Professional Documents
Culture Documents
EES
The 1,000 ppm guideline value for CO2 used in the 1989 standard was based on an
assumed ventilation air (outdoor air) rate of 15 CFM/person and an outdoor baseline
CO2 concentration of 300 ppm. (Note that the 1999 standard set a differential CO2 level
of 700 ppm along with minimum ventilation rates for given spaces rather than an
absolute value like 1,000 ppm. This change to the standard occurred because
background CO2 levels are closer to 400 ppm than 300 ppm resulting in an indoor level
of 1,100 ppm CO2 using the same 15 CFM/person as was used in the 1989 standard.
Thus the current standard would have a baseline above 1,000 ppm CO2. Moreover, as
will be discussed, this absolute value led to confusion in the design, and health and
safety communities.)
Specific language contained in the 1989 standard are reproduced below:
Section 6.1.3:
Section 6.2.1:
Table 3:
Contaminant
Concentration
Carbon Dioxide
a
1.8 g/m3
ppm
Exposure Time
Comments
1000a
Continuous
See App. D
This level is not considered a health risk but is a surrogate for human comfort (odor).
See Section 6.1.3 and Appendix D.
This last statement clearly defines the role of CO2 in the standard.
ASHRAE also produced a document entitled Interpretations for ASHRAE Standard 621989 Ventilation for Acceptable Indoor Air Quality that provided specific interpretations
of this standard. Two questions, and their responses, (see Attachment B) are directly
relevant to this current topic and confirm the last statement just discussed.
Q:
EES
June 26, 1995 The carbon dioxide level of 1000 ppm noted in 6.1.3 and 6.2
including Table 3 appears to be provided as a recommended guideline rather
than a mandatory requirement. Can the carbon dioxide level in a space ever
exceed the referenced value of 1000 ppm, and still remain in compliance with the
standard?
A:
Yes. The CO2 level of 1000 is a guideline for comfort acceptability, not a ceiling
value for air quality.
A similar series of questions on the topic were responded to on January 29, 1995:
Ms. Paolini, Manager of Health and Safety notes that.It is unclear what is meant by
the clause, ventilation rate is set so the 1000 ppm CO2 is not exceeded.
Q1:
Is the 1000 ppm CO2 a ceiling value or a time weighted average value?
A1:
The reference to 1000 ppm CO2 in Section 6.1.3 is only as a point of information.
This is not a requirement of ASHRAE 62-1989. Since it is not a requirement it is
neither a ceiling nor a time weighted average value. Rather, it can be considered
a target concentration level. Since comfort (odor) criteria are likely to be satisfied
when the CO2 does not exceed 1000 ppm the converse is also likely to be true,
i.e., when the CO2 level exceeds 1000 ppm, the comfort (odor) criteria may not
be satisfied.
Q2:
If it is a time weighted average value, how are the CO2 test results to be
calculated and weighted?
A2:
Q3:
Would CO2 levels measured only during room occupancy be used or CO2 levels
measured throughout the time period of ventilation system operation?
A3:
CO2 levels should be measured during the time of occupancy. This is defined for
the classroom as the time between initial occupancy in the morning and
dismissal time for the students.
Again, these questions and answers suggest that the CO2 level of 1,000 ppm is a
guideline (surrogate for odors), not a standard.
One should note that the 1999 Standard has removed all mention of the 1,000 ppm
value from the Standard.
EES
The current ASHRAE Standard Ventilation for Acceptable Indoor Air Quality
(ANSI/ASHRAE 62-1999) does not reference the term 1,000 ppm CO2.
The former ASHRAE Standard Ventilation for Acceptable Indoor Air Quality
(ANSI/ASHRAE 62-1989) references the term 1,000 ppm CO2 as a surrogate for
where human bioeffluents (odors) may be at levels not acceptable for human
comfort. Further, this value of 1,000 is a guideline value only and not considered
a regulated standard.
Interpretation document questions and answers confirm this concept of the CO2
concentration of 1,000 ppm as a guideline level to be used as a surrogate for
odor causing compounds from human activity that may not be acceptable for
human comfort.
If you have any questions or comments regarding this document, please contact the
author at:
Energy & Environmental Solutions, Inc.
84 N. High Street, Suite 2B
Dublin, OH 43017
www.eesinc.cc
EES
ATTACHMENT A
Demand Control Ventilation Using CO2
EES
A-1
ATTACHMENT B
Portions of ASHRAE Standard 62-1989 Interpretation
Document
EES
B-1