You are on page 1of 26

Medium voltage products

UniMix JTI
Secondary distribution switchgear
with rapid delivery times
2
The JTI Just To Install acronym indicates a type of
medium voltage switchgear for primary and secondary
distribution featuring very rapid delivery and putting into
service.
The customer usually receives the UniMix JTI switchgear
within two weeks.
By means of a product configuration which allows the
preparation of precise and rapid estimates, the customer
receives complete proposals and is relieved of the task
of preparing the technical specifications and design
drawings.
UniMix JTI
Designed and built for industry customers
The UniMix JTI switchgears are based on the standard
switchgear design and have a range of types that can satisfy
even partial installation requirements, thanks to both their
electrical characteristics and the standard accessories
supplied.
UniMix JTI switchgears are always fitted with mechanical and
electro-mechanical interlocks in accordance with IEC 62271-
200 standards, and are available with gas and vacuum circuit-
breakers; all the solutions have the incoming unit complying
with the CEI 0-16 standard and involve the use of the
onboard circuit-breaker relay REF601 (see warning page 3),
or alternatively, the REF542 plus unit as the protection unit.
The technical design documentation is immediately available
and the customer gives official approval of the project during
the offer stage.
3
General characteristics
Units and sides made of pre-galvanized sheet
Front panel doors painted grey RAL 7035
Fixed HD4/Unimix-F or fixed VD4/UniMix-F circuit-breaker
On-board circuit-breaker current sensors or combined
current/voltage sensors in accordance with DIN standards
On-board circuit-breaker protection relay REF601 (see
warning page 3) or protection and microprocessor control
unit REF542plus
Protection system for incoming units conforming to
standard CEI 0-16 Edition July 2008
Provision for earthing by using mobile devices or earthing
switch in the incoming unit on the network side
Conformity with Standards
IEC 62271-200
EN 62271-200
Version
Standard (not arc-proof)
Classication
Service continuity: LSC2A
Partitions: PM (Partition metallic)
UniMix JTI
Characteristics
Protection degree
IP2X inside the switchgear
IP3X on the external housing (except for the operating
seats)
IP2XC on the operating seats
Mechanical interlocks available
Circuit-breaker with line-side insulator
Line-side insulator with earthing switch
Door with earthing switch
Auxiliary circuits voltage
220 VAC
Electrical characteristics
Rated voltage kV 24
Test voltage (50 Hz/1 min) kV 50
Impulse withstand voltage kV 125
Rated frequency Hz 50
Rated current A 630
Short-time withstand current kA 16
Peak current kA 40
WARNING!
REF 601 cannot be applied for protecting systems
characterized by the presence of high harmonic currents,
in particular for feeders supplying:
electronic converters, speed regulators
active or passive PFC (Power Factor Compensation)
systems
induction heating and welding systems
arc furnaces.
Even in the case where the load is not supplied directly,
but through a power transformer.
Should the REF 601 be applied under these conditions,
ABB declines any liability for possible malfunctions.
For further information, please contact ABB.
4
HD4/UniMix-F gas circuit-breaker
(with REF601
(*)
relay and current sensors).
Current-transformer.
Current/voltage sensor.
SHS2 gas switch-disconnector. REF542plus multiple-function
control and protection unit.
VD4/UniMix-F vacuum circuit-breaker
(with REF601
(*)
relay and current sensors).
UniMix JTI
Main components
(*) see warning page 3
5
JTI A1-CLsx Switchgear
No. 1 Incoming/Outgoing Unit with CL Left
cable Riser Unit + No. 1 P1/F unit with fixed
circuit-breaker

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F or VD4/UniMix-F p230 non-
motorised circuit-breaker with shunt opening
release, shunt closing release, operation
counter, 2 NO + 2 NC auxiliary contacts,
undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication
(51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)
with 3 on-board circuit-breaker sensors and
toroid for earth fault, conforming to standard
CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side isolator in the
closed position and 1 removable key in the
open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position.

Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
UniMix JTI
Configurations available
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A1_Z_CLsx_N_N_GAS 1VCF594000R0233 Without accessories
HD4/UniMix-F JTI_A1_Z_CLsx_N_R_GAS 1VCF594000R0234 Anti-condensation heater
HD4/UniMix-F JTI_A1_Z_CLsx_I_N_GAS 1VCF594000R0235 Internal lighting
HD4/UniMix-F JTI_A1_Z_CLsx_I_R_GAS 1VCF594000R0236 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A1_Z_CLsx_N_N_VUOTO 1VCF594000R0273 Without accessories
VD4/UniMix-F JTI_A1_Z_CLsx_N_R_VUOTO 1VCF594000R0274 Anti-condensation heater
VD4/UniMix-F JTI_A1_Z_CLsx_I_N_VUOTO 1VCF594000R0275 Internal lighting
VD4/UniMix-F JTI_A1_Z_CLsx_I_R_VUOTO 1VCF594000R0276 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0145
6
JTI A1-CLdx Switchgear
No. 1 Incoming/Outgoing Unit with CL Right
cable Riser Unit + No. 1 P1/F unit with fixed
circuit-breaker

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F or VD4/UniMix-F p230 non-
motorised circuit-breaker with shunt opening
release, shunt closing release, operation
counter, 2 NO + 2 NC auxiliary contacts,
undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication
(51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)
with 3 on-board circuit-breaker sensors and
toroid for earth fault, conforming to standard
CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side isolator in the
closed position and 1 removable key in the
open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position.

Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A1_Z_CLdx_N_N_GAS 1VCF594000R0237 Without accessories
HD4/UniMix-F JTI_A1_Z_CLdx_N_R_GAS 1VCF594000R0238 Anti-condensation heater
HD4/UniMix-F JTI_A1_Z_CLdx_I_N_GAS 1VCF594000R0239 Internal lighting
HD4/UniMix-F JTI_A1_Z_CLdx_I_R_GAS 1VCF594000R0240 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A1_Z_CLdx_N_N_VUOTO 1VCF594000R0277 Without accessories
VD4/UniMix-F JTI_A1_Z_CLdx_N_R_VUOTO 1VCF594000R0278 Anti-condensation heater
VD4/UniMix-F JTI_A1_Z_CLdx_I_N_VUOTO 1VCF594000R0279 Internal lighting
VD4/UniMix-F JTI_A1_Z_CLdx_I_R_VUOTO 1VCF594000R0280 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0145
UniMix JTI
Configurations available
7
No. 1 Incoming/Outgoing Unit with incoming
cables from the top AC + No. 1 P1/F unit with
fixed circuit-breaker

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F or VD4/UniMix-F p230 non-
motorised circuit-breaker with shunt opening
release, shunt closing release, operation
counter, 2 NO + 2 NC auxiliary contacts,
undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication
(51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)
with 3 on-board circuit-breaker sensors and
toroid for earth fault, conforming to standard
CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side insulator in
the closed position and 1 removable key in
the open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position.


Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
JTI A1-AC Switchgear
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A1_Z_AC_N_N_GAS 1VCF594000R0241 Without accessories
HD4/UniMix-F JTI_A1_Z_AC_N_R_GAS 1VCF594000R0242 Anti-condensation heater
HD4/UniMix-F JTI_A1_Z_AC_I_N_GAS 1VCF594000R0243 Internal lighting
HD4/UniMix-F JTI_A1_Z_AC_I_R_GAS 1VCF594000R0244 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A1_Z_AC_N_N_VUOTO 1VCF594000R0281 Without accessories
VD4/UniMix-F JTI_A1_Z_AC_N_R_VUOTO 1VCF594000R0282 Anti-condensation heater
VD4/UniMix-F JTI_A1_Z_AC_I_N_VUOTO 1VCF594000R0283 Internal lighting
VD4/UniMix-F JTI_A1_Z_AC_I_R_VUOTO 1VCF594000R0284 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0143
8
JTI A1-Asx Switchgear
No. 1 Incoming Unit with Unit A with
Left earthing switch + No. 1 P1/F Unit
with fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing
switch in the open position.
P1/F Outgoing Unit

Presence of voltage on cable side.

HD4/Unimix-F or VD4/UniMix-F p230
non-motorised circuit-breaker with
shunt opening release, shunt closing
release, operation counter, 2 NO +
2 NC auxiliary contacts,
undervoltage release and contact
signalling release de-energised.

REF601 protection relay without
communication (51, I>; 51, I>>; 50,
I>>>; 51N, Io>; 50N, Io>>) with 3
on-board circuit-breaker sensors
and toroid for earth fault, conforming
to standard CEI 0-16 (see warning
page 3).

SHS2/IB disconnector with:
1 removable key with line-side
insulator in the closed position
and 1 removable key in the open
position;
1 removable key with earthing
switch in the closed position
and 1 removable key in the open
position.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A1_Z_Asx_N_N_GAS 1VCF594000R0245 Without accessories
HD4/UniMix-F JTI_A1_Z_Asx_N_R_GAS 1VCF594000R0246 Anti-condensation heater
HD4/UniMix-F JTI_A1_Z_Asx_I_N_GAS 1VCF594000R0247 Internal lighting
HD4/UniMix-F JTI_A1_Z_Asx_I_R_GAS 1VCF594000R0248 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A1_Z_Asx_N_N_VUOTO 1VCF594000R0285 Without accessories
VD4/UniMix-F JTI_A1_Z_Asx_N_R_VUOTO 1VCF594000R0286 Anti-condensation heater
VD4/UniMix-F JTI_A1_Z_Asx_I_N_VUOTO 1VCF594000R0287 Internal lighting
VD4/UniMix-F JTI_A1_Z_Asx_I_R_VUOTO 1VCF594000R0288 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
UniMix JTI
Configurations available
9
JTI A1-Adx Switchgear
No. 1 Incoming Unit with Unit A with
Right earthing switch + No. 1 P1/F
Unit with fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing
switch in the open position.
P1/F Outgoing Unit

Presence of voltage on cable side.

