Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE

DESIGN OF STORM WATER DRAIN for ( ZONE -01 )


Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 19,000 Sqm
19000 Sqm
Intensity of rainfall " I " 100 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 19000 13300 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 100 x 13300 0.33 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 19000 5700 sq.mtr
Discharge = Q2 = C x I x A2
Hence,
Dischage = Q2 = 0.6 x 100 x 5700 0.095 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.428 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.5 mtrs.
Also assume breadth to depth ratio 1.5
So, breadth of drain = B = 1.5 D 0.75 mtrs.
Area of flow = A = 0.75 x 0.5 0.375 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.75 + 2 x 0.5 1.75 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.375 / 1.75 0.214 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 350 350
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Designed discharge is higher than the actual discharge 1.47 m/sce
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Drain size - C to D
Area of Sub-catchment 20,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 20000 14000 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 20000 6000 sq.mtr
Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.450 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - E to F
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Drain size - G to H
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - I to J
Area of Sub-catchment 72,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 72500 50750 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 72500 21750 sq.mtr
Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.631 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Drain size - K to L
Area of Sub-catchment 15,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 15000 10500 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 15000 4500 sq.mtr
Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.338 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - M to N
Area of Sub-catchment 39,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 39500 27650 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 39500 11850 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.889 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Drain size - O to P
Area of Sub-catchment 37,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 37950 26565 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 37950 11385 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.854 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - Q to R
Area of Sub-catchment 28,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 28950 20265 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 28950 8685 sq.mtr
Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.651 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Drain size - ALL drain size including the part - Q to R
Area of Sub-catchment 371,150 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 371150 259805 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 371150 111345 sq.mtr
Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec
Actual total run off Q = Q
1
+ Q
2 8.351 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec
Calculated size :-
Width of drain is 2400 mm
Depth of drain is 1200 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
DESIGN OF STORM WATER DRAIN for ( ZONE -02)
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 17,512 Sqm
17512 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 30%
Total Paved area = 0.3 x 17512 5254 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 100 x 5253.6 0.13 cum/sec
Percentage un-paved area in Total Area "A2" 70%
Total Un-paved area = 0.7 x 17512 12258 sq.mtr
Discharge = Q2 = C x I x A2
Hence,
Dischage = Q2 = 0.6 x 100 x 12258.4 0.204 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.336 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.4 mtrs.
Also assume breadth to depth ratio 1.75
So, breadth of drain = B = 1.75 D 0.7 mtrs.
Area of flow = A = 0.7 x 0.4 0.28 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.7 + 2 x 0.4 1.5 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.28 / 1.5 0.187 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 300 300
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.28 x (0.187)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 0.41 cum/sec
Calculated size :-
Width of drain is 700 mm
Depth of drain is 400 mm
Designed discharge is higher than the actual discharge 1.45 m/sce
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 5,855 Sqm
5855 Sqm
Intensity of rainfall " I " 60 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 90%
Total Paved area = 0.9 x 5855 5855 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 60 x 5855 0.09 cum/sec
Actual total run off Q 0.09 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.45 mtrs.
Also assume breadth to depth ratio 0.45
So, breadth of drain = B = 0.45 D 0.3 mtrs.
Area of flow = A = 0.3 x 0.45 0.135 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.3 + 2 x 0.45 1.2 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.135 / 1.2 0.113 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 350 350
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.135 x (0.113)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.13 cum/sec
Calculated size :-
Width of drain is 300 mm
Depth of drain is 450 mm
Designed discharge is higher than the actual discharge 0.96 m/sce
Drain size - C to D
Area of Sub-catchment 20,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 20000 14000 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 20000 6000 sq.mtr
Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.450 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - E to F
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - G to H
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - I to J
Area of Sub-catchment 72,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 72500 50750 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 72500 21750 sq.mtr
Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.631 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - K to L
Area of Sub-catchment 15,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 15000 10500 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 15000 4500 sq.mtr
Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.338 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - M to N
Area of Sub-catchment 39,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 39500 27650 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 39500 11850 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.889 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - O to P
Area of Sub-catchment 37,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 37950 26565 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 37950 11385 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.854 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - Q to R
Area of Sub-catchment 28,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 28950 20265 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 28950 8685 sq.mtr
Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.651 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - ALL drain size including the part - Q to R
Area of Sub-catchment 371,150 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 371150 259805 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 371150 111345 sq.mtr
Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec
Actual total run off Q = Q
1
+ Q
2 8.351 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec
Calculated size :-
Width of drain is 2400 mm
Depth of drain is 1200 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 13,900 Sqm
13900 Sqm
Intensity of rainfall " I " 60 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 90%
Total Paved area = 0.9 x 13900 13900 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 60 x 13900 0.21 cum/sec
Actual total run off Q 0.21 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.6 mtrs.
