You are on page 1of 23

Transformer Protection

Application Guide
About the Author

George Rockefeller is President of Rockefeller Associates, Inc. He has a BS in EE from Lehigh


University; a MS from New Jersey Institute of Technology and a MBA from Fairleigh Dickinson
University. Mr. Rockefeller is a Fellow of IEEE and Past Chairman of IEEE Power Systems Relaying
Committee. He holds nine U.S. Patents and is co-author of Applied Protective Relaying (1st Edition).

Mr. Rockefeller worked for Westinghouse Electric Corporation for twenty-one years in application and
system design of protective relaying systems. He worked for Consolidated Edison Company for ten
years as a System Engineer. He has also served as a private consultant since 1982.

This Guide contains a summary of information for the protection of various types of electrical
equipment. Neither Basler Electric Company nor anyone acting on its behalf makes any warranty or
representation, express or implied, as to the accuracy or completeness of the information contained
herein, nor assumes any responsibility or liability for the use or consequences of use of any of this
information.
Revised 8/03
Transformer Protection
Application Guide

This guide focuses primarily on electrically Setting procedures are not included; refer to
actuated relays for the more prevalent applica- specific instruction manuals. Fuse protection is
tions. Principles are emphasized. The refer- only briefly addressed. Grounding transformers
ences provide a source for additional informa- and 3 phase banks of single-phase transformers
tion. Reference 1 includes extensive references are not considered here, but are treated in
and bibliographies. References 2 & 3 contain a Reference 1.
chapter on transformer protection.
Table I (page 18) provides Basler model,
This guide was prepared to assist in the selec- function, description and style number. It also
tion of relays to protect power transformers. The references the figures where the relays are
purpose of each relay is described and related indicated by their ANSI numbers.
to one or more power system examples.
1. Failure Statistics
The engineer must balance the expense of
applying a particular relay against the conse- Table II (page 3) lists failures for six categories
quences of relying on other protection or sacri- of faults (Reference 1). Winding and tap chang-
ficing the transformer. Allowing a protracted fault ers account for 70% of failures. Loose connec-
would increase the damage to the transformer tions are included as the initiating event, as well
and the possibility of tank rupture with a conse- as insulation failures. The miscellaneous
quent oil fire. An increase in damage would not category includes CT failure, external faults,
necessarily have significant economic impact, overloads and damage in shipment. An undis-
depending upon whether the initial damage can closed number of failures start as incipient
be repaired on site. For example, a tap changer problems. These failures can be detected by
flashover can ordinarily be repaired in the field, sophisticated on-line monitoring devices (e.g.
but if this fault is allowed to evolve into a winding gas-in-oil analyzer) before a serious event
fault, the economic impact can be substantial. occurs. Such devices will probably see increas-
Transformers used in a unit-connected genera- ing use on larger transformers, to supplement
tor unit are particularly critical, since the unavail- more conventional relays (Reference 8).
ability of the transformer can create large
generation-replacement costs. Similar economic 2. Fuses
impacts may also exist at industrial sites. This
explains why the MVA rating of the transformer Fuses are economical, require little maintenance
may not be the pivotal aspect in choosing the and do not need an external power source to
appropriate protection. clear a fault. However, they introduce single-
phasing conditions when just one or two

1
FIGURE 1. (See Legend, next page).
LEGEND FOR FIGURES.
resistance grounded on the 13 kV side. A
Device Description Legend detailed discussion of this application is prema-
49 Thermal CS Circuit Switcher
50/51 Instantaneous & Time Rg Grounding Resistor
ture, but the following is an introductory treat-
Overcurrent ment. The phase differential (87), ground
51 Time Overcurrent Transformer differential (87N) and sudden pressure relay (63)
51N-1 Ground Time Overcurrent Bushing
51N-2 Neutral Time Overcurrent N.C. Normally Closed
provide the primary transformer fault protection.
51N-3 Ground Time Overcurrent OP Operating Coil Note that the 51N-2 relay serves primarily as
63 Sudden Pressure Pol Polarizing Coil back-up rather than as transformer protection.
67 Directional Overcurrent
67N Directional Ground Overcurrent
The 51 and 51N-3 relays function as partial
86 Lockout Auxiliary differential relays to protect the bus and back up
87T Phase Differential, 3 Phase the downstream relays and breakers. The 67N
87N Ground Differential
relay offers an alternative to the 87N function.
The 50/51 phase overcurrent relays provide
Table II (Ref. 1) Failure Statistics for Two Time Periods
transformer backup. Also note the redundant
lockout relays (86), with the trip connections
1955 - 1965 1975-1982
Description Typical Settings & arranged such that complete protection is
Remarks
available even with a failure of one 86 relay or its
1 Number % of Number % of dc feed.
Total Total

1 Winding failures 134 51 615 51 If such an installation involves local generation,


2 Tap changer 49 19 231 19 frequency and voltage relays might also sense
failures
the islanding of the station. The 67 directional
3 Bushing failures 41 15 114 9 overcurrent relays respond to circulating load
4 Terminal board 19 7 71 6
current through the 13 kV busses if the 115 kV
failures breaker A opens. The 67 relays also provide
5 Core failures 7 3 24 2 backup for the 115 kV line relays, as well as
backup for transformer-zone faults. This is in
6 Miscellaneous 12 5 72 13
failures addition to the backup provided by the 50/51
relays.
262 100 1217 100

This example will be revisited after presenting


fuses blow, which can cause overheating of some principles and concepts.
3 phase motors. Also, fuses have a somewhat
limited interrupting capability and provide less 4. Differential Relaying
sensitive protection than that of a differential or
ground relay. Fuses should not be employed on Differential relays sense the unbalance in the
resistance-grounded systems, since they must flow of currents in various apparatus or busses.
carry the maximum load current and, therefore, In the absence of a fault in the protected zone,
cannot blow for low-current ground faults. Fuses this unbalance tends to be small because the
are probably the predominant choice for trans-
formers below 10 MVA.

