Product Data
AIR HANDLER TECHNOLOGY
AT ITS FINEST
A10083
The FB4C fan coil has the proven technology of Bryant fan coil
units with Puron refrigerant as well as vertical and horizontal
applications. The design features contoured condensate pans with
rugged drain connections, ensuring that little water is left in the
unit at the end of the cooling duty cycle. The lack of standing
condensate and corrosion free pans improves IAQ and product life,
features homeowners appreciate.
Standard features include grooved tubing and louvered fins. Coil
circuiting has also been updated to make the most of all Bryant
heat pumps and air conditioners. Units come with solid state fan
controls, 1--inch (25mm) thick insulation with R--value of 4.2,
multi--speed motors, and fully--wettable coils. Units can
accommodate factory-- and/or field--installed heaters from 3 to 30
kW.
It also should be noted that the unique cabinet design of these fan
coils meet stringent regulations for cabinet air leakage -- a
requirement of 2% cabinet leakage rate when tested at 1.0 inches of
static pressure.
The FB4C fan coil design is loaded with popular features. These
fan coils utilize the latest in electronic commutation motor (ECM)
technology through the use of high efficiency, multi--tap ECM
motors allowing reliable air delivery with increased static pressure.
It comes in a pre--painted (taupe metallic) galvanized steel casing
and a factory--supplied power plug for ease of installation. The
FB4C unit is shipped with a factory--installed Teflon--ring piston
FB4CNF(018--048) or a Puron refrigerant TXV FB4CNF060,
FB4CNP(018--060).
STANDARD FEATURES
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
ADDITIONAL FEATURES
S
2
B
3
4
4
C
5
N
6
F
7
0
8
1
9
8
10
0
Product
F = Fan Coil
11
0
12
0
Heating Size
00 = No Heat
05 = 5 kW
75 = 7.5 kW
08 = 8 kW
10 = 10 kW
11 = 11 kW
15 = 15 kW
Type
B = Base, Puron
Position
4 = Multipoise
Coil Type
0 = Copper
T = Tin ---plate
L = Aluminum
Series
C
Electrical
N = 208/230v, 1 ph, 60 Hz
Capacity
018 = 18,000
024 = 24,000
030 = 30,000
036 = 36,000
042 = 42,000
048 = 48,000
060 = 60,000
Cabinet Style
F = Single Piece with piston (TXV on FB4CNF060)
P = TXV
DIMENSIONS
A12512
DIMENSIONS (cont.)
A14026
DIMENSIONS (cont.)
A12509
DIMENSIONS (cont.)
A12513
DIMENSIONS (cont.)
A14027
DIMENSIONS (cont.)
A12511
PHYSICAL DATA
ORDERING NO.
NOMINAL COOLING
CAPACITY (Btuh)
FB4CN(F,P)018(0,T,L)
DIMENSIONS
Height
Width
Depth
SHIPPING
WEIGHT
18,000
112 lb
51 kg
FB4CN(F,P)024(0,T,L)
24,000
112 lb
51 kg
FB4CN(F,P)030(0,T,L)
30,000
122 lb
55 kg
FB4CN(F,P)036(0,T,L)
36,000
122 lb
55 kg
FB4CN(F,P)042(0,T,L)
42,000
157 lb
71 kg
FB4CN(F,P)048(0,T,L)
48,000
157 lb
71 kg
FB4CN(F,P)060(0,T,L)
60,000
175 lb
79 kg
SPECIFICATIONS
FB4C
18
24
30
36
42
48
60
EVAPORATOR COIL
Face Area (sq. ft)
2.23
2.97
Configuration
