Professional Documents
Culture Documents
&
OPERATION MANUAL
CONTENTS
PAGE
1.
INTRODUCTION
01
2.
SAFETY PRECAUTIONS
03
3.
03
4.
STORAGE
04
5.
UNPACKING
05
6.
INSTALLATION
05
7.
08
08
9.
CHARGING
10
10.
PERFORMANCE OF BATTERIES
18
11.
24
12.
WARRANTY CONDITIONS
25
13.
MAINTENANCE
28
14.
31
8.
Please read the instructions given in this manual to obtain the optimum
(best) performance and life out of Low Maintenance Lead acid batteries.
Precautions pertaining to installation, commissioning and operating of
these batteries given in various sections of this manual (Following
precautions) should be strictly followed.
AD
TU
RN
LE
RE
RECYCLE
Disposal Action
Pb
1.0 INTRODUCTION
HBL backed by its core strength as R&D has been continuously
updating its designs with the latest advancements for various
applications.
Products from HBL have been in use in sectors of Telecom,
Industry, Defence, Railways, Aviation and are well designed to meet
the rigorous working conditions.
1.1
1.2
1.3
2
material is prepared under controlled conditions with necessary
additives for an efficient electrical performance of the cell / battery
including features of long service life.
1.4
MICROPOROUS SEPARATORS
The separators used have high porosity, low electrical resistance
for ionic flow and high oxidation resistance.
1.5
1.6
1.7
4
z If unloaded manually, the packing boxes should be handled
carefully. Do not drop on to the ground.
z Do not handle more than one box at a time.
3.2
4.0 STORAGE
If the batteries are not to be used immediately, they should be stored
in a cool, dry location, protected from direct sunlight and rain. If
batteries are to be stored in packed condition, packing boxes should
be placed on the floor in the upright position as indicated by the
direction arrows. Do not keep the packing boxes one on top of the
other since this may cause damage to the batteries.
4.1
STORAGE PERIOD
z HBL batteries are supplied in DRY and UNCHARGED condition
and can be stored for a maximum period of 2 Years under shelter.
z It is not recommended to store the batteries after electrolyte
filling and initial charging. If stored, because of whatever reason,
storage period shall not exceed 3 months @ 27 deg. C.
z If storage period exceeds 3 months @ 27 deg. C, then freshening
charge should be given as detailed in section 9.3.
z It is advisable to reduce the storage interval between freshening
charges, when there is a doubt in estimating the average ambient
temperature during storage.
z Ensure that the service record is duly filled in when the battery
is given a freshening charge.
5
Note: Frequency of giving equalizing charge shall be increased by
two times for every 9 to 10 deg. C rise in operating temperature i.e.
for every 1.5 months if operating temperature is 36 deg. C.
5.0 UNPACKING
Cells / batteries are packed in wooden packing boxes, which are
internally lined with shock absorbing Materials. Each battery is
packed in a separate packing box. A separate packing case
containing accessories is provided with every battery bank.
For easy unpacking of batteries without causing damage to the
cells / batteries, the following step-by-step instructions have to be
followed.
z Cut the metallic strap of the packing box with the help of a
cutter or a plier.
z Slowly turn the packing box over so as to make the packing
box sitting on its side.
z With the help of chisel and hammer, open and remove the
bottom of packing box.
z Slowly turn the packing box so that the packing box is in
upright position.
z Slowly lift the packing box with the help of side planks provided
on the packing box.
6.0 INSTALLATION
Install batteries on the battery stands. After ensuring that, the cells
are in perfect level, tighten the connectors securely as per the G.A.
drawing using insulated tools.
Visually check that all connections have been made as per the
G.A. drawing. Also check the open circuit voltage (OCV) of all the
cells / batteries. Total OCV of the battery bank should be equal to
the sum of individual OCVs of all the cells / batteries.
6.1
CELL ARRANGEMENT
Before assembling, please refer the G.A drawing, for the number
of cells to be stacked and polarities.
6
z Lift the cells / batteries slowly and place it on the battery stand.
z Care should be taken while lifting cells / batteries to avoid
slipping.