Where a fused transformer uses a low-side


circuit breaker, the breaker should be equipped
with phase and ground overcurrent relays as
backup of downstream devices. However, these
relays will not respond to a transformer fault.

3. Protection Example

Fig. 1 shows extensive use of relays representa-


tive of a large industrial load. There are two 115 FIGURE 2.
kV feeds to 30 MVA transformers that are

3
istic can be set from 15 to 60%. The relay
becomes desensitized at the higher currents in
order to remain secure in the presence of
dissimilar CT performance. This creates false
operating current. In contrast, the characteristic
of the relay in Fig. 2 is a horizontal line. The
restraint current can be derived in a number of
ways. In the BE1-87T, the maximum of the input
currents provides the restraint, yielding a
consistent method regardless of the number of
inputs. Up to 5 inputs per phase can be sepa-
FIGURE 3. rately measured, depending upon the relay
flows into the zone are cancelled by the flows style.
leaving. Accordingly, such relays can be more
sensitive than phase overcurrent relays and Transformers present differential relays with
need not be delayed to coordinate with other distinctive problems, which affect their design
relays during external faults. and application. These are:
• Unequal secondary currents, because of
The simplest implementation of differential the different turns ratios of the power
protection merely parallels the CTs on all the transformer windings and the cts.
connections to the zone, per Fig. 2. However, • Phase shift of wye-delta banks.
more sophisticated means are usually employed • Tap changing under load.
to provide faster, more sensitive and reliable • Magnetizing inrush.
schemes. • Unmeasured grounded neutral current.

Transformer differential relays utilize a restraint 4.1 Current Matching


current in addition to the operating current of
Fig. 2. This produces a percentage differential The matching of unequal currents requires either
characteristic, by separately measuring the input auxiliary CTs or a means of scaling within the
currents, per Fig. 3. Fig. 4 shows such a relay. Fig. 5 shows the use of taps on the relay
characteristic for the BE1-87T phase-differential windings to match a 2-to-1 difference in the
relay, where operating (or “differential”) current levels of the CT secondary currents under non-
is plotted against the maximum (or larger) fault conditions. For this difference the 10A
restraint current. The scaling is in “multiples of current flows through just half the number of
tap”. The ratio matching taps will be explained in turns in restraint winding R1 as does the 5A
the next section. The slope of the character- current in restraint winding R2, so that the
ampere-turns of the two windings are equal.

FIGURE 4. FIGURE 5.
This tap position also connects to the midpoint
of the operating winding, so that the net opera-
ting ampere-turns is zero. Thus, by ratio match-
ing, the input currents are normalized and the
operating signal is reduced to zero. Fig. 5
applies generally to electromechanical relays.

FIGURE 7.

FIGURE 6.

Fig. 6 shows the BE1-87T’s matching taps on


the secondary of the relay’s input CTs. Rather
than use an operating CT, this relay develops
the operating signal electronically. The BE1-87T
has a matching range of 2 to 8.9A in 0.1A steps.
The taps are selected to be in proportion to the
currents to be matched.

Matching of three winding transformer applica-


tions must in effect be done two windings at a
time, rather than assuming some arbitrary
current distribution among the three windings.
FIGURE 8.
The procedure can be streamlined by assuming
identical power in all three windings. While this is
a physical impossibility, it allows proper current need to connect the main CTs in delta. With
matching for all current distributions. wye CTs a ground relay also can be connected.
A wye connection also reduces lead burden for
4.2 Phase Shift Compensation a phase fault. The worst case is for a 3-phase
fault with delta cts, per Fig. 8; the lead burden
The phase shift developed in a wye-delta power voltage is magnified to three times the 3 phase-
transformer can be handled by connecting the fault value with wye cts.
CTs in wye on one side and in delta on the other
side, per Fig. 7. The relay current input from the Note in Fig. 7 that the delta CTs are on the wye-
delta CTs is the phasor difference of two phase grounded side of the transformer. The phase
currents. The BE1-87T can perform this shift can be accommodated with the delta CTs
differencing electronically, preventing the on either side. However, it is essential to put the

5
wye-side CTs is caused by zero-sequence
current, the delta CTs filter out this unbalance in
Fig. 10.

There are two ways to form the CT delta. The


connections must mirror those of the power
transformer to provide the proper balance.

4.3 Tap Changing Under Load

FIGURE 9.

FIGURE 11.