HD4/Unimix-F or VD4/UniMix-F p230
non-motorised circuit-breaker with
shunt opening release, shunt closing
release, operation counter, 2 NO +
2 NC auxiliary contacts, undervoltage
release and contact signalling release
de-energised.

REF601 protection relay without
communication (51, I>; 51, I>>; 50,
I>>>; 51N, Io>; 50N, Io>>) with 3
on-board circuit-breaker sensors
and toroid for earth fault, conforming
to standard CEI 0-16 (see warning
page 3).

SHS2/IB disconnector with:
1 removable key with line-side
insulator in the closed position
and 1 removable key in the open
position;
1 removable key with earthing
switch in the closed position
and 1 removable key in the open
position.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A1_Z_Adx_N_N_GAS 1VCF594000R0249 Without accessories
HD4/UniMix-F JTI_A1_Z_Adx_N_R_GAS 1VCF594000R0250 Anti-condensation heater
HD4/UniMix-F JTI_A1_Z_Adx_I_N_GAS 1VCF594000R0251 Internal lighting
HD4/UniMix-F JTI_A1_Z_Adx_I_R_GAS 1VCF594000R0252 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A1_Z_Adx_N_N_VUOTO 1VCF594000R0289 Without accessories
VD4/UniMix-F JTI_A1_Z_Adx_N_R_VUOTO 1VCF594000R0290 Anti-condensation heater
VD4/UniMix-F JTI_A1_Z_Adx_I_N_VUOTO 1VCF594000R0291 Internal lighting
VD4/UniMix-F JTI_A1_Z_Adx_I_R_VUOTO 1VCF594000R0292 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
10
JTI A2-Racsx switchgear with SF
6
circuit-breaker
No. 1 Incoming/Outgoing Unit with Rac Left
cable Riser Unit + No. 1 P1/F Unit with fixed
circuit-breaker

235 mm LV compartment.

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F p230 non motorised circuit-
breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts,
operation counter and springs charged
signalling.

REF542 plus protection and control unit (51,
I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)
with DATA LOGGER and 3 KEVCD type ABB
voltage/current sensors and toroid for earth fault
conforming to standard CEI 0-16.

SHS2/IB disconnector with:
1 removable key with line-side insulator in
the closed position and 1 removable key in
the open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position;
Auxiliary contacts: 2 NO or NC with line-side
disconnector and 2 NO or NC for earthing
switch.


Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A2_Z_RACsx_N_N_GAS 1VCF594000R0313 Without accessories
HD4/UniMix-F JTI_A2_Z_RACsx_N_R_GAS 1VCF594000R0314 Anti-condensation heater
HD4/UniMix-F JTI_A2_Z_RACsx_I_N_GAS 1VCF594000R0315 Internal lighting
HD4/UniMix-F JTI_A2_Z_RACsx_I_R_GAS 1VCF594000R0316 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0459
UniMix JTI
Configurations available
11
JTI A2-Racsx switchgear with vacuum circuit-breaker
No. 1 Incoming/Outgoing Unit with Rac Left
cable Riser Unit + No. 1 P1/F Unit with fixed
circuit-breaker

235 mm LV compartment.

Presence of voltage on busbar side and cable
side.

VD4/Unimix-F p230 non motorised circuit-bre-
aker with shunt opening release, shunt closing
release, 3 NO + 4 NC auxiliary contacts, ope-
ration counter and springs charged signalling,
undervoltage release and contact signalling
release de-energised.

REF542 plus protection and control unit (51, I>;
51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC) with
3 KEVCD type ABB voltage/current sensors
and toroid for earth fault conforming to stan-
dard CEI 0-16.

SHS2/IB disconnector with:
1 removable key with line-side disconnector
in the closed position and 1 removable key
in the open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position;
Auxiliary contacts: 2 NO or NC with line-side
disconnector and 2 NO or NC for earthing
switch.

Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A2_Z_RACsx_N_N_VUOTO 1VCF594000R0345 Without accessories
VD4/UniMix-F JTI_A2_Z_RACsx_N_R_VUOTO 1VCF594000R0346 Anti-condensation heater
VD4/UniMix-F JTI_A2_Z_RACsx_I_N_VUOTO 1VCF594000R0347 Internal lighting
VD4/UniMix-F JTI_A2_Z_RACsx_I_R_VUOTO 1VCF594000R0348 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0459
12
JTI A2-Racdx switchgear with SF
6
circuit-breaker
No. 1 Incoming/Outgoing Unit with Rac Right
Cable Riser Unit + No. 1 P1/F Unit with fixed
circuit-breaker

235 mm LV compartment.

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F p230 non motorised circuit-
breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts,
operation counter and springs charged
signalling.

REF542 plus protection and control unit (51,
I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)
with DATA LOGGER and 3 KEVCD type ABB
voltage/current sensors and toroid for earth fault
conforming to standard CEI 0-16.