6.2
ELECTRICAL CONNECTIONS
7
6.3.1 Preparation of electrolyte
z Use battery grade sulphuric acid conforming to IS: 266 (latest
issue). Refer to the "Acid mixing" table given below for making
sulphuric acid of desired specific gravity.
z Concentrated sulphuric acid shall be added to distilled water
slowly with constant stirring.
z While mixing, the acid temperature increases. Allow the acid to
cool down to room temperature.
z Stirring shall be done while taking acid for Filling
Note: To get the electrolyte of desired specific gravity, concentrated
sulphuric acid should not be diluted by adding distilled water
as will lead to accidents (may result in explosion).
6.3.2 Electrolyte filling
z Remove the vent plugs and fill with the electrolyte until the float
guide touches the green mark in transparent indicator.
z Quantity and specific gravity of electrolyte used for filling of new
cells / batteries shall be as specified in the following table:
Type of battery Electrolyte specific gravity Quantity of electrolyte to be filled
NDP series
1.1800.005@27 deg.C
HDP series
1.1800.005@27 deg.C
-do-
SPV series
1.2200.005@27 deg.C
-do-
8
z After electrolyte filling, the cells / batteries shall be allowed to
be under rest for 12 to 24 hrs
z After completion of the rest period, if level indicator falls below
the lower level in transparent indicator, it should be adjusted by
adding some more electrolyte of same specific gravity used for
filling prior to proceeding for charging.
9
z Number of Cells / batteries required to be charged per cycle
based on the operation demands
z The charger voltage to be considered 3V per cell ( e.g. If the
number of 2V cells to be charged is 60 nos, the charger to be
capable attaining 180 Volts)
z Charger current rating 10 to 15 % extra than the current values
given in table in order to avoid operating the charger at full load
z Ripple content shall be kept to minimum (Preferably less than
3%)
z Built in resistive load for discharge can be considered or Load
banks can be used for discharge
8.2
For low voltage disconnect: Should be taken from the bus bar
of the power plant.
10
8.3
INSTALLATION OF CHARGER
z Charger to be protected against acid attack by providing partition
between battery charging and charger
z The distance between the charger and battery under charge to
be kept minimum to avoid loss of energy and proper charging of
cells/batteries
9.0 CHARGING
9.1
INITIAL CHARGING
z DC charger having ripple < 3 % of RMS shall only be used for
charging.
z Please remove vent plugs and float guide during initial charging,
initial cycling to avoid the container bulging due to the excess
gas generation.
z Connect the cables from the battery charger to the end terminals
of the battery system with correct polarity i.e. charger's positive
to battery positive and charger's negative to battery negative.
z Measure and record the open circuit voltage (OCV) of all the
cells / batteries. Total OCV of the battery should be equal to the
sum of individual OCV's of all the cells / batteries.
z For cells / batteries made and supplied with unformed plates:
Measure and record the cell voltages within a maximum period
of 15 minutes after starting the charging. Ensure that, cell /
battery voltages are measured with correct polarity i.e. by
connecting positive probe of multimeter on to cell's/battery's
positive terminal and vice versa.
Check, if there are any cells / batteries connected in series with
reverse polarity. If, observed correct the connections and resume
the charging.
z During charging, voltage, specific gravity and electrolyte
temperature of each cell / battery shall be measured and
recorded once in 4 hours until cell / battery voltage reaches up
to 2.40 V/cell and there after for every 1 hour.
11
z The cells / batteries are said to be fully charged when cell /
battery voltage and specific gravity values remain constant (with
minimal variation, Voltage: +/- 0.010 V and Specific gravity +/0.005) in 3 consecutive hourly readings.
z If electrolyte temperature of the cell / battery rises above 50C,
charging should be stopped and cells / batteries shall be allowed
to be under rest until the electrolyte temperature comes down
to 35C there after charging shall be resumed.
z Throughout the initial charging, electrolyte level shall be
maintained up to the maximum mark. If electrolyte level falls
below the maximum mark it should be adjusted by adding the
electrolyte having specific gravity same as that is used for initial
filling.