FB4CNF
Metering Device
(Teflon--- ring piston)
Puron Refrigerant
FB4CNP
Metering Device
Puron Refrigerant
4.45
Slope
EA52PT052
EA52PT057
TXV
TXV
5.93
A
EA52PT067
EA52PT070
TXV
TXV
EA52PT076
TXV
EA52PT080
TXV
(Copper and
Tin models
only)
TXV
TXV
(Aluminum
models
only)
FILTER*
21--- 1/2--- in
(546 mm) X
13--- in
(330 mm)
16--- 3/8--- in
(417 mm)
19--- 7/8--- in
(505 mm)
BLOWER ASSEMBLY
Motor Type (ECM)
Motor HP
1/3
1/3
1/3
1/2
1/2
3/4
3/4
CFM
600
800
1000
1200
1400
1600
1750
10
PERFORMANCE DATA
FB4C AIRFLOW PERFORMANCE (CFM)
MODEL & SIZE
FB4C 018
FB4C 024
FB4C 030
FB4C 036
FB4C 042
FB4C 048
FB4C 060
BLOWER SPEED
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
0.10
767
614
701
614
614
969
826
826
701
617
1108
1026
1026
909
825
1301
1227
1227
1087
1026
1560
1419
1419
1249
1242
1743
1669
1669
1452
1300
1897
1817
1817
1657
1443
0.20
739
569
660
569
569
936
795
795
660
592
1090
1000
1000
873
795
1276
1191
1191
1062
1000
1544
1397
1397
1220
1205
1712
1634
1634
1413
1256
1867
1785
1785
1621
1412
0.30
702
534
616
534
534
892
766
766
616
552
1065
969
969
842
757
1245
1169
1169
1030
969
1507
1358
1358
1184
1158
1679
1599
1599
1377
1221
1836
1757
1757
1589
1377
0.40
669
486
581
486
486
835
743
743
581
507
1034
938
938
799
722
1218
1143
1143
1001
938
1464
1320
1320
1142
1110
1642
1564
1564
1339
1182
1808
1724
1724
1557
1332
0.50
620
436
537
436
436
763
706
706
537
472
1009
899
899
762
674
1176
1105
1105
966
899
1424
1279
1279
1093
1069
1610
1531
1531
1308
1142
1774
1693
1693
1518
1286
0.60
565
398
499
398
398
676
660
660
499
420
974
865
865
724
634
1121
1074
1074
930
865
1358
1239
1239
1052
1026
1574
1499
1499
1271
1101
1736
1655
1655
1474
1243
11
FB4C
018
FB4C
024
FB4C
030
FB4C
036
FB4C
042
FB4C
048
FB4C
060
INDOOR COIL
AIR
CFM
EWB
72 / 22
67 / 19
525
62 / 17
72 / 22
67 / 19
600
62 / 17
72 / 22
67 / 19
675
62 / 17
72 / 22
67 / 19
700
62 / 17
72 / 22
67 / 19
800
62 / 17
72 / 22
67 / 19
900
62 / 17
72 / 22
67 / 19
875
62 / 17
72 / 22
67 / 19
1000
62 / 17
72 / 22
67 / 19
1125
62 / 17
72 / 22
67 / 19
1050
62 / 17
72 / 22
67 / 19
1200
62 / 17
72 / 22
67 / 19
1350
62 / 17
72 / 22
67 / 19
1225
62 / 17
72 / 22
67 / 19
1400
62 / 17
72 / 22
67 / 19
1575
62 / 17
72 / 22
67 / 19
1400
62 / 17
72 / 22
67 / 19
1600
62 / 17
72 / 22
67 / 19
1800
62 / 17
72 / 22
67 / 19
1600
62 / 17
72 / 22
67 / 19
1750
62 / 17
72 / 22
67 / 19
2000
62 / 17
TC
41
33
26
45
37
29
49
40
32
43
35
28
47
38
30
51
41
33
62
51
40
68
56
44
74
60
48
68
56
44
75
61
49
81
66
53
89
73
58
98
80
64
106
87
69
88
72
57
97
79
63
105
86
68
106
86
68
113
92
73
124
101
80
35 / 2
SHC
20
20
20
22
22
22
24
24
25
22
23
23
24
25
26
26
27
28
31
32
32
34
35
36
37
38
39
34
36
36
38
39
40
41
43
44
44
45
46
49
50
51
53
55
56
46
48
49
51
52
54
55
57
59
54
56
56
58
59
61
64
66
67
BF
0.00
0.03
0.03
0.00
0.04
0.04
0.00
0.05
0.05
0.00
0.05
0.06
0.00