SHS2/IB disconnector with:
1 removable key with line-side disconnector
in the closed position and 1 removable key
in the open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position;
Auxiliary contacts: 2 NO or NC with line-side
disconnector and 2 NO or NC for earthing
switch.

Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A2_Z_RACdx_N_N_GAS 1VCF594000R0317 Without accessories
HD4/UniMix-F JTI_A2_Z_RACdx_N_R_GAS 1VCF594000R0318 Anti-condensation heater
HD4/UniMix-F JTI_A2_Z_RACdx_I_N_GAS 1VCF594000R0319 Internal lighting
HD4/UniMix-F JTI_A2_Z_RACdx_I_R_GAS 1VCF594000R0320 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0459
UniMix JTI
Configurations available
13
JTI A2-Racdx switchgear with vacuum circuit-breaker
No. 1 Incoming/Outgoing Unit with Rac Right
Cable Riser Unit + No. 1 P1/F Unit with fixed
circuit-breaker
235 mm LV compartment.
Presence of voltage on busbar side and cable
side.
VD4/Unimix-F p230 non motorised circuit-
breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts,
operation counter and springs charged
signalling, undervoltage release and contact
signalling release de-energised.
REF542 plus protection and control unit (51,
I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)
with 3 KEVCD type ABB voltage/current
sensors and toroid for earth fault conforming to
standard CEI 0-16.
SHS2/IB disconnector with:
1 removable key with line-side disconnector
in the closed position and 1 removable key
in the open position;
1 removable key with earthing switch in the
closed position and 1 removable key in the
open position;
Auxiliary contacts: 2 NO or NC with line-side
disconnector and 2 NO or NC for earthing
switch.
Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A2_Z_RACdx_N_N_VUOTO 1VCF594000R0349 Without accessories
VD4/UniMix-F JTI_A2_Z_RACdx_N_R_VUOTO 1VCF594000R0350 Anti-condensation heater
VD4/UniMix-F JTI_A2_Z_RACdx_I_N_VUOTO 1VCF594000R0351 Internal lighting
VD4/UniMix-F JTI_A2_Z_RACdx_I_R_VUOTO 1VCF594000R0352 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0459
14
JTI A2-Asx switchgear with SF
6
circuit-breaker
No. 1 Incoming Unit with Unit A Left
earthing switch + No. 1 Unit P1/F with
fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing switch
in the open position.
P1/F Outgoing Unit

235 mm LV compartment.

Presence of voltage on cable side.

HD4/Unimix-F p230 non motorised
circuit-breaker with shunt opening
release, shunt closing release, 3 NO
+ 4 NC auxiliary contacts, operation
counter and springs charged signalling.

REF542 plus protection and control unit
(51, I>; 51, I>>; 50, I>>>; 50N, Io>>;
67NI; 67NC) with DATA LOGGER and 3
KEVCD type ABB voltage/current sen-
sors and toroid for earth fault confor-
ming to standard CEI 0-16.

SHS2/ES Earthing switch with:
1 removable key with line-side
disconnector in the closed position
and 1 removable key in the open
position;
1 removable key with earthing
switch in the closed position and 1
removable key in the open position;
auxiliary contacts: 2 NO or NC with
line-side disconnector and 2 NO or
NC for earthing switch.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A2_Z_Asx_N_N_GAS 1VCF594000R0321 Without accessories
HD4/UniMix-F JTI_A2_Z_Asx_N_R_GAS 1VCF594000R0322 Anti-condensation heater
HD4/UniMix-F JTI_A2_Z_Asx_I_N_GAS 1VCF594000R0323 Internal lighting
HD4/UniMix-F JTI_A2_Z_Asx_I_R_GAS 1VCF594000R0324 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
UniMix JTI
Configurations available
15
JTI A2-Asx switchgear with vacuum circuit-breaker
No. 1 Incoming Unit with Unit A Left
earthing switch + No. 1 P1/F Unit with
fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing
switch in the open position.
P1/F Outgoing Unit

235 mm LV compartment.

Presence of voltage on cable side.

VD/Unimix-F p230 non motorised
circuit-breaker with shunt opening
release, shunt closing release, 3 NO
+ 4 NC auxiliary contacts, operation
counter and springs charged signalling,
undervoltage release and contact
signalling release de-energised.

REF542 plus protection and control unit
(51, I>; 51, I>>; 50, I>>>; 50N, Io>>;
67NI; 67NC) with 3 KEVCD type ABB
voltage/current sensors and toroid for
earth fault conforming to standard
CEI 0-16.