Current matching should occur for the condition


where the load tap changer is in its neutral
position. Then, the relay must accomodate the
unbalance with the taps at the full boost or buck
position. The percentage differential characteristic
provides this accomodation, per Fig. 11. The
“total mismatch” line represents the sum of the
imperfect relay-tap match plus the power trans-
former tap contribution. The slope of this line is
approximately the total % mismatch. The mis-
match line is offset by the transformer exciting
current, which produces its own unbalance. In the
BE1-87T, available taps limit the maximum
mismatch to 2.5%. Fig. 11 also shows the BE1-
87T characteristics at the two
extremes of slope setting (15 and 60%), as well
as the related safety margins at the critical points.
FIGURE 10. The relay characteristic contains the flat section
in order to maintain good sensitivity for
delta CTs on the wye side in order to prevent low-current faults where the load current is non-
incorrect tripping for an external ground fault, negligible. The total current flowing is the pre-fault
shown in Fig. 9. Here, the delta CTs are on the current plus the current produced by the fault.
wrong side. The three units of current flow Accordingly, for small fault currents the load
entering from the grounded wye are not mea- current introduces a significant restraint bias.
sured, so they produce an unbalance. (The
delta-CT ratio is assumed to be 3/1 to provide 4.4 Magnetizing Inrush
balancing for phase faults.) In contrast, in Fig.
10 delta CTs on the wye side produce a bal- Inrush is the transient exciting current resulting
ance. Since the unbalance on the primary of the from a sudden change in the exciting voltage.
This occurs at the instant of energization, the The unrestrained element responds to the
clearing of an external fault (recovery inrush) or operating or differential current and must be set
during the inrush period of another transformer to override the largest expected inrush pulses. It
(sympathetic inrush). (Reference 4) must also override similar pulses caused by
dissimilar dc saturation of the CTs during high
Since inrush current appears as operating current external faults. For these reasons this
current to a differential relay, the relay must element is set two orders of magnitude higher
have sufficient delay and insensitivity to the than the restrained element pickup.
distorted wave or take advantage of the inrush’s
distinctive waveform by using harmonic restraint 4.4.1 Energizing Inrush
or some other form of pattern recognition. The
second harmonic predominates in inrush cur- This transient results from remanence (residual
rents (Reference 4) and is used in most trans- flux) in the core. If the instantaneous voltage at
former differential relays, either alone or in energization calls for flux of the same polarity
combination with other non-fundamental compo-
nents. The relays restrain if the harmonic(s)
exceed(s) a percentage of the fundamental
component. Historically, this percentage has
been fixed by design. Some newer designs
provide for a user setting.

Current transformer saturation also generates


harmonics. Under symmetrical conditions, CT
distortion produces only odd harmonics.
Under assymetrical conditions CT distortion
produces both even and odd harmonics. CT
saturation under assymetrical conditions can
delay a harmonically restrained element. Ac-
cordingly, an unrestrained element, set above
the maximum inrush level complements
the restrained unit. It is important to provide CTs
with sufficient quality to provide good waveform FIGURE 13.
long enough to allow either the restrained or
unrestrained element operation. as the remanence, the core is driven into
saturation, creating peak exciting currents that
Reference 5 provides means to evaluate CT can exceed ten times rated peak. This compares
adequacy. Appendix I (page 19) of this guide with a normal steady-state exciting current of
provides an example of such an evaluation. 0.01 to 0.02 times rated. Inrush current appears
as relay operating current.

In Fig. 12 the steady-state flux at the instant of


energization matches the residual flux, so no
transient current flows. In contrast, in Fig. 13 the
steady-state flux at energization is at its negative
peak. Combined with a positive remanence, this
condition produces the maxi-
mum level of transient current. The inrush
current is actually much larger in relation to
steady-state current ie than indicated by Fig. 13.

Fig. 14 shows a typical inrush waveform. Note


FIGURE 12. the “dead spot”, where almost no current is
flowing as the core exits the saturated region.

7
4.5 Overexcitation

FIGURE 14.

However, this “dead spot” disappears on subse-


quent cycles because of CT saturation (Refer- FIGURE 15.
ence 5). In extreme cases the CT can saturate
during the first cycle, eliminating the “dead spot”. Overexcitation results from excessive voltage or
The decay rate of successive primary-current below-normal frequency or a combination of the
peaks depends upon the amount of resistance in two such that the volts/Hz exceed rated. Fig. 16
the source and the non-linear inductance of the shows three situations where overexcitation can
transformer. In Fig. 14, the negative peaks are occur: a unit-connected generator isolated from
reduced further by CT saturation. The primary the system or a transformer connected on the
current peaks will not decay as fast as indicated open end of a long line. In addition, an intercon-
by the CT output of Fig. 14. nected system can experience a dynamic
overvoltage following a protracted fault as a
4.4.2 Recovery Inrush result of generator fields at ceiling or following
load shedding. All of these scenarios involve
A recovery inrush occurs at the clearing of an essentially balanced conditions. Substantial
external fault as a result of the sudden increase phase-to-ground overvoltages can also occur on
in voltage from the depressed level during the sound phases during a ground fault on imped-
fault. This voltage transient causes a flux ance-grounded systems. In these cases delta
transient, with accompanying abnormally high windings or wye-ungrounded windings will not
exciting current. The current level will be less be overexcited, since the line-line voltages will
than that of an energizing case. not increase.

4.4.3 Sympathetic Inrush The dashed curve in Fig. 17 illustrates the


increase in transformer exciting current with
Current Ip in Fig. 15 shows sympathetic inrush increased excitation, resulting in thermal stress.
current in transformer T1, resulting from the This exciting current produces operating current
energization of an adjacent transformer T2. The in the differential relay, but an operation of this
decaying dc component of current Ie flowing in relay is not desirable, since immediate response
T2 develops a drop in the source resistance Rs, is not necessary. For a dynamic overvoltage
producing pulses of inrush current Ip on the condition, the power system should be allowed
alternate half cycles. Note the delayed buildup of time to correct itself. Also, a differential
Ip. The severity of the sympathetic inrush is a operation indicates a transformer failure, requir-
function of the level of dc voltage drop across ing unnecessary investigation and delayed
the source resistance. A common set of differen- restoration of the transformer. Accordingly,
tial relays should not be used to protect both T1 where sustained overexcitation is a concern, a
and T2 transformers in Fig. 15 if they can be separate volts/Hz relay should be applied (24).
switched separately. The sum of the two trans-
former currents, Is, may not contain sufficient
harmonics to restrain the relays once trans-
former T1 saturates severely.
104 to 138% of rated excitation.

