1 Introduction
The FTIM (Fast Trip Input Module) is an ADVC Controller Range accessory that accepts external control signals
from third party devices. It provides optically isolated inputs. These allow connection of an external protection relay
or Remote Terminal Unit (RTU). The electronic circuit is installed in a die cast, sealed enclosure which is attached
to the upper accessory mounting tray of an ADVC ULTRA controller.
It is possible to interface external trip, close or block signals to the recloser controller via the FTIM.
FTIM enclosure
Terminals
Output
+
Inputs
1 Fast Trip
2 Fast Close
3 Trip Block
4 Close Block
Controller connection
1.1
Compatibility
The FTIM is compatible with the ADVC Controller range. If a controller will be used with an FTIM, a connection
cable for the module has to be included during manufacturing. It is therefore necessary to specify the intended use
of an FTIM when ordering the controller. Note this connection cable cannot be retrofitted in the field.
An FTIM can be used with controllers displaying one of the following part numbers on the rating plate:
Part number
88xxxx2xxx
88xxxx3xxx
88xxxx5xxx
st
1
8
8
8
nd
2
8
8
8
rd
3
x
x
x
th
4
x
x
x
th
5
x
x
x
th
6
x
x
x
th
7
2
3
5
th
8
x
x
x
th
9
x
x
x
th
10
x
x
x
The part number has to start with 88 and the 7th digit must be a 2, 3 or 5.
1.2
Note:
The EMC gland and shielded
cable are essential for
reliable operation.
2 Specifications
Isolated power supply output:
Optically isolated inputs:
Dimensions [mm]:
Controller connection:
Page 2
Schneider Electric
3 FTIM installation
The FTIM must be fitted to the upper accessory mounting tray.
3.1
Brackets
Hinges
3.2
Method:
1. Remove the Upper Accessory Mounting Tray
from the ADVC ULTRA cubicle (see 3.1);
2. Two mounting options are provided on the tray
(Left and Right). Select a convenient option;
3. Align the FTIM to the 4 holes as indicated.
Using the screws and washers provided,
attach the FTIM to the tray. Tighten the screws
to 4Nm of torque; and
4. Fit the tray and FTIM in the Upper Accessory
Mounting Space using the existing mounting
points (see 3.1).
Mounting
option Right
Mounting
option Left
Mounting holes
3.3
Page 3
Schneider Electric
4 Electrical connections
4.1 Using the built-in isolated supply
The FTIM has a built-in isolated power supply that can
be used as field excitation voltage. The following
connection diagram describes using this DC voltage as
a source to supply the external switches.
4.2
Warning:
Field excitation MUST NOT be
provided from the battery nor
the radio power supply.
Warning:
The field excitation power
supply must be isolated from
earth.
+
FTIM
Fast
Trip
Fast
Close
Fast
Close
Trip
Block
Fast
Trip
Trip
Block
Close
Block
Close
Block
External
SW
4
4.3
SW
3
SW
2
External
SW
1
Shielded cable
SW
4
4.4
SW
3
SW
2
SW
1
Page 4
Schneider Electric
Clamping ring
Gland body
Sleeve
O ring
Seal
Braid connection
Earth braid
Cable sheath
Method
Illustrations
120 cm
1.
Note:
Pushing the cable in the
opposite direction will
damage the gland.
Page 5
Schneider Electric
Method
Continue pushing the cable through the gland, until the
earth braid aligns with the gland.
Illustrations
2 cm
3.
4.
5.
6.
Note:
Shielded cable is
essential for reliable
operation. See 4.3.
Page 6
Schneider Electric