BRITISH STANDARD

Electrical test methods


for low voltage energy
cables

The European Standard EN 50395:2005 has the status of a


British Standard

ICS 29.060.20

12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:

BS EN
50395:2005

BS EN 50395:2005

National foreword
This British Standard is the official English language version of
EN 50395:2005.
The UK participation in its preparation was entrusted by Technical Committee
GEL/20, Electric cables, to Subcommittee GEL/20/17, Low voltage cables,
which has the responsibility to:

aid enquirers to understand the text;

present to the responsible international/European committee any


enquiries on the interpretation, or proposals for change, and keep
UK interests informed;

monitor related international and European developments and


promulgate them in the UK.

A list of organizations represented on this subcommittee can be obtained on


request to its secretary.
Cross-references
The British Standards which implement international or European
publications referred to in this document may be found in the BSI Catalogue
under the section entitled International Standards Correspondence Index, or
by using the Search facility of the BSI Electronic Catalogue or of British
Standards Online.
This publication does not purport to include all the necessary provisions of a
contract. Users are responsible for its correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.

Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 14, an inside back cover and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.

This British Standard was


published under the authority
of the Standards Policy and
Strategy Committee
on 14 November 2005

BSI 14 November 2005

ISBN 0 580 46737 6

Amendments issued since publication


Amd. No.

Date

Comments

EN 50395

EUROPEAN STANDARD
NORME EUROPENNE
EUROPISCHE NORM

August 2005

ICS 29.060.20

Partly supersedes HD 21.2 S3:1997 + A1:2002 &


HD 22.2 S3:1997 + A1:2002

English version

Electrical test methods for low voltage energy cables


Mthodes d'essais lectriques
pour les cbles d'nergie basse tension

Elektrische Prfverfahren
fr Niederspannungskabel und -leitungen

This European Standard was approved by CENELEC on 2005-07-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comit Europen de Normalisation Electrotechnique
Europisches Komitee fr Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
2005 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50395:2005 E

EN 50395:2005

Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric cables.
In accordance with the decision of TC 20 at its Setubal meeting (June 2004), the text of the draft was
submitted to the formal vote. It was approved by CENELEC as EN 50395 on 2005-07-01.
This European Standard, together with EN 50396:2005, supersedes HD 21.2 S3:1997 + A1:2002 and
HD 22.2 S3:1997 + A1:2002.
The following dates were fixed:

latest date by which the EN has to be implemented


at national level by publication of an identical
national standard or by endorsement

(dop)

2006-07-01

latest date by which the national standards conflicting


with the EN have to be withdrawn

(dow)

2008-07-01

__________

EN 50395:2005

Contents
Page
Introduction.............................................................................................................................................5
1

Scope................................................................................................................................................5

Normative references......................................................................................................................5

General requirements .....................................................................................................................6


3.1

Pre-conditioning......................................................................................................................6

3.2

Test temperature ....................................................................................................................6

3.3

Test voltage ............................................................................................................................6

3.4

Test values .............................................................................................................................6

Definitions........................................................................................................................................6

Electrical d.c. resistance of conductor .........................................................................................6

Voltage test on completed cable ...................................................................................................6

Voltage test on cores in water .......................................................................................................7

7.1

Test sample ............................................................................................................................7

7.2

Procedure ...............................................................................................................................7

7.3

Requirement ...........................................................................................................................7

Insulation resistance test ...............................................................................................................7


8.1

8.2

Insulation resistance for cables having maximum conductor temperatures


not exceeding 90 C ...............................................................................................................7

8.1.1 Test sample ...............................................................................................................7


8.1.2 Procedure ..................................................................................................................8
8.1.3 Requirement ..............................................................................................................8
Insulation resistance for cables with maximum conductor temperatures
exceeding 90 C .....................................................................................................................8
8.2.1
8.2.2
8.2.3

Test sample ...............................................................................................................8