0.06
0.07
0.00
0.07
0.08
0.00
0.04
0.05
0.00
0.06
0.06
0.00
0.07
0.07
0.00
0.06
0.07
0.00
0.07
0.08
0.00
0.08
0.09
0.00
0.04
0.04
0.00
0.05
0.06
0.00
0.06
0.07
0.00
0.05
0.06
0.00
0.06
0.07
0.00
0.07
0.08
0.00
0.04
0.04
0.00
0.04
0.05
0.00
0.06
0.06
12
TC
21
13
11
23
15
13
25
16
14
22
14
12
24
15
13
26
17
15
32
21
18
35
22
20
38
24
21
35
22
20
38
25
22
41
27
24
46
29
25
50
32
28
54
35
31
45
29
25
49
32
28
54
34
30
54
35
29
58
37
32
63
41
35
55 / 13
SHC
11
11
11
12
12
13
13
14
14
12
13
12
14
14
13
15
16
15
17
18
18
19
20
20
21
22
21
20
20
20
22
22
22
23
25
24
25
25
25
28
28
28
30
31
31
26
27
25
29
30
28
31
33
30
31
31
29
33
33
32
36
37
35
BF
0.03
0.04
0.26
0.04
0.05
0.28
0.05
0.06
0.29
0.05
0.06
0.29
0.06
0.08
0.31
0.07
0.09
0.33
0.04
0.05
0.28
0.06
0.07
0.30
0.07
0.08
0.32
0.06
0.07
0.31
0.07
0.09
0.33
0.09
0.10
0.35
0.04
0.05
0.28
0.05
0.06
0.29
0.06
0.07
0.31
0.05
0.06
0.29
0.06
0.08
0.31
0.07
0.09
0.33
0.04
0.05
0.28
0.04
0.05
0.28
0.06
0.07
0.30
NOTES:
BYPASS
FACTOR
79
78
77
76
75
Under 75
81
82
83
84
85
Over 85
25
25
24
24
Under 75
27
28
28
29
29
Over 85
Use
formula
shown
below
Correction Factor
0.10
.098
1.96
2.94
3.92
4.91
0.20
0.87
1.74
2.62
3.49
4.36
0.30
0.76
1.53
2.29
3.05
3.82
Interpolation is permissible.
Correction Factor = 1.09 x (1 --- BF) x (db --- 80)
FB4C AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT
INDICATED AIRFLOW (DRY TO WET COIL)
UNIT SIZE
018
024
030
036
042
048
060
500
0.034
0.034
--- ----- ----- ----- ----- ---
600
700
0.049 0.063
0.049 0.063
--- ----- ----- ----- ----- ----- ----- ----- ----- ----- ---
800
--- --0.076
0.049
--- ----- ----- ----- ---
900 1000
--- ----- --0.089 --- --0.059 0.070
--- --0.070
--- ----- ----- ----- ----- ----- ---
CFM
1100 1200 1300
--- ----- ----- ----- ----- ----- --0.080 --- ----- --0.080 0.090 0.099
--- --0.049 0.056
--- ----- ----- ----- ----- ----- ---
1400 1500
--- ----- ----- ----- ----- ----- ----- ----- --0.063 0.070
0.063 0.070
--- ----- ---
1600
--- ----- ----- ----- ----- --0.076
0.049
1700 1800
--- ----- ----- ----- ----- ----- ----- ----- ----- ----- --0.083 0.090
0.054 0.059
1900
--- ----- ----- ----- ----- ----- --0.065
2000
--- ----- ----- ----- ----- ----- --0.070
FB4C
042 --- 060
HEATER
ELEMENTS
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
HEATER
ELEMENTS
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
0
1
2
3
4
0
3, 5
8, 10
9, 15
20
+.02
+.01
0
.02
.04
0
2
3
4
6
0
8, 10
9, 15
20
18, 24, 30
+.04
+.02
0
.02
.10
The airflow performance data was developed using fan coils with 10--- kW electric heaters (2 elements) in the 018 through 036 size units and
15--- kW heaters (3 elements) in the 042 through 060 size units. For fan coils with heaters of a different number of elements, the external available static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as indicated above.
