VITOTRANS 333
File in:
Vitotec technical guide folder, register4
Technical guide
Vitocrossal300, up to 142kW
(typeCM3)
Vitocrossal300
Gas fired condensing boiler
Vitocrossal300 (typeCM3) for natural gasE and LL
87 to 142kW, with MatriX radiant burner
Vitocrossal300 (typeCT3) for natural gasE, LL and LPG
187 to 635kW
187kW with MatriX radiant burner (only for natural gasE and LL)
Vitocrossal300 (typeCR3) for natural gasE, LL and LPG
787 and 978kW
Vitotrans333
Flue gas/water heat exchanger
for gas or oil fired boilers up to 6 600kW
58221983 GB5/2004
Contents
Contents
Page
Specification
1.1
1.2
1.3
1.4
1.5
Vitocrossal300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boiler control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching points and temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vitotrans333 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
4
5
6
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
8
10
11
13
13
14
16
27
28
29
31
Application examples
3.1 Vitocrossal300
H Application example1
Single boiler system with Vitocrossal300 boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Application example2
Single boiler system with Vitocrossal300 boiler
with several heating circuits and one low temperature heating circuit . . . . . . . . . . . .
H Application example3
Multi-boiler system with Vitocrossal300 boiler
with several heating circuits and one low temperature heating circuit . . . . . . . . . . . .
H Application example4
Multi-boiler system with Vitocrossal300 and Vitoplex boiler
with several heating circuits and one low temperature heating circuit . . . . . . . . . . . .
H Application example5
Multi-boiler system with Vitocrossal300 and Vitoplex boiler
with several heating circuits and one low temperature heating circuit
Vitoplex with shunt pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Application example6
Multi-boiler system with Vitocrossal300 and Vitoplex boiler
with several heating circuits and one low temperature heating circuit
Vitoplex with ThermControl and boiler circuit pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Application example7
Multi-boiler system with Vitocrossal300 and Vitoplex boiler
with three-way mixing valve and several heating circuits
plus one low temperature heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Vitotrans333 flue gas/water heat exchanger
H Application example1
Single boiler system with boiler and
Vitotrans333 flue gas/water heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Application example2
Multi-boiler system with boilers
and Vitotrans333 flue gas/water heat exchanger
connected to low temperature heating circuits with shunt pump . . . . . . . . . . . . . . . . . . . . .
H Application example3
Multi-boiler system with boilers
and Vitotrans333 flue gas/water heat exchanger
connected to low temperature heating circuits with boiler circuit pump . . . . . . . . .
3.3 Heating DHW with a cylinder loading system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Installation notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Hook-up of on-site control equipment via LON BUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix
34
36
38
40
42
44
46
47
48
49
50
62
63
5822198 GB
32
1.1Vitocrossal300
1.2Operating conditions
1.1 Vitocrossal300
Gas fired condensing boiler
H 87 to187kW for natural gasE and LL
H 248 to 978kW for natural gasE, LL and
LPG
with Inox-Crossal heating surfaces.
Rated output 87 to 978kW
Permissible operating temperature up
to 100C
Permissible safety temperature up
to 110C
Permissible operating pressure
87 to 142 kW (typeCM3) . . . . . . . . . . . . . . . 4bar
187 to 635 kW (typeCT3) . . . . . . . . . . . . . . . . 4bar
(408 to 635 kW with 5.5bar, on request)
787 and 978kW (typeCR3) . . . . . . . . . . . . . . . . 6bar
Advantages
H Vertical stainless steel Inox-Crossal
heating surfaces for high operational
reliability and long service life.
Vertical hot gas flues let condensate
drain easily downwards and out. This
prevents concentrations through
re-evaporation of condensate.
Increased self-cleaning effect through
smooth stainless steel surface.
H Highly efficient heat transfer and high
condensation rate through
heat exchanger surfaces which
intensely turbulate the flue gas flow
boiler water and hot gases flow in
counterflow.
H Standard efficiency up to 109 % through
intensive condensation. The flue gas
temperature is only approx. 5 to 15K
higher than the return temperature.
None
None
None
None
None
6.Reduced mode
7.Weekend setback
5822198 GB
" Note
For water quality requirements, see page28.
The following control units are available for the condensing boilers:
For the operation of single boiler systems
Vitotronic100 (typeGC1)
H Electronic boiler circuit control for
operation with constant temperature
or
weather-compensated operation in
conjunction with a Vitocontrol control
panel with Vitotronic 333 typeMW1S)
or
an external control unit
H for two-stage or modulating burners
H with cylinder thermostat
H with control unit for cylinder loading
system with mixing assembly
or
alternatively for regulating a constant
return with regulated three-way valve
H with integral diagnostic system
H optional function extension to supply a
default set boiler water temperature via
a 0 10 V input (accessory).
Vitotronic200 (typeGW1)
H Weather-compensated digital boiler
control unit
H for single boiler systems
H for two-stage or modulating burners
H with time switch with day and week
programs
H with programming unit with clear text
display
H with separately adjustable periods
H with cylinder thermostat
H with control unit for cylinder loading
system with mixer assembly
or
alternatively for regulating a constant
return with regulated three-way valve
H with integral diagnostic system
H optional function extension to supply a
default set boiler water temperature via
a 0 10 V input (accessory).
Vitotronic300 (typeGW2)
H Weather-compensated digital boiler and
heating circuit control
H for single boiler systems
H for max. 2heating circuits with mixer
H for two-stage or modulating burners
H with time switch with day and week
programs
H with programming unit with clear text
display
H with separately adjustable periods and
heating curves
H with cylinder thermostat
H with control unit for cylinder loading
system with mixer assembly
or
alternatively for regulating a constant
return with regulated three-way valve
H with integral diagnostic system
H optional function extension to supply a
default set boiler water temperature via
a 0 10 V input (accessory).
External demands:
H Enable boiler/open butterfly valve
H Burner stage 1ON
H Burner stage 1 and 2ON
A zero volt contact must be provided for
each command.
Connect the zero volt contacts to LV
plug-in connectorsaVD and aVH.
Vitotronic100 (typeGC1)
H Electronic boiler control unit
H for two-stage or modulating burners
H communication ability via LON BUS.