SHS2/ES Earthing switch with:
1 removable key with line-side discon-
nector in the closed position and 1
removable key in the open position;
1 removable key with earthing switch
in the closed position and 1 removable
key in the open position;
auxiliary contacts: 2 NO or NC for
line-side insulator and 2 NO or NC
for earthing switch.
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A2_Z_Asx_N_N_VUOTO 1VCF594000R0353 Without accessories
VD4/UniMix-F JTI_A2_Z_Asx_N_R_VUOTO 1VCF594000R0354 Anti-condensation heater
VD4/UniMix-F JTI_A2_Z_Asx_I_N_VUOTO 1VCF594000R0355 Internal lighting
VD4/UniMix-F JTI_A2_Z_Asx_I_R_VUOTO 1VCF594000R0356 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
16
JTI A2-Adx switchgear with SF
6
circuit-breaker
No. 1 Incoming Unit with Unit A Right
earthing switch + No. 1 P1/F Unit with
fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing switch
in the open position.
P1/F Outgoing Unit

235 mm LV compartment.

Presence of voltage on cable side.

HD4/Unimix-F p230 non motorised
circuit-breaker with shunt opening rele-
ase, shunt closing release, 3 NO + 4 NC
auxiliary contacts, operation counter and
springs charged signalling.

REF542 plus protection and control unit
(51, I>; 51, I>>; 50, I>>>; 50N, Io>>;
67NI; 67NC) with DATA LOGGER and 3
KEVCD type ABB voltage/current sensors
and toroid for earth fault conforming to
standard CEI 0-16 (see warning page 3).

SHS2/ES Earthing switch with:
1 removable key with line-side discon-
nector in the closed position and 1
removable key in the open position;
1 removable key with earthing switch
in the closed position and 1 removable
key in the open position;
auxiliary contacts: 2 NO or NC with
line-side disconnector and 2 NO or
NC for earthing switch.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_A2_Z_Adx_N_N_GAS 1VCF594000R0325 Without accessories
HD4/UniMix-F JTI_A2_Z_Adx_N_R_GAS 1VCF594000R0326 Anti-condensation heater
HD4/UniMix-F JTI_A2_Z_Adx_I_N_GAS 1VCF594000R0327 Internal lighting
HD4/UniMix-F JTI_A2_Z_Adx_I_R_GAS 1VCF594000R0328 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
UniMix JTI
Configurations available
17
JTI A2-Adx switchgear with vacuum circuit-breaker
No. 1 Incoming Unit with Unit A Right
earthing switch + No. 1 P1/F Unit with
fixed circuit-breaker
Incoming Unit A

Presence of voltage on cable side.

SHS2/ES Earthing switch with:
2 removable keys with earthing
switch in the open position.
P1/F Outgoing Unit

235 mm LV compartment.

Presence of voltage on cable side.

VD/Unimix-F p230 non motorised
circuit-breaker with shunt opening
release, shunt closing release, 3 NO
+ 4 NC auxiliary contacts, operation
counter and springs charged signalling,
undervoltage release and contact
signalling release de-energised.

REF542 plus protection and control unit
(51, I>; 51, I>>; 50, I>>>; 50N, Io>>;
67NI; 67NC) with 3 KEVCD type ABB
voltage/current sensors and toroid for
earth fault conforming to standard
CEI 0-16.

SHS2/ES Earthing switch with:
1 removable key with line-side
disconnector in the closed position
and 1 removable key in the open
position;
1 removable key with earthing
switch in the closed position and 1
removable key in the open position;
auxiliary contacts: 2 NO or NC with
line-side disconnector and 2 NO or
NC for earthing switch.
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_A2_Z_Adx_N_N_VUOTO 1VCF594000R0357 Without accessories
VD4/UniMix-F JTI_A2_Z_Adx_N_R_VUOTO 1VCF594000R0358 Anti-condensation heater
VD4/UniMix-F JTI_A2_Z_Adx_I_N_VUOTO 1VCF594000R0359 Internal lighting
VD4/UniMix-F JTI_A2_Z_Adx_I_R_VUOTO 1VCF594000R0360 Internal lighting and anti-condensation heater
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0457
18
JTI B1 Switchgear
No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer
Protection Units
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable side.

HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-
breaker with shunt opening release, shunt closing release,
operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage
release and contact signalling release
de-energised.

REF601 protection relay without communication (51, I>;
51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>) with 3 on-board
circuit-breaker sensors and toroid for earth fault, conforming to
standard CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
2 removable keys with earthing switch in the open position.

Provision for earthing by means of insulating rod. The insulating
rod is not included in the supply unless ordered separately.
P1/F Transformer Protection Unit

Presence of voltage on cable side.

HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-
breaker with shunt opening release, shunt closing release, 2 NO +
2 NC auxiliary contacts and operation counter.

REF601 protection relay conforming to IEC standard with 3
sensors and toroid for earth fault (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
1 removable key with earthing switch in the closed position
and 1 removable key in the open position.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_B1_Z_N_N_GAS 1VCF594000R0377 Without accessories
HD4/UniMix-F JTI_B1_Z_N_R_GAS 1VCF594000R0378 Anti-condensation heater
HD4/UniMix-F JTI_B1_Z_I_N_GAS 1VCF594000R0379 Internal lighting
HD4/UniMix-F JTI_B1_Z_I_R_GAS 1VCF594000R0380 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_B1_Z_N_N_VUOTO 1VCF594000R0385 Without accessories
VD4/UniMix-F JTI_B1_Z_N_R_VUOTO 1VCF594000R0386 Anti-condensation heater
VD4/UniMix-F JTI_B1_Z_I_N_VUOTO 1VCF594000R0387 Internal lighting
VD4/UniMix-F JTI_B1_Z_I_R_VUOTO 1VCF594000R0388 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0147
UniMix JTI
Configurations available
19
JTI B2 switchgear with SF
6
circuit-breaker
No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer
Protection Units
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable side.

