www.ElectaCourse.com
3
www.ElectaCourse.com
This presentation is suitable for those studying for the
City & Guilds 2391 and 2400 courses
4
www.ElectaCourse.com
The presentation includes guidance and
continuous self-assessment
5
www.ElectaCourse.com
In order to work through this presentation you will need copies
Of the following publications
BS 7671:2001 (16
th
Edition IEE Wiring Regulations)
Guidance Note 3 (Inspection and Testing
6
www.ElectaCourse.com
7
www.ElectaCourse.com
To ensure the safety of any electrical installation it should be
inspected, tested and the necessary certification completed:
Before being put into service (initial verification)
At regular intervals thereafter (Periodic Inspection Report)
On completion of any alteration or addition
8
www.ElectaCourse.com
9
www.ElectaCourse.com
For an initial verification
BS 7671:2002 states:
Installed equipment to an appropriate standard, i.e. BS, BS EN
Correctly selected and erected
Not visibly damaged or defective as to impair safety
10
www.ElectaCourse.com
11
www.ElectaCourse.com
The Periodic Installation Report (PIR)
BS 7671:2001 states:
Periodic inspection and testing of an electrical installation
shall be carried out to determine, so far as is reasonably
practicable, whether the installation is in a satisfactory condition
for continued service
12
www.ElectaCourse.com
Generally, the main reason for undertaking an inspection and
test is to ensure that the installation is safe to use
13
www.ElectaCourse.com
What Are the likely reasons for an installation failing to be safe?
Age
Wear and tear
Damage, i.e. fire, flooding etc
Electrical overload
DIY enthusiasts
Unscrupulous contractors
14
www.ElectaCourse.com
What factors would influence the need for a PIR
Expiry of current certificate
Change of ownership or use of the installation
As a result of damage or electrical overloading
Mortgage/insurance purposes
Compliance with current regulations
Local bylawrequirements
15
www.ElectaCourse.com
What factors would influence the safety of an installation?
Poorly installed equipment/accessories
Loose connections giving rise to shock and or fire
Inadequate overcurrent protection of equipment and circuits
Underrated/overloaded circuit conductors
Inadequate/non-existent earthing or bonding arrangements
16
www.ElectaCourse.com
17
www.ElectaCourse.com
Inspection always proceeds testing
Prior to visual inspection the supply to the installation or part
of the installation undergoing inspection should be
disconnected fromthe supply
18
www.ElectaCourse.com
Electrical installations which comply with BS 7671:2001 are
regarded by the Health & Safety Executive as likely to achieve
conformity with which statutory regulations?
19
www.ElectaCourse.com
The Electricity at Work Regulations 1989
20
www.ElectaCourse.com
Page 8
BS 7671:2001 Note by the Health and Safety Executive
21
www.ElectaCourse.com
Identify THREE areas which should be given consideration prior to
undertaking alterations or additions to an existing electrical
installation
22
www.ElectaCourse.com
The ability of existing equipment including that of the supplier is
adequate for the additional load
The earthing arrangements are adequate
The bonding arrangements are adequate
23
www.ElectaCourse.com
Page 14
130-07 Additions and alterations to an installation
Regulation 130-07-01
24
www.ElectaCourse.com
Identify SIX characteristics of the incoming electrical supply that
would need to be ascertained by the person undertaking an
inspection and test of an electrical installation
25
www.ElectaCourse.com
(i) the nominal voltage(s)
(ii) the nature of the current and frequency
(iii) the prospective short circuit current at the origin
(iv) the external earth fault loop impedance (Ze)
(v) the suitability for the requirements of the installation
including the maximumdemand
(vi) the type and rating of the overcurrent protective device
26
www.ElectaCourse.com
Page 33
313 Nature of Supply
Regulation 313-01-01
27
www.ElectaCourse.com
Identify two precautions that should be observed during
inspection and testing of an electrical installation
28
www.ElectaCourse.com
avoid danger to persons
avoid damage to property and installed equipment
29
www.ElectaCourse.com
Page 170
Chapter 71 - Initial Verification
Regulation 711-01-01
30
www.ElectaCourse.com
State the THREE requirements of BS 7671 with regard to installed
electrical equipment
31
www.ElectaCourse.com
(i) in compliance with Section 511
(ii) correctly selected and erected in accordance with the
Regulations
(iii) not visibly damaged or defective so as to impair safety
32
www.ElectaCourse.com
Page 170- Inspection
Regulation 712 - 01 - 02
Note: Section 511 deals with compliance with standards. All
equipment should comply with the appropriate British Standard or
Harmonized Standard- See page 84 - Selection and Erection of
Equipment
33
www.ElectaCourse.com
Identify TWO statutory, and FIVE non-statutory documents that an
inspecting engineer may need to refer when undertaking an
inspection and test on an electrical installation
34
www.ElectaCourse.com
Statutory:
Health and Safety at Work Act etc 1974
Electricity at Work Regulation 1989
Non-statutory:
BS 7671:2001
IEE Guidance Note 3 (Inspection and Testing
IEE On-Site Guide
GS 38 Equipment used by electricians (HSE Guidance)
Memorandumof Guidance to The Electricity at Work Regulations
35
www.ElectaCourse.com
36
www.ElectaCourse.com
Visual inspection always precedes testing
37
www.ElectaCourse.com
Fromthe inspection check list within BS 7671 Identify THREE
methods of protection against direct electric shock (contact)
38
www.ElectaCourse.com
Insulation of live parts
Barriers
Enclosures
39
www.ElectaCourse.com
Risk of direct contact. Barrier removed and not replaced
40
www.ElectaCourse.com
Risk of direct contact. Barrier removed and not replaced
41
www.ElectaCourse.com
Risk of direct contact.
