How to Calculate the Suitable Capacitor Size in Farads & kVAR for Power factor Improvement (Easiest
way ever)
Hi there! With a very important tutorial.. I hope you will find it very useful because I have already spent two days
to prepare this article. I think all of those who have sent messages and mails about the topic will never ask again if
they follow these simple methods to calculate the proper Size of Capacitor bank in kVAR and micro-farads for
power factor correction and improvement in both single phase and three phase circuits. I think its too much..
Now lets begin
Consider the following Examples.
Example: 1
A 3 Phase, 5 kW Induction Motor has a P.F (Power factor) of 0.75 lagging. What size of Capacitor in kVAR is
required to improve the P.F (Power Factor) to 0.90?
Solution #1 (By Simple Table Method)
Motor Input = 5kW
From Table, Multiplier to improve PF from 0.75 to 0.90 is .398
Required Capacitor kVAR to improve P.F from 0.75 to 0.90
Required Capacitor kVAR = kW x Table 1 Multiplier of 0.75 and 0.90
= 5kW x .398
= 1.99 kVAR
And Rating of Capacitors connected in each Phase
1.99/3 = 0.663 kVAR
Solution # 2 (Classical Calculation Method)
Motor input = P = 5 kW
Original P.F = Cos1 = 0.75
Final P.F = Cos2 = 0.90
1 = Cos -1 = (0.75) = 41.41; Tan 1 = Tan (41.41) = 0.8819
2 = Cos -1 = (0.90) = 25.84; Tan 2 = Tan (25.50) = 0.4843
Required Capacitor kVAR to improve P.F from 0.75 to 0.90
Required Capacitor kVAR = P (Tan 1 - Tan 2)
= 5kW (0.8819 0.4843)
= 1.99 kVAR
And Rating of Capacitors connected in each Phase
1.99/3 = 0.663 kVAR
Subscribe
230
To RSS Feed
Followers
301,146
Fans
Subscribers
Advertisement
Popular
Recent
Comments
Tags
Tables
The following tables have been prepared to simplify kVAR calculation for power factor improvement. The size of
capacitor in kVAR is the kW multiplied by factor in table to improve from existing power factor to proposed power
factor. Check the others Examples below.
Table from 0.01 to 0.09 (Click image to enlarge)
11/22/2012
04/20/2013
Find us on Facebook
Explanation: There is a problem with the page you are trying to rea
and it cannot be displayed.
Refresh page: Search for the page again by clicking the Refr
button. The timeout may have occurred due to Internet
congestion.
Check spelling: Check that you typed the Web page addres
correctly. The address may have been mistyped.
Access from a link: If there is a link to the page you are loo
for, try accessing the page from that link.
Categories
Select Category
Example 2:
An Alternator is supplying a load of 650 kW at a P.F (Power factor) of 0.65. What size of Capacitor in kVAR
is required to raise the P.F (Power Factor) to unity (1)? And how many more kW can the alternator supply
for the same kVA loading when P.F improved.
Solution #1 (By Simple Table Method)
Supplying kW = 650 kW
From Table 1, Multiplier to improve PF from 0.65 to unity (1) is 1.169
Required Capacitor kVAR to improve P.F from 0.65 to unity (1)
Required Capacitor kVAR = kW x Table 1 Multiplier of 65 and 100
= 650kW x 1.169
= 759.85 kVAR
We know that P.F = Cos = kW/kVA . . .or
kVA = kW / Cos
= 650/0.65 = 1000 kVA
When Power Factor is raised to unity (1)
No of kW = kVA x Cos
= 1000 x 1 = 1000kW
Hence increased Power supplied by Alternator
1000kW 650kW = 350kW
Solution # 2 (Classical Calculation Method)
Supplying kW = 650 kW
Original P.F = Cos1 = 0.65
Final P.F = Cos2 = 1
How to Calculate the Required Capacitor bank value in both kVAR and Farads?
(How to Convert Farads into kVAR and Vice Versa)
Example: 3
A Single phase 400V, 50Hz, motor takes a supply current of 50A at a P.F (Power factor) of 0.6. The motor
power factor has to be improved to 0.9 by connecting a capacitor in parallel with it. Calculate the required
capacity of Capacitor in both kVAR and Farads.
Solution.:
(1) To find the required capacity of Capacitance in kVAR to improve P.F from 0.6 to
0.9 (Two Methods)
Solution #1 (By Simple Table Method)
Motor Input = P = V x I x Cos
= 400V x 50A x 0.6
= 12kW
From Table, Multiplier to improve PF from 0.60 to 0.90 is 0.849
Required Capacitor kVAR to improve P.F from 0.60 to 0.90
Required Capacitor kVAR = kW x Table Multiplier of 0.60 and 0.90
= 12kW x 0.849
= 10.188 kVAR
Solution # 2 (Classical Calculation Method)
Motor Input = P = V x I x Cos
= 400V x 50A x 0.6
= 12kW
Actual P.F = Cos1 = 0..6
Required P.F = Cos2 = 0.90
1 = Cos -1 = (0.60) = 53.13; Tan 1 = Tan (53.13) = 1.3333
2 = Cos -1 = (0.90) = 25.84; Tan 2 = Tan (25.50) = 0.4843
Required Capacitor kVAR to improve P.F from 0.60 to 0.90
Required Capacitor kVAR = P (Tan 1 - Tan 2)
= 5kW (1.3333 0.4843)
= 10.188 kVAR
(2) To find the required capacity of Capacitance in Faradsto improve P.F from 0.6 to
0.9 (Two Methods)
Solution #1 (Using a Simple Formula)
We have already calculated the required Capacity of Capacitor in kVAR, so we can easily convert it into Farads by
using this simple formula
Required Capacity of Capacitor in Farads/Microfarads
C = kVAR / (2 f V2 ) in microfarad
Putting the Values in the above formula
= (10.188kVAR) / (2 x x 50 x 4002)
= 2.0268 x 10-4
= 202.7 x 10-6
= 202.7F
Solution # 2 (Simple Calculation Method)
kVAR = 10.188 (i)
We know that;
IC = V/ XC
Whereas XC = 1 / 2 F C
IC = V / (1 / 2 F C)
IC = V 2 F C
= (400) x 2 x (50) x C
IC = 125663.7 x C
And,
kVAR = (V x IC) / 1000 [kVAR =( V x I)/ 1000 ]
= 400 x 125663.7 x C
IC = 50265.48 x C (ii)
Equating Equation (i) & (ii), we get,
50265.48 x C = 10.188C
C = 10.188 / 50265.48
C = 2.0268 x 10-4
C = 202.7 x 10-6
C = 202.7F
Example 4
What value of Capacitance must be connected in parallel with a load drawing 1kW at 70% lagging power
factor from a 208V, 60Hz Source in order to raise the overall power factor to 91%.
