FTIM Installation guide

Fast Trip Input Module (FTIM)


for ADVC Controller Range

Scope of this document


This document describes the installation procedures for the FTIM
with ADVC Controller.
Limitations
This document is copyright and is provided solely for the use of the
purchaser. It is not to be copied in any way, nor its contents
divulged to any third party, nor to be used as the basis of a tender
or specification without the express written permission of the
manufacturer.
Disclaimer
The advisory procedures and information contained within this
document have been compiled as a guide to the safe and effective
operation of products supplied by Schneider Electric Recloser
Solutions.
It has been prepared in conjunction with references from subassembly suppliers and the collective experience of the
manufacturer.
In-service conditions for use of the products may vary between
customers and end-users. Consequently, this document is offered
as a guide only. It should be used in conjunction with the customers
own safety procedures, maintenance program, engineering
judgment and training qualifications.
No responsibility, either direct or consequential, for injury or
equipment failure can be accepted by the manufacturer resulting
from the use of this document.
Copyright
2009 by Schneider Electric.
All rights reserved. No part of the contents of this document may be
reproduced or transmitted in any form or by any means without the
written permission of the manufacturer.
Document part number
ADVC2-1185

Schneider Electric (Australia) Pty Limited


80 Schneider Road,
Eagle Farm,
Qld 4009
AUSTRALIA
Tel: +61 7 3635 7500
Fax: +61 7 3635 7560

1 Introduction
The FTIM (Fast Trip Input Module) is an ADVC Controller Range accessory that accepts external control signals
from third party devices. It provides optically isolated inputs. These allow connection of an external protection relay
or Remote Terminal Unit (RTU). The electronic circuit is installed in a die cast, sealed enclosure which is attached
to the upper accessory mounting tray of an ADVC ULTRA controller.
It is possible to interface external trip, close or block signals to the recloser controller via the FTIM.
FTIM enclosure
Terminals
Output

Isolated 12 Vdc power supply terminals


Isolated power source to
Negative
external switches.
Positive

+
Inputs

Optically isolated inputs

1 Fast Trip

Input to trip the recloser

2 Fast Close

Input to close the recloser

3 Trip Block

Input to block all trip and


close commands.

4 Close Block

Input to block all close


commands.

Controller connection

1.1

Compatibility

The FTIM is compatible with the ADVC Controller range. If a controller will be used with an FTIM, a connection
cable for the module has to be included during manufacturing. It is therefore necessary to specify the intended use
of an FTIM when ordering the controller. Note this connection cable cannot be retrofitted in the field.
An FTIM can be used with controllers displaying one of the following part numbers on the rating plate:
Part number
88xxxx2xxx
88xxxx3xxx
88xxxx5xxx

st

1
8
8
8

nd

2
8
8
8

rd

3
x
x
x

th

4
x
x
x

th

5
x
x
x

th

6
x
x
x

th

7
2
3
5

th

8
x
x
x

th

9
x
x
x

th

10
x
x
x

The part number has to start with 88 and the 7th digit must be a 2, 3 or 5.

1.2

Parts supplied with the FTIM

The following parts are supplied with each FTIM.


1 x FTIM module
4 x M5 stainless steel screws
4 x flat washers and 4 x spring washers
1 x EMC cable gland

Note:
The EMC gland and shielded
cable are essential for
reliable operation.

2 Specifications
Isolated power supply output:
Optically isolated inputs:
Dimensions [mm]:
Controller connection:

12 15 Vdc , 100 mA max.


ON = 12 150 Vdc, 12 150 Vac.
OFF = 0 3 Vdc, 0 3 Vac.
188 high, 119.5 wide, 37 deep.
Shielded cable with shielded 15 pin D-type connector.

FTIM Installation Guide (ADVC2-1185)

Page 2

Schneider Electric

3 FTIM installation
The FTIM must be fitted to the upper accessory mounting tray.

3.1

Removing and installing the mounting tray

Brackets
Hinges

Upper accessory tray removal

3.2

It is very easy to remove the upper accessory mounting tray:


1. Undo and remove the self locking nuts and washers;
2. Rotate the accessory tray to the slide-out position by lifting
the bottom of the tray away from the cubicle; and
3. Slide the tray to your left.
To install the upper tray, locate the accessory tray hinges to the left
of the brackets in the top corner of the cubicle. Use the corner as a
guide and slide the tray to your right. The self-locating hinges will
guide the tray into the brackets. Continue to slide the tray until the
hinges are completely inside the brackets. Rotate the tray into the
lock-down position and fasten the nuts.

