Professional Documents
Culture Documents
_________________
Serial Number
Operation &
Maintenance Manual
68/S41TX-03XXX
Rev. 0
March, 2003
USFilter
10 Technology Drive
Lowell, MA 01851
Technical Support: 800-875-7873 ext. 5000
Telephone: 978-934-9349
Fax: 978-458-6922
Email: Lowell_TechSupport@usfilter.com
TABLE OF CONTENTS
FOR
VP SERIES TWO-BED DEIONIZER
SECTION
DESCRIPTION
PAGE
PREFACE PAGES
Disclaimer Statement ................................................................................... i
Proprietary Rights Statement ....................................................................... i
Manual Users Guide .................................................................................. ii
Equipment Support .................................................................................... iii
1.0
INTRODUCTION
1.1
1.2
1.3
2.0
2.1
2.2
2.3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.0
TABLE OF CONTENTS
FOR
VP SERIES TWO-BED DEIONIZER
SECTION
DESCRIPTION
4.0
OPERATION
4.1
4.2
4.3
4.4
4.5
4.6
5.0
PAGE
5.1
5.2
6.0
6.1
6.2
6.3
7.0
7.1
7.2
7.3
8.0
8.1
8.2
8.3
9.0
9.1
DISCLAIMER STATEMENT
The VPT Series Two Bed Deionizer Operation and Maintenance (O&M) manual should be used with
the vendor literature in Section 9.0 of this manual. Both sources should provide the most current and
complete information to meet your operating and/or service requirements as available at the time of
publication. However, USFilter assumes no responsibility for the technical content of the vendor
literature in Section 9.0 of this manual.
The information in these manuals may not cover all operating details or variations, or provide for all
conditions concerning installation, operation and maintenance. Should questions arise which are not
answered specifically in this manual, contact the USFilter Service Department at the toll free number on
this manuals front cover.
USFilter reserves the right to make engineering refinements that may not be reflected in these manuals.
The material in these manuals is for informational purposes and is subject to change without notice.
Page numbering will skip over any special documents and continue on the page
following the document. Special documents will be noted with an introduction
statement that is listed in the table of contents.
Warnings, Cautions, and Notes are used to attract attention to essential or critical information in a manual.
Warnings and Cautions will appear before the text associated with them, and notes can appear either before
or after associated text.
WARNING
CAUTION
NOTE:
Notes are used to add information, state exceptions, and point out areas that may
be of greater interest or importance.
ii
EQUIPMENT SUPPORT
USFilter continually strives to provide safe, efficient, trouble-free equipment using the optimum
technology for your application. If problems should develop, USFilters worldwide network of technical
support will be available to provide assistance. For service, sales, parts, or additional manual copies, call
your area sales representative or the telephone numbers provided on this manuals front cover.
iii
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-1
Rev. 0
1.0
1.1
INTRODUCTION
VPT-016
10
VPT-020
17
VPT-024
24
VPT-030
38
VPT-036
54
VPT-042
74
VPT-048
97
VPT-054
123
VPT-060
153
VPT-066
182
VPT-072
220
The VP Series two bed deionizers consist of an acid regenerated cation vessel piped in
series with a caustic regenerated anion vessel. The cation resin is a strong acid type and
is regenerated with 30% HCl from a carboy, tote or drum. The anion resin is a strong
base, type II and is regenerated with 50% NaOH from a carboy, tote or drum. The
regenerant chemicals are automatically diluted to the proper strength for the regeneration
of the resins.
These pre-engineered units provide high-quality water over the length of the service
cycle. The typical effluent quality is in the 10 to 25 micromho/cm range when the
influent water quality has less than 300 ppm of total dissolved solids as CaCO3 (17.5
grains per gallon). Operating conditions and an influent water analysis are required for
predicting the effluent quality and total volume of water treated before regeneration is
required. Please refer to the Process Influent Guidelines for more information on the
influent water requirements.
VP TWO-BED DEIONIZER
INTRODUCTION
1.1.1
Page 1-2
Rev. 0
Mechanical Description
Two pressure vessels are piped in series (left to right orientation). The first vessel
contains cation resin shipped in the sodium form. The second vessel contains anion resin
shipped in the chloride form. The two-bed system must be regenerated before being put
into service with 30% HCl (cation) and 50% NaOH (anion).
The piping is constructed of Schedule 80 PVC using socket-welded and flanged fittings.
Complete piping from the inlet of the cation to the outlet of the anion is provided. Reassembly of the interconnecting piping is required, unless the skid-mounted option is
selected. All automatic valves are spring-to-close, except the backwash, rinse outlets,
and dilution water to the eductors. These are actuated using dry, oil-free, instrument air.
Four structural steel legs, designed for seismic zone 2A (standard) or seismic zone 4
(optional) support each vessel.
The skid-mounting option provides a structural steel open frame secured to both vessels,
eliminating the need for re-assembly of the interconnecting piping. The skid options
consist of frames designed for seismic zone 2A (standard) or seismic zone 4 (optional).
All external steel surfaces are sandblasted and coated with durable epoxy paint. The
interiors of the vessels are sandblasted and lined with a chemical and abrasion-resistant
vinyl ester coating. Baked PVC linings are available as an option.
Regenerant eductors are supplied in the face piping of each vessel and will require the
customer to supply concentrated chemicals within the immediate vicinity of the
equipment.
1.1.2
Electrical Description
To control the operational sequences and monitor the performance of the VP Series two
bed deionizer, a highly reliable solid-state programmable logic controller (PLC), flow
totalizing meter and conductivity monitor are provided. Opening and closing of the
process valves is accomplished using instrument air and solenoid pilot valves located on
the control enclosure. The flow totalizing meter and conductivity monitor is used to
initiate the regeneration sequence. Flow and conductivity meters are mounted in the
panel door for ease of viewing. Adjustment of the factory pre-set step times is easily
accomplished by using the Data Access Tool (DAT) which is provided with the
equipment and located inside of the enclosure. All electrical components are contained
within a NEMA 4 enclosure for protection from humidity, moisture and dust.
1.1.3
Operational Description
The deionizer has two modes of operation, manual and automatic. In the manual mode,
operator intervention is required to start the regeneration sequence and return the unit to
service. A high conductivity alarm and a totalized gallon throughput alarm are provided
to alert the operator that regeneration is required. In the automatic mode, all functions
are performed without operator intervention.
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-3
Rev. 0
When the volume of water treated or the product water conductivity has exceeded the
pre-set values, the unit is automatically taken off-line and the regeneration sequence
begins. A low flow recirculation pump can be supplied as an option to maintain a
minimum flow rate through the deionizer during periods of low or no product water
demand while in the service mode.
Regeneration of the cation and anion vessels occurs sequentially; that is, the cation vessel
is regenerated first, then the anion vessel is regenerated. Anion regeneration water is
derived from the cation vessel. The rated capacity (Kgrains) of the deionizers is based on
the anion resin volume. The regeneration sequence for each vessel consists of four steps:
backwash, chemical in, slow rinse and fast rinse.
Duplex systems will operate in an alternating or parallel fashion. In the alternating
fashion, one set of deionizers will be in the service mode while the other set of deionizers
will be in the regeneration or standby mode. This provides a continuous, uninterrupted
supply of deionized water. In the parallel mode, each deionizer operates independently
as two single units. Each of the deionizers will be provided with a PLC and solenoid
pilot valves, pre-tubed to the process valves and pre-wired to the PLC terminal strip. The
duplex alternating configuration requires wiring of the interlocks between the two
enclosures by the customer.
1.1.4
Design Parameters
Feed Temperature:
45 to 95 F
Feed Pressure:
45 to 100 psig
5 NTU
Anion Vessel
3
Sizing:
Bed Depth:
36 inches
42 inches
Capacities:
20 Kgr/ft3
17 Kgr/ft3
Regeneration:
Freeboard:
VP TWO-BED DEIONIZER
INTRODUCTION
1.2
Page 1-4
Rev. 0
Standard Specifications
Pressure Vessels:
Materials:
Rating:
Support:
Access Openings
16, 20, and 24 diameter
30 through 72 diameter
Process Connections:
Pad flange
Paint
Lining
Distribution Systems:
Upper
Lower (underdrain)
Piping Systems:
Process
Regenerant
Backwash
Actuation
Manual Valves:
Feedwater Sample
Regenerant Sample
Gauge Isolation
VP TWO-BED DEIONIZER
INTRODUCTION
1.2.2
Page 1-5
Rev. 0
Instrumentation Specifications
Pressure:
Service Inlet Gauge
Cation Effluent
Flow:
Feedwater Sensor
Feedwater Monitor
Red Lion digital display with rate and totalized flow mounted in
panel
Quality:
Product Conductivity Sensor
1.2.3
Controls Specifications
Enclosure
PLC Input/Output
DAT
Allen-Bradley
Alarm horn
Edwards, NEMA 4
Allen-Bradley
Circuit breaker
Warning alarms
Numeric displays
Red Lion, XX LED for flow rate (gpm) and total gallons
Operator interface
VP TWO-BED DEIONIZER
INTRODUCTION
1.2.4
Page 1-6
Rev. 0
Output 1 (relay)
1.2.5
Operating Limits
Temperature:
Maximum Feed Temperature
95F
45F
Pressure:
Maximum Feed Pressure
95 psig
45 psig
NOTE:
If any of the operating conditions are not within the limits given, consult the factory for the
appropriate recommendation and application assistance.
1.2.6
Parameter
Guideline
Suspended Solids
5 NTU maximum
Alkalinity
Chlorides
Sodium
Silica
Iron + Manganese
Free Chlorine
0.2 ppm
Color
5 APHA units
Organics
NOTE:
If any of the feedwater parameters are not within the limits given, consult the factory for the
appropriate recommendation and application assistance.
VP TWO-BED DEIONIZER
INTRODUCTION
1.2.7
Page 1-7
Rev. 0
Pressure Vessels
Surface Preparation
SSPC SP-10 for vessel interior, SSPC SP-6 for external steel
surfaces
Electrical
Seismic Rating
Piping
1.2.8
Documentation Package
Documents
Drawings
Software
Quality Documents
1.2.9
Diameter
016
020
024
030
036
042
048
054
060
066
072
Service (design)
10
17
24
38
54
74
97
123
153
182
220
Service (minimum)
10
14
19
23
31
39
47
55
Backwash Cation*
12
17
26
37
51
67
85
105
125
151
Backwash Anion*
Combined Fast
Rinse
10
15
20
27
34
42
50
61
10
17
24
38
54
74
97
123
153
185
220
* The backwash rates are based upon a flow temperature of 60F (16C).
NOTE:
If the service flow rate drops below the minimum values listed, the automatic low flow
recirculation pump accessory should be selected to maintain reliable performance of the
deionization system.
The service flow rate must be limited with a rate-set valve. An unrestricted flow rate will
lower the quality of the effluent.
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-8
Rev. 0
016
020
024
030
036
042
048
054
060
066
072
U.S. Filter C-211: 8% cross-linked strong acid, shipped in sodium form (50 lbs/ft3)
Cation:
Resin Volume (ft3)
10
15
21
28
36
46
57
69
82
Resin weight #
224
336
560
840
1176
1568
2016
2576
3192
3864
4592
Capacity (Kgrains)
80
120
200
300
420
560
720
920
1140
1380
1640
U.S. Filter A-244: strong base, Type II (gel), shipped in chloride form (44 lbs/ft3)
Anion:
Resin Volume (ft3)
4.5
11
17
24
33
42
54
67
81
96
Resin Weight #
198
308
484
748
1056
1452
1848
2376
2948
3564
4224
Capacity (Kgrains)
77
120
190
290
410
560
715
920
1140
1380
1640
NOTE:
The resin capacities listed are nominal values only. The actual operating capacity will
depend on the feed water composition and other operating conditions.
Refer to Section 7, Parts List, for media part numbers and specifications.
