CT Parameters & Adequacy check calculations for 220kV Switchyard at

Ranjangaon
(4)-G71000-V0022-D001

Date:10.01.08

Client

FIATINDIA AUTOMOBILES (P) LTD.

Project

220 kV Switchyard at Ranjangaon.

Consultant

TCE Consulting Engineers Ltd, Pune.

Title

220kV CT Adequacy check calculations.

Document no:

(4)-G71000-V0022-D001

For Approval

Page:

For Review

For Information

Rev

Date

Page

Prepared

Checked

10.01.08

All

SGP

SGP

Approved

1 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

ABBREVIATIONS USED FOR CALCULATION :


ISSC =

Maximum symmetrical short circuit current.

Ipn =

CT rated primary current.

Isn =

CT rated secondary current.

ISCC EXT FAULT =

External short circuit fault current.

VK =

Knee point voltage.

Ktd =

Transient dimensioning factor.

KSSC =

Rated symetrical short circuit current factor.

K'SSC =

Effective symetrical short circuit current factor.

R'b =

Connected resistive burden.

Rb =

Rated resistive burden.

Rct =

Secondary winding resistance at 75 Deg. C

CT dimensioning formula

R ct R b
K ' SSC
R ct R ' bI

K SSC

Page:
Date:10.01.08

2 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon

Page:

(4)-G71000-V0022-D001

Date:10.01.08

SUMMARY OF CT DATA :
Sl.No
A

Description
220kV Line From

Bay No
Bay 05

800-400-200/
1A
PS
NA

Ratio
Class
Burden

Ratio
Class
Burden
Application

Relay details
220kV Point of sulpply
Ratio
Class
Burden
Application

Relay details
220kV Trfo Bay- 01
Ratio
Class
Burden
Application
Relay details

Core 2

Core 3

Core 4

Core 5

800-400800-400800-400-200/ 1A
200/ 1A
200/ 1A
PS
0.2
PS
NA
20 VA
NA

800-400200/ 1A
PS
NA

Metering &
SCADA

OC & EF
Protection

Bus Bar
Protection

7SD

NA

7SJ62

7SS52

800-400-200/
1A
PS
NA

800-400800-400800-400-200/ 1A
200/ 1A
200/ 1A
PS
0.2
PS
NA
20 VA
NA

800-400200/ 1A
PS
NA

Metering &
SCADA

OC & EF
Protection

Bus Bar
Protection

7SD

NA

7SJ62

7SS52

800-400-200/
1A
PS
NA

800-400800-400800-400-200/ 1A
200/ 1A
200/ 1A
PS
0.2
PS
NA
20 VA
NA

Pilot wire
differential

Application
Relay details
220kV Line From
Ranjangaon

Core 1

Spare

Bay 06

Pilot wire
differential

OC & EF
Protection

Spare

Spare

7SJ62

TOD Metering

Spare

NA

800-400200/ 1A
PS
NA
Bus Bar
Protection
7SS52

150 / 1A

150 / 1A

150 / 1A

150 / 1A

PS
NA

5P 20
5 VA

0.2
30 VA

0.2
30 VA

800-400200/ 1A
PS
NA

Trafo
Differeential

OC & EF
Protection

FIAPL Metering

MSETCL
SCADA

Bus Bar
Protection

7UT613

7SJ62

150 / 1A

150 / 1A

150 / 1A

150 / 1A

PS
NA

5P 20
5 VA

0.2
30 VA

0.2
30 VA

800-400200/ 1A
PS
NA

Trafo
Differeential

OC & EF
Protection

FIAPL Metering

MSETCL
SCADA

Bus Bar
Protection

7UT613

7SJ62

7SS52

220kV Trfo Bay- 02


Ratio
Class
Burden
Application
Relay details

7SS52

3 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

Page:
Date:10.01.08

A 220kV Line From Ranjangaon


A-1-1

Core 1 - Pilot wire differential Protection

Fault current Iscc =

V K K td
Ktd =

40000

I SCC
( Rct R' b ).I SN
1.3 x I PN
1.2

for Transmission Line as per Siemens catalog

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
A-1-2
Rrelay

800
1
NA
PS
NA

CT Sec. resistance(Ohms)- Rct

16

Core-1
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Burden on secondary side of Core 1 For 7SD Relay


0.05 VA

for 7SD Relay

Cable Resistance (Rc)


Length of cable from CT to relay (L)

9.48 ohm/kM
150 mtrs.