If the transformer is unloaded, as per Fig. 16(a)


and (b), the relay operating current will be the
exciting current less its third harmonic compo-
nent; then, based on Fig. 17, the fifth harmonic
content exceeds 35% over the range of about
104 to 138% of rated excitation. Should the
transformer become faulted, the relay will
operate if the fault current is sufficient to reduce
the fifth harmonic component below the relay’s
restraint level. Such a reduction occurs both
because of the reduced excitation level and due
to the fundamental-frequency fault current.
FIGURE 16.
If the transformer is loaded (e.g. Fig. 16(c)), any
The solid curves of Fig. 17 illustrate the variation mismatch current will reduce the fifth harmonic
in harmonic content with voltage changes as a level of the operating current; the relay may not
percentage of the fundamental value for a be restrained by the fifth harmonic. However, the
balanced excitation. The presence of a third transformer loading will reduce the
harmonic component indicates that the wye- overexcitation to a level where the operating
grounded winding was energized. When a delta current will be below pickup. For example, if the
winding is energized all triplen frequency transformer is at 115% excitation, Fig. 17
currents (i.e. third, ninth, etc.) are blocked, indicates a magnetizing current of 3% (including
because they are in phase on a fundamental 3rd harmonic); this plus mismatch current should
basis. With a wye-delta bank, the CTs are be insufficient to operate a relay.
connected in delta on the wye side (or the wye
currents are electronically differenced). Thus, With normal system connections the power
third harmonic component in the relay currents system could be operated at 105% continuously
is cancelled. Accordingly, the lowest harmonic and dynamically as high as about 115% during a
available to the relay for restraint is the fifth. The severe disturbance. Under these conditions the
BE1-87T restrains if the fifth harmonic exceeds third harmonic may be sufficient to restrain the
35% of the fundamental. In Fig. 17, this relay will relay; should the transformer become faulted,
restrain over the voltage range of the fault current will swamp out the exciting
current to allow the relay to trip.

Voltages in excess of 138% can follow full-load


rejection of hydro units. However, generator
speed will be correspondingly high, so the volts/
Hz value will not significantly exceed normal.

4.6 Connection Examples

Fig. 18 provides application examples for two-,


three- and five-restraint cases. The relay
derives restraint signals separately from each
set of CT inputs. In Fig. 18(a) the relay protects
a delta-wye transformer, with the CTs connected
in delta on the wye-winding side. These CTs
could be connected in wye when using a 3
phase style BE1-87T by selecting the electronic
FIGURE 17. differencing option. This differencing option

9
CTs must be connected in delta (or equivalent
electronic differencing with a 3 phase relay),
since the autotransformer is a zero-sequence
current source. Otherwise, any current flowing in
the transformer ground connection will unbal-
ance the differential relay. This current is
not measured and inputted to the relay. The
relay Fig. 18(c) protects the combination of a
bus and transformer.

A transformer differential relay can be applied


for bus or combination bus/transformer protec-
tion. CTs can be paralleled and connected to a
common restraint input. Radial feeder CTs can
be paralleled as long as the continuous rating of
the relay winding is not exceeded. Source
circuit CTs can also be paralleled, but it must be
done judiciously. Fig. 19 shows the use of a two-
restraint relay for the bus/transformer combina-
tion. Here four sets of source CTs are paralleled
and connected to a common restraint winding
R1. Such paralleling might produce a current in
excess of the continuous rating of the restraint
winding. Also, incorrect operation may occur
during an external fault as illustrated in Fig.
19(a) and (b), where the faulted-circuit CT
saturates severely. The secondary current on
circuit 2 should be 70A, but is only 50A due to
CT saturation. The CT deficiency of 20A causes
the flow in restraint winding R1 and in the
operating circuit. Since no current flows in R2,
the relay is operating along the “single-feed line”
in Fig. 19(b). This is an operating condition,
even though the fault is external to the relay
zone of protection.

Paralleling of CTs on non-source circuits can be


safe, within the thermal limitations of the relay. In
this case there is no loss of restraint for external
faults, since these circuits contribute no fault
current. Again, source CTs can also be paral-
leled, but it must be done judiciously. For
example, in Fig. 19(a), if CTs 1 and 2 were
paralleled on R1 and CTs 3 and 4 on a third
FIGURE 18.
input R3, the 40A flow in R3 would be sufficient
to prevent incorrect tripping if the relay is set
duplicates the effect of a delta-CT connection. with a 60% slope.
The operating signal is obtained by connecting
the operating coil to measure the sum of the 4.7 Phasing Example
relay input currents or electronically as is the
case in the BE1-87T. A three-input relay Fig. 20 shows a procedure for phasing the CT
protects the autotransformer in Fig. 18(b). All connections for a wye-delta transformer. There

10
A)

B)

FIGURE 20.

wye CTs (on the delta side) and to one side of


the delta-connected CTs, as shown in Fig. 20(a).
FIGURE 19. Step 2 is to show the currents flowing to
the wye power transformer winding: Ia, Ib, Ic.
are two ways to make the delta connection of Step 3 develops the currents flowing out of the
the power transformer for either a 30 degree delta power transformer winding—these depend
lead or lag. The delta CTs (or relay differencing) upon the actual transformer delta connections.
must compensate for this power transformer Step 4 shows the relay currents resulting from
phase shift. The circled numbers in Fig. 20(a) the wye CT primary currents which are deter-
represent the steps in the phasing process. The mined from the polarities of the CTs. Step 5
first step completes the relay connections to the duplicates the currents from step 4 and dictates