1.2.11 Regeneration Flow Rate Specifications (in gpm)
Diameter
016
020
024
030
036
042
048
054
060
066
072
Exhaustion Rinse
10
17
24
38
54
74
97
123
153
182
220
Backwash Cation
12
17
26
37
51
67
85
105
125
151
Acid In
1.7
2.5
4.2
6.3
8.8
11.8
15.1
19.3
23.9
29
34.4
1.4
2.1
3.6
5.4
7.5
10.0
12.9
16.4
20.3
24.6
29.3
10
17
24
38
54
74
97
123
153
182
220
Backwash Anion
2.9
4.6
6.6
10
15
20
27
34
42
50
61
Caustic In
1.7
2.7
4.2
6.5
9.2
12.6
16.0
20.6
25.6
30.9
36.7
1.6
2.5
4.0
6.2
8.7
11.9
15.2
19.5
24.3
29.3
34.8
Final Rinse
10
17
24
38
54
74
97
123
153
182
220
NOTE:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-9
Rev. 0
016
020
024
030
036
042
048
054
060
066
072
Exhaustion Rinse
104
168
240
376
544
744
968
1232
1528
1816
2200
Backwash Cation
107
173
248
388
561
767
998
1271
1576
1873
2269
Acid In
42
63
105
158
221
294
378
483
599
725
861
30
45
75
112
157
210
270
345
427
517
615
62
101
144
226
326
446
581
739
917
1090
1320
Backwash Anion
43
69
99
155
224
307
399
508
630
749
908
Caustic In
77
120
189
292
413
567
722
928
1152
1392
1650
34
53
84
129
182
251
319
411
509
616
730
Final Rinse
104
168
240
376
544
744
968
1232
1528
1816
2200
30% HCl
6.3
9.4
16
23
33
44
56
72
89
108
128
50% NaOH
4.2
6.6
10
16
23
31
40
51
63
76
91
Anion Regen
258
411
612
953
1363
1869
2409
3079
3819
4573
5488
Waste Water
604
961
1423
2212
3173
4331
5604
7149
8866
10593
12752
Totals
NOTE:
10
15
25
21
6
15
45
21
10
Total Time
168
Water
Water
5% HCl
Water
Water
Water
4% NaOH
Water
Water
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-10
Rev. 0
016
020
024
030
036
042
048
054
060
066
072
Service Inlet
Service Outlet
Drain
Control Air
024
030
036
042
048
054
060
066
072
153
185
220
016
020
Electrical
Control Air
Feedwater
Maximum Drain
(gpm)
Floor Drain
10
16
24
38
54
74
92
123
A floor drain (in addition to waste drain) should be supplied for general purposes.
Option Items:
Low Flow
Recirc.
0.75 hp
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-11
Rev. 0
016
020
024
030
036
042
048
054
060
066
072
72
72
72
72
72
72
72
72
72
72
72
4 8
5 4
6 0
7 0
8 0
9 0
10 0
11 0
12 0
13 0
14 0
Depth
310
40
42
411
52
55
66
610
70
78
84
Height, non-code
810
81
83
90
96
910
100
105
107
110
114
1,800
2,900
3,800
4,400
6,000
7,860
9,670
11,880
14,880
20,040
25,200
900
1,450
1,600
1,702
2,006
2,358
2,570
2,780
3,380
4,190
5,000
2325
3,740
5,370
9,950
13,650
18,300
22,785
28,300
35,290
44,920
54,550
NOTE:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-12
Rev. 0
VPT
060
Configuration
S
Simplex (see note)
Vessel Size
016 16 x 72
020 20 x 72
024 24 x 72
030 30 x 72
036 36 x 72
042 42 x 72
048 48 x 72
054 54 x 72
060 60 x 72
066 66 x 72
072 72 x 72
Vessel Rating
X
100 psig non-code
A
100 psig ASME code
Vessel Support
X
Legs, seismic zone 4
Y
Skid, seismic zone 2A
Z
Skid, seismic zone 4
Lining & Paint
B
PVC / PVC
Controls
P
Solid state PLC
Control Rating
D
NEMA 4 and UL label
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-13
Rev. 0
VP
060
Reserved
Z
Accessory
Size Code
Diam.
16
20
24
30
36
42
48
54
60
66
72
Accessory
LFR
TRP
PRV
LFR
016
020
024
030
036
042
048
054
060
066
072
Size Codes
TRP PRV
100
075S
100
075D
100
100D
125
125S
150
125D
200
200S
200
200D
250
200D
300
250S
300
250D
400
300S
LFR
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-14
Rev. 0
Description of Option:
100-psig ASME code stamped vessel. This option provides pressure vessels
designed and manufactured according to strict ASME code standards and are
supplied with a code stamp permanently affixed to the pressure vessels.
Specify Y in the Vessel
Seismic zone 2A skid. This option provides a structural steel, open frame skid
Support placeholder.
underneath the cation and anion vessels designed in accordance to seismic zone 2A,
for ease of shipment and installation. The piping between the cation and anion
vessels is shipped intact.
Specify Z in the Vessel
Seismic zone 4 skid. This option provides a structural steel, open frame skid
Support placeholder.
underneath the cation and anion vessels designed in accordance to seismic zone 4,
for ease of shipment and installation. The piping between the cation and anion
vessels is shipped intact.
* Refer to the Standard Product Ordering Information for building the part number based on the options you
have chosen.
Description of Accessory:
Enter the vessel diameter for the low flow recirculation (LFR) accessory, e.g., a 60
diameter unit would have a size code of 060.
Enter the pipe size for the resin trap (TRP) and inlet pressure reducing regulator
(PRV). The pipe size code is listed in the Accessories Ordering Information for
each diameter unit, e.g., a 60 diameter unit has 3 piping and the pipe size code is
300.
Automatic low flow recirculation pump. This accessory provides a recirculation
pump that automatically takes the effluent service water and directs it to the inlet
(bypassing the inlet flow meter) when the flow rate drops below the minimum
specified flow rate. The pump assembly is pre-wired to a junction box and shipped
loose. Customer will be required to provide the wiring between the control
enclosure and the junction box as well as piping from the pump assembly to the
deionizer.
Effluent resin trap. This option provides a PVC slotted strainer in the effluent
piping of the anion vessel to prevent a catastrophic loss of resin to downstream
processes. The strainer is housed in a clear PVC sight glass to permit visual
inspection. The resin trap is the same size as the service effluent piping on the
deionizer.
Pressure reducing regulator. This option provides a self-contained pressurereducing regulator on the inlet of the cation vessel to control fluctuations in
feedwater pressure +/- 5 psig. The pressure-reducing regulator is the same or
smaller size than the inlet piping of the deionizer and will require the customer to
provide reducing fittings if required.
* Refer to the Accessories Ordering Information for specifying the accessories. Each accessory item must be
ordered as a separate line item.
VP TWO-BED DEIONIZER
INTRODUCTION
1.3
Page 1-15
Rev. 0
GLOSSARY OF TERMINOLOGY
NOTE:
1.3.1
The following terms are defined as they relate to the liquid-treatment industry. Many
terms refer to processes, items or equipment not part of this order.
Terminology Common to All Systems
This section contains terms and definitions that are common to all liquid-treatment
systems.
Alkalinity:
Anion:
Bicarbonate
Alkalinity:
Calcium Carbonate
Equivalent:
The presence in a solution of hydroxyl (OH-) ions resulting from the hydrolysis of
carbonates or bicarbonates. When these salts react with water, a strong base and a
weak acid are produced, and the solution is alkaline.
This is the value obtained when salts are calculated in terms of equivalent
quantities of calcium carbonate; a convenient method of reducing all salts to a
common basis for comparison.
PPM as CaC03=ION (PPM as such) X Equivalent WT of CaCO3
Equivalent WT of Ion
Carbonate Hardness: That hardness in a water caused by bicarbonates and carbonates of calcium and
magnesium. If alkalinity exceeds total hardness, all hardness is carbonate
hardness; if hardness exceeds alkalinity, the carbonate hardness equals the
alkalinity.
Cation:
Cavitation:
The phenomenon which occurs in a pump where there is insufficient NPSH (Net
Positive Suction Head) available. The pressure of the liquid is reduced to a value
equal to or below its vapor pressure and small vapor bubbles or pockets begin to
form. As these vapor bubbles move along the impeller vanes to a higher pressure
area, they rapidly collapse. The collapse, or "implosion" is so rapid that it may be
heard as a rumbling noise, as if pumping gravel. May result in reduced capacity,
erratic power consumption, vibration, and mechanical damage.
Colloids:
Matter of very fine particle size, usually in the range of 10-5 to 10-7 cm. in
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-16
Rev. 0
diameter.
Composite Sample:
Concentration:
Condensate:
Conductivity:
Contaminant:
Any foreign component present in another substance; e.g., anything in water that
is not H20 is a contaminant.
Degasifier:
A vessel or device that removes gasses from a liquid by increasing their surface
area and/or subjecting them to a vacuum.
Density:
Dissociation:
Ionization.
Effluent:
Electrolyte:
Elements:
Equivalent Weight:
The molecular weight of any element or radical expressed as grams, pounds, etc.,
divided by the valence.
Feed:
Flow Rate:
The volume of solution which passes through a system within a given time. Flow
rate is usually expressed in terms of gallons per minute per cubic foot of resin, or
as milliliters per minute per milliliter of resin.
Formula, Chemical:
Grab Sample:
Grain:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-17
Rev. 0
Hardness as
Calcium Carbonate: The expression ascribed to the value obtained when the hardness forming salts are
calculated in terms of equivalent quantities of calcium carbonate; a convenient
method of reducing all salts to a common basis for comparison.
Header:
Headloss:
The reduction in liquid pressure associated with the passage of a solution through
a system; a measure of the resistance of a system or component to the flow of the
liquid passing through it.
Hydroxyl:
The term used to describe the anionic radical (OH-) which is responsible for the
alkalinity of a solution.
Indicators:
Substances which change from one color to another when the hydrogen-ion
concentration reaches a certain value, different for each indicator.
Influent:
Ion
Any particle of less than colloidal size possessing either positive or negative
electric charge.
Ionization:
Ionization
Constant:
Kilograin:
A unit of weight; one thousand grains. There are seven kilograins per pound.
Mineral:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-18
Rev. 0
Mole:
Molecule:
The smallest unit quantity of matter which can exist by itself and retain all the
properties of the original substance.
Negative Charge:
The electrical potential which an atom acquires when it gains one or more
electrons; a characteristic of an anion.
Noncarbonate
Hardness:
Orifice:
pK:
pOH:
Positive Charge:
The electrical potential acquired by an atom which has lost one or more electrons;
a characteristic of a cation.
Precipitate:
Prefilter:
A filter placed before and in series with some other type of liquid-treatment
equipment.
Productivity:
The measurement of rated output, expressed in gallons/24 hour day under a given
temperature, pressure and salinity (Product Flow).
Purity:
The percentage of desirable vs. undesirable components on a weight basis per unit
volume of sample.
Raw Water:
Recovery:
The quantity of a given component by weight in the product stream vs. the
amount of that specific component in the feed.
Salinity:
Scale:
The precipitate that forms on surfaces in contact with water as the result of a
physical or chemical change.
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-19
Rev. 0
TDS:
Turbidity:
A suspension of fine particles that obscure light rays but require many days for
sedimentation because of small particle size.
1.3.2
Anion Exchange:
Attrition:
The rubbing of one particle against another in a resin bed; frictional wear that will
affect the size and life span of resin particles.
Backwash:
The counter-current flow of water through a resin bed (i.e. in at the bottom of the
exchange unit, out at the top) to clean and reclassify the bed after exhaustion. In
mixed bed deionizers, this will separate the heavier cation resin from the lighter
anion resin so that each can be regenerated separately.
Bed:
Blocking Flow:
A flow of water used during regeneration of a mixed bed that prevents caustic
from entering the cation resin layer (See "Mixed-bed").
Carboxylic:
A term describing a specific acidic group (COOH) that contributes cationexchange ability to some resins.
Cleavage and furrowing of a resin bed due to faulty operational procedures. The
solution being treated follows the path of least resistance, runs through these
furrows, and fails to contact active groups in other parts of the bed.
Channeling:
Color Throw:
Cross-Regeneration: Regeneration of a resin with a base and then an acid (or vice-versa) that is
intended to shrink and swell the resin to loosen color bodies and other materials.
De-Ashing:
The removal of inorganic salts from solution by means of adsorption by ionexchange resins of both the cations and the anions that comprise the salts. See
deionization.
