You are on page 1of 4

08/06/13 7:46 PM

Page 1 of 4 http://www.tlc-direct.co.uk/Book/4.3.11.htm






chapter 1
The IEE
Regulations
chapter 2
Installation
Requirements
and
Characteristics
chapter 3
Installation
Control
and Protection
chapter 4
Cables,
Conduits
and Trunking
chapter 5
Earthing
chapter 6
Circuits
chapter 7
Special
Installations
chapter 8
Testing
and
Inspection
chapter 9
Data cabling
and Networks
Contents
Cables, conduits and trunking
4.1 - Cable insulation materials 4.4 - Cable supports, joints and terminations
4.2 - Cables 4.5 - Cable enclosures
4.3 - Cable choice 4.6 - Conductor and cable identification
------------------------------------------------------------------
4.3.1 - Cable types 4.3.8 - Protection by semi-enclosed (rewirable) fuses
4.3.2 - Current carrying capacity of conductors 4.3.9 - Cable rating calculation
4.3.3 - Methods of cable installation 4.3.10 - Special formulas - grouping factor calculation
4.3.4 - Ambient temperature correction factors 4.3.11 - Cable volt drop
4.3.5 - Cable grouping correction factors 4.3.12 - Harmonic currents and neutral conductors
4.3.6 - Thermal insulation correction factors 4.3.13 - Low smoke-emitting cables
4.3.7 - When a number of correction
--------- factors applies
4.3.14 - The effects of animals, insects and plants
4.3.11 - Cable volt drop
All cables have resistance, and when current flows in them this results in a volt drop. Hence, the voltage
at the load is lower than the supply voltage by the amount of this volt drop.
The volt drop may be calculated using the basic
Ohm's law formula
U = I x R
where U is the cable volt drop (V
I is the circuit current (A), and
R is the circuit resistance W(Ohms)
Unfortunately, this simple formula is seldom of use in this case, because the cable resistance under load
conditions is not easy to calculate.
[525-01-03] indicates that the voltage at any load must never fall so low as to impair the safe working of
that load, or fall below the level indicated by the relevant British Standard where one applies.
[525-01-02] indicates that these requirements will he met if the voltage drop does not exceed 4% of the
declared supply voltage. If the supply is single-phase at the usual level of 240 V, this means a maximum
volt drop of 4% of 240 V which is 9.6 V, giving (in simple terms) a load voltage as low as 230.4 V. For a
415 V three-phase system, allowable volt drop will be 16.6 V with a line load voltage as low as 398.4 V.
It should be borne in mind that European Agreement RD 472 S2 allows the declared supply voltage of
230 V to vary by +10% or -6%. Assuming that the supply voltage of 240 V is 6% low, and allowing a 4%
volt drop, this gives permissible load voltages of 216.6 V for a single-phase supply, or 374.5 V (line) for a
415 V three-phase supply.
To calculate the volt drop for a particular cable we use {Tables 4.6, 4.7 and 4.9}. Each current rating
table has an associated volt drop column or table. For example, multicore sheathed non-armoured
P.V.C. insulated cables are covered by {Table 4.7} for current ratings, and volt drops. The exception in
the Regulations to this layout is for mineral insulated cables where there are separate volt drop tables for
single- and three-phase operation, which are combined here as {Table 4.9}.
to the 16th Edition IEE Regulations
08/06/13 7:46 PM
Page 2 of 4 http://www.tlc-direct.co.uk/Book/4.3.11.htm
Each cable rating in the Tables of [Appendix 4] has a corresponding volt drop figure in millivolts per
ampere per metre of run (mV/A/m). Strictly this should be mV/(A m), but here we shall follow the pattern
adopted by BS 7671: 1992. To calculate the cable volt drop:
1. - take the value from the volt drop table (mV/A/m)
2. - multiply by the actual current in the cable (NOT the current rating)
3. - multiply by the length of run in metres
4. - divide the result by one thousand (to convert millivolts to volts).
For example, if a 4 mm! p.v.c. sheathed circuit feeds a 6 kW shower and has a length of run of 16 m, we
can find the volt drop thus:
From {Table 4.7}, the volt drop figure for 4 mm! two-core cable is 11 mV/A/m.
Cable current is calculated from I = P = 6000 A = 25 A
U 240-----
Volt drop is then 11 x 25 x 16 V = 4.4 V
1000
Since the permissible volt drop is 4% of 240 V, which is 9.6 V, the cable in question meets volt drop
requirements. The following examples will make the method clear.
Example 4.5
Calculate the volt drop for the case of Example 4.1. What maximum length of cable would allow the
installation to comply with the volt drop regulations?
The table concerned here is {4.7}, which shows a figure of 7.3 mV/A/m for 6 mm! twin with protective
conductor pvc insulated and sheathed cable. The actual circuit current is 12.5 A, and the length of run is
14 m.
Volt drop = 7.3 x 12.5 x 14 V = 1.28 V
1000
Maximum permissible volt drop is 4% of 240 V = 4 of 240 V = 9.6 V
100
If a 14 m run gives a volt drop of 1.28 V,
the length of run for a 9.6 V drop will be:
9.6 x 14m = 105m
1.28
Example 4.6
Calculate the volt drop for the case of {Example 4.2}. What maximum length of cable would allow the
installation to comply with the volt drop regulations?
The Table concerned here is {4.7} which shows a volt drop figure for 4.0 mm! cable of 11mV/A/m, with
the current and the length of run remaining at 12.5 A. and 14 m respectively.
Volt drop = 11 x 12.5 x 14 V = 1.93 V
1000
Maximum permissible volt drop is 4% of 240 V = 4 of 240 V = 9.6 V
100
If a 14 m run gives a volt drop of 1.93 V, 9.6 x 14m = 70m