HD4/Unimix-F or VD4/Unimix-F p230 non motorised
circuit-breaker with shunt opening release, shunt closing release,
3 NO + 4 NC auxiliary contacts, operation counter and springs
charged signalling.

REF542 plus protection and control unit (51, I>; 51, I>>;
50, I>>>; 50N, Io>>; 67NI; 67NC) with DATA LOGGER and
3 KEVCD type ABB voltage/current sensors and toroid for earth
fault conforming to standard CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
2 removable keys with earthing switch in the open position;
auxiliary contacts: 2 NO or NC with line-side disconnector
and 2 NO or NC for earthing switch.

Provision for earthing by means of insulating rod. The insulating
rod is not included in the supply unless ordered separately.
P1/F Transformer Protection Unit

Presence of voltage on cable side.

HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-
breaker with shunt opening release, shunt closing release, 2 NO +
2 NC auxiliary contacts and operation counter.

REF601 protection relay conforming to IEC standard with 3
sensors and toroid for earth fault (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
1 removable key with earthing switch in the closed position
and 1 removable key in the open position.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_B2_Z_N_N_GAS 1VCF594000R0393 Without accessories
HD4/UniMix-F JTI_B2_Z_N_R_GAS 1VCF594000R0394 Anti-condensation heater
HD4/UniMix-F JTI_B2_Z_I_N_GAS 1VCF594000R0395 Internal lighting
HD4/UniMix-F JTI_B2_Z_I_R_GAS 1VCF594000R0396 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0147
20
JTI B2 switchgear with vacuum circuit-breaker
No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer
Protection Units
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable side.

VD4/Unimix-F p230 non motorised circuit-breaker with shunt
opening release, shunt closing release, 3 NO + 4 NC auxiliary
contacts, operation counter and springs charged signalling,
undervoltage release and contact signalling release
de-energised.

REF542 plus protection and control unit (51, I>; 51, I>>; 50,
I>>>; 50N, Io>>; 67NI; 67NC) with 3 KEVCD type ABB voltage/
current sensors and toroid for earth fault conforming to standard
CEI 0-16.

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
2 removable keys with earthing switch in the open position;
auxiliary contacts: 2 NO or NC with line-side disconnector
and 2 NO or NC for earthing switch.

Provision for earthing by means of insulating rod. The insulating
rod is not included in the supply unless ordered separately.
P1/F Transformer Protection Unit

Presence of voltage on cable side.

HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-
breaker with shunt opening release, shunt closing release, 2 NO
+ 2 NC auxiliary contacts and operation counter.

REF601 protection relay conforming to IEC standard with 3
sensors and toroid for earth fault (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed
position and 1 removable key in the open position;
1 removable key with earthing switch in the closed position
and 1 removable key in the open position.
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_B2_Z_N_N_VUOTO 1VCF594000R0401 Without accessories
VD4/UniMix-F JTI_B2_Z_N_R_VUOTO 1VCF594000R0402 Anti-condensation heater
VD4/UniMix-F JTI_B2_Z_I_N_VUOTO 1VCF594000R0403 Internal lighting
VD4/UniMix-F JTI_B2_Z_I_R_VUOTO 1VCF594000R0404 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
UniMix JTI
Configurations available
21
JTI B3 Switchgear
No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer
Protection Units with switch-disconnector
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable side.

HD4/Unimix-F or VD4/Unimix p230 non-motorised circuit-breaker with
shunt opening release, shunt closing release, operation counter, 2 NO
+ 2 NC auxiliary contacts, undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication (51, I>; 51, I>>; 50, I>>>;
51N, Io>; 50N, Io>>) with 3 on-board circuit-breaker current sensors and
toroid for earth fault, conforming to standard CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed position
and 1 removable key in the open position;
2 removable keys with earthing switch in the open position.

Provision for earthing by means of insulating rod. The insulating rod is not
included in the supply unless ordered separately.
P2 Transformer Protection Unit (unit width: 500 mm)

Presence of voltage on cable side.

SHS2/T2F switch-disconnector with:
1 removable key with line-side disconnector in the closed position
and 1 removable key in the open position;
1 removable key with earthing switch in the closed position and 1
removable key in the open position;

shunt opening release;
fuse-holder;
mechanical trip system for blown fuse;
contact for signalling fuse blown;
auxiliary contacts: 2 NO or NC with line-side disconnector and
2 NO or NC for earthing switch.

