LECTURE 3

THE CONTENTS OF THIS LECTURE ARE AS FOLLOWS:


1.0 TYPES OF HYGROMETERS
1.1 Wall Mounted Type Hygrometer
1.1.1 Construction
1.1.2 Working
1.1.3 Precautions
1.2 Whirling Hygrometer or Sling Psychrometer
1.2.1 Construction
1.2.2 Working
1.2.3 Precautions
1.2.4 Limitations
1.3 Assmann Psychrometer
1.3.1 Construction
1.3.2 Working
1.3.3 Advantages
1.3.4 Precautions

Page 1 of 14

2.0 CALCULATING WATER VAPOUR CONTENT IN THE


UNSATURATED AIR
3.0 STEPS FOR CALCULATING WATER VAPOUR CONTENT
OF MOIST AIR
3.1 Method I
3.2 Method II
3.3 Method III

REFERENCES

Page 2 of 14

1.0 TYPES OF HYGROMETERS


There are three types of hygrometers which employ the thermodynamic method of
measuring water content in the air. They are:
-

Wall mounted type

Whirling hygrometer or sling psychrometer

Aspirated type or Assmann psychrometer

1.1 Wall Mounted Type Hygrometer


It is non-ventilated type in nature. It is fixed at suitable place in mine so that it is
well ventilated by mine air-current.
1.1.1 Construction
It has two thermometers mounted on it side by side. One of them is exposed
directly to mine air while the other has a wet muslin cloth all around the bulb. The
lower end of the muslin cloth is always immersed in some container having water.
This ensures continuous supply of the water to the muslin cloth (Fig. 1).
1.1.2 Working
It records dry and wet bulb temperatures using respective thermometers. Using a
barometer, barometric pressure is recorded. The three readings are used to
calculate the humidity.
1.1.3 Precautions
There should not be any source of heat nearby, while taking readings. Also bulbs of
thermometers should be wiped out properly so as to make it dust/dirt free. This is
done because impurities affects evaporation rate of water. Keeping this thing in
mind, it is better to use distilled water.

Page 3 of 14

Fig.1 Wall mounted hygrometer

Page 4 of 14

1.2 Whirling Hygrometer or Sling Psychrometer


1.2.1 Construction
It consists of a wooden frame with a handle attached to it. The handle is used for
rotating. Two thermometers are mounted in the wooden frame. They are mounted
such that they do not break when wooden frame is rotated. One of the
thermometers is directly exposed to atmosphere while the other has a muslin cloth
wrapped around the bulb. The muslin cloth has one end (lower) dipped in water
container. The water from container makes the muslin cloth wet by capillary action.
The former records dry-bulb temperature while the latter one records wet-bulb
temperature.
1.2.2 Working
The muslin cloth, wrapped around the bulb of the thermometer, is made wet using
distilled water. Then the wooden frame is rotated at a uniform speed of around 200
rpm for a span of 1-2 minute, so that a steady reading is obtained. This rotation
provides the air-current causing water to evaporate. Due to this, the temperature
of the thermometer with wet-muslin cloth is depressed.
1.2.3 Precautions
- While rotating the hygrometer, it should be kept away from the observers body to
avoid heat flow between observers body and the wet-muslin cloth. Same should be
applied while taking reading.
- The reading for the wet-bulb temperature should be taken as soon as possible
after stopping the rotation. This is because wet-bulb temperature starts fluctuating
while dry-bulb temperature remains steady. Therefore, wet-bulb temperature
should be recorded first.

Page 5 of 14

Fig.2. Whirling hygrometer (after Banerjee, 2003)


1.2.4 Limitations
The moisture evaporated from the muslin cloth affects both the thermometers,
unless an air-current of velocity 3 m/s or more is provided. That is why it is rotated
at around 200 rpm to provide an air-current of velocity equal to or more than 3
m/s. Actually the minimum velocity required is governed by the shape and size of
the bulb and the orientation of bulb with the direction of airflow.

Page 6 of 14

1.3 Assmann Psychrometer


1.3.1 Construction
It consists of two thermometers -one wet bulb and one dry bulb thermometer, and
a battery driven fan. The fan is at the top. The bulbs of the two thermometers are
covered by metal sleeves whose outer surface is coated with chromium. The two
thermometers are thermally insulated from each other through a central tube (as
shown in Fig.3). The two thermometers cover a range of 0 to 60C.

Fig.3 Assmann psychrometer (after Banerjee, 2003)

Page 7 of 14

1.3.2 Working
When the fan is kept on, the air through inner sleeves (metal sleeves provided at
the bulb of each thermometer) and annular spaces enters the apparatus. The air
travels through the central tube and goes out of the apparatus through the slits
provided at the top near the fan. The fan is kept on for an interval of approximately
3 minutes. The fan should provide a velocity of more than 2m/s. This is done to
ensure that wet-bulb thermometer attains a constant temperature.
1.3.3 Advantages
i.

It can measure humidity with an accuracy of 1%.

ii.

The metal sleeves around the bulbs of the thermometers, shield the bulb
from any radiation. This ensures that using this, we can accurately
measure humidity in sunlit areas also.

iii.

Easy to operate.

1.3.4 Precautions
i.

The instrument requires calibration with respect to the fan speed and
hence the ventilation speed.

ii.

The instrument should be hold away from observers body.

iii.

The instrument should be held opposite to the direction of the flow when
experiment/survey is being carried out in a strong air-current.

We have repeatedly interchanged the words hygrometer and psychrometer in this


lecture. In general, the word psychrometer is used if the instrument gives result
with a higher degree of accuracy.