Vitotronic333 (typeMW1)
H Weather-compensated cascade control
unit for multi-boiler systems with up to
4boilers with Vitotronic100 (typeGC1)
H for max. 2heating circuits with mixer
H with time switch with day and week
programs
H incl. programming unit with clear text
display
H with cylinder thermostat
H with control unit for cylinder loading
system with mixer assembly
H with automatic lead boiler selection
H communication ability via LON BUS
H with integral diagnostic system and
additional functions
H optional function extension to supply a
default set system flow temperature via a
0 10 V input (accessory).
5822198 GB
Vitotronic 333
or
(type MW1)
VTS =
VTS =
= ATS
120
110
100
90
80
75
70
60
5822198 GB
Flow temperature in C
50
40
30
20
10
+20
+15
+10
Outside temperature in C
+5
Installation of a Vitotrans333 flue gas/water heat exchanger downstream for higher efficiency
The installation of a Vitotrans333 flue
gas/water heat exchanger downstream of
a boiler significantly increases its
efficiency. By condensing the flue gases
inside the heat exchanger, the boiler turns
into a condensing boiler according to the
requirements of the Efficiency
Directive92/42/EEC.
Increases in efficiency
through Vitotrans333 and
Vitoplex300,
Vitomax200 and 300
Increase in efficiency
through Vitotrans333 and
Vitoplex100, Vitorond200
and Vitomax100
75/60C
9.0 %
10.0 %
60/50C
10.0 %
11.0 %
40/30C
11.5 %
12.5 %
90/70C
6.0 %
7.0 %
5822198 GB
Example:
Standard efficiency of Vitoplex300=96 %
Increase in standard efficiency of
Vitotrans333 at 75/60C=9 % results in
an overall standard efficiency of the
condensing unit of 96 %+9 %=105 %.
in C
80
60
A Flow temperature at
heating system 75/60C
B Return temperature at
heating system 75/60C
C Flow temperature at
heating system 40/30C
D Return temperature at
heating system 40/30C
40
20
+15
+10
+5
-5
-10
-15
Outside temperature in C
759000kWha
Qa
=
BN=
3
N @ H u
0.96 @ 8.83kWhm
BN=89 500m3/h
BE=7 640m3/p.a.
H Savings in percent
7640 @ 100=8.5
%
89500
759000kWha
Qa
=
tot @ H u 1.05 @ 8.83kWhm 3
BB=81 860m3/h
5822198 GB
Delivery
We deliver the equipment to site on a
vehicle with crane facility and will unload
the equipment without special
requirements.
Location
A=150cm2+2
.
cm 2 (S . 50kW)
QN
kW
General requirements
The boiler location must meet the
standards laid down by the regulations
for combustion equipment for the
relevant country.
In rooms where air contamination
through halogenated hydrocarbons may
occur, such as hairdressing salons,
printing shops, chemical cleaners,
laboratories, etc., the boiler may only be
installed if adequate measures can be
taken to provide a supply of
uncontaminated combustion air.
If in doubt, please contact us.
Flow temperatures
To keep distribution losses to a minimum,
we recommend that the
H heat distribution system and the
H DHW heating
are designed for a max. of 70C (flow
temperature).
For boilers supplied with a boiler control
unit, limit the max. boiler water
temperature to 75C. The flow
temperature may be increased by
changing the control thermostat.
Safety temperatures
Viessmann boilers correspond to EN303
and DIN4702 and are all type-tested.
They are suitable for installation in sealed
heating systems to EN12828.
Permiss. flow temperatures (=safety
temperatures): up to 110C.
Maximum possible flow temperature:
approx. 15K (Kelvin) below the safety
temperature.
As delivered condition
Adjustable to
120C
110 or 100C
System design
Temperature
Flow/return
(TV/TR)
Rated output in kW
87
80
115
105
142
130
187
170
248
225
314
285
408
370
508
460
635
575
787
720
978
895
5822198 GB
40/30C
50/30C
80/60C
2.2Water connection
Heating return
Channel the return water from all
consumers or heating circuits via the
return connector into the condensing
equipment.
Vitocrossal300 is equipped with two
boiler return connectors. If only one
heating circuit is installed, connect this to
connector KR 1.
Either some or the entire volume flow can
be routed through Vitotrans333.
Heating circuits
For underfloor heating, we recommend
the use of impermeable pipes to prevent
the infusion of oxygen through the pipe
walls.
Provide system segregation in underfloor
heating systems with plastic pipes
(DIN4726) which are non-impermeable.
We supply separate heat exchangers for
this purpose.
System accessories
Application examples
5822198 GB
10
2.3Safety equipment
HK
HV
HK
HKP
AV1
AV1
SIV
EST
SDB1
HR
Further legends
TH TR
HK
HKP
HR
HV
STB
AV2
Heating circuit
Heating circuit pump
Heating water return
Heating water flow
WB
ADG
SDB2
2
E
AV1
AV2
General notes
Low water indicator
According to EN12828, boilers must be
equipped with a low water indicator
(boil-dry protection) or a minimum
pressure switch (up to 142kW).
5822198 GB
Safety valve
Equip the boilers according to EN12828
for hot water heating system with a max.
safety temperature of 110C and in
accordance with their type approval with a
type-tested safety valve.
This valve should be identified in
accordance with TRD721, i.e. with
H H up to 3.0bar permissible operating
pressure and max. 2 700kW output,
H D/G/H for all other operating conditions.
The pipework between the boiler and the
safety valve must not be able to be shut
off. Pumps, fittings or restrictions must
not be present in this pipework.
Flash trap
For boilers above 300kW, install a flash
trap with blow off and drain line adjacent
to the safety valve. Lead the blow-off line
outdoors. Any expelled steam must not
endanger anyone.
The blow-off line from the safety valve
must be designed and constructed so as
to prevent the possibility of increases in
pressure.
Arrange the outlet of the drain so that any
water expelled from the safety valve can
be safely observed and drained off.
A flash trap and blow-off line are not
required if a second high limit safety
cut-out and a second maximum pressure
limiter are installed.
