Coal is widely available and cheap fuel for industries. We offer highly
efficient Thermal Oil Heater using bituminous coal as fuel. Now you can
get the advantage of the low cost coal to run your process.
Fuel Flexibility
100 % capacity of the boiler can be obtained with
nearly all types of coals. No capacity reduction for lower
heating value.
latest development in
control system
latest development in
control system
other advantages of
thermal oil system
other advantages of
thermal oil system
Fully Automatic
The entire heating plant from fuel storage, feeding, combustion and the
oil circuit operates automatically to give continuous supply of hot heat
transfer fluid to the process. There are adequate safeties to ensure a
safe and reliable operation.
No Need of Softener
Thermal oil systems do not need equipment like softeners as required
for water or steam system.
8
capacity selection
BASUKI can design, supply, and erect thermal oil heating plants of
capacity from 400,000 kcal/hr to 6,000,000 kcal/hr, using variety of
solid fuels. Other capacity are available on request.
Description U/M VTF-04 VTF-06 VTF-10 VTF-15 VTF-20 VTF-25 VTF-30 VTF-40 VTF-50 VTF-60
THERMAL CAPACITY kcal/hr 400,000 600,000 1,000,000 1,500,000 2,000,000 2,500,000 3,000,000 4,000,000 5,000,000 6,000,000
Thermal Oil Flow Rate m3/hr 28 42 70 105 140 175 210 280 350 420
Maximum oil temperature 300 C 300 C 300 ºC 300 ºC 300 ºC 300 ºC 300 ºC 300 ºC 300 ºC 300 ºC 300 ºC
Temperature rise 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC 30 ºC
Inlet/Outlet Header size DN 65 80 100 150 150 150 150 200 250 250
Coal consumption *) kg/hr 87 130 217 325 433 542 650 867 1,083 1,300
Oil content of coil liter 400 650 1,050 1,300 2,100 2,300 3,750 4,400 7,350 7,400
Chimney; Diameter mm 320 400 500 600 700 800 900 1,000 1,100 1,200
Height m 20 20 20 20 20 20 20 20 20 20
Overal dimension; Furnace Height ( H2 ) mm 2,619 3,193 3,917 4,279 5,929 5,281 6,305 6,850 7,455 8,402
Diameter ( D ) mm 1,613 1,804 2,176 2,404 2,736 2,972 3,176 3,372 3,772 3,973
Overal dimension; Coil assembly Diameter ( D ) mm 1,613 1,804 2,176 2,404 2,736 2,972 3,176 3,372 3,772 3,973
Height ( H1 ) mm 1,500 1,500 1,500 2,000 2,000 2,500 2,500 2,500 2,550 2,550
Total transportation weight; Furnace ( 1 ) kgs 3,434 3,841 6,753 5,118 9,325 9,010 12,899 13,243 16,013 18,159
Coil ( 2 ) kgs 2,003 4,283 6,580 7,936 10,931 12,584 17,414 20,043 28,361 34,127