Deionization:
See de-Ashing. Deionization, a more general term than de-ashing, embraces the
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-20
Rev. 0
removal of all charged constituents or ionizable salts (both inorganic and organic)
from solution.
Demineralization:
See de-ashing.
Distribution:
Double DishBottom: A concave plate inside a vessel that blocks off the bottom head (shell). Used to
eliminate problems with gravel or quartz support beds (see "support media").
Downflow:
Exchange Velocity:
The rate with which an ion is displaced from an exchanger in favor of another.
False Bottom:
A flat plate inside a vessel that blocks off the bottom head (shell). Used to
eliminate problems with gravel or quartz support beds (see "support media").
Fines:
Freeboard:
The space provided above the resin bed in an ion-exchange column to allow for
expansion of the bed during backwashing.
Greensand:
Hydraulic
Classification:
Hydrogen Cycle:
InterfaceCollector:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-21
Rev. 0
Lateral:
One of the individual drilled pipes that branch out from the internal vessel
distribution headers. Used as an entry or exit point for process fluids.
Media:
Mixed-Bed:
An ion-exchange vessel containing a mixture of cation and anion resin (in a single
bed).
Physical
Stability
The quality which an ion-exchange resin must possess to resist changes that might
be caused by attrition, high temperatures, and other physical conditions.
Polisher:
Quartz:
A hard mineral. Graded quartz is used as a support media in some liquidtreatment applications.
Regenerant:
The solution used to restore the activity of an ion exchanger. Acids are employed
to restore a cation exchanger to its hydrogen form. Brine solutions may be used
to convert the cation exchanger to the sodium form. The anion exchanger may be
rejuvenated by treatment with an alkaline solution.
Regeneration:
Reverse
Deionization:
The use of an anion-exchange unit and a cation-exchange unit (in that order) to
remove all ions from solution.
Rinse:
The final step in a unit regeneration, in which water is flushed through the unit
until the effluent quality is proper.
Riser:
The distribution (internal piping) pipe that carries a process liquid to or away
from the distribution headers.
Salt Splitting:
The act of separating cations from anions in a process feed stream. Usually done
with ion-exchange resin.
Softening:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-22
Rev. 0
Support Media:
Any type of media that is used to support the bottom distribution laterals and a
media material above it.
Sweeten-On/Off:
Terms used mostly in the sugar industry which describe the process of either
filling a vessel with syrup while displacing water from the vessel or displacing
syrup from a vessel while filling it with water.
Two-Bed:
An ion-exchange unit with a cation vessel and an anion vessel operating in series.
Usually referred to as a "deionizer".
Upflow:
Zeolite:
1.3.3
Acid:
Acidity:
Base:
Brine:
Caustic Soda:
Chelating Agents:
Organic compounds having the ability to withdraw ions from their water solutions
into soluble complexes. Used in clean-up of R.O. membranes.
Coagulation:
Elution:
VP TWO-BED DEIONIZER
INTRODUCTION
Page 1-23
Rev. 0
Flocculation:
Neutralization:
pH:
Polyelectrolyte:
Regenerant:
The solution used to restore the activity of an ion exchanger. Acids are employed
to restore a cation exchanger to its hydrogen form. Brine solutions may be used
to convert the cation exchanger to the sodium form. The anion exchanger may be
rejuvenated by treatment with an alkaline solution.
Sedimentation:
Specific Gravity:
The ratio of the mass of a body to the mass of an equal volume of water at 4o C or
other specified temperature. Dimension - unity.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
Page 2-1
Rev. 0
Operator Training
Equipment operators must be trained in the operation of the equipment and in the proper
handling of any hazardous materials or chemicals. Only experienced operators who have
studied this entire manual should be allowed to operate the equipment.
2.1.2
First-Aid Equipment
First-aid equipment must be available in all areas. This equipment must consist of items
needed to treat most common injuries and the items required by the Material Safety Data
Sheets (MSDS's) for the hazardous chemicals and materials used by your system (see
section 2.3).
2.1.3
Equipment Access
Workers must use caution when accessing the equipment. All measures must be taken to
prevent falls and other accidents when equipment is being installed or serviced.
Use extreme caution when working around liquid-treatment equipment. Valve handles,
sample pipes, and other protruding components can cause severe injury to body parts that
strike them. Workers should wear hard hats and safety glasses and should move
cautiously when working under piping and around the equipment.
Climbing on piping can cause worker injury or equipment damage due to falls and equipment
WARNING
tipping.
Never climb on piping to reach equipment or components.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
Page 2-2
Rev. 0
Whenever possible, use a wide, stable folding (free-standing) ladder and tie it to the
equipment or piping.
2.1.4
Maintain the necessary clothing and equipment to protect operating personnel. For
protection when handling hazardous chemicals or materials, refer to the MSDS's in
section 2.3.
2.1.5
Pressures
WARNING
2.1.6
Extreme caution must be used when working with high air or liquid pressures. Pressure
monitoring devices must always be installed and working properly. The liquid-treatment
system must be operated within the pressure limits given in section 1.0 of this manual.
An accidental and sudden release of pressure or fluid, accidental contact with energized
electrical components, or the sudden movement of equipment parts during maintenance
procedures can result in severe injury to workers.
Refer to the individual component literature in the Vendor Literature Manual for specific
maintenance guidelines.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
2.1.7
WARNING
Page 2-3
Rev. 0
Electricity
Electricity can shock, injure, or cause death.
Always disconnect and lock out electrical power for panels or components
before performing repairs or service.
Operators and workers must use caution when working with motors, control panels, and
other electrical components. These components must be properly wired and grounded,
and should not be allowed to come in contact with process fluids or other liquids.
2.1.8
Temperatures
WARNING
2.1.9
Operators and workers must use caution when working with processes (steam cleaning)
or components (heat exchangers, motors, pumps etc.) that involve high temperatures.
WARNING
CAUTION
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
Page 2-4
Rev. 0
Finally, inform other operators and control room workers of repairs or servicing in
progress.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
2.2
Page 2-5
Rev. 0
WARNING
Empty tanks and vessels may tip forward suddenly and without warning,
causing equipment damage or injury to workers.
Always brace tanks and vessels securely until they are loaded or are bolted to
the plant floor.
WARNING
Tanks and vessels that are empty (contain no liquids or media bed) may not balance when
stood upright. Workers must use extreme caution when working with empty tanks and
vessels and must brace them securely or mount them permanently to the plant floor.
Heavy manhole covers can cause equipment damage or severe personal
injury or death if dropped from any height.
Do not stand under workers who are removing manhole covers. Use extreme
caution when removing or moving heavy manhole covers.
Use extreme caution when removing heavy manhole covers from vessels being loaded. If
lifting davits (arms) are not provided for the covers, use a sling or chain and some type of
lifting device to remove and hold the cover. Do not remove all of the cover bolts until it
is certain that the cover is securely slung and supported and will not fall.
Falls from the top of a vessel can cause severe injury or death to workers.
WARNING
Always load vessels from a platform or lifting device. Platforms and lifting
devices must be equipped with side rails and slip-resistant surfaces where
workers will stand.
Do not stand of top of a vessel while loading it. The curved top surface does
not provide adequate footing, and the lack of hand holds and the small
surface area can lead to falls.
When a vessel is being loaded, workers must stand on a safe platform or lifting device
and must take all necessary measures to avoid falls.
If a vessel must be loaded using a ladder, use a stable, free-standing ladder that is tall
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
Page 2-6
Rev. 0
enough to allow workers to easily reach the vessel opening. If possible, tie the ladder to
the vessel with a rope.
WARNING
WARNING
If the vessel must be entered, adhere to the OSHA permit-required confined space
procedures in standard #29 CFR Part 1910.
Process fluids - especially chemicals - entering a vessel while workers are
inside can cause severe injury or death.
Make sure all of the vessel's process entry and exit points have been blinded
off.
WARNING
Before entering a vessel, verify that all connections to the vessel have been isolated and
tagged out. Also assign a person (called a "spotter") to stay outside the vessel near the
manhole. The spotter should be prepared to give assistance to those inside the vessel or
call for help in the event of an emergency.
Spilled ion exchange resin makes standing and walking extremely hazardous
and can lead to falls and worker injury.
If ion exchange resin is spilled on the surfaces where workers must stand and
walk, clean up the media immediately.
When handling vessel media (especially ion-exchange resins), avoid stepping on any of
the media that is spilled. Sweep up and dispose of the spilled media as soon as possible refer to the media MSDS in section 2.3 for cleanup details.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
2.2.2
Page 2-7
Rev. 0
Chemical Systems
This subsection covers safety precautions for those systems that use corrosive chemicals,
such as ion exchange systems, chemical day tanks and regenerant dilution stations.
Chemical systems often use highly corrosive chemicals that can cause severe
burns or blindness upon contact.
WARNING
Wear the proper personal protective equipment (PPE) when handling these
chemicals - refer to the chemical MSDS from the chemical supplier.
Equipment operators must be trained in the safe use and handling of hazardous
chemicals.
Fixed (hard-piped) eye washes and emergency showers should be installed at locations
where hazardous chemicals are stored or used.
NOTE:
Facilities such as eye washes and showers must conform to national and local
safety codes and laws.
In areas where large quantities of hazardous chemicals are stored, emergency ("escape")
respirators should provided.
Workers must wear safety glasses, face shields, respirators, and protective clothing when
working with corrosive chemicals.
Refer to the material safety data sheets from the chemical suppliers for information on
recommended safety wear, handling procedures, and storage practices for specific
chemicals.
Operators must use extreme caution when working with corrosive chemicals.
Workers must read the chemical safety information in section 2.3 carefully and must be
familiar with basic first-aid procedures for the chemicals used with this system.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
WARNING
Page 2-8
Rev. 0
Chemical sprays from pressurized piping can cause severe injury to workers.
Relieve all pressure from piping before performing service.
Wear protective clothing and face protection when disassembling chemical
piping.
WARNING
Before servicing components that handle hazardous chemicals, make sure all internal
pressure is relieved and that all chemicals have been drained.
Regenerant chemicals entering a vessel while workers are inside can cause
severe injury or death.
Make sure all of the vessel's process entry and exit points have been closed.
Before entering a vessel connected to chemical systems, follow the guidelines given
earlier in this chapter.
Provide adequate water supply to flood areas of spills - refer to the chemical MSDS's
from the chemical supplier for details on handling chemical spills.
Do not breathe chemical vapors or mists. Protect nose, mouth and lungs from damage by
wearing a NIOSH-approved breathing mask.
If chemicals are mixed manually, add chemicals slowly to the full amount of water and
stir the solution. Never add water to a chemical because boiling and spattering can result.
Do not smoke, weld, or operate electrical equipment that may arc in the vicinity where
hydrochloric acid or volatile chemicals are stored or used.
WARNING
Corrosive chemical leaks at bolted flanges and other connections can cause
worker injury and equipment damage.
Chemical-resistant safety shields are recommended for all connections in
piping that carries concentrated corrosive chemicals.
The chemical storage, pumping, and mixing systems must be properly piped, valved, and
wired, and must be leak-free. Piping carrying concentrated corrosive chemicals must be
installed properly using the proper chemically-resistant materials, and all flanged
connections should be covered with shields to prevent chemical sprays in the event of
leaks.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
2.2.3
Page 2-9
Rev. 0
WARNING
Contact with rotating drive mechanisms can cause severe personal injury.
Never operate fans, blowers, or pumps without safety shields around the
motor drive mechanisms.
Any fans, blowers, and pumps that are supplied loose (unmounted) must be properly
mounted to avoid movement and excessive vibration.
Also, all motor drive safety shields and belt guards must be properly installed, and all
supplied WARNING and CAUTION signs and labels must be maintained at the device.
Fans and blowers must be covered with shrouds and guard screens before being started.
Inlet screens for fans and blowers must have a small enough grating to keep large
particles and debris from entering the intake.
WARNING
Contact with rotating fans and blower wheels can cause severe injury to
workers.
Do not service filters, guards, or other components until the fan or blower is
stopped and locked out of operation.
2.2.4
WARNING
If glass-tube type flow meters or level gauges are used with the system, the clear safety
shields must be undamaged and must be installed properly.