08/06/13 7:46 PM
Page 3 of 4 http://www.tlc-direct.co.uk/Book/4.3.11.htm
If a 14 m run gives a volt drop of 1.93 V,
the length of run for a 9.6 V drop will be:
9.6 x 14m = 70m
1.93
Example 4.7
Calculate the volt drop for the cases of {Example 4.3} for each of the alternative installations. What
maximum length of cable would allow the installation to comply with the volt drop regulations in each
case?
In neither case is there any change in cable sizes, the selected cables being 6 mm! in the first case and
4 mm! in the second. Solutions are thus the same as those in {Examples 4.5 and 4.6} respectively.
Example 4.8
Calculate the volt drop and maximum length of run for the motor circuit of {Example 4.4}.
This time we have a mineral insulated p.v.c. sheathed cable, so volt drop figures will come from {Table
4.9}. This shows 9.1 mV/A/m for the 4 mm! cable selected, which must be used with the circuit current of
15.3 A and the length of run which is 20 m.
Volt drop = 9.1 x 15.3 x 20 V = 2.78 V
1000
Maximum permissible volt drop is 4% of 415 V = 4 of 415V = 16.6 V
100
Maximum length of run for this circuit
with the same cable size and type will be:
16.6 x 20m = 119m
2.78
The 'length of run' calculations carried out in these examples are often useful to the electrician when
installing equipment at greater distances from the mains position.
It is important to appreciate that the allowable volt drop of 4% of the supply voltage applies to the whole
of an installation. If an installation has mains, sub-mains and final circuits, for instance, the volt drop in
each must be calculated and added to give the total volt drop as indicated in {Fig 4.10}.
All of our work in this sub-section so far has assumed that cable resistance is the only factor responsible
for volt drop. In fact, larger cables have significant self inductance as well as resistance. As we shall see
in Chapter 5 there is also an effect called impedance which is made up of resistance and inductive
reactance (see {Fig 5.8(a)}).
Inductive reactance XL = 2(pi)fL
where XL = inductive reactance in Wohms
(pi) = the mathematical constant 3.142
f = the system frequency in hertz (Hz)
L = circuit self inductance in henrys (H)
It is clear that inductive reactance increases with frequency, and for this reason the volt drop tables apply
only to systems with a frequency lying between 49 Hz and 61 Hz.
08/06/13 7:46 PM
Page 4 of 4 http://www.tlc-direct.co.uk/Book/4.3.11.htm
Fig 4.10 Total volt drop in large installations
For small cables, the self inductance is such that the inductive reactance, is small compared with the
resistance. Only with cables of cross-sectional area 25 mm! and greater need reactance be considered.
Since cables as large as this are seldom used on work which has not been designed by a qualified
engineer, the subject of reactive volt drop component will not be further considered here.
If the actual current carried by the cable (the design current) is less than the rated value, the cable will
not become as warm as the calculations used to produce the volt drop tables have assumed, The
Regulations include (in [Appendix 4]) a very complicated formula to be applied to cables of cross-
sectional area 16 mm! and less which may show that the actual volt drop is less than that obtained from
the tables. This possibility is again seldom of interest to the electrician, and is not considered here.


Return to top of page
Extracted from The Electricians Guide Fifth Edition
by John Whitfield