You are on page 1of 4

SFG

Gas-insulated indoor switch disconnector

SFG
Gas-insulated indoor switch disconnector for secondary distribution.
Range from 12 kV to 24 kV and from 630 A to 800 A.
The SFG is a gas-insulated switch disconnector for medium
voltage switchgear within secondary distribution networks.
There are several advantages that make the SFG concept
suitable for many different applications. For instance the
compact size and the lightweight construction of the switch
disconnector are significant features for smart integration.

There are two types of operating mechanisms:


the single spring device and the double spring device.
Motor operation can be added to both types
of operating mechanisms.

Single
spring
device

Single
spring
device
with
motor
operation

Double
spring
device

Double
spring
device
with
motor
operation

SFG on the world


The SFG is an ABB global mainline product used in different
applications worldwide. It is also a standard component
in the Uniswitch concept.
Reference list: Argentina, Australia, Austria, Belgium, Brazil,
Chile, China, Croatia, Denmark, Egypt, Estonia, Finland, France,

2 Gas-insulated indoor switch disconnector

Germany, Ghana, Great Britain, Greece, Hong Kong, Indonesia,


Ireland, Italy, Iran, Ivory Coast, Japan, Jordan, Kameroon, Libanon,
Lithuania, Luxemburg, Mali, Netherlands, New-Zealand, Norway,
Poland, Portugal, Romania, Russia, Saudi-Arabia, Senegal, Spain,
Sweden, Switzerland, Taiwan, Thailand, Tunisia, Turkey, Uruguay,
Uzbekistan, USA, Yemen,

The SFG concept creates value


Compact size

Non-corrosive
leakproof enclosure

Voltage
indication
contact

Pressure relief flaps

Top Unit frame

Gas gauge
or pressure
indicator

Operating mechanism

Pressure relief channel

Voltage indication display

Gas valve

Inspection windows

Safety: user value


Safety of the SFG means safety for the operating personnel.
Wekeep the safety aspect of our apparatus continuously in
focus; weconcentrate on every step in the manufacturing process
toensure quality right down tothe last detail. One way of proving
our dedication tosafety is compliance with IEC standards.

Interlocking
device

Reliability: performance value


ABBs long experience in switching and isolating technology is an
advantage when it comes toensuring the highest reliability of the
SFG. The highest technical values and the low number of moving
parts guarantee reliable operation throughout the entire life span
of the product. The epoxy resin enclosure prevents the influence
of external disturbances and stresses.

Highlights of safety aspects:


Integrated voltage indicator
Interlocking device
Gas gauge, pressure indicator
Inspection windows
Non-corrosive leak-proof enclosure
Pressure relief channel

Highlights of reliability aspects:


Each unit is stringently tested
Used worldwide in the Uniswitch
Extremely durable and reliable operating mechanism
Local ABB support globally

Economy: financial value


In all our solutions and applications wepay attention tothe
economical aspects and cost optimisation during the total life
cycle of the product. The SFG is virtually maintenance
free and the life span is guaranteed toaminimum of 30 years.

Smart integration: process value


Webelieve that our customers rate smart integration as one
of the most important features. The SFG concept is based on
amodular construction, which offers many flexible opportunities
for you todecide on the best solution. Tomeet your requirements
and tofulfil your needs, the SFG concept includes afull range of
operating mechanism and accessories.

Highlights of economy aspects:


Long lifecycle
High mechanical endurance
Low maintenance costs
Low environmental impact

Highlights of smart integration:


Compact size
One switch many applications
Easy installation
Part of the ABB solution

Gas-insulated indoor switch disconnector 3

Technical data
Ratings

Value

Value

Value

Rated voltage

Unit
kV

12

17.5

24

Rated lighting impulse withstand voltage


Common value

kV

75

95

125

Across the isolating distance

kV

85

110

145

Rated short duration power frequency withstand voltage


Common value

kV

28

1)

38

1)

50

Across the isolating distance

kV

32

1)

45

1)

60

Rated frequency

Hz

50/60

50/60

50/60

Rated current Ir

800

800

630

Rated short time withstand current

kA

25

20

20

Rated duration of short circuit

Rated peak withstand current

kA

62.5

50

50

Making and breaking tests (IEC 60265-1, Class E3) for the SFG switch
Mainly active load current

800

800

630

Closed-loop distribution circuit current

800

800

630

Cable charging current

50 and 10

50 and 10

50 and 10

Line charging current

20

20

20

Cable and line charging current under earth faults

87

87

87

Short circuit making current

kA

62.5

50

50

25

20

20

ok

ok

ok

1530

1260

920

Mechanical endurance of switch close/open

Operations

1000

1000

1000

Mechanical endurance of switch open/earth

Operations

1000

1000

1000

+40

Making and breaking tests (IEC 60420) for the SFG switch fuse combination
Withstanding and making the cut-off current of the fuse

kA

Breaking test with long prearcing time of fuse


Breaking capacity at rated transfer current
Mechanical performance

Ambient temperature
Maximum value

+40

+40

Maximum value of 24 h mean

+35

+35

+35

Minimum value

-5

-5

-5

Altitude above sea level

< 1000

1) H
 igher values in accordance with national standards on request

For more information please contact:


ABB High Voltage Switchgear Co. Ltd., Beijing
12 Jingyuan Street
Beijing Economic-Technological Development Area
Beijing 100076, P.R. China
Phone: +86 10 6781 8000
Fax: +86 10 6781 8001
www.abb.com

3)

2) Higher altitudes on request

2)

3)

< 1000

2)

3)

< 1000

3) Lower ambient temperature on request

ABB reserves the right to perform technical


changes or modifications of this document
without prior notification. For orders agreed
conditions will be binding.
Copyright 2009 ABB.
All rights reserved.

3405PL132-W1-en. Edition 04.2009

Compliance with IEC standards: IEC 60694; IEC 60265-1; IEC 60129; IEC 60420; IEC 60282-1; IEC 62271-102; IEC 62271-105