CT lead burden in two way (RL)

2 I SN 2 Rc L 1000

Connected resistive burden

R'b=Rrelay+Rlead

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

Accordingly Required resistive burden R'b=3.844 VA


A-1-3

Selecting PS Class core for 800/ 1A Ratio

Minimum required Vk as per 7SD protection manual

VK K td
A-1-4

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

872.03 V

for Ipn 800A

1005.60 V

for Ipn 400A

Selecting PS Class core for 400/ 1A Ratio

Minimum required Vk as per 7SD protection manual

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

4 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

Page:
Date:10.01.08

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SD relay requires a minimum Vk as 872.03V , and with
ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SD relay requires a minimum Vk as 1005.60V. However
selected Knee point voltage of CT is 30 ( Rct + 36) i.e. For 800/1A Vk = 1560V & for 400/1 Vk = 1320V. Hence
selected Knee point voltage is adequate.
A-2-1

Core-2 Spare

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6

800
1
NA
PS
NA

CT Sec. resistance (Ohms) - Rct

16

Core-2
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Knee Point Voltage Selected Vk = 30(Rct +36)


A-3-1

Core-3 MSETCL Metering & SCADA Purpose

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
A-3-2

800
1
20
0.2
NA

CT Sec. resistance (Ohms) - Rct

16

Core-3
400
1
20
0.2
NA
8

200
1
20
0.2
NA
4

Burden at secondary side of core-3 for metering.

Equipment
MFM
Analog Amm. 3 No
Analog MW Meter
Total

Burden in VA
0.2
4.5
1.0
5.7

CT lead burden in two way (Rlead) =

Connected resistive burden

(As calculated in B-1-2)


2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

8.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 8.544 VA , Hence selected ratio of 800-400-200/1 A with
class 0.2 & 20 VA burden is adequate.

5 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001
A-4-1

Date:10.01.08

Core 4 - OC & EF Protection with relay 7SJ62

Maximum Fault current Issc =

40000 A

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
A-4-2

Page:

800
1
NA
PS
NA

CT Secondary resistance (Ohms)-Rct

16

Core-4
400
1
NA
PS
NA

200
1
NA
PS
NA

Burden at secondary side of core-4 for protection

Rrelay

0.05 VA

Cable Resi. (RC)


Length of cable from CT to relay (L)

For 7SJ62 relays as per SIEMENS Relay manual


9.48 ohm/kM
150 mtrs.

2 Nos.

for 2.5 sq. mm CU. Cable

CT lead burden in two way (RLead) 2 I SN R L L 1000

Connected resistive burden


R'b=Rrelay+Rlead
A-4-3
Checking of CT adequacy

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.944 VA @ Isn=1A

Accordingly required resistive burden R'b=2.894VA


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

291.45 V

for Ipn 800A

VK

K'ssc
(R CT R'B ).ISN =
1.3

168.37 V

for Ipn 400A

VK

K'ssc
(R CT R'B ).ISN =
1.3

106.83

for Ipn 200A

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SJ62 relay requires a minimum Vk as 291.45V , and
with ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SJ62 relay requires a minimum Vk as 168.37,with ratio
as 200/1 A, class PS, Rct=4 ohm connected to 7SJ62 relay requires a minimum Vk as 106.83V However selected
Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V, for 200/1 A Vk = 360V.
Hence selected Knee point voltage is adequate.

6 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

A-5-1

Page:

7 of 14

Date:10.01.08

Core 5 - Bus Bar Protection with relay 7SS52

Fault current Issc =

40000 A

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
A-5-2

800
1
NA
PS
NA

CT Sec.resistance (Ohms) - Rct

16

Core-5
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Burden at secondary side of core-5 for Busbar protection

Rrelay

1.8 VA

For 7SS5 relays

Cable Resistance. (Rc)


Length of cable from CT to relay (L)

9.48 ohm/kM
150 mtrs.

for 2.5 sq. mm CU. Cable

CT lead burden in two way (RLead) 2 I SN R L L 1000

=
=

2.844 Ohm
2.844 VA @ Isn=1A

Connected resistive burden

4.644 VA @ Isn=1A

A-5-3

R'b=Rrelay+Rlead

Checking of CT adequacy

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 800

25.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 800A

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 400

50.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 400A

Selecting class PS for bus bar protection core


Minimum required VK for Ratio 800 / 1A ,RCt=16 Ohms, as per siemens protection manual for 7SS52 relays.

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

397.00 V

Minimum required VK for Ratio 400 / 1A ,RCt=8 Ohms, as per siemens protection manual for 7SS52 relays.

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

486.31 V

Conclusion :With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SS52 relay requires a minimum Vk as 397.00V, and
With ratio as 400/1 A, class PS Rct=8 ohm connected to 7SS52 relay requires a minimum Vk as 486.31V, However
selected Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V. Hence selected
Knee point voltage is adequate.