11
2.3Safety equipment
>300kW
110C
110C
Control thermostat
Standard delivery of the boiler control unit
Boiler thermometer
Standard delivery of the boiler control unit
Safety valve
A 3 bar safety valve is part of the safety equipment block (applicable up to 142kW)
Flash trap
on-site*4
*1In
its delivered state, the high limit safety cut-out (STB) for Vitotronic is set to 120C and must be adjusted.
alternative to a low water indicator, a minimum pressure switch can be installed (accessory) for Vitocrossal300, 87 to 142kW.
*3Only required for systems with flow temperatures in excess of 100C; one per system required in multi-boiler systems.
*4See Vitoset price list.
*5According to EN12828, the flash trap may be omitted if an additional high limit safety cut-out plus safety pressure limiter
(maximum pressure switch) are installed (components are available as accessory flash trap alternative set).
*2As
5822198 GB
12
2.4Fuels
2.5Burner
2.4 Fuels
Vitocrossal300
Vitocrossal300 boilers are suitable for the
combustion of natural gas, town gas and
LPG to EN437 on test gases, test
pressures or in accordance with local
regulations. Viessmann MatriX radiant
burners are only suitable for the
combustion of natural gasE and LL.
Vitotrans333
Vitotrans333 flue gas/water heat
exchangers can be operated temporarily
with fuel oilEL (for a max. of 6weeks
during any heating season), when using
an oil/gas combination burner. The fuel
oilEL must comply with DIN51603 and
may contain a max. of 0.2 % sulphur.
Applications
The boiler operates with positive
pressure in the combustion chamber. Use
a burner which is suitable for the
respective resistance on the flue gas side
and the required flue pipe draught (see
the datasheet for the respective boiler).
Burner versions
You may use multi-stage or variable
(modulating) burners.
2.5 Burner
Suitable burners
Pressure jet gas burner
The burner must be tested to EN676 and
should carry the CE designation in
accordance with guideline 90/396/EEC.
Unit burners
Viessmann Unit pressure jet gas burners
are available as MatriX radiant burners
for Vitocrossal300 with 87 to 187kW. The
residual head of these burners is 70Pa.
Pressure jet gas burners made by
Weishaupt are available for
Vitocrossal300 with 248kW to 978kW.
See price list.
Supplied direct by Weishaupt.
Further suitable burners available upon
request.
Burner installation
Vitocrossal300 (typeCM3 and CT3), 87 to
187kW with MatriX radiant burner:
The boiler door for mounting the MatriX
radiant burner is part of the standard
burner delivery.
Vitocrossal300 (typeCT3), 248 to 635kW:
The hole circle for burner mounting and
the blast tube insertion hole comply with
the dimensions of a variety of renowned
burner makes.
5822198 GB
13
.
.
a 1.0 m
0.4 m
.
x 1.5 m
if
then
x 1.5 m
a 1.0 m
5822198 GB
14
5822198 GB
15
Note
A flue gas temperature protection in
conjunction with Vitocrossal300 is not
required, as the maximum permissible
flue gas temperature of 120C (flue pipe
typeB) will not be exceeded in any
operating or fault condition.
5822198 GB
16
5822198 GB
Approval certificate for the PPs flue gas system for Vitocrossal300
17
1 Boiler adaptor
(order separately)
3
4
5
C
4
3
4
5 87
2 Extension piece
required for system sizes
150 and 200mm
3 Basic duct unit
Comprising:
H Support bend
H Support rail
H Duct cover
H Spacer (3pieces)
Spacers (3pieces)
4 Pipe
2m long (2pieces=4m long)
2m long (1piece)
1m long (1piece)
0.5m long (1piece)
5 Inspection piece,
straight (1piece)
B
3
3
4
1
F
8 Inspection bend
87 (1piece)
Reducer
(from system sizes150 to 125)
2
D
A
B
C
D
E
F
Flue gas
Secondary ventilation
Flue pipe diameter
Min. internal duct size
Inspection aperture
Ventilation air
Condensate drain
B
3
15
Minimum distance for secondary ventilation between the clearance cross-section of the duct and the connection dimension:
18
System
size
External
Minimum internal
dimension duct dimensionD
(mm)
(mm)
d
round
mm
c
rectangular
Vmm
125
150
200
145
184
227
205
244
287
185185
224224
267267
5822198 GB
1 Boiler adaptor
(order separately)
3 Pipe (125mm)
2m long (1piece)
1m long (1piece)
0.5m long (1piece)
4 Inspection piece
straight (1piece)
max. 5m
5
3
4
B
C
3
2
1
5 Reducer
DN125/100
(order with Vitocrossal300, 87 to
115kW, and install next to the coaxial
roof outlet)
6 Vertical coaxial roof outlet
(100mm)
Length 1.95m
(below the roof 0.30m and
1m above the roof)
Colour black
or
roof tile red
7 Universal roof tile
(colour black or roof tile red)
or
flat roof collar
max. 1 m
5822198 GB
A Secondary ventilation
B Flue gas
C Ventilation air
(ventilation opening 1150cm2 or 275cm2)
19
15
35
60
30
25
25
10
20
60
20
40
Note
With Vitocrossal300 with MatriX radiant
burner, a draught of 70Pa is available at
the flue outlet.
40
70
50
30
70
50
15
60
30
10
40
70
20
20
50
15
30
30
50
0
80
100
120
140
160
180
200
220
Required burner draft of Matrix radient burner in Pa
(boiler and flue pipe)
240
*1Measured
from the height of the flue outlet on the boiler to the top edge of the flue
gas system.
Example
Vitocrossal300 with 314kW
Flue pipe height 16m
The following diagram shows how to
check the required draught for a flue gas
system using the adjacent diagrams.
20
40
30
30
70
25
60
20
30
100
50
15
90
10
90
80
40
80
70
90
70
60
80
0
130
150
170
190
210
100
230
250
270
290
310
330
20
30
32
10
20
117
100
120
140
Required burner draft in Pa
*2Required draught at the flue outlet
H At a flue pipe height of 16m, the
intersection with the performance/
diameter curve results in a required
draught at the flue outlet of 50Pa.
H Dropping the plumb line onto the axis
below results in a required total burner
draught of 210Pa.