HEATER kW
3
10
15
18
20
24
30
018
525
525
525
600
024
700
700
700
700
775
030
875
875
875
875
1060
036
1050
970
970
970
920
1040
042
1225
1225
1225
1225
1225
1225
048
1400
1400
1400
1400
1400
1400
1400
1400
060
1750
1750
1750
1750
1750
1750
1750
1750
Speed Tap 4 (white wire) is used for electric heat only. White wire must remain on tap 4.
13
400
0.02
600
0.044
0.022
800
0.075
0.048
1000
0.072
0.051
CFM
1200
0.100
0.070
1400
0.092
1600
0.120
0.086
1800
0.152
0.105
2000
0.130
kW @
240V
VOLTS/
PH
STAGES (kW
OPERATING)
INTERNAL
CIRCUIT
PROTECTION
HEATING CAP.**
@ 230V
KFCEH0401N03
KFCEH0501N05
KFCEH0801N08
KFCEH0901N10
KFCEH3201F20
KFCEH1601315
KFCEH2001318
KFCEH3401F24
KFCEH3501F30
KFCEH2401C05
KFCEH2501C08
KFCEH2601C10
KFCEH3301C20
KFCEH2901N09
KFCEH3001F15
KFCEH3101C15
3
5
8
10
20
15
18
24
30
5
8
10
20
9
15
15
230/1
230/1
230/1
230/1
230/1
230/3
230/3
230/3*
230/3*
230/1
230/1
230/1
230/1
230/1{
230/1
230/1
3
5
8
10
5, 20
5, 15
6, 12, 18
8, 16, 24
10, 20, 30
5
8
10
5, 20
3, 9
5, 15
5, 15
None
None
None
None
Fuse}
None
None
Fuse
Fuse
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
None
Fuse}
Circuit Breaker
018024
018060
018060
018060
030060
036060
042060
048, 060
048, 060
018060
018060
018060
030060
036060
024060
024060
9,400
15,700
25,100
31,400
62,800
47,100
56,500
78,300
94,100
15,700
25,100
31,400
62,800
28,200
47,100
47,100
CONDITIONS
Ext Static
CFM
Pressure
600
0.25
800
0.25
1000
0.25
1200
0.25
1400
0.25
1600
0.25
2000
0.25
125
250
500
1000
2000
4000
64.7
66.0
67.0
67.8
68.4
69.0
70.0
60.7
62.0
63.0
63.8
64.4
65.0
66.0
56.7
58.0
59.0
59.8
60.4
61.0
62.0
53.7
55.0
56.0
56.8
57.4
58.0
59.0
51.7
53.0
54.0
54.8
55.4
56.0
57.0
49.7
51.0
52.0
52.8
53.4
54.0
55.0
45.7
47.0
48.0
48.8
49.4
50.0
51.0
*Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, Chapter 52, p.
52.7.
14
HEAT PACK
INSTALLED
HEATER
AMPS
MCA
DUAL CIRCUIT
MOCP
HTR.
AMPS
MCA
MOCP
HTR.