11
how the CT delta windings must be completed overcurrent relay, shown as 87N-1 in Fig. 21.
as shown in step 6 of Fig. 20(b). For example, However, such protection must use a delay (e.g.
in order to produce IA-IC in the direction shown, 25 cycles) to ride through the false residual
the non-polarity side of the phase “C” CT must current resulting from the dissimilar performance
connect to the phase “A” polarity side. With the of the phase CTs during a phase fault. The
delta CT connection, the relay currents on each phase fault current can be 100 times the maxi-
phase are in phase. Any difference in magnitude mum level of current during a ground fault. Thus,
is handled by selecting current taps approxi- it does not take much difference in the perfor-
mately in proportion to the current input mance of the phase CTs to create a large false
proportion. The delta CT connection also serves residual current. For the same reason, a per-
to filter any zero-sequence component from the centage differential relay for the ground differen-
relay. This component circulates in the CT delta, tial function can be insecure during external
but does not appear in the relay. phase faults, since the neutral current contrib-
utes negligible restraint during phase faults.
4.8 Ground Differential
With the 13.8kV bus tie normally closed in Fig.
1, either a ground differential or directional
ground relay is needed. Otherwise, the neutral
overcurrent relays on both transformers will
operate for a 13.8kV winding or lead fault,
resulting in an unnecessary interruption of the
station.

The amount of current for a ground fault in the


wye winding tends to be a function of the fault
location in relation to the winding neutral. A
good objective is to provide sufficient sensitivity
to detect a fault 10% from the neutral end,
where the current will be about 10% of the
maximum current. In Fig. 21, the 20 ohm resistor
limits the transformer ground current to about
(13,800/1.73)/20= 400A for a lead or transformer
terminal fault. A 10% fault, then, yields 40A
primary and 0.67A in the secondary of the 300/5
neutral CT. This current is matched by the
residual current from the 2000/5 CTs by the
auxiliary CTs (ACT) with a step-up current ratio
of 1 to 6.7A. The secondary burden on the ACT
will be magnified by the square of the current
ratio or 44 times. However, while the ohmic
burden can be very high, the ground current
level is limited by the grounding impedance. For
example, a 0.5 ohm secondary burden reflects
FIGURE 21. to a 22 ohm primary burden, but the maximum
current is just 400/400= 1A for an external line-
ground fault, yielding a burden voltage on the
Where impedance grounding limits the ground 2000/5 CTs of 1*22= 22V.
fault current to levels below the sensitivity of the
phase differential, this relay can be comple- The 87N-1 relay pickup in Fig. 21 is set for 0.5A
mented with a separate ground differential relay. based on a neutral current contribution of 0.67A
This can be a differentially-connected relay current for a ground fault 10% from the
neutral end of the wye winding. By comparison, A wye connection for the 2000/5 CTs on the low
the 87T phase differential relay sees the trans- side facilitates the auxiliary ct (ACT) connection.
former contribution for a phase fault as 0.05A With the conventional delta connection of these
compared to a pickup of 0.7A. The 87T pick-up CTs for a 3-phase 87T relay, 3 ACTs must be
current is based on a high side tap setting of 2 placed inside the delta, requiring the running of
and a relay pickup of 35% of tap. Other 13.8 kV all six CT leads to the relay location.
ground sources, where available, will increase
the level of relay current for an internal fault. In Fig. 21, the BE1-87T relay (3 phase model)
However, the protection must cover the case allows a wye connection with electronic
with no added current contribution. differencing duplicating the phase shift otherwise
provided by the delta CT connection. The 4.3A
tap of the 87T on the low-side is selected as if
the CTs were connected in delta. This tap
matches the currents within 1%.

Fig. 22 shows the development of false residual


current by the phase CTs during an external
“AB” fault due to dissimilar CT performance. The
phase A CT performs well, but the phase B CT
current of 28A is deficient by 2A. This deficiency
appears as residual current and develops 13.3A
in the 87N relay, producing 27 times pickup.

Fig. 23 shows the application of a current


FIGURE 22.
polarized directional ground-overcurrent relay for
the 87N-2 ground differential relay function. The
polarizing winding of the directional element
measures the neutral current, while the differen-
tial current supplies the directional element
operating signal and the overcurrent signals.
Fig. 23 shows that the auxiliary CT in the
residual circuit over-mismatches the neutral
current. For a 400A line-ground fault the differ-
ential current is 1.3A of the polarity to provide a
bias in the non-trip direction, providing added
security.

The directional element provides security during


multi-phase external faults, where dissimilar
phase CT performance develops false residual
current, as shown in Figure 22. Because the
residual current is highly distorted and the wave
FIGURE 23.
form varies from cycle to cycle, directional
operation is intermittent. Each time the direc-
tional element resets, it resets the time-
In Fig. 21 the transformation of the 40A low-side overcurrent element. Accordingly, the
current to the high-side requires multiplication by overcurrent element delay can be set for a
the transformer turns ratio, rather than by the fraction of the fault duration.
line-line voltage ratio. The per unit current on the
delta side is 57.7% of the per unit current on the
wye side for a line-ground fault on the wye side.