5822198 GB
*1Measured
15
Support rail
a
25
System size
a
b
c
d
e
mm
mm
mm
mm
mm
125
150
200
145
125
120
264
147
184
160
137
296
163
227
200
153
490
310
125
150
200
126
185
257
350
161
228
258
350
202
260
261
480
125
150
200
402
402
734
10.5
20
400
50
50
50
e
A System size125, 150 or 200
Duct cover
(fixing material for securing the duct cover on the cover plate is part of the standard delivery)
System size
a
b
c
d
mm
mm
mm
Vmm
Spacers (3 pieces)
System size
mm
5822198 GB
21
System size
a
b
c
mm
mm
mm
125
150
200
75
125
145
83
160
184
122
200
227
125
150
200
75
205
125
145
83
225
160
184
122
300
200
227
125
150
200
75
145
125
150
150
83
184
160
170
170
122
227
200
350
310
mm
mm
mm
mm
5822198 GB
a
b
c
d
e
mm
mm
mm
125
150
200
75
145
125
83
184
160
122
227
200
125
150
200
125
160
200
Ventilation flashing
300
30
System size
mm
40
30
a
300
A Spacer
2.5
5
Inspection bend (87)
System size
a
b
c
d
e
mm
mm
mm
mm
mm
125
150
200
100
125
145
148
148
100
160
184
163
159
100
200
227
310
350
5822198 GB
e
VITOCROSSAL 300 / VITOTRANS 333
23
mm
mm
mm
mm
275
145
200
150
270
184
200
270
227
250
150
310
227
A Test nipple
B Optional connection for a flue gas high limit safety cut-out
Extension
Reducer
Reducer
a mm
b mm
c mm
125
150
205
150
200
270
Extension
a mm
b mm
c mm
125/150 150/200
125
150
210
150
200
310
5822198 GB
24
775
1195
B
A
500
110
150
150
5822198 GB
25
PlewaWerke GmbH
54662Speicher/Eifel
Schiedel GmbH & Co.
Hauptverwaltung
Lerchenstrae9
80995Munich
E
D
or Plewa adaptor
A
B
C
D
E
Adaptor
Flue gas
Secondary ventilation
MR chimney
Inspection aperture
5822198 GB
26
2.8Sound insulation
Anti-vibration measures
Anti-vibration foundations for the heat
generator are an economical and effective
measure. For this purpose, anti-vibration
supports are offered.
When sizing such supports, take the
entire operating weight of the boiler
system and, when using longitudinal
anti-vibration brackets, the condition of
the supporting surface into consideration.
Effective anti-vibration measures are
particularly important when installing
boilers into an attic. Compensators may
be used to physically separate the
combustion equipment from the building.
These should be installed into the boiler
flow, return and safety pipe and as near as
possible to the boiler.
Also insulate any braces or hanging
arrangements, if installed, against sound/
vibration transmission to the building.
Detailed information for reducing noise
emissions by combustion equipment in
heating systems can be found in
information sheet no. 10 of the BDH
(Bundesverband der Deutschen
Heizungsindustrie e. V.).
5822198 GB
27
100kW<Qx 100kW
No requirement *1
No requirement *1
100kW<Q. x 350kW
350kW<Qx1 000kW
Ca (HCO3)2x2.0mol/m3
Ca (HCO3)2x1.5mol/m3
Vmax [m3]=
1 000kW<Q
0.0313
*1The
*2
.
Q[kW]
Ca(HCO 3) 2[molm 3]
.
requirements for systems withQ>100kW apply to the replacement of the boiler in systems with originally Q>100kW and a
system water volume y20litre/kW.
*2Apply this equation for heating systems <100kW with a specific system volume y20litres/kW.
28
5822198 GB
5822198 GB
29
Neutralising system
Matching neutralising systems are
available for Vitocrossal300 condensing
boilers:
H Granulate neutralising system for
boilers up to 508kW
H Granulate neutralising system with lift
pump and granulate re-fill indicator for
boilers between 635 and 978kW.
5822198 GB
30
Gas installation
Pipe connections
All pipe connections to the boiler should
be made free from stress and torque.
Electrical installation
Operating instructions
According to EN12828, section 5 and
EN12828, section5, and EN12170/12171,
the system installer must produce
operating instructions for the whole
system.
5822198 GB
31
3.1Vitocrossal300Application example1
Application example1
Single boiler system with Vitocrossal300 boiler
System
Function description
Advantages
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
Description
1 or 2
7450650
1 or 2
1 or 2
7450642
1 or 2
7450641
5822198 GB
Item
1
2
32
3.1Vitocrossal300Application example1
Installation diagram
A
M2
2
A
M3
2
20
20
52
52
A1
M2
20 2 20 52
M3
20 52
146
143
40
41
90
28
21
5
Plug-in connector
!
Outside temperature sensor*1
?M 2 Flow temperature sensor, mixer*2
?M 3 Flow temperature sensor, mixer*2
gSM 2
gSM 3
l
aVD
aVH
Mixer motor*2
Mixer motor*2
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page50
DHW cylinder
*1Only
Neutralising system
(see also page30)
5822198 GB
*2Only
33
3.1Vitocrossal300Application example2
Application example2
Single boiler system with Vitocrossal300 boiler with several heating circuits and
one low temperature heating circuit
System
Function description
Advantages
Possible applications:
For heating circuits with varying
temperatures.
Wiring diagram
Pump connections for the underfloor
circuit.
20
N
L1
M H K
1~
L M
1~
Item
Description
1
2
1 or 2
7450650
1 or 2
1 or 2
7450642
1 or 2
7450641
7151728
7151729
34
5822198 GB
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
3.1Vitocrossal300Application example2
Installation diagram
A
M2
2
M3
2
M3
2
20
20
52
52
20
146
143
41
90
40
52
M3
20 52
28
21
5
or
A1
M2
20 2 20 52
Plug-in connector
!
Outside temperature sensor*1
?M 2 Flow temperature sensor, mixer*1
?M 3 Flow temperature sensor, mixer*1
gSM 2
gSM 3
l
aVD
aVH
Mixer motor*1
Mixer motor*1
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page50
Neutralising system
(see also page30)
DHW cylinder
for Vitotronic300.
