Professional Documents
Culture Documents
Assistant Professor, Department of Mechanical Engineering, SHIATS-DU, Allahabad, Uttar Pradesh, India
Assistant Professor, Department of Mechanical Engineering, ACET, Aligarh, Uttar Pradesh, Uttar Pradesh, India
ABSTRACT
Vapor Absorption refrigeration systems are those systems which produce cooling effect by using solar heat
energy, and have no moving parts. The stages of design are presented including the design of the evaporator, absorber,
Solution heat exchanger, generator and condenser and solar collector. Double-pass Horizontal-tube heat exchangers have
been used for the condenser and for the evaporator. For generator, absorber, solution heat exchanger vertical tube heat
exchanger is used. The solution heat exchanger is designed as a single -pass vertical tube heat exchanger. The generator is
designed using vertical tube heat double-pass heat exchanger. The absorber is designed using as Double-pass vertical tube
heat exchanger. The condenser handles pure water vapor and adequate equations exist for the determination of the U-value.
This work is done on the basis of ASHRAE charts, steam table and many research papers which are related to this work.
Copper tubes with 8X2 matrix are used.
www.tjprc.org
editor@tjprc.org
28
buildings, in a wide range of weather conditions. These include night cooling with ventilation, evaporative cooling,
desiccant cooling, slab cooling and absorption cooling. Solar cooling is very attractive topic for researches of the solar
thermal system field. The reason is that the cooling load usually reaches its peak value when solar energy is mostly
available. Most of the research works in this field are carried out employing either a vapor compression cooling cycle or an
absorption cooling cycle. The absorption cooling cycle is usually a preferable alternative since it use thermal energy
collected from the sun without the need to convert this energy into mechanical energy as required by the vapor
compression cycle. In addition the absorption cycle use thermal energy at a lower temperature than that dictated by the
vapor compression cycle. Most of the absorption cooling cycles use either Li-Br-H2O or NH3-H2O solutions. In solar
applications the Li-Br-H2O is superior to the NH3-H2O system due to following reasons:
Generally, Li-Br-H2O absorption units require generator inlet temperatures of 70-88C, while H2O-NH3
absorption units require temperatures of 90-180C; which results in the H2O-NH3 cooling systems achieving a
lower COP when using flat plate collectors.
A more complex system requiring a rectifier to separate ammonia and water vapor at the generator outlet.
NH3-H2O system is restricted in building applications because of the hazards associated with the use NH3 whereas
29
generator to the absorber passes through a heat exchanger in order to preheat the weak solution entering the generator.
In the absorber, the strong solution absorbs water vapor leaving evaporator. The mixing process of the absorbent and
refrigerant vapor generates latent heat of condensation and this heat rejected to cooling water system. An auxiliary energy
source is provided, so that the hot water is supplied to the generator, when solar energy is not sufficient to heat the water to
the required temperature needed by the generator. Solar heated water can be provided at 85-90C and is used to supply heat
to the generator where the water vapor released from the saturated solution of Li-Br-H2O. Since the storage tank heat
source strongly relies on weather and solar radiation data, which are time dependent. It is necessary to evaluate the
absorption cycle performance with variable generator and condenser temperature.
Generator and condenser as well as evaporator and absorber are under same pressure.
Refrigerant vapor leaving the generator has the equilibrium temperatures of the weak solution at generator
pressure.
Pump is isentropic.
www.tjprc.org
editor@tjprc.org
30
which is being fed to generator supplied by solar collector .this temperature is used to heat the weak
to 90
)
)
(3.2)
From above equation and (3.39) and (3.38)
Where
31
(3.3)
(3.4)
From Duffci and Beckman
(3.5)
Collector
efficiency
(3.6)
Coefficient of Performance
Efficiency of an absorption refrigeration system can be easily expressed by a Coefficient of Performance (COP)
which is defined as the ratio between the amount of heat absorbed from the environment by the evaporator and the heat
supplied to the generator to operate the cycle and pump work.
(3.7)
As the work supplied to the absorption system is very small compared to the amount of heat supplied to the
generator, generally the amount of work is often excluded from the calculation.
(3.8)
www.tjprc.org
editor@tjprc.org
32
the
COP.
33
Effect of Generator Temperature on COP and Heat Input for Different Absorber Temperature
Figure 4 plots graph between COP and generator temperature (Tgen). Both the graphs have been plotted for
different absorber temperature (Tabs) at keeping condenser temperature as (Tcond=30C) and evaporator temperature as
(Tevap=10C) fix. The different absorber temperatures taken are 25C, 30C and 35C.It is clear from Figure that for
Tgen<65C, COP shares inverse relation with Tabs. This is primarily due to the fact that an appreciable increase in heat input
(Qgen) is observed.
CONCLUSIONS
In this study modeling and design has been carried out for 10.5 kW of solar assisted vapor absorption air
conditioning system using Lithium Bromide-Water as refrigerant. Also parametric study has been carried out to study the
effect of condenser temperature, generator temperature, evaporator temperature, absorber temperature on co-efficient of
performance (COP) and effect of generator temperature on specific solution circulation rates (f).
Based upon the study following conclusions have been drawn:
A model has been developed which can predict the COP of the system. Each component of the absorption system
i.e. generator, condenser, evaporator and absorber has been designed.
www.tjprc.org
editor@tjprc.org
34
Higher evaporator and generator temperature, results in higher coefficient of performance (COP) of the system
due to the fact that as generator temperature increases, the heat transfer to the solution in the generator increases,
result in the increase of mass flow rate and so does the COP.
Low condensing temperature results in higher COP due to the fact that as Tcond increases, the condensing
temperature increases and hence causes less heat transfer in the condenser, which results in an increase in
temperature and enthalpy of the refrigerant at the condenser outlet. Hence, the cooling capacity decreases as does
the COP.
For generator temperature from 65C to 80C, the absorption system work efficiently.
REFERENCES
1.
2.
3.
Mittal V, Kasana K.S. and Thakur N. S. Modeling and simulation of a solar absorption cooling system for
India, Journal of Energy in Southern Africa, 2006; 17: 65-70.
4.
5.
Kalogirou S, Florides G, Tassou S. and Wrobel L, Design and construction of a lithium bromide water
absorption refrigerator, CLIMA2000/Napoli world congress; 2001.
6.
7.
Horuz I. A comparison between ammonia-water and water-lithium bromide solution in vapor refrigeration
systems, Int. Comm. Heat mass transfer, 1998; 25: 711-721.
8.
Sun D. W. Thermodynamic design data and optimum design maps for absorption refrigeration system, Applied
Thermal Engineering, 1996; 17:211-221.
9.
Hammad M. A. and Audi M. S. Performance of a solar Li-Br-H2O water absorption refrigeration system,
Renewable energy, 1992; 2:275-282.