VP TWO-BED DEIONIZER
SAFETY PRECAUTIONS
2.3
Page 2-10
Rev. 0
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-1
Rev. 0
The purpose of this section is to provide general information on receipt and installation of new
equipment. Procedures for the installation of specific components can be found in the Vendor Literature
Manual.
All equipment must be installed as shown on the piping, wiring and layout drawings for this job. Refer
to the drawings supplied with this equipment when reading and performing the procedures in this
section.
3.1.1
2.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.2
3.2.1
Page 3-2
Rev. 0
CAUTION
1.
NOTE:
2.
Record the item and crate numbers of all received pieces. Some crates will
contain several different tagged items; these crates should be opened temporarily
to check the different items.
Compare the item and crate numbers recorded to those shown on the shipping list
supplied with the equipment, and check off each item that has been located. If
items appear to be missing, contact the carrier and U.S. Filter immediately.
NOTE:
Small components that were removed from major components during preparation
for shipping may not have item numbers. These untagged components can be
identified by referring to the piping drawings and the part lists for this job.
3.
4.
Perform a close inspection of all shipping crates, boxes and loose components.
Verify that no damage has occurred to these pieces.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-3
Rev. 0
Check for visible damage to crates, piping, and piping ends. If a crate or box appears damaged, open the
crate or box and investigate further.
3.2.2
NOTE:
Shipping damage should be promptly reported to both U.S. Filter and the carrier
to ensure repair or replacement. Avoid releasing equipment for assembly until
all damage claims and/or shortage problems have been resolved.
5.
If the equipment will be stored before being assembled, reseal any crates that
were opened for inspection. Refer to the storage procedures given in subsection
1.3.
If the vessel(s) were loaded at U.S. Filter, use caution when opening to avoid
spilling or losing resin.
2.
3.
If damage to the lining is found, notify U.S. Filter immediately so that repairs can
be made. If the lining is not repaired before the vessels are stored, the areas of
damage must be thoroughly documented with U.S. Filter.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.3
3.3.1
Page 3-4
Rev. 0
Use the following instructions if the equipment will be stored before it is assembled.
NOTE:
To store individual system components (such as instruments, valves, controls etc.) refer
to the manufacturer's storage instructions in the Vendor Literature Manual.
Place a copy of the marked-up shipping list and the written list of received item numbers
together and store them in a safe place. If necessary, make copies of these lists and distribute
them to the individuals who will be involved in the assembly of the equipment.
Select a storage location where all U.S. Filter equipment can be stored in one area. Avoid
separating equipment, components, and crates.
On large job sites, it is easy for small or separated components to become misplaced or lost.
If the equipment must be separated, note the exact locations of all pieces on the shipping list
or the written list of received pieces.
Set the skids and other components on wooden blocks to keep them out of any standing
water and to protect their painted surfaces.
If possible, store the equipment indoors where it will be protected from sunlight and adverse
weather conditions.
If the equipment will be stored for an extended length of time (inside or outside), cover it
with plastic or canvas tarps to protect it from water, dust, paint over-spray, etc.
Items that can be damaged by water must be securely wrapped with plastic and covered with
tarps.
CAUTION
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-5
Rev. 0
If outdoor temperatures are warm, remove all vessel manhole covers to allow air circulation.
When the outdoor temperature is below 32F (0C), it is important to verify that the piping,
pumps, valves, and any other components where liquid may have accumulated are
completely drained.
CAUTION
Always drain all liquids from components that must be stored in freezing
temperatures. Expanding ice can damage components.
Open all hand valves on the equipment to allow trapped water and moisture to escape.
To store electrical panels, make sure all of the openings in the panels are sealed with tape and
that the panel doors are securely closed.
When equipment has been stored in extremely hot or cold temperatures and then is moved to
an assembly area, always allow the equipment temperature to stabilize before beginning
assembly. This is especially important if the equipment is very cold.
When equipment is brought out of storage, compare the component quantities with the
original shipping list. Any pieces that are not found at this time must be located quickly to
avoid delays in assembly and startup of the equipment.
Prior to assembly of the equipment, perform a quick recheck for possible equipment damage.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.3.2
Page 3-6
Rev. 0
CAUTION
If lined vessels are stored outside in warm weather, the vessels must be
ventilated and protected from direct sunlight.
1.
If a vessel is lined with a hard epoxy material, use extreme caution when
moving the vessel when it is cold. Epoxy linings will crack easily when cold.
CAUTION
2.
3.3.3
If a vessel lining has been damaged, it must be repaired before the vessel is
loaded with resin or other media.
Whenever lined vessels are brought out of storage, the linings must be inspected
for possible damage.
CAUTION
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.4
Page 3-7
Rev. 0
NOTE:
Below is a suggested sequence for installing the components for this system. This
sequence may be altered depending on the conditions at the jobsite. Some of the
procedures may be performed simultaneously depending on the availability of workers
and operators.
NOTE:
Before proceeding with the steps in this subsection read the installation procedures
specific to each piece of equipment provided in the Vendor Literature Manual.
1.
CAUTION
Position and level all major components as shown on the layout and piping
drawings, paying special attention to elevations and center-to-center dimensions.
If components do not attach easily or line up exactly, apply only a moderate
amount of force to install them. Excessive force will put an unnecessarily
high stress on the components, which could damage them or cause process
stream leaks.
This equipment was originally assembled at U.S. Filter using the dimensions
given on the design drawings. The components that were shipped loose or
disassembled for shipping will fit back together more easily if the original design
dimensions are adhered to during installation.
NOTE:
When installing an assembly or instrument, do not tighten the bolts and other
fasteners until all of the adjacent assemblies and instruments have been attached
to it. Then evenly tighten all of the assemblies and instruments at the same time.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-8
Rev. 0
NOTE:
Equipment which requires anchoring to the floor will be equipped with anchor
bolt holes. After positioning, aligning, and leveling each piece of equipment,
anchor it to the plant floor.
Vibrations may cause equipment to "walk" if not properly anchored to the floor.
3.
Mount all loose instruments to their proper locations. Connect the valve/piping
assemblies. Each valve/piping assembly and instrument is labeled with an item
number, which corresponds to the same item number on the shipping list and on
the piping drawings.
4.
Be sure that all of the installed equipment is braced properly so that only a
minimum amount of stress is put on the components and fasteners.
5.
Fabricate and/or install the interconnecting piping between the major components
and their subassemblies, as required. Brace as needed. Always use piping
materials that are compatible with the process stream(s) that the pipe will carry.
6.
Install electrical controls, instruments and any loose field enclosures next to the
equipment or instruments they will control, and connect the necessary tubing
and/or wiring from the enclosures to the equipment valves and instruments. The
tubing connections on the side of each solenoid enclosure or stager valve
(automatic systems only) should be labeled with the tag numbers of the valves
they connect to.
If possible, panels that rest directly on the floor (no support legs) should be
mounted on a slightly raised floor or pad. This will help reduce the chance of
moisture or water getting in the panel.
NOTE:
7.
When mounting a control panel on a raised pad or other structure, be sure that
the height of the controls (switches, etc.) does not exceed the normal reach of
operators.
Install the main control panel (if applicable), and connect the tubing and/or wiring
from the panel to the field enclosures and equipment.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
8.
Page 3-9
Rev. 0
Connect the required process streams and utilities to the U.S. Filter equipment as indicated on
the piping drawings. Refer to section 1.0 of this manual for the types of process
streams and utilities used with your system.
9.
3.4.2
CAUTION
CAUTION
Never weld on a lined vessel. High temperatures will damage the vessel
lining.
Some of the vessels for this system may be lined with sheet PVC. Sheet PVC
is a thermoplastic and must not be exposed to temperatures above 150F.
Do not weld on lined vessels. The high temperatures necessary for welding may
damage the lining. If welding must be performed on the vessel legs, do not weld
within 12 inches of the actual vessel.
3.4.3
WARNING
Failure to install, pre-test, and operate the chemical systems properly can
result in serious injury to workers due to leaks and mechanical malfunctions.
Because of the hazardous chemicals used with regenerant and chemical-feed systems,
special attention must be paid to the installation of their components.
1.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
2.
Page 3-10
Rev. 0
Always use chemically resistant materials for the chemical system components.
3.4.4
3.
All supplied caution and warning labels must be installed and maintained at
chemical storage tanks and other components. If labels are lost or damaged, new
labels are available from U.S. Filter or the component manufacturer.
4.
If check valves or chemical ejectors are used, verify that they were installed for
the proper flow direction.
5.
When installation is complete, the entire chemical system must be pressure tested
before actual chemicals are introduced.
Once single-phase pumps and pump skids have been installed, the alignment
of the pump-drive couplings must be checked and corrected as necessary to
prevent shattering or distortion of the coupling.
CAUTION
1.
NOTE:
If pumps are shipped loose (not skid-mounted), they must be positioned and then
mounted and grouted to the floor using approved construction procedures. On
single-phase pumps coupled to motors, align the coupling using the pump
manufacturer's instructions in the Vendor Literature Manual.
Do not couple 3-phase pump motors until proper rotational direction has been
achieved (refer to subsection 5.0).
2.
Mount the pump motor starters (if applicable) next to the pump or in a common
motor control center. Wire the motor starters to the pump motors and to the main
control panel.
3.
Many pump manufacturers ship their pumps without lubricants installed; these
lubricants are often shipped in separate containers.
After pumps are mounted and aligned, the proper types and quantities of pump
and gear lubricants should be located and installed.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.5
Page 3-11
Rev. 0
3.5.1
Process Feed
The quality of the feed stream must be maintained as described in section 1.0.
3.5.2
CAUTION
Pipe elbows, tees, and other fittings combined with long pipe runs can
increase backpressure to the point that proper drain flows cannot be
achieved.
Drain piping should be as straight and as short as possible. Drain pipes
should be one size larger than the manifold piping.
The drain piping can be piped into headers to drain, but it is best to pipe the individual
component to a sump, drain trench, or other open drain. Open drains make it easier to
take samples and allow for visual observation by the operating personnel.
If the drain flow will contain hazardous or corrosive chemicals, be sure to use piping
materials that will resist these chemicals.
3.5.3
Interconnecting Piping
CAUTION
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.5.4
Page 3-12
Rev. 0
3.5.5
Electrical
Proper power connections are required for controllers, pumps, etc. Refer to the U.S.
Filter wiring diagrams for specific power requirements.
3.5.6
Air
Dry, oil-free plant air is required for pneumatic valve operation and other functions. Air
must be filtered to remove moisture, oil, and particulates. Refer to section 1.0 or the job
drawings for specific pressure requirements.
NOTE:
3.5.7
All air sources must be filtered to remove moisture, oil, and particulates.
Pumps
All customer-supplied pumps must be leveled, aligned, piped, wired, lubricated and
checked for proper rotation.
NOTE:
3.5.8
The same procedures can be followed as those described for U.S. Filter equipment. Also
refer to the vendor literature supplied with the components.
Storage Tanks
Any storage tanks used with this system must be piped and ready to hold liquids. If
possible, these tanks should be filled with water and checked for leaks prior to beginning
operation.
Be sure storage tanks are clean before introducing any liquids.
3.5.9
Cartridge Filters
Any cartridge filters used with U.S. Filter equipment should be installed, inspected, and
cleaned at this time.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.6
Page 3-13
Rev. 0
Air Supply
Instrument calibration checked by qualified technician and documented by log sheet or sticker on
each device.
Pumps And Motors
All pumps utilized by the system grouted in and aligned by a certified millwright.
Motor wiring and MCC complete with proper wire size, fuses, heaters, etc.
Pump motors checked for rotation and vibration prior to coupling.
All pumps coupled and lubricated as per manufacturers specifications.
Drain Connections
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-14
Rev. 0
If distribution piping has already been installed in the vessel, inspect it using the procedures given
below. If damage is found, call U.S. Filter immediately.
1. Internal vessel cleanliness is critical. Particulates and/or debris will plug distribution
screen. Any plugged screens will adversely affect system operation. All precautions
must be exercised. For example, all uniforms and shoes must be clean; all manholes
protected so as not to allow debris to enter a vessel or section; and no flushing of pipes
into the vessel.
2. Extreme care must be exercised such that any tools or movement in a vessel does not
puncture a screen or the vessel lining. If a screen or piece of lining is damaged
accidentally, it is critical that workers report it so repairs can be made.
