GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.

12
Seal & sign of Bidder Page 1 of 71




GUJARAT ENERGY TRANSMISSION
CORPORATION LTD.
SARADAR PATEL VIDYUT BHAVAN,
RACE COURSE, BARODA 390 007.




TECHNICAL SPECIFICATIONS

FOR

66kV CONTROL & RELAY PANELS







GETCO / E / TS- CRP 3600 / R4 Dt.22.08.12
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 2 of 71
SPECIAL INSTRUCTIONS TO BIDDER


Please read following instructions carefully before submitting your bid.


1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in
AutoCAD format and manuals in PDF format, for offered item shall be
submitted. Also the hard copies as per specification shall be submitted.

2. The bidder shall submit Quality Assurance Plan with the technical bid.

3. The bidder shall have to submit all the required type test reports for the offered
item. Bid without type tests will be evaluated accordingly.

4. The bidder must fill up all the points of GTP for offered item/s. Instead of
indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in.

5. All the points other than GTP, which are asked to confirm in technical
specifications must be submitted separately with the bid.

6. The bidder is required to impart training in view of manufacture, assembly,
erection, operation and maintenance for offered item, at his works, to the
person/s identified by GETCO, in the event of an order, free of cost. The cost of
logistics will be bear by GETCO.

7. Please note that the evaluation will be carried out on the strength of content of
bid only. No further correspondence will be made.

8. The bidder shall bring out all the technical deviation/s only at the specified
annexure.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 3 of 71
QUALIFYING REQUIREMENT DATA

QUALIFYING REQUIREMENT FOR BIDDERS FOR CONTROL & RELAY PANEL
and RELAYS
1. The bidder shall be original equipment manufacturer (OEM). The offered Relay /
C&R Panels have to be designed manufactured and tested as per relevant IS/IEC
with latest amendments.

1.A Bidders not meeting the requirements at 1 above but authorized by OEM having
qualifying requirement as per 1 above can also participate, provided they have
valid ongoing collaboration with manufacturer. In such an event the bidder shall
furnish, along with his bid, documentary evidence for the same and an undertaking
from the bidder and collaborator accepting joint and several liabilities of all the
obligations under the contract.

2. The minimum requirement of manufacturing capacity of offered type, size and
rating of Relays / C&R panels shall be as per Annexure-A. The bidder should
indicate manufacturing capacity by submitting latest updated certificate of a
Chartered Engineer (CE).

3. Relay / C&R panel offered shall be of similar or higher rating and in service for a
minimum period of THREE (3) years and satisfactory performance certificate from
utilities like SEBs, NTPC, PGCIL etc. in respect of this should be submitted.

4. The bidder should clearly indicate the quantity and single value contract executed
during last five (5) years for the offered product. Bidder should have executed one
single contract during last five years for the quantity equivalent to tender / bid. The
details should be submitted as per following format.

Sr.
No.
ITEMS
SUPPLIED
TO
ORDER
REFERENCE
NO. & DATE
ITEMS QUANTITY ORDER
FULLY
EXECUTED
YES/NO
STATUS
IF ORDER
UNDER
EXECUTION
REMARKS

5. Relay / C&R panel offered shall have type test certificates from accredited
laboratory (accredition based on ISO/IEC/Guide 25/17025 or EN 45001 by the
national accredition body of the country where the lab is located.) as per
IS/IEC/Technical specification, not older than FIVE (5) years and valid till expiry of
the offer.

6. The bidder shall guarantee for supplying maintenance spares and services as well
as repairing of relays for a period of the life expectancy of 25 years (for Relays
10 Years).





GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 4 of 71



ANNEXURE - A

Sr.
No.
Product Annual manufacturing capacity
(In multiple of tender / bid quantity)
1 Relays 5
2 C&R Panels 5








































GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 5 of 71


TECHNICAL SPECIFICATIONS
FOR 66 KV CONTROL AND RELAY PANELS

SECTION I
GENERAL TECHNICAL REQUIREMENTS
FOR 66 KV CONTROL AND RELAY PANELS:

1.1 SCOPE :

1.1.1 This specification covers the manufacture, assembly, testing at manufacturer's
works, supply and delivery of control and relay panels complete with wiring,
meters, relays, control switches and other miscellaneous equipments specified
herein-after, in this Specification.

1.2 STANDARDS :

1.2.1 The 66KV control & relay panel and materials covered by this Specification
shall comply with the requirements of the latest edition of the following
standards as amended up to date except where specified otherwise in the
specifications.

01. A.C. Electricity meter : IS: 722 (Part I & IV) (Latest edition)
02. Indicating instruments : IS: 1248 (Latest edition)
03. Recording instruments : IS: 6236 (Latest edition)
04. Protective relays : IS: 3231 & IEC 60255 (Latest edition)

1.2.2 However, in the event of offered 66KV control & relay panels, confirming to
standard other than above Standards, the salient points of differences between
the standards adopted and the specified standards shall be stated in the offer.

1.3 DRAWINGS :

1.3.1 Bidder shall submit following drawings, with the offer for preliminary scrutiny.

i) Principal dimensional details of each control and relay panel.
ii) Front and rear views of the panels with instrument, devices and relay
positions marked.
iii) Details of protection schemes for lines, transformers etc. and
annunciation system offered with its leaflet.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 6 of 71

1.3.2 The successful bidders shall furnish the following drawings for approval to the
purchaser, within twenty days of receipt of order.
a) General arrangement drawings of control and relay panels, showing all
parts / items mounted on them with height of each along with complete
panel wise list of equipment and list of nameplates.
b) Schematic internal wiring diagram of each panel, showing termination of
external wiring.
c) Schematic drawing shall follow TB Nos. as under.
1 CT Circuits,
2 PT Circuits,
3 Aux. AC & DC supply
4 Control Circuits,
5 Indication Circuits,
6 Annunciation Circuits,
7 RTU / Spare,
B Bus wires
M - Energy meter RS485 communication wires
d) Details of all switches.
e) Outline drawings and internal wiring diagrams of all instruments, relays
and other parts / items.
f) Outline drawings, mounting details, internal wiring diagram and item
wise bill of material for all devices not located in bidders panels, but
supplied by him with the panels.
g) Complete three-phase diagram (A.C. Schematic), covering all elements
controlled from the control panels. They shall show all A.C. Power
connections, and secondary connections for relays, meters etc. with
vector representation.
h) Complete schematic control diagrams of all parts / items controlled from
the panels, including synchronizing circuits, if required. These diagrams
shall show complete internal circuits of the controlled parts / items and
clearly indicate the terminal markings for extra connections.
i) Complete schematic drawing for annunciation system with various
purposes for which it is suitable.
j) Foundation drawings including Cable Cutouts and floor plans of control
and relay panels.
k) Locations of cable slot for Bus wires and weights shall also be given on
these drawings.

1.3.3 They may submit any other drawing found necessary in addition to the
drawings stated above.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 7 of 71
1.3.4 The sequence of drawing sheets shall be as follows.
1. Title Sheet
2. Brief Product specifications
3. GA drawings Front view , Rear View, Side View, Internal views,
Foundation Drawing including Cable Cutouts
4. Bill Of Materials
5. Station Single Line Diagram (if applicable)
6. Single line Diagram
7. Protection Single Line Diagram
8. AC & DC distribution
9. Metering Circuit
10. Main Protection Relay Circuit
11. Back up Protection Relay circuit
12. Circuit Breaker Closing & Tripping circuit
13. Indication Circuit
14. Annunciation Circuit
15. TB details
16. Wiring Table ( with as built drawings only)

1.4 DETAILED DESCRIPTION :

1.4.1 Construction of panel and detailed description :

1.4.1.1 The control and relay panel shall be of simplex type and comprise of one
vertical stationary front panel, provided with single door (fitted and lockable with
latches at three points) on the rear.

1.4.1.2 The control relay panels shall be fabricated out of structure leveled, finished
sheet steel of minimum thickness 3mm for front side and 2.5mm for all other
sides and necessary stiffening members. They shall form rigid, unyielding
freestanding, completely assembled enclosures, neat in appearance. All
structural members shall be bolted or welded together. All joints shall be made
flush and all edges shall be bent at right angles and rounded. Necessary
arrangements shall be made for bolting the adjacent panels together as well as
for fastening them to the floor. Suitable vibration absorption devices and kick-
plates along the base shall be bent at right angles and rounded. The opening
required for mounting the parts / items shall be punched or cut and filed
smooth.

Panel shall be painted first with antirusting paint and then by two coats of
synthetic enamel grey paint of shade 631 of IS: 5 for exterior and white for
interior respectively.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 8 of 71

1.4.1.3 Dimensions :
The dimension of the panels shall be as nearer as those stated below.
Height - 2312mm including M.S. frame of 50 x 50 x 4mm
size for base.
Depth - 610mm
Width - 610 mm

1.4.1.4 Controls, relays and instruments shall be mounted on the front of the panel and
not on any moving parts of panel. The panels shall be vermin proof and
suitable for IP54 protection. They will be suitable for tropical climate. The
panels shall be supplied complete with wiring, through wiring supports, interior
lighting device, wiring, terminal blocks, space heaters, channels, base
grounding M.S. bolts, nuts, washers etc.

1.4.2 Mimic Diagram and Symbols:
Coloured mimic diagrams of metal or plastic, with symbols to facilitate exact
representation of the system shall be fixed on the front of control panel. Control
switches and semaphore indicators shall be incorporated in the mimic diagram
to represent the respective circuit breaker and isolators. Scheme of mimic
diagram shall be subject to the approval of the Purchaser.

1.4.3 Name plates and Marking:
Name plates shall be with black background with white engraved letters. Each
part / item on the panels shall, also, have an appropriate nameplate.
Nameplates for relays shall be marked with their function standard code
number.

1.4.4 Indicating Lamps:

1.4.4.1 Indicating lamps shall be of LED type, the supply for which shall be
110V/220V D.C. unless stated otherwise. Lamp covers shall be preferably of
screwed type, unbreakable and moulded from heat resisting material. They
shall be translucent to diffuse light and shall be of following unless otherwise
stated. The over all diameter of lamp shall be 30 mm while that of cut out shall
be 22.5 mm

a) 'RED' for indicating CLOSED position of breakers.
b) 'GREEN' for indicating OPEN position of breakers.
c) 'BLUE' for indicating Spring charged position
d) MILKY WHITE for SF6 Gas Pressure Normal.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 9 of 71
e) WHITE for TRIP CIRCUIT HEALTHY indication (2 Nos with Push
buttons).
f) AMBER FOR AUTO TRIP indication.

1.4.5 Semaphore Indicators :

1.4.5.1 Semaphore indicators shall be provided on the front side of the panel on Mimic
diagram for indicating position of circuit breakers, isolators and earthing
switches. They shall be of two coil type and their operating voltage shall be
110V / 220V D.C., unless otherwise stated.

1.4.6 Switches :

1.4.6.1 All switches shall be of rotary operated type with silver to silver contacts of
adequate making, carrying and breaking current ratings and shall be provided
with easily removable protective terminal covers. The contacts of all switches
shall preferably open and close with snap action to minimize arcing. Switches
shall be suitable for accommodating spare / additional contacts, if required
subsequently, and this point shall be brought out in the offer. The bidder shall
clearly state the continuous current ratings and interrupting current rating for
D.C. and A.C. inductive and non-inductive circuits. The type of switches used
shall be subject to approval of the Purchaser.

1.4.6.2 Voltmeter switches for A.C. shall be suitable for reading all line to line voltages
for effectively earthed systems. The switch shall be 4-way stay put type with
minimum 10A continuous rating.

1.4.6.3 Circuit breaker and isolator control switches shall be of THREE POSITION
SPRING RETRUN type with pistol grip handles. The spring return type switch
shall have spring return from close and trip position to `After Close and `After
Trip positions respectively. The control springs shall be strong and robust
enough to prevent inadvertent operation due to light touch. The continuous
rating of the switches shall not be less than 25 Amps. and that for one second
shall be 150 Amps. Breaker control switches shall be provided with adequate
nos. of spare contacts for control, interlocking, annunciation and discrepancy
indication. Breaker control switches shall be with lost motion device for
indicating auto trip indication.





GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 10 of 71
1.4.7 Instruments, Meters and Recorders :

1.4.7.1 All instruments, meters and recorders shall be enclosed in dust-proof, moisture
resistant, black finished cases and shall be suitable for tropical atmosphere. All
accessories, including test switches and test plugs, wherever required, shall be
furnished. They shall be capable of withstanding over currents due to faults in
primary circuits. Their elements shall be shock-resistant and shielded from
external magnetic fields. The instruments shall be of 144mm x 144mm size
with 240 degree scale. These shall be mounted semi-flush on the panel with
only flange projecting. Dials shall be white with black numbers.

1.4.7.2 Ammeters :
All ammeters shall be provided with direct reading, double range scale, one on
each side of the dial or alternatively two scales for two ranges. The scale value
of A.C. ammeters shall be equal to 1 to 1.3 times the rated primary current of
the current transformers feeding it. The rated current of the ammeter element
shall be 1.0 Amp. D.C. ammeter shall have shunt and shunt leads. Class of
accuracy shall be 1.0 or better.

1.4.7.3 Voltmeter :
All voltmeters shall be provided with direct reading scales. The maximum value
of the voltage scale shall be 115 % of the normal circuit voltage. The rated
voltage of the voltmeters shall be 110/3 volts. The voltmeters shall preferably
be supplied with suppressed scales with initial suppression, wherever
necessary. Class of accuracy shall be 1.0 or better.