Fuses not included in the supply (if not ordered separately).
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_B3_Z_N_N_GAS 1VCF594000R0409 Without accessories
HD4/UniMix-F JTI_B3_Z_N_R_GAS 1VCF594000R0410 Anti-condensation heater
HD4/UniMix-F JTI_B3_Z_I_N_GAS 1VCF594000R0411 Internal lighting
HD4/UniMix-F JTI_B3_Z_I_R_GAS 1VCF594000R0412 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_B3_Z_N_N_VUOTO 1VCF594000R0417 Without accessories
VD4/UniMix-F JTI_B3_Z_N_R_VUOTO 1VCF594000R0418 Anti-condensation heater
VD4/UniMix-F JTI_B3_Z_I_N_VUOTO 1VCF594000R0419 Internal lighting
VD4/UniMix-F JTI_B3_Z_I_R_VUOTO 1VCF594000R0420 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0149
Fuses for P2 unit Sales code Note
24 kV - 16 A 1VCF594000R0194 To be ordered in sets of 3 pieces
24 kV - 25 A 1VCF594000R0195 To be ordered in sets of 3 pieces
24 kV - 40 A 1VCF594000R0196 To be ordered in sets of 3 pieces
24 kV - 50 A 1VCF594000R0471 To be ordered in sets of 3 pieces
24 kV - 63 A 1VCF594000R0197 To be ordered in sets of 3 pieces
22
JTI B4 Switchgear
No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer
Protection Units with switch-disconnector
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable side.

HD4/Unimix-F or VD4/Unimix p230 non-motorised circuit-breaker with
shunt opening release, shunt closing release, operation counter, 2 NO
+ 2 NC auxiliary contacts, undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication (51, I>; 51, I>>; 50, I>>>;
51N, Io>; 50N, Io>>) with 3 on-board circuit-breaker current sensors and
toroid for earth fault, conforming to standard CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector in the closed position
and 1 removable key in the open position;
2 removable keys with earthing switch in the open position.

Provision for earthing by means of insulating rod. The insulating rod is not
included in the supply unless ordered separately.
P2 Transformer Protection Unit (unit width: 375 mm)

Presence of voltage on cable side.

SHS2/T2F switch-disconnector with:
1 removable key with line-side disconnector in the closed position
and 1 removable key in the open position;
1 removable key with earthing switch in the closed position and 1
removable key in the open position;
shunt opening release;
fuse-holder;
mechanical trip system for blown fuse;
contact for signalling fuse blown;
auxiliary contacts: 2 NO or NC with line-side disconnector and 2 NO
or NC for earthing switch.

Fuses not included in the supply (if not ordered separately).
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_B4_Z_N_N_GAS 1VCF594000R0425 Without accessories
HD4/UniMix-F JTI_B4_Z_N_R_GAS 1VCF594000R0426 Anti-condensation heater
HD4/UniMix-F JTI_B4_Z_I_N_GAS 1VCF594000R0427 Internal lighting
HD4/UniMix-F JTI_B4_Z_I_R_GAS 1VCF594000R0428 Internal lighting and anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_B4_Z_N_N_VUOTO 1VCF594000R0433 Without accessories
VD4/UniMix-F JTI_B4_Z_N_R_VUOTO 1VCF594000R0434 Anti-condensation heater
VD4/UniMix-F JTI_B4_Z_I_N_VUOTO 1VCF594000R0435 Internal lighting
VD4/UniMix-F JTI_B4_Z_I_R_VUOTO 1VCF594000R0436 Internal lighting and anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0149
Fuses for P2 unit Sales code Note
24 kV - 16 A 1VCF594000R0194 To be ordered in sets of 3 pieces
24 kV - 25 A 1VCF594000R0195 To be ordered in sets of 3 pieces
24 kV - 40 A 1VCF594000R0196 To be ordered in sets of 3 pieces
24 kV - 50 A 1VCF594000R0471 To be ordered in sets of 3 pieces
24 kV - 63 A 1VCF594000R0197 To be ordered in sets of 3 pieces
UniMix JTI
Configurations available
23
JTI C1 Dx JTI C1 Sx
JTI C1 Switchgear
No.1 Incoming Line with P1/A Unit
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and
cable side.

HD4/Unimix-F or VD4/Unimix p230
non-motorised circuit-breaker with shunt
opening release, shunt closing release,
operation counter, 2 NO + 2 NC auxiliary
contacts, undervoltage release and
contact signalling release de-energised.

REF601 protection relay without
communication (51, I>; 51, I>>; 50, I>>>;
51N, Io>; 50N, Io>>) with 3 on-board
circuit-breaker sensors and toroid for
earth fault, conforming to standard CEI
0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side
disconnector in the closed position
and 1 removable key in the open
position;
2 removable keys with earthing switch
in the open position.

Provision for earthing by means of
insulating rod. The insulating rod is not
included in the supply unless ordered
separately.