42
www.ElectaCourse.com
Page 170
Regulation 712 - 01 - 03
Two additional methods of protection against direct shock of a
special nature are:
Placing out of reach
Obstacles Note: this method of protection is intended to prevent
inadvertent contact with live parts and therefore areas
incorporating this type of protection should only be accessible to
skilled persons only
43
www.ElectaCourse.com
Fromthe inspection check list within BS 7671 Identify THREE
methods of protection against indirect contact
44
www.ElectaCourse.com
EEBAD
Class II
Electrical Separation
Non-conducting location
Earth-free local equipotential bonding
45
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
Note: Protection by non-conducting location and earth-free local
equipotential bonding are both of a special nature and very rarely
encountered
46
www.ElectaCourse.com
Fromthe inspection check list within BS 7671 Identify TWO methods
of protection against both direct and indirect contact
47
www.ElectaCourse.com
Separated extra-lowvoltage (SELV)
Limitation of discharge energy
48
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
49
www.ElectaCourse.com
Fromthe inspection check list within BS 7671 Identify FOUR types of
protective conductor
50
www.ElectaCourse.com
earthing conductor
circuit protective conductor (CPC)
main equipotential bonding conductor
supplementary equipotential bonding conductor
51
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
52
www.ElectaCourse.com
Presence of main equipotential bonding conductors
53
www.ElectaCourse.com
One requirement fromRegulation 712-01-03 is the selection of
equipment and protective measures appropriate to external
influences. List the external influences likely to be encountered by
an electrical installation located within a commercial greenhouse
accessible to the general public.
54
www.ElectaCourse.com
Ultra-violet radiation
Extremes of temperature
Mechanical damage
Water/moisture/humidity
Rodent attack
Chemicals
Corrosion
Vandalism
55
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
56
www.ElectaCourse.com
Regulation 712- 01 - 03 requires visual inspection to ensure
cables are routed in safe zones and also considers erection
methods.
Here are some examples of non-compliance
57
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
2
-
0
8
Routing of cables
58
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
s
5
2
2
-
0
8
Routing of cables
59
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
2
-
0
8
Routing of cables
60
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
s
5
2
2
-
0
8
Routing of cables
61
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
s
5
2
2
-
0
8
Routing of cables
62
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
s
5
2
2
-
0
8
Routing of cables
63
www.ElectaCourse.com
Selection of conductors for current carrying capacity
Identification of conductors
Selection of conductors for voltage drop
Requirements for circuit conductors
64
www.ElectaCourse.com
Regulation 712- 01 - 03 requires visual inspection to ensure
cables are correctly and adequately identified
Here are some examples of non-compliance
65
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
1
4
-
0
1
-
0
1
/
0
2
Identification of conductors
66
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
1
4
-
0
1
-
0
1
/
0
2
Identification of conductors
67
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
1
4
-
0
1
-
0
1
/
0
2
Identification of conductors
68
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
1
4
-
0
1
-
0
1
/
0
2
Identification of conductors
69
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
1
4
-
0
1
-
0
1
/
0
2
Identification of conductors
70
www.ElectaCourse.com
Electrical connections
Regulation 526-01-1
Every connection between conductors to provide durable
electrical connection and mechanical strength
71
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
6
-
0
1
-
0
1
Connection between conductors
72
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
6
-
0
1
-
0
1
Taped joint between PVC and VRI cables
73
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
6
-
0
1
-
0
1
Taped joint between PVC and VRI cables
74
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
6
-
0
1
-
0
1
Faulty conductor termination
75
www.ElectaCourse.com
Result of insecure/loose connection
76
www.ElectaCourse.com
Result of insecure/loose connection
77
www.ElectaCourse.com
The Regulations require that connections and joint be accessible
for inspection, testing and maintenance. There are however FOUR
situations where this regulation does not apply. Identify these
FOUR situations.