1.4.7.4 Wattmeters :
Indicating wattmeters shall be 3 phase, 3 wire, two-element type provided with
direct reading scale. The current coil shall be rated for 1.0 Amps. and the
voltage coil for 110V.
The wattmeters shall be suitable for circuits with UNBALANCED LOADS to be
usually met within commercial service. Centre zero type of wattmeters shall be
supplied, wherever specified. Class of accuracy shall be 1.0 or better.

1.4.7.5 Energy Meter :
The Energy Meter shall be 3-Phase, 4 Wire type with accuracy class 0.5S. It
shall be as per attached technical specifications and it shall be compatible to
the existing DAS (Data Acquisition System) working in GETCO network.


GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 11 of 71
Energy meters shall be of L&T / ELSTER / SEMS make and it shall be as
per discretion of GETCO & shall be finalized during detailed engineering.

1.4.7.6 MVAR Meter :
Two elements type MVAR meter suitable for 3 phase 3 wire shall be provided
with direct reading scale. Class of accuracy shall be 1.0 or better.

1.4.8 Annunciation System :

1.4.8.1 General :
Alarm annunciation system shall be provided for the control board in order to
draw the attention of the operator to the abnormal operating conditions or the
operation of any protective device. The annunciation equipment shall be
suitable for operation on 220/110V DC in normal conditions and on 230V AC in
case the DC supply to Annunciation is failed i.e. it shall work on both AC & DC
supply with AC supply as standby.
Annunciation scheme shall have provision of AC fail and DC fail alarm
internally without any external relays or wiring. Trip and Non-Trip alarms shall
be distinguished by separate Hooter while DC fail alarm shall be through AC
Buzzer.

1.4.8.2 Annunciation :
This annunciation is used to draw the attention of the operator, when the circuit
breaker / relay trips due to fault or abnormality. The audible annunciation shall
be provided by means of a "Bell". The visual annunciation shall be by flickering
of a facia window.

1.4.8.3 Warning / Non Trip Annunciation :
This is used during occurrence of an abnormal operating condition, other than
the tripping of the circuit breaker / relay. The audible annunciation shall be
provided by means of 'Hooter'. The visual annunciation shall be obtained by
flickering of the respective facia window.
1.4.8.4 DC Fail Annunciation :
This shall be used for indicating DC fail condition. The audible annunciation
shall be provided by means of 'Buzzer'. The visual annunciation shall be
obtained by flickering of the respective facia window.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 12 of 71
1.4.9 Relays :
Shall be as per PART-III Requirement of protective relays for 66KV
C&R Panels
1.4.10 Auxiliary Relays :

Shall be as per PART-III Requirement of protective relays for 66KV C&R
Panels

1.4.11 Trip Circuit Supervision Relays :

Shall be as per PART-III Requirement of protective relays for 66KV
C&R Panels

1.4.12 Electrical Equipment and Wiring :

1.4.12.1 Electrical equipment furnished by the contractor shall be designed for use
under the climatic conditions, prevailing at site. Metal parts shall be protected
against corrosion by plating and / or painting. Power & control wiring, shall
have insulation of non-hygroscopic type unless specifically stated otherwise.

1.4.12.2 Control wiring shall be securely supported, neatly arranged, readily accessible
and connected to equipment terminals and terminal blocks voltage grade 1.1
KV. Each wire shall be provided with identifying ferrule at each end or
connecting point. Colour coding of control wiring shall be as per standard
modern practice. All wires shall be flexible, multi strand copper wires with
P.V.C. insulation of 1100 volts grade and shall be suitable for specified control
& relay panel and shall be of adequate cross section not less than 2.5mm
2

stranded copper wire. The wire shall be flame-retardant and vermin proof, type,
suitable for the tropical climate.

1.4.13 Terminal Blocks :

1.4.13.1 One piece moulded, barrier type, terminal block of non-inflammable plastic,
having voltage grade of 800 V shall be used complete with washers, and heads
strips etc. and stud type terminals. Continuous current ratings for the terminal
blocks shall not be less than 45 Amps. At least twenty percent spare terminals
shall be provided in each panel and evenly distributed in all TBs. The terminal
blocks shall be located, on both sides of the panel.

1.4.13.2 Purchaser's control cable shall be of 2.5, 4.0, mm
2
size copper. The terminals
shall be suitable for connection of copper conductors. In case of 2.5 sq.mm.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 13 of 71
size, the number of cables to be taken inside the terminal may be four.
Accordingly the terminal size shall be suitable.

1.4.13.3 The control schemes shall incorporate necessary arrangements for isolation
purpose, while testing and checking faults in control and signaling circuits.

1.4.14 Space Heaters:

1.4.14.1 Tubular space heaters of 60 watts with thermostat control of suitable rating for
connection to single phase, 240 Volts, A.C. Supply complete with switches
conveniently located, shall be provided at the bottom of the cubicle to prevent
condensation of moisture. The loss of power shall be low enough to keep the
temperature of surface well below permissible limits.

1.4.15 Test Blocks:

1.4.15.1 Switch board type, back connected, semi-flush mounting type test blocks
having Voltage rating 1100 V and Current rating 45A shall be provided with
links or other devices to enable insertion of a device into the circuit without
causing open circuit secondary of CT or to enable short circuiting of secondary
of the C.T.

1.4.15.2 Test Terminal Blocks shall be used to facilitate complete isolation of meters,
instruments and relays, so that power for testing can be supplied either from
the instrument transformers or from an external source.

1.4.15.3 Loose Test Plugs / handles required for online testing of the relays through
Test Blocks shall be in the scope of the tender and shall be supplied with the
panels. However its quantity shall be 5% of the panel quantity.

1.4.16 Safety Earthing:

1.4.16.1 Control panels shall be provided with earthing bus of copper having a minimum
cross sectional area of 150 sq.mm. Earthing bus shall be securely mounted
across the inside base of the panels. Earthing bus shall run throughout the
width of panel. It shall be provided with M4 holes and Nuts & Bolts at a
distance of 100mm. Provisions shall be made for extending the grounding bus
bar to future adjoining panels. Earthing wires shall be connected by using
suitable terminals and clamp connections. Solder connections shall not be
employed.




GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 14 of 71
1.4.17 Switch Board Lighting:

1.4.17.1 The switchboard shall be illuminated by 11 W, CFL with fixture including
reflector, front cover, etc. The voltage rating shall be 230 Volts, 1, 50 Hz, AC
supply. This light shall be operated by door operated switch.

1.4.18 Supporting Steel:

1.4.18.1 All necessary embedded leveling steel, steel, anchor bolts, channels and other
parts for supporting and fastening the panels shall be supplied by the
successful bidder.

1.4.19 Accessories:

1.4.19.1 The successful bidder shall supply necessary accessories like test blocks, test
links, special terminal boards etc. for testing, operation and maintenance of all
relays and meters, as specified.

1.4.20 Tropicalization:

1.4.20.1 Wiring, terminal blocks, relays, instruments, meters and control devices shall
be suitable for installation in a tropical monsoon area, having a hot humid
climate and dry and dusty season with ambient conditions specified Section-II.
All equipment and accessories shall be painted by means of spray or dip
coating and shall be protected against fungus growth condensation, vermin
and other harmful effects due to tropical environment.


1.4.21 Painting:
A suitable rust resisting primer paint shall be applied on the interior and exterior
steel surfaces of control panel after removing rust by sand blasting, foreign
adhering matter of grease, scale etc. An under coat to serve a base and binder
for the finishing coat shall be applied. The finishing coat on the exterior of the
panels shall be of shade No. 631 (Light grey) of IS 5. Polished cellulose
enamel of light grey evenly sprayed on the outside and egg shall white paint
evenly sprayed on the inside shall be applied as finishing coat. Sufficient
quantity of finishing paint shall be supplied for minor touching up required at
site.




GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 15 of 71
1.4.22 Fire Protection:

1.4.22.1 All equipment connections and cabling shall be designed and arranged to
minimize the risk of fire and damage, which may be caused by fire.

1.5 PROTECTIVE SCHEME REQUIREMENT :
Shall be as per PART-III Requirement of protective relays for 66KV
C&R Panels

1.6 TESTS:


1.6.1 Type Test :

The bidder shall submit the reports of the type tests as stated hereunder for the
offered item along with the offer, otherwise the offer shall be liable to be
rejected. These tests must have been conducted in the NABL approved
laboratory within last 5 years prior to date of validation of the offer.

1. Degree of Protection IP 54

It shall be certified by the successful bidder that the type tests in accordance
with the relevant standards have been successfully carried out on all type of
relays, meters, switches and other devices being supplied by him. Certified
copies of all type tests shall be submitted to the purchaser (two sets).

1.6.2 Routine & Acceptance Tests:

Before commencement of supply, one prototype shall be offered for
inspection. Mass production shall only be allowed after clearing this inspection.
This inspection shall be in addition to the regular lot wise inspection to be
offered by the supplier.

All control & relay panels shall be subjected to routine tests according to the
relevant standards and to such other tests as may be required to ensure that
each panel is satisfactory and in accordance with this specification. The
Purchaser reserves the right to witness all the tests and advance intimation
shall be given regarding these tests. Test reports of all such tests shall be
submitted to the purchaser for approval before inspection. Any modification
required in the testing procedure shall be made as directed by the Purchaser at
no additional cost to the Purchaser. No panel shall be dispatched from the
manufacturer's work before the relevant tests reports have been approved by
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 16 of 71
the purchaser. The successful bidder shall send two copies of the certified final
test reports to each consignee of all factory tests carried out on each panel,
relay, meter, switch, instrument, transformer and other devices, which shall
furnish complete information including the method of application and duration
of test. List of routine tests to be performed on the panel shall, also, be
furnished with the offer.


1.7 CO-ORDINATION WITH OTHER MANUFACTURERS :
The control panel manufacturer shall also co-operate and co-ordinate in every
respect with the suppliers of the switchgear, equipment and other associated
equipment and shall provide complete technical data, schematic drawings of
control, indication, protection etc.

1.8 PACKING AND TRANSPORTATION :

1.8.1 After satisfactory final inspection and tests and after written approval has been
given by the purchaser, the successful bidder shall suitably pack for
transportation of panels by rail and road transport and deliver the same to the
site. The marking shall include the contact number and the name and address
of the consignee.

1.8.2 The supplier shall be responsible for arranging transport to site and shall satisfy
himself that the transport arrangements are satisfactory.

1.8.3 The panels may be transported with all instruments. Relays, switches and other
devices mounted in position and wired. Instruments, relays etc. shall be
specially covered so as they shall not be damaged during the panel
transportation & handling. Four copies of the packing list shall be sent well in
advance before the goods are delivered.

1.8.4 The packing list for each panel shall indicate complete details of the panel
being dispatched to enable the consignee to identify the parts and to ensure
that no part / item stated to have been supplied / transported has either been
lost in transit or damaged to initiate procedure for replacement and also to
enable loading of insurance claims. If the invoice does not contain full details
and if any part has not been specifically mentioned in the packing list & is
missing in transit, the supplier shall be responsible for the same and shall
supply such parts to the purchaser without any extra cost.



GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 17 of 71
1.9 GUARANTEED TECHNICAL PARTICULARS:

The bidder shall furnish complete guaranteed technical particulars as called for
in Appendix I of Section-III of this Specification. Incomplete details against
GTP, shall be considered as incomplete offer.

1.10 INSTRUCTION MANUAL & DRAWINGS:

1.10.1 A copy of operating, maintenance & erection manuals and Drawings in English
language shall be supplied with each panel.

1.10.2 The manuals shall be bound volume and shall contain all the printed drawings,
requisite information for erection, operation and maintenance of the panels and
the following particulars.
a) Marked erection prints, identifying the components parts / items of the
panels as dispatched with assembly drawings.
b) Performance curves, nameplate details and other data of all devices.
c) Complete list of spare parts.
d) All the drawings of the panel




GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 18 of 71
SECTION II

SPECIFIC TECHNICAL REQUIREMENTS
FOR 66KV CONTROL AND RELAY PANELS:

2.1 SCOPE :

2.1.1 This specification covers the specific technical particulars climatic and
isoceraunic conditions, system particulars, to be considered for the control and
relay panels whose Technical Requirements have been described under
Section-I of this Specification and the Schedule of requirements.

2.2 SYSTEM AND CLIMATIC CONDITIONS :

2.2.1 System details :
(i) Normal system voltage (KV) : 66
(ii) Highest system voltage (KV) : 72.5
(iii) Number of phases. : 3
(iv) System frequency (Hz) : 50
(v) Earthing. : Solidly earthed.
(vi) AC Auxiliary supply : 3-phase 4-Wire, 415V AC
: 1-phase 2-Wire, 50 C/s,
230V AC. Voltage variation
+10% & - 15%, Frequency
Variation 3%
(vii) DC Auxiliary supply : 2 Wire, 110/220V DC
With 10%, ungrounded.
2.2.2 Climatic Particulars :
a) Maximum ambient temperature of : 50
Air in shade (
0
C).
b) Minimum ambient temperature of : 4
Air in shade (
0
C).
c) Maximum yearly average ambient : 40
Temperature (
0
C).
d) Minimum yearly average ambient : 30
Temperature (
0
C).
e) Maximum relative humidity (%). : 95
f) Average number of thunder storm : 15
Days per annum.
g) Average annual rain fall (CM). : 115
h) Maximum wind pressure (Kg/M
2
). : 150
i) Earth quake acceleration : 0.08 x 2 g.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 19 of 71
j) Height above mean sea level. : Not exceeding 1000m.