3. Prior to entering an empty vessel, read and follow the Vessel Entry Procedures given in
section 2.0.
4. Remove the vessel manhole cover.
5. Inspect the internal distribution for the following. Refer to the drawing on the next page
for an illustration of the proper lateral orientation.
6.
7.
All distribution screens are free from rips or tears, are clean, and are free
from bacterial growth and other foreign materials.
In vessels with dished bottoms and tops (not with a flat false top or
bottom), vertical riser pipes are drilled with 1/4" holes right at the point
where they exit the vessel. The holes on bottom risers are wrapped with
screen to prevent media loss.
Use a long vacuum hose to clean any dirt or contaminants out of the vessel.
Replace the manhole cover.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-15
Rev. 0
Gasket
Tank
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.8
Page 3-16
Rev. 0
3.8.1
1.
All system inlet piping must be flushed thoroughly before it is connected to the
U.S. Filter system.
Newly-installed piping usually contains welding slag, dirt, and other debris that
will plug filters and can damage pumps.
2.
If the inlet piping runs have already been connected to the skid, the piping must
be disconnected at this time.
3.
Each inlet piping run must be flushed with clean, clear water at the maximum
possible velocity.
The piping runs should be flushed one at a time while workers observe the
effluent flow of water.
3.8.2
4.
Each piping run must be flushed until the effluent is clear and clean.
5.
When a piping run has been flushed thoroughly, it can be connected to the U.S.
Filter system.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.8.3
Page 3-17
Rev. 0
Piping Flush
Do not flush into a vessel; always flush away from a vessel to protect the
vessel distribution piping (if applicable) and keep the vessel clean.
CAUTION
1.
Open the various process valves needed to allow water to flow through and flush
the system piping.
To open a solenoid-controlled automatic valve, override its solenoid in the panel
closest to the valve. Refer to the vendor literature for the procedure for the
specific solenoids used.
2.
Start the flow of water to the system. If necessary, start a pump to move the flush
water forward.
3.
The flush water should now flow through the piping and to drain through the
various effluent outlets.
As the flush continues, close or throttle hand valves as required to direct the water
through all areas of the piping.
While the piping is flushing, open each sample valve in the piping momentarily to
flush all dead legs.
4.
When the flush effluent is clear and clean, stop the water flow.
If applicable, turn off the pump, reconnect the valve tubing, and remove the
solenoid overrides.
3.8.4
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.9
Page 3-18
Rev. 0
PRESSURE TESTING
Mechanical failure during pressure testing can result in serious injury to
workers. Do not exceed the pressure rating of components when performing
pressure tests.
WARNING
Vent the vessel or piping, and fill it with water using the normal inlet valves.
For systems with stainless steel piping or fittings, you may want to use water with
a low chloride content (<50 ppm), such as deionized water, to minimize the
corrosion of the piping during extended pressure-testing.
Do not pressure-test the system with compressed air. If a mechanical failure
occurs while the system is pressurized with air, the released air can propel
fragments of piping or other components at high speeds, resulting in worker
injury.
WARNING
Always fill and pressurize the system with water. Water is basically
incompressible and will not "store" energy as will compressed air.
2.
Be sure that the piping and vessels to be tested are filled with water. This
minimizes the possibility of injuries should a mechanical failure occur during the
pressure testing.
3.
Pressurize each portion of the system to its maximum operating pressure, but not
any higher. To do this, deadhead the pump(s) that supplies process feed to that
portion of the system.
4.
During pressure testing, stand away from vessel windows, in-line sight glasses,
glass-tube flowmeters, and plastic piping. These are the components that are
most likely to fail during pressure testing.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
5.
Page 3-19
Rev. 0
When the vessels and piping are completely filled with water, close any vent
valves and allow the pressure to reach the maximum pressure of the inlet pump
(dead-head the pump) or the maximum pressure rating on the system, whichever
is lower. Refer to section 1.0 for vessel pressure ratings.
When the pressure stabilizes, close the inlet valves and turn off the pump to keep
the system at the desired pressure.
6.
If possible, allow the system to remain pressurized for several hours, then perform
a close inspection.
7.
Tighten any fittings or other bolted components that are leaking. If components
must be disassembled for repairs, be sure to relieve all pressure from the system
first.
NOTE:
3.9.2
After the system has been operated at normal temperatures for some time, the
fasteners may require retightening.
To check for inward leaks, close all valves and pressurize all inlet and outlet
headers with water. Open all manifold sample valves and allow the manifold to
drain.
If water continues to flow from a sample valve after the manifold is drained, a
leaking valve is indicated.
2.
To check for outward leaks, pressurize the vessel and manifold piping with water.
Close all valves and drain any accessible inlet and outlet headers. If water
continues to flow from the inlet and outlet headers after they are drained, a
leaking valve is indicated.
3.
Valves must be able to hold pressure for a minimum of one hour. Any leaking
valves must be adjusted, repaired, or replaced and then retested before the system
is operated.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
NOTE:
3.9.3
Page 3-20
Rev. 0
Make sure that all of the nuts are too tight to spin by hand. If not, loosen all of
the nuts to hand-tight, and tighten them to 12 ft-lbs in 2 ft-lb increments. Tighten
them in the order shown on the next page.
2.
If a leak occurs at a vessel window, tighten the window nuts in 2 ft-lb increments
until the leak stops or until the maximum torque is reached, as shown in the table
below. Tighten in the sequence shown on the drawings that follow the table.
After repairs are made, pressurize the system again to double-check these repairs.
Table 3-1: Window Tightening Pressures/Torques
Maximum Pressure (psig)
75
12
100
14
150
18
200
22
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-21
Rev. 0
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.10
Page 3-22
Rev. 0
VESSEL LOADING
Remove the manhole cover on the top or upper sidesheet of the vessel (refer to
section 2.0 for safety precautions). On small vessels with no manhole, disconnect
the piping going into the top of the vessel, remove the bolts holding the flanged
top piece to the spool body of the vessel, and lift off the entire top piece.
2.
Prior to loading any media into a vessel, all internal distribution must be inspected
using the procedures given earlier in this section, and the vessel must be cleaned
to remove foreign material.
If the distribution laterals are wrapped with steel or plastic screen, check the
wrappings carefully for tears or breaks. Use extreme care when working with
wrapped laterals.
3.
The vessel to be loaded must be properly leveled and braced before loading
begins.
4.
Refer to Section 1.0 of the main manual for the sizes, types, and quantities of
media to be loaded into each vessel or tank.
To find the relationship between media weight and volume, use the table in
Section 1.2.10 of the main manual.
While loading each two-bed, be sure to fill out the data form at the end of this
Section of the main manual.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
CAUTION
Page 3-23
Rev. 0
If the vessel has bottom distribution laterals wrapped with screen, use
extreme care when loading the vessel. If the screens are torn or broken
during loading the media can be lost to drain.
MEDIA
vp2bedmedia.wmf
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-24
Rev. 0
When loading anion resin, use soft or deionized water to fill the vessel.
Before loading any resins, always verify that the proper resins are being used.
Cation and anion resins must not be mixed or placed in the wrong vessels.
Prior to loading resins into process vessels, record the lot or batch number(s) of
the resin. When loading the resins, record the installed location (vessel number or
name) of each lot or batch of resin.
If resin container labels are missing or if there is doubt about the identity of a
resin, contact U.S. Filter or the resin manufacturer.
4.
Larger quantities of resin are most conveniently loaded using a large eductor.
The eductor draw line is inserted directly into a shipping drum and the eductor
outlet line is placed in the vessel manhole or is connected to a resin sluice nozzle
near the top of the vessel (where applicable). Once the eductor motive flow is
started, a separate sluice (fluidization) line must be inserted into the drum to keep
the resin fluidized.
When transferring resin with an eductor, some of the water in the vessel may have
to be drained out as the transfer progresses.
5.
If the resin is new, it must receive an initial regeneration before being placed in
Service. Perform all startup procedures given later in this section.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.11
Page 3-25
Rev. 0
STARTUP PROCEDURES
To start up the VP Series two-bed deionizer, use the following procedures.
WARNING
1.
2.
3.
Set the air pressure regulators for the valve solenoids to 55 psi.
1.
Open all customer supplied manual valves. In addition, close all sample valves
and vent valves, and open all of the instrument isolation valves.
2.
Make sure that the customer's waste system is ready to handle the chemical
wastes that will be generated by the two-bed system.
Contact with electricity can cause burns, cardiovascular failure, or death.
Follow the precautions given in section 2.0 of the main manual.
WARNING
3.
Start up the controller using the applicable vendor literature provided for that
controller (see section 9.1 of the main manual). Verify that the values in the Data
Access tool (DAT) on the control monitor contain the initial control setpoints
listed in the Control Write-Up document in section 4.2.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-26
Rev. 0
4.
5.
Verify that the vessels have been properly loaded using the instructions given
earlier in this chapter.
6.
Regenerate the two-bed unit using normal start-up procedures with the following
exceptions:
8.
A.
Extend the backwash steps so that each step lasts until the backwash
effluent is clear and clean.
B.
Extend all of the chemical-in steps so that each step lasts twice as long as
indicated in the Regeneration Sequence in section 1.2.13. New resins
require twice the normal amount of chemicals for the first regeneration.
Following the initial regeneration of the unit, put the system into Service. This
completes the startup of the two-bed system.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
3.12
Page 3-27
Rev. 0
2.
3.
4.
Record the serial number off of the component, if not available record the
system serial number.
eg. 56034
5.
REGENERATION DATA
6.
7.
8.
9.
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-28
Rev. 0
SERVICE DATA
12. Record the minutes used during the leak test.
13. Record the pressure during the leak test.
14. Record the feed temperature during service.
15. Are the chemical tanks full, empty, clean, etc?
16. Record the flow rate during service.
17. Record the test method used to determine the flow rate.
eg. Flow indicator FI-1
18. Record the feed pressure during service.
eg. Pressure indicator PI-1
19. Record the test method used to determine the pressure.
20. Record the ph during service. This should be taken as soon after a regeneration as
possible.
21. Record the test method used to determine the ph.
eg. paper, handheld meter, meter ph-1
PERFORMANCE DATA
22. Record the conductivity during service
23. Record the test method used to determine conductivity
eg. Thornton L, CE-1
REFERENCE DATA
24 Record the resin loaded into the vessel, use the marking on the drum or bag
eg. C-211, A-264
P/N XYZ
25. Record the lot number of the resin, use the markings on the bag or drum.
26. Record the cubic feet of resin loaded.
27. This area is used for systems that require subfill. This system does not use subfill
underneath the resin.
28. Quantity in pounds or cubic feed of each layer of subfill.
29. Record the type and grade of chemicals used for regeneration.
eg. HCl-Technical, NaOH Rayon
30. Record the concentrated chemical concentration.
eg. 20%, 50%
31. Record the dilute chemical concentration (to the bed).
eg. 4%
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-29
Rev. 0
VP TWO-BED DEIONIZER
PREPARATION AND STARTUP
Page 3-30
Rev. 0
VP TWO-BED DEIONIZER
OPERATION
Page 4-1
Rev. 0
4.0 OPERATION
This section gives the procedures needed to operate the VP Series two-bed deionizer system for units
that consist of a cation exchanger, an anion exchanger, a customer-supplied acid day tank, and a
customer-supplied caustic tank.
WARNING
Acid and caustic are very hazardous materials. Use extreme caution when
working with these chemicals. Operators must read and understand section
2.0 of the main manual before attempting to work with regenerants.
4.1
THEORY OF OPERATION
When in service, water from the customers source flows through both the cation and anion (two-bed)
vessels supplied with this system. The two-beds are controlled automatically with an Allen-Bradley
MicroLogix programmable logic controller (PLC). Operators may interface with the system - to change
presets, modify setpoints using the A-B Data Access Tool (DAT).
Water from the customers source flows to the distribution piping in the top of the cation vessel then
down through the resin bed to the outlet line. The cation exchanger removes the majority of the
dissolved cations (sodium, calcium, magnesium, etc.). After exiting the cation vessel, the water flows to
the top distribution of the anion vessel. The water passes down through the anion resin bed where
dissolved anions (chloride, sulfate, nitrate) are removed. The effluent from the anion vessel flows to the
customers application.
