A thorough understanding of the D3 manual as well as a working knowledge of Microsoft Excel are prerequisites for using this spreadsheet. This spreadsheet uses revised versions of the printed D3 worksheets. Use the printed D3 manual for guidance to enter information into the Effective Length, Friction Rate and Duct Sizing tabs. Microsoft Excel version 97 is the minimum requirement to use the spreadsheet but Microsoft Excel version 2000 or greater is recommended to utilize the full features of the spreadsheet. We strongly suggest that you print out and read the instructions on using this electronic spreadsheet that are contained in the following Help tab. This spreadsheet can be downloaded from the ACCA System Design website. Please visit the website often to check for updates to the spreadsheet. The most recent version number is listed on Notes tab. ACCA System Design ACCA Manual D, 3rd Edition *** Refer to the Notes Tab to verify the latest revision *** Help Section Refer to Manual D Residential Duct Systems, Third Edition Version 1.xx Step 1: Go to the Effective Length Tab and enter up to 4 supply runs to determine the longest equivilent run in the system. Enter the linear feet of trunk and runout ducts in the length sections for the supply ducts. Click on the Group Code and find the equivilent feet for all fittings used in the selected supply runs. The program will automatically select the "Total Equivilent Feet" to be used in the Friction Rate Tab. Repeat the steps above for the return ducts. Step 2: Go to the Friction Rate Tab and enter the "External Static Pressure" and "CFM" for the selected equipment. Next enter "Component Pressure Losses" for all components and accesories external of the fan unit. The program will automatically calculate the "Design Friction Rate" value to be used for Duct Sizing. Step 2: Go to the Duct Sizing 1 Tab and enter the heating and cooling BTUH for each supply run. There is a maximum of 14 supply runs per unit. For larger rooms divide the BTUH by the number of runs required for proper distribution of airflow. The program will automatically select the duct size for round metal ductwork. For rectangular metal ductwork enter the height and the program will automatically select the duct size. If Flex Duct is used refer to the Equivilent Flex column to select the correct duct size. Under the supply truck section, select the associated supply runs for this supply trunk section and the CFM will automatically calculate. The program will automatically select the duct size for round metal ductwork. For rectangular metal ductwork enter the height and the program will automatically select the duct size. If Flex Duct is used refer to the Equivilent Flex column to select the correct duct size. If more than four (4) supply trunk sections are required select the Duct Sizing 2 Tab. Repeat the steps above for the return ducts. Air Conditioning Contractors of America, Manual D, Third Edirtion Element Length Length Length Length Trunk Length Trunk Length Trunk Length Runout Length Group Effective Group Effective Group Effective Group Effective Letter Length Letter Length Letter Length Letter Length Group 1 A 12 A 11 Group 2 Group 3 Group 4 Group 8 Group 9 Group 11 Group 12 Other Other Other Total Length 12 11 0 0 Design TEL Element Length Length Length Length Trunk Length Trunk Length Trunk Length Runout Length Group Effective Group Effective Group Effective Group Effective Letter Length Letter Length Letter Length Letter Length Group 5 Group 6 Group 7 Group 8 Group 10 Group 11 Group 12 Other Other Total Length 0 0 0 0 Design TEL 12 0 Straight Run Fittings Effective Length Worksheet Supply Run ID Number Return Run ID Number Fittings Straight Run Air Conditioning Contractors of America, Manual D, Third Edition IWC Error IWC #VALUE! IWC 12 Feet #VALUE! IWC/100 Step 2) Component Pressure Losses (CPL) Direct expansion refrigerant coil Electric resistance heating coil Hot water coil Step 3) Available Static Pressure (ASP) Step 4) Total Effective Length (TEL) Step 5) Friction Rate Design Value (FR) Total component losses (CPL) Friction Rate Worksheet External static pressure (ESP) Return grille heat exchanger CFM Step 1) Manufacturer's Blower Data UV lights or other device Low efficiency filter High or mid-efficiency filter Electronic filter Humidfier Balancing damper Supply outlet Air Conditioning Contractors of America, Manual D, Third Edition Equivilent ID Dsn Cfm Round Size Velocity Final Size Height Width Flex SR-1 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-2 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-3 