Procedure ..................................................................................................................8
Requirement ..............................................................................................................8

Long term resistance of insulation to d.c.....................................................................................9


9.1

Test sample ............................................................................................................................9

9.2

Procedure ...............................................................................................................................9

9.3

Requirement .........................................................................................................................10

10 Check for the absence of faults in insulation ............................................................................10


10.1 General .................................................................................................................................10
10.2 Spark test..............................................................................................................................10
10.2.1 Procedure ................................................................................................................10
10.2.2 Requirement ............................................................................................................10
10.3 Voltage test...........................................................................................................................10
10.3.1 Procedure ................................................................................................................10

EN 50395:2005

10.3.2 Requirement ............................................................................................................10


11 Surface resistance of sheath .......................................................................................................11
11.1 Test samples ........................................................................................................................11
11.2 Procedure .............................................................................................................................11
11.3 Requirement .........................................................................................................................11
12 Transfer impedance ......................................................................................................................11
Annex A .................................................................................................................................................12
A.1

Basic formula........................................................................................................................12

A.2

Rounding ..............................................................................................................................12

A.3

Examples of calculation........................................................................................................12

Annex B (informative) Source of electrical test methods in EN 50395.............................................13


Bibliography..........................................................................................................................................14
Figure 1 Positioning of electrodes .........................................................................................................9

EN 50395:2005

Introduction
EN 50395 contains the electrical test methods that are used for harmonized low voltage energy
cables. These electrical test methods include all those previously contained in HD 21 and HD 22.
Annex B gives a comparison between the original location of each test method and its place in this
new European Standard.
The content of EN 50395 is not, and will not be, restricted only to test methods for cables to HD 21
and HD 22. Other test methods for harmonized LV cables may be included. Furthermore, the use of
test methods in EN 50395 for cables outside HD 21 and HD 22 is not prohibited, but it is strongly
recommended that expert advice be taken before such use, or before any proposal for incorporation
into another standard.

Scope

EN 50395 contains electrical test methods required for the testing of harmonized low voltage energy
cables, especially those rated at up to and including 450/750 V.
NOTE 1 A description of the origin of these test methods and the background to this European Standard is given in the
Introduction and in Annex B.

The particular cable standard dictates the tests which need to be performed on the relevant cable
type. It also specifies whether the specific test is a type test (T), a sample test (S) or a routine test (R)
for the particular cable type.
NOTE 2

T, S and R are defined in the relevant cable standard.

The requirements to be met during or after the test are specified for the particular cable type in the
relevant cable standard. However, some test requirements are obvious and universal, such as the fact
that no breakdown shall occur during voltage tests, and these are stated in the particular test method.

Test methods for use specifically in utility power cables are not covered by this European Standard.
They can be found in HD 605.
Test methods for use specifically in communications cables are the responsibility of the Technical
Committee CENELEC TC 46X, Communication cables. At present such test methods are given in
EN 50289 series.

Normative references

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50289-1-6

2002

Communication cables Specifications for test methods Part 1-6: Electrical test methods Electromagnetic performance

EN 50356

2002

Method for spark testing of cables

EN 60228

2005

Conductors of insulated cables

EN 50395:2005

3
3.1

General requirements
Pre-conditioning

All the tests shall be carried out not less than 16 h after the extrusion or cross-linking, if any, of the
insulating or sheathing compounds.

3.2

Test temperature

Unless otherwise specified, tests shall be made at an ambient temperature of (20 15) C.

3.3

Test voltage

Unless otherwise specified in the individual clause of this European Standard or in the product
standard, the test voltage shall be a.c. of approximately sine-wave form and of frequency between
49 Hz and 61 Hz. The ratio of peak value to r.m.s. value shall be equal to 2 with a tolerance of 7 %.
The values quoted are r.m.s. values.

