The document describes the design of storm water drainage systems for multiple zones (A to B, C to D, etc.) of a project site. It involves calculating storm water runoff from each zone using the Rational Method formula, which considers factors like rainfall intensity, area size, surface types. Manning's formula is then used to design the appropriate size of RCC drains for each zone's calculated runoff, considering parameters like flow velocity, depth, width, slope. The drain sizes are presented, with widths ranging from 750mm to 1300mm and depths from 500mm to 650mm, ensuring the designed discharge capacity is higher than the actual calculated runoff.
The document describes the design of storm water drainage systems for multiple zones (A to B, C to D, etc.) of a project site. It involves calculating storm water runoff from each zone using the Rational Method formula, which considers factors like rainfall intensity, area size, surface types. Manning's formula is then used to design the appropriate size of RCC drains for each zone's calculated runoff, considering parameters like flow velocity, depth, width, slope. The drain sizes are presented, with widths ranging from 750mm to 1300mm and depths from 500mm to 650mm, ensuring the designed discharge capacity is higher than the actual calculated runoff.
The document describes the design of storm water drainage systems for multiple zones (A to B, C to D, etc.) of a project site. It involves calculating storm water runoff from each zone using the Rational Method formula, which considers factors like rainfall intensity, area size, surface types. Manning's formula is then used to design the appropriate size of RCC drains for each zone's calculated runoff, considering parameters like flow velocity, depth, width, slope. The drain sizes are presented, with widths ranging from 750mm to 1300mm and depths from 500mm to 650mm, ensuring the designed discharge capacity is higher than the actual calculated runoff.
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 19,000 Sqm 19000 Sqm Intensity of rainfall " I " 100 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 19000 13300 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 100 x 13300 0.33 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 19000 5700 sq.mtr Discharge = Q2 = C x I x A2 Hence, Dischage = Q2 = 0.6 x 100 x 5700 0.095 cum/sec Actual total run off Q = Q 1 + Q 2 0.428 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.5 mtrs. Also assume breadth to depth ratio 1.5 So, breadth of drain = B = 1.5 D 0.75 mtrs. Area of flow = A = 0.75 x 0.5 0.375 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.75 + 2 x 0.5 1.75 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.375 / 1.75 0.214 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 350 350 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Designed discharge is higher than the actual discharge 1.47 m/sce DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Drain size - C to D Area of Sub-catchment 20,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 20000 14000 sq.mtr. Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 20000 6000 sq.mtr Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec Actual total run off Q = Q 1 + Q 2 0.450 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - E to F Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Drain size - G to H Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - I to J Area of Sub-catchment 72,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 72500 50750 sq.mtr. Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 72500 21750 sq.mtr Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec Actual total run off Q = Q 1 + Q 2 1.631 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Drain size - K to L Area of Sub-catchment 15,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 15000 10500 sq.mtr. Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 15000 4500 sq.mtr Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec Actual total run off Q = Q 1 + Q 2 0.338 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - M to N Area of Sub-catchment 39,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 39500 27650 sq.mtr. Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 39500 11850 sq.mtr Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec Actual total run off Q = Q 1 + Q 2 0.889 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Drain size - O to P Area of Sub-catchment 37,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 37950 26565 sq.mtr. Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 37950 11385 sq.mtr Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec Actual total run off Q = Q 1 + Q 2 0.854 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - Q to R Area of Sub-catchment 28,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 28950 20265 sq.mtr. Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 28950 8685 sq.mtr Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec Actual total run off Q = Q 1 + Q 2 0.651 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Drain size - ALL drain size including the part - Q to R Area of Sub-catchment 371,150 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 371150 259805 sq.mtr. Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 371150 111345 sq.mtr Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec Actual total run off Q = Q 1 + Q 2 8.351 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec Calculated size :- Width of drain is 2400 mm Depth of drain is 1200 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD DESIGN OF STORM WATER DRAIN for ( ZONE -02) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 17,512 Sqm 17512 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 30% Total Paved area = 0.3 x 17512 5254 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 100 x 5253.6 0.13 cum/sec Percentage un-paved area in Total Area "A2" 70% Total Un-paved area = 0.7 x 17512 12258 sq.mtr Discharge = Q2 = C x I x A2 Hence, Dischage = Q2 = 0.6 x 100 x 12258.4 0.204 cum/sec Actual total run off Q = Q 1 + Q 2 0.336 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.4 mtrs. Also assume breadth to depth ratio 1.75 So, breadth of drain = B = 1.75 D 0.7 mtrs. Area of flow = A = 0.7 x 0.4 0.28 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.7 + 2 x 0.4 1.5 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.28 / 1.5 0.187 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 