At the end of charge, the electrolyte specific gravity shall be adjusted
to the value specified in the following table:
Description
NDP series
batteries
HDP series
batteries
SPV series
batteries
10 %
12 %
10 %
5%
6%
5%
1.240 +/0.005
50C
550 %
minimum
660 %
minimum
300 % minimum
550 %
minimum
12
9.2
CATEGORISATION OF APPLICATIONS
Based on duty cycle applications are broadly classified into the
following 3 categories:
FRESHENING CHARGE
If cells/batteries are stored after completion of initial charging / after
certain usage period, freshening charge shall be given for every 3
months (while the cells / batteries are stored at 27 deg. C) as per
the procedure given below:
z For cells / batteries used with constant current chargers:
o Charge the cells / batteries at a current of 0.05 C for 6 hrs.
13
o Voltage of the cells on charge shall be reaching to 2.600 - 2.700
V at the end of this charging and specific gravities shall be 1.200
+/- 0.005 and 1.240 +/- 0.005 for NDP / HDP and SPV series
batteries respectively.
o If cell voltages & electrolyte specific gravities did not reach to
the values specified, continue to charge the battery at the same
current until voltage & s.g. values are achieved.
z For cells / batteries used with constant voltage chargers:
o Charge the cells / batteries at 2.400 V, 0.1 C current limit for 24
hrs.
o Electrolyte specific gravities of the cells / batteries shall be 1.200
+/- 0.005 and 1.240 +/- 0.005 for NDP / HDP and SPV series
batteries respectively.
o If electrolyte specific gravities did not reach to the values
specified, continue to charge the battery with the same voltage
until s.g. values are achieved.
9.4
14
9.4.1 Constant current charging
z Charger used for this purpose shall be of constant current type
having ripple content in output DC less than 3 % of RMS.
z The chargers should have provision for adjusting the charge
current.
z Charging should be done with the following currents:
o Cells / batteries of NDP series: Charge at a current of 10 % of
battery capacity until cell voltage reaches to 2.400 V/cell and
there after at a current of 5 % until cell voltage reached to 2.600
- 2.700 V/cell.
o Cells / batteries of HDP series: Charge at a current of 12 % of
battery capacity until cell voltage reaches to 2.400 V/cell and
there after at a current of 6 % until cell voltage reached to 2.600
- 2.700 V/cell.
o Cells / batteries of SPV series: Charge at a current of 5 % of
battery capacity until cell voltage reaches to 2.600 - 2.700 V/
cell.
Note: For all types of batteries, it shall be ensured that input on
recharge shall be minimum 110 % capacity drained in
previous discharge. Also, it is important to charge the battery
immediately after every discharge and maintain the battery
in fully charged condition.
9.4.2 Constant voltage / potential charging
z Charger used for this purpose shall be of constant voltage /
potential type having ripple content in output DC less than 3 %
of RMS.
z The chargers should have provision for adjusting both the charge
voltage and charge current.
z Charging should be done with the following voltage & current
settings:
15
9.5
Type of
application
Type of
charging
recommended
Float
Float
Cyclic
Shallow
cycling
HDP series
SPV series
2.15 - 2.20 V/
cell, 10 %
current
Not
applicable
Boost
2.40 V/cell,
10 to 20 %
current
2.40 V/cell,
12 to 24 %
current
Not
applicable
Boost
Not applicable
Not applicable
EQUALIZING CHARGING
Float
16
Note:
z In case of shallow discharge applications, equalizing charge
helps in raising the charge level of the battery (there by
minimizing the effect of PSOC on life of the battery) in addition
to minimizing cell-to-cell variations.
z If required, equalizing charge shall be given more frequently
(than the frequency given in the above table) if variation among
above-stated parameters of individual cells are crossing the
specified limits.
z Equalizing charge shall be started when battery is said to be in
fully charged condition as per the normal procedure.
9.5.2 Procedure for giving equalizing charge
9.5.2.1
a) NDP series:
z Charge @ 5 % current until voltages of all cells reaches to 2.600
to 2.700 V.
z While the battery is under charging, adjust the specific gravity
of electrolyte to 1.200 +/- 0.005 by adding distilled water.
z Minimum input that is to be given during equalizing charge shall
be 50 % of battery rated capacity.
b) HDP series:
z Charge @ 6 % current until voltages of all cells reaches to 2.600
to 2.700 V.
z While the battery is under charging, adjust the specific gravity
of electrolyte to 1.200 +/- 0.005 by adding distilled water.
z Minimum input that is to be given during equalizing charge shall
be 50 % of battery rated capacity
c) SPV series:
z Charge @ 5 % current until voltages of all cells reaches to 2.600
to 2.700 V.
