Professional Documents
Culture Documents
Architectural summary
The strategy for the recommendations provided in
the following tables is to allow the system to
support any realistic combination within the
recommended limits without negative effect on the
total performance.
Function
Enterprise Server
Automation Server
Comment
Number of servers
32
Number of concurrent
10
WebStation or WorkStation
connections
Enterprise Server: 2
engineering users
Automation Server: 1
engineering user
Number of concurrent
mobile connections
Function
Enterprise Server
Automation Server
Comment
100
30b
Maximum number of
LonWorks devices per
server
200
64b
200
64b
400
400
Maximum number of
LonWorks networks
a) Xenta 280/300/401 needs to be of version 3.6 or higher. In version 3.8, a new feature improves the performance up to 500%
when reading values in StruxureWare Building Operation.
b) When using both LonWorks and BACnet MS/TP networks on the Automation Server, the network with more than 10 devices
connected is considered to be the main network. The other network then supports up to 10 devices. The main network will
support the number of devices specified in the table for the used protocol. For example, if the Automation Server has 64
LonWorks devices connected to it, the BACnet MS/TP network can support 10 devices.
www.schneider-electric.com/buildings
June 2013
Table: LonWorks
[SmartStruxure Solution]
2
Table: Modbus
Function
Enterprise Server
Automation Server
Comment
62
62
100
100
Maximum number of
2
concurrent TCP client
connections when acting as
TCP server
Maximum number of
Modbus objects per server
2,500
2,500
Enterprise Server
Automation Server
Comment
Maximum number of
N/A
BACnet MS/TP devices per
server
50a
Maximum number of
BACnet/IP devices per
server
50
Maximum number of
foreign devices per sever
64
Function
600
64
a) When using both LonWorks and BACnet MS/TP networks on the Automation Server, the network with more than 10 devices
connected is considered to be the main network. The other network then supports up to 10 devices. The main network will
support the number of devices specified in the table for the used protocol. For example, if the Automation Server has 64
LonWorks devices connected to it, the BACnet MS/TP network can support 10 devices.
Enterprise Server
Automation Server
Comment
Maximum number of
internal trend logs
2,000
1,000
www.schneider-electric.com/buildings
June 2013
Table: BACnet
[SmartStruxure Solution]
3
Continued
Function
Enterprise Server
Automation Server
Comment
Maximum number of
extended trend logs
5,000
1,500
Maximum number of
records per trend log
100,000
100,000
N/A
500
Function
Enterprise Server
Automation Server
Comment
10,000
1,000
1,000
1,000
Automation Server
Comment
10,000
6,000
6,000
Table: Alarms
Table: Events
Function
Enterprise Server
Function
Enterprise Server
Automation Server
Comment
Maximum number of
variable connectors
500
Function
Enterprise Server
Automation Server
Comment
Maximum number of
connections
WebServices and
EcoStruxure Web Services
www.schneider-electric.com/buildings
June 2013
[SmartStruxure Solution]
4
Continued
Enterprise Server
Automation Server
Comment
2,000
3 seconds
1 second
Design considerations
Load measurements
There are two server properties that are relevant for
understanding the load on the Automation Server:
Memory usage (%)
CPU usage (%)
The Memory usage (%) property measures the
current RAM memory usage. The memory usage
should never exceed 80 %. No peaks should be
seen above this limit.
The CPU usage (%) property measures the current
CPU load in the Automation Server. The CPU
usage should stay below 80 %. It is normal that the
CPU usage peaks at 100 % on occasion when
lower priority activities are performed. This peak
does not affect the overall performance.
These two properties are the key measurement
points when monitoring the load of the Automation
Server. They need to be considered at all times,
especially when getting close to (or exceeding) the
defined limits. The properties can be trend logged
or online plotted in a standard trend chart. These
properties are not available for the Enterprise
Server.
Backup operations
Back up the system when users are not interacting
with the servers or the system.
Variable connectors
The system has a base philosophy where different
objects and properties are connected using
bindings. Bindings do not usually cause any
significant load to the system, but in some cases
the bindings need to be driven by an external object
called a variable connector. The user does not
create variable connectors.
The system creates variable connectors either
when there is no obvious direction of the binding
(analog value to analog value, for example) or when
passing data between protocols (LonWorks to
BACnet or LonWorks to Modbus).
Schneider Electric | Building Business
03-13027-01-en
www.schneider-electric.com/buildings
June 2013
Function
[SmartStruxure Solution]
5
Field busses
All field busses
Do not use a change of value trend log to monitor a
value outside of the Automation Server where the
trend log resides.
If possible, avoid having the Automation Server poll
values for alarms or trend logs from devices on a
field bus. Instead, use the capabilities of the field
bus protocol to transfer the value to the Automation
Server where the alarm or trend log resides.
LonWorks
A LonWorks device template can in rare cases
include thousands of objects. Each member of
each NV/CP is an object. When using these device
templates, there is a risk that the number of objects
the Automation Server database can support is
exceeded.
www.schneider-electric.com/buildings
June 2013
[SmartStruxure Solution]
6
I/O modules
The I/O module bus supports 32 devices. This limit
is determined by the terminal base hardware and
cannot be extended. Out of the 32 addressable
slots, the first slot is used for the PS-24V power
www.schneider-electric.com/buildings
June 2013