Earthing Arrangements
Earthing Arrangements
ElectaCourse.com
2005 Last Updated August 2006
2
www.ElectaCourse.com
Definitions fromPart 2 BS 7671
Definitions fromPart 2 BS 7671
3
www.ElectaCourse.com
Bonding conductor
A protective conductor providing
equipotential bonding
4
www.ElectaCourse.com
Where protection against electric shock does not rely
solely on basic insulation alone. Exposed-conductive
parts being connected to a protective conductor within
the fixed wiring of the installation.
Class I equipment
Class I insulation
Single-layer insulation
Live part
Exposed conductive
part
5
www.ElectaCourse.com
Class II equipment
Where protection against electric shock relies on the
application of additional or supplementary insulation.
There is no provision for the connection of a protective
conductor to exposed metalwork.
Class II insulation
live part
two layers of
insulation
exposed metalwork
6
www.ElectaCourse.com
Double insulation
Double insulation (Class II) - Insulation
comprising both basic insulation and
supplementary insulation
7
www.ElectaCourse.com
Earth fault loop impedance
The impedance of the earth fault current
loop starting and ending at the point of
earth fault.
Symbol Z
Symbol Z
Unit
Unit

8
www.ElectaCourse.com
The earth fault loop
The earth fault loop starting at the point of fault
consists of:
the circuit protective conductor (c.p.c.)
consumers earthing terminal and earthing conductor
for TN systems, the metallic sheath of supply cable
for TT systems, the general mass of earth
the path through the earthed neutral point of the
transformer
the transformer winding and phase conductor to point
of fault
9
www.ElectaCourse.com
Earth leakage current
A current which flows to earth, or to
extraneous conductive parts, in a circuit
which is electrically sound. This current
may have a capacitive effect including
that from the deliberate use of capacitors.
10
www.ElectaCourse.com
Leakage current
Electric current in an unwanted conductive
path under normal operating conditions
11
www.ElectaCourse.com
Electric current which flows in a protective conductor
under normal operating conditions
Protective conductor current
12
www.ElectaCourse.com
Earthed equipotential zone
A zone within which exposed conductive parts and
extraneous conductive parts are maintained at
substantially the same potential by bonding, such
that under fault conditions, the differences in potential
simultaneously accessible exposed and extraneous-
conductive parts will not cause electric shock.
13
www.ElectaCourse.com
Direct contact (shock)
Results from
Making contact with parts of a circuit or
Making contact with parts of a circuit or
systemwhich are live under normal conditions systemwhich are live under normal conditions
14
www.ElectaCourse.com
Earthing
Connection of the exposed conductive
parts of an installation to the main earthing
terminal of that installation
15
www.ElectaCourse.com
Extraneous conductive part
A conductive part liable to introduce a
potential, generally earth potential, and not
forming part of the electrical installation.
16
www.ElectaCourse.com
Functional earthing
Connection to Earth necessary for proper
functioning of electrical equipment
Table 51A
Table 51A
Functional earthing conductors to be
coloured cream
17
www.ElectaCourse.com
Contact of persons or livestock with
exposed-conductive parts which have
become live under fault conditions.
Indirect contact
18
www.ElectaCourse.com
Protective conductors
A conductor used for some measure of protection against
electric shock and intended for connecting together any
of the following parts
(i) exposed conductive parts
(ii) extraneous-conductive parts
(iii) the main earthing terminal
(iv) earth electrode(s)
(ii) the earthed point of the source, or an artificial neutral
19
www.ElectaCourse.com
Protective conductors
earthing conductor
main bonding
conductor
circuit protective
conductor
20
www.ElectaCourse.com
Shock conditions
Shock conditions
21
www.ElectaCourse.com
Direct contact
Contact of persons or livestock
with live parts
22
www.ElectaCourse.com
Uo = 230V
Direct contact (shock)
ouch ouch
23
www.ElectaCourse.com
Direct Contact
Direct Contact
Maximum shock voltage
Maximum shock voltage
No disconnection
No disconnection
24
www.ElectaCourse.com
Protection against Direct contact (shock)
Insulation
Insulation
Barriers
Barriers
Enclosures
Enclosures
25
www.ElectaCourse.com
Protection against Direct contact (shock)
Placing out of reach
Placing out of reach
Obstacles
Obstacles
Protection of a specialist nature
Protection of a specialist nature
26
www.ElectaCourse.com
Uo = 230V
Indirect contact (shock)
Automatic operation of protective device
Automatic operation of protective device
Reduced shock risk Reduced shock risk
27
www.ElectaCourse.com
Protection against indirect contact (shock)
E
E
E E
B
B
A
A
D
D
O
O
S
S
arthed arthed
quipotential quipotential
onding onding
nd automatic nd automatic
isconnection isconnection
f
f
upply
upply
28
www.ElectaCourse.com
Earthing Arrangements
Earthing Arrangements
29
www.ElectaCourse.com
TT Earthing Arrangement
TT Earthing Arrangement
PES
cut out
P.E.S
metering
earthing
conductor
from overhead
supply
to earth electrode
consumer unit
30
www.ElectaCourse.com
1st Letter - Method of earthing for suppliers network
2nd Letter - Method of earthing at consumers
installation
T = Direct connection to earth at one or more points
T = Direct connection to earth
31
www.ElectaCourse.com
Frequently used types of earth electrode
plate
lattice
rod
Regulation 542
Regulation 542
-
-
02
02
-
-
01
01
32
www.ElectaCourse.com
Earth electrodes recognised by BS 7671 Earth electrodes recognised by BS 7671
The following types of earth electrode are recognised by
the Regulations:
(i) earth rods or pipes
Regulation 542
Regulation 542
-
-
02
02
-
-
01
01
(ii) earth tapes or wires
(iii) earth plates
(iv) underground structural metalwork embedded in foundations
(v) welded metal reinforcement of concrete
(except pre-stressed concrete) embedded in earth
(vi) lead sheaths and other and other metal coverings of cables, where not
precluded by Regulation 542-02-05
(vii) other suitable underground metalwork
33
www.ElectaCourse.com
Installation of earth electrodes
When installing earth electrodes the
following precautions should be observed
Regulation 542
Regulation 542
-
-
02
02
-
-
02
02
Remember climatic conditions could affect
electrode resistance
The type and embedded depth of an earth
electrode shall be sufficient to avoid soil
drying and freezing
34
www.ElectaCourse.com
Earth electrode resistance Earth electrode resistance
The graph illustrates the relationship between electrode
resistance and buried depth for a rod type electrode. The
deeper the rod, the closer to the water table it becomes,
resulting in lower resistance
Typical value of resistance of
rod type electrode buried to
a depth of 1 metre (60 approx.)
35
www.ElectaCourse.com
Reducing earth electrode resistance Reducing earth electrode resistance
Under certain circumstances the value of
electrode resistance may be excessively
high and steps must be taken to reduce
its value. The following methods may be
adopted:
use of extendable rods
use of additional rods
soil conditioning agents
(temporary measure
electrodes buried to a greater depth
36
www.ElectaCourse.com
Use of additional rods to reduce resistance Use of additional rods to reduce resistance
distance (m)
depth (m)
As a rule of thumb, the distance between adjacent
earth rods should not be less than the buried depth.
earthing
conductor
37
www.ElectaCourse.com
Problems associated with the TT system Problems associated with the TT system
Vulnerable to mechanical damage
Vulnerable to corrosion
High resistance as compared to High resistance as compared to
TN systems
TN systems
38
www.ElectaCourse.com
Providing automatic disconnection for TT systems Providing automatic disconnection for TT systems
Under phase to earth fault conditions overcurrent
device should cut of supply rapidly.
Increase earth path resistance may be
sufficiently high so as to prevent automatic
disc connection resulting in:
Shock
Shock
Fire
Fire
and, or
39
www.ElectaCourse.com
Use of the residual current device Use of the residual current device
Regulation 413
Regulation 413
-
-
02
02
-
-
19
19
Preferred method of protection against indirect
contact, by means of residual current device.
40
www.ElectaCourse.com
Calculating touch voltage
Calculating touch voltage
Maximum permitted touch voltage = 50V unless
special location. (max 25V)
Regulation 413
Regulation 413
-
-
02
02
-
-
20
20
41
www.ElectaCourse.com
The following condition must be fulfilled:
R
R
A. A.
I
I