13
5. Turn-to-Turn Faults bellows 5 closing microswitch contact 7. Equal-
izer port 8, much smaller than the main port 4,
Phase differential relays may not detect a turn- prevents bellows movement for slow changes in
to-turn fault and ground differential relays do not gas pressure due to ambient temperature
respond to such faults. A neutral overcurrent changes and load cycling.
relay will see fault current if an external ground
source exists. However, for an impedance Fig. 24(b) shows use of the break contact of the
grounded system most of the fault current microswitch (63) in conjunction with auxiliary
probably will be contributed by the delta-side relay 63X. This circuit prevents tripping for a
source. A single turn fault may produce a total flashover of the make contact of 63.
less than rated current (Reference 6). Accord-
ingly, a sudden pressure relay (SPR) should be A design similar to that of Fig. 24(a) is mounted
applied to complement the differential protection. within the oil either in gas-cushioned or in
The SPR will detect any abnormality that gener- conservator-type transformers.
ates a sudden increase in pressure due to gas
generation (e.g. arcing due to a loose connec- The SPR will respond only to arcs within the oil.
tion). While more sensitive than a differential relay, the
SPR is not as fast as the electrical relay, so both
6. Sudden-Pressure Relays (63) relays should be applied.

Because these relays have experienced a


A) 1. sudden gas pressure
substantial number of undesired operations,
relay
many users connect them only to alarm. Their
2. transformer tank
reliabililty has improved by installing them on
3. insulating oil level
stiffer sections of the tank and by blocking
4. main port
tripping for high current faults. During high-
5. bellows
current external faults, winding movement
6. gas cushion
generates an oil pressure wave which has a
7. snap switch
tendency to cause relay operation. In fact, there
8. equalizer port
have been cases where a relay operation has
been a precursor to transformer failure due to
B) excessive winding movement.

Conservator-type power transformers do not


have a gas cushion within the main tank. In-
stead, the cushion resides in a separate auxil-
iary tank. A gas accumulator relay (“Bucholz”)
can be installed in the pipe connecting the main
and auxiliary tank to detect the generation of
gas. This relay has two elements, an accumula-
tor alarm and a trip function. The accumulator,
which stores a portion of the gas, provides an
alarm for slowly developing conditions. A baffle
in the pipe actuates the trip element for relatively
FIGURE 24. fast gas flow to the auxiliary tank.

Fig. 24(a) shows a SPR that detects an increase


in gas pressure, applied on gas-cushioned 7. Monitoring for Incipient Problems
transformers of about 5 MVA and up. The gas
pressure is generated by an arc under the oil, A number of on-line devices have been devel-
producing decomposition of the oil into gas oped in recent years to detect incipient condi-
products. The change in pressure actuates tions which threaten serious consequences.
These include: gas-in-oil analysis, acoustic also should prevent operation during transformer
partial-discharge detection, moisture sensor, energization. This element provides important
tap-changer-operation supervision and pump/fan fast backup of 87T for high-side faults.
supervision (Reference 8).
Because of its high pickup and slow operation,
8. Overcurrent Relays the time element provides poor protection for
transformer winding and tap changer faults.
Fig. 1 shows a number of overcurrent relays: Accordingly, this relay (and the ground
50/51, 51, 51N-1, 51N-2, 51N-3, 67 and 67N. overcurrent protection) is not a substitute for
With the possible exception of the 51 and 51N-3 differential and gas relays except for transform-
relays, the overcurrent relays serve as back-up ers smaller than about 3 MVA. The conse-
functions. quences of a slow cleared fault include the
threat of an oil fire due to a ruptured tank or
8.1 50/51 Relay bushing explosion and the necessity of having to
remove the transformer for repair. Removal is
The 50/51 phase relay time element in Fig. 1 generally necessary for even a fast cleared
(Page 2) must be set to carry the maximum winding fault. This is not the case for a tap-
expected load current. Since a transformer is changer flashover that is cleared before winding
capable of carrying considerable overload for a damage.
short period, a high pickup is normally called for
(e.g. twice the forced-cooled rating). The time 8.2 51 Relay
unit should coordinate with the 51 partial-
differential relay; otherwise, both transformers The partial differential relay 51 in Fig. 1 mea-
would be tripped for a fault downstream from the sures the sum of the transformer and bus-tie
51 relay. In the absence of a low-side trans- breaker currents. Such a connection is appropri-
former or bus-tie overcurrent relay the high-side ate with a normally-closed bus-tie breaker, to
relay should be coordinated with the feeder or avoid unwanted transformer breaker tripping for
line protection. The use of partial-differential an adjacent bus fault. This relay serves as
relays introduces an added coordination step. primary bus protection or backs up the bus
An alternative is to utilize bus-differential protec- differential protection. It also backs up for line or
tion, although a failure of this type of protection feeder faults. This relay must be set to coordi-
will result in the loss of all feeders to the station. nate with the feeder or line protection. It trips the
This is a low-probability scenario, particularly transformer and bus-tie breakers.
with metalclad switchgear.
If the transformer and bus-tie breakers are
The 50/51 operating time needs to be faster than interlocked to prevent both from being closed, a
the through-fault (external fault) withstand single set of overcurrent relays on the bus-tie
capability of the transformer (Reference 1, breaker will suffice, rather than a set of partial
Appendix). Limits have been established for 4 differential relays on both busses.
MVA ranges, based on thermal and mechanical
stresses. Fig. 25 illustrates both “frequent” and 8.3 51N-1 Relay
“infrequent” limits and recognizes the cumulative
effect of these stresses. Feeder or line relay The 51N-1 relay in Fig. 1 provides sensitive
times should fall under the frequent curves, back-up of 63 and 87T for high-side ground
while the 50/51 times should fall under the faults, but no response to turn-turn faults. The
infrequent curve. This is based upon the relative high-side ground overcurrent unit in the Fig. 1
probability of these two classes of faults. application has no coordination requirement
because the delta winding blocks ground current
The 50/51 instantaneous element should be set flow for a low-side fault. However, it must be
for about 160% of the current for a low-side 3 delayed to ride through false residual current
phase fault. This setting not only prevents that can be developed during low-side phase
incorrect operation for a low-side bus fault, but faults (see Fig. 22).