When the two-bed resins are full of dissolved cations and anions, the vessels are removed from service
and regenerated. The volume of water treated, or the waters conductivity is used to determine when
regeneration is needed. When the volume or conductivity of the effluent water surpasses the setpoint,
regeneration can be automatically or manually initiated. During regeneration, the hydrochloric acid
(HCl) flows down through the cation resin and sodium hydroxide (NaOH-caustic) flows down through
the anion resin. The regenerant waste water flows to drain for disposal. After completion of the
chemical-in steps, the vessels are rinsed and returned to service.
4.2
PROCESS CONTROL DOCUMENT
The document starting on the next page is the Process Control Document (Control Write-Up), which
describes the automatic controls, system alarms, interlocks between the different units in the total
system (if applicable), and how each of the subsystem units sequence between the service modes and
regeneration steps. This document has its own table of contents. This section of the manual continues
after page 14 of the Control Write-Up.
VP TWO-BED DEIONIZER
OPERATION
4.3
Page 4-2
Rev. 0
VP TWO-BED DEIONIZER
OPERATION
Page 4-3
Rev. 0
Average
50.6%
200 ppm
20 ppm
Less than 1 ppm
10 ppm
10 ppm
3 ppm
3 ppm
0.6 ppm
2 ppm
0.6 ppm
0.2 ppm
Less than 0.2 ppm
1.0 ppm
54o F
Average
98.25%
76.61%
7,600 ppm
5,700 ppm
Less than 2 ppm
10 ppm
39 ppm
10 ppm
27 ppm
38 ppm
0.2 ppm
0.5 ppm
0.5 ppm
0.9 ppm
2,000 ppm
0.01 ppm
VP TWO-BED DEIONIZER
OPERATION
4.4
Page 4-4
Rev. 0
Resin Beds
+40
(+22)
Degrees F
(Degrees C)
Above Design
Temperature
+30
(+17)
+20
(+11)
+10
(+5)
Design
Temperature
-10
(-5)
Degrees F
(Degrees C)
Below Design
Temperature
-20
(-11)
-30
(-17)
-40
(-23)
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
VP TWO-BED DEIONIZER
OPERATION
4.5
Page 4-5
Rev. 0
During the Service mode, periodically sample the effluent at the anion vessel's lower
sample valve and make sure that the product quality is acceptable. Refer to Section 5 of
the main manual for typical sampling procedures.
If a backwash flow rate is too high, resin can be lost to the drain. If resin is
seen in the backwash effluent, throttle the setting device immediately.
CAUTION
3.
During each Backwash step, make sure that whole resin beads do not go above the upper
vessel window (if applicable) or into the flow glass (FG) on the backwash drain line. If
so, check the backwash flow against the table in section 1.2.12.
Acid and caustic are very hazardous materials. Use extreme caution when
working with these chemicals. Operators must read and understand section
2.0 of the main manual before attempting to work with regenerant chemicals.
WARNING
4.
5.
4.6
During the chemical-in steps, periodically sample the dilute chemical and determine its
specific gravity. Use the testing procedures given in section 5 of the main manual.
Near the end of the Cation Final Rinse step, take two samples of the rinse effluent one
minute apart, and check their pH. If the pH is stable, let the step time-out normally. If
the pH is still changing, extend the step until the pH is stable, and adjust the step time
accordingly.
P&ID DRAWINGS
The VP Series two-bed P & ID drawing follows this page. This drawing shows system
components and their relationship to each other. The P&ID covers all the various sized units.
NOTE:
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
Page 5-1
Rev. 0
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
5.1
Page 5-2
Rev. 0
5.1.1
CAUTION
2.
At the end of the regeneration, open a manual vent valve at the top of the vessel
and a manual drain valve at the bottom of the piping manifold and drain the water
in the vessel down to the top of the resin bed. If desired, compressed air can be
used to "blowdown" the water in the vessel.
3.
When the water in the vessel has been drained down to the top of the resin bed,
close the drain valve. Leave the vent valve open.
If compressed air was used to blowdown the water, relieve all pressure from the
vessel. Open a vent valve before proceeding further.
4.
Remove the upper manhole cover in the sidesheet or the head shell.
5.
To provide the most accurate information on resin condition, a resin sample must
be representative of the entire resin bed. Use a "grain thief" or related device to
take a core sample of the resin bed. Figure 5-1 demonstrates the use of a grain
thief to take a resin sample.
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
Page 5-3
Rev. 0
Do not take a resin sample by taking resin from only the top of the bed. The
particulates and resin fines that normally collect at the top of the resin bed will
not accurately represent the entire bed.
6.
Take enough resin from the bed to fill a quart jar. Seal the jar tightly, label the jar
with the date, type of deionizer (cation, anion, mixed bed, etc.), and the original
U.S. Filter/Rockford job number, and then send the sample to U.S. Filter or to any
lab with resin testing facilities.
Contact U.S. Filter/Rockford for current prices for resin testing services.
Grain
Thief
Grain
Thief
Manhole
Manhole
Top of Media
Acceptable
sample.wpg, 7/26/95
Top of Media
Best
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
5.1.2
Page 5-4
Rev. 0
1.
The following items are required when sampling resin with an eductor.
(1)
(1)
(1)
flexible hose to carry water and educted resin from the eductor to a
dewatering device
(1)
(1)
2.
3.
If the deionizer will not attain the proper conductivity or resistivity during its final
rinse, allow the vessel to rinse for the normal amount of time and then stop the
regeneration.
Draining a vessel without an air vent open can cause the vessel to collapse
due to the vacuum produced by the draining water. When water is
gravity-drained from a vessel, a vent valve must be opened near the top of
the vessel.
CAUTION
4.
At the end of the regeneration, open a manual vent valve at the top of the vessel
and a manual drain valve at the bottom of the piping manifold and drain the water
in the vessel down to the top of the resin bed. If desired, compressed air can be
used to blowdown the water in the vessel.
5.
When the water in the vessel has been drained down to the top of the resin bed,
close the drain valve. Leave the vent valve open.
If compressed air was used to blowdown the water, relieve all pressure from the
vessel. Open a vent valve before proceeding further.
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
Page 5-5
Rev. 0
6.
7.
Open all manifold valves normally used to backwash the vessel. Throttle a hand
valve to provide a slow upward flow of water to fluidize the resin bed.
8.
Start the motive flow of water to the eductor. Direct the eductor outlet hose into
the resin dewatering device.
9.
Insert the draw hose or wand into the resin bed and slowly push it to the bottom
of the vessel. When the hose or probe touches the bottom of the vessel, pull it
back out slowly.
NOTE:
Do not take a resin sample by taking resin from only the top of the bed. The
particulates and resin fines that normally collect at the top of the resin bed will
not accurately represent the entire bed.
10.
Continue to push the draw hose or wand into the resin bed until the desired
amount of resin has collected in the dewatering device.
11.
When the desired amount of resin has been collected, stop all water flows, close
all valves in the vessel manifold, and reinstall the manhole cover.
12.
13.
Seal the bottle tightly, label it with the date, type of deionizer (cation, anion,
mixed bed, etc.), and the original U.S. Filter/Rockford project number, and then
send it to Rockford or to any lab with resin testing facilities.
VP TWO-BED DEIONIZER
SAMPLING AND TESTING
5.2
Page 5-6
Rev. 0
1.
Rinse Hydrometer with fresh water and dry with clean cloth.
2.
3.
Gently float hydrometer in solution and spin the hydrometer stem so that it does not hang
up on the side of the cylinder.
4.
Read the scale at the point where the liquid surface touches.
5.
CAUSTIC
SODA
(X=.021%)
HYDROCHLORIC
(X=.019%)
1.010
1.003
1.021
1.008
1.032
1.013
1.043
1.018
1.054
1.023
1.065
1.028
1.076
1.033
1.087
1.038
10
1.110
1.047
12
1.131
1.057
15
1.164
1.073
20
1.219
1.098
26
1.285
1.129
30
1.328
1.149
50
1.525
-------
93
-------
-------
The value of the specific gravity at 68 F (S68) will change (x)% for each F above or below 68F. The specific
gravity (St) at (t)F can be calculated using the formula below. The expansion factor (x) is given in the chart for
each regenerant.
St = S68 [ 1 - x(t - 68)/100 ]
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-1
Rev. 0
MAINTENANCE
Because of the complexity of many of the instruments and mechanical components used with this
system, no attempt is made here to give specific instructions for maintenance or repairs of these
components. The purpose of this section is to alert operators and maintenance workers of general
areas where maintenance is required.
CAUTION
For specific and detailed maintenance procedures for vendor components, refer to Section 9.1
Vendor Literature.
NOTE:
Most maintenance procedures for this equipment can be performed using common hand tools and
plumbing equipment; any special tools required for individual components must be obtained from the
component manufacturers.
6.1.1 General Maintenance Guidelines
Maintenance personnel should have a thorough understanding of the safety procedures given
in section 2.0 before attempting repairs or maintenance to this equipment.
Before working on any of the components and equipment used with this system, workers must
read and understand the safety-related material given in section 2.0 of this manual. Of special
importance are the areas of equipment access, pressures, and servicing system components,
and the precautions specific to the types of equipment in your system.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-2
Rev. 0
Workers who perform maintenance on the components and equipment used with this system
should read and follow all instructions and procedures given in section 8.4 Vendor Literature.
Spring-loaded devices, such as valves, should be in their "relaxed" state - that is, with no
compression on the loading spring - to avoid the sudden and accidental motion of individual
parts.
The table on the next page contains typical schedules for maintenance of the most commonlyused system components. This should be used as a guide only. For actual maintenance
frequencies, refer to the component instructions in the Vendor Literature.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-3
Rev. 0
MAINTENANCE PROCEDURE
RECOMMENDED INTERVAL
As required
Weekly
As required
Annually
Every 6 months
Weekly
Weekly
Media sampling
Weekly
diagnostic
As required
VP TWO-BED DEIONIZER
MAINTENANCE
6.2
Page 6-4
Rev. 0
COMPONENT MAINTENANCE
This subsection contains general maintenance procedures for the component types that are most
often used on U.S. Filter systems but not included in the Vendor Literature.
The maintenance procedures for all other components on your system are covered by the
component manufacturer's instructions in the Vendor Literature.
6.2.1 Piping
The main piping on the system vessels is PVC pipe. Any fasteners used on this piping may
need periodic tightening to prevent leaks. If the system is operated within the temperature
and pressure limitations given in this manual, little or no maintenance is required.
WARNING
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-5
Rev. 0
Very little maintenance is required for control panels and their components. The following is
a list of general guidelines for operators to use while operating and maintaining control panels.
Operators must be certain the operating conditions for microprocessor controllers are within
the ranges listed in the component instructions in the Vendor Literature.
Check any air inlet and outlet grilles at least once a week and clean them when necessary.
The controller must be properly grounded and protected from the possibility of
static-electricity discharges.
Operators must monitor the condition of any controller backup battery and must replace it
when necessary. An audible alarm and/or an alarm light are often activated when the backup
battery is low.
Control panel doors must be kept closed at all times to prevent excessive dirt or dust from
collecting inside the panel.
If the control panel is located in a corrosive or damp atmosphere, the panel should be
inspected, cleaned, and painted regularly.
Externally-mounted switches (on valves, pumps, etc.) should be checked periodically for
corrosion, debris, and loose or broken wires.
Switches that are used to initiate step, modes, or alarms (flow or pressure switches, for
example) should be checked for calibration occasionally. Also, any limit switches used on the
control valves may have to be adjusted periodically.
The vessels should provide many years of service with only minimal exterior maintenance
(painting), provided the system is operated within the design pressure and temperature
limitations.
If vessels are installed outside and are exposed to freezing temperatures, the vessels and their
piping must be insulated and heated or else must be shutdown and drained.
If vessels are stored outside and are exposed to freezing temperatures, they must be
completely drained and must be handled carefully when moved.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-6
Rev. 0
CAUTION
Vessels in this system are lined with PVC. PVC is a thermoplastic and must
not be exposed to temperatures > 150F.
PVC linings are not recommended for use with organic chemicals containing
chlorine or nitrogen groups, glacial acetic acid or acetic anhydride, ketones,
lacquer solvents and thinners and petroleum fractions lighter than No. 1 fuel
oil.