2.2.3 The panels offered shall be suitable for continuous operation at the full rated
capacity under the above conditions.

2.2.4 Since the Sub-Stations are near seashore or in an industrial area, the offer
shall be suitable for heavily polluted atmosphere.

2.3 SPECIFIC REQUIREMENTS :

2.3.1 Type I - 66KV Transformer C & R Panel : with differential protection

2.3.1.1 Instruments :
(a) 3 Moving iron Ammeters, 144mm x 144mm size, flush pattern,
having scale range of 0-100-150 Amp. or 0-300-600 Amps.
connected to secondary of 150-100/1-1-1 Amps. or 600-300/1-1-
1 Amp. 66 KV CTs.

(b) 1 - Voltmeter, 144mm x 144mm size, flush pattern, with selector
switch having scale range of 0-75 KV connected to secondary of
66000/3KV / 110/3V PTs.

(c) 1 - Static KWh meter, flush pattern, connected to above CT and
PTs. The detailed specifications are attached separately.

(d) 1 - MW meter, 144mm x 144mm size, flush pattern connected to
above CT and PTs. (Suitable for unbalanced load).

(e) 1 - MVAR meter, 144mm x 144mm, size flush pattern connected to
above CT and PTs. (Suitable for unbalanced load.)

(f) 1 - Mimic diagram to represent bus bars, Isolators, circuit breaker,
etc.

(g) 1 - Pistol Grip, spring return type, 3 position control switch with lost
motion device for 66KV circuit breakers with one spare contact
in each position.

(h) 2 - Automatic semaphore indicators for position indication of the
breaker and the isolator. (size of semaphore for breaker shall be
63 mm while that for isolator shall be 36 mm)

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 20 of 71
(i) 2 - One RED and one GREEN - 'ON' and 'OFF' indicating lamps,
suitable for 110/220V DC, for the circuit breaker.

(j) 2 - WHITE Indicating lamp, for 'Trip Circuit' healthy indication with
push button.

(k) 1 - Blue indicating lamp for spring charged position of the
breaker.

(l) 1 - AMBER indicating lamp for Auto Trip indication of breaker.

(m) 1 - Milky White indicating lamp for SF6 Gas Pressure Normal
indication Breaker.

2.3.1.2 Annunciation :
a) 1 - 18 Way illuminated facia window type alarm annunciation for
indication of individual types of faults as under :-
(i) Differential Protection Operated
(ii) Over Current Protection Operated
(iii) Earth Fault Protection Operated
(iv) Buchholz Trip
(v) Winding / Oil Temp. High Trip
(vi) PRV Trip
(vii) OLTC Surge Relay Trip
(viii) Buchholz Alarm
(ix) Winding / Oil Temp. High Alarm
(x) Low oil level Alarm
(xi) DC Fail
(xii) AC Fail
(xiii) CB Lockout
(xiv) SF6 Gas Pressure Low
(xv) Differential Relay Faulty
(xvi) Trip Circuit -1 / 2 Faulty
(xvii) Over Current & Earth fault Relay Faulty
(xviii) Trip Relay Operated
The unit shall be complete with necessary, bell, hooter lamps,
push key units for alarm reset, alarm acknowledgment and lamp
test. It shall be mounted on the front of the panel.

b) 1 - Set of alarm accept, reset and lamp test push buttons, if
required separately.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 21 of 71
2.3.1.3 Protection (Transformer C & R panel with differential protection)

1. Transformer Differential Relay
2. Non directional O/C & E/F Relay
3. Transformer Trouble Relays
4. Trip Circuit Supervision Relays
5. Master Trip Relay

It shall be as per PART-III Requirement of protective relays for 66KV C&R
Panels

2.3.2 Type II 66KV Feeder Control & Relay Panel :
2.3.2.1 Instruments :
a) 3 - Moving iron ammeters as in 2.3.1.1 (a) above.
b) 1 - Voltmeter as in 2.3.1.1(b) above.
c) 1 - static KWH meter as in 2.3.1.1(c) above
d) 1 - MW meter as in 2.3.1.1(d) above.
e) 1 - Mimic diagram as in 2.3.1.1(f) above.
f) 1 - Pistol grip, spring return type, 3 position control switch as in
2.3.1.1.(g) above.
g) 4 - Automatic semaphore indicators as in 2.3.1.1(h) above, for
breaker and isolator & earth switch position indication.
h) 2 - One RED and one GREEN indicating lamps, working on
110V/220V D.C. to show circuit breaker 'ON' and 'OFF' position.
i) 2 - White trip circuit healthy indicating lamps with push button.
j) 1 - Blue indicating lamp for spring charged position of breaker as
in Cl.2.3.1.1(k) above.
k) 1 - Amber indicating lamp for Auto trip of breaker as in
Cl.2.3.1.1(l) above.
l) 1 - Milky White indicating lamp for SF6 Gas Pressure Normal
indication of the breaker.
2.3.2.2 Annunciation :
a) 1 - 12 window annunciator for annunciation.
(i) Over Current Protection Operated
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 22 of 71
(ii) Earth Fault Protection Operated
(iii) Trip Relay Operated
(iv) Trip Circuit -1 Faulty
(v) Trip Circuit -2 Faulty
(vi) O/C & E/F Relay Faulty
(vii) CB SF6 Gas Pressure Low
(viii) CB Lockout
(ix) Spare
(x) Spare
(xi) DC Fail
(xii) AC Fail

b) 1 - Set of alarm accept reset and lamp test push buttons, if required
separately.
2.3.2.3 Protection (66 KV Feeder) :
1. Directional O/C & E/F Relay
2. Trip Circuit Supervision Relays
3. Master Trip Relay

It shall be as per PART-III Requirement of protective relays for 66KV
C&R Panels

2.3.3 Type III - 66KV Transformer Control & Relay Panel: Without differential
protection

The 66KV C/R Panel for 66KV side of 220/66KV or 132/66KV Power
Transformers shall be similar to type II 66 KV feeder C/R Panels with
consideration of the following points.
2 - Automatic semaphore indicator for isolator and breaker instead of 4
nos.
1 - MVAR meter, 144mm x 144mm size shall be provided suitable for CT
ratios 600-300 / 1-1-1 and 1200-600 / 1-1-1 and PT ratio 66/3KV /
110/3V.
CT ratio shall be 600-300 / 1-1-1A or 1200-600 / 1-1-1A

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 23 of 71
2.3.4 Type IV - 66 KV Bus Coupler C & R panel

2.3.4.1 Instruments :
a) 3 - Moving iron ammeters with selector switch as in 2.3.1.1 (a)
above.
b) 2 - Voltmeter as in 2.3.1.1(b) above.
c) 2 - Digital frequency meters, 72 X 72 mm size, flush mounted,
accuracy class - 0.5.
d) 1 - Section of mimic diagram as in 2.3.1.1(f) above.
e) 1 - Pistol grip, spring return type, 3 position control switch as in
2.3.1.1.(g) above.
f) 5 - Automatic semaphore indicators as in 2.3.1.1(h) above, for
breaker and isolator & PT isolators position indication.
g) 2 - One RED and one GREEN indicating lamps, working on
110V/220V D.C. to show circuit breaker 'ON' and 'OFF' position.
h) 2 - White trip circuit healthy indicating lamps with push button.
i) 1 - Blue indicating lamp for spring charged position of breaker as
in Cl.2.3.1.1(k) above.
j) 1 - Amber indicating lamp for Auto trip of breaker as in
Cl.2.3.1.1(l) above.
k) 1 - Violet Milky White indicating lamp for SF6 Gas Pressure
Normal indication of the breaker.
2.3.4.2 Annunciation :
a) 1 - 12 window annunciator for annunciation as in 2.3.2.2(a) above.
b) 1 - Set of alarm accept reset and lamp test push buttons, if required
separately.
2.3.4.3 Protection (66 KV Bus Coupler) :
1. Non Directional O/C & E/F Relay
2. Trip Circuit Supervision Relays
3. Master Trip Relay
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 24 of 71
It shall be as per PART-III Requirement of protective relays for 66KV C&R
Panels


2.3.5 Type V 66KV Capacitor Bank Control & Relay Panel :
2.3.5.1 Instruments :
a) 3 - Moving iron ammeters as in 2.3.1.1 (a) above.
b) 1 - Moving iron ammeters as in 2.3.1.1 (a) above but with range
0 1 Amp to connect to 66 KV CT of ratio 1/1A. OR
2 - Moving iron ammeters as in 2.3.1.1 (a) above but with range
0 1 Amp to connect to 66 KV CT of ratio 1/1A, if Panel is
asked for controlling 2 Banks
c) 1 - Voltmeter as in 2.3.1.1(b) above.
d) 1 - static KWH meter as in 2.3.1.1(c) above
e) 1 - MVAR meter as in 2.3.1.1(e) above.
f) 1 - Mimic diagram as in 2.3.1.1(f) above.
g) 1 - Pistol grip, spring return type, 3 position control switch as in
2.3.1.1.(g) above.
h) 4 - Automatic semaphore indicators as in 2.3.1.1(h) above, for
breaker and isolator & earth switch position indication. OR
6 - Automatic semaphore indicators as in 2.3.1.1(h) above, for
breaker and isolator & earth switch position indication, if Panel
is asked for controlling 2 Banks.
i) 2 - One RED and one GREEN indicating lamps, working on
110V/220V D.C. to show circuit breaker 'ON' and 'OFF' position.
j) 2 - White trip circuit healthy indicating lamps with push button.
k) 1 - Blue indicating lamp for spring charged position of breaker as
in Cl.2.3.1.1(k) above.
l) 1 - Amber indicating lamp for Auto trip of breaker as in
Cl.2.3.1.1(l) above.
m) 1 - Milky White indicating lamp for SF6 Gas Pressure Normal
indication of the breaker.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 25 of 71
2.3.5.2 Annunciation :
a) 1 - 12 window annunciator for annunciation.
(i) Unbalance Current Protection Alarm
(ii) Unbalance Current Protection Operated
(iii) O/C & E/F Protection Operated
(iv) Trip Relay Operated
(v) Trip Circuit -1 Faulty
(vi) Trip Circuit -2 Faulty
(vii) Protection Relay Faulty
(viii) CB SF6 Gas Pressure Low
(ix) CB Lockout
(x) Over Voltage Protection Operated
(xi) Under Voltage Protection Operated
(xii) DC Fail
(xiii) AC Fail

b) 1 - Set of alarm accept reset and lamp test push buttons, if required
separately.
2.3.5.3 Protection (66 KV Capacitor Bank) :
1. Unbalance Current Protection
2. Over Voltage & Under Voltage Protection
3. Non - Directional O/C & E/F Relay
4. Leading Power Factor Controller Relay
5. Trip Circuit Supervision Relays
6. Master Trip Relay

It shall be as per PART-III Requirement of protective relays for 66KV
C&R Panels
2.3.6 Indicating lamp, instruments and vector group of power transformer, instrument
transformer :

1. Indicating instruments shall be of flush type and shall have 240
0
C scale
and 144mm x 144mm size. Instruments shall be of the taut band
suspension type.

2. Coloured mimic diagram of 10mm width shall be for main bus and that
of 5mm for remaining. Colour shade shall be as under:
Earth - Green.
66 KV - Golden brown shade 414 of IS : 5.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 26 of 71
2.4 Vector Group of 10MVA/15MVA : Dyn 11
66/11.55KV Power transformer.

2.4.1 Particulars of 66KV
Current transformer:

1. CT ratio. : a) 150-100/1-1-1 Amp.
b) 600-300/1-1-1 Amp.
c) 1200-600/1-1-1 Amp.

2. Rated burden (VA) : Core-1 30 VA
(At minimum tap.) : Core-2 30 VA
Core-3 -

3. Class of accuracy. : Core-1 0.5
Core-2 5P
Core-3 PS

4. Rated Instrument security. & accuracy: Core-1 - 5 (ISF).
Limit factor Core-2 - 10 (ALF).
Core-3 - ---

5. Exciting current at : 25 mA.
Knee point voltage.

6. Purpose. : Core-1 Metering.
Core-2 Back up Protection
Core-3 Differential Protection.

7. Minimum knee point : 600 Volts for a)
voltage 650 Volts for b) & c)

8. Resistance of the : 10 Ohms.
Secondary winding.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 27 of 71
STATEMENT I

66KV CONTROL AND RELAY PANELS SPECIFIC REQUIREMENT PER PANEL:

Sr. Particulars Unit Transformer panels. Feeder Capacitor Bus
No. With diff.
protn.

Without
differential
protection /
LV side of
220/66KV or
132/66KV
Trans.

Panels. Bank coupler
Panels Panels

01 02 03 04 05 06 07 08

01.

Automatic semaphore for breaker.


No.

01

01

01 01 01
02. Automatic semaphore for isolator
and Earth Switch

01 01 03 03 / 04
05
(for 2 Banks)
03. Indication lamp (C.B. closed, open,
trip circuit healthy, spring charged,
auto trip, gas pr Normal).

07 07 07 07 07
04. Breaker control switch (Pistol grip,
3 position with lost motion device
and bell alarm contacts).

01 01 01 01 01
05. Taut Band type Ammeter 144mm x
144mm and circular scaled.