2.0 CALCULATING WATER VAPOUR CONTENT IN THE UNSATURATED AIR


We have already learnt that at equilibrium when the wet bulb temperature becomes
constant, the heat loss (latent) by the bulb is equal to the sensible heat gained by

Page 8 of 14

it. We are interested in knowing the amount of heat lost at equilibrium by the wet
bulb. This can be better understood by Fig.4

Fig. 4 Heat balance on a wet bulb thermometer (after, McPherson, 1993)


Fig.4 shows that some mass of unsaturated air when passes through a wet muslin
cloth, it becomes saturated. Let X be the specific humidity of unsaturated air. To
attain saturation, the specific humidity should be Xs. Then mass of water vapour
evaporating from the wet muslin cloth is (Xs X) per kg of dry air. Therefore, heat
loss (latent) from wet-bulb surface is
q = L m(Xs X)

joule

(a)

Where,
L= latent heat of vapourization (J/kg)
Page 9 of 14

m= mass of dry air (kg)


X = specific humidity of unsaturated air (kg/kg dry air)
Xs=specific humidity of saturated air (kg/kg dry dir)
q= heat lost (J)
Now, we require to know, the amount of heat gained by wet-bulb from the
unsaturated air passing through the muslin cloth. Let the mass of dry air in the
unsaturated air be m.
Then total mass of the moist/unsaturated air is m(1+X) kg. Therefore heat gain is
q = mass of unsaturated air specific heat of unsaturated air at constant pressure
difference between the dry bulb and wet bulb temperature
Therefore, q = m(1 + X) Cpm (t d t w )

joule . (b)

Where,
q= heat lost (J)
X = specific humidity of unsaturated air (kg/kg dry air)
m= mass of dry air (kg)
Cpm = specific heat of moist air at constant pressure (J/kg)
td = dry bulb temperature ()
tw = wet bulb temperature ()

Now, when the wet bulb temperature attains a constant value, the heat gain and
loss by the wet-bulb surface is equal. Equating equation (a) and (b), we have:
L(X s X) = (1 + X) Cpm (t d t w )
Substituting the expression of
Page 10 of 14

J per kg dry air

Cpm =

Cpd +XCpv
1+X

. (1)
in equation (1) we get,

L(X s X) = (1 + X)

Cpd +XCpv
1+X

(t d t w )

J per kg dry air

. (2)

The above equation results in

X=

LXs Cpd (t d t w )
kg
Cpv (t d t w ) + L kg dry air

This gives the specific humidity of moist/unsaturated air.

3.0 STEPS FOR CALCULATING WATER VAPOUR CONTENT OF MOIST AIR


In all methods described below, unit of pressure is Pa and temperature is C, unless
and otherwise stated.

3.1 Method I
a. Record/measure t d , t w and Pb
b. Evaluate e, esw and esd using following equations.

es = 610.6 exp (

17.27 t
) Pa
237.3 + t

{replace t by t d and t w for esd and esw respectively }

and

e = esw 0.000644 Pb (t d t w ) Pa
c. Evaluate

Specific humidity (X) = 0.622


Relative humidity(rh) =
Page 11 of 14

e
esd

kg

Pb e kg dry air

100 %

and

3.2 Method II
a. Measure Pb , t d and t w
b. Evaluate esw and esd using following equations.
17.27 t
es = 610.6 exp (
) Pa
237.3 + t
{replace t by t d and t w for esd and esw respectively }

c. Evaluate
(X s ) = 0.622

esw
kg
Pb esw kg dry air

d. Evaluate latent heat of vaporization at wet bulb temperature, Lw using equation

LW = (2502.5 2.386t w ) 1000


e. Evaluate

J/kg

X by substituting the values of constants used in the following

equation

Specific humidity (X) =

Lw X s Cpd (t d t w )
kg
Cpv (t d t w ) + L kg dry air

f. Evaluate
Relative humidity(rh) =

e
esd

100%

3.3 Method III


a. Measure Pb , t d and t w
b. Evaluate esw and esd using following equations.
Page 12 of 14

{e can be calculated using X }

es = 610.6 exp (

17.27 t
) Pa
237.3 + t

{replace t by t d and t w for esd and esw respectively }


c. Evaluate
(X s ) = 0.622

esw
kg
Pb esw kg dry air

d. Evaluate latent heat of vaporization at wet bulb temperature, Lw using equation

LW = (2502.5 2.386t w ) 1000

J/kg

e. Evaluate sigma heat S using formula given below


S = (Lw X s + 1005t w )

J
kg dry air

f. Evaluate specific humidity (X) of the moist air


X=

S 1005t d
Lw + 1884(t d t w )

Lw X s 1005(t d t w)
kg
Lw + 1884(t d t w ) kg dry air

g. Evaluate

Relative humidity(rh) =

e
esd

100%

{e can be calculated using X }

REFERENCES
Banerjee S.P. (2003); Mine Ventilation; Lovely Prakashan, Dhanbad, India.
Deshmukh, D. J. (2008); Elements of Mining Technology, Vol. II; Denett & Co.,
Nagpur, India.
Hartman, H. L., Mutmansky, J. M. & Wang, Y. J. (1982); Mine Ventilation and Air
Conditioning; John Wiley & Sons, New York.
Le Roux, W. L. (1972); Mine Ventilation Notes for Beginners; The Mine Ventilation
Society of South Africa.
McPherson, M. J. (1993); Subsurface Ventilation and Environmental Engineering;
Chapman & Hall, London.
Page 13 of 14

Misra G.B.

(1986); Mine Environment and Ventilation; Oxford University Press,

Calcutta, India.
Vutukuri, V. S. & Lama, R. D. (1986); Environmental Engineering in Mines;
Cambridge University Press, Cambridge.

Page 14 of 14