U.S. Filter guarantees all vessel linings against defective materials and workmanship for a
limited period of time. Improper handling or storage procedures may void the lining
guarantee. Follow all instructions given in this manual when handling or storing lined
vessels.
6.2.9 Resins
CAUTION
If sight strainers are removed from the pipe lines, be certain to reinstall them
in the correct positions.
As shown on the blueprints for this job, strainer elements must point "upstream" when
installed in the piping runs. If strainers are installed backwards, they will still trap resin,
but operators will not be able to observe this resin.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-7
Rev. 0
6.3 TROUBLESHOOTING
This section provides the procedures needed to avoid and troubleshoot problems with the two-bed
deionizer system. While this deionizer does not require a great deal of routine or periodic servicing,
certain maintenance procedures are required to guarantee continued satisfactory operation.
6.3.1 General Troubleshooting Tips
This section describes some of the common problems that can occur during operation of this
system and the steps an operator can take in finding their causes. The best troubleshooting tool
an operator can have is his knowledge of the normal system operation. Operators should read and
be familiar with the rest of this manual prior to using this section. During the first few months of
system operation, operators should carefully observe and note normal operation characteristics for
future reference.
1.
The most helpful tool in troubleshooting problems is the operator's knowledge of the
normal operating conditions. Then, if the system develops a problem, the operator may
notice a change in operating conditions that could help him identify the cause of the
problem. Many problems occur because the system is no longer operating under the
conditions stated in this manual, particularly chapter 3.0 (Operation.)
Selected sampling and testing procedures should be performed regularly during the
operation of this system. While the actual frequency of sampling and testing is at the
discretion of the customer, any tests used with this system must be preformed on a regular
basis and must be accurately recorded in a logbook.
A well-kept logbook of test dates and results and of operator observations is an invaluable
tool for troubleshooting future performance problems.
2.
3.
4.
To troubleshoot flow blockage, locate any large pressure drop and investigate all the
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-8
Rev. 0
To troubleshoot electrical problems, first identify the control flow pattern, which is the
pathway that the signal takes from an input device to the controller, through the
controller, then from the controller to the output device. Second, investigate all the
components of this control flow pattern until the cause of the problem is discovered. Start
with the easiest and most probable components, such as the input and output modules
(where applicable).
6.
7.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-9
Rev. 0
COMMENTS
1. Normal exhaustion
Broken resin beads (fines) stay in the resin bed and cause
large pressure drop.
Resin fouled
Distribution improper
Inspect distribution.
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-10
Rev. 0
CAUSE
9. Feed flow too high - improper feed
setpoint
COMMENTS
Once the flow exceeds the maximum the resins can't remove
as many ions.
COMMENTS
Calibrate all instruments involved. Check flow rates
independently. Check controller setpoints.
3. Increase in feed salt or color content Bring the feed in line with normal specs or add more resin.
not following feed specs provided in
Section 1 of the main manual
4. Low resin volumes
Distribution leaking resin, backwash
flow too high
Resin fouled
Inspect distribution
Distribution improper
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-11
Rev. 0
CAUSE
COMMENTS
End service runs after recommended volume of feed has
been treated or when effluent has high conductivity, or
low pH
COMMENTS
Check backwash flow rate and time; may have resin leak.
Resin is fouled
7. Obstruction in line
COMMENTS
VP TWO-BED DEIONIZER
MAINTENANCE
Page 6-12
Rev. 0
COMMENTS
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
Page 7-1
Rev. 0
7.0
7.1
CAUTION
If a vessel must shutdown for more than a month, perform the storage
procedures given at the end of this chapter.
7.1.1
If power to the equipment is lost, all valves at the equipment will close and
all pumps will stop.
Turn off all pumps upstream and downstream of the system. This will prevent
deadheading and starvation of customer-supplied pumps.
2.
Place all HAND/OFF/AUTO selector switches at the control panel in the OFF
position.
Place all MAN/AUTO selector switches at the control panel in the MAN position.
3.
Try to determine what the operating status (Regeneration, Service, etc.) of the
equipment was when the power was lost. This information will be helpful when
the system is restarted.
4.
All equipment being worked on during a power loss must be isolated and disconnected
from power and air supplies to prevent injury to workers if the power is restored without
notice.
5.
7.1.2
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
Page 7-2
Rev. 0
When electrical power is restored to the system, perform the following procedures.
1.
2.
Observe, note, and acknowledge any alarm conditions at the control panel.
3.
Check the operating status of the equipment and verify that the individual
units have returned to the positions they were in when the power was lost.
4.
Return all selector switches at the control panel to their normal positions.
5.
6.
7.
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
Page 7-3
Rev. 0
CAUTION
If a vessel must shutdown for more than a month, perform the storage
procedures given at the end of this chapter.
A.
2.
To shutdown the entire system quickly, turn off the power to the control
panel. All air open / spring to close valves will close and all pumps will
stop.
If the power to the panel is disconnected, perform the power-loss procedures given
earlier.
3.
B.
1.
If a unit was shutdown with the by the pushbutton, place it back in Service
by pressing the SERVICE pushbutton.
2.
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
7.2
Page 7-4
Rev. 0
The recommended procedure is to unload the resin using the resin removal opening in the
vessel side sheet.
2.
Drain all water from the vessel and then place the dewatering device under the resin
removal opening and remove the blind flange from the opening. If there is not enough
room to fit a dewatering device near the vessel, install a hose and flange at the removal
opening and direct the hose to the dewatering device.
3.
Allow enough water to flow into the vessel through the bottom distribution. The water
stream with resin should begin to flow out of the vessel.
If difficulties are encountered in transferring the resin out of the vessel, it may be
necessary to introduce a fast flow of water into the vessel through the top distribution
while the fluidization flow continues from the bottom distributor. The fast downward
flow of water should push the fluidized resin out of the removal opening.
4.
If desired, the resin can be unloaded using an eductor to reverse the procedure used when
loading with an eductor.
Drain the water in the vessel down to the top of the resin bed, insert the eductor suction
line into the vessel, and then direct the eductor outlet line to the dewatering device.
Control a flow of water a into the vessel through the bottom distribution and then start the
eductor motive flow. Maintain a minimum fluidization flow to avoid dilution and
excessive water use.
5.
If the unloaded resin is to reinstalled later, it must be sealed in drums or other containers
and stored carefully. The resin must not be allowed to dry out and must not be exposed
to extremes of temperature.
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
7.3
Page 7-5
Rev. 0
STORAGE
The following procedures apply to all of the ion-exchange vessels for this system.
NOTE:
The following procedures must be performed manually using the air solenoid
overrides at the unit solenoid panels.
1.
2.
3.
4.
To completely exhaust the resins, remove the deionizer tank covers and pour into each
tank 8 lbs. of evaporated salt for each cubic foot of resin. After the salt is in, replace the
covers and rinse the beds to drain until the salt is completely washed out.
5.
Rinse the salt through the beds until a sample taken at the drain tests at approximately
1.005 specific gravity.
6.
Close the inlet water valve and open the vent valve momentarily to relieve the internal
pressure. With the vessel filled and all valves securely closed, the deionizer shutdown is
complete.
7.
If the vessel is to be stored for over one month, it must be rinsed with 2-3 bed volumes of
water every 2 weeks to avoid bacterial growth.
8.
When returning the vessel to Service, perform the startup procedures given in chapter 2
of the Subsystem Operating Manual in Section 3.2. New or completely exhausted cation
resin must be regenerated with double the normal acid dose.
NOTE:
If a lined vessel has been in storage for more than three months, the lining must be
inspected before the vessel is returned to Service.
VP TWO-BED DEIONIZER
SHUTDOWN AND STORAGE
7.3.1
Page 7-6
Rev. 0
Storage of Tanks
7.3.2
1.
2.
Cover all tank openings and the drain nozzles to prevent dust and dirt from
entering the tank.
3.
Before placing the tank in service, rinse thoroughly with clean water and dry with
oil-free compressed air.
VP TWO-BED DEIONIZER
PARTS LIST
Page 8-1
Rev. 0
8.1
EQUIPMENT LIST
The equipment list for the systems described in this manual follows this page. The purpose of
the equipment list is to convey the part number, quantity and description of all tagged items
shown on the process and instrumentation drawing(s).
VP TWO-BED DEIONIZER
PARTS LIST
8.2
Page 8-2
Rev. 0
VP SERIES
TWO BED SPARE PARTS LIST
Page 1 of 3
Rev. 0
DESCRIPTION
PLC Base with (12) 24VDC Digital Inputs and (12) ac/dc Relay Outputs
PLC Processor
Add On 8pt AC/DC Relay Output Module
PLC Rack Assembly Right End Cap
Data Access Tool
Power Distribution
03/03714-01
03/02938-14
03/02938-20
VP SERIES
TWO BED SPARE PARTS LIST
USF PART #
Page 2 of 3
Rev. 0
DESCRIPTION
VP SERIES
MIXED BED SPARE PARTS LIST
Page 3 of 3
Rev. 0
16
20
24
30
36
42
05/31114-18
05/31114-18
05/31114-20
05/32284-16
05/32284-17
48
54
60
05/31717-22
05/31717-24
66
72
PART
Valves 101,
103, 201,
202, 203
05/31114-16
Valve 104
05/32284-08
Valves 105
205
05/32284-12
Valve 106,
204, 207
05/32284-08
Valve 108
05/31114-08
Valve 209
Valve 114,
214
Valve 131
05/31114-08
Valve 247
05/11134-08
Valve 132
Valve 233
Valves 135,
137, 235,
Valves 134,
136, 138,
236, 239
Ejector 101,
201
Gage 101,
102, 201
Flow
Element 101
Lower Hub
Lower
Lateral
AE-201
conductivity
element
05/85626-31
05/85626-31
05/32284-12
05/32284-16
05/32284-18
05/32284-17
05/32284-20
05/32284-12
05/32284-16
05/3171
7-28
05/32284-20
05/3228
4-24
05/14335-24DA
05/32284-17
05/1433
5-28DA
05/3228
4-18
05/31114-12
05/01463-08
05/14304-01
05/11134-12
05/85626-32
05/02461-04
05/14426-04
05/85505-08, -08A, -08B & -08H
05/85505-12
05/85505-16
14/86552-37
14/86552-38
05/85505-17
15/02332-04
21/31623-01N
14/86552-32
14/86552-32
14/86552-32
14/86552-52
14/31827-07
14/31827-09
14/31827-11
14/31827-12
18/02839-01
18/02839-02
14/86552-53
49/32360-01
N/A
N/A
N/A
N/A
VP SERIES
MIXED BED SPARE PARTS LIST
Page 4 of 3
Rev. 0
1.25
1.5
2.5
VP TWO-BED DEIONIZER
PARTS LIST
8.3
Page 8-3
Rev. 0
DRAWINGS
The VP Series two-bed drawings follow this page. The electrical drawings show the control
panel layout and line wiring. The piping drawings show the piping arrangement and components
as assembled. The drawings for all the various sized units are included. Use the drawing for the
specific unit you have.
VP SERIES
TWO BED CONTROL WRITE-UP
Page 1 of 14
Rev. 5
RECORD OF REVISIONS
Electrical
Engineer
REV
DATE
DESCRIPTION
04-29-00
RGW
12-26-00
RGW
01-23-01
RGW_
03-02-01
RGW_
03-22-01
_ RGW _
04-04-03
_ ADN _
VP SERIES
TWO BED CONTROL WRITE-UP
Page 2 of 14
Rev. 5
TABLE OF CONTENTS
for
TWO BED VP SERIES
SECTION
DESCRIPTION
1.0
CONTROL OVERVIEW.....................................................................................3
2.0
3.0
PAGE
Regeneration ...........................................................................................................3
Regeneration Complete...........................................................................................4
Service Rinse / Service ...........................................................................................4
Exhaustion Rinse ....................................................................................................4
Off Line...................................................................................................................5
Status Lamp Reference Chart .................................................................................5
ALARMS ...............................................................................................................6
3.1
3.2
3.3
3.4
3.5
4.0
Alarm Silence..........................................................................................................6
Total Throughput ....................................................................................................6
Exhausted................................................................................................................6
Excessive Service Rinse ..........................................................................................6
Excessive Final Rinse ..............................................................................................6
DATA ACCESS TOOL.........................................................................................7
4.1
4.2
4.3
5.0
VALVE SEQUENCE..........................................................................................10
6.0
INSTRUMENTATION ......................................................................................10
6.1
6.2
7.0
EXTERNAL INTERLOCKS..............................................................................13
7.1
7.2
8.0
VP SERIES
TWO BED CONTROL WRITE-UP
Page 3 of 14
Rev. 5
REGENERATION
1.