3.4

Test values

Full test conditions (such as temperatures, durations, etc.) and full test requirements are not specified
in this European Standard; it is intended that they should be specified by the standard dealing with the
relevant type of cable.

Any test requirements which are given in this European Standard may be modified by the relevant
cable standard to suit the needs of a particular type of cable.

Definitions

For the purposes of this document, the following terms and definitions apply.
4.1
median value
when several test results have been obtained and ordered in an increasing or decreasing succession,
the median value is the middle value if the number of available values is odd, and is the mean of the
two middle values if the number is even

Electrical d.c. resistance of conductor

The test shall be carried out in accordance with Annex A of EN 60228.

Voltage test on completed cable

If the cable has no metallic layer, a sample of the cable as manufactured shall be immersed in water.
The length of the sample, the temperature of the water and the period of immersion shall be as
specified in the cable standard. A voltage shall be applied between conductor(s) and groups of
conductors in such a way that the insulation on each core is tested against all adjacent cores and the
water.

EN 50395:2005

If the cable has a metallic layer, a sample of the cable shall be taken of the length specified in the
cable standard. A voltage shall be applied between conductor(s) and groups of conductors in such a
way that the insulation on each core is tested against all adjacent cores and the metallic layer, which
shall be earthed.
If the cable has a metallic strain-bearing member, this shall be connected to the water or to the
metallic layer, as appropriate.
In each case, the voltage and the duration of its application shall be as specified in the cable standard.
The voltage shall be increased gradually on each occasion to the specified value.
No breakdown of the insulation shall occur during the test.

Voltage test on cores in water

The test applies to sheathed cables, braided cables and flat unsheathed cords.
NOTE For 1-core unsheathed cables, the test in Clause 6 generally applies, in which case this test on cores is not required.

7.1

Test sample

Prepare a sample of cable 5 m long, by carefully removing, without damaging the cores, the sheath or
the overall braid and any other covering or filling from a length of completed cable.

In the case of flat unsheathed cord, make a cut in the insulation between the cores, and separate the
cores by hand for a length of 2 m.

7.2

Procedure

Immerse the sample in water at the temperature, and for the period, specified in the cable standard.
Ensure that the ends of the cores protrude above the water by a distance sufficient to prevent
excessive surface leakage when the test voltage is applied. Apply a voltage, of the magnitude
specified in the cable standard, between the conductors and the water for the time specified in the
cable standard.

7.3

Requirement

No breakdown of the insulation shall occur during the test.

Insulation resistance test

8.1

8.1.1

Insulation resistance for cables having maximum conductor temperatures not


exceeding 90 C
Test sample

Make the test on a sample of cable 5 m long, previously submitted to the test specified in Clause 7 or,
in the case of 1-core unsheathed cable, to the test described in Clause 6.

EN 50395:2005

8.1.2

Procedure

Immerse the sample in water previously heated to the temperature specified in the cable standard,
with a length of about 250 mm at each end of the sample projecting above the water, for the period of
time specified in the cable standard.
Apply a d.c. voltage of between 80 V and 500 V between each conductor and the water.
Measure the insulation resistance of each core 1 min after application of the voltage. Use this value to
calculate the insulation resistance of a 1 km length of each core.
8.1.3

Requirement

None of the resulting values shall be below the minimum insulation resistance value specified in the
cable standard.

8.2

Insulation resistance for cables with maximum conductor temperatures


exceeding 90 C

NOTE Further basic information on this test method may be obtained from HD 429, Clause 6 Test pieces for the volume
resistivity measurement.

8.2.1

Test sample

Make the test on the same sample of cable used for the voltage test in Clause 7 or, in the case of
1-core unsheathed cable, to the test described in Clause 6.
8.2.2

Procedure

Cut a test piece 1,40 m long from the cable or core to be tested. Cover this test piece with a semiconducting layer, and over this layer apply a metal braid or a metal tape in such a way as to obtain an
active measuring length of 1,0 m.
At both ends of the active measuring length, leaving a gap 1 mm wide, apply a protective wire binding
of approximately 5 mm length (see Figure 1).
Wind the test piece to form a ring with a diameter of approximately 15D but at least 0,20 m
(D = nominal outer diameter of insulation).