The busbars for coupling with adjacent
unit are not included in the supply unless
ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_C1_Z_Sx_N_N_GAS 1VCF594000R0441 Without accessories
HD4/UniMix-F JTI_C1_Z_Sx_N_R_GAS 1VCF594000R0442 Anti-condensation heater
HD4/UniMix-F JTI_C1_Z_Dx_N_N_GAS 1VCF594000R0443 Without accessories
HD4/UniMix-F JTI_C1_Z_Dx_N_R_GAS 1VCF594000R0444 Anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_C1_Z_Sx_N_N_VUOTO 1VCF594000R0449 Without accessories
VD4/UniMix-F JTI_C1_Z_Sx_N_R_VUOTO 1VCF594000R0450 Anti-condensation heater
VD4/UniMix-F JTI_C1_Z_Dx_N_N_VUOTO 1VCF594000R0451 Without accessories
VD4/UniMix-F JTI_C1_Z_Dx_N_R_VUOTO 1VCF594000R0452 Anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 mm 1VCF594000R0143
Busbars for coupling with adjacent unit Sales code
With 375 mm unit 1VCF594000R0208
With 500 mm unit 1VCF594000R0207
With 750 mm unit 1VCF594000R0206
Note: the units concerned can only be used for coupling existing UniMix switchgears by means
of omnibus bus bars to be ordered using the relative code.
24
UniMix JTI
Configurations available
JTI C1-AC Switchgear
No.1 Incoming Line with P1/A Unit
with AC top exit
Incoming Unit P1/A

235 mm LV compartment.

Presence of voltage on busbar side and cable
side.

HD4/Unimix-F or VD4/Unimix p230 non-
motorised circuit-breaker with shunt opening
release, shunt closing release, operation
counter, 2 NO + 2 NC auxiliary contacts,
undervoltage release and contact signalling
release de-energised.

REF601 protection relay without communication
(51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)
with 3 on-board circuit-breaker sensors and
toroid for earth fault, conforming to standard
CEI 0-16 (see warning page 3).

SHS2/IB disconnector with:
1 removable key with line-side disconnector
in the closed position and 1 removable key in
the open position;
1 removable key with earthing-switch in the
closed position and 1 removable key in the
open position.


Provision for earthing by means of insulating
rod. The insulating rod is not included in the
supply unless ordered separately.
Circuit-breaker Switchgear description Sales code Fittings
HD4/UniMix-F JTI_C1_Z_AC_N_N_GAS 1VCF594000R0463 Without accessories
HD4/UniMix-F JTI_C1_Z_AC_N_R_GAS 1VCF594000R0464 Anti-condensation heater
Circuit-breaker Switchgear description Sales code Fittings
VD4/UniMix-F JTI_C1_Z_AC_N_N_VUOTO 1VCF594000R0467 Without accessories
VD4/UniMix-F JTI_C1_Z_AC_N_R_VUOTO 1VCF594000R0468 Anti-condensation heater
Completion Description Sales code
Insulating rod Kit for mobile earthing 1VCF594000R0218
Completion Height Sales code
Raising plinth 300 m 1VCF594000R0143
25
W
D
H
Maximum operating temperature of
transformer
T [C]
No-load losses Wo [W]
Load losses Wcc [W]
Load factor a
Rated current In [A]
Total losses Ptot. = Wo + a2 x Wcc
Types available
Unit W [mm] D [mm] H [mm]
TR1 1600 1150 1950
TR2 2000 1150 1950
TR3 2000 1300 2250
TR4 2200 1500 2250
TR5 2200 1800 2250
Type of box
Total losses [W]
T=100 C T=120 C T=140 C
TR1 5.000 6.000 7.000
TR2 6.000 7.500 8.500
TR3 7.500 9.000 10.500
TR4 8.500 10.000 11.500
TR5 9.000 10.500 12.500
No. 1 Transformer box Units
The transformer box unit is only available in the standard
version. The transformer box is made of galvanised sheet
with the doors painted standard RAL 7035, is supplied in an
assembly kit and can be fitted with internal lighting. Please
contact us for transformer boxes of different sizes.
Selection of the transformer box units
After having defined the type of transformer box unit
according to the total transformer losses, it is necessary to
check that the transformer box unit dimensions are sufficient
to ensure adequate insulation distances.
Unit description Sales code
TR1 1VCF594000R0086
TR2 1VCF594000R0087
TR3 1VCF594000R0088
TR4 1VCF594000R0089
TR5 1VCF594000R0090
JTI (TR) Switchgears
Contact us
1
V
C
P
0
0
0
2
4
9


R
e
v
.

L
,


e
n


T
e
c
h
n
i
c
a
l

c
a
t
a
l
o
g
u
e


2
0
1
1
.
0
6

(
U
n
i
M
i
x

J
T
I
)

(
m
t
)
The data and illustrations are not binding. We reserve
the right to make changes in the course of technical
development of the product.
Copyright 2011 ABB.
All rights reserved.
ABB S.p.A.
Power Products Division
Unit Operativa Sace-MV
Via Friuli, 4
I-24044 Dalmine
Tel: +39 035 6952 111
Fax: +39 035 6952 874
E-mail: info.mv@it.abb.com
www.abb.it