15
8.4 51N-2 Relay 67N provides just marginal value, since 51N-2
backs up 87N. Because ground fault current is
The neutral overcurrent relay in Fig. 1 primarily limited, the need for fast backup is less impel-
backs up the 51N-3 partial differential protection ling. Relays 67N and 51N-2 offer an alternative
for bus faults and it backs up 87N as well. In the to 87N. However, the advantage of the 87N
absence of the 87N application, 51N-1 provides application is that it provides fast response with
the primary ground fault protection for the the low-side breaker open or with no external
transformer low-side zone. It also backs up 87T, ground source.
depending upon the sensitivity of the 87T. The
51N-2 relay must coordinate with 51N-3 to allow 9.0 49 Thermal Protection
the latter to clear a bus fault without tripping both
transformers. Conventional thermal relays measure the oil
temperature and transformer current to estimate
If the 13.8kV bus tie can be closed with both the hot-spot temperature. They provide an
transformers in service, as shown in Fig. 1, the indication and means for controlling pumps and
51N-2 relays on both transformers will operate fans. Typically these devices provide two
for a 13.8kV winding or lead fault, unless a 67N temperature sensing levels for control, and a
or 87N relay is provided for faster clearing. third, higher temperature sensing for alarm or
tripping.
8.5 51N-3 Relay
Recently developed fiber-optic sensors, incorpo-
Section 8.2 also applies to the 51N-3 relay rated in the transformer winding, provide a direct
except that this relay provides the ground fault method of measuring the hot-spot temperature.
coverage. About four of these sensors would provide good
coverage.
8.6 67 Relay
References
The 67 relay operates for power flow from the
transformer low side toward the high side. Such 1. ANSI/IEEE C37.91-1985, IEEE Guide for
flow could occur with the 115 kV tie breaker Protective Relay Applications to Power
open, either for a 115 kV fault or under load Transformers
conditions. Reversed flow can also occur with 2. Lewis Blackburn, “Protective Relaying:
the 115 kV tie breaker closed, with local genera- Principles and Applications”, Marcel Dekker,
tion. This relay will respond to high-side ground Inc. 1987
faults, because of the phase current flow (posi- 3. S. Horowitz and A. Phadke, “Power System
tive- and negative-sequence). This is valid only Relaying”, John Wiley & Sons, Inc., 1992
as long as a remote high-side ground source 4. W. K. Sonnemann, C.L. Wagner and G.D.
remains connected. 50/51 is the only other relay Rockefeller, “Magnetizing Inrush Phenom-
in Fig. 1 responsive to a high-side ground fault ena in Transformer Banks”, AIEE Transac-
beyond the transformer high-side bushings. tions, Vol. 77, pt. III, pp 884-892, Oct. 1958
Because normal load flow is toward the low side, 5. IEEE Committee Report, “Transient Re-
67 can be set more sensitively than 50/51 and sponse of Current Transformers”, IEEE
may also be faster. Relays associated with the Special Publication, 76CH1130-4PWR
115kV breaker "A" will trip the high side circuit 6. Klingshorn, H.R. Moore, E.C. Wentz,
switcher. However, if the circuit switcher fails to “Detection of Faults in Power Transfor-
open, the 67 relay tripping the circuit switches mers”, AIEE Transactions, Vol. 76, pt. III,
and the 13.8kV breaker "B" functions as backup Apr. 1957, pp 87-98
to de-energize the circuit. 7. ANSI/IEEE C37.95-1989 “IEEE Guide for
Protective Relaying of Utility-Consumer
8.7 67N Relay Interconnections”
8. “On-Line Transformer Monitoring,” Electrical
The 67N relay serves as fast back-up protection World, Oct. 1995, pp. 19-26.
for the 87N relay. Unless 87N is not applied,
FIGURE 25.