Attaching the FTIM

Method:
1. Remove the Upper Accessory Mounting Tray
from the ADVC ULTRA cubicle (see 3.1);
2. Two mounting options are provided on the tray
(Left and Right). Select a convenient option;
3. Align the FTIM to the 4 holes as indicated.
Using the screws and washers provided,
attach the FTIM to the tray. Tighten the screws
to 4Nm of torque; and
4. Fit the tray and FTIM in the Upper Accessory
Mounting Space using the existing mounting
points (see 3.1).

Mounting
option Right
Mounting
option Left

Mounting holes

3.3

Connect the FTIM to the controller

Turn all power to the controller OFF.


(See adjacent PSU photo).
Warning:
Failure to power OFF the
controller when connecting the
FTIM to CAPE may cause
unwanted trip/close operation.

Connect the shielded 15 pin D connector to the FTIM.


Fasten the connector properly to ensure a reliable
connection.

Turn all power to the controller ON when the


installation is complete.

FTIM Installation Guide (ADVC2-1185)

Page 3

Schneider Electric

4 Electrical connections
4.1 Using the built-in isolated supply
The FTIM has a built-in isolated power supply that can
be used as field excitation voltage. The following
connection diagram describes using this DC voltage as
a source to supply the external switches.

4.2

Warning:
Field excitation MUST NOT be
provided from the battery nor
the radio power supply.

Warning:
The field excitation power
supply must be isolated from
earth.

+
FTIM

Fast
Trip

Fast
Close

Fast
Close

Trip
Block

Field excitation voltage


12 150 Vac/dc
FTIM

Fast
Trip

Using an external source

It is also possible to use a custom AC or DC source for


field excitation of the external switches. This supply
must be isolated from earth.
Field excitation voltage: 12 Vac/dc up to 150 Vac/dc.

Trip
Block

Close
Block

Close
Block

External

SW
4

4.3

SW
3

SW
2

External

SW
1

Shielded cable

For the external connections, shielded cable with the


following main characteristics is recommended:
Operating Temperature: -55C to +105C
Voltage Rating:
600 V
Product Description:
Conductor:
Stranded Tinned Copper
Number of Cores: 10
Area Conductor:
0.22 mm
External Diameter: 7.2 mm
Insulation:
Colour-Coded PVC
Shield:
Braided Tinned Copper
(90% Coverage)
Jacket:
PVC

Picture of the shielded cable (not supplied)

FTIM Installation Guide (ADVC2-1185)

SW
4

4.4

SW
3

SW
2

SW
1

Cable Gland Specification

An M20 EMC cable gland with the following main


characteristics is required:
Diameter, cable max:
12 mm
Diameter, cable min:
6 mm
Diameter, cable screen min: 5 mm
Material:
Brass
Plating:
Nickel
Thread size:
M20
Length, thread:
8 mm
IP Rating:
IP68

Picture of the EMC cable gland (supplied)

Page 4

Schneider Electric

4.5 Customer Cable Installation


4.5.1 EMC gland installation
Note:
Correct installation of the
EMC gland is essential
for reliable operation.

Clamping ring

Gland body

Sleeve

O ring

Seal

Braid connection
Earth braid

Cable sheath

Method

Illustrations
120 cm

1.

At 120 cm from the cable-end that will be connected to the


FTIM, remove 2 cm of the plastic sheath to expose the
earth braid.
2 cm

Push the end of the cable that will be connected to the


FTIM through the cable gland in the direction as shown.
2.

Note:
Pushing the cable in the
opposite direction will
damage the gland.

FTIM Installation Guide (ADVC2-1185)

Page 5

Schneider Electric

Method
Continue pushing the cable through the gland, until the
earth braid aligns with the gland.

Illustrations
2 cm

3.

4.

Ensure the earth braid is in contact with the braid


connection ring in the gland.

5.

Ensure the seal and clamping mechanism is overlapping


with the plastic sheath. Tighten the gland sleeve to firmly
grip the cable in place.

Select a 20mm hole in the base of the controller. The two


holes on the right hand side are provided for this purpose.

6.

FTIM and IOEX


cable holes

Remove the plug and fit the cable with gland.

4.5.2 Cable termination


1. Use cable ties to secure the cable to the cubicle
wall.
2. Cut the cable to the appropriate length, and
terminate the cable at the FTIM connectors.

FTIM Installation Guide (ADVC2-1185)

Note:
Shielded cable is
essential for reliable
operation. See 4.3.

Page 6