03 03 03 04 / 03
05
(for 2 Banks)
07. Voltmeter as in 5 above.

01 01 01 01 02
08. Selector switch for voltmeter

01 01 01 01 02
09. MW meter as in 5 above

01 01 01 -- --
10. Static KWH meter

01 01 01 01 --
11. (i) Power factor meter as in 5
above.
(ii) MVAR meter as in 5 above.



--

01
--

01
-- -- --

-- 01 --
12. Numerical Non directional O/C-
E/F relay (as per Part-III)
01 -- -- 01 01
13. Numerical Differential relay (as per
Part III)
01 -- -- -- --
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 28 of 71
14. Numerical Directional O/C-E/F
relay (as per Part-III)
-- 01 01 -- --
15. Numerical Unbalance Current
Relay
-- -- -- 01 --
16. Electromagnetic / Static Over
Voltage Relay
-- -- -- 01 --
17. Electromagnetic / Static Under
Voltage Relay
-- -- -- 01 --
18. Leading Power Factor Controller
Relay
-- -- -- 01 --
19. 5 Minute Delay Relay / Timer -- -- -- 01 --
20. PT Selection Relay (applicable to
C & R Panel for two main bus
system)
02 02 02 02 --
21. Trip circuit supervision relay (as
per Part-III)

02 02 02 02 02
22. Ten element auxiliary relay for
Buchholz, oil temp, winding temp,
PRV Trip. OLTC surge Relay Trip
& Low oil level Trip. (as per Part-
III)
01 -- -- -- --
23. (a) Master Trip Relay (as per
Part-III)
No. 01 01 01 01 01
24. 12/18 way facia annunciation
scheme, complete, with 3 nos.
push buttons for accept. Reset and
lamp test with bell, hooter, Buzzer
for Trip, Non Trip and DC fail.
Set. 01 01 01 01 01
25. Panel illumination with door
operated switch.
CFL with fixture shall be provided for each panel
26. Space heater with thermostat
control, Cam type ON / OFF switch
and required fuses.
--- To be provided with each Panel ---
27. Mimic diagram. --- do ---
28. Car type lockable handle. --- do ---
29. Multipin 15A Socket

--- do ---
30. 3.0 / 2.5 mm thick sheets steel for
front / all sides respectively.
--- do ---
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 29 of 71
31. Circuit wiring to comply to
specification with required fuses,
links, terminal blocks.
--- do ---
32. Push buttons for trip ckt. healthy.

No. 02 02 02 02 02
33. Test terminal block. 1100V grade.
(for energy meter)
" 01 01 01 01 01
34. M.S. foundation blots/nuts, size
18mm dia x120mm long.
" 04 04 04 04 04
35. Relay Test Block, 1100 V, 45A

02 01 01 03 01

36. Suitably rated fuses and fuse links shall be provided as per schematic drawing requirement
in each Panel

Note :
1. The energy meter shall be as per attached technical specifications and it
shall be compatible to the existing DAS (Data Acquisition System) working in
GETCO network. Energy meters shall be of L&T / ELSTER / SEMS make
and it shall be finalized during detailed engineering.

2. Indicating lamps offered shall be as under :

a) C.B. Closed. :Red colour
b) C.B. open. :Green colour
c) Trip circuit healthy. :White colour
d) Spring charged. :Blue colour
e) Auto trip. :Amber colour
f) SF6 Gas Pressure Normal : Milky White colour
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 30 of 71
PART II
GENERAL REQUIREMENTS

1. SCOPE :
This part covers design, manufacture, inspection, dispatch and delivery of
electric control and relay panels and accessories. 'Control Panel' shall be
suitable for interchangeability. This covers duplex panels as well as control
desks. Both parts of this specification are mutually dependent and are essential
for correct and complete interpretation. Part I covers specific requirements and
part II covers general requirements which hold good for all projects. When
requirements of two parts conflict, those of part one shall prevail.

1.1 The following works have been included within the scope of this specification :

(a) Design and fabrication of complete panel including provision for all parts
/ items and wiring.

(b) Painting of all panels specified in part one of this specifications,
together with such auxiliary items as may be incidental or
complementary to those specified.

(c) All internal wiring to equipment and terminals and inter panel wiring.

(d) Furnishing of all necessary material and parts / items required for the
control panel/desk to perform as specified in part I.

(e) Electrical detailing as outlined in this specification.

(f) Preparation and furnishing of all drawing as required.

1.2 Bidder shall separately state, in his offer all deviations from this specification, in
the enclosed schedule of deviations. Unless the proposed deviations are
brought out clause by clause in the prescribed schedule, the proposal shall be
deemed to be in total conformity with this specification.

2. STANDARD :

2.1 The intent of this specification is to specify essential general requirements
rather than all details of design construction and equipment. The supplier shall
be responsible for furnishing a control board complete in all respects and
details, within the limits outline above in "SCOPE" and conforming in all
respects to high standards of engineering, design and workmanship. The
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 31 of 71
supplier shall be responsible to make good at his own expense, any failure of
circuits to function as intended when the Board is installed.

2.2 All materials and parts / items offered shall conform to the requirements of the
latest editions of the relevant Indian Standards and Codes of Practices.
However, in the event of offering equipment, conforming to standard other than
Indian standard or this specification, the salient points of comparison between
the standard adopted and Indian Standards shall be indicated in the offer.

2.3 Any materials, parts / items or methods which the supplier considers preferable
to those specified here in, for the purpose intended, may be offered for
consideration and prior approval.

3. GENERAL DESCRIPTION :
Simplex Control Board shall comprise of single vertical standing control or relay
panels sections bolted together at their sides to form a single control or relay
panel or control relay board. Each panel shall have a hinged rear access door
provided with locks.

4. GENERAL CONSTRUCTIONS :
Control Board shall be completely closed, constructed from specially selected
smooth finished sheet steel, not less than 3mm for front and 2.5 mm for all
other sides and top, in thickness, bent and formed into a rigid unit and suitable
for mounting auxiliary apparatus. There shall be sufficient reinforcement to
provide flat level surfaces, resistance to vibration and rigidity during
transportation and installation. Support and enclosure of cables and wiring
shall be safe, neat and shall provide sufficient accessibility.

4.1 Design, material selection and workmanship shall be such as to result in a neat
appearance outside and inside, with no welds, rivets or bolt heads apparent
from outside and with all exterior surfaces true and smooth.

4.2 Cut outs and small wiring for items / parts shall be according to items / parts
manufacturer's drawings and diagrams.

4.3 Items / parts shall be mounted such that removal and replacement can be
accomplished individually without interruption of service to adjacent parts /
items. Parts / items mounted inside the panel shall be so located that terminals
and adjacent devices are readily accessible without the use of special tools.
Terminal markings shall be clearly visible.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 32 of 71
4.4 Relays and devices mounted on or inside the control board shall have
identification markings clearly visible from the insider, of control board
enclosure. Devices mounted on the control board shall also be labeled on the
outside of the control board.

4.5 Control Board base shall be designed with a flat bearing surface for mounting
on two strips each of 10mm thick of approved type of shock absorbing
materials which shall be supplied by the supplier. Foundation pamphlets
describing by details in regard to method of mounting and cable trench, to be
provided in the foundation platform shall be furnished by the supplier well in
advance of the dispatch of the panels.

5. DESIGN DETAILS :
Panels and openings shall have edges and corners slightly rounded for safe
handling.

5.1 Supports shall be provided for purchaser's incoming and outgoing cables.
Terminal blocks shall be provided for connections between these cable and
control board wiring, wiring gutter shall be provided for vertical panel wiring and
for interconnecting wiring.

5.2 Auxiliary parts / items shall be mounted inside the panels in a manner that will
not interfere with the inspection or maintenance of the wiring and the terminal
connections. Wiring through, gutters, cable supports and mountings for
terminal blocks shall be provided for future circuits, whenever these are
specified in part I.

5.3 One piece moulded, barrier type, 800 Volt grade terminal blocks complete with
washers heads, terminal screws and identification strips shall be used.
Continuous current ratings for the terminal blocks shall not be less than 45
Amps. At least twenty percent spare terminal blocks shall be provided on each
panels.

Terminal blocks shall be suitable for connection up to three conductors of
purchaser's cables which will be of following sizes :

i) PT and control - 2.5 4mm
2
Copper.
Circuit.
ii) C.T. circuits. - 4 mm
2
Copper.

5.4 The supplier shall be solely responsible for correctness of the internal wiring
and for the proper functioning of the panels furnished by him.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 33 of 71

5.5 Designation for the panel sections, relay instruments and meters, control
devices circuit breakers, test blocks, fuses etc. shall be clearly marked close to
the equipment. Laminated plastic name plate shall be provided for small relays,
meters, test facilities and control devices.

5.6 A mimic bus shall be mounted on the face of the panels in the general location
indicated on the switch board layout drawings accompanying this specification.
This mimic bus shall be of screwed on type, anodized aluminum or plastic.

5.7 Terminal Blocks for bus wires i.e. (A.C. and D.C.) supply, PTs, and other
common services shall be provided near the top of the panels, running
throughout the length of the Board.

5.8 Adequate illumination shall be provided for the access to interior of the switch
board.
Illumination for simplex panels shall be through provision of a 240V, 1 phase
50 C/s. A.C. CFL mounted in each panel controlled through rear door operated
'ON/OFF' switched.

5.9 Tubular space heaters with thermostat suitable for operation at 240V, 1 phase,
50 Cycles, A.C. supply complete with switches located at convenient positions
shall be provided at the bottom of the cubicle to prevent condensation of
moisture. The watt loss per unit surface of the heaters shall be low enough to
keep surface temperature well below visible heat.

5.10 Auxiliary parts / items which has to be mounted adjacent or complementary to
the parts / items specified in part one shall be mounted inside the enclosure on
inner surface of panels or on supplementary structures.

5.11 Clamping devices shall be provided for fixing purchaser's incoming multicore
control cables. These clamps shall be of robust construction, capable of
clamping the cable firmly without injury to insulation. Cable type and sizes will
be specified later.


6. PAINTING :
A suitable rust resisting primer shall be applied on the interior and exterior
surfaces of the steel after removing rusts, greases, scale etc. An under coat to
serve as base and binder for the finishing coat shall be provided. Polished
cellulose enamel of light grey colour specified in part one, evenly spread on the
exterior of the panel & egg shall colour on the inside of panel shall be applied
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 34 of 71
as finishing coat. A small quantity of finishing paint shall be supplied for minor
touching up required at site.

7. WIRING :
Control Board panels shall be furnished completely wired, ready for
purchaser's connections at the terminal blocks. All inter panel wiring and
connections shall be furnished by the supplier.

7.1 Control wiring shall be securely supported, neatly arranged, readily accessible
and connected to equipment terminal and terminal blocks. Terminals on the
terminal blocks shall be marked and numbered by the supplier to show wiring
designation and shall be suitable for connecting purchaser's cables. Terminal
marking shall correspond to the designations on the wiring diagrams.

7.2 Wiring shall be carried out with 1100V grade cable of minimum 2.5mm
2
copper
wire. Wiring shall comprise of switchboard type, single core, multi-conductor
(Minimum three strands), and annealed copper wire with PVC insulation and
shall be fire retardant and vermin proof type suitable for the climatic conditions
outlined in part I.

7.3 Wire terminals shall be made with compression type tinned copper lugs which
firmly grip the conductor and the insulation. Wire terminations shall be provided
with insulated sleeves to reduce the possibility of short circuits.

7.4 Numbered sleeves shall be used in the control panel wiring. Sleeves bearing
identical numbers shall be placed at both, ends of the wire, the sleeve number
being shown in the panel wiring diagram. This is to facilitate checking of panel
wiring and to permit easy replacement of components during maintenance.

8. TROPICALIZATON :
Wiring, terminal blocks, relays instruments, meters and control devices shall be
suitable for application in tropical and shall be with suitable treatments to
protect them against tropical conditions which are conductive to rust and
fungus growth.

9. TEST FACILITIES :
Protective relays and electric meters shall have built in test blocks. Devices
which are not available with built in test blocks or which have been specified to
have separate auxiliary devices in their test circuits, shall be supplied with
external test facilities. Test blocks in such case, shall be mounted near the
auxiliary device.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 35 of 71
9.1 Test blocks shall provide complete isolation of energy meters, instruments and
relays, so that testing power can be supplied either from the instrument
transformers or from an out external source.

9.2 Terminal blocks with disconnecting facilities shall be used for C.T. , P.T.
secondary circuits and Auxiliary AC & DC supply.


10. GROUNDING :
Control panels shall be equipped with a ground bus bar of copper having a
minimum cross sectional area of 150 Sq.mm. Ground bus shall be securely
mounted across the inside base of the panels. Provisions shall be made for
extending the grounding bus bar to future adjoining panels. Earthing wires shall
be inter connected by using suitable terminals and clamp connections. Solder
connections shall not be employed.

11. INSTRUMENTS :
Indicating instruments shall be of flush type and shall have scale of 240 degree
and of 144mm x 144mm size and shall be of taught band suspension type.
These shall be mounted semi-flush on the panel with only flange projection.
Dials shall be white with black numbers and letters free dial, in parallel, is
preferred.