78
www.ElectaCourse.com
Page 100
Regulation 526-04-01
(i) A compound-filled or encapsulated joint
(ii) A connection between a cold tail and a heating element
(iii) A joint made by welding, soldering, brazing or compression
tool
(iv) A joint forming part of the equipment complying with the
appropriate product standard
79
www.ElectaCourse.com
Page 100
Regulation 526-04-01
80
www.ElectaCourse.com
Erection of wiring systems
81
www.ElectaCourse.com
Lid/covers not fitted
82
www.ElectaCourse.com
R
e
g
u
l
a
t
i
o
n
5
2
2

0
8
Lid/covers not fitted
83
www.ElectaCourse.com
Lid/covers not fitted
84
www.ElectaCourse.com
Enclosure door not secured
85
www.ElectaCourse.com
Equipment door forced open to defeat interlock
86
www.ElectaCourse.com
Enclosure not secured to wall
87
www.ElectaCourse.com
I
n
t
e
r
n
a
t
i
o
n
a
l
P
r
o
t
e
c
t
i
o
n
88
www.ElectaCourse.com
Enclosure not secured to wall
I
n
t
e
r
n
a
t
i
o
n
a
l
P
r
o
t
e
c
t
i
o
n
89
www.ElectaCourse.com
A visual inspection is to be carried out on a domestic installation.
Detail FIVE specific areas of visual inspection at the origin of this
installation.
For the purpose of this exercise the PES supply has been isolated
by the removal of the service head fuse.
90
www.ElectaCourse.com
Presence and size of earthing conductor
Presence and size of main equipotential bonding conductors
Type and rating of overcurrent protective devices
Prospective breaking capacity of overcurrent devices
Circuit and conductor identification
Type of earthing arrangement
IP rating of distribution board
91
www.ElectaCourse.com
A miniature circuit breaker within the distribution board is marked
as a Type 2, M6 device.
Describe the characteristics of this device and state to which
Standard it complies.
92
www.ElectaCourse.com
As the device carries an M rating its has been manufactured to
BS 3871 (nowreplaced by BS EN 60898 device)
Mindicates its maximumprospective fault current value M6 = 6kA
6000A.
Type 2 indicates the instantaneous tripping characteristic
4.0 7.0 In.
93
www.ElectaCourse.com
Page 60 Guidance Note 3
Table 4.2 Rated short-circuit capacities
94
www.ElectaCourse.com
State TWO functional tests that may be applied at the distribution
board
95
www.ElectaCourse.com
Operation of circuit breakers
Operation of the main switch
96
www.ElectaCourse.com
State the hand lighting would you use if working in a confined
damp location?
97
www.ElectaCourse.com
Hand lighting provided froman SELV (Separated Extra-LowVoltage)
supply
98
www.ElectaCourse.com
Separated Extra-LowVoltage (SELV)
Supplied froma recognised safety source - Regulation
ELV conductors NOT referenced to earth - Regulation
Within voltage constraints - Regulation
99
www.ElectaCourse.com
The following information relates to a circuit breaker complying
with BS EN 60898.
Type B
Icn 10
Ics 7.5
State the meaning of each of the above terms
100
www.ElectaCourse.com
Type B relates to the instantaneous tripping characteristic of
the device. In this case 3 - 5 In (where In is the rating of the
device in amperes
Icn - the rated short-circuit capacity (indicted on the device)
Ics the service short-circuit capacity.
101
www.ElectaCourse.com
Page 60 Guidance Note 3
Table 4.2 Rated short-circuit capacities
102
www.ElectaCourse.com
State TWO characteristics of the incoming supply that may be
determined by enquiry or measurement
103
www.ElectaCourse.com
Prospective fault current
External earth fault loop impedance
104
www.ElectaCourse.com
Page 33
313 Nature of supply
Regulation 313-01-01
Any of the following characteristics may be obtained by
measurement or enquiry:
Nominal voltage, nature of current and frequency. Generally
however the two most common characteristics determined by
enquiry and calculation are Ze (external earth fault loop
impedance) and prospective fault current Ip.