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-4 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-5 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-6 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-7 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-8 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-9 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-10 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-11 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-12 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-13 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! SR-14 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! Equivilent ID 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ST-1 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! ST-2 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! ST-3 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! ST-4 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! Equivilent ID Dsn Cfm Round Size Velocity Final Size Height Width Flex RR-1 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-2 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-3 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-4 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-5 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-6 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-7 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-8 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-9 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-10 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-11 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-12 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-13 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RR-14 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! Return-side Trunks Equivilent ID Dsn Cfm Round Size Velocity Final Size Height Width Flex RT-1 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RT-2 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RT-3 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! RT-4 #VALUE! #VALUE! #VALUE! 8 #VALUE! #VALUE! Duct Sizing Worksheet 1 Supply-side Runouts 11 1234 C-Btuh 456 H-Btuh Room ID Velocity Associated Supply Runs Associated Supply Runs 1234 Associated Supply Runs Supply-side Trunks Return-side Runouts Dsn Cfm Round Size Equivilent Rect. Duct Equivilent Rect. Duct Final Size Height Width 456 Equivilent Rect. Duct Equivilent Rect. Duct Flex ID Dsn Cfm Round Size Velocity Final Size SR-1 #VALUE! #VALUE! #VALUE! SR-2 #VALUE! #VALUE! #VALUE! SR-3 #VALUE! #VALUE! #VALUE! SR-4 #VALUE! #VALUE! #VALUE! SR-5 #VALUE! #VALUE! #VALUE! SR-6 #VALUE! #VALUE! #VALUE! SR-7 #VALUE! #VALUE! #VALUE! SR-8 #VALUE! #VALUE! #VALUE! SR-9 #VALUE! #VALUE! #VALUE! SR-10 #VALUE! #VALUE! #VALUE! SR-11 #VALUE! #VALUE! #VALUE! SR-12 #VALUE! #VALUE! #VALUE! SR-13 #VALUE! #VALUE! #VALUE! SR-14 #VALUE! #VALUE! #VALUE! ID 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ST-5 #VALUE! #VALUE! #VALUE! ST-6 #VALUE! #VALUE! #VALUE! ST-7 #VALUE! #VALUE! #VALUE! ST-8 #VALUE! #VALUE! #VALUE! ID Dsn Cfm Round Size Velocity Final Size RR-1 #VALUE! #VALUE! #VALUE! RR-2 #VALUE! #VALUE! #VALUE! RR-3 #VALUE! #VALUE! #VALUE! RR-4 #VALUE! #VALUE! #VALUE! RR-5 #VALUE! #VALUE! #VALUE! RR-6 #VALUE! #VALUE! #VALUE! RR-7 #VALUE! #VALUE! #VALUE! RR-8 #VALUE! #VALUE! #VALUE! RR-9 #VALUE! #VALUE! #VALUE! RR-10 #VALUE! #VALUE! #VALUE! RR-11 #VALUE! #VALUE! #VALUE! RR-12 #VALUE! #VALUE! #VALUE! RR-13 #VALUE! #VALUE! #VALUE! RR-14 #VALUE! #VALUE! #VALUE! Return-side Trunks ID Dsn Cfm Round Size Velocity Final Size RT-5 #VALUE! #VALUE! #VALUE! RT-6 #VALUE! #VALUE! #VALUE! RT-7 #VALUE! #VALUE! #VALUE! RT-8 #VALUE! #VALUE! #VALUE! Room ID H-Btuh C-Btuh Duct Sizing Worksheet 2 Supply-side Runouts 11 1234 456 1234 456 Supply-side Trunks Associated Supply Runs Dsn Cfm Round Size Velocity Final Size Associated Supply Runs Return-side Runouts Associated Supply Runs Equivilent Height Width Flex 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! Equivilent 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! Equivilent Height Width Flex 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! Equivilent Height Width Flex 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! 8 #VALUE! #VALUE! Duct Sizing Worksheet 2 Equivilent Rect. Duct Equivilent Rect. Duct Height Width Equivilent Rect. Duct Flex Equivilent Rect. Duct Return Return Return Return Return Return Return Return Return Return Return Return Return Release Notes: Version MD3 1.00 01SEP09 Initial Release