Maintain the test piece in an air oven for at least 2 h at the test temperature specified in the relevant
cable standard, leaving a clearance between the sample and the walls of the air oven of at least
50 mm.
After the conditioning period a d.c. voltage between 80 V and 500 V shall be applied between the
conductor and the screen (semi-conducting layer and metal braid/metal tape including the protective
wire binding), the sample still being kept in the air oven.
The insulation resistance shall be measured 1 min after application of the voltage and this value shall
be used to calculate the insulation resistance of a 1 km length of cable.
8.2.3

Requirement

None of the resulting values shall be below the minimum insulation resistance value specified in the
cable standard.
NOTE Annex A shows the calculation method for minimum insulation resistance.

Key
1

guard electrode (protective wire binding)

EN 50395:2005

screen electrode

Figure 1 Positioning of electrodes

9
9.1

Long term resistance of insulation to d.c.


Test sample

Carry out the test on a sample of cable of 5 m length from which all coverings have been removed.
The cores of flat unsheathed cords shall not be separated.
For cables having up to five cores, each core shall be tested. For multicore cables having more than
five cores, one core of each colour in the cable shall be tested, and where the number of colours is
less than 5, duplicate coloured cores shall be tested as necessary to bring the number of cores tested
up to a minimum of 5.
Take care to avoid damage to the core(s) during removal of the coverings.

9.2

Procedure

Immerse the sample, for the period and at the temperature given in the relevant cable standard, in an
aqueous solution of sodium chloride having a concentration of 10 g/l, with a length of about 250 mm at
each end of the sample projecting above the solution. Connect the negative pole of a 220 V d.c.
supply to the conductor(s) of the sample and the positive pole to a copper electrode immersed in the
solution for the time given in the relevant cable standard.

EN 50395:2005

9.3

10

Requirement

No breakdown of the insulation shall occur during the test and, after the test, the exterior of the
insulation shall show no sign of damage.
NOTE Discoloration of the insulation should be ignored.

10 Check for the absence of faults in insulation


10.1 General
Test all cable that is in the final stage of manufacture, whether it is in delivery lengths or in
manufacturing lengths prior to being cut into delivery lengths.
Test single core cables, whether sheathed or unsheathed, by the spark test in accordance with 10.2.
Test all other cables, including sheathed flat cables, by the voltage test in accordance with 10.3.
The requirements of 3.1 of this European Standard do not apply when the check for absence of faults
is carried out as a Routine (R) test.

10.2 Spark test


10.2.1 Procedure

Carry out the test according to EN 50356, except that the option to use a pulsed waveform high
voltage source is not permitted.
10.2.2 Requirement
No faults shall be detected during the test.

10.3 Voltage test


10.3.1 Procedure
With the cable in the dry state and at ambient temperature apply a voltage of the magnitude given in
the relevant cable standard, supplied either from an a.c. source or from a d.c. source, between each
conductor and all the other conductors and, if any, the metallic layer connected to earth.
Increase the voltage gradually and maintain it at the full value for the duration given in the relevant
cable standard.
10.3.2 Requirement
No breakdown of the insulation shall occur during the test.

11

EN 50395:2005

11 Surface resistance of sheath


11.1 Test samples
Carry out the test on three samples of completed cable, each about 250 mm in length.

11.2 Procedure
Clean the sheath of each of the samples with industrial methylated spirit, and apply to each sample
two electrodes, consisting of wire helices of copper wire of between 0,2 mm and 0,6 mm diameter, at a
distance of (100 2) mm from each other. After the wire has been applied, clean the surface of the
sheath again thoroughly between the electrodes.
Condition the samples with electrodes attached in a conditioning chamber at a temperature of
(20 2) C and a relative humidity of (65 5) % for 24 h.
Immediately after removal from the conditioning chamber, apply a d.c. voltage of between 100 V and
500 V between the electrodes, and measure the resistance after 1 min.
Multiply the measured resistance of each sample, in ohms, by a/100, where a is the circumference of
the sheath of the sample, in millimetres. Record the median of the three values so obtained as the
surface resistance of the sheath.