105
www.ElectaCourse.com
Regulation 313-01-01 requires that the supply characteristics from
whatever source be verified. Give TWO examples of sources other
than that of the PES supply that may supply an installation
106
www.ElectaCourse.com
Those of:
standby generators (alternators
Uninterruptible Power Supplies (UPS)
107
www.ElectaCourse.com
108
www.ElectaCourse.com
An RCD protected A
2
radial circuit feeds five 13A socket outlets to
BS 1363. The circuit has been added to an existing installation
within domestic premises.
identify the relevant document that should be completed for this
installation
The sequence of tests, in the correct order that should be
applied to this circuit
If the supply to the installation is TN-S state the main purpose of
the RCD
In the correct sequence identify the tests that should be applied
to the RCD
109
www.ElectaCourse.com
Minor Works Certificate
Continuity of CPCs
Provide supplementary protection against direct contact
x I n
1 x I n
5 x I n
110
www.ElectaCourse.com
Page 29 GN 3
2.7.4 The sequence of tests
Page 171
Regulation 713-01-01 (sequence of tests)
111
www.ElectaCourse.com
State the action you would take if ONE of the tests undertaken in
question 22 indicated a defect
112
www.ElectaCourse.com
Determine whether fault would have any adverse effect on any
previous tests result
When rectified repeat any tests that may have been adversely
affected
113
www.ElectaCourse.com
Explain why applying a functional test only, to a residual current
device is unacceptable during a periodic inspection (PIR)
Howoften should an RCD undergo functional testing
114
www.ElectaCourse.com
Functional testing relies upon an imbalance between phase and
neutral within thetoroidal winding of the device. It does not verify:
the presence of earthing conductor
the presence of any CPCs
the presence of any earthing arrangements
does not verify operating time or current
Functional testing applied at three month intervals
115
www.ElectaCourse.com
Page 61 GN
32.7.16 Operation of residual current devices
Page 173
Regulation 713-13-01 Functional testing
116
www.ElectaCourse.com
Explain why an insulation resistance test instrument is required to
produce a current of 1 mA when loaded at the minimumacceptable
value of insulation as permitted by BS 7671?
117
www.ElectaCourse.com
Effect of instrument loading on output (terminal) voltage
0.5M 1.0M 10M
Terminal voltage
500V d.c.
Insulation resistance M
Minimumacceptable value for 230/400V circuits
118
www.ElectaCourse.com
Page 86 GN
4.4 Insulation resistance testers
Page 172
Regulation 713-04-03
An effective test for insulation can only be made if the output
voltage is maintained by the instrument
119
www.ElectaCourse.com
Explain the possible danger of removing test probes froma circuit
under test before releasing the test button of an insulation
resistance tester
120
www.ElectaCourse.com
Capacitance of the circuit's under test may be as high as 5F.
When releasing the test button the instrument automatically
discharges the circuit under test. Failure to employ this discharge
circuit may lead to electric shock fromcapacitive charge.
121
www.ElectaCourse.com
Page 86 GN
4.4 Insulation resistance testers
122
www.ElectaCourse.com
Explain the termstanding voltage and the electrical test that may
give rise to this situation
Describe TWO methods of reducing the risk of shock fromthese
standing voltages
123
www.ElectaCourse.com
Restrict duration of instrument test currents
Place warning notices in location of test area
124
www.ElectaCourse.com
Page 86 GN
4.6 Earth fault loop impedance testers
Restrict test currents to 40mS
125
www.ElectaCourse.com
Where impedance tests are undertaken on circuits of rating up to
50A, the instrument used should have a resolution and accuracy
of?
126
www.ElectaCourse.com
resolution of 0.01 ohm
accuracy of around 0.2 ohm
127
www.ElectaCourse.com
Page 86 GN
4.6 Earth fault loop impedance testers
Instruments to BS EN 61557-3 will comply with the requirements of
BS 7671 with regard to impedance testers
128
www.ElectaCourse.com
129
www.ElectaCourse.com
State the requirements of the Electricity @Work Regulations 1989
with regard to access and lighting whilst undertaking a visual
inspection of the distribution board.
130
www.ElectaCourse.com
Working space
Adequate to allowto pull back away fromlive conductors
without hazard
Adequate to allowpersons to pass one another safely
Lighting
Natural light preferred. Where this is impractical permanent
lighting arrangements of an acceptable design should be
provided. At times, lighting may need to be temporary, i.e.
torches or hand lamps. Whichever method is employed the level
of lighting must be adequate to avoid injury
131
www.ElectaCourse.com
Page 38
Regulation 15 Working space, access and lighting
132
www.ElectaCourse.com
Means of escape in the event of an emergency
133
www.ElectaCourse.com
Means of escape blocked in the event of an emergency
134
www.ElectaCourse.com
Safe access and exit fromworkplace?
135
www.ElectaCourse.com
A safe and tidy workplace!