z While the battery is under charging, adjust the specific gravity
of electrolyte to 1.240 +/- 0.005 by adding distilled water.
z Minimum input that is to be given during equalizing charge shall
be 50 % of battery rated capacity
17
9.5.2.2 For batteries used with constant voltage / potential chargers:
NDP / HDP series:
z Charge @ 2.500 V/cell, 10 % current for a minimum period of
16 hrs
SPV series:
z Charge @ 2.550 V/cell, 10 % current for a minimum period of
16 hrs
9.5.2.3
If there is a provision for discharging all the cells, then this method
also can be employed.
z Discharge the cells @ 10 % current until all cells reaches to
1.850 V/cell. Bypass the cells those are reaching to 1.850 V
faster.
z Adjust the electrolyte specific gravity by adding distilled water
to 1.200 +/- 0.005 and 1.240 +/- 0.005 for NDP / HDP and SPV
series cells respectively while the cells are under charging with
low current i.e. in 2nd phase.
Note: Observe for variation in on-load voltages by conducting one
more test discharge @ 10 % load after giving equalling charge
with any of the above-detailed methods. If variations are still
exceeding the acceptable limits, then repeat the equalizing
charge for 2 more times. Even after 3 cycles (total), if
variations are not falling within the specified limits consult
HBL for guidance.
9.6
18
EFFECT OF TEMPERATURE
Lead acid battery is an electrochemical device and is sensitive to
temperature variations. Higher temperature accelerates chemical
activity and lower temperature slows it down, and hence cells/
batteries will give higher capacity and vice versa. Operating at
higher temperatures may give higher capacity momentarily but it
will lead to premature failures and there by shortens the life of the
battery. So, for optimum performance and life, it is recommended
to use the battery in environment having temperature close to 27C.
19
In general battery which is operated in a cool environment
(temperatures up to 10C) will last longer than the one which is
operated in hot environment. Low temperature operation will result
in low available output capacity. Temperatures below 10C will also
reduce the battery life.
Capacity that battery can deliver at different operating temperatures:
Capacity that battery can deliver varies with the operating
temperature. For estimating the battery capacity at temperatures
other than 27 C, following empirical formula to be used:
Capacity at T, CT = C27 / (1 + (R x (27-T) /100))
Where
CT = Capacity that battery can deliver at a temperature t C
C27 = Capacity corrected to 27 deg. C
R
= Rate of discharge (ROD) factor (Shall be chosen from the
table given below)
T
= Average room temperature in C
Rate of discharge (ROD) factors for different rates of discharges:
Discharge rate (Hrs)
ROD factor, R
120
72
6
0.54
5
0.58
48
0.43
4
0.62
20
10
8
0.47
3
0.68
2
0.90
1
0.98
20
10.2 MONITORING OF BATTERIES
10.2.1
BATTERY MAINTENANCE
21
o Record open circuit voltage for pilot cells. Verify state of charge
(SOC) with voltage of pilot cells and take necessary action if
SOC is observed to be low.
o Measure and record the on-load voltages of all the cells (after a
minimum period of 15 min from the time battery is put on
discharge) while the battery is loaded / discharged with site load.
o Check the voltage & current settings on charger, correct if any
deviations are observed.
o Check for any dust accumulation on cell cover, vent plug if
observed, clean it thoroughly.
o Check the tightness / firmness of vent plug.
o Check for any broken container or cover. Remove and replace
with good one, as it will damage the battery stand.
z Half-yearly Inspection
o Verify the monthly inspection reports.
o Check the level of electrolyte of each cell in the system. If any
cell showing the float level above RED MARK or less, top up
with distilled water up to green mark. Record the quantity of
water topped up to each cell.
o Check the condition of vent plug. Replace if it is broken.
o Check for the proper functioning and accuracy of measuring
instruments (Ammeter and Voltmeter). Replace with calibrated
instruments if not satisfactory.
o Check the open circuit voltage & electrolyte specific gravity of
each cell and ascertain the state of charge of the battery referring
the tables / graphs given below.
o Give equalizing charge as detailed above.
Note: For adjusting the electrolyte levels, distilled water shall only
be added to the cells/batteries but not the normal water /
packaged drinking water.