5822198 GB
*1Only
35
3.1Vitocrossal300Application example3
Application example3
Multi-boiler system with Vitocrossal300 boiler with several heating circuits and
one low temperature heating circuit
System
Function description
Advantages
52 A1
156
L
N
open closed
open closed
N G
Item
Description
Number
Part no.
1
2
3
1
1 to 3
corresponding
heating circuits
7450650
corresponding
heating circuits
corresponding
heating circuits
7450642
corresponding
heating circuits
corresponding
heating circuits
2 to 8
7450641
or
mixer motor for flanged mixer and plug-in connector
and
contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
4
36
5822198 GB
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
3.1Vitocrossal300Application example3
Installation diagram
M2
M3
2 20 52 2 20 52
M3
2
20
20
52
52
LON
52 A1
143
146
41
40
52 A1
90
143
146
90
LON LON
41
LON LON
40
Flow 2
143
LON
40
LON
146
1
28
5
21
M2
2
20
52
LON
40
5
C
D
2
5
Plug-in connector
!
Outside temperature sensor*1
?FlowFlow temperature sensor
common heating flow*1
?M 2 Flow temperature sensor, mixer*1
?M 3 Flow temperature sensor, mixer*1
?
Flow temperature sensor
Vitotronic050
gSA 1
gSM 2
gSM 3
gS
l
aVD
aVH
A
B
5822198 GB
*1Only
Neutralising system
(see also page30)
LON
DHW cylinder
for Vitotronic333.
37
3.1Vitocrossal300Application example4
Application example4
Multi-boiler system with Vitocrossal300 and Vitoplex boiler with several heating
circuits and one low temperature heating circuit
System
Function description
Advantages
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
Item
Description
Number
Part no.
1
2
3
1
1 to 3
corresponding
heating circuits
7450650
corresponding
heating circuits
corresponding
heating circuits
7450642
corresponding
heating circuits
corresponding
heating circuits
1 to 3
7450641
and
contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
4
*1Combinations
38
of up to four boilers (incl. two or three Vitocrossal300 and one to three Vitoplex) are feasible.
5822198 GB
or
mixer motor for flanged mixer and plug-in connector
3.1Vitocrossal300Application example4
Installation diagram
M2
M3
2 20 52 2 20 52
146
143
52
LON
52
LON LON
LON LON
3
17A
52 A1
40
90
143
146
143
146
1
41
20
40
90
LON
LON
M3
2
Flow 2
20
40
41
1
28
5
21
M2
2
20
52
LON
40
Plug-in connector
!
Outside temperature sensor*1
?FlowFlow temperature sensor
common heating flow*1
?M 2 Flow temperature sensor mixer*1
?M 3 Flow temperature sensor mixer*1
?
Flow temperature sensor
Vitotronic050
aJA
sM 2
sM 3
s
A
B
5822198 GB
*1Only
sA
sK
f
Temperature sensorThermControl
Heating circuit pump mixer*1
Heating circuit pump mixer*1
Heating circuit pump
Vitotronic050
Cylinder loading pump*1
DHW circulation pump*1
Mains connection, 230V~/50Hz
Install the mains electrical isolator
in accordance with regulations
fA
gSA 1
gSM 2
gSM 3
gS
l
aVD
aVH
Neutralising system
(see also page30)
LON
Burner (stage 1)
Motorised butterfly valve
Mixer motor*1
Mixer motor*1
Mixer motor Vitotronic050
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page52
Connection LON BUS (available
connections with terminator)
DHW cylinder
for Vitotronic333.
39
3.1Vitocrossal300Application example5
Application example5
Multi-boiler system with Vitocrossal300 and Vitoplex boiler with several heating circuits
and one low temperature heating circuitVitoplex with shunt pump
System
Function description
Advantages
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
Item
Description
Number
Part no.
1
2
3
1
1 to 3
corresponding
heating circuits
7450650
corresponding
heating circuits
corresponding
heating circuits
7450642
corresponding
heating circuits
corresponding
heating circuits
7450641
1 to 3
7450642
1 to 3
7450641
1 to 3
7450642
1 to 3
1 to 3
1 to 3
7450641
on-site
on-site
or
mixer motor for flanged mixer and plug-in connector
and
contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
4
Temperature sensorT 2
Contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
Temperature sensorT 1*2
Contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
Shunt pump
Motorised butterfly valve
7
8
(typeTX3).
40
are feasible.
460kW) and Vitoplex300
5822198 GB
*1Combinations of up to four boilers (incl. two or three Vitocrossal300 and one to three Vitoplex)
*2An immersion sensor without sensor well is part of the standard delivery of Vitoplex100 (up to
3.1Vitocrossal300Application example5
Installation diagram
M2
M3
2 20 52 2 20 52
M3
2
146
143
LON
20
52
52
LON LON
LON LON
3
17B
17A
T2
143
146
40
90
143
146
90
1
41
29
52 A1
LON
LON
40
Flow 2
20
40
41
1
28
5
21
M2
2
20
52
LON
40
8
6T1
Plug-in connector
!
Outside temperature sensor*1
?FlowFlow temperature sensor
common heating flow*1
?M 2 Flow temperature sensor, mixer*1
?M 3 Flow temperature sensor, mixer*1
?
Flow temperature sensor
Vitotronic050
aJA
aJB
sM 2
sM 3
s
A
B
5822198 GB
*1Only
sA
sK
sL
f
Temperature sensorT 1
Temperature sensorT 2
Heating circuit pump mixer*1
Heating circuit pump mixer*1
Heating circuit pump
Vitotronic050
Cylinder loading pump*1
DHW circulation pump*1
Shunt pump
Mains connection, 230V~/50Hz
Install the mains electrical isolator
in accordance with regulations
fA
gSA 1
gSM 2
gSM 3
gS
l
aVD
aVH
Neutralising system
(see also page30)
LON
Burner (stage 1)
Motorised butterfly valve
Mixer motor*1
Mixer motor*1
Mixer motor Vitotronic050
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page52
Connection LON BUS (available
connections with terminator)
DHW cylinder
for Vitotronic333.
41
3.1Vitocrossal300Application example6
Application example6
Multi-boiler system with Vitocrossal300 and Vitoplex boiler with several heating circuits
and one low temperature heating circuit Vitoplex with ThermControl and boiler circuit
pump
System
Function description
Possible applications:
For heating circuits with temperature
differentials y20K.
