You are on page 1of 15

Product presentation

GSec
Gas-insulated switch-disconnector

GSec
Main feature

ABB Group
Month DD, Year

| Slide 2

SF6-insulated switch-disconnector

3 positions: LINE OPEN EARTHED


(separate slots for opening and earthing)

Suitable for metal-enclosed secondary


distribution switchgear
(incoming/outgoing, with CB and fuses)

Safety

Lower part in stainless steel for partition


metallic (PM) classified panels

Interlocks to prevent incorrect operations

Plug&play accessories to cover a wide range


of applications

Reduced maintenance

Compact design

GSec
Main data and ratings
Electrical characteristics

Standards:
IEC 60694,
IEC 62271-102,
IEC 62271-105,
IEC 60265-1.

Operating
temperature:
-5C +40C (5)

Max installation
altitude:
3000 m (6)

Phase distance:
230mm

SF6 pressure:
1,48 bar
(absolute)

Rated voltage
Withstand voltage (50/60 Hz, 1 min)
- Phase-phase and phase-earth
- Between open contacts
Impulse withstand voltage (BIL 1.2/50 s)
- Phase-phase and phase-earth
- Between open contacts
Rated frequency
Rated current
Rated short-time withstand current
Rated short-time making capacity
Breaking capacity
- Active load
- No-load transformers
- No-load lines
- No-load cables
- Ring circuit
(1) up to 630A for GSec/T2
(2) up to 16kA(3s) for GSec/T2
(3) For 21 kA (3s) please contact ABB

kV

12

17,5

24

kV
kV

28
32

38
45

50
60

kVp
kVp
Hz
A
kA
kAp

75
85
50-60
800 (1)
25(2s) (2)
63

95
110
50-60
800 (1)
20(3s) (2) (3)
52,5

125
145
50-60
630
16(3s) - 20(3s) (2) (3)
40 - 52,5

A
A
A
A
A

800 (1)
16
25
50
800 (1)

800 (1)
16
25
50
800 (1)

630
16
25
50
630

Electrical and mechanical performance


(5) According to IEC 62271
(6) Ka correction factor
needed according to
62271-1

ABB Group
Month DD, Year

| Slide 3

Line electrical endurance


Earth electrical endurance
Line mechanical endurance with 1S - Single spring actuator
Line mechanical endurance with 2S - Double spring actuator
Earth mechanical endurance

class
class
class
class
class

E3 - up to 5 makings and 100 breaking of rated current


E2 - up to 5 makings
M2 - up to 5000 mechanical operations
M1 - up to 1000 mechanical operations
M0 - up to 1000 mechanical operations

Typical units
GSec/T1 and GSec/T2

GSec/T1

GSec/T2

Three positions switch disconnector

Three positions switch disconnector

1S Single spring mechanism

2S Double spring mechanism (stored energy)

Incoming/outgoing panels

Incoming/outgoing panels

ABB Group
Month DD, Year

| Slide 4

Typical units
GSec/T2F and GSec/IB

GSec/T2F

Three positions switch disconnector

2S Double spring mechanism

Fuse tripping system

Earthing switch with transmission

Fuse base

Fuse blown indicator

ABB Group
Month DD, Year

| Slide 5

GSec/IB

Three positions switch disconnector

1S Single spring mechanism

Earthing switch with transmission

For panels with removable circuit breakers

GSec
Main components and dimensions

In Line

Open

Earth
ABB Group
Month DD, Year

| Slide 6

Components
Power part Enclosure

ABB Group
Month DD, Year

| Slide 7

Lower part in stainless steel:

PM classified (metallic partition)

No leakage currents

Maximum personnel safety

Panel classified LSC2A

Compact design:

Upper part in epoxy resin

Capacitive sockets integrated in the apparatus


lower insulators

Cable connection directly to the lower bushings

Granted Sealed for life for 30 years


according to IEC 60694

Gas exhaust valve

Components
Actuators
Closing/
Opening
Speed of the
operation
Manual
operation
Automatic
operation
Earthing
switch
function

Safety

Note
ABB Group
Month DD, Year

| Slide 8

1S Single Spring

2S Double Spring

Operating energy is provided by


charging a spring (lever or motor),
which, when released, causes the
contacts to open or close

- Springs charging (with lever or motor)


- Using the stored energy for closing and
opening operations (with pushbuttons or shunts)

Independent

Independent

Lever

Lever and pushbutton

Motor

Motor and coils

- Operating energy is provided by charging a spring (with a lever),


which, when released, causes the contacts to open or close
- Independent speed
- Separate lever insertion point for line and earth operation
- Operating lever with anti-reflex function
- For motor operated actuators, in case of emergency, it is always possible to operate
manually the actuators
- In combination with fuses, opening can be
triggered by the fuse striker
- Possibility to discharge springs once loaded

Components
Actuators diagrams
1S Single Spring

2S Double Spring

time

time

Ts1
Tc
Tclose
Topen
ABB Group
Month DD, Year

Position of line contact (0 = open, 1 = closed)


Spring status (0% = discharged, 100% = charged)
Spring charging time
- manual operation: depend on operator
- automatic operation with motor = 3-4 s.
Opening or closing time of the contact < 0,3 s.
Total closing time < 5 s.
Total opening time < 5 s.

| Slide 9

Ts2
Tc
Tclose
Topen

Position of line contact (0 = open, 1 = closed)


Springs status (0% = discharged, 100% = charged)
Springs charging time
- manual operation: depend on operator
- automatic operation with motor = 3-4 s.
Opening or closing time of the contact < 0,3 s.
Total closing time < 0,3 s.
Total opening time < 0,3 s.

Components
Front cover
1.
2.
3.

4.
5.
6.
7.

Line operating slot


Earth operating slot
Line diagram with indicators
(mounted directly on the
operating shaft)
Pushbuttons (for 2S actuator)
Voltage indicators
Spring charged signal
Fuse blown signal

ABB Group
Month DD, Year

| Slide 10

Components
Accessories 1/4

Auxiliary contacts
4 line + 4 earth
Each can be a make
contact or a break contact
250 VAC - 16A
250 VDC - 0,3A

ABB Group
3th May Slide 11

Spring charging motor


For 1S and 2S actuators
AC (50Hz): 48, 110 and 220 V
DC: 24, 48, 110 and 220 V

Voltage indicators
VPIS type
Capacitive dividers
integrated in the apparatus
bottom isolators
Possibility to perform phase
concordance

Components
Accessories 2/4
Key locks and padlocking

Key locks type: standard, Ronis and Profalux


Possibility to use up to 3 padlocks

Fuse blown signaling contact


Make or break contact
In addition to the mechanical indicator
For GSec/T2F

ABB Group
3th May Slide 12

Components
Accessories 3/4

Shunt opening release (MBO)


and shunt closing release (MBC)
DC: 24, 48, 60, 110-132, 220-250
AC (50-60Hz): 48, 60, 110-127, 220-250
For GSec/T2 and /T2F

ABB Group
3th May Slide 13

Undervoltage release (MBU)


DC: 24, 48, 60, 110-132, 220-250
AC (50Hz): 48, 60, 110-132(*), 220-250(*)
For GSec/T2 and /T2F
(*) available also for 60Hz

Components
Accessories 4/4

Temperature-compensated pressure switch

Temperature-compensated device
Possibility to have also an electrical output of
the pressure

ABB Group
3th May Slide 14

Manometer
Analogic indication
Temperature-compensated scale
Possibility to have also an electrical output of
the pressure

You might also like