22
z Annual Inspection
o Remove the cells from the battery stands and bring them to
battery shop for attention.
o Clean the acid traces if any on out side surface of the cells after
fitting the plugs.
o Follow special maintenance instructions for revival of cells /
batteries suffering from undercharging due to frequent deep
discharges, improper charging and not giving equalizing charge
as and when required.
o Test for capacity at 10 hr discharge rate. If capacity of any cell/
battery is observed to be less than 80 % of rated value, then
subject them to revival exercise. Even after revival, if capacity
is observed to be less than 80% of the rated value, replace them.
o Recharge the battery following the applicable procedure detailed
in Section 9.5.2.3
o Clean all the ventplugs in warm DI water to remove the dust
accumulated on ventplugs.
z Inspection
If battery failure or other difficulty is reported, conduct the following
checks and tests in sequence:
o Measure the total voltage of battery on open circuit and under
load. If it is normal, then problem must be with some other
equipment.
o Check all battery connections to ensure that they are clean and
tight.
o Measure and record the voltage of all cells in the system. If,
voltage of all the cells is low, it indicates that the battery is either
deep discharged or it is not receiving sufficient charge due to
the problems with charging equipment. In either cases, recharge
the battery with alternative power plant / charger without any
delay. Locate the cause of deep discharge / undercharge and
take necessary corrective & preventive measures.
23
o If voltage of one or more cells is observed to be relatively low,
check for electrolyte level and specific gravity of the same and
adjust if the values are deviating from normal range. Give
equalizing charge following the procedure detailed in Section
9.5 If cells did not improve even after giving equalizing charge,
then replace them.
o The Performance of the batteries shall be monitored during
operation at regular intervals for various parameters detailed
above in order to detect and correct abnormalities, if any.
o Maintain records of all parameters (float voltages, on-load
voltages, electrolyte s.g., etc.) monitored at various intervals
using the service record formats, and send a copy of the same
to M/s HBL for monitoring the performance of the battery. Failure
to maintain service record will invalidate the warranty of the
battery.
Note: Instruments used for testing shall be duly calibrated and shall
have the accuracy & least count specified below:
Instrument
Accuracy
Least count
0.5 %
1 mV
1.0 %
0.1 A
1 deg. C
1 deg. C
0.01 points
0.01
10.2.2
The state of charge (SOC) for low maintenance lead acid batteries
can be predicted roughly through electrolytes specific gravity
measurements using the following table
State of charge
(SOC)
HDP series
SPV series
100 %
1.200
1.240
75 %
1.193
1.210
50 %
1.182
1.170
25 %
1.160
1.130
24
25
11.2
DON'TS
z Never place the cells nearer to fire.
z Do not connect or disconnect any cell without switching off the
load & charger.
z Do not expose the battery to (hostile) hot environment.
z Do not store the Charged batteries for longer periods without
giving freshening charge at regular intervals.
z Do not short the terminals of the cells / battery.
z Do not over-tighten the nuts/bolts while giving connections.
z Do not mix batteries of different types or makes.
z Do not mix low maintenance lead acid cells with VRLA cells or
vice versa.
z Do not make intermediate / tap connections from battery.
z Do not charge two or more sets of batteries (of same capacities
/ different capacities / different types / makes) connected in
parallel.
z Do not connect extra load (over and above specified) on to the
battery.
z Never discharge cells below 1.85 V/cell.
z Do not add acid during for adjusting the electrolyte level. Only
water is lost during battery operation, so add only distilled water
to adjust the electrolyte level.
26
HBL must be notified immediately upon detection of any defects
and HBL has the authority to inspect any questionable sites. If HBL
determines the batteries to be defective due to material or
workmanship, it will repair or replace them at its own option.
12.2 EXCLUSIONS AND LIMITATIONS
z Warranty does not cover physical damage due to the acts of
nature or man, which stress the battery beyond design limits
and exert undesirable influence, which enhance normal wear
and tear.
z Warranty will cease if the units are opened or tampered with, or
an attempt is made to repair the battery by any person other
than the manufacturer's authorised representative.
z HBL will not be responsible for any work accomplished or
expenses incurred except with expressed written consent from
HBL.
z HBL shall not be liable for indirect, incidental or consequential
damages arising out of the sale or relating to the use of this
product, and the purchaser assumes responsible for all personal
injury and property damage resulted during handling, possession
or use of the product.
z In no event shall the liability of HBL, for any and all claims;
including claims of breech of warranty or negligence, exceed
the purchase price of the product.
z The above warranty is in lieu of all other remedies, including
actions. For contract or negligence (incomplete sentence). All
other warranties expressed or implied including but not limited
to the warranties of merchantability and fitness for a particular
purpose are hereby excluded.
z User shall not return the batteries to HBL without prior
information.