17
Table I Relays and Typical Settings for 60 Hz Models
ANSI Qty. Basler Model/ Typical Settings & Figure
No. Description Basler Style No.
Function Remarks No.
24 1 BE1-24 1-3.99 V/Hz ACXF1XX0SXX Inverse:2.05 V/Hz --
Overexcitation (107%), TD=2, Reset:
2s/% FS; Alarm: 2.26
V/Hz(118%)
49 1 Thermal 1
50/5 3 BE1-50/51B 0.5-15.9A., 1 ph. 50/51B-1XX P.U.: 9A; TD:2 (VI); 1
1 phase 1-99A inst. Instantaneous reset;
overcurrent 60A instantaneous
51 3 BE1-50/51B 0.5-15.9A, 1 ph. 50/51B-1XX P.U.: 9A; TD: 1 (VI); 1
partial Instantaneous reset;
differential Disconnect instantaneous
51N-1 1 BE1-50/51B 0.1-3.18A, 1 ph. 50/51B-1XX P.U.: 0.25A; TD: 4 (VI); 1
ground Instantaneous reset;
overcurrent Disconnect instantaneous
51N-2 1 BE1-50/51B 0.1-3.18A, 1 ph. 50/51B-1XX P.U.: 0.5A; TD: 5 (VI); 1
Neutral Instantaneous reset;
overcurrent Disconnect instantaneous
51N-3 1 BE1-50/51B 0.1-3.18A, 1 ph. 50/51B-1XX P.U.: 0.1A; TD: 2 (VI) 1
Ground partial Instantaneous reset;
differential Disconnect instantaneous
63 Sudden pressure or 1,23
Bucholz Gas Accum.
67 1 BE1-67 Phase 0.5-12A; inst. B1XZ2XX3C6X TOC: 1A, 02 TD, B6 (VI) 1
Directional 1-40 times; 3 ph. Inst.: 15A
overcurrent
67N 1 BE1-67N 0.25-6A; directional A1XZ2XX3CXX Inst.: Not connected TOC:1
Directional instant, 2-100A 0.25A, 01 TD, B3 (Def.)
overcurrent
86-1/ 2 Lockout Aux. 1
86-2
87N-1 1 BE1-50/51M 0.1-3.18A TOC BE1-50/51M-2 Inst.: not connected 20
0.2-19.8A inst. TOC: 0.5A, 2 TD, D (Def.)
87N-2 1 BE-67N 0.25-6A TOC; A1XZ2XX3CXX Inst: 2A, polar. p.u.: 2A; 1,22
Ground 2-100A dir. inst. TOC: 0.25A, 07 TD,
differential B1(Short)
87T 3 BE-87T 2-8.9A, 3 phase E1EA1XX1XXX See Setting section of IM 1,17,2
Transformer
differential
Appendix I:
Time to Ct Saturation
For the application in Fig. 1, assume a high-side,
wye-connected, multiratio 600/5 CT on the 300/5
tap and an ANSI accuracy class of C200. The
unrestrained element pickup is 22A on the
secondary of the 300/5 CTs. The maximum time
constant of the fault current is 0.02s. Two way
lead burden (for ground fault) and CT winding
resistance is 0.4 ohms. Assume an internal fault
producing 33A, which is 150% of pickup.

Ks = (ct knee pt. voltage)/(burden voltage) =


(0.6*Effective Accuracy Class)/(22*1.5*0.4) =
(0.6*200*300/600)/13.2 = 60/13.2 = 4.5 FIGURE I-1.

[The effective accuracy class voltage is


100V, since only half the total CT turns
are in use. The knee point is at about
0.6 times the effective accuracy class.
Checking at 1.5 times the unrestrained
unit pickup.]

From Fig. I-1 (Reference 5), the time to satura- FIGURE I-2.
tion is 13ms (3/4 cycle). This applies for a fully
offset current of 33A rms symmetrical and
assumes the CT saturates at the knee point, a
somewhat conservative assumption.

This result indicates marginally acceptable CT


performance. Fig. I-2 shows CT waveform
similar to that expected for the above example,
although the dc time constant is much longer in
Fig. I-2 than the assumed 0.02s. Note that the
CT delivers considerable energy even after
onset of severe saturation, including the nega-
tive excursions. At higher levels of current the
CT will saturate sooner; however, the negative
excursions, during which interval the CT recov-
ers from saturation, produce increased energy.
Fast response depends upon the relay’s reac-
tion to this distorted waveform.

Use of a higher CT ratio will improve ct perfor-


mance, but the reduced current levels will result
in desensitizing the unrestrained element unless
the relay taps are lowered in proportion to the
drop in secondary current level.

19
the unrestrained pickup level (see Appendix I).
Appendix II: Ks is the ratio of the CT knee-point voltage to
the burden voltage. The higher the Ks value, the
Harmonics During Ct better the CT performance.
Saturation
CTs experience both “ac” and “dc” saturation.
Ac saturation results under symmetrical current
conditions. Dc saturation occurs when the
current contains a “dc” component, during a
fault, magnetizing inrush, motor starting or
generator synchronizing. CTs that produce
negligible distortion under symmetrical condi-
tions can become severely distorted when a dc
component exists (Reference 5). While faults
generally produce the most current, other
conditions such as a motor starting produce
much slower dc decay than occurs for a fault. A
smaller dc current that persists longer can also
produce dc saturation. For these external
disturbances, unequal times to saturation in
various CTs results in false operating current.
Either the harmonic-restraint or the percentage
differential restraint (fundamental frequency
characteristic) prevents unwanted tripping for
this condition.

Under symmetrical current conditions, CT


distortion generates odd harmonics, but no even
harmonics. A CT experiencing dc saturation
during an assymetrical fault develops both even
and odd harmonics. Relays that restrain on odd
harmonics may fail to operate if the harmonic
content exceeds the relays’ threshold for re-
straint. Relays that restrain on just even harmon-
ics may be temporarily restrained until the CTs
recover from the effects of the dc transient.
High-set unrestrained elements (instantaneous)
supplement the restrained elements, so that high
current faults, where CT saturtion can be
severe, can be cleared independent of any
harmonic restraint. These elements must be set
above the maximum inrush level and above the
maximum false operating current produced by
dissimilar ct performance during external faults.
For satisfactory protection, harmonic generation
by the cts should not exceed the restraint level
for a current below the unrestrained element
pickup. Poor CT quality can materially detract
from the reliability of the differential relay. A
good objective is Ks=8 or higher for a current at
Revised 8/03
If you have any questions or need Basler Electric Headquarters Basler Electric International
additional information, please contact Route 143, Box 269, P.A.E. Les Pins, 67319
Basler Electric Company. Highland Illinois USA 62249 Wasselonne Cedex FRANCE
Our web site is located at: Phone 618/654-2341 Phone (33-3-88) 87-1010
http://www.basler.com Fax 618-654-2351 Fax (33-3-88) 87-0808
e-mail: info@basler.com

You might also like