System-specific coding
On Vitotronic333
change 3B to 3sequential switching of
boilers with flow temperature sensor. On
Vitotronic100 of Vitoplex
change 4D to 3ThermControl to boiler
circuit pump.
Advantages
Because of the separate return
connections for heating circuits with high
and low return temperatures, high
standard efficiencies up to 109 % will also
be achieved if the larger proportion of
consumers is operated at high
temperatures.
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
Item
Description
Number
Part no.
1
2
3
1
1 to 3
corresponding
heating circuits
7450650
corresponding
heating circuits
corresponding
heating circuits
7450642
corresponding
heating circuits
corresponding
heating circuits
1 to 3
7450641
or
mixer motor for flanged mixer and plug-in connector
and
contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
4
to four boilers (incl. two or three Vitocrossal300 and one to three Vitoplex) can be linked up.
For Vitoplex300, the ThermControl is part of the standard delivery.
42
5822198 GB
*1Up
3.1Vitocrossal300Application example6
Installation diagram
M2
M3
2 20 52 2 20 52
1
28
5
21
M2
2
146
143
LON
LON
40
M3
2
LON
20
52
52
LON LON
LON LON
3
17A
143
146
90
29
41
40
90
143
146
3
41
Flow 2
20
40
20
52
LON
40
Plug-in connector
!
Outside temperature sensor*1
?FlowFlow temperature sensor
common heating flow*1
?M 2 Flow temperature sensor, mixer*1
?M 3 Flow temperature sensor, mixer*1
?
Flow temperature sensor
Vitotronic050
Temperature sensor
ThermControl
sM 2 Heating circuit pump mixer*1
sM 3 Heating circuit pump mixer*1
s
Heating circuit pump
Vitotronic050
sA
Cylinder loading pump*1
sK
DHW circulation pump*1
sL
Boiler circuit pump
f
Mains connection, 230V~/50Hz
Install the mains electrical isolator
in accordance with regulations
fA
gSM 2
gSM 3
gS
l
aVD
aVH
A
B
5822198 GB
*1Only
aJA
Neutralising system
(see also page30)
LON
Burner (stage 1)
Mixer motor*1
Mixer motor*1
Mixer motor Vitotronic050
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page52
Connection LON BUS (available
connections with terminator)
DHW cylinder
for Vitotronic333.
43
3.1Vitocrossal300Application example7
Application example7
Multi-boiler system with Vitocrossal300 and Vitoplex boiler with three-way mixing
valve and several heating circuits plus one low temperature heating circuit
System
Function description
System-specific code
On Vitotronic333
Change 3B to 3sequential switching of
boilers with flow temperature sensor.
On Vitotronic100 of Vitoplex
Change 4D to 2plug-in connectorsL for
the boiler circuit pump;
Change 0C to 1boiler with constant
return temperature raising.
Advantages
Because of the separate return
connections for heating circuits with high
and low return temperatures, high
standard efficiencies up to 109 % will also
be achieved if the larger proportion of
consumers is operated at high
temperatures.
Possible applications:
For heating circuits with temperature
differentials y20K.
Equipment required
(for standard systemsequipment with additional system modules, see Vitotec folder)
Item
Description
Number
Part no.
1
2
3
1
1 to 3
corresponding
heating circuits
7450650
corresponding
heating circuits
corresponding
heating circuits
7450642
corresponding
heating circuits
corresponding
heating circuits
7450641
1 to 3
7450642
1 to 3
1 to 3
1 to 4
7450641
on-site
on-site
or
mixer motor for flanged mixer and plug-in connector
and
contact temperature sensor
or
immersion temperature sensor (incl. sensor well)
4
6
7
to four boilers (incl. two or three Vitocrossal300 and one to three Vitoplex) are feasible.
immersion sensor without sensor well is part of the standard delivery.
5822198 GB
*1Combinations of up
*2For Vitoplex300, an
44
3.1Vitocrossal300Application example7
Installation diagram
M2
M3
2 20 52 2 20 52
M3
2
146
143
LON
20
52
52
LON LON
LON LON
143
146
40
143
146
90
3
17A
90
1
41
29
52 A1
LON
LON
40
Flow 2
20
40
41
1
28
5
21
M2
2
20
52
LON
40
5T1
Plug-in connector
!
Outside temperature sensor*1
?FlowFlow temperature sensor
common heating flow*1
?M 2 Flow temperature sensor, mixer*1
?M 3 Flow temperature sensor, mixer*1
?
Flow temperature sensor
Vitotronic050
aJA
sM 2
sM 3
s
A
B
5822198 GB
*1Only
sA
sK
sL
f
Temperature sensorT 1
Heating circuit pump mixer*1
Heating circuit pump mixer*1
Heating circuit pump
Vitotronic050
Cylinder loading pump*1
DHW circulation pump*1
Boiler circuit pump
Mains connection, 230V~/50Hz
Install the mains electrical isolator
in accordance with regulations
fA
gSA 1
gSM 2
gSM 3
gS
l
aVD
aVH
Neutralising system
(see also page30)
LON
Burner (stage 1)
Three-way mixing valve
Mixer motor*1
Mixer motor*1
Mixer motor Vitotronic050
Burner (stage 2/modulation)
External hook-up and
External hook-up
see from page52
Connection LON BUS (available
connections with terminator)
DHW cylinder
for Vitotronic333.
45
Application example1
Single boiler system with boiler and Vitotrans333 flue gas/water heat exchanger
System
Function description
Advantages
System-specific coding
Change 4C to 3plug-in connector sA1
for Vitotrans333 circulation pump.
Installation diagram
20
A1
L1
E
D
Plug-in
connectorsA1
on Vitotronic100,
Vitotronic200 or
Vitotronic300
5822198 GB
Application example2
Multi-boiler system with boilers and Vitotrans333 flue gas/water heat exchanger
connected to low temperature heating circuits with shunt pump
System
Function description
Advantages
System-specific coding
On every Vitotronic100
Change 4C to 3plug-in connector sA1
for Vitotrans333 circulation pump.