Solution:
You can use either Table method or Simple Calculation method to find the required value of Capacitance in Farads
or kVAR to improve Power factor from 0.71 to 0.97. So I used table method in this case.
P = 1000W
Actual Power factor = Cos1 = 0.71
Desired Power factor = Cos2 = 0.97
From Table, Multiplier to improve PF from 0.71 to 0.97 is 0.783
Required Capacitor kVAR to improve P.F from 0.71 to 0.97
Required Capacitor kVAR = kW x Table Multiplier of 0.71 and 0.97
= 1kW x 0.783
=783 VAR (required Capacitance Value in kVAR)
Current in the Capacitor =
IC = Q C / V
= 783 / 208
= 3.76A
And
XC = V / IC
= 208 / 3.76 = 55.25
C = 1/ (2 f XC)
C = 1 (2 x 60 x 55.25)
C = 48 F (required Capacitance Value in Farads)
Good to Know:
Important formulas which is used for Power factor improvement calculation as well
as used in the above calculation
Power in Watts
kW = kVA x Cos
kW = HP x 0.746 or (HP x 0.746) / Efficiency (HP = Motor Power)
kW = ( kVA2- kVAR2)
kW = P = VI Cos (Single Phase)
kW = P =3x V x I Cos (Three Phase)
Apparent Power in VA
kVA= (kW2+ kVAR2)
kVA = kW/ Cos
Reactive Power in VA
kVAR= (kVA2- kW2)
kVAR = C x (2 f V2)
193
11
Tw eet Electrical
0
Share !EE Library
Wiring 11
7456
Share
3
EE Popular
Basic Concepts
StumbleUpon
E-Machines
Power System
Google+
Previous:
Next:
Comparison between
Star and Delta
Analyzing Circuits
Controlling
More
Loads
Connections
Current Values
09/24/2014
09/06/2014
09/05/2014
09/03/2014
08/21/2014
09/04/2014
8 comments
Anonymous
11/05/2013 at 11:22 am
But luckily with online resources, UV nail dryers can be sourced rather quickly and so <br />can the CND
polish. Keep in mind that the use of ear candles starts back <br />to the very early days of the Chinese.
After she vents a little more,<br />ask another question like, 'Is there anything else about your current
vendor that you'd like to improve'.<br /><br /><br />Also visit my web
Reply
Siva Shankar
11/21/2013 at 5:54 pm
sir u have biven best examples<br /> and i have one dought how we r going to get 1.169 value<br /> From
Table 1, Multiplier to improve PF from 0.65 to unity (1) is 1.169
Reply
Electrical Technology
11/22/2013 at 8:11 am
Check in the table the existing PF is 0.65 and required one is unity (i.e, 1)<br />so the
connecting point number between these two numbers (i.e, 0.65 and 1) is 1.169. this is multilier
<br />or<br />you can find it easily by scientific calculator as;<br />1 = Cos-1 = (0.65) = 49.45;
Tan 1 = Tan (41.24) = 1.169<br />2 = Cos-1 = (1) = 0; Tan 2 = Tan (0) = 0<br />(Check solution
number
Reply
Electrical Technology
11/22/2013 at 8:15 am
Required Capacitor kVAR = P (Tan 1 Tan 2)
Reply
abba sarkinfawa
12/31/2013 at 8:05 pm
pls i need a simple circuit to try and see @fb.com/sarkinfawa
Reply
Anonymous
02/09/2014 at 10:40 pm
Terrific article. I was examining frequently this weblog and I am <br />amazed! Exceptionally useful details
specially the last section <br />I treatment for these types of data significantly.<br /><br />I was seeking
this specific information for a pretty very <br />long time. Thank you and good luck.<br /><br />Also visit
my web-site: AskNow Psychics Review (<a href="http://www.youtube.com/
Reply
Anonymous
02/14/2014 at 12:46 pm
Nice Article.<br /><br />Can you also teach us on how to size up the capacitors in capacitor start
capacitor run motor?<br /><br />Thanks..
Reply
Er Parveer Singh
06/02/2014 at 12:07 pm
I am Mechanical Engineer But i love to do Electrical Job to, Love this Page
Reply
Leave a Reply
Your email address will not be published. Required fields are marked *
Name *
Email *
Post Comment
Notify me of follow-up comments by email.
Notify me of new posts by email.
Recent Posts
Recent Comments
Follow us on Google+
Electrical Techn
09/24/2014
Follow
09/05/2014
+ 1,600
09/06/2014
+1
09/04/2014
09/03/2014