27
12.3 WARRANTY CONDITIONS
z The Low Maintenance Lead Acid Batteries are warranted against
material & manufacturing defects for a period of 12 months from
the date of installation or 18 months from the date of dispatch,
whichever is earlier. This warranty limits the purchaser remedy
for the repair or replacement of a defective battery or parts
thereof due to manufacturing defects. The right to determine
whether a battery or cell needs to be repaired / replaced or not
lies with the manufacturer.
z Warranty period will vary based on operating conditions of the
application (Operating temperature, Depth of discharge, Rate
of discharge, Available charge settings in power plant). Consult
HBL for warranty period specific to application.
z Warranty is null and void for those charged batteries which have
been stored for more than 6 months without giving a freshening
charge or when the cell / battery have been tampered with.
z Warranty claims will not be entertained, if the operating
instructions are not strictly adhered to.
z Warranty will not be entertained, if an attempt is made to repair
the battery by any person other than the HBL authorized
representative.
z Warranty is applicable only for those batteries for which the
Service records are maintained as per the guidelines given in
this booklet.
z Warranty will cease for the batteries or cells damaged during
transit unless the local representatives of manufacturer to
informed within 7 days from the date of receipt of the damaged
consignment.
z Warranty claims will not be entertained if transit damages are
notified after storage period.
z Litigation arising out of any transaction with the company is
subjected solely to Hyderabad jurisdiction.
28
13.0 MAINTENANCE
13.1 CHECK LIST
Impact if not followed /
maintained
Accumulation of dust & Cell / Battery surface shall be Self-discharge will be higher in case
acid spillages on Cell / kept clean, dry and tidy
battery is under storage. Acts as a
Battery surface
path for leakage voltage there by
chances of getting electrical shock
in high voltage systems
Check
Requirement
29
The loss of water in HBL's low maintenance lead battery was
ascertained through extensive tests. Results indicate that topping
up is required ONCE IN > 6 MONTHS while it is continuously over
charged @ 2.400 V/cell and 50 deg. C. In actual operating
conditions, such continuous over charging will not be present (the
batteries under goes charge / discharge cycles) as and hence the
topping up frequency will be further low.
Above explanation on reasons for water loss & how it is being
reduced in our design may not be required for the user. We shall
detail on when & how to top up.
HBL recommends to top up with distilled water once in 6 months or
whenever the float guide reaches close to RED MARK in order to
avoid to increase in specific gravity of electrolyte due to evaporation
of water, which will affect the life of the battery.
Prior to topping up with distilled water, charge status of cells shall
be verified with by voltage and specific gravity measurements.
Measure and record the voltage & s.g. values prior to topping up.
Topping up is to be done while the battery is in fully charged
condition. Indication for battery being in fully charged condition is
as follows:
z For batteries used with constant current chargers: Cell voltage
on charge shall be in the range of 2.600 - 2.700 V/cell.
z For batteries used with constant voltage chargers: Current drawn
by the battery shall be stabilised at low current and variation in
3 hourly readings shall be less than 5 %.
While the battery is in fully charged condition, electrolyte specific
gravity will reach to the maximum possible value and under this
condition add distilled water until the float guide in level indicator
touches the GEEN / MAXIMUM mark.
After topping up with distilled water, cells shall be overcharged for
minimum 6 hrs to enable proper mixing of electrolyte through
gassing there after electrolyte specific gravity shall be measured
and recorded. Measured s.g. Shall be in the range specified for
each type of battery.