AMPS
MCA
MOCP
L1/L2
L1/L2
L1/L2
L3/L4
L3/L4
L3/L4
018(0,T,L)05
1/3
2.8
30/30
N/A
N/A
N/A
N/A
N/A
N/A
018(0,T,L)08
1/3
2.8
40/45
N/A
N/A
N/A
N/A
N/A
N/A
024(0,T,L)05
1/3
4.1
30/30
N/A
N/A
N/A
N/A
N/A
N/A
024(T,L)10
1/3
4.1
60/60
N/A
N/A
N/A
N/A
N/A
N/A
030(0,T,L)08
1/3
2.8
40/45
N/A
N/A
N/A
N/A
N/A
N/A
030(0,T,L)10
1/3
2.8
50/60
N/A
N/A
N/A
N/A
N/A
N/A
036(T,L)10
1/2
4.1
60/60
N/A
N/A
N/A
N/A
N/A
N/A
042(T,L)10
1/2
4.1
60/60
N/A
N/A
N/A
N/A
N/A
042(T,L)15
1/2
4.1
80/80
048(T,L)10
3/4
6.0
60/60
048(T,L)15
3/4
6.0
80/90
36.2/40.0 50.4/55.2
N/A
N/A
50/60
N/A
36.2/40.0 52.8/57.5
60/60
18.1/20.0 22.6/25.0
N/A
N/A
18.1/20.0 22.6/25.0
N/A
25/25
N/A
25/25
MTR
HP
MTR
FLA
VOLTS/PH/HZ
FB4CN(F,P)018(0,T,L)00
1/3
2.8
FB4CN(F,P)024(0,T,L)00
1/3
4.1
FB4CN(F,P)030(0,T,L)00
1/3
FB4CN(F,P)036(0,T,L)00
FB4CN(F,P)042(0,T,L)00
BRANCH CIRCUIT
MIN WIRE SIZE*
AWG
MCA
MAXIMUM
OVERCURRENT
PROTECTION
208/230/1/60
3.5
15
14
208/230/1/60
5.1
15
14
2.8
208/230/1/60
3.5
15
14
1/2
4.1
208/230/1/60
5.1
15
14
1/2
4.1
208/230/1/60
5.1
15
14
FB4CN(F,P)048(0,T,L)00
3/4
6.0
208/230/1/60
7.5
15
14
FB4CN(F,P)060(0,T,L)00
3/4
6.0
208/230/1/60
7.5
15
14
*Use copper wire only. Use 75_C only in this application. When using non ---metallic (NM) sheathed cable, wire size required should be based on that of 60_C
conductors, instead of wire sizes shown in table above per NEC Article 336 ---26.
NOTE: If branch circuit wire length exceeds 100 ft (30 m), consult NEC 215 ---2 to determine maximum wire length. Use 2% voltage drop.
FLA --- Full Load Amps
15
16
18.0
18.0
22.5
22.5
10
10
15
15
15
18
20
20
24
24
30
30
KFCEH2401C051
KFCEH2401C052
KFCEH0801N08
KFCEH2501C08
KFCEH2901N09
KFCEH2901N09**
KFCEH0901N10
KFCEH2601C10
KFCEH3001F15
KFCEH3101C15
KFCEH1601315
KFCEH2001318
KFCEH3201F20
KFCEH3301C20
15.0
13.5
11.3
11.3
11.3
7.5
7.5
6.8
6.8
6.0
6.0
3.8
3.8
3.8
Fuse
Fuse
Fuse
Fuse
Ckt Bkr
Fuse
None
None
Ckt Bkr
Fuse
Ckt Bkr
None
None
None
Ckt Bkr
None
Ckt Bkr
Ckt Bkr
None
None
None
INTERNAL
CIRCUIT
PROTECTION
109.0/120.0
62.6/69.2
86.7/95.5
50.1/55.4
72.3/79.9
37.6/41.5
31.3/34.6
54.2/59.9
36.2/40.0
36.2/40.0
18.8/20.8
32.8/36.0
28.9/32.0
28.9/32.0
18.1/20.0
18.1/20.0
18.1/20.0
18.1/20.0
10.9/12.0
Single
Circuit
36.2/40.0
36.2/40.0
36.2/40.0
36.2/40.0
L1,l2
36.2/40.0
36.2/40.0