Installation diagram
Wiring diagram for the connection of the
circulation pump and the motorised
shut-off valve of the Vitotrans333 flue
gas/water heat exchanger.
Plug-in connectorsA1 on Vitotronic100
20 A1
L1
L1
5822198 GB
Application example3
Multi-boiler system with boilers and Vitotrans333 flue gas/water heat exchanger
connected to low temperature heating circuits with boiler circuit pump
System
Function description
Advantages
System-specific coding
On every Vitotronic100
Change 4C to 3plug-in connector sA1
for Vitotrans333 circulation pump.
Installation diagram
20 A1
L1
L1
48
K
D
5822198 GB
28
5
5
21 17 B 52 A1 20 A1
Vitocell-L 100
Plug-in connector
%
Top cylinder temperature sensor
(terminals 1 and 2)
%
Bottom cylinder temperature
sensor (terminals 2 and 3)
aJB
Temperature sensor Vitotrans222
sA 1 Primary pump connection in the
cylinder loading system
sA
Secondary pump connection in
the cylinder loading system
sK
DHW circulation pump (not for
Vitotronic100)
gSA 1 Three-way valve Vitotrans222
Vitotrans 222
(heat exchanger set)
System-specific coding on Vitotronic1
Change 4C to 1use plug-in
connectors as primary pump for the
heat exchanger set.
Change 4E to 1use outputgS as
primary control for the heat exchanger
set.
Change 55 to 3use the cylinder
thermostat for the heat exchanger set.
5822198 GB
Boiler
Note
The cylinder loading system can be
controlled by Vitotronic100, 200, 300 or
333. Control can be achieved via a mixer
control through Vitotronic050
(typeHK1W, HK1S, HK3W or HK3S) if
none of these control units is available or
if several cylinder loading systems are
installed.
Order an additional cylinder temperature
sensor when controlling the cylinder
loading system by means of
Vitotronic100, typeGC1, or
Vitotronic050.
In multi-boiler systems, the cylinder
loading systems are controlled by
Vitotronic333.
49
3.4Installation notes
146
1 2 3
Burner stage 2 ON
Burner stage 1 ON
Settings on Vitotronic100
The high limit safety cut-out adjustment and
further settings can be made in accordance
with the system requirements.
110C 100C
100C 87C
95C 85C
Maximum temperature
of the on-site control unit
90C 80C
Contact closed:
Burner stage 1 is switched ON.
Burner stage 2 is only switched ON for
maintaining the minimum temperature.
The boiler water temperature is limited by
the electronic maximum temperature
limiter (see Vitotronic100 service
instructions), if it is set below that of
mechanical control thermostatR.
Contact closed:
Both burner stages are switched ON. The
boiler water temperature is limited by the
electronic maximum temperature limiter,
if it is set below that of mechanical
control thermostatR. Burner stage 2 is
switched OFF 2K sooner.
Contact open:
Burner stage 1 is switched OFF.
50
Contact open:
Burner stages 1 and 2 are switched OFF.
5822198 GB
3.4Installation notes
Modulation controller:
Reduce burner output
Increase burner output
A Vitotronic100
B Burner control
C Unused
5822198 GB
Contact closed:
Burner stage 1 is switched ON.
The boiler water temperature is limited by
the electronic maximum temperature
limiter (see Vitotronic100 service
instructions), if it is set below that of
mechanical control thermostatR.
Contact open:
Burner stage 1 is switched OFF.
Settings on Vitotronic100
The high limit safety cut-out adjustment and
further settings can be made in accordance
with the system requirements.
High limit safety cut-out
110C 100C
Control thermostat
100C 87C
95C 85C
Maximum temperature
of the on-site control unit
90C 80C
51
3.4Installation notes
146
1 2 3
Change code01 to 3
The connections on plug-in connectorsaVD
and aVH are required when connecting an
external control unit. The DHW cylinder
temperature and the load-dependent
cascade control must be controlled by an
external control unit.
Burner stage 2 ON
Burner stage 1 ON
Please note
An enable boiler contact is compulsory
for multi-boiler systems. This contact
must always be closed on the lead boiler.
Contact closed:
H Vitocrossal300:
The butterfly valve opens.
H Low temperature boiler:
Initially, the pre-heat function for lag
boilers is activated (see Vitotronic100
service instructions).
After the preheat function has expired,
the boiler minimum temperature will be
maintained, and the burner stages can
be controlled externally. The butterfly
valve opens.
Contact closed:
Burner stage 1 is switched ON.
Burner stage 2 is switched ON only for
maintaining the minimum temperature
(only low temperature boilers).
The boiler water temperature is limited by
the electronic maximum temperature
limiter (see Vitotronic100 service
instructions), if it is set below that of
mechanical control thermostatR.
Contact closed:
Both burner stages are switched ON. The
boiler water temperature is limited by the
electronic maximum temperature limiter,
if it is set below that of mechanical
control thermostatR. Burner stage 2 is
switched OFF 2K sooner.
Settings on Vitotronic100
The high limit safety cut-out adjustment and
further settings can be made in accordance
with the system requirements.
110C 100C
100C 87C
95C 85C
Maximum temperature
of the on-site control unit
90C 80C
Contact opened:
The butterfly valve is closed after approx.
5minutes (see Vitotronic100 service
instructions).
Burner stages cannot be switched ON
externally; a minimum temperature will
not be maintained.
52
Contact open:
Burner stages 1 and 2 are switched OFF.
Contact open:
Burner stage 1 is switched OFF.
5822198 GB
3.4Installation notes
Modulation controller:
Reduce burner output
Increase burner output
5822198 GB
A Vitotronic100
B Burner control
C Unused
Contact closed:
The burner can be externally switched.
The butterfly valve opens.
Contact closed:
Burner stage 1 is switched ON.
The boiler water temperature is limited by
the electronic maximum temperature
limiter (see Vitotronic100 service
instructions), if it is set below that of
mechanical control thermostatR.
Contact open:
The butterfly valve is closed after approx.
5minutes (see Vitotronic100 service
instructions).
Burner stages cannot be externally
switched ON.
Contact open:
Burner stage 1 is switched OFF.
Settings on Vitotronic100
The high limit safety cut-out adjustment and
further settings can be made in accordance
with the system requirements.