30
13.3 SYMPTOMS OF BATTERY FAILURE, PROBABLE CAUSES
AND REMEDIES
Symptom
Probable causes
Corrective / Preventive
actions
Electrolyte specific gravity is - Float charge voltage set is high - Adjust the charge voltage to
increasing in less time span while - Error in measuring instruments the specified value.
the batteries are on float charge
(Voltmeter)
- Correct the voltmeter's error if
any
Progressive decline in value of - Float charge voltage set is low - Adjust the charge voltage to
specific gravity while the battery is - Error in measuring instruments the specified value.
on float charge
(Voltmeter)
- Correct the voltmeter's error if
any
- Cell / battery surface shall be
cleaned with (Na2Co3) washing
soda thoroughly to eliminate
leakage paths.
Rapid fall in on-load voltage of cell - Loose connection or corroded - Make all connections firm and
/ battery during discharge
terminals must be present which tight
causes higher voltage drop
- Clean corroded terminal parts
with dilute alkaline solution and
water there after with dry cloth
and apply petroleum jelly
Cell getting discharged
Excessive gassing
Electrolyte is overflowing from the - Electrolyte level must be above - Adjust the electrolyte level
cell / battery
the maximum level
such that it doesn't go above
maximum mark
Reverse polarity in cells
31
32
z Charge the cell with a current 5 % of rated capacity until cell
voltage reaches to 2.300 - 2.400 V/cell. Please be noted that,
voltage will not increase further as the electrolyte is weak (more
diluted / less specific gravity).
z Dump the electrolyte completely after completion of above
charging and fill with the fresh electrolyte having gravity specific
to each type of battery pertaining to 100 % state of charge (for
NDP / HDP series cells / batteries - 1.200 +/- 0.005 and for SPV
series cells / batteries - 1.240 +/- 0.005).
z Charge the battery following the procedure detailed in Section
9.5.2 Check the specific gravity of electrolyte at the end of
charging and adjust it to the value specified above (if SG is low
add the electrolyte of 1.400 specific gravity and if it is high add
distilled water) and continue charging for two hours to enable
proper mixing of electrolyte.
z Conduct C10 discharge, if cell does not give desired capacity
(minimum capacity that battery shall deliver to put into service
is 80 % of rated value) cell/battery shall be discarded.
14.3 REVIVAL OF A CELL THAT HAS ATTAINED REVERSE
POLARITY
This happens when the battery is discharged deeply below ZERO
volts. If such deep discharge occurs repeatedly / number of times
battery will attain reverse polarity (show negative voltage). These
batteries should be taken out for revival action immediately. Any
delay will reduce the possibility of revival.
Following remedial actions are recommended for revival of cells /
batteries suffering from reverse polarity:
z Drain out the electrolyte from the cell/battery.
z Rinse the cell/battery with distilled water for 3 to 5 times and
shall be dried.
z Fill the cell with distilled water and allow the cells / batteries to
be under rest for 2 to 4 hours.
z Follow the procedure detailed in the above section / Section
14.2.
z Consult HBL for clarifications & guidance.
33
Hydrometer
Reading
1.25
1.25
1.25
Correction
Factor
-0.007
0.0
+0.007
Corrected
Sp.Gr
1.243
1.250
1.257
Desired Specific
gravity at 27C
1.280
1.270
1.260
1.255
1.250
1.240
1.230
1.224
1.220
1.200
1.180
Electrolyte Preparation:
Battery Grade sulphuric acid is usually available in 1.800 or 1.400
Sp.gr. concentration. To change the sp.gr. to another value , it is
necessary to mix it slowly with distilled water, to obtain the desired
specific gravity.
Caution:
1. Store sulphuric acid only in plastic or lead containers.
2. Add acid slowly to DI water while mixing, especially when using
high gravity acid. Never add water to acid.
3. Always wear goggles, rubber gloves and apron while handling
acid. Be extremely not to spill or splash acid.
34
Branch
Address
Tel. No.
Fax No.
Remarks
Banglore
080-41130303
080-41130306
Service
Bhopal
09329787676
Service
Chennai
044-42970300
(10 Lines),
32969870
044-4290333
Service
9444985576
Service
0484-2334007,
9388694890
Service
4 Coimbatore
Cochin
Delhi-1
Gujarat
Hubli
Hyderabad
10
Jaipur
11
Kolkatta
12
Lucknow
13
Madurai
14
Mumbai
15
Punjab
16
Pune
011-22161210,
011-42141129
22160062
982451488
Service
9900138296
Service
Service
0141-3223455,
09314884881
Service
Service
Service
Service
Service
Service
Service
Service