n
n

50V.
50V.
Where:
R R
AA
is the sum of the earth electrode and protective
conductors connecting it to the exposed-conductive parts
I.
I.

n
n is the current causing automatic operation
of the r.c.d.
42
www.ElectaCourse.com
43
www.ElectaCourse.com
Load Load
Exposed Exposed
metalwork metalwork
Test resistor Test resistor
Test button Test button
Search coil Search coil
Toroid Toroid
Operating coil Operating coil
The residual current device The residual current device
44
www.ElectaCourse.com
The r.c.d. under healthy circuit conditions The r.c.d. under healthy circuit conditions
45
www.ElectaCourse.com
The r.c.d. under earth fault conditions The r.c.d. under earth fault conditions
46
www.ElectaCourse.com
Protection and the TT system Protection and the TT system
Remember! The earth fault loop impedance for a TT system
may be too high to allow circuit breakers and fuses to
operate under phase to earth fault conditions.
47
www.ElectaCourse.com
48
www.ElectaCourse.com
TN TN- -S Earthing Arrangement S Earthing Arrangement
Separate neutral and earth conductors
49
www.ElectaCourse.com
1st Letter - Method of earthing for suppliers network
2nd Letter - Method of earthing at consumers installation
T = Direct connection to earth at one or more points
N = Consumers exposed metalwork directly connected to the
earthed neutral point of the supply
3rd Letter - Relationship between earth & neutral conductors
on suppliers network
S = Separate neutral and earth conductors at consumers
installation
50
www.ElectaCourse.com
Fig. 7
PES consumer
The circuit arrangement for the TN The circuit arrangement for the TN- -S system S system
51
www.ElectaCourse.com
PES consumer
The TN The TN- -S system under fault conditions S system under fault conditions
52
www.ElectaCourse.com
TN TN- -C C- -S Earthing Arrangement S Earthing Arrangement
combined neutral and earth conductors
53
www.ElectaCourse.com
1st Letter - Method of earthing for suppliers network
2nd Letter - Method of earthing at consumers installation
T = Direct connection to earth at one or more points
N = Consumers exposed metalwork directly connected to the
earthed neutral point of the supply
3rd Letter - Relationship between earth & neutral conductors
on suppliers network
C = Combined neutral and earth on suppliers side
4th Letter - Arrangement of earth and neutral conductors
at consumers installation
S = Separate neutral and earth conductors at consumers
installation
54
www.ElectaCourse.com
PES
consumer
PEN conductor
The circuit arrangement for the TN The circuit arrangement for the TN- -C C- -S system S system
55
www.ElectaCourse.com
The TN The TN- -C C- -S system under fault conditions S system under fault conditions