/60 23.2 29 30 56.2 70.3 80
460/3/60 17.6 22 25 27.3 34.1 35
Cooling w/ Electric Reheat /Heat Only (No humidier)
208/1/60 27 33.8 35 N/A
208/3/60 15 18.8 20 39.9 49.9 50
460/3/60 13.9 17.4 20 19.9 24.9 25
Cooling w/ Humidication (No Heat/Reheat)
208/1/60 16 20 25 N/A
208/3/60 16 20 25 26 32.5 35
460/3/60 8.9 11.1 15 12.1 15.1 20
Cooling Only
208/1/60 7.8 9.8 15 N/A
208/3/60 7.8 9.8 15 9.7 12.1 20
460/3/60 5.2 6.5 15 4.7 5.9 15
Air Technology Systems, Inc.
Notes
N
o
t
e
s
5-4
Air Technology Systems, Inc.
Physical Data - Standard "Mini-Space Congurations
P
h
y
s
i
c
a
l

D
a
t
a






-



I
n
d
e
x
6-1
"Index"
(Drwg. #) MODEL TYPE ............ page
Vertical Floor System Dimensions
CCU/D/ 41-121 & 110-A/W/G/CW
(MS-01) "Up-Flow" Air Pattern Conguration ............. 6-2
(MS-02) "Down-Flow" Air Pattern Conguration ........ 6-3
CCU/D/ 171,201 & 200-A/W/G/CW
(MS-03) "Up-Flow" Air Pattern Conguration ............. 6-4
(MS-04) "Down-Flow" Air Pattern Conguration ........ 6-5
Up-Flow & Down-Flow Air Patterns Available
Air Technology Systems, Inc.
1 to 3.5 Ton - CCU - "Up-Flow" Air Pattern Systems
D
i
m
e
n
s
i
o
n
a
l

D
a
t
a






-


1

t
o

3
.
5

T
o
n
s

(
"
U
p
-
F
l
o
w
"

A
i
r

P
a
t
t
e
r
n

S
y
s
t
e
m
s
)
6-2
DIMENSIONAL DATA - FLOOR STAND HEIGHTS
A DIMENSION
TURNING
VANE NOMINAL
HEIGHT
ADJUSTABLE HEIGHT
MAX MIN
4 upow only 3.5 4.5 Not available
6 5.0 7.0 Not available
12 11.0 15.0 Optional
15 14.0 18.0 Optional
18 17.0 21.0 Optional
24 23.0 26.0 Optional
Adjustable Floor Stand: (Optional)
(MS-01) CCU-41/61/81/121-A, W, G,
& -110-CW
Up-Flow Vertical A/C
(Ducted or optional 2- or 3-way plenum box)
Air Technology Systems, Inc.
1 to 3.5 Ton - CCD - "Down-Flow" Air Pattern Systems
D
i
m
e
n
s
i
o
n
a
l

D
a
t
a






-


1

t
o

3
.
5

T
o
n
s

(
"
D
o
w
n
-
F
l
o
w
"

A
i
r

P
a
t
t
e
r
n

S
y
s
t
e
m
s
)
6-3
DIMENSIONAL DATA - FLOOR STAND HEIGHTS
A DIMENSION
TURNING
VANE NOMINAL
HEIGHT
ADJUSTABLE HEIGHT
MAX MIN
4 upow only 3.5 4.5 Not available
6 5.0 7.0 Not available
12 11.0 15.0 Optional
15 14.0 18.0 Optional
18 17.0 21.0 Optional
24 23.0 26.0 Optional
Adjustable Floor Stand: (Optional)
(MS-02) CCD-41/61/81/121-A, W, G,
& -110-CW
Down-Flow Vertical A/C
(Free Return or with optional Ducted Return)
Air Technology Systems, Inc.
5 to 7 Ton - CCU - "Up-Flow" Air Pattern Systems
D
i
m
e
n
s
i
o
n
a
l

D
a
t
a






-


5

t
o

7

T
o
n
s

(
"
U
p
-
F
l
o
w
"

A
i
r

P
a
t
t
e
r
n

S
y
s
t
e
m
s
)
6-4
DIMENSIONAL DATA - FLOOR STAND HEIGHTS
A DIMENSION
TURNING
VANE NOMINAL
HEIGHT
ADJUSTABLE HEIGHT
MAX MIN
4 upow only 3.5 4.5 Not available
6 5.0 7.0 Not available
12 11.0 15.0 Optional
15 14.0 18.0 Optional
18 17.0 21.0 Optional
24 23.0 26.0 Optional
Adjustable Floor Stand: (Optional)
(MS-03) CCU-171/201-A, W, G,
& -200-CW
Up-Flow Vertical A/C
(Ducted or optional 2- or 3-way plenum box)
Air Technology Systems, Inc.
5 to 7 Ton - CCD - "Down-Flow" Air Pattern Systems
D
i
m
e
n
s
i
o
n
a
l

D
a
t
a






-


5

t
o

7

T
o
n
s

(
"
D
o
w
n
-
F
l
o
w
"

A
i
r

P
a
t
t
e
r
n

S
y
s
t
e
m
s
)
6-5
DIMENSIONAL DATA - FLOOR STAND HEIGHTS
A DIMENSION
TURNING
VANE NOMINAL
HEIGHT
ADJUSTABLE HEIGHT
MAX MIN
4 upow only 3.5 4.5 Not available
6 5.0 7.0 Not available
12 11.0 15.0 Optional
15 14.0 18.0 Optional
18 17.0 21.0 Optional
24 23.0 26.0 Optional
Adjustable Floor Stand: (Optional)
(MS-04) CCD-171/201/200-A, W, G,
& -200-CW
Down-Flow Vertical A/C
(Free Return or with optional Ducted Return)
Air Technology Systems, Inc.
Notes
Air Technology Systems, Inc.
1572 Tilco Drive, Frederick, Maryland 21704
Phone: 301.620.2033, Fax: 301.662.5487
E-mail: info@stulz-ats.com
ISO-9001:2001 Quality Registered
ISO9001
Registered
Quality System
Air Technology Systems, Inc.
www.stulz-ats.com
This document was printed on recycled paper, with
ecosmart
tm
environmentally responsible ink products.
Copyright December 2012
QE-MIN0027 Rev-A