___________________ __________________________
SEAL OF THE FIRM SIGNATURE OF BIDDER.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 36 of 71

APPENDIX I
SECTION-III
BIDDING SCHEDULES

Schedule of Guaranteed Technical Particulars
for 66KV Control and Relay panels :

I. Control and Relay panels:
1. Dimensions of control and relay panels. (mm)
2. Complete dimensions of supporting channel. (mm)
3. Thickness of the steel plates proposed for use of panels.
(a) Front - (mm)
(b) Other sides (mm)

II. Control Switches for Circuit Breakers:
4. Make.
5. Type.
6. Type of handle provided.
7. No. of positions.
8. No. of contacts :
i) Normally closed.
ii) Normally open

III. Selector Switches :
9. Make.
10. Type.
11. Type of handle.
12. No. of position.
13. No. of contacts in each position :
i) Open.
ii) Closed.
14. Making capacity of contacts. (Amp)
15. Breaking capacity of contacts. (Amp)
16. Whether locking arrangement provided or not.



IV. SEMAPHORE INDICATORS : For circuit For isolators &
breaker. earth switches.
17. Make.
18. Type.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 37 of 71
19. Diameter of the disc. (mm)
20. Operating voltage. (Volts)
21. Burden. (Watts)
22. Whether latch in Mechanism provided.

V. INDICATING LAMPS :
23. Make.
24. Type.
25. Operating voltage.
26. Size of lens.
27. Wattage of lamp. (Watts)
28. Colour of lamp.

VI. SWITCH BOARD WIRING :
29. Insulation of wiring.
30. Size of wiring conductor for the following :
i) P.T. circuits. (mm
2
)
ii) C.T. circuits. (mm
2
)
iii) D.C. supply circuit. (mm
2
)
iv) Other circuits. (mm
2
)
31. Size of earthing bar for safety earthing. (mm
2
)
32. Type of terminals provided on wiring.
33. Wiring conductor / copper.

VII. Instruments and Meters :
Ammeter, voltmeter, wattmeter, KWH meter etc. :
34. (a) Type of instruments.
(b) Applicable IS
35. Size.
36. Whether magnetically shielded or not.
37. Limits of error in the effective range.
38. Maximum scale length.
39. Whether tropicalised.
40. V.A. burden. (VA)
41. Short time overload capacity.
42. i) Current coil (VA)
ii) Potential coil (VA)
43. Power consumption :
i) Current coil (Watts.)
ii) Potential coil. (Watts)
44. Temperature at which the instruments are
Calibrated. (C
0
)
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 38 of 71
45. Description of leaflet reference.
Nos. submitted.
46. Maker's name and country.
47. Type of selector switch.

VIII. Annunciators :
48. Type & make of annunciator.
49. Type of particulars of window.
50. Particulars of wiring.
51. Rated voltage. (Volts)
52. Power consumption. (Watts.)
53. Instantaneous making capacity
of contacts.
54. Breaking capacity.
55. Overall dimensions of annunciator.
56. Description leaflet No.

IX. Terminal Blocks:
57. Make & Type
58. Voltage grade
59. Current Rating

X. Energy meter TTB:
60. Make & Type
61. Voltage grade
62. Current Rating

XI. Relay Test Block
63. Make & Type
64. Voltage grade
65. Current Rating

XII. RELAYS :
Shall be as per Schedule B of Part III, Requirement of protective relays
for 66KV C&R Panels



___________________ __________________________
SEAL OF THE FIRM SIGNATURE OF BIDDER

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 39 of 71
APPENDIX II 66KV Control & Relay Panels
Details to be furnished by the Bidder

Sr.
No.
Particulars Make Type /
Designation
Catalogue /
Literature
attached
01 02 03 04 05
01. Automatic semaphore for
breaker.

02. Automatic semaphore for
isolator and Earth Switch

03. Indication lamps
04. Breaker control switch
05. Taut Band type Ammeter
144mm x 144mm and circular
scaled.

06. Voltmeter as in 5 above.
07. Selector switch for voltmeter
08. MW meter as in 5 above
09. Static KWH meter
10 MVAR meter as in 5 above.
11. Numerical Non directional
O/C-E/F relay (as per Part-III)

12. Numerical Differential relay (as
per Part III)

13. Numerical Directional O/C-E/F
relay (as per Part-III)

14. Numerical Unbalance Current
Relay

15. Electromagnetic / Static Over
Voltage Relay

16. Electromagnetic / Static Under
Voltage Relay

17 Leading Power Factor
Controller Relay

18 5 Minute Delay Relay / Timer
19. PT Selection Relay (applicable
to C & R Panel for two bus
system)

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 40 of 71
20. Trip circuit supervision relay (as
per Part-III)

21. Ten element auxiliary relay for
Buchholz, oil temp, winding
temp, PRV Trip. OLTC surge
Relay Trip & Low oil level Trip.
(as per Part-III)

22. Master Trip Relay (as per Part-
III)

23. 12/18 way facia annunciation
scheme

24 Panel illumination with door
operated switch.

25. Space heater
26. Thermostat
27. Cam type ON / OFF switch for
space heater

28. Mimic diagram.
29. Car type lockable handle.
30 Multipin 15A Socket
31 3.0 / 2.5 mm thick sheets steel
for front / all sides respectively.

32 Circuit wiring
33 Push buttons for trip ckt.
healthy.

34 Test terminal block. 1100V
grade.
(for energy meter)

35 M.S. foundation blots/nuts, size
18mm dia x120mm long.

36 Relay Test Block, 1100 V, 45A
37 Suitably rated fuses and fuse
links


NOTE : The bidder should clearly indicate the Make & Type of the above items
instead of indicating 'or its equivalent'.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 41 of 71
TECHNICAL SPECIFICATIONS OF RELAYS REQUIRED FOR 66KV C&R
PANELS
PART - III
SECTION I

SPECIFICATION FOR PROTECTIVE RELAYS

1.0 SCOPE

1.1 The overall scope of work proposed to be assigned to the successful bidder
according to this specification covers the following aspects.

1.1.1 The design, manufacture, testing at manufacturers works, supply and
demonstration of the Protective Relays as detailed in the Protective Relays
schedule, F.O.R destination supply thereof, testing and commissioning at
site.

1.1.2 Design and manufacture of Protective Relays to meet the requirements of
Protection of power equipments viz.

a) 66KV feeders
b) 220/66KV, 132/66KV, 66/11KV Auto/Two winding
transformers

1.1.2.1 Design and fabrication of Protective Relays along with all necessary
accessories like switches, indicating LED etc. to provide self contained
and ready to use Protective Relays as per this specification.

1.1.3 Complete testing at manufacturers works.

1.1.4 F.O.R. destination supply of completely assembled Protective Relays.

1.1.5 Testing and commissioning of these Protective Relays at site.

1.1.6 It is not the intent to specify completely all the details of the design and
construction of Protective Relays. However, the Protective Relays shall
conform in all respects to high standards of engineering, design and
workmanship as mentioned in clause 4.0 and shall be capable of
performing continuous commercial operation up to the suppliers
guarantee. In a manner acceptable to the purchaser, who will interpret
the meaning of drawings and specifications, and shall have the power to
reject any work of material which, in his judgment is not in accordance
therewith. The offered Protective Relays shall be complete with all
components necessary for their effective trouble free operation. Such
components shall be deemed to whether those are specifically brought
out in this specification and/or the commercial order or not.


GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 42 of 71
2.0 SCHEDULE OF REQUIREMENT

2.1 The consignee details/ Delivery instructions shall be issued by CE (Project)
GETCO, Corporate office, Vadodara, to the successful bidder after successful
inspection and testing of all relays & equipments at manufacturers works.

2.2 Any special tools jigs and testing equipment if required for the
maintenance/testing of the equipment offered shall be quoted as
optional items. Unit prices of such equipment shall be quoted.

2.3 Recommended spares

The bidder shall furnish in his offer, a list of recommended spare with unit
rates for Protective relays that may be required for trouble free operation for a
period of 10 years. The purchaser reserves the right of selection of items and
quantities of these spares to be ordered.


3.0 STANDARDS:

Unless otherwise specified elsewhere, in this specification, the rating,
performance and testing of Protective Relays shall conform to the latest
revisions, available at the time of placement of order of all relevant standards.
However the supplier shall submit the copies of English version of the
relevant standards applicable to the Protective Relays.

4.0 PRINCIPAL TECHNICAL PARAMETERS:

The Protective Relays covered in these specifications shall have the technical
requirements listed in Annexure III.

5.0 GENERAL TECHNICAL REQUIREMENTS:

5.1 SCOPE OF WORK.

5.1.1 Supply of Protective Relays as specified in accompanying schedule `G and
in this specification together with such auxiliary equipment and materials as
required. The bidder shall indicate make, type and designation of each
Protective Relays in the bid.
5.1.2 Preparation and furnishing of all the required drawings.
5.1.3 Testing of Protective Relays and associated equipment and furnishing of test
certificates
5.1.4 Preparation and furnishing of commissioning instructions, operation and
maintenance manuals with all operational features/optional features.
5.1.5 The successful tenders have to submit three sets of all types of drawings,
operation and maintenance manuals.

5.2 GENERAL REQUIREMENT FOR THE PROTECTIVE RELAYS:

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 43 of 71
Design, material selection and workmanship shall be such as to result in neat
appearance inside and outside with no weld, rivets or bolt heads apparent
from outside and with all exterior surface true and smooth.

5.2.0 RELAYS:

5.2.1 All relays shall confirm to the requirements of IS: 3231/IEC-60255. Relays shall
be suitable for flush or semi-flush mounting on the front with connections from
the rear.

5.2.2 All AC operated relays shall be suitable for operation at 50 Hz. AC voltage
operated relays shall be suitable for 110V VT secondary and current operated
relays for 1 or 5 amp. CT secondary. All DC operated relays and timers shall be
designed for the DC voltage specified, and shall operate satisfactorily between
80% and 110% of rated voltage. Voltage operated relays shall have adequate
thermal capacity for continuous operation.

5.2.3 The protective relays shall be suitable for efficient and reliable operation of the
protection scheme described in the specification. Necessary auxiliary relays
and timers required for interlocking schemes for multiplying of contacts suiting
contact duties of protective relays and monitoring of control supplies and
circuits etc. also required for the complete protection schemes described in the
specification shall be provided. All protective relays shall be provided with at
least two pairs of potential free isolated output contacts. Auxiliary relays and
timers shall have pairs of contacts as required to complete the scheme
contacts shall be silver faced with spring action. Relay case shall have
adequate number of terminals for making potential free external connections to
the relays coils and contacts, including spare contacts.

5.2.4 All protective relays, auxiliary relays and timers except the lockout relays and
interlocking relays specified shall be provided with self-reset type contacts. All
protective relay and timers shall be provided with externally hand reset positive
action operation indicators with inscription. All protective relays which do not
have built-in hand-reset operation indicators shall have additional auxiliary
relays with operating indicators (flag relays) for this purpose.

5.2.5 Timers shall be of continuous rating. Time delay in terms of ms obtained by the
external capacitor resistor combination is not acceptable. The variable pot type
timer is not acceptable.

5.2.6 No control relay which shall trip the power circuit breaker when the relay is de-
energized shall be employed in the circuits.

5.2.7 Provision shall be made for easy isolation of trip / CT / PT circuits of each relay
for the purpose of on line testing and maintenance. Test Block and Test
plugs/test handles, necessary for this, shall be included in contractors
scope of supply free of cost.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 44 of 71
5.2.8 Auxiliary seal-in-units if provided on the protective relays shall preferably be of
shunt reinforcement type. If series, relays are used the following shall be strictly
ensured.

a) The operating time of the series seal-in-unit shall be sufficiently shorter than
that of the trip relay in series with which it operates to ensure definite
operation of the flag indicator of the relay.

b) Seal in unit shall obtained adequate current for operation when one or
more relays operate simultaneously.

c) Impedance of the seal in- unit shall be small enough to permit satisfactory
operation of the trip coil on trip relays when the D.C supply voltage is
minimum.

5.2.9 All protective relays shall be provided with one extra isolated pair of contacts
wired to terminals exclusively for future use.

5.2.10 The setting ranges of the relays offered, if different from the ones specified
shall also be acceptable if they meet the functional requirements.

5.2.11 For numerical relays, the scope shall include the following.

a) Necessary licensed software and hardware to up/down load the data
to/from the relay from/to the personal computer installed in the sub
station. However, the supply of PC is not covered under this clause.
b) The software shall be suitable for operations like switching, retrieval of
information or changing of setting groups, retrieve oscillographic fault
data from the relay memory and to store fault record data as
oscillographic records in standard COMTRADE format. The software
shall be suitable to provide oscillographic data into several different
graphical representations that can be used to analyze the fault or event
captured by the relay It shall also be possible to calculate additional
values from the captured signals and displaying analog curve with time
base phasor diagram locus diagrams, harmonic graphs etc. Automatic
upload of DR files should be possible. The software shall be suitable for
creating / modifying logics of the protective relay.
c) The relay shall have communication facility, if specified in the technical
requirements listed in Annexure III, with suitable port for local
communication with PC and preferably also for future connectivity to
SCADA. In such case the relay shall be capable of supporting IEC-
60870-5-103 / IEC 61850-8-1 protocols, as specified.
d) The relay shall be provided with all the software mentioned in the
catalogue.

5.2.12 Any alternative/additional protections or relays considered necessary
for providing complete effective and reliable protection shall also be
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 45 of 71
offered separately. The acceptance of this alternative/additional
equipment shall lie with the GETCO.