18.1/20.0
18.1/20.0
L3,L4
Dual Circuit
HEATER AMPS
208/230V
144.8/158.5
86.8/95.0
116.9/127.9
71.2/77.8
98.9/108.4
55.5/60.4
47.7/51.8
76.3/83.4
53.8/58.5
53.8/58.5
32.0/34.5
49.5/53.5
44.7/48.5
44.7/48.5
31.2/33.5
26.0/28.4
31.2/33.5
26.0/28.4
15.9/17.3
Single
Circuit
53.8/58.5
53.8/58.5
53.8/58.5
53.8/58.5
L1,L2
30
KFCEH3501F30
kW
22.5
18.0
208V
P
H
A
S
E
L1,L2
36.2/40.0
28.9/32.0
36.2/40.0
28.9/32.0
L3,L4
HEATER AMPS
208/230V
L5,L6
36.2/40.0
28.9/32.0
L1,L2
53.8/58.5
44.7/48.5
45.3/50.0
36.2/40.0
L3,L4
MIN AMPACITY
208/230V*
L5,L6
45.3/50.0
36.2/40.0
0/00
3/3
1/1
4/4
3/2
6/6
8/6
4/4
6/6
6/6
8/8
8/6
8/8
8/8
8/8
8/8
8/8
10/10
10/10
6/6
8/8
8/8
8/8
L3,L4
8/8
8/8
L5,L6
6/6
8/8
6/6
8/8
8/6
10/8
10/10
8/8
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
12/12
Single
Circuit
10/10
10/10
MIN GND
WIRE SIZE
208/230V
10/10
10/10
10/10
10/10
L1, L2
60/60
60/60
60/60
60/60
60/60
45/50
50/50
40/40
L3,L4
50/50
40/40
L5,L6
50/50
50/50
25/25
25/25
L3,L4
Dual Circuit
L1,L2
150/175
90/100
125/150
80/80
100/110
60/70
50/60
80/90
60/60
60/60
35/35
50/60
45/50
45/50
35/35
30/30
35/35
30/30
20/20
Single
Circuit
L1,L2
10/10
10/10
10/10
10/10
L3,L4
Dual Circuit
BRANCH CIRCUIT
6/6
6/6
6/6
6/6
L3, L4
Dual Circuit
L1, L2
L1,L2
10/10
8/8
10/10
12/12
Single
Circuit
78/80
78/80
78/80
78/80
78/80
59/60
L1,L2
59/59
73/73
L3,L4
59/59
73/73
L5,L6
59/59
59/59
75/76
75/76
L3,L4
Dual Circuit
L1,L2
117/150
97/98
115/116
94/95
85/109
76/77
56/90
88/89
78/80
78/80
83/85
54/87
59/60
59/60
85/88
66/66
85/88
66/66
67/68
Single
Circuit
*Includes blower motor amps of largest fan coil used with heater.
{Copper wire must be used. If other than uncoated (non ---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code
(ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
**Field convertible to 3 phase.
{{Field convertible to 1 phase, single or multiple supply circuit.
NOTES:
1. For fan coil sizes 018 ---036.
2. For fan coil sizes 042 ---060.
3. Single circuit application of F15 and F20 heaters requires single ---point wiring kit accessory.
24
240V
KFCEH3401F24
HEATER PART
NO.
45.3/50.0
45.3/50.0
22.7/25.0
22.7/25.0
L3,L4
Dual Circuit
Min Ampacity
208/230V*
KFCEH3501F30
KFCEH3401F24
15.0
KFCEH0501N052
3.8
KFCEH0501N051
2.3
208v
240v
kW
KFCEH0401N03
HEATER
PART NO.