High limit safety cut-out
110C 100C
Control thermostat
100C 87C
95C 85C
Maximum temperature
of the on-site control unit
90C 80C
53
3.4Installation notes
Operation with a modulating burner fitted to a low temperature boiler (on-site modulation controller)
in multi-boiler systems
Connection modulating burner:
H Burner stage1fA of Vitotronic100
H Plug-in connectorl from
Vitotronic100 via the modulation
controller (on site) to burner plug-in
connectorl.
H Set the minimum temperature at the
overriding control unit with modulation
controller 5K higher than the lower
boiler water temperature (see operating
conditions in the boiler datasheet).
143
146
1 2 3 1 2 3
Modulation controller:
Reduce burner output
Please note
An enable boiler contact is compulsory
for multi-boiler systems. This contact
must always be closed on the lead boiler.
A Vitotronic100
B Burner control
Contact closed:
Initially, the pre-heat function for lag
boilers is activated (see Vitotronic100
service instructions).
After the pre-heat function has expired,
the boiler minimum temperature will be
maintained, and the burner stages can be
controlled externally.
Contact closed:
Burner stage 1 is switched ON.
The full load is switched ON only for
maintaining the minimum temperature.
The boiler water temperature is limited by
the electronic maximum temperature
limiter (see Vitotronic100 service
instructions), if it is set below that of
mechanical control thermostatR.
Contact open:
The butterfly valve is closed after approx.
5minutes (see Vitotronic100 service
instructions).
Burner stages cannot be switched ON
externally; a minimum temperature will
not be maintained.
54
Contact open:
Burner stage 1 is switched OFF.
Settings on Vitotronic100
The high limit safety cut-out adjustment
and further settings can be made in
accordance with the system requirements.
High limit safety cut-out
110C 100C
Control thermostat
100C 87C
95C 85C
Maximum temperature
of the on-site control unit
90C 80C
5822198 GB
3.4Installation notes
24V
5V
Electrical connections
Electronics
F1
250 mA
(slow)
ON
OFF 1 2 3 4
L1
S P
1 2 3
40
_ +
230V~
A
157
1 2 3
144
145
Functions
Function
DIP switch
Vitotronic
100 200/300 333 050 (see above)
4:ON 10 to 100C
4:OFF 30 to 120C
1 to 3: OFF
5822198 GB
55
3.4Installation notes
Function
Preconditions
Vitotronic100
Code01:1
Function
Preconditions
Code01:2 at Vitotronic100
Function
Preconditions
Code01:3 at Vitotronic100
Vitotronic100 with 0 10 V signal and The boiler is enabled; the minimum temperature is
enable via switching outputaVH
maintained
1 10V additional temperature default
Connecting the function extension to
Vitotronic100
Code01:3 at Vitotronic100
Contact at terminals2 and 3 of
plugaVH closed
Note
This contact must always be closed on
the lead boiler.
5822198 GB
Note
On the lead boiler the voltage must be
1V higher.
56
3.4Installation notes
Switching outputaBJ
The output optionally switches
H the heating circuit pump to a lower speed in reduced mode
or
H a feed pump, if there is a demand from a heating circuit or the DHW cylinder of Vitotronic050.
H Rated current: 8 (4)A~
The function of the switching output is determined via the DIP switches (see also page55).
Heating circuit pump connection
MIN
K1
K1
ON
SP
OFF 1 2 3 4
157
A Function extension
B Heating circuit pump
K1
K1
157
ON
OFF 1 2 3 4
S P
L1
N
L1
M
B 1~
5822198 GB
A Function extension
B Feed pump
57
3.4Installation notes
Code99
Burner OFF
Note
The frost protection of the relevant boiler
or heating circuit is no longer effective
during the controlled shutdown or when
the mixer closes. A lower boiler water
temperature or the flow temperature will
no longer be maintained.
Heating circuit1
(mixer circuitM1)
Heating circuit2
(mixer circuitM2)
Heating circuit3
(mixer circuitM3)
0
1
6
7
10
11
12
13
14
15
5822198 GB
58
3.4Installation notes
Code2
enables a changeover after
9
or
D5:0
(as delivered condition)
w
or
D5:1
rw
Heating circuit1
(mixer circuitM1 or directly
connected heating circuitA1)
Heating circuit2
(mixer circuitM2)
Heating circuit3
(mixer circuitM3)
0
1
6
7
Heating circuit1
(mixer circuitM1)
Heating circuit2
(mixer circuitM2)
Heating circuit3
(mixer circuitM3)
0
1
2
3
4
5
5822198 GB
59
3.4Installation notes
Contact open:
mod. operation,
Contact closed: two-stage operation
In code1, set the burner type to
modulating (code02:2).
Note
When scanning the burner version,
modulation appears even after an
external changeover (no rewriting).
143
1 2 3
146
1 2 3
Changeover stepped/modulating
(only for Vitotronic200 and 300)
5822198 GB
60
3.4Installation notes
Contact open:
The boiler is reinstated into the current
boiler sequence.
External connections to Vitotronic100 (typeGC1) when operating in conjunction with Vitotronic333 (typeMW1 or MW1S)
143
1 2 3
146
1 2 3
Changeover stepped/modulating
Block boiler
5822198 GB
61
5822198 GB
62
4.1Keyword index
Regulations,31
B
Boiler circuit pump,10
Boiler control units,4
Building Regulations approval
procedure,31
I
Installation location,8
L
C
Combustion air,8
Combustion Order,8
D
Delivery,8
Divicon heating circuit distributor,10
E
Efficiency, increasing,6
Expansion vessels,9
External controls,58
F
Flash trap,11
Flue gas system,14, 16, 21,31
Function extension, 0 10 V
S
Safety regulations,31
Safety temperature,9
Safety valve,11
Sizing,9
Standard efficiency,3
System accessories,10
Transportation,8
Two-stage burner,50,52
W
Water indicator, low, 11, 12
N
Neutralisation,29
O
Output limits,8
P
Pipe diameters (flue gas),20
Pipe lengths (flue gas),20
Primary side corrosion (prevention),28
5822198 GB
63
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Tel:
+44 1952 675000
Fax:
+44 1952 675040
E-mail: info-uk@viessmann.com
64
5822198 GB