5.2.13 All the bidders have to demonstrate, mentioned fully programmable
numerical relays, as may be demanded by the GETCO, free of cost
within 15 days after issue of intimation for verifying its functions,
features, accuracies etc. the testing shall be performed by fully 3 phase
automatic testing set. The relays, which dont meet requirements, dont
function as per GTP will not be accepted.

5.2.14 The bidder shall include in his bid a list of installations where the relays
quoted have been in satisfactory operation.

5.2.15 All relays and their drawings shall have phase indications as R-Red, Y-
Yellow, B-Blue.

6.0 TESTS:

The bidder shall submit the complete type test reports as stated hereunder for
the offered relay along with the offer otherwise the offer shall be liable to be
rejected. These tests must have been conducted in the NABL approved
laboratory as per IEC 60255, IEC 60068, IEC 61000, IEC 60529, IEC 61010-1
within last 5 years prior to date of validation of the offer.

a. Performance tests:
i. Accuracy requirements
ii. Limits of operating range of auxiliary energizing inputs and auxiliary
Voltage dependence.
iii. Limits of frequency range and frequency dependence
iv. Rated burden
v. Mechanical Endurance test
vi. Characteristic and Functional test

b. Thermal requirements:
i. Maximum allowable temperature
ii. Limits of short time thermal withstand value of input energizing
quantities.
iii. Limiting dynamic value

c. Insulation Tests:
i. Dielectric Tests
ii. Impulse Voltage withstand Test
iii. Insulation resistance measurement

d. Influencing Quantities
i Permissible ripples
ii. Interruption of input voltage


GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 46 of 71
e. Electromagnetic Compatibility Test:
i. 1 MHZ burst disturbance test
ii. Electrostatic Discharge Test
iii. Radiated Electromagnetic Field Disturbance Test
iv. Electrical Fast transient Disturbance Test
v. Conducted Disturbances Tests induced by Radio Frequency Field
vi. Magnetic Field Test
vii. Emission (Conducted and Radiated) Test.
viii. Surge Immunity Test

f. Contact performance Test
i. Contact making/Breaking capacity test
ii. Continuous capacity test

g. Environmental tests:
i. Dry Cold Test
ii. Dry Heat test
iii. Storage temperature test
iv. Damp heat Cyclic test

h. Mechanical Tests:
i. Vibration response & Vibration endurance test
ii. Bump test
iii. Shock response test
iv. Seismic test

i. Enclosure Test:
i. Degree of Protection test IP51

j. Safety Test:
i. Single fault condition assessment
ii. Earth bonding impedance test
iii. Mechanical resistance to shock and impact
iv. Protection against electrical shock
v. Protection against the spread of fire


The purchaser reserves the right to demand repetition of some or all the type
test in the presence of the purchasers representative. For this purpose the
bidder may quote unit rates for carrying out each type test.

6.1 Acceptance and routine tests.

All acceptance and routine test as stipulated in the relevant standards shall be
carried out by the supplier in presence of Purchasers representative without
any extra cost.

Immediately after finalization of the programme of type / acceptance/ routine /
testing the supplier shall give two weeks advance intimation to the purchaser to
enable him to depute his representative for witnessing the tests.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 47 of 71

6.2 QUALITY ASSURANCE PLAN:

6.2.1 The bidder shall invariably furnish, along with his offer, the quality assurance
plan adopted by him/his sub-suppliers in the process of manufacturing all major
equipment/component.

6.2.2 Precaution taken for ensuring usage of quality raw materials and sub-
components shall be stated in the quality assurance plan.

6.2.3 The bidder should specifically express their consent to accept additions,
revisions to their quality assurance plan to meet the purchasers requirements if
needed. The final quality assurance plan to be adopted, with mutual consent,
shall be decided after discussion with successful bidder.
6.2.4 The offers are likely to be rejected if the quality assurance plan & details
as per clause No. 6.2.1 to 6.2.3 are not submitted along with the offer.

7.0 PERFORMANCE GUARANTEE

All Protective Relays supplied against this specification shall be guaranteed
for a period of 24 months from the date of commissioning.

8.0 DOCUMENTATION:

The bidder shall furnish as a part of their offer, complete set of technical
literature/manuals in original, in triplicate copy and typical schematic drawings
in respect of each Protective Relays offered by them.

8.1 Demonstration

During technical scrutiny of the bid, purchaser may ask to give
demonstration of the offered Protective Relays at purchasers site. The
bidder shall demonstrate the Protective Relays within one week of
intimation from purchaser.

9.0 PACKING AND TRANSPORT

9.1. All Protective Relays/material shall be suitably packed for transport, carriage at
site and outdoor storage during transit. The contractor shall be responsible for
any damage to the Protective Relays during transit due to improper and
inadequate packing. The cases containing easily damageable material shall be
very carefully packed and marked with appropriate caution symbols i.e.
`FRAGILE `HANDLE WITH CARE, `USE NO HOOK etc. The contents of
each package shall bear marking that can be readily identified from the
package list and packing shall provide complete protection from moisture,
termites and mechanical shocks etc.

9.2 Wherever necessary proper arrangement for attaching slings for lifting shall be
provided and all packages clearly marked with gross weight, signs showing
`UP and DOWN sides of boxes, contents of each package, order no. and
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 48 of 71
date, name of the plant/SS/ of which the material in the package forms part of
and any handling and unpacking instructions considered necessary. Any
material found short inside the intact packing cases shall be supplied by the
manufacturer/supplier without any extra cost.

9.3 Bidder shall ascertain, prior to shipment, from concerned authorities, the
transport limitations like weight and maximum allowable package size for
transportation. Fragile material such as Instruments and other glass material
shall be carefully covered with shock absorbing protective materials, such as
thermocol, silica gel or equivalent moisture absorbent material in small cotton
bags shall be placed inside the packing wherever necessary

9.4 Each consignment shall be accompanied by a detailed packing list containing
the following information.

a) Purchase order No.
b) Name of consignee
c) Details of consignment
d) Destination
e) Total weight of consignment
f) Handling and unpacking instructions.
g) Bill of materials indicating contents of each package
h) Sign showing upper/lower side of the crate.

10.0 SCHEDULES:

10.1. The bidder shall fill in the following schedules which form part of the tender
specification and offer. If the schedules are not submitted duly filled in with the
offer, the offer is likely to be rejected.

Schedule B Guaranteed Technical particulars
Schedule G List of the offered Protective Relays.

10.4 Unless other wise brought out separately by the bidder in the schedules of
deviations the protective relay offered shall be deemed to conform to the
specification, as listed in this tender, scrupulously.

10.3 For any deviation from the specification specifically brought out in the
schedules shall be supported by authentic documents, standards and
clarifications, otherwise the offer may be liable for rejection. Any deviation from
the specification shall be high lighted giving reasons and unit prices.

10.4 If the Protective Relay is being designed and manufactured in collaboration
with other manufacturer, the following information shall be submitted by the
bidder along with his offer.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 49 of 71

a) Copy of collaboration between the bidder and manufacturer.
b) List of orders for offered Protective Relays, executed/ being executed by
the supplier.

11 INFORMATION TO BE FILLED IN INVARIABLY BY THE BIDDER:

For ready reference of the purchaser, the items of information required to be
invariably furnished by him in his offer, are listed below:

1. Four copies of the authentic English translation of each of the
standards to which the offered Protective Relays conforms.
2. Schedule - `B and `G .
3. Documents and drawing listed in Clause no. 8.0

12 UNIT RATE FOR OTHER ACCESSORIES.

12.1 The bidder has to submit along with their offer unit rate of all the type of
accessories required for trouble free operation of the protective relay for
minimum 10 years. The offers without above unit rate are likely to be rejected.
12.2 The above unit rate shall be kept valid till the expiry of guarantee period.

13.0 GUARANTEE FOR MAINTENANCE SPARES AND SERVICES:

The bidder shall guarantee for supplying maintenance spares and services as
well as repairing of protective relay for a period of the life expectancy of 10
years.

14.0 GENERAL:

a. The successful bidder has to provide reproducible tracings/ soft copy for all the
drawings as a part of supply contract to the CE (Projects) GETCO, HO,
VADODARA for documentation.

b. The successful Bidder has to provide instruction manual, O & M manual,
Commissioning manual, all drawings, literature etc. for all relays and devices.
Detailed circuit diagrams with trouble shooting protocols to all consignee
destinations as well as to the ACE (Testing), GETCO, and the CE(Projects)
GETCO, HO, VADODARA.


c. The successful bidder has to do testing/commissioning of protection relays
to be supplied of each type, by deputing his Service Engineer free of cost.

d. The successful bidder has to depute his service engineer along with necessary
tools/kits/instruments/testing accessories required for testing, commissioning
of relays and devices.

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 50 of 71
ANNEXURE: I

SCHEDULE OF REQUIREMENT AND DESIRED DELIVERY

Sr.
No.
Name of Sub-
Station
Particulars Qty. Desired
Delivery
Successful bidder has to
collect the details of
substations and locations
from CE (Project), GETCO,
Corporate Office, Baroda.





SIGNATUARE AND
SEAL OF BIDDER

































GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 51 of 71
ANNEXURE: II
LIST OF STANDARDS - GENERAL

Sr.No. Standard no. Title
1. IS-3231 Electrical relays for power system protection.
2. IEC-255
Part 1 to 3
Electrical relays for power system protection.
3. BS 142 Electrical relays for power system protection
4. IS 1248
IS 2419
Indicating instruments.
5. BS 89 Indicating instruments
6. IS 6236 Recorders
7. BS-90 Recorders
8. BS 152 Relay coding, auxiliary wiring and panel and
wiring.
9. IS 8686 Static protective relays
10. IS 2147 Degree of protection for cubicles
11. IS 5 Colour for ready mixed paints and channels.
12. IS 3842
Part- II to IV
Application guide for protection
13. IS 6005 Code of practice for phosphating iron and
steel
14. IS-5578 Guide for making of insulated conductors.
15. IS 11353 Guide for uniform system of marking and
identification of conductors and apparatus
terminals.
16. IS 9482-
1980
Characteristics values of input and outputs of
single side band PLCC terminals.
17. IS- 9528
Part-1 and 2
Planning of (single side band) power line
carrier systems.
18. IS 10706
1983
Methods of tests for single side band PLC
terminals.
19. IS-8997-
1978
Coupling device for PLC systems (note This
is to be referred for the PLCC terminal
connections.
20. IEC-686-1 Transducers
21. IS 2206 Fuses
22. IS 9000 Dry heat test
23. IEC 801-4 Electrical heat transient bursts.
24. IS 694 PVC Insulated cable for working voltage up
to & including 1100 volt.

List Of IEC Standards Protective Relays

Sr.No. Standard no. Title
Characteristic, Performance, Accuracy, Burden, Mechanical endurance test
1. IEC-60255-6 Thermal requirements
Mechanical requirements
Limiting dynamic value
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 52 of 71
Accuracy requirements
Rated Burden
2. IEC-60255-11 Interruption to and alternating
component in DC aux. Energizing
quantity
3. IEC-60255-3, IEC-60255-12,
IEC-60255-13
Relay characteristic & Performance
test
4. IEC-60255-23 Contact Performance test
Electromagnetic Compatibility type test:
1. IEC-60255-22-1, Class-III, 1MHz burst immunity test
2. IEC-60255-22-2, Class-III

IEC-61000-4-2, Class-III
Electrostatic discharge test
Direct application
Indirect application
3. IEC-60255-22-4, Class-A Fast transient / burst immunity test
4. IEC-, 60255-22-5 Surge immunity test
5. IEC-60255-22-7, Class-A Power frequency immunity test
6. IEC-61000-4-8, Class-V Power frequency magnetic field
test
7. IEC- 60255-22-3 Radiated electromagnetic field
immunity
8. IEEE/ANSI/C37.90.2 Radiated electromagnetic field
disturbance
9. IEC- 60255-22-3 Immunity to conducted
disturbances induced by radio
frequency fields test
10. IEC- 60255-25 Electromagnetic emission tests
- Conducted emission test
- Radiated emission test
Insulation tests:
1. IEC- 60255-5 Dielectric test
Impulse voltage test
Insulation resistance
Environmental tests:
1. IEC-60068-2-1 Cold test
Storage test
2. IEC-60068-2-2 Dry heat test
3. IEC-60068-2-3 Damp heat test, steady state
4. IEC-60068-2-30 Damp heat test, cyclic
5. IEC-60068-2-48 Storage temperature test
CE compliance
1. IEC- 60255-26 Electromagnetic compatibility
requirements
Mechanical tests
1. IEC- 60255-21-1 Vibration
2. IEC- 60255-21-2 Shock and bump
3. IEC- 60255-21-3 Seismic
Degree of protection test
1. IEC 60529 Degree of Protection Provided by
enclosure test
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 53 of 71
Safety test
1. IEC 61010-1 Single fault condition assessment
Earth bonding impedance test
Mechanical resistance to shock
and impact
- Rigidity test
- Impact hammer test
Protection against electrical shock
Protection against the spread of
fire








































GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 54 of 71
ANNEXURE: III

PRINCIPAL TECHNICAL PARAMETERS OF RELAYS

SR.
NO.
Item Specification
1.




































DIRECTIONAL
O/C AND E/F
PROTECTION
RELAYS.

