Also assume breadth to depth ratio 1.2
So, breadth of drain = B = 1.2 D 0.6 mtrs.
Area of flow = A = 0.6 x 0.6 0.36 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.6 + 2 x 0.6 1.8 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.36 / 1.8 0.200 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 350 350
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.36 x (0.2)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.51 cum/sec
Calculated size :-
Width of drain is 600 mm
Depth of drain is 600 mm
Designed discharge is higher than the actual discharge 1.41 m/sce
Drain size - C to D
Area of Sub-catchment 20,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 20000 14000 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 14000 0.35 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 20000 6000 sq.mtr
Dischage = Q2 = 0.6 x 100 x 6000 0.100 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.450 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - E to F
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - G to H
Area of Sub-catchment 83,600 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 83600 58520 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 58520 1.46 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 83600 25080 sq.mtr
Dischage = Q2 = 0.6 x 100 x 25080 0.418 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.881 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 250) ^(1/2) / 0.013 ) 1.94 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - I to J
Area of Sub-catchment 72,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 72500 50750 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 50750 1.27 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 72500 21750 sq.mtr
Dischage = Q2 = 0.6 x 100 x 21750 0.363 cum/sec
Actual total run off Q = Q
1
+ Q
2
1.631 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.845 x (0.325)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 1.77 cum/sec
Calculated size :-
Width of drain is 1300 mm
Depth of drain is 650 mm
Drain size - K to L
Area of Sub-catchment 15,000 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 15000 10500 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 10500 0.26 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 15000 4500 sq.mtr
Dischage = Q2 = 0.6 x 100 x 4500 0.075 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.338 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.375 x (0.215)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.55 cum/sec
Calculated size :-
Width of drain is 750 mm
Depth of drain is 500 mm
Drain size - M to N
Area of Sub-catchment 39,500 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 39500 27650 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 27650 0.69 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 39500 11850 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11850 0.198 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.889 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - O to P
Area of Sub-catchment 37,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 37950 26565 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 26565 0.66 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 37950 11385 sq.mtr
Dischage = Q2 = 0.6 x 100 x 11385 0.190 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.854 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - Q to R
Area of Sub-catchment 28,950 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 28950 20265 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 20265 0.51 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 28950 8685 sq.mtr
Dischage = Q2 = 0.6 x 100 x 8685 0.145 cum/sec
Actual total run off Q = Q
1
+ Q
2
0.651 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 0.54 x (0.258)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.90 cum/sec
Calculated size :-
Width of drain is 900 mm
Depth of drain is 600 mm
Drain size - ALL drain size including the part - Q to R
Area of Sub-catchment 371,150 Sqm
Intensity of rainfall " I " 100 mm/hr
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Percentage paved area in Total Area "A1" 70%
Total Paved area = 0.7 x 371150 259805 sq.mtr.
Dischage = Q1 = 0.9 x 100 x 259805 6.50 cum/sec
Percentage un-paved area in Total Area "A2" 30%
Total Un-paved area = 0.3 x 371150 111345 sq.mtr
Dischage = Q2 = 0.6 x 100 x 111345 1.856 cum/sec
Actual total run off Q = Q
1
+ Q
2 8.351 cum/sec
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Design Discharge
= 2.88 x (0.6)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 9.10 cum/sec
Calculated size :-
Width of drain is 2400 mm
Depth of drain is 1200 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
GREEN WARE HOUSE, LORRY PARKING, ADMIN., CAR PARKING
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 16,500 Sqm
16500 Sqm
Intensity of rainfall " I " 60 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 90%
Total Paved area = 0.9 x 16500 16500 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 60 x 16500 0.25 cum/sec
Actual total run off Q 0.25 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.6 mtrs.
Also assume breadth to depth ratio
So, breadth of drain = B = D 0.5 mtrs.