P
H
A
S
E
PHASE
FUSE
QTY/SIZE
CKT BKR*
QTY/SIZE
1/60
1/60
1/3
10
1/60
15
2/302/60
2/60
15
18
20
4/60
2/60
24
1/3
6/60
30
1/3
6/60
When using units with 20--, 24--, and 30--kW electric heaters, maintain a 1--in. (25mm) clearance from combustible materials to discharge
plenum and ductwork and maintain a distance of 36--in. (914mm) from the unit. Use an accessory downflow base to maintain proper
clearance on downflow installations. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric
heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing
through unconditioned space must be insulated and covered with vapor barrier
ACCESSORIES
ITEM
1.
2.
Disconnect Kit
Downflow Base Kit
KFADK0201DSC
KFACB0101CFB
018, 024
KFACB0201CFB
030, 036
KFACB0301CFB
KFADC0201SLP
KFADC0401ACL
KFAHD0101SLP
All
5.
KFAHC0125AAA
All
6.
KFASP0101SPK
KFAFK0112SML
018, 024
KFAFK0212MED
030, 036
3.
4.
7.
8.
9.
10.
11.
12.
13.
KFAFK0312LRG
FNCCABCC0014
(FILXXFNC0014)
018, 024
FNCCABCC0017
(FILXXFNC0017)
030, 036
FNCCABCC0021
(FILXXFNC0021)
KFAET0150ETK
All
KEAVC0201240
All
KFAFR0101FRM
KFAFR0201FRM
KFAFR0301FRM
KFAFR0401FRM
KSATX0201PUR
018, 024
030, 036
042, 048, 060
NA
018, 024, 030
KSATX0301PUR
036, 042
KSATX0401PUR
048
KSATX0601HSO
KSATX0701HSO
048
KSATX1001HSO
060
17
ACCESSORIES (cont.)
Accessory Kits Description Suggested and Required Use
1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: Units for 3-- through 10--kW electric resistance heaters and cooling controls.
2. Downflow Base Kit
This kit is designed to provide a 1--in. (25mm) minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap--free seal with the floor.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
3. Downflow Conversion Kit
Fan coils are shipped from the factory for upflow or horizontal--left applications. Downflow conversion kits provide proper condensate
water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A--coils.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
4. Downflow/Horizontal Conversion Gasket Kit
This kit provides the proper gasketing of units when applied in either a downflow or horizontal application.
REQUIRED USE: Fan coils in either downflow or horizontal applications.
5. Horizontal Applications -- Water Management Kit
This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity.
SUGGESTED USE: All fan coils.
6. Single Point Wiring Kit
The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run
two heavy--gauge, high--voltage wires into the fan coil rather than 4 light--gauge, high--voltage wires.
SUGGESTED USE: Fan coils with 15-- and 20--kW fused heaters only.
7. Filter Kit (12 pack)
The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and
prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the
efficiency of the system.
SUGGESTED USE: To replace filters in fan coils.
REQUIRED USE: All units unless a filter grille is used.
8. Fan Coil Filter Cabinet
This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are
insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using
FILXXFNC00(14, 17, 21, 24) media filter cartridges. These fan coil media filter cartridge kits are designed for the removal of particles
from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream.
SUGGESTED USE: All fan coils.
9. Condensate Drain Trap Kit
This kit consists of 50 PVC condensate traps. Each trap is pre--formed and ready for field installation. This deep trap helps the system
make and hold proper condensate flow even during blower initiation.
SUGGESTED USE: All fan coils.
10. Air Cleaner 240--volt Conversion Kit
The AIRA electronic air cleaner comes ready for 115--v operation.
REQUIRED USE: This kit is required when running 240--volt circuit to air cleaner.
11. Standard Filter Rack Kit
This kit mounts in fan coil filter rack area and modifies the existing filter rack to support standard 1--in. filter sizes.
SUGGESTED USE: Fan coils using standard filter sizes.
E2014 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
18