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

Page:
Date:10.01.08

B 220kV Point of supply Breaker


B-1-1

Core 1 - OC & EF Protection with relay 7SJ62

Fault current Iscc =

40000

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
B-1-2

800
1
NA
PS
NA

CT Sec.resistance (Ohms) - Rct

16

Core-1
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Burden at secondary side of core-1 for protection

Rrelay

0.05 VA

Cable Resi. (RC)


Length of cable from CT to relay (L)

For 7SJ6 relays as per SIEMENS Relay manual


9.48 ohm/kM
150 mtrs.

for 2.5 sq. mm CU. Cable

CT lead burden in two way (RLead) 2 I SN R L L 1000

Connected resistive burden


R'b=Rrelay+Rlead
B-1-3
Checking of CT adequacy

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

Accordingly required resistive burden R'b=2.894VA.


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

290.68 V

for Ipn 800A

VK

K'ssc
(R CT R'B ).ISN =
1.3

167.60 V

for Ipn 400A

VK

K'ssc
(R CT R'B ).ISN =
1.3

106.06

for Ipn 200A

Conclusion
With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SJ relay requires a minimum Vk as 290.68V , and with
ratio as 400/1 A, class PS, Rct=8 ohm connected to 7SJ relay requires a minimum Vk as 167.60,with ratio as 200/1
A, class PS, Rct=4 ohm connected to 7SJ relay requires a minimum Vk as 106.06V However selected Knee point
voltage of CT is 30 ( Rct +36) i.e. For 800/1A Vk = 1560V & for 400/1 Vk = 1320V, for 200/1 A Vk = 1200V. Hence
selected Knee point voltage is adequate.

8 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001
B-2-1

Date:10.01.08

Core-2 Spare

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6

Page:

800
1
NA
PS
NA

CT Sec.resistance (Ohms) - Rct

16

Core-2
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Knee Point Voltage Selected Vk = 30(Rct +36)


B-3-1

Core-3 TOD Metering

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
B-3-2

800
1
20
0.2
NA

CT Sec.resistance (Ohms) - Rct

16

Core-3
400
1
20
0.2
NA
8

200
1
20
0.2
NA
4

Burden at secondary side of core-3 for metering.

Equipment
Burden in VA
TOD
0.2
Analog Amm. 3 Nos.
4.5
Total
4.7
CT lead burden in two way (Rlead) =

Connected resistive burden

(As calculated in B-1-2)


2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

7.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 7.544 VA , Hence selected ratio of 800-400-200/1 A with
class 0.2 & 20 VA burden is adequate.
B-4-1

Core-4 Spare

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6

CT Sec.resistance (Ohms) - Rct

Knee Point Voltage Selected Vk = 40(Rct + 7)

800
1
NA
PS
NA
16

Core-4
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

9 of 14

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001
B-5-1

Core 5 - Bus Bar Protection with relay 7SS52

Core-5
400
1
NA
PS
NA

800
1
NA
PS
NA

CT Sec.resistance (Ohms) - Rct

16

200
1
NA
PS
NA
4

Note :- Please refer CT sizing calculation A-5 & C-5


C 220kV Line To Transformer Bay
C-1-1

Core 1 - Transformer differential Protection

Transformer rating =

50

MVA

Voltage Ratio =

220/22

KV

Percentage Imp =

13.25

Fault MVA =
(3 Ph Short Circuit)

419.28721 MVA

Fault Current Iscc =


at 220 KV side

1100.3758 A

V K K td
Ktd =

I SCC
( Rct R' b ).I SN
1.3 x I PN
4

for Transformer as per Siemens catalog

Core-1 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
C-1-2
Rrelay

Core-1
150
1
NA
PS
NA

CT Secondary resistance(Ohms)- Rct

Burden on secondary side of Core 1 For 7UT613 Relay


0.1 VA

Cable Resistance (Rc)


Length of cable from CT to relay (L)

10 of 14

Date:10.01.08

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6

Page:

for 7UT612 Relay


9.48 ohm/kM
150 mtrs.

for 2.5 sq. mm CU. Cable

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

Page:

Date:10.01.08

CT lead burden in two way (RL)

2 I SN Rc L 1000

Connected resistive burden

R'b=Rrelay+Rlead

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.944 VA @ Isn=1A

89.02 V

Accordingly Required resistive burden R'b=3.844 VA


C-1-3

Selecting PS Class core for 150/ 1A Ratio

Minimum required Vk as per 7UT612 protection manual

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

for Ipn 150A

Conclusion
With ratio as 150/1 A, class PS, Rct=1 ohm connected to 7UT613 relay requires a minimum Vk as 89.02V .
However selected Knee point voltage of CT is 500V. Hence selected Knee point voltage is adequate.
C-2-1

Core2- OC & EF Protection with relay 7SJ62

Maximum Fault current Issc =

40000 A

Core-2 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
C-2-2
Rrelay

Core-2
150
1
15
5P
20

CT Secondary resistance (Ohms)-Rct

Burden at secondary side of core-2 for protection


0.05 VA

Cable Resi. (RC)