(A) Features:

a) Shall be Numerical type.
b) Shall have 3 over current and 1 Earth Fault element.
c) TRUE RMS Measurement.
d) Have selectable and front panel programmable normal,
inverse, very inverse, extremely inverse & long
inverse IEC / ANSI Characteristic.
e) Selectable CT Secondary. i.e. 1A & 5A
f) High set over current with selectable time delay.
g) High set Earth fault with selectable time delay
h) Have adjustable characteristic angle, lead/ lag, for
Directional over current/ Earth Fault respectively.
i) Shall decide directionality through zero sequence
quantity, derived internally.
j) Shall have Breaker Failure Protection as in built feature.
k) Include hand reset Flag/LED indicators for phase
identification for all faults.
l) Readable Human Machine Interface with LED/ LCD
display.
m) Should be able to store at least last 3 events with fault
data viz. Fault current, Faulty Phase etc. with time
stamp
n) Shall have in built Disturbance Recorder with total time
minimum 3 sec.
o) Shall have continuous self hardware & software
monitoring and diagnostic features
p) Relay offered shall be communicable type.
q) Relay shall have on line testing facility as per clause no.
5.2.7.
(B) Technical Parameters:

1. Analogue input:
Rated Current : 1A & 5A (site selectable), 50 Hz
2.5 Hz
Rated Burden : <0.05VA/0.3 VA for 1/5 Amp
Over load capability: 4xIn continuous
100xIn 1 Sec.
25xIn 3 Sec.
250xIn Dynamic
Rated Voltage: 110/63.5V, 50 Hz 2.5 Hz
Rated Burden : <0.3 VA per phase
Over load capability: 2xVn continuous

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 55 of 71
2. Auxiliary Supply: 110/220 V DC 15 %
Power consumption: < 15W
Ripple (peak to peak): < 12%

(C) Relay settings:
1. Over Current: 50% - 200%
(In steps of 5%)
2. Earth Fault: 5% - 80%
(In steps of 5%)
3. High set O/C: 0.5 15 times In or more.
4. High set E/F: 0.5 12 times In or more.
5. Time multiplier for IDMT: 0.05 1.0
(In steps of 0.025)
(Independent for O/C & E/F)
6. Time delay for high set element : 0.02 to 2 sec
(in steps of 0.01 sec)
7. Pick up: Within 1.1 times of set current value.
8. Reset current: 95% to 90% of pick-up current.
9. Operating Time: As per selectable characteristic.
For Inst. Element 50ms for 2xIn.
10. LBB feature :
Current setting range 0.1 to 2 X In
Time delay - 0.1 to 2 sec(In steps of 0.010
Sec)

(D) Other Features:

1. Binary Inputs : Minimum 5 Nos.
2. Outputs :
Provide sufficient number of potential free contacts to
cater the needs of connection to alarm annunciation.
Trip contacts: Minimum 2 N/O contacts with
- Continuous carry 5 A
- Make & Carry for 0.5 s 30 A
- Make & Carry for 3.0 s 15 A
Signaling contact: Minimum 4 Nos.
(Programmable at site)

3. Local PC Communication:
Ports - Front RS232 and Rear RS485
Protocol - IEC-60870-5-103
4. Housing
Flush Mounting
Screw Terminals (O Lug for CT Connection)
Degree of Protection IP51
5. Temperature and humidity
(a) Ambient temp -10 to 55
o
C
(b) Relative humidity 10% to 90%
Non Condensing
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 56 of 71
(c) Operate range 0-95%
(d) Storage temp. -40 to 70
o
C

2 NON-
DIRECTIONAL
O/C AND E/F
PROTECTION
RELAYS.





























(A) Features:

a) Shall be Numerical type.
b) Shall have 3 over current and 1 Earth Fault element.
c) TRUE RMS Measurement.
d) Have selectable and front panel programmable normal,
inverse, very inverse, extremely inverse & long
inverse IEC / ANSI Characteristic.
e) Selectable CT Secondary i.e. 1A & 5A
f) High set over current with selectable time delay.
g) High set Earth fault with selectable time delay
h) Shall have Breaker Failure Protection as in built feature.
i) Include hand reset Flag/LED indicators for phase
identification for all faults.
j) Readable Human Machine Interface with LED/LCD
display.
k) Should be able to store at least last 3 events with fault
data viz. Fault current, Faulty Phase etc. with time
stamp.
l) Shall have Disturbance Recording facility with total time
minimum 3 sec.
m) Shall have continuous self hardware & software
monitoring and diagnostic feature.
n) Relay offered shall be communicable type.
o) Relay shall have on line testing facility as per clause no.
5.2.7.
(B) Technical Parameters:

1. Analogue input:
Rated Current : 1A & 5A (site selectable), 50 Hz
2.5 Hz
Rated Burden : <0.05VA/0.3 VA for 1/5 Amp
Over load capability: 4xIn continuous
100xIn 1 Sec.
25xIn 3 Sec.
250xIn Dynamic
2. Auxiliary Supply: 110/220 V DC 15 %
Power consumption: < 15W
Ripple (peak to peak): < 12%

(C) Relay settings:
1. Over Current: 50% - 200%
(In steps of 5%)
2. Earth Fault: 5% - 80%
(In steps of 5%)
3. High set O/C: 0.5 15 times In or more.
4. High set E/F: 0.5 12 times In or more.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 57 of 71
5. Time multiplier for: 0.05 1.0
(In steps of 0.025)
(Independent for O/C & E/F)
6. Time delay for high set element : 0.02 to 2 sec
(in steps of 0.01 sec)
7. Pick up: Within 1.1 times of set current value.
8. Reset current: 95% to 90% of pick-up current.
9. Operating Time: As per selectable characteristic.
For Inst. Element < 40 ms for 2xIn.
10. LBB feature :
Current setting range 0.1 to 2 X In
Time delay - 0.1 to 2 sec(In steps of 0.010
Sec)

(D) Other Features:
1. Binary inputs: Min 5 nos.
2. Outputs:
Trip contacts: Minimum 2 N/O contacts with
- Continuous carry 5 A
- Make & Carry for 0.5 s 30 A
- Make & Carry for 3.0 s 15 A
Signaling contacts : Minimum 4 Nos.
(Programmable at site)
3. Communication:
Ports - Front RS232 and Rear RS485
Protocol - IEC-60870-5-103
4. Housing
Flush Mounting
Screw Terminals (O Lug for CT Connection)
Degree of Protection IP51

5. Temperature and humidity
(a) Ambient temp -10 to 55
o
C
(b) Relative humidity 10% to 90%
Non Condensing
(c) Operate range 0-95%
(d) Storage temp. -40 to 70
o
C
3 DIFFERENTIAL
RELAY WITH
HIGHSET
A) Differential % BIASED protection
i). Be high speed with an operating time of less than
30 ms at 5 times the rated current.
ii). Shall have principle of biased differential type with
highset feature and adjustable slope characteristic.
iii). Shall be numerical type.
iv). Shall have true RMS measurement.
v). Shall have continuous self monitoring and
diagnostics features.
vi). Shall have ratio and phase angle matching
through software.
vii). Shall have site selectable CT secondary 1& 5 A
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 58 of 71
viii). Be suitable for three phase two winding
transformer.
ix). Be stable on heavy through faults.
x). Be immune to magnetizing inrush current.
xi). Have features to provide stability under over
excited conditions and have 2
nd
harmonic
restraint features.
xii). Shall have the following functions.
i. Differential Protection
ii. Restricted Earth Fault Protection.
iii Breaker Failure Protection
xiii). Be triple pole type with faulty phase identification/
indication.
xiv). Provide sufficient number of potential free contacts
to cater the needs of connection to alarm
annunciation. Data acquisition and optional trip
facility to be connected by purchaser where
needed.
xv). Be supplied along with all suitable Original
Customized licensed software &
communication cable for local and remote
communications, analysis of fault etc.
xvi). Have a local user interface (MMI) comprising of a
2-3 line alphanumeric LCD display and a soft
touch key pad to access the settings, events and
records in the relay.
xvii). Have a front RS232/RJ45/USB communication
ports for use with a PC locally for local access to
settings, events and recorders.
xviii). Have rear RS485 communication port to support
all the facilities available via the integral user
interface or communication based on IEC60870-5-
103 connectivity.
xix). Have a disturbance recording feature to record
graphic form of instantaneous values of current in
all windings in analog channels during faults and
disturbances for the pre fault and post fault period.
The disturbance recorder shall have the facility to
record the following external digital channel
signals apart from the digital signals pertaining to
differential relays.

a. HV Each Breaker pole status i.e. 1 no. inputs
b. LV Each Breaker pole status i.e. 1 no. inputs
c. Buchholz / OLTC Buchholz alarm / trip i.e. 4
no. inputs.
d. WTI/OTI/PRV alarm /trip of transformer.
e. External signals as per CRP schematics as
finalized during detailed engineering.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 59 of 71
xx). Have internal battery used to backup the clock
and other circuits like switching status, fault
indication etc. The battery shall be reliable and
long lasting. There shall be an alarm and
indication for declining battery status.
xxi). DR & SER shall have date & time stamping
xxii). Storage capability of DR- Minimum 10 no. of
DR (Duration of each DR shall be 2 Sec).
xxiii). The relay shall have on line testing facility
as per clause no. 5.2.7

B) REF feature

i). Be single pole type
ii). Be high impedance differential protection
iii). Be high speed circulating current type
iv). Be tuned to the system frequency
v). Be high speed with typical operating time of less than 30
ms


Technical Parameters:

1. Analogue input:
Rated Current : 1A & 5A (site selectable), 50 Hz
2.5 Hz
Rated Burden : <0.05VA/0.3 VA for 1/5 Amp
Over load capability: 4xIn continuous
100xIn 1 Sec.
25xIn 3 Sec.
250xIn Dynamic

2. Auxiliary Supply: 110/220 V DC 15 %
Power consumption: < 15W
Ripple (peak to peak): < 12%

Differential protection settings:
1. Diff. Current: 10% - 50% In
2. Diff. High Current 2 10 times In
(In steps of 1)
3. Bias Diff Current 10% - 50% In
4. 2
nd
Harmonic Restraint ratio 10 to 80%

REF Protection Settings:

5. Differential Current 0.1 to 1 A

Other Features:

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 60 of 71
6. Binary Inputs: Min 8 nos. and suitable for station Aux.
DC (Programmable at site)
7. Output contacts
Trip contacts: Minimum 2 N/O contacts with
- Continuous carry 5 A
- Make & Carry for 0.5 s 30 A
- Make & Carry for 3.0 s 15 A
Signaling contacts : Minimum 6 Nos and suitable for
Station Aux. DC (Programmable at
site)
8. Communication:
Front Port - RS232 / USB/ RJ45
Rear Port - RS485
Protocol - IEC 60870-5-103

9. Housing
Flush Mounting
Screw Terminals (O Lug for CT Connection)
Degree of Protection IP51

10. Temperature and humidity
(a) Ambient temp -10 to 55
o
C
(b) Relative humidity 10% to 90%
Non Condensing
(c) Operate range 0-95%
(d) Storage temp. -40 to 70
o
C

4 UNBALANCE
CURRENT
RELAY
The relay shall be suitable for rated current of 1 amp & have
suitable D.C/D.C converter suitable for 110 / 220 V D.C.
(Preferably 88V TO 300V D.C.). DC voltage range of 15% to
+ 25% harmonic level is max, .2% at rated value. It shall
1) be Single pole OR two pole type (in case of controlling 2
Banks)
2) be of numerical type
3) be two Stage relay so that alarm & tripping can be set at
different values of current
4) have current setting of 10- 50 % of rated current.
5) have alarm and trip output contacts.
6) have a local user interface (MMI) comprising of a 2-3 line
alphanumeric LCD display and a soft touch key pad to
access the settings, events and records in the relay.
7) include hand reset flag/LED indicator.
8) be high speed with typical operating time of less than 25
ms.
9) be provided with sufficient number of potential free contacts
to cater the needs of connection to alarm annunciation.
Data acquisition and optional trip facility to be connected by
purchaser whenever needed.
10) store minimum 3 Nos of fault data.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 61 of 71

5 OVER
VOLTAGE
RELAY
The relay shall
1) be electromagnetic/static type
2) monitor all three phases
3) have adjustable voltage setting range of 100 150% of
rated voltage & adjustable time setting range of 0 to 10
seconds continuously or in step of 1 Sec.
4) have independent alarm & trip out put contacts.
5) have drop off to pick up ratio equal to or greater than 95%.
6) be provided with Hand reset flag/LED type operation
indicator.
7) have sufficient potential free contacts to cater for local LED
indicator & for DR & SER.