300 300 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.28 x (0.187)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 0.41 cum/sec Calculated size :- Width of drain is 700 mm Depth of drain is 400 mm Designed discharge is higher than the actual discharge 1.45 m/sce Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE DESIGN OF STORM WATER DRAIN for ( ZONE -01 ) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 5,855 Sqm 5855 Sqm Intensity of rainfall " I " 60 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 90% Total Paved area = 0.9 x 5855 5855 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 60 x 5855 0.09 cum/sec Actual total run off Q 0.09 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.45 mtrs. Also assume breadth to depth ratio 0.45 So, breadth of drain = B = 0.45 D 0.3 mtrs. Area of flow = A = 0.3 x 0.45 0.135 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.3 + 2 x 0.45 1.2 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.135 / 1.2 0.113 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 350 350 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.135 x (0.113)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.13 cum/sec Calculated size :- Width of drain is 300 mm Depth of drain is 450 mm Designed discharge is higher than the actual discharge 0.96 m/sce Drain size - C to D Area of Sub-catchment 20,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 20000 14000 sq.mtr. Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 20000 6000 sq.mtr Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec Actual total run off Q = Q 1 + Q 2 0.450 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - E to F Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - G to H Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - I to J Area of Sub-catchment 72,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 72500 50750 sq.mtr. Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 72500 21750 sq.mtr Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec Actual total run off Q = Q 1 + Q 2 1.631 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - K to L Area of Sub-catchment 15,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 15000 10500 sq.mtr. Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 15000 4500 sq.mtr Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec Actual total run off Q = Q 1 + Q 2 0.338 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - M to N Area of Sub-catchment 39,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 39500 27650 sq.mtr. Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 39500 11850 sq.mtr Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec Actual total run off Q = Q 1 + Q 2 0.889 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - O to P Area of Sub-catchment 37,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 37950 26565 sq.mtr. Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 37950 11385 sq.mtr Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec Actual total run off Q = Q 1 + Q 2 0.854 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - Q to R Area of Sub-catchment 28,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 28950 20265 sq.mtr. Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 28950 8685 sq.mtr Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec Actual total run off Q = Q 1 + Q 2 0.651 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - ALL drain size including the part - Q to R Area of Sub-catchment 371,150 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 371150 259805 sq.mtr. Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 371150 111345 sq.mtr Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec Actual total run off Q = Q 1 + Q 2 8.351 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec Calculated size :- Width of drain is 2400 mm Depth of drain is 1200 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE DESIGN OF STORM WATER DRAIN for ( ZONE -01 ) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 13,900 Sqm 13900 Sqm Intensity of rainfall " I " 60 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 90% Total Paved area = 0.9 x 13900 13900 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 60 x 13900 0.21 cum/sec Actual total run off Q 0.21 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.6 mtrs. Also assume breadth to depth ratio 1.2 So, breadth of drain = B = 1.2 D 0.6 mtrs. Area of flow = A = 0.6 x 0.6 0.36 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.6 + 2 x 0.6 1.8 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.36 / 1.8 0.200 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 350 350 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.36 x (0.2)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.51 cum/sec Calculated size :- Width of drain is 600 mm Depth of drain is 600 mm Designed discharge is higher than the actual discharge 1.41 m/sce Drain size - C to D Area of Sub-catchment 20,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 20000 14000 sq.mtr. Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 20000 6000 sq.mtr Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec Actual total run off Q = Q 1 + Q 2 0.450 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - E to F Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - G to H Area of Sub-catchment 83,600 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 83600 58520 sq.mtr. Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 83600 25080 sq.mtr Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec Actual total run off Q = Q 1 + Q 2 1.881 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - I to J Area of Sub-catchment 72,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 72500 50750 sq.mtr. Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 72500 21750 sq.mtr Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec Actual total run off Q = Q 1 + Q 2 1.631 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec Calculated size :- Width of drain is 1300 mm Depth of drain is 650 mm Drain size - K to L Area of Sub-catchment 15,000 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 15000 10500 sq.mtr. Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 15000 4500 sq.mtr Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec Actual total run off Q = Q 1 + Q 2 0.338 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec Calculated size :- Width of drain is 750 mm Depth of drain is 500 mm Drain size - M to N Area of Sub-catchment 39,500 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 39500 27650 sq.mtr. Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 39500 11850 sq.mtr Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec Actual total run off Q = Q 1 + Q 2 0.889 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - O to P Area of Sub-catchment 37,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 37950 26565 sq.mtr. Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 37950 11385 sq.mtr Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec Actual total run off Q = Q 1 + Q 2 0.854 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - Q to R Area of Sub-catchment 28,950 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 28950 20265 sq.mtr. Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 28950 8685 sq.mtr Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec Actual total run off Q = Q 1 + Q 2 0.651 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec Calculated size :- Width of drain is 900 mm Depth of drain is 600 mm Drain size - ALL drain size including the part - Q to R Area of Sub-catchment 371,150 Sqm Intensity of rainfall " I " 100 mm/hr "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Percentage paved area in Total Area "A1" 70% Total Paved area = 0.7 x 371150 259805 sq.mtr. Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec Percentage un-paved area in Total Area "A2" 30% Total Un-paved area = 0.3 x 371150 111345 sq.mtr Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec Actual total run off Q = Q 1 + Q 2 8.351 cum/sec Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Design Discharge = 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec Calculated size :- Width of drain is 2400 mm Depth of drain is 1200 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE GREEN WARE HOUSE, LORRY PARKING, ADMIN., CAR PARKING DESIGN OF STORM WATER DRAIN for ( ZONE -01 ) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 16,500 Sqm 16500 Sqm Intensity of rainfall " I " 60 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 90% Total Paved area = 0.9 x 16500 16500 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 60 x 16500 0.25 cum/sec Actual total run off Q 0.25 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.6 mtrs. Also assume breadth to depth ratio So, breadth of drain = B = D 0.5 mtrs. Area of flow = A = 0.5 x 0.6 0.3 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.5 + 2 x 0.6 1.7 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.3 / 1.7 0.176 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 350 350 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.3 x (0.177)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.39 cum/sec Calculated size :- Width of drain is 500 mm Depth of drain is 600 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE north light hall,1/2, welfare row half, DESIGN OF STORM WATER DRAIN for ( ZONE -01 ) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 11,000 Sqm 11000 Sqm Intensity of rainfall " I " 60 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.90 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 90% Total Paved area = 0.9 x 11000 11000 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.9 x 60 x 11000 0.17 cum/sec Actual total run off Q 0.17 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.45 mtrs. Also assume breadth to depth ratio So, breadth of drain = B = D 0.5 mtrs. Area of flow = A = 0.5 x 0.45 0.225 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.5 + 2 x 0.45 1.4 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.225 / 1.4 0.161 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 350 350 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.225 x (0.161)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.27 cum/sec Calculated size :- Width of drain is 500 mm Depth of drain is 450 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE 60000 55000 5111.5242 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE Main drain DESIGN OF STORM WATER DRAIN for ( ZONE -01 ) Rational formula for calculating runoff Q = (C I A) QRunoff in m 3 /sec C Co-efficient of run off I Intensity of rainfall in mm/ hr. A Drainage area in sq.mtrs. Run-off co-efficient for various types of surfaces Open grounds, unpaved street : 0.10 to 0.30 Parks, lawns, gardens : 0.10 to 0.25 Macadam roads, pavements : 0.25 to 0.70 Asphalt pavements : 0.85 to 0.90 Water tight roof surface : 0.90 to 0.95 Storm frequency Intensity of precipitation. Time of concentration Mannings formula for calculating the size of drain Q= A x V V = (1 x R 2/3 x S 1/2 ) / n V = Velocity of flow in m/sec. n = Co-efficient of friction, 0.013 R = Hydraulic mean depth in mts. R = A / P A = area of cross section in m 2 (Top width + bottom width)/2xdepth of flow for trapezoidal Section Bottom width x depth of flow for rectangular section P = Wetted perimeter in meters Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D Where D= depth of flow Bottom width + 2 x depth of flow for rectangular section = B + 2D S = Hydraulic bed slope. DESIGN DRAIN- A to B Area of Sub-catchment 32,528 Sqm 32528 Sqm Intensity of rainfall " I " 60 mm/hr DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE "C" Run-off coefficient for Hardscape area 0.60 "C" Run-off coefficient for Softscape area. 0.60 Percentage paved area in Total Area "A1" 90% Total Paved area = 0.9 x 32527.8810408922 32528 sq.mtr. Discharge = Q1 = C x I x A1 Hence, Dischage = Q1 = 0.6 x 60 x 32527.8810408922 0.33 cum/sec Actual total run off Q 0.33 cum/sec Design of RCC drain Q = A x V Area of flow A = B x D Assume depth of flow for a rectangular drain ' D ' 0.7 mtrs. Also assume breadth to depth ratio So, breadth of drain = B = D 0.45 mtrs. Area of flow = A = 0.45 x 0.7 0.315 Sqm. Wetted perimeter = P = B + 2D Perimeter = P = 0.45 + 2 x 0.7 1.85 mtrs. Wetted Radius = R = A / P Wetted Radius = R = 0.315 / 1.85 0.170 mtrs. Mannings formula for calculating the size of drain Mannings Formulae = Q = (A X R 2/3 X S 1/2 ) / n Where, Slope of drain = S = 1 in 300 300 Mannings constant (friction coefficient) " n " for RCC Drains 0.013 Design Discharge = 0.315 x (0.171)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 0.43 cum/sec Calculated size :- Width of drain is 450 mm Depth of drain is 700 mm DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE 525000 173160 275000 555000 16092.9 25557.6 51579.926 DATE : 16/02/09 REV: RO CONSULTANTS :SEMAC PVT LTD