11.3 Requirement

The median of the three values so obtained shall be not lower than the value in the cable standard.

12 Transfer impedance
The test shall be carried out in accordance with EN 50289-1-6, clause 6.
NOTE EN 50289-1-6 is maintained by the Technical Committee CENELEC TC 46X, Communication cables.

EN 50395:2005

12

Annex A
(informative)
Calculation of minimum insulation resistance
A.1

Basic formula

The general basic formula is:

D
R = 0,0367. .10 8. log
d
where:
R =

insulation resistance in M.km

volume resistivity in .m

d =
the diameter of the bare conductor as given in EN 60719 Table 1 (class 1 and class 2
conductors) or Table 2 (class 5 and class 6 conductors)
D =
d + twice the specified mean value of the thickness of the insulation and any
mandatory separator between conductor and insulation.

NOTE For cables with PVC insulation, the volume resistivity of the insulation compounds at the operating temperature of the
cable is assumed to be 10+8.m. Thus the general formula reduces to:

D
R = 0,0367. log M . km
d

A.2

Rounding

As the requirement in cable standards is for a minimum value the calculated value of R should be
rounded down to two significant figures.

A.3

Examples of calculation
HD 21.3 S3, Table 1, H07V-R
Conductor
crosssection

Insulation
thickness

Conductor
diameter
(d)

Overall
diameter

R (rounded)

mm

mm

mm

mm

M.km

M.km

1,5

0,7

1,45

2,85

0,010 77

0,010

35

1,2

7,0

9,4

0,004 699

0,004 6

50

1,4

8,2

11,0

0,004 682

0,004 6

13

EN 50395:2005

Annex B
(informative)
Source of electrical test methods in EN 50395

Test

Source (subclause number)

Clause in EN 50395

HD 21.2 S3

HD 22.2 S3

Electrical resistance
of conductor

2.1

2.1

Voltage test on
completed cable

2.2

2.2

Voltage test on cores

2.3

2.3

Insulation resistance

2.4

2.4

Long term resistance


of insulation to d.c.

2.5

2.5

Test to check
absence of faults on
insulation

2.6

2.6

10

Transfer impedance
(Screening efficiency)

2.7

Surface resistance of
sheath

2.8

12

2.7

11

EN 50395:2005

14

Bibliography

The following documents are referred to in the text for information.


HD 21.2 S3:1997

Cables of rated voltages up to and including 450/750 V and having


thermoplastic insulation - Part 2: Test methods

HD 22.2 S3:1997

Cables of rated voltages up to and including 450/750 V and having crosslinked insulation - Part 2: Test methods

HD 429

Methods of test for volume resistivity and surface resistivity of solid electrical
insulating materials (IEC 60093)

HD 605

Electric cables - Additional test methods

EN 50289 Series

Communication cables - Specifications for test methods

blank

BS EN
50395:2005

BSI British Standards Institution


BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001.
Fax: +44 (0)20 8996 7001. Email: orders@bsi-global.com. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.
Information on standards

BSI provides a wide range of information on national, European and


international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: info@bsi-global.com.
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001.
Email: membership@bsi-global.com.
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means electronic, photocopying, recording or otherwise without prior written
permission from BSI.

BSI
389 Chiswick High Road
London
W4 4AL

This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.
Details and advice can be obtained from the Copyright & Licensing Manager.
Tel: +44 (0)20 8996 7070. Fax: +44 (0)20 8996 7553.