Regeneration Initiation
With the unit in off line, the "Regeneration" pushbutton may be pressed to place the unit
into the regeneration sequence. The REGENERATION lamp will light.
Automatic Operation Selector Switch in "On".
With the unit in exhaustion rinse and exhausted; or totalized, the unit will enter the
regeneration sequence automatically. The REGENERATION lamp will light.
2.
Sequence
The regeneration sequence consists of sequential timed steps of Backwash Cation, Acid
In Cation, Slow Rinse Cation, Fast Rinse Cation, Backwash Anion, Caustic In Anion,
Slow Rinse Anion, and Final Rinse The presets for these steps are entered into the PLC at
the factory. The presets can be changed in the field with the Data Access Tool (See
Section 4.0). Final Rinse is terminated by reaching the proper conductivity set point
entered on the Thornton conductivity monitor so the preset time entered for this step is
for excessive final rinse. If proper conductivity is not reached within this time the
"Excessive Final Rinse" alarm will sound.
3.
VP SERIES
TWO BED CONTROL WRITE-UP
2.2
Page 4 of 14
Rev. 5
REGENERATION COMPLETE
Automatic Operation Selector Switch in "Off".
When the regeneration sequence is complete the regeneration lamp will blink on to
indicate the regeneration is complete.
Automatic Operation Selector Switch in "On".
When the regeneration sequence is complete the unit will enter service rinse.
2.3
2.4
EXHAUSTION RINSE
While in service, should the conductivity rise above the set point (typically at the end of
the service run), the unit will go into exhaustion rinse. The SERVICE lamp will blink off.
If the conductivity stays bad for the duration set on the exhaustion rinse preset,
the exhaustion rinse timer will time out activating the "Exhausted" alarm. If the
conductivity drops below the set point before the preset time, the unit will return to
service and the exhaustion rinse timer will reset. The preset can be changed in the field
with the Data Access Tool (See Section 4.0).
VP SERIES
TWO BED CONTROL WRITE-UP
2.5
Page 5 of 14
Rev. 5
OFF LINE
With the unit in service rinse, service, or exhaustion rinse, the "Service" pushbutton may
be pressed to take the unit off line. The lack of a REGENERATION lamp or SERVICE
lamp represents the off line mode.
Automatic Operation Selector Switch in "On".
The unit will go into regeneration automatically when the unit is "Exhausted (high
conductivity) or the totalizer exceeds the preset volume set on the Red Lion flow
indicator.
2.6
SERVICE Lamp
Off Line
Off
Off
Regeneration normal
Steady On
Off
Blink Off
Off
Fast Alternating
Off
Slow Alternating
Off
Regeneration Complete
Blink On
Off
Service Rinse
Off
Blink On
Service
Off
Steady On
Exhaustion Rinse
Off
Blink Off
Service Standby
because of loss of supply water
Off
Slow Alternating
Steady On
Steady On
VP SERIES
TWO BED CONTROL WRITE-UP
Page 6 of 14
Rev. 5
3.0 ALARMS
3.1
ALARM SILENCE
Press the Alarm Silence pushbutton to silence the audible alarm. By holding the Alarm
Silence pushbutton for 3 seconds it becomes a Lamp Test pushbutton for the
REGENERATION and SERVICE lamps.
3.2
TOTAL THROUGHPUT
The Totalized alarm is active at all times and is indicated when the totalizer total throughput
value has exceeded the preset on the Red Lion flow instrument. The alarm is reset at the end of
regeneration. (see section 6.1 for setting preset).
3.3
reset
EXHAUSTED
The Exhausted alarm is active during the exhaustion rinse mode and is indicated by the
conductivity reading on the Thornton conductivity monitor above the set point. The alarm is
at the end of regeneration. (see section 6.2 for set point)
NOTE:
If the " Automatic Operation Selector Switch is in "On" the unit
will enter regeneration automatically upon "Exhaustion" or "Total Throughput".
The appropriate alarm will register but will be automatically silenced.
3.4
3.5
by
VP SERIES
TWO BED CONTROL WRITE-UP
Page 7 of 14
Rev. 5
HOW TO USE
The Data Access Tool mounted on the front of the MicroLogix PLC can be used to monitor the
regeneration sequence and modify the step presets. The only keys used are the INT (integer) key,
ENTER key, ESC (escape) key, and the UP/DOWN arrow key.
Monitoring and editing:
1.
Press the INT key. The element (left two digit display) flashes if not protected.
2.
Use the UP/DOWN arrow key to scroll through the list of elements 0-47. Check the
listing on the next page for the specific function.
3.
Press ENTER to select the element you want to edit. The element number becomes
steady and the data (right four digit display flashes if it is not protected.
4.
Use the UP/DOWN arrow key to increment or decrement the value. Holding down the
UP/DOWN arrow key causes the integer value to increment or decrement quickly.
5.
Press ENTER to accept the new data. Press ESC to discard the new data.
4.2
REGENERATION DATA
Minutes
Entry Value
N/A
N/A
Yes
N/A
N/A
Yes
N/A
N/A
Yes
N/A
0 or 1
No
15.0
150
11
No
25.0
250
12
No
21.0
210
13
No
15.0
150
14
No
15.0
150
15
No
45.0
450
16
No
18.0
180
17
No
25.0
250
18
No
VP SERIES
TWO BED CONTROL WRITE-UP
4.3
SERVICE DATA
Page 8 of 14
Rev. 5
Minutes
Entry Value
20
31
No
100
32
No
100
33
No
10.0
VP SERIES
TWO BED CONTROL WRITE-UP
Page 9 of 14
Rev. 5
Valves Open
Off Line
-----------------
Service Rinse
Service
Exhaustion Rinse
Regeneration
Step 1
Backwash Cation
10103, 10104
Step 2
Acid In Cation
Step 3
10106, 10105
Step 4
10101, 10105
Step 5
Backwash Anion
Step 6
Caustic In Anion
Step 7
Step 8
Final Rinse
Regeneration Complete
-------------------------
VP SERIES
TWO BED CONTROL WRITE-UP
Page 10 of 14
Rev. 5
6.0 INSTRUMENTATION
6.1
Unit
Dia
Pipe
Dia
Fitting
K
Factor
PV8T010
PV8T010
PV8T010
Service
Flow
GPM
10
16
24
(rINP1)
352.44
352.44
352.44
Range
GPM
(rdSP1)
15
25
35
88.1
146.9
205.6
(ASCFAC
)
10.215
10.215
10.215
16
20
24
1
1
1
30
36
42
1-1/4
1-1/2
2
PV8T012
PV8T015
PV8S020
48
54
60
2
2-1/2
3
66
72
3
4
(HyS-2)
38
54
74
177.18
117.85
66.74
55
80
100
162.4
157.1
111.2
20.318
30.547
53.941
3.5
5
6.5
7
10
13
1.8
2.5
3.3
PV8S020
PV8S025
PV8S030
97
123
153
66.74
42.99
26.65
120
160
200
133.5
114.6
88.8
53.941
83.740
2.251
8.5
11
13.5
17
22
27
4.3
5.5
6.8
PV8S030
PV8S040
182
220
26.65
15.01
250
300
111.0
75.1
2.251
3.997
16
19
32
38
8
9.5
0.5
0.8
1
The Red Lion DIP switch settings and programming for a unit using a Signet #2536 flow sensor.
N/A denotes programming locations that may not even appear or can be left at the factory
default. Bold Print requires setting other than default.
Dip Sw Settings:
DOWN
UP
UP
VP SERIES
TWO BED CONTROL WRITE-UP
1-INP
1-INP
1-INP
1-INP
1-INP
1-INP
1-INP
1-INP
A CNt
ArESEt
AdECPt
ASCFAC
ASCALr
ACNtLd
A P-UP
PrSEN
2-FNC
2-FNC
2-FNC
2-FNC
2-FNC
2-FNC
2-FNC
2-FNC
USr-1
USr-2
Usr-3
F1
F2
rSt
Sc-F1
Sc-F2
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
3-LOC
A CNt
b CNt
C CNt
rAtt
HI
LO
SP-1
SP-2
ACNtLd
bCNtLd
CCNtLd
ASCFAC
bSCFAC
CSCFAC
COdE
cnt
2Er0
0
(See Chart)
1
(0)
NO
NO
(dsPrSt)
NO
NO
NO
NO
dsPrSt
NO
NO
rEd
LOC
LOC
rEd
LOC
LOC
LOC
LOC
LOC
LOC
LOC
Ent
LOC
LOC
0
Page 11 of 14
Rev. 5
4-rtt
4-rtt
4-rtt
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
4-rtE
rAteeN
LO-Udt
HI-Udt
rtE dP
SEG5
rdSP 0
r INP 0
rdSP 1
r INP 1
rOUNd
LOCUt
HI-t
LO-t
rAtE-A
1.0
2.0
0
0
0
0.0
(See Chart)
(See Chart)
1
(See Chart)
2.0
2.0
5-CtrC
C CNt
NONE
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
6-SPt
Lit-n
Out-1
SUP-n
Act-n
ASN-n
SP-n
trC-n
tyP-n
Stb-n
HyS-n
tOFF-n
tON-n
tOUt-n
AUtO-n
rSd-n
rSAS-n
rSAE-n
SP-1
NOr
NOr
(Save)
(LAtCH)
(A CnE)
(*500)
NO
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NO
NO
NO
SP-2
NOr
NOr
(Save)
(bOUNd)
(ratE)
(See Chart)
NO
(LO)
(yES)
(See Chart)
0.00
0.00
1.00
NO
NO
NO
NO
VP SERIES
TWO BED CONTROL WRITE-UP
6.2
Page 12 of 14
Rev. 5
Setpoint
Relay
Left
- A primary
- Fixed range - (u)S / cm
Right
- A secondary (a)
- Deg F
Auto Scroll
- Off
Number/Signal
Value/State
Assigned relay
Overrange
- 1 / A primary
- 10.00 (factory default) / (u) High
-1
- Yes
- 1, delay = 0
- Hyster = 00%
- Inverted
- Wired to C1 and NO1
VP SERIES
TWO BED CONTROL WRITE-UP
Page 13 of 14
Rev. 5
INPUT INTERLOCKS
Input interlock #1:
The input must be a dry isolated contact. This input is non configurable. Water Supply
Available is assumed when the input is energized. The panel is shipped with a jumper
(JMP1) installed between terminals H1 and 217. To use, remove the jumper and replace with the
dry isolated contact which is closed when there is a water supply available.
If the unit is in service rinse, service, or exhaustion rinse; and the dry contact opens the unit will
go to service standby indicated by the SERVICE lamp at slow alternating. When the contact
closes the unit will go back to service via service rinse.
If the unit is in regeneration and the dry contact opens the unit will go to auto lockout indicated
by the REGENERATION lamp at slow alternating. The sequence timer is stopped, and all
regeneration associated valves are de-energized. When the contact closes the unit will continue
the regeneration.
See electrical drawings for connection.
Input interlock #2:
The Service pushbutton is wired to terminals H1 and 207 so it can be paralleled by a remote
signal for start/stop of the service mode. This signal must be a dry contact closure. It must also
be momentary in nature as the same signal is used to start the mode sequence of service
rinse/service/exhaustion rinse and stop that mode sequence.
See electrical drawings for connection.
7.2
Send a signal (energized output relay) that the unit is in regeneration. This
interlock could be used to prevent equipment upstream from shutting off
the water supply during regeneration.
Enter a 1 to:
Send a signal (energized output relay) that there is flow forward. This
could be used to tell equipment downstream when water is available.
VP SERIES
TWO BED CONTROL WRITE-UP
Page 14 of 14
Rev. 5
Page 9-1
Rev. 0