Length of cable from CT to relay (L)

For 7SJ62 relays as per SIEMENS Relay manual


9.48 ohm/kM
150 mtrs.
2

CT lead burden in two way (RLead) 2 I SN R L L 1000

Connected resistive burden

11 of 14

R'b=Rrelay+Rlead

for 2.5 sq. mm CU. Cable

=
=

2.844 Ohm
2.844 VA @ Isn=1A

2.894 VA @ Isn=1A

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001
C-2-3

Page:

Date:10.01.08

Checking of CT adequacy

Accordingly required resistive burden R'b=2.894VA. However , Selected resitive burden = 15 VA


As per Siemens Manual the minimum required symetrical short circuit current factor (K'ssc) shall be at least 20
Minimum required Vk as per siemens protection manual

VK

K'ssc
(R CT R'B ).ISN =
1.3

59.91 V

for Ipn 150A

246.15 V

for Ipn 150A

Vk of CTs for rated class 5P20, 15VA

VK

K SCC ( R B R CT ).I SN
1.3

Conclusion
With ratio as 200/1 A, class 5P20, 15VA, Rct=1 ohm connected to 7SJ62 relay requires a minimum Vk as 59.91V &
the CT's Vk is 246.15 Volts. Hence adequate.

C-3-1

Core-3 Metering Purpose

Core-3 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6
C-3-2

Core-3
150
1
30
0.2
NA

CT Sec.resistance (Ohms) - Rct

Burden at secondary side of core-2 for metering.

Equipment
Burden in VA
MFM
0.2
Analog Amm. 3 Nos.
4.5
Total
4.7
CT lead burden in two way (Rlead) =

Connected resistive burden

(As calculated in B-1-2)


2.844 Ohm
2.844 VA @ Isn= 1 A
R'b=Rm+Rlead

12 of 14

7.544

VA @ Isn= 1 A

Conclusion
As calculated from above , the required VA burden is 7.544 VA , Hence selected ratio of 150/1 A with class 0.2 &
30 VA burden is adequate.

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001
C-4-1

Core-4 MSETCL SCADA.

C-5-1

Core-4
150
1
30
0.2
NA

CT Sec.resistance (Ohms) - Rct

Core 5 - Bus Bar Protection with relay 7SS52

Fault current Issc =

40000 A

Core-5 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC
6

Rrelay

800
1
NA
PS
NA

CT Sec. resistance (Ohms) - Rct

16

Core-5
400
1
NA
PS
NA
8

200
1
NA
PS
NA
4

Burden at secondary side of core-5 for Busbar protection


1.8 VA

For 7SS52 relays

Cable Resistance. (Rc)


Length of cable from CT to relay (L)

9.48 ohm/kM
150 mtrs.

for 2.5 sq. mm CU. Cable

CT lead burden in two way (RLead) 2 I SN R L L 1000

=
=

2.844 Ohm
2.844 VA @ Isn=1A

Connected resistive burden

4.644 VA @ Isn=1A

C-5-3

13 of 14

Date:10.01.08

Core-4 Specification:Sl. No Description


1
Primary Current Ipn (A)
2
Secondary Current Isn (A)
3
Rated Output (VA) Rb
4
Class of Accuracy
5
Accuracy Limit factor - KSSC

C-5-2

Page:

R'b=Rrelay+Rlead

Checking of CT adequacy

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 800

25.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 800A

K'SCC K td

ISCC
I PN

= 0.5 X 40000 / 400

50.00 with Ktd as 0.5 as per Siemens


Manual for Ipn = 400A

CT Parameters & Adequacy check calculations for 220kV Switchyard at


Ranjangaon
(4)-G71000-V0022-D001

Page:

Date:10.01.08

Selecting class PS for bus bar protection core


Minimum required Vk for Ratio 800 / 1A ,Rct=16 Ohms, as per siemens protection manual for 7SS52 relays.

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

397.00 V

Minimum required Vk for Ratio 400 / 1A ,Rct=8 Ohms, as per siemens protection manual for 7SS52 relays.

VK K td

I SCC (EXT. FAULT)


1.3 x I PN

(R CT R' B ).I SN

14 of 14

486.31 V

Conclusion :With ratio as 800/1 A, class PS, Rct=16 ohm connected to 7SS52 relay requires a minimum Vk as 397.00V, and
with ratio as 400/1 A, class PS Rct=8 ohm connected to 7SS52 relay requires a minimum Vk as 486.31V, However
selected Knee point voltage of CT is 40 ( Rct + 7) i.e. For 800/1A Vk = 920V & for 400/1 Vk = 600V. Hence selected
Knee point voltage is adequate.