6 UNDER
VOLTAGE
RELAY
The Relay shall
1) be electromagnetic/static type
2) be triple pole type.
3) have adjustable voltage setting range of 40 90% of rated
voltage & adjustable time setting range of 0 to 10 seconds
continuously or in step of 1 Sec.
4) be provided with Hand reset flag/LED type operation
indicator.
5) have minimum two potential free NC contact. Self reset
type.
7 AUXILIARY
RELAYS FOR
TRANS.
TROUBLES
(1). Buchholz trip. 1 No.
(2). Buchholz alarm --- 1 No.
(3). OLTC Buchholz trip. --- 1 No.
(4). Oil temperature trip. --- 1 No.
(5). Oil temperature alarm. 1 No.
(6). Winding temperature trip. --- 1 No.
(7). Winding temperature alarm. --- 1 No
(8). P.R.V. trip. --- 2 No.
(9). Low oil level alarm 1 No.
Provide sufficient number of potential free contacts to cater the
needs of connection to alarm annunciation, Data acquisition
and optional trip facility to be connected by purchaser where
needed. The relay shall have clear visible indication flag/LED.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 62 of 71
8 HIGH SPEED
TRIP RELAY
As per the system design sufficient relays having potential free
contacts for trip circuit 1 & 2 of main / coupler breaker shall be
provided. The relay shall
1) Have Heavy Duty Contacts for trip circuit.
2) Provide sufficient number of potential free contacts to cater
the needs of connection to alarm annunciation, Optional trip
facility to be connected by Purchaser where needed.
2) It shall be instantaneous with inherent operating time less
than 10 ms. It shall have 8 NO & 2NC hand resetting type
contacts. It shall be 220/110V DC operating and preferably
provided with single coil.
3) Be provided with operation indicators.
9 TRIP CIRCUIT
SUPERVISION
RELAY
Trip circuit supervision relay shall be provided for each trip coil
of the breaker.
The relay shall
a) Monitor the complete trip circuit with circuit breaker in pre-
close & post-close condition.
b) Monitor loss of battery supply.
c) Have a delay on drop off
d) Provide alarm output.
e) Include hand reset flag indicator.
f) Provide sufficient number of potential free contacts to meet
the scheme & future requirement.
10 PT SELECTION
RELAY
The necessary PT selection relay shall be provided for bus
voltage selection. It shall be provided with sufficient contacts
for selected P.T. to protection and metering circuits and D.C
permissive to protection. The relay should be latched type with
operating and resetting coils. The relay shall have clear visible
indication flag/LED.
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 63 of 71
SCHEDULE B

GUARANTEED TECHNICAL PARTICULARS FOR RELAYS

(TO BE FILLED IN BY THE BIDDER AND FURNISH WITH TECHNICAL BID)

The GTP is to be filled up in this format and, in the page of Tender
Specification only, to be submitted in duplicate along with the offer. This is
intended for speedy comparison of various bidders GTP. The Bidder shall
fill in the particulars against appropriate items in respect of each rating and
type of Protective Relays offered in the broad categories listed below:



PARAMETERS Bidders
comment
A DIRECTIONAL OVERCURRENT AND EARTH FAULT
RELAY

1 Make
2 Type
3 Whether comply to Principle Technical Parameters as
per Annexure III

4 Whether Numerical and have true RMS measurement.
5 Display type for HMI
6 Give the details of self monitoring (Hardware &
Software) and indication/ alarm facility on internal relay
failure

7 Current Input (CT Secondary) with thermal
rating and burden
Whether selectable from front panel at site
Voltage Input (VT Secondary) with thermal
rating and burden

8 Auxiliary Supply and its burden with permissible
tolerance & Ripple

9 No. of O/C & E/F elements
10 Current setting range for Over Current element
11 Current setting range for Earth Fault element
12 Type of Characteristics available
Whether selectable from front panel at site

13 MTA setting for Phase fault
Whether site adjustable

14 MTA setting for Earth Fault
Whether site adjustable

15 Criterion for decision of directionality
16 High set current setting range for Over Current
17 High set current setting range for Earth Fault
18 Time multiplier
19 Reset Ratio
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 64 of 71
20 Built-in Breaker Failure Protection
1. Current Setting range
2. Timer range
3. No. of O/P Contacts available for this feature.

21 No. of fault event can be stored
Type of data stored on fault

22 Maximum duration for DR on each fault
23 No. of Binary Inputs
24 No. of outputs. (Trip/ Signaling)
25 Contact rating
i) Make and carry continuously
ii) Make and carry for 0.5 sec.
iii) Break resistive load and inductive load with 40m
sec. time constant
iv) Whether self reset or hand reset

26 Ref. no. of descriptive leaflet enclosed
27 Temp. rise over ambient temperature
28 One minute power frequency withstand volt.
29 Degree of Protection
30 Mounting and dimensional details.
31 Overall dimensions
32 Weight
33 Temperature and humidity
(a) Ambient temp
(b) Relative humidity Non Condensing
(c) Operate range
(d) Storage temp.

34 Any other information
B NON-DIRECTIONAL OVERCURRENT AND EARTH
FAULT RELAY

1 Make
2 Type
3 Whether comply to Principle Technical Parameters as
per Annexure III

4 Whether Numerical and have true RMS measurement.
5 Display type for HMI
6 Give the details of self monitoring (Hardware &
Software) and indication/ alarm facility on internal relay
failure

7 Current Input (CT Secondary) with thermal
rating and burden
Whether selectable from front panel at site

8 Auxiliary Supply and its burden with permissible
tolerance & Ripple

9 No. of O/C & E/F elements
10 Current setting range for Over Current element
11 Current setting range for Earth Fault element


GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 65 of 71
12 Type of Characteristics available
Whether selectable from front panel at site

13 High set current setting range for Over Current
14 High set current setting range for Earth Fault
15 Time multiplier
16 Reset Ratio
17 Built-in Breaker Failure Protection
1. Current Setting range
2. Timer range
3. No. of O/P Contacts available for this feature.

18 No. of fault event can be stored
Type of data stored on fault

19 Maximum duration for DR on each fault
20 No. of Binary Inputs
21 No. of outputs. (Trip/ Signaling)
22 Contact rating
i) Make and carry continuously
ii) Make and carry for 0.5 sec.
iii) Break resistive load and inductive load with 40m
sec. time constant
iv) Whether self reset or hand reset

23 Ref. no. of descriptive leaflet enclosed
24 Temp. rise over ambient temperature
25 One minute power frequency withstand volt.
26 Degree of Protection
27 Mounting and dimensional details.
28 Overall dimensions
29 Weight
30 Temperature and humidity
(a) Ambient temp
(b) Relative humidity Non Condensing
(c) Operate range
(d) Storage temp.

31 Any other information
C DIFFERENTIAL RELAYS
1 Make
2 Type and designation
3 Whether comply to Principle Technical Parameters
as per Annexure III

4
Whether Numerical measurement.

5
Whether continuous self monitoring and
diagnostic feature is available

6 Whether Differential Protection, Restricted Earth
Fault Protection & Breaker Failure Protection
features are available.

7
Be supplied along with all suitable Original
Customized licensed software & communication
cable for local and remote communications,

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 66 of 71
analysis of fault etc.

8 Have a local user interface (MMI) comprising of a 2-3
line alphanumeric LCD display and a soft touch key
pad to access the settings, events and records in the
relay.

9 Have a disturbance recording feature to record
graphic form of instantaneous values of current in all
windings in analog channels during faults and
disturbances for the pre fault and post fault period.

10
Have internal battery used to backup the clock
and other circuits like switching status, fault
indication etc. The battery shall be reliable and
long lasting. There shall be an alarm and
indication for declining battery status.

11
DR & SER shall have date & time stamping.

12
Storage capability of DR- Minimum 10 no. of DR
(Duration of each DR shall be 2 Sec).

13
Current Input (CT Secondary) with thermal
rating and burden
Whether selectable from front panel at site

14 Auxiliary Supply and its burden with permissible
tolerance & Ripple

15 Operating principle
16 Number of CT inputs
17 Min. Operating current
18 Is the slope setting variable.
19 Setting ranges available
Differential Protection
Diff. Current
Diff. High set Current
Bias Diff Current
Bias slope
Feature
2nd Harmonic Restraint
5th Harmonic Restraint

20 REF Protection current setting range
21 Nos of Binary inputs
Whether programmable at site


22 Nos of Output contacts for
Tripping
Signaling
Whether programmable at site


23 Power consumption
i) Operating circuit

GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 67 of 71
ii) Restraining circuit
24 Whether internal phase angle and ratio correction is
available.

25 Operating time at 5 x In
26 Resetting ratio
27 Three pole instantaneous high set units provided.
28 Nos Output contacts and their ratings.
(i) Make and carry continuously
(ii) Make and carry for 0.5 sec.
(iii) Make and carry for 3.0 sec.
(iv) Break resistive load and inductive load with 40m
sec. time constant
(v) Whether self reset or hand reset

29 Communication ports
Front
Rear

30 Communication Protocol
31 Housing
Mounting
Terminals
Degree of Protection

32 Temperature and humidity
(a) Ambient temp
(b) Relative humidity Non Condensing
(c) Operate range
(d) Storage temp.

D UNBALANCE CURRENT RELAY
1 Make
2 Type
3 Whether comply to Principle Technical Parameters
as per Annexure III

4 Whether Numerical and have true RMS
measurement.

5 Display type for HMI
6 Give the details of self monitoring (Hardware &
Software) and indication/ alarm facility on internal
relay failure

7 Current Input (CT Secondary)
Whether selectable from front panel at site

8 Auxiliary Supply and its burden with permissible
tolerance.

9 No. of poles
10 Current setting range for Unbalance Current alarm
for current input 1 & 2

11 Current setting range for Unbalance Current trip for
current input 1 & 2

12 Burden at CT inputs
No. of fault event can be stored
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 68 of 71
Type of data stored on fault
13 No. of Binary Inputs
14 No. of outputs. (Trip/ Signaling)
15 Contact rating
Make and carry continuously
Make and carry for 0.5 sec.
Break resistive load and inductive load with 40m sec.
time constant
Whether self reset or hand reset

16 Ref. no. of descriptive leaflet enclosed
17 Temp. rise over ambient temperature
18 One minute power frequency withstand volt.
19 Degree of Protection
20 Mounting and dimensional details.
21 Overall dimensions
22 Weight
E OVER VOLTAGE RELAY
1 Make
2 Type / designation
3 Whether comply to Principle Technical Parameters
as per Annexure III

4 Auxiliary Supply and its burden with permissible
tolerance.

5 No. of poles
6 Voltage setting range
7 Time setting range
8 Drop off to pick up ratio
9 Burden at VT inputs
10 No. of outputs. (Trip/ Alarm)
11 Contact rating
Make and carry continuously
Make and carry for 0.5 sec.
Break resistive load and inductive load with 40m sec.
time constant
Whether self reset or hand reset

12 Ref. no. of descriptive leaflet enclosed
13 Temp. rise over ambient temperature
14 One minute power frequency withstand volt.
15 Degree of Protection
16 Mounting and dimensional details.
17 Overall dimensions
18 Weight
F UNDER VOLTAGE RELAY
1 Make
2 Type / designation
3 Whether comply to Principle Technical Parameters
as per Annexure III

4 Auxiliary Supply and its burden with permissible
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 69 of 71
tolerance.
5 No. of poles
6 Voltage setting range
7 Time setting range
8 Burden at VT inputs
9 No. of outputs. (Trip/ Alarm)
10 Contact rating
Make and carry continuously
Make and carry for 0.5 sec.
Break resistive load and inductive load with 40m sec.
time constant
Whether self reset or hand reset

11 Ref. no. of descriptive leaflet enclosed
12 Temp. rise over ambient temperature
13 One minute power frequency withstand volt.
14 Degree of Protection
15 Mounting and dimensional details.
16 Overall dimensions
19 Weight
G LEADING POWER FACTOR CONTROLLER
RELAY

1 Make
2 Type / designation
3 Auxiliary Supply and its burden with permissible
tolerance.

4 Power factor setting range
5 Burden at CT inputs
6 Burden at VT inputs
7 No. of outputs. (Trip/ Alarm)
8 Contact rating
Make and carry continuously
Make and carry for 0.5 sec.
Break resistive load and inductive load with 40m sec.
time constant
Whether self reset or hand reset

9 Ref. no. of descriptive leaflet enclosed
10 Temp. rise over ambient temperature
11 One minute power frequency withstand volt.
12 Degree of Protection
13 Mounting and dimensional details.
14 Overall dimensions
15 Weight
H AUXILIARY RELAYS FOR TRANSFORMER
TROUBLE

1. Make
2. Type & Designation
3. Nominal voltage and % variation
4. Contacts, hand reset/self reset
GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 70 of 71
5. No. of pairs of contacts
i) Make contacts
ii) Break contacts

6. Operating time of relay
7. Burden of relay VA
8. i) Contact rating
ii) Voltage
iii) Making current and duration
iv) Breaking current
a) Resistive
b) Inductive 0.3 PF
c) Inductive L/R 10m sec
40m sec

9. Detailed literature furnished.
10. Type of operation indicator (Flag / LED)
I HIGH SPEED TRIPPING RELAYS
1. Make
2. Type & designation
3. Rating
4. i) Operating principal
ii) Literature write up enclosed

5. Operating time at rated voltage.
6 No. of Tripping Contact and rating
7 Hand reset contacts
i) No. of NO & NC contacts
ii) Rating of contacts.

J TRIP CIRCUIT SUPERVISION RELAY
1 Make
2 Type & designation
3 Rating
4 i) Operating principle
ii) Literature write-up enclosed.

5 Minimum voltage for satisfactory operation.
6 Burden
7 Monitoring of breaker trip coil in both open and
close position provided.


8 Safety resistor provided to limit the current if the
relay coil is short circuited.

9 Output contacts
i) No. of NO/NC contacts
ii) Rating of contacts

10 Time delay on drop off
11 Type of indication
12 Standard
13 Any other relevant details.



GETCO / E / TS- CRP 3600 / R4 Dt. 22.08.12
Seal & sign of Bidder Page 71 of 71







SCHEDULE: G
LIST OF PROTECTIVE RELAYS AND OTHER ACCESSORIES

Sr.no. Description Qty. reqd. Make and type
Designation
Shall be listed as per
the requirements of the
panel type mentioned