Area of flow = A = 0.5 x 0.6 0.3 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.5 + 2 x 0.6 1.7 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.3 / 1.7 0.176 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 350 350
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.3 x (0.177)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.39 cum/sec
Calculated size :-
Width of drain is 500 mm
Depth of drain is 600 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
north light hall,1/2, welfare row half,
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 11,000 Sqm
11000 Sqm
Intensity of rainfall " I " 60 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.90
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 90%
Total Paved area = 0.9 x 11000 11000 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.9 x 60 x 11000 0.17 cum/sec
Actual total run off Q 0.17 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.45 mtrs.
Also assume breadth to depth ratio
So, breadth of drain = B = D 0.5 mtrs.
Area of flow = A = 0.5 x 0.45 0.225 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.5 + 2 x 0.45 1.4 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.225 / 1.4 0.161 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 350 350
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.225 x (0.161)^(2/3) x (1 / 350) ^(1/2) / 0.013 ) 0.27 cum/sec
Calculated size :-
Width of drain is 500 mm
Depth of drain is 450 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
60000
55000
5111.5242
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
Main drain
DESIGN OF STORM WATER DRAIN for ( ZONE -01 )
Rational formula for calculating runoff Q = (C I A)
QRunoff in m
3
/sec
C Co-efficient of run off
I Intensity of rainfall in mm/ hr.
A Drainage area in sq.mtrs.
Run-off co-efficient for various types of surfaces
Open grounds, unpaved street : 0.10 to 0.30
Parks, lawns, gardens : 0.10 to 0.25
Macadam roads, pavements : 0.25 to 0.70
Asphalt pavements : 0.85 to 0.90
Water tight roof surface : 0.90 to 0.95
Storm frequency
Intensity of precipitation.
Time of concentration
Mannings formula for calculating the size of drain
Q= A x V
V = (1 x R
2/3
x S
1/2
) / n
V = Velocity of flow in m/sec.
n = Co-efficient of friction, 0.013
R = Hydraulic mean depth in mts.
R = A / P
A = area of cross section in m
2
(Top width + bottom width)/2xdepth of flow for trapezoidal Section
Bottom width x depth of flow for rectangular section
P = Wetted perimeter in meters
Bottom width + (2 x 2 x depth of flow) for trapezoidal section = B + 2 x 2 x D
Where D= depth of flow
Bottom width + 2 x depth of flow for rectangular section = B + 2D
S = Hydraulic bed slope.
DESIGN
DRAIN- A to B
Area of Sub-catchment 32,528 Sqm
32528 Sqm
Intensity of rainfall " I " 60 mm/hr
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD
Project : WIPRO TECHNOLOGY AT GOPANAPALLY ARCH : MINDSPACE
"C" Run-off coefficient for Hardscape area 0.60
"C" Run-off coefficient for Softscape area. 0.60
Percentage paved area in Total Area "A1" 90%
Total Paved area = 0.9 x 32527.8810408922 32528 sq.mtr.
Discharge = Q1 = C x I x A1
Hence,
Dischage = Q1 = 0.6 x 60 x 32527.8810408922 0.33 cum/sec
Actual total run off Q 0.33 cum/sec
Design of RCC drain Q = A x V
Area of flow A = B x D
Assume depth of flow for a rectangular drain ' D ' 0.7 mtrs.
Also assume breadth to depth ratio
So, breadth of drain = B = D 0.45 mtrs.
Area of flow = A = 0.45 x 0.7 0.315 Sqm.
Wetted perimeter = P = B + 2D
Perimeter = P = 0.45 + 2 x 0.7 1.85 mtrs.
Wetted Radius = R = A / P
Wetted Radius = R = 0.315 / 1.85 0.170 mtrs.
Mannings formula for calculating the size of drain
Mannings Formulae = Q = (A X R
2/3
X S
1/2
) / n
Where,
Slope of drain = S = 1 in 300 300
Mannings constant (friction coefficient) " n " for RCC Drains 0.013
Design Discharge
= 0.315 x (0.171)^(2/3) x (1 / 300) ^(1/2) / 0.013 ) 0.43 cum/sec
Calculated size :-
Width of drain is 450 mm
Depth of drain is 700 mm
DATE : 16/02/09
REV: